ATTACHMENT 1F - Drawings-Plumbing.pdf

PDF 3 MB Posted

Attached to
Project# 501-21-101: Repair Sterile Processing Service (SPS) & Upgrade Equipment Area
Solicitation number
36C26224B0007
Issued by

About this file

This document package includes construction drawings and specifications for repair and upgrade work at a Department of Veterans Affairs medical facility. The project scope involves rehabilitating sewer piping, upgrading domestic water and medical gas systems, and installing temporary trailer facilities in the Sterile Processing Service department located in Building 41 at the Raymond G. Murphy VA Medical Center in Albuquerque, New Mexico. Drawings show demolition, new construction and renovation details. Specifications reference requirements for trenchless sewer repair methods, piping materials, medical equipment, and infection control protections. The pre-solicitation notice invites bids due in early 2023 for general contractor and associated trade services to complete this project.

View the file

Other files

File Type Posted
C01 Award Notice of 36C26224C0167.pdf PDF
S06 36C26224B0007 0006.pdf PDF
S06 ATTACHMENT 4 - REVISED WAGE DETERMINATION NM20240044 01-06-2024.pdf PDF
S06 36C26224B0007 0005.pdf PDF
AMENDMENT 0004 - ATTACHMENT A - GEOTECHNICAL REPORT.pdf PDF
AMENDMENT 0004 - ATTACHMENT C - ASBESTOS SURVEY REPORT.pdf PDF
AMENDMENT 0004 - ATTACHMENT B - SECTION 26 12 19.pdf PDF
AMENDMENT 0004 - ATTACHMENT 4 - REVISED WAGE DETERMINATION NM20240001.pdf PDF
S06 36C26224B0007 0004.pdf PDF
S06 36C26224B0007 0003.pdf PDF
S06 36C26224B0007 0002 01-30-2024.pdf PDF
S06 36C26224B0007 0001 01162024.pdf PDF
ATTACHMENT 4 - WAGE DETERMINATION NM20230044 06-09-2023.pdf PDF
ATTACHMENT 1D - Drawings-Architectural.pdf PDF
ATTACHMENT 1H - Drawings-Electrical.pdf PDF
ATTACHMENT 1A - Drawings-General.pdf PDF
ATTACHMENT 1E - Drawings-Fire Protection.pdf PDF
ATTACHMENT 1C- Drawings-Structural.pdf PDF
ATTACHMENT 1B - Drawings-Civil.pdf PDF
ATTACHMENT 2 - 501-21-101 Bid Spec Complete-Updated.pdf PDF
ATTACHMENT 1G - Drawings-Mechanical.pdf PDF
ATTACHMENT 3 - RFI FORM 501-21-101.docx DOCX document
ATTACHMENT 1I - Drawings-Telecommunications.pdf PDF
S02 36C26224B0007.docx DOCX document
S02. 36C26224B0007 Pre-Solicitation Notice.docx DOCX document
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MA

MV

CO

VEAI

FOV

FOR

FOS

LPG

NPW

NO

O

N

G

MPG

SA

CD

ACD

VAV

AW

ST

OST

GW

SS

SCW

140°ORAL EVACUATION

LABORATORY VACUUM

LABORATORY AIR

INDUSTRIAL AIR

LA

LV

OA

IA

FILTERED COLD WATERFCW

FUEL OIL DISCHARGEFOD

SQUARE FLOOR DRAIN (FD)

ROOF DRAIN (RD), SIZE & TYPESQUARE FLOOR SINK (FS)

CONDENSATE DRAIN

NATURAL GAS

NITROUS OXIDE

LIQUIFIED PETROLEUM GAS

SHOP AIR

NITROGEN

MEDICAL AIR

OXYGEN

DOMESTIC HOT WATER RECIRC.

STORM DRAIN

ACID WASTE

DOMESTIC COLD WATER

DOMESTIC HOT WATER

140° DOMESTIC HOT WATER (140°)

SANITARY SEWER

GREASE WASTE

SOFTENED COLD WATER (SCW)

ACID VENT VENT

WALL CLEANOUT (WCO)

FLOOR CLEANOUT (FCO)

OVERFLOW STORM DRAIN

NON POTABLE WATER (NPW)

FUEL OIL SUPPLY

FUEL OIL RETURN

FUEL OIL VENT

AUXILIARY CONDENSATE DRAIN

CARBON DIOXIDE

MEDICAL VACUUM

MEDICAL VACUUM EXHAUSTMEDICAL AIR INTAKE

MEDIUM PRESSURE NATURAL GAS

END OF LINE CLEANOUT

PLUMBING EQUIPMENT DESIGNATIONXX-1

A. ALL PIPING SHALL BE COORDINATED WITH CIVIL UTILITY PIPING, FIRE PROTECTION,

DUCTWORK, MECHANICAL PIPING, LIGHTING, STRUCTURAL AND ARCHITECTURAL SYSTEMS.

B. PIPE CLEANOUTS SHALL BE LINE SIZE (6" MAX.). LOCATE 100' APART MAXIMUM FOR SIZES UP

THROUGH 6".

C. PLUMBING VENTS THROUGH ROOF (VTR) SHALL BE 3" MINIMUM. SMALLER VTR'S INDICATED

SHALL INCREASE TO 3" PIPE, 12" BELOW ROOF.

D. ACCESS PANELS SHALL BE PROVIDED FOR ALL WATER HAMMER ARRESTORS LOCATED IN

WALLS TO ACCESS EQUIPMENT. PANEL SHALL BE AS LARGE AS PRACTICAL FOR THE

FUNCTION THEY ARE INTENDED.

E. DO NOT SCALE DRAWINGS, SEE ARCHITECTURAL FLOOR PLAN FOR DIMENSIONS.

F. ALL PLUMBING WORK SHALL COMPLY WITH THE 2009 INTERNATIONAL PLUMBING CODE.

G. PIPE ROUTING IS SCHEMATIC AS SHOWN AND IS NOT INTENDED TO INDICATE EXACT

ROUTING. CONTRACTOR SHALL PROVIDE ANY ADDITIONAL OFFSET AND FITTINGS REQUIRED

FOR PROPER INSTALLATION AND TO MAINTAIN CLEARANCES.

H. CONCEAL PIPING ABOVE CEILING AND WITHIN WALLS OR CHASES, EXCEPT IN MECHANICAL

SPACES OR WHEN OTHERWISE NOTED.

DHWR

DHW

DCW

ABBREVIATIONS

PLUMBING PIPING TYPES

A/E ARCHITECT / ENGINEER

B

BFP REDUCED PRESSURE BACKFLOW

PREVENTER

BHP BRAKE HORSEPOWER

BT BATHTUB

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

DA

F FAHRENHEIT

FCO FLOOR CLEANOUT

FCW FILTERED COLD WATER

E

ET EXPANSION TANK

FD FLOOR DRAIN

FM FLOW METER

FOP FUEL OIL PUMP

FOV FUEL OIL VENT

G

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GT GREASE TRAP

K

J

J INTENTIONALLY LEFT BLANK

ID INSIDE DIAMETER

H

H&CW HOT & COLD WATER

HB HOSE BIBB

HD HUB DRAIN

HP HORSEPOWER

HWP HOT WATER PUMP

I

L

L/s LITERS PER SECOND (OR LITERS/SECOND)

LA LABORATORY AIR

LBS/HR POUNDS PER HOUR

NTS NOT TO SCALE

N

NC NORMALLY CLOSED

NG NATURAL GAS

M

M METER, SI UNIT

MA MEDICAL AIR

MAV MANUAL AIR VENT

MBH 1000 BTUH

P

PP PLUMBING PUMP

PA PASCAL

PD PRESSURE DROP

PG PRESSURE GAGE

PPM PARTS PER MILLION

PRS PRESSURE REDUCING STATION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH – ABSOLUTE

PSIG POUNDS PER SQUARE INCH – GAGE

PTRV PRESSURE TEMPERATURE RELIEF VALVE

O

O OXYGEN

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

Q

Q INTENTIONALLY LEFT BLANK

TCV TEMPERATURE CONTROL VALVE

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TSTAT THERMOSTAT

TWR TEMPERED WATER RETURN

SAN SANITARY SEWER

SCFM STANDARD CUBIC FEET PER MINUTE

SQ FT SQUARE FOOT (FEET)

SS STAINLESS STEEL

ST STORAGE TANK

R

RD ROOF DRAIN

RO REVERSE OSMOSIS

T

X INTENTIONALLY LEFT BLANK

W

W WASTE

WC WATER CLOSET

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

V VENT

VP VACUUM PUMP

VSD VARIABLE SPEED DRIVE

X

V

DEMOLITION GENERAL NOTES:

PL-100

DETAIL NUMBER

SHEET NUMBER

SHEET NUMBER

SECTION NUMBER

1 OWNER FURNISHED, CONTRACTOR

INSTALLED EQUIPMENT DESIGNATION

EXISTING TO BE DEMOLISHED

EXISTING TO REMAIN

NEW PIPE

CONNECT NEW TO EXISTING

LIMIT OF DEMOLITION

GENERAL PIPING SYMBOLS

GENERAL ANNOTATIONS

AV

STRAINER

FLOAT & THERMOSTATIC

STEAM TRAP

INVERTED BUCKET

STEAM TRAP

FLANGE CONNECTION PIPE DROP

PIPE RISER

TEE DOWN

TEE UP UNION

PRESSURE REDUCING

VALVE

BALL VALVE

ANGLE GLOBE VALVE SAFETY RELIEF VALVE

GLOBE VALVE

MANUAL OR

AUTOMATIC AIR VENT

PRESSURE AND

TEMPERATURE TEST PLUG

FLOW METER

PLUMBING PIPING SYMBOLS

CAP

REDUCER (ECCENTRIC)

Name

XX-XX

ANCHOR

TEE

DIRECTION OF FLOW

S

DIRECTION OF PIPE

PITCH (DOWN)

FM

MV

PLUMBING VALVE SYMBOLS

ROOM TAG

PUMP

REDUCER (CONCENTRIC)

BUTTERFLY VALVE

CHECK VALVE

THERMOMETER

PRESSURE GAUGE

YCO YARD CLEANOUT

Y

Z INTENTIONALLY LEFT BLANK

Z

AD AREA DRAIN

AFF ABOVE FINISHED FLOOR

AG AIR GAP

AFG ABOVE FINISHED GRADE

AP ACCESS PANEL

AS AUTOMATIC SPRINKLER

ASD ADJUSTABLE SPEED DRIVES

ASD AUTOMATIC SPRINKLER DRAIN

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

ASHRAE AMERICAN SOCIETY OF HEATING,

REFRIGERATION, AIR CONDITIONING

ENGINEERS

ASPE AMERICAN SOCIETY OF PLUMBING

ENGINEERS

ASR AUTOMATIC SPRINKLER RISER

AV ACID VENT

AW ACID WASTE

BSP BLACK STEEL PIPE

C

C CENTIGRADE (CELSIUS)

CFM CUBIC FEET PER MINUTE

CV CONTROL VALVE

CO CLEANOUT

CA COMPRESSED AIR

CGA COMPRESSED GAS ASSOCIATION

CI CAST IRON

CS CLINICAL SINK

DCW DOMESTIC COLD WATER

DFU DRAINAGE FIXTURE UNITS

DHW DOMESTIC HOT WATER

DI DEIONIZED WATER

DW DISHWASHER

DHWR DOMESTIC HOT WATER RETURN

DHWS DOMESTIC HOT WATER SUPPLY

DN DOWN

DS DOWNSPOUT

DWG DRAWING

DWH DOMESTIC WATER HEATER

DWR DRINKING WATER RETURN

DWS DRINKING WATER SUPPLY

DWV DRAIN WASTE VENT

EX. EXISTING

EWS/SH EYE WASH/ DRENCH SHOWER

EWS EYE WASH STATION

EWH ELECTRIC WATER HEATER

ETR EXISTING TO REMAIN

ESH EMERGENCY SHOWER

ESC ESCUTCHEON

EPACT ENERGY POLICY ACT

EMCS ENERGY MONOSERRAT AND

CENTRAL SYSTEM

EPA ENVIRONMENTAL PROTECTION AGENCY

EL ELEVATION

F

FDC FIRE DEPARTMENT (HOSE) CONNECTION

FFA FROM FLOOR ABOVE

FFB FROM FLOOR BELOW

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FS FLOOR SINK

FS FLOW SWITCH

FU FIXTURE UNITS

GAL GALLONS

GCO GRADE CLEANOUTS

GPS GAS REGULATOR STATION

GVTR GAS VENT THROUGH ROOF

GWH GAS FIRED UNIT HEATER

HX HEAT EXCHANGER

HS HAND SINK

HST HOT WATER STORAGE TANK (DOMESTIC)

HWB HOT WATER BOILER

HWCP HOT WATER CIRCULATING PUMP

HYD HYDRANT

IE INVERT ELEVATION

ICW INDUSTRIAL COLD WATER

IHW INDUSTRIAL HOT WATER

INV INVERT

IPC INTERNATIONAL PLUMBING CODE

IRW IRRIGATION WATER

IW INDIRECT WASTE

IWH INSTANTANEOUS WATER HEATER

IWR INDUSTRIAL WATER RETURN

IWS INDUSTRIAL WATER SUPPLY

kW KILOWATT kWh KILOWATT HOUR

LAV LAVATORY

LCW LABORATORY COLD WATER

LHW LABORATORY HOT WATER

LV LABORATORY VACUUM

LNG LIQUID NATURAL GAS

LOX LIQUID OXYGEN

LW LOW WATER

MED MEDICAL

MER MECHANICAL EQUIPMENT ROOM

MH MANHOLE

MOU MEMORANDUM OF UNDERSTANDING

MSB MOP SERVICE BASIN

MV MEDICAL VACUUM

N2 NITROGEN

N2O NITROUS OXIDE

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM. NOMINAL

NPW NON POTABLE WATER

OC ON CENTER

OR OPERATING ROOM

OVFL OVERFLOW

PDI PLUMBING AND DRAINAGE INSTITUTE

PO POTABLE WATER

RDL ROOF DRAIN LEADER

RL ROOF LEADER

RP RECIRCULATION PUMP

RWL RAIN WATER LEADER

SMACNA SHEET METAL AND AIR CONDITIONING

CONTRACTORS NATIONAL ASSOCIATION

SCW SOFTENED COLD WATER

SDMH STORM DRAIN MANHOLE

SMH SANITARY MANHOLE

SP SUMP PUMP

SPR SPRINKLER LINE

SW STORM WATER

TD TRENCH DRAIN

TEMP TEMPERATURE

TFA TO FLOOR ABOVE

TFB TO FLOOR BELOW

TMV THERMOSTATIC MIXING VALVE

TP TRAP PRIMER

TWS TEMPERED WATER SUPPLY

TYP TYPICAL

U

U INTENTIONALLY LEFT BLANK

VS VENT STACK

VTR VENT THROUGH ROOF

VAC VACUUM

VB VACUUM BREAKER

VCO VACUUM CLEANER OUTLET

WCO WALL CLEANOUT

WH WALL HYDRANT

WH WATER HEATER

WHA WATER HAMMER ARRESTER

WL WATER LINE

WM WATER METER

WS WASTE STACK

WSFU WATER SUPPLY FIXTURE UNITS

YH YARD HYDRANT

BACKFLOW PREVENTER

NONFREEZE WALL

HYDRANT

PLUMBING CLEANOUT AND DRAIN SYMBOLS

MODULATING CONTROL

VALVE

THERMOSTATIC MIXING

VALVE

M MOTOR OPERATED VALVE

I. SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS.

J. PROVIDE TRAP PROTECTION FOR ALL FLOOR DRAINS.

K. PROVIDE AN AIR GAP, WHEN REQUIRED BY CODE, SERVING INDIVIDUAL FIXTURES, DEVICES, APPLIANCES AND APPARATUS.

L. COORDINATE PIPING WITH ELECTRICAL EQUIPMENT PRIOR TO INSTALLATION. ROUTE PIPING

TO AVOID ELECTRICAL EQUIPMENT AND CLEARANCE AREAS.

M. ANY DEVIATIONS IN ELECTRICAL REQUIREMENTS FROM THE BASIS OF DESIGN FOR THE

PLUMBING EQUIPMENT SHALL BE THE RESPONSIBILITY OF THE PLUMBING CONTRACTOR TO

ENSURE COORDINATION WITH THE ELECTRICAL CONTRACTOR FOR PROPER SIZE

ELECTRICAL MATERIAL AND EQUIPMENT AT NO ADDITIONAL COST.

N. PROVIDE SHOCK ARRESTORS PER STANDARD PDI-WH-201.

O. SEAL ALL FIRE AND SMOKE BARRIER PENETRATIONS IN ACCORDANCE WITH THE APPLICABLE

BUILDING CODE, SPECIFICATIONS, AND DETAILS. REFER TO ARCHITECTURAL DRAWINGS FOR

LOCATIONS AND RATINGS OF FIRE AND SMOKE WALLS, BARRIERS, AND PARTITIONS.

ROUND FLOOR DRAIN (FD)

GENERAL NOTES:

A. VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY GENERAL CONTRACTOR

REGARDING CONFLICTS BEFORE PROCEEDING WITH WORK.

B. VERIFY SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION.

RELOCATE, REMOVE AND ADJUST MECHANICAL AND ELECTRICAL ITEMS AS NECESSARY TO

COORDINATE WITH NEW WORK.

C. AFTER DEMOLITION IS COMPLETE, PATCH AND REPAIR FINISHES TO MATCH EXISTING

CONDITIONS.

D. COORDINATE DEMOLITION WITH GENERAL CONTRACTOR. NOTIFY GENERAL CONTRACTOR

AND OWNER IF A SHUDTOWN OF UTILITIES IS REQUIRED.

E. PROTECT EXISTING UTILITIES TO REMAIN FROM DAMAGE DURING DEMOLITION.

F. TEMPORARILY MOVE OR TAKE EQUIPMENT OUT OF SERVICE AS NECESSARY TO COMPLETE

WORK.

G. SAWCUT CONCRETE FLOOR AS REQUIRED FOR DEMOLITION WORK INDICATED. COORDINATE

WITH NEW PLUMBING BEFORE CUTTING ANY FLOOR. CONTRACTOR TO X-RAY FLOORS FOR

ALL STRUCTURAL FLOORS.

NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.

REAGENT WATERRG

SS LINED SANITARY SEWER PIPE

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR SBBL COLLABORATIVE JN, INC.

100 N. STONE AVE STE 1102

TUCSON, AZ 85701-1524

(520) 620-0255

NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023

NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024

NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023

CIVIL / STRUCTURAL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

HEALTHCARE PLANNER

THE INNOVA GROUP

3196 NORTH SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:2

:4

A

M

PLUMBING LEGEND

GH 45RJS

BID DOCUMENTS

REPAIR SPS SEWER AND

UPGRADE EQUIPMENT AREA

08/11/23

501-21-101

RAYMOND G. MURPHY VAMC

1501 SAN PEDRO DRIVE SE

ALBUQUERQUE, NM 87108

P-000

SPUR #: 1993.10

No. REVISION DESCRIPTION DATE

1 2 3 4 5 6 7

G

H

I

4" SS

4" SS

4" S

S

5" SS4" SS

5" S

S 8"

S S

4" S

S

4" S

S

4" S

S

4" SS

4" S

S

2" S

S

4" SS

5" SS

4" SS

4" S

S

ELECTRICAL CLOSET

BC-110E

MECH

BD-141

VESTIBULE

BC-125

STAIR

N0-3

MECH EQUIP

BC-112

PARTS RM

BC-126A

TECHNICAL WORK

SPACE

BC-126

EQUIP TEST &

STORAGE

BC-115D

STERILIZATION

PREPARATION

BC-111

SOILED RECV &

DECONTAMINATION

BC-110

CORRIDOR

CB-15

BREAK ROOM

BC-103B

HAC

BC-115A

MED SUPPLY TECH

BC-121B

OFFICE

BC-123

RECEPTION

BC-121A

STAFF WORK AREA

BC-115

STAFF WORK AREA

BC-115

TLT

BC-105

TLT

BC-104

LOCKERS

BC-102

CORRIDOR

CB-16

CART WASH

BC-114

SPS CHANGE AREA

BC-103

OFFICE

BC-115ESTERILIZATION

PREPARATION

BC-111

WORK AREA & STOR

BC-115C BREAKDOWN

BC-115B

MED GAS

BC-121

BIOMED WORK SPACE

BC-125D

OFFICE OF CHIEF

BIOMED

BC-125A

RECEPTION AND PGM

ASST

BC-125

CORRIDOR

CB-17

4" SS

6" S

T 6"

S T

6" ST

6" S

T

D4 D4

D5 D5

D5

D6 D6 D6

D7D7

SEWAGE PUMPS

D8

D8 D8

D8

D8

D8

4" SS

2 3 4 5 6 71

D10

D10

2" V

2" V

2" V

3" V

4" V

2" V

4" SS

4" V

4" S

S

P-414

P-414

P-414

EX. FD

EX. CO

EX. FD

EX. CO

EX. FS

EX. FS EX. FS

EX.FS

EX. 4" W

EX. FD

EX. CO

EX. FD

EX. COEX. COEX. CO

EX. 4" W

EX. 2" W

EX 4" CO

EX FD

EX FD

EX FD EX. CO

EX FD

EX.FD

EX. 4" W

D10

D10

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

D10 D10

D10

D10

HLD ALCOVE

BC-110C

HLD ANTEROOM

BC-110A

HLD DECON

BC-110B

VESTIBULE

BC-100

TLT (F)

BC-115G

TLT

BC-102A

LOCKERS

BC-102

STOR

BC-118

D11 D11

D11

D12

P-708

P-708

P-418

P-103

P-103 P-103

P-414P-414

P-103

P-103

D13

D13

D13

D10 D10

D10

SPS DEPARTMENT

BUILDING 41

BASEMENT LEVEL, QUAD C

N

BUILDING 41 - BASEMENT LEVEL KEY PLAN

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR SBBL COLLABORATIVE JN, INC.

100 N. STONE AVE STE 1102

TUCSON, AZ 85701-1524

(520) 620-0255

NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023

NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024

NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023

CIVIL / STRUCTURAL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

HEALTHCARE PLANNER

THE INNOVA GROUP

3196 NORTH SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:2

:4

A

M

PLUMBING BASEMENT - SPS -

WASTE/VENT DEMOLITION PLAN

WRS 46 79RJS

BID DOCUMENTS

REPAIR SPS SEWER AND

UPGRADE EQUIPMENT AREA

08/11/23

501-21-101

RAYMOND G. MURPHY VAMC

1501 SAN PEDRO DRIVE SE

ALBUQUERQUE, NM 87108

PD100

SPUR #: 1993.10

N

1/8" = 1'-0"

PLUMBING BASEMENT - SPS - WASTE/VENT DEMOLITION PLAN1

DEMOLITION KEYNOTES

D4 CUT AND CAP 4" SEWER PIPE BELOW GRADE. ABANDON LINE IN PLACE AND CAP AT THE WYE FITTING.

D5 CUT AND CAP 4" SEWER PIP BELOW GRADE AT THIS LOCATION. ABANDON REMAINING LINE IN PLACE. NEW

CLEANOUT TO BE INSTALLED IN THIS LOCATION.

D6 CAP AND SEAL CLEANOUT BELOW GRADE AT THIS LOCATION.

D7 REMOVE EXISTING SEWAGE PUMPS AFTER LINING IS COMPLETE. SEWAGE PUMPS WILL BE IN USE AS A BY-PASS IN ORDER THAT THE SEWER PIPING TO THE SOUTH (TO THE EXISTING MAIN SEWER LIFT

STATION) CAN BE RELINED. CAP AND SEAL PIPE WHEN FINISHED.

D8 ALL WASTE LINES TO BE SCOPED WITH CAMERA BEFORE ABANDONING PIPE.

D10 SAW CUT FLOOR TO ACCESS PIPE. CONTRACTOR TO VERIFY PIPE LOCATION AND X-RAY FLOOR CUTTING

LOCATIONS BEFORE ANY CUTTING IS DONE. PATCH AND REPAIR FLOOR TO MATCH.

D11 REMOVE PLUMBING FIXTURES AND ALL ASSOCIATED PIPING BACK TO WALL. PIPE TO BE REUSED FOR NEW

FIXTURE.

D12 REMOVE PLUMBING FIXTURES AND ALL ASSOCIATED PIPING. CAP AND SEAL PIPE WASTE PIPE BELOW

FLOOR AND CAP AND SEAL PIPE WATER PIPE ABOVE FLOOR TO ELIMINATE DEAD LEGS.

D13 TO ALLOW ACCESS FOR SEWER LINING EQUIPMENT TO LINE SEWERS GOING SOUTH AND EAST. WHEN SEWER LINING PROCESS IS COMPLETE, BACKFILL AREA, PROVIDE MINIMUM 8", 3000 PSI CONCRETE TO

PATCH EXCAVATED AREA, AND PROVIDE FLOOR FINISH TO MATCH SURROUNDING AREA.

H

I

MECH

BD-141

IRM SIGNAL CLOSET

BC-110D

CLOSET

BC-110C

SOILED RECV &

DECONTAMINATION

BC-110

STOR

BC-127

ELECTRICAL CLOSET

BC-110E

STERILIZATION

PREPARATION

BC-111

VESTIBULE

BC-125

STAIR

N0-3

MECH EQUIP

BC-112

RECEPTION AND PGM

ASST

BC-125

OFFICE OF CHIEF

BIOMED

BC-125A

VESTIBULE

BC-113

EQUIP TEST &

STORAGE

BC-115D

WORK AREA & STOR

BC-115C

BIOMED WORK SPACE

BC-125D

OFFICE

BC-115E

BREAKDOWN

BC-115B

HALL

BC-103A

BREAK ROOM

BC-103B

TLT (F)

BC-115G

TLT

BC-104

TLT

BC-105

STOR

BC-118

STAFF WORK AREA

BC-115

RECEPTION

BC-121A

MED SUPPLY TECH

BC-121B

OFFICE

BC-123

HAC

BC-115A

TECHNICAL WORK

SPACE

BC-126

PARTS RM

BC-126A

MECH RM

BC-126B

CORRIDOR

CB-17

STOR

BC-119

MECH

BC-115F

LOCKERS

BC-102

MED GAS

BC-121

CORRIDOR

CB-15

CART WASH

BC-114

CORRIDOR

CB-16

SPS CHANGE AREA

BC-103

1/

2" D

C W

1/

2" D

H W

1/

2" D

C W

1/

2" D

H W

1/

2" D

C W

2 1/2" DHW

2 1/2" DHW

2 1/2" DCW

2" DCW

1" DHW

2 1/2" DHW

2 1/2" DCW 2 1/2" DCW

2 1/2" DHW

2 1/2" DCW

3/4" DHW

3/4" DCW

3/4" DCW

D2

D1

D1

D1

1" DHW

1" DCW

3/4" DHW 3/4" DCW

1" DHW

1" DCW

2 3 4 5 6 71

1" D

H W

R

1" DHWR

1" D

H W

1" D

H W

R

1" DHW

1" DHWR

3/4" RG

3/4" RG

3/4" SCW

3/4" RG

3/4" SCW

1" RG

NOT IN SCOPE

NOT IN SCOPE

HLD ALCOVE

BC-110C

HLD DECON

BC-110B

HLD ANTEROOM

BC-110A

P-418

P-414

P-414

P-414

P-708

P-708

D11 D11

P-103

P-103 P-103

P-414

P-414

P-103

P-103

D12

D14

SPS DEPARTMENT

BUILDING 41

BASEMENT LEVEL, QUAD C

N

BUILDING 41 - BASEMENT LEVEL KEY PLAN

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR SBBL COLLABORATIVE JN, INC.

100 N. STONE AVE STE 1102

TUCSON, AZ 85701-1524

(520) 620-0255

NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023

NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024

NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023

CIVIL / STRUCTURAL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

HEALTHCARE PLANNER

THE INNOVA GROUP

3196 NORTH SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:2

:4

A

M

PLUMBING BASEMENT - SPS - DOMESTIC

WATER DEMOLITION PLAN

WRS 47 79RJS

BID DOCUMENTS

REPAIR SPS SEWER AND

UPGRADE EQUIPMENT AREA

08/11/23

501-21-101

RAYMOND G. MURPHY VAMC

1501 SAN PEDRO DRIVE SE

ALBUQUERQUE, NM 87108

PD101

SPUR #: 1993.10

N

1/8" = 1'-0"

PLUMBING BASEMENT - SPS - DOMESTIC WATER DEMOLITION PLAN1

DEMOLITION KEYNOTES

D1 EXISTING PIPE SHOWN ON THIS DRAWING IS SHOWN FOR REFERENCE ONLY. PIPE IS LOCATED IN THE INTERSTITIAL SPACE ABOVE.

D2 CAP WATER, STEAM AND AIR LINES FOR EXISTING CART WASHER. PIPE WILL BE REUSED FOR NEW CART WASHER.

D11 REMOVE PLUMBING FIXTURES AND ALL ASSOCIATED PIPING BACK TO WALL. PIPE TO BE REUSED FOR NEW FIXTURE.

D12 REMOVE PLUMBING FIXTURES AND ALL ASSOCIATED PIPING. CAP AND SEAL PIPE WASTE PIPE BELOW FLOOR AND CAP AND SEAL

PIPE WATER PIPE ABOVE FLOOR TO ELIMINATE DEAD LEGS.

D14 REMOVE AIR LINE FROM COLUMN. CAP AND SEAL PIPE ABOVE IN CEILING.

H

I

4" SS 5" SS

4" SS

4" S

S

4" S

S

4" S

S

5" SS

8" S

S 5"

S S

5" SS

4" SS 4" SS

4" S

S

2" S

S

2" SS

8" S

S

4" SS

4" SS4" SS

4" S

S

4" S

S

3" SS

4" S

S

5" S

S

4" S

S

4" S

S

4" SS

2" SS

2" SS

4" S

S

4" SS

2" S

S

2" SS

MECH

BD-141

IRM SIGNAL CLOSET

BC-110D

CLOSET

BC-110C

SOILED RECV &

DECONTAMINATION

BC-110

STOR

BC-127

ELECTRICAL CLOSET

BC-110E

STERILIZATION

PREPARATION

BC-111

VESTIBULE

BC-125

STAIR

N0-3

MECH EQUIP

BC-112

RECEPTION AND PGM

ASST

BC-125

OFFICE OF CHIEF

BIOMED

BC-125A

VESTIBULE

BC-113

EQUIP TEST &

STORAGE

BC-115D

WORK AREA & STOR

BC-115C

BIOMED WORK SPACE

BC-125D

OFFICE

BC-115E

BREAKDOWN

BC-115B

HALL

BC-103A

BREAK ROOM

BC-103B

TLT (F)

BC-115G

TLT

BC-104

TLT

BC-105

STOR

BC-118

STAFF WORK AREA

BC-115

RECEPTION

BC-121A

MED SUPPLY TECH

BC-121B

OFFICE

BC-123

HAC

BC-115A

TECHNICAL WORK

SPACE

BC-126

PARTS RM

BC-126A

MECH RM

BC-126B

CORRIDOR

CB-17

STOR

BC-119

MECH

BC-115F

LOCKERS

BC-102

MED GAS

BC-121

CORRIDOR

CB-15

CART WASH

BC-114

CORRIDOR

CB-16

SPS CHANGE AREA

BC-103

FCO

LINE #19

LINE #18

LINE #17

LINE #11

LINE #12

LINE #14

LINE #15

LINE #13

LINE #16

LINE #20

LINE #21

19 19

EXISTING MANHOLE TO REMAIN

3" SS

4" SS

2" SS

P-418

HAC

BC-110D

2 3 4 5 6 71

EX. FD

EX. CO

EX. FD

EX. CO

EX. FS

EX.FS

EX. 4" W

EX. FD

EX. CO

EX. FD

EX. CO

EX. CO

EX. CO

EX. 4" W

EX. 2" W

EX 4" CO

EX FD

EX FD

EX FD EX. CO

EX FD

EX.FD

EX. 4" W

4" SS

FS-R

2" SS

P-414

P-414

P-414

P-707

FD-C

P-502

3" SS

HLD ALCOVE

BC-110C

HLD ANTEROOM

BC-110A

HLD DECON

BC-110BNOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

4" SS

3" SS

2" SS

6" S

T

6" ST

6" S

T 6"

S T

4" S

S 4"

S S

4" S

S

2" SS

2" SS

EX. CO

12 12

P-708

2" SS

2" V 1 1/2" V

4" SS

FS-R

LINE #18

P-103

P-103P-103

P-103

P-414 P-414

P-103

P-708

2" V

FS-R

FS-R

2" V

2" V

EX. HAND WASH SINK

4" V

FS-R

4" SS

2" V

28 28

SPS DEPARTMENT

BUILDING 41

BASEMENT LEVEL, QUAD C

N

BUILDING 41 - BASEMENT LEVEL KEY PLAN

SEWER LINES WITHIN THIS HATCHING

ARE REPAIRED FROM PREVIOUS JOB.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR SBBL COLLABORATIVE JN, INC.

100 N. STONE AVE STE 1102

TUCSON, AZ 85701-1524

(520) 620-0255

NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023

NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024

NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023

CIVIL / STRUCTURAL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

HEALTHCARE PLANNER

THE INNOVA GROUP

3196 NORTH SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:2

:4

A

M

PLUMBING BASEMENT - SPS -

WASTE/VENT PLAN

WRS 48 79RJS

BID DOCUMENTS

REPAIR SPS SEWER AND

UPGRADE EQUIPMENT AREA

08/11/23

501-21-101

RAYMOND G. MURPHY VAMC

1501 SAN PEDRO DRIVE SE

ALBUQUERQUE, NM 87108

PL100

SPUR #: 1993.10

N

1/8" = 1'-0"

PLUMBING BASEMENT - SPS - WASTE/VENT PLAN1

KEYNOTES

1 UNDERFLOOR SANITARY PIPING SHOWN SHALL BE THERMOFORM-PVC LINING BY TRENCHLESS SEWER REPAIR. CONTRACTOR TO CLEAN AND RUN A HI-DEFINITION 4K CAMERA DOWN THE LINES AFTER REPAIR IS MADE TO ASSURE PROPER FLOW OF REPAIRED PIPE. CONTRACTOR TO PROVIDE HI DEF 4K

VIDEO TO OWNER OF BEFORE AND AFTER PIPE CONDITIONS.

12 EXISTING SANITARY SEWER PIPE BEING ABANDONED IN PLACE OR CAPPED WILL NOT NEED TO BE LINED.

14 CONNECT NEW 2" VENT TO NEAREST VENT IN INTERSTITIAL FLOOR ABOVE.

18 DEMARCATION LINE BETWEEN NEW TO-BE-LINE AND NOT-TO-BE-LINED SEWER PIPING.

19 AFTER COMPLETION OF SEWER MAIN RE-LINING, CLEANLY RE-ESTABLISH SEWER BRANCH WITH REINSTATEMENT CUTTER. IF CONTRACTOR DAMAGES EITHER THE MAIN LINE OR THE REINSTATED LINE DURING THIS PROCESS, CONTRACTOR SHALL REPAIR DAMAGED LINE TO THE SATISFACTION OF THE VA.

NEW CONSTRUCTION

20 EXISTING STORM DRAIN PIPING TO REMAIN.

21 NEW PIPE LINING TO PROTRUDE SLIGHTLY INTO MANHOLE - NO MORE THAN 2".

27 EXTEND LINING UP INTO CLEAN-OUT AS MUCH AS POSSIBLE. CLEAN AND EPOXY COAT BOTH CLEAN-OUT RISER AND PIPING TO LIMITS OF NEW PIPE

LINING.

28 CUT AND CAP 4" SEWER PIPE BELOW GRADE. EXTEND AND INSTALL NEW 4" WALL CLEANOUT, 18" ABOVE FINISH FLOOR AND OPENING INTO CORRIDOR CB-15. ALL NEW SEWER PIPE SHALL BE NEW AGE CAST IRON. VERIFY EXISTING WALL THICKNESS FOR PIPE FIT. ADVISE VA IF WALL WILL NEED TO BE MODIFIED TO ACCOMMODATE NEW PIPE/CLEANOUT. COORDINATE TEMPORARY WORK ROOM ISOLATION FOR CORRIDOR WORK WITH VA.

30 ISOLATION WORK ROOM (IWR #6 & IWR#7). THESE IWR'S ARE UTILIZED FOR RESTRICTING ACCESSING OF THE SPD AND CLEAN STORAGE. IWR #6:

NOMINAL 7.75'X7.5' WITH DOUBLE DOORS. NO HEPA FILTER EXHAUST UNIT #7: NOMINAL 9'X7.5' WITH DOUBLE DOORS. NO HEPA FILTER EXHAUST UNIT.

31 PROVIDE FLOOR PROTECTION. 1/4" MASONITE WIH TAPED SEAMS OF TILE FLOOR IN THIS AREA.

32 ABANDON 4" WP IN PLACE. REMOVE EXISTING FLOOR CLEANOUT TO BELOW GRADE AND PATCH FLOOR TO MATCH EXISTING ADJACENT FLOORING.

33 EXISTING FLOOR CLEANOUT. USE FOR PIPE ACCESS TO CLEAN PIPE AND PIPE LOCATOR TO CONFIRM EXACT LOCATION OF ISOLATION WORK ROOM AND SAW CUTS PRIOR TO CONSTRUCTION OR ISOLATION WORK ROOMS. COORDINATE WITH VA FOR EXACT REQUIREMENT OF CONTAINMENTS AT CLEANOUT

LOCATIONS PRIOR TO CLEANING/LOCATOR PROCESS COMMENCES.

37 INSTALL NEW CLEANOUT AT THIS LOCATION. REMAINING LINE TO BE ABANDONED IN PLACE AND CAPPED.

40 CONTRACTOR TO INSTALL NEW SINK PROVIDED TO EXISTING PLUMBING. ROUTE DRAIN TO NEAREST FLOOR SINK. SINK SHOWN FOR REFERENCE, REFER

TO SHEET AE102 FOR MORE INFORMATION.

43 2" VENT UP/3" WASTE DOWN.

54 4" WASTE DOWN/ 2" VENT UP.

GENERAL NOTES

1. THIS SHEET DEFINES THE SEWER PIPE RE-LINING OPERATIONS. THE SEWER PIPE RE-LINING OPERATIONS SHALL BE PERFORMED WITH THE CURED IN PLACED PLASTIC PIPE TECHNOLOGY SPECIFICATIONS AND DETAILS. PERMA PIPE IS THE BASIS OF DESIGN.

2. UNLESS SPECIFICALLY INDICATED OTHERWISE AT PARTICULAR WORK AREAS, ALL SAW-CUTTING, PNEUMATIC DRILLING (JACK - HAMMMERING), EXCAVATION WORK, AND EXCAVATED SOILS STORAGE SHALL BE PERFORMED AND CONTAINED INSIDE HEPA EXHAUSTED/PROTECTED ENCLOSURES COMPLYING WITH THE INFECTION RISK ASSESSMENT LEVEL IV CATEGORY. SEE DRAWING 41-P004 AND SPECIFICATIONS FOR DETAILS.

3. ALL SEWER PIPING EXPOSED BY THE ACCESS PITS SHALL BE REPLACED WITH NEW PIPE AND PIPE FITTINGS. TRANSITION COUPLINGS SHALL BE PROVIDED BETWEEN SEWER SEGMENTS THAT HAVE BEEN REHABILITATED AND NEW PIPE AND PIPE FITTINGS.

4. ARROW ADJACENT TO PIPING ← INDICATES RECOMMENDED DIRECTION OF PIPE RE-LINING PROCESS.

5. BROKEN CONCRETE SHALL BE REMOVED FROM BUILDING WITHIN A CLEAN AND DUST FREE COVERED CART, VIA A PATH AND AT TIMES AS COORDINATED WITH VA COTR AND INFECTION CONTROL. CLEAN ROOM GARB FOR WORKERS TRANSPORTING CART WILL BE REQUIRED.

ELECTRICAL CLOSET

BC-110E

MECH

BD-141

SOILED RECV &

DECONTAMINATION

BC-110

BREAK ROOM

BC-103B

CORRIDOR

CB-15

BREAK ROOM

BC-103BTLT (F)

BC-115G

CART WASH

BC-114

STERILIZATION

PREPARATION

BC-111

VESTIBULE

BC-125

STAIR

N0-3

VESTIBULE

BC-113

MECH EQUIP

BC-112

MECH RM

BC-126B

PARTS RM

BC-126A

TECHNICAL WORK

SPACE

BC-126

RECEPTION AND PGM

ASST

BC-125

OFFICE OF CHIEF

BIOMED

BC-125A

CORRIDOR

CB-17

BIOMED WORK SPACE

BC-125D

WORK AREA & STOR

BC-115C

MED GAS

BC-121

BREAKDOWN

BC-115B

STOR

BC-118

STAFF WORK AREA

BC-115

OFFICE

BC-115E

SPS CHANGE AREA

BC-103

STOR

BC-119

RECEPTION

BC-121A

OFFICE

BC-123

MED SUPPLY TECH

BC-121B

HAC

BC-115A

LOCKERS

BC-102

TLT

BC-105

TLT

BC-104

CORRIDOR

CB-16

1/

2"

1/ 2"

1/

2"

1/ 2" 2 1/

2"

1/ 2"

3/4" 3/4"

1"

1/

2"

2 1/2" DHW

2 1/2" DCW

1/2"

1/2"

2 1/2"

1/

2" D

H W

1/

2" D

C W

1"

1/

2"

1/

2"

1" DHW

1" DCW

1" DCW

1" DHW

P-414

P-414

P-414

P-418

1" DHWR

1" D

H W

R

1" DHWR

1" D

H W

R

1" DHW

HAC

BC-110D

P-401

2 3 4 5 6 71

P-707

1/2" DHW/DCW

DOWN

3/4" DHW

3/4" DCW

P-502

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

HLD ANTEROOM

BC-110A

HLD ALCOVE

BC-110C

TMV-1

TMV-1

TMV-1

P-708

P-708

EX. HAND WASH SINK

FS-R

SPS DEPARTMENT

BUILDING 41

BASEMENT LEVEL, QUAD C

N

BUILDING 41 - BASEMENT LEVEL KEY PLAN

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR SBBL COLLABORATIVE JN, INC.

100 N. STONE AVE STE 1102

TUCSON, AZ 85701-1524

(520) 620-0255

NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023

NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024

NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023

CIVIL / STRUCTURAL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

HEALTHCARE PLANNER

THE INNOVA GROUP

3196 NORTH SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:2

:4

A

M

PLUMBING BASEMENT - SPS - DOMESTIC

WATER PLAN

WRS 49 79RJS

BID DOCUMENTS

REPAIR SPS SEWER AND

UPGRADE EQUIPMENT AREA

08/11/23

501-21-101

RAYMOND G. MURPHY VAMC

1501 SAN PEDRO DRIVE SE

ALBUQUERQUE, NM 87108

PP100

SPUR #: 1993.10

N

1/8" = 1'-0"

PLUMBING BASEMENT - SPS - DOMESTIC WATER PLAN1

KEYNOTES

2 EXISTING PIPES SHOWN ON THIS DRAWING IS SHOWN FOR REFERENCE ONLY. PIPE IS LOCATED IN THE INTERSTITIAL SPACE

ABOVE.

39 EXISTING DOMESTIC HOT AND COLD-WATER LINES DOWN.

40 CONTRACTOR TO INSTALL NEW SINK PROVIDED TO EXISTING PLUMBING. ROUTE DRAIN TO NEAREST FLOOR SINK. SINK

SHOWN FOR REFERENCE, REFER TO SHEET AE102 FOR MORE INFORMATION.

42 CONTRACTOR TO DISCONNECT EXISTING EQUIPMENT TO ALLOW FOR DRAIN LINING. ANY SHUT DOWN NEEDS TO BE COORDINATED WITH THE COR OF THE VA BEFORE DISCONNECTING. ANY EQUIPMENT MOVED FOR DRAIN LINING WILL REQUIRE RECONNECTION ONCE THE LINING PROCESS IS COMPLETE. CONTRACTOR TO VERIFY ALL PIPING CONNECTIONS ARE

GOOD BEFORE START UP.

45 EXISTING RG WATER FROM ABOVE.

46 1-1/4" DCW AND 1" DHW FROM INTERSTITIAL ABOVE. ROUTE TO MIXING VALVE LOCATED IN INTERSTITIAL SPACE.

47 EXISTING 1" DHWR, 3" DHW, AND 4" DCW FROM INTERSTITIAL ABOVE.

48 EXISTING 1/2" DHW AND DCW TO FIXTURE.

50 ROUTE 3/4" DHW AND DCW TOW TO MOP SINK.

56 ROUTE 3/4" REAGENT WATER (PURE WATER) FROM ABV DOWN TO SINK. PROVIDE SHUT OFF VALVE ON WALL NEAR SINK.

2 3 4 5 6 7 8

D

E

F

2" O

2" MA

2" LV

1" G

1" RG

1" RG

1" RG

6" DCW

4" DCW

1 1/2" SA

6" DCW

4" DCW

4" DHW

1" RG

1" RG

2" O

1" RG

1/2" SA

1 1/2" SA

4" DCW

3" DHW

1" DHWR

3/4" LV

1" SA1" G1" LV3" MV2" MA2" O

6" DCW

4" DCW

4" DHW4" OA

2" O

1" G

1" LV

4" MV

2" MA

2" O

4" DCW

6" DCW

4" DHW

2 1/2" DHWR

2" RG

1" RG

3/4" RG

3/4" RG

1/2" SA

4" SCW

NOT IN SCOPE

1-1/4" DCW AND 1" DHW

MIXING VALVE DOWN TO P-707

FIXTURE IN SPS1 1/4" DCW

1" DHW

2" RG

1" RG

1" RG

3/4"RG WATER DOWN TO SINK

SPS DEPARTMENT

BUILDING 41

BASEMENT LEVEL, QUAD C

N

BUILDING 41 - BASEMENT LEVEL KEY PLAN

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR SBBL COLLABORATIVE JN, INC.

100 N. STONE AVE STE 1102

TUCSON, AZ 85701-1524

(520) 620-0255

NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023

NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024

NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023

CIVIL / STRUCTURAL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

HEALTHCARE PLANNER

THE INNOVA GROUP

3196 NORTH SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:2

:5

A

M

PLUMBING INTERSTITIAL - SPS -

DOEMSTIC WATER PLAN

GH 50 79RJS

BID DOCUMENTS

REPAIR SPS SEWER AND

UPGRADE EQUIPMENT AREA

08/11/23

501-21-101

RAYMOND G. MURPHY VAMC

1501 SAN PEDRO DRIVE SE

ALBUQUERQUE, NM 87108

PP101

SPUR #: 1993.10

N

1/8" = 1'-0"

PLUMBING INTERSTITIAL - SPS -DOMESTIC WATER PLAN1

PLUMBING KEYNOTES

49 ROUTE NEW REAGENT WATER DOWN TO CART WASHER BELOW.

H

I

2 3 4 5 6 71

ELECTRICAL CLOSET

BC-110E

MECH

BD-141

SOILED RECV &

DECONTAMINATION

BC-110

BREAK ROOM

BC-103B

CORRIDOR

CB-15TLT (F)

BC-115G

CART WASH

BC-114

STERILIZATION

PREPARATION

BC-111

VESTIBULE

BC-125

STAIR

N0-3

VESTIBULE

BC-113

MECH EQUIP

BC-112

MECH RM

BC-126B

PARTS RM

BC-126A

TECHNICAL WORK

SPACE

BC-126

RECEPTION AND PGM

ASST

BC-125

OFFICE OF CHIEF

BIOMED

BC-125A

CORRIDOR

CB-17

BIOMED WORK SPACE

BC-125D

WORK AREA & STOR

BC-115C

MED GAS

BC-121

BREAKDOWN

BC-115B

STOR

BC-118

STAFF WORK AREA

BC-115

OFFICE

BC-115E

SPS CHANGE AREA

BC-103

STOR

BC-119

RECEPTION

BC-121A

OFFICE

BC-123

MED SUPPLY TECH

BC-121B

HAC

BC-115A

LOCKERS

BC-102

TLT

BC-105

TLT

BC-104

CORRIDOR

CB-16

HAC

BC-110D

3/4" LA3/4" LA

1/2" SA

1/2" SA

MA

MV

42 4242 4242

1/2" SHOP AIR

FROM ABOVE.

NOT IN SCOPE

NOT IN SCOPE

HLD ANTEROOM

BC-110A

HLD DECON

BC-110B

HLD ALCOVE

BC-110C

VESTIBULE

BC-100

IRM SIGNAL CLOSET

BC-110D

CLOSET

BC-110C

MECH

BC-115F

EQUIP TEST &

STORAGE

BC-115D

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR SBBL COLLABORATIVE JN, INC.

100 N. STONE AVE STE 1102

TUCSON, AZ 85701-1524

(520) 620-0255

NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023

NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024

NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023

CIVIL / STRUCTURAL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

HEALTHCARE PLANNER

THE INNOVA GROUP

3196 NORTH SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:2

:5

A

M

PLUMBING BASEMENT - SPS- MEDICAL

GAS PLAN

GH 51 79RJS

BID DOCUMENTS

REPAIR SPS SEWER AND

UPGRADE EQUIPMENT AREA

08/11/23

501-21-101

RAYMOND G. MURPHY VAMC

1501 SAN PEDRO DRIVE SE

ALBUQUERQUE, NM 87108

PG100

SPUR #: 1993.10

N

1/8" = 1'-0"

PLUMBING BASEMENT - SPS - MEDICAL GAS PLAN1

PLUMBING KEYNOTES

13 CONNECT EXISTING SHOP AIR LINE TO CART WASHER.

42 CONTRACTOR TO DISCONNECT EXISTING EQUIPMENT TO ALLOW FOR DRAIN LINING. ANY SHUT DOWN NEEDS TO BE COORDINATED WITH THE COR OF THE VA BEFORE DISCONNECTING. ANY EQUIPMENT MOVED FOR DRAIN LINING WILL REQUIRE RECONNECTION ONCE THE LINING PROCESS IS COMPLETE. CONTRACTOR TO

VERIFY ALL PIPING CONNECTIONS ARE GOOD BEFORE START UP.

44 EXISTING 3/4" LAB AIR FROM ABOVE.

S A

N

P

ED

R O

DR

I V E

DR

IV

E

R

I DG

EC RE

ST

5 350

5 350

3 5

5 340

5348.7

5348.5

5347.2

5337.2

5345.6

5348.6

5347.8

5346.9

5328.7

5347.0

5347.2

5347.4

5346.8

5348.6

5348.4

5348.4

5348.3

5348.1

5348.2

5348.2

5348.2

5347.3

5346.8

5349.0

5348.7 5348.2

5347.2

5347.2

5346.6

5345.2

5346.5

5346.6 5347.0

5345.2

5340.7

5337.1

5340.4

5342.7

5338.4 5335.6

5339.4 5339.1

5340.1

5336.3

5342.9

5345.6

5340.8

5327.1

5322.8

5324.4

5328.4

5323.2

5322.7

5320.8

5320.5

5340.5

5339.6 5340.7 5342.8

5348.8 5350.1

5348.2

5349.4

5349.8

5351.2

5350.2

5340.8

5348.5

5348.3

5344.5

5346.6

5346.7

5344.6

5340.3

5342.4

5342.7

5347.2

5346.4

5348.6

5346.5

5345.4

5345.2

5344.4 5346.5

5344.2

5342.8

5345.2

5340.2

5340.9

5338.6

5337.8

5342.85340.9

5340.9 5342.7

5344.4

5344.4

5344.8

5345.2 5345.2

5346.7

5346.7

5348.4

5346.5

5346.5 5346.6 5347.1

5348.8

5348.3

5348.2

5347.7

5349.0

5350.6

5349.0

5326.8

5326.5

5355.0

5350.8

5348.7

5344.8

5346.4

5348.4

5332.4

5342.8

5344.7

5349.6

5340.6

5340.1

5348.5

5336.5

5339.0

5352.4

5330.4

5326.3

5328.2

5350.9

5348.4

5346.6

5341.1 5344.9

5345.3

5347.3

5343.5

5346.2

5346.7

5344.9

5349.1

5338.8

5340.6

5341.2

5338.6

5336.6

5337.1

5334.6

5334.6

5328.7

5328.2

5327.0

5326.7

5325.2

5324.5

W

ALL

C O U

RT

C OU RT

C OU RT

W A

LL

WALK

EN CLOSED

WALK

EN CLOSED

W

ALL

E N

CL

OS ED

W

ALK

W

ALL

W

ALL

W A

LL

W A

LL

W A

LL

W

ALL

W

ALL

W A

LL

W

AL LS

W A

LL

W A

LL

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

MECHANICAL EQUIP.

DHW-EX

STERIS TRAILER

#1

STERIS TRAILER

#2

2" DCW

2" DHW

1 1/2" DCW

1 1/2" DHW

1 1/2" DHW

1 1/2" DCW

4" SS

4" S

S

4" SS

1 1/2" DHW

1 1/2" DCW

2" DHW

2" DCW

3/4" DHWR

3/4" DHWR

C.O.

C.O.

DHW-1

3" SS

4" SS

4" SS 3"

S

S

6" ST

6" S

T

3" SS

4" S

S

4" SS

2" S

S

FD-D

FD-C

FD-D

FD-C

FD-D

FD-D

FD-D

FD-D

FD-DFD-D

FD-D

FD-D

S1

S4

S3

S3S3

S5

S6S6

S6S6

S7

S7

BFP-1

BFP-2

2" SS

DHWCP-1

2" SS

1-1/2" VENT

3" X 2" HUB DRAIN

1-1/2" VENT

3" X 2" HUB DRAIN

2" DCW

S12

S12

3/4" O

3/4" O

S13

S14

3/4" O

WS-1

BY-PASS VALVE

2" DCW

TEMPORARY SPS FACILITY

SE LOT NEAR BUILDING 45

RAYMOND G. MURPHY VA MEDICAL CENTER CAMPUS

N

B45

B41 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR SBBL COLLABORATIVE JN, INC.

100 N. STONE AVE STE 1102

TUCSON, AZ 85701-1524

(520) 620-0255

NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023

NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024

NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023

CIVIL / STRUCTURAL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

HEALTHCARE PLANNER

THE INNOVA GROUP

3196 NORTH SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:3

:0

A

M

PLUMBING SITE PLAN - TEMPORARY

SPS TRAILER

WRS 52 79RJS

BID DOCUMENTS

REPAIR SPS SEWER AND

UPGRADE EQUIPMENT AREA

08/11/23

501-21-101

RAYMOND G. MURPHY VAMC

1501 SAN PEDRO DRIVE SE

ALBUQUERQUE, NM 87108

PS100

SPUR #: 1993.10

N

1/8" = 1'-0"

PLUMBING SITE PLAN - TEMPORARY BUILDINGS1

PLUMBING KEYNOTES

S1 REMOVE EXISTING MANHOLE COVER. REPLACE WITH MODIFIED EJCO 4000 SERIES TEMPORARY SAFETY COVER. EJCO PRODUCT OR EQUAL TO ACCEPT 4" SANITARY PIPE FROM TRAILER.

S3 CONTRACTOR TO PROVIDE FREESTANDING PIPE SUPPORT STAND. MAX. 6'-0" ON CENTER FOR 1-1/4" AND SMALLER PIPE, 10'-0" ON CENTER FOR 1-1/2" OR LARGER.

S4 NEW SEWER PIPE SHALL BE NEW AGE CAST IRON. NEW SEWER PIPE TO BE SUPPORTED EVERY 5'-0". MAINTAIN A MINIMUM SEWER SLOPE OF 1/8" PER FOOT.

S5 PROVIDE ALUMINUM JACKET FOR EXTERIOR PIPING: WEATHERPROOF, MINIMUM 0.023" THICKNESS, WITH LOCKING LONGITUDINAL JOINTS AND STAINLESS-STEEL BANDS NOT GREATER THAN 18" ON CENTER.

S6 CONNECT 1-1/2" DCW AND 1-1/4" DHW TO STERIS TRAILER HOT AND COLD 1-1/4" MPT FRESH-WATER FILL PORTS. PROVIDE FULL PORT BALL VALVES BEFORE TRAILER CONNECTION.

S7 CONNECT 4" SANITARY WASTE TO STERIS TRAILER WASTE LINES.

S12 CONTRACTOR TO TEST BACK FLOW PREVENTERS BEFORE CONNECTING PIPE TO TEMP SPS TRAILER.

S13 PROVIDE A TEMPORARY EMERGENCY OXYGEN INLET CONNECTION WHILE TEMPORARY TRAILERS ARE IN USE. CAP AND SEAL ONCE TRAILERS ARE REMOVED.

S14 REMOVE AND REPLACE EXISTING DOMESTIC WATER HEAT EXCHANGER. UNIT WILL BE USED TO PROVIDE HOT WATER FOR TRAILERS AND WILL REMAIN ONCE THE TRAILERS ARE GONE.

1. CONTRACTOR TO VERIFY LOCATION AND SIZE OF THE UTILITIES BEFORE ANY CONSTRUCTION IS TO BEGIN. PIPING REFER TO CIVIL SHEETS FOR MORE

INFORMATION.

2. STERIS TRAILERS WILL REQUIRE THE COLD WEATHER INSULATION PACKAGE.

GENERAL NOTES

4" SS

4" SS

1 1/2" DCW

1 1/2" DHW

2" DCW

2" DHW

3/4" DHWR

4" SS

1 1/2" DCW

1 1/2" DHW

3/4" DHWR

TEMP-AH-1

2" SS

DHW-1

DHW-EX

2 1/2" DHW

1 1/2" DHWR

2" FS

4" FS

4" DCW

4" FS

1" DCW

1" DCW

4" DCW

2 1/2" DHW

1 1/2" DHWR

1 1/2" DHWR

BFP-1

BFP-2

DHWCP-1

S1

S2

S2

S4

S4

S3

S3

S8

S9S9

S9

S6

1 1/4" DHW

1 1/2" DCW

S6

S5

S5

C.O.

S10

S11

2" SS

4" SS

S4

S11

S10

TEMP-AH-2

3/4" O

3/4" O

S13

S12

S12

EX. OXYGEN CONNECTION

WS-1

2" DCW

2" DHW

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR SBBL COLLABORATIVE JN, INC.

100 N. STONE AVE STE 1102

TUCSON, AZ 85701-1524

(520) 620-0255

NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023

NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024

NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023

CIVIL / STRUCTURAL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

HEALTHCARE PLANNER

THE INNOVA GROUP

3196 NORTH SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:3

:1

A

M

PLUMBING ISOMETRIC - TEMPORARY

TRAILER PIPING

GH 53 79RJS

BID DOCUMENTS

REPAIR SPS SEWER AND

UPGRADE EQUIPMENT AREA

08/11/23

501-21-101

RAYMOND G. MURPHY VAMC

1501 SAN PEDRO DRIVE SE

ALBUQUERQUE, NM 87108

P-301

SPUR #: 1993.10

NTS

PLUMBING ISOMETRIC - TEMPORARY TRAILER PIPING1

PLUMBING SITE KEYNOTES

S1 REMOVE EXISTING MANHOLE COVER. REPLACE WITH MODIFIED EJCO 4000 SERIES TEMPORARY SAFETY COVER. EJCO PRODUCT OR EQUAL TO ACCEPT 4" SANITARY PIPE FROM

TRAILER.

S2 CONNECT 4" SANITARY TO STERIS TRAILER 4" STUB OUT.

S3 CONTRACTOR TO PROVIDE FREESTANDING PIPE SUPPORT STAND. MAX. 6'-0" ON CENTER FOR 1-1/4" AND SMALLER PIPE, 10'-0" ON CENTER FOR 1-1/2" OR LARGER.

S4 NEW SEWER PIPE SHALL BE NEW AGE CAST IRON. NEW SEWER PIPE TO BE SUPPORTED EVERY 5'-0". MAINTAIN A MINIMUM SEWER SLOPE OF 1/8" PER FOOT.

S5 PROVIDE ALUMINUM JACKET FOR EXTERIOR PIPING: WEATHERPROOF, MINIMUM 0.023" THICKNESS, WITH LOCKING LONGITUDINAL JOINTS AND STAINLESS-STEEL BANDS NOT GREATER

THAN 18" ON CENTER.

S6 CONNECT 1-1/2" DCW AND 1-1/4" DHW TO STERIS TRAILER HOT AND COLD 1-1/4" MPT FRESH-WATER FILL PORTS. PROVIDE FULL PORT BALL VALVES BEFORE TRAILER CONNECTION.

S8 CONNECT TO EXISTING 4" DCW PIPING.

S9 CONTRACTOR TO ROUTE TEMPORARY PIPE THROUGH EXISTING WALL FROM THE MECH ROOM TO THE TRAILERS.

S10 CONTRACTOR TO ROUTE CONDENSATE FROM BARD UNIT TO DRAIN. REFER TO MECHANICAL FOR MORE INFORMATION.

S11 3" X 2" HUB DRAIN FOR CONDENSATE.

S12 CONTRACTOR TO TEST BACK FLOW PREVENTERS BEFORE CONNECTING PIPE TO TEMP SPS TRAILER.

S13 PROVIDE A TEMPORARY EMERGENCY OXYGEN INLET CONNECTION WHILE TEMPORARY TRAILERS ARE IN USE. CAP AND SEAL ONCE TRAILERS ARE REMOVED.

STOR

BC-119

SPS CHANGE AREA

BC-103

SPS CHANGE AREA

BC-103

CORRIDOR

CB-16

HALL

BC-103A

MECH

BC-115F

1/2" SA

1" DHW

1" DCW

3/4" RG3/4" RG

2 1/2" DHW

2 1/2" DCW

1" DHW

1" DCW

3/4" DHW

3/4" DCW

SPS DEPARTMENT

BUILDING 41

BASEMENT LEVEL, QUAD C

N

BUILDING 41 - BASEMENT LEVEL KEY PLAN

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR SBBL COLLABORATIVE JN, INC.

100 N. STONE AVE STE 1102

TUCSON, AZ 85701-1524

(520) 620-0255

NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023

NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024

NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023

CIVIL / STRUCTURAL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

HEALTHCARE PLANNER

THE INNOVA GROUP

3196 NORTH SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:3

:1

A

M

PLUMBING PARTIAL PLANS

GH 54 79RJS

BID DOCUMENTS

REPAIR SPS SEWER AND

UPGRADE EQUIPMENT AREA

08/11/23

501-21-101

RAYMOND G. MURPHY VAMC

1501 SAN PEDRO DRIVE SE

ALBUQUERQUE, NM 87108

P-401

SPUR #: 1993.10

N

3/8" = 1'-0"

ENLARGED PLUMBING PLAN - CART WASHER1

HWS CWS

EMERGENCY FIXTURE.

CONFIGURATION AND TYPE

MAY VARY.

COUNTER.

THERMOSTATIC MIXING VALVE

THERMOMETER (OPTIONAL)

1/2" NOM. SWEAT FEMALE

INLET (HOT)

1/2" DOMESTIC HOT WATER

SUPPLY PIPING.

1/2" DOMESTIC COLD WATER

SUPPLY PIPING.

1/2" NOM. SWEAT FEMALE

INLET (COLD)

3-PORT THERMOSTATIC MIXING VALVE WITH

LOCKING TYPE TEMPERATURE REGULATOR

AND ADJUSTABLE HIGH TEMPERATURE LIMIT

STOP SET FOR 90 F. (NOTE 1)

1/2" NPT THREADED FEMALE OUTLET

1/2" NPT TEPID WATER FLEXIBLE SUPPLY RISER TO

EMERGENCY FIXTURE. WATER TEMPERATURE

BETWEEN 60-90F PER THE EMERGENCY FIXTURE

SPECIFICATIONS.

1/2" NPT THREADED MALE INLET

INTEGRAL INLET CHECK

VALVE (TYP. 2)

NOTES:

1. THERMOSTATIC MIXING VALVE SHALL BE CERTIFIED TO MEET ASSE 1071 AND LOW

LEAD REQUIREMENTS.

T W

S

TMV

HOT PIPECOLD PIPE

REFER TO SPECIFICATIONS FOR INSULATION TYPES, INSULATION

THICKNESSES, HANGER TYPES, HANGER ROD CONNECTIONS TO SRUCTURE

AND HANGER SPACING.

CUT INSULATION TO FIT AROUND

HANGER. SEAL EXPOSED

INSULATION ENDS WITH JOINT

SEALANT.

PROVIDE A SECTION OF HIGH

DENSITY INSULATION OR

STYROFOAM BILLETS AT EACH

HANGER OF COLD INSULATED PIPE.

THREADED STEEL ROD WITH

NUT AND WASHER BOTH

SIDES (TYP.).

CLEVIS HANGER, SHOWN FOR CLARITY.

SIZE HANGER FOR COLD PIPE OUTSIDE

DIAMETER PLUS INSULATION THICKNESS.

DO NOT PENETRATE INSULATION WITHE

HANGER.

CLEVIS HANGER, SHOWN FOR

CLARITY. SIZE HANGER FOR HOT

PIPE OUTSIDE DIAMETER.

SECURE PIPE HANGER TO

STRUCTURE (TYP.)

PROVIDE SHORT INSULATION SHIELD

FOR LAPPING INSULATION JACKET

OVER HIGH DENSITY INSULATION OR

STYROFOAM BILLETS. MAINTAIN

VAPOR BARRIER.

NOTE:

1. POINT-OF-USE THERMOSTATIC MIXING VALVES MUST

CONFORM TO ASSE 1070.

TYPICAL FAUCET (OR

OTHER LEVER

CONTROLLED FIXTURE)

THERMOSTATIC

MIXING VALVE

TEMPERED WATER

SUPPLY OUTLET

COLD WATER SUPPLY

OUTLET

COLD WATER

SUPPLY INLET

HOT WATER

SUPPLY INLET

PROVIDE A METAL SUPPORT

PLATE WHEN DRAIN IS INSTALLED

IN AN EXISTING FLOOR - CAULK

AROUND DRAIN PRIOR TO RE-

GROUTING

NOTE:

1. SLOPE MEMBRANE LINER 2% TO DRAIN.

THREADED, CAULKED OR NO-HUB

CONNECTION

FLASHING CLAMP

WITH WEEP HOLES

STRUCTURAL SLAB

TILE FLOOR

CONCRETE FILL

NICKLE BRONZE

ADJUSTABLE

STRAINER (FLUSH

WITH FINISHED

FLOOR)

CEMENT BED

LOOSE GRAVEL AT

WEEP HOLES 3mm to 6mm SIZE

WATERPROOF

MEMBRANE

CLAMP WATERPROOF

MEMBRANE INSIDE OF DRAIN

BODY TO DRAIN TO WEEP

HOLES

STANDARD 1/8 BEND

CAST IRON PIPE

RISER

CLEANOUT PLUG

TOP OF COVER SHALL BE

FLUSH WITH TOP OF

FLOOR

FINISHED FLOOR

CHROME WALL COVER

AND SCREW

STANDARD 1/8 BEND

PLUGGED TEE WITH

CLEANOUT

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR SBBL COLLABORATIVE JN, INC.

100 N. STONE AVE STE 1102

TUCSON, AZ 85701-1524

(520) 620-0255

NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023

NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024

NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023

CIVIL / STRUCTURAL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

HEALTHCARE PLANNER

THE INNOVA GROUP

3196 NORTH SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:3

:1

A

M

PLUMBING DETAILS

GH 55RJS

BID DOCUMENTS

REPAIR SPS SEWER AND

UPGRADE EQUIPMENT AREA

08/11/23

501-21-101

RAYMOND G. MURPHY VAMC

1501 SAN PEDRO DRIVE SE

ALBUQUERQUE, NM 87108

P-501

SPUR #: 1993.10

N

12" = 1'-0"

3-PORT TMV TO EMERGENCY FIXTURE1

N

12" = 1'-0"

PIPE HANGER DETAIL2

N

12" = 1'-0"

POINT-OF-USE 4-PORT THERMOSTATIC MIXING VALVE DETAIL3

N

12" = 1'-0"

TYPE "C" FLOOR DRAIN DETAIL4

N

12" = 1'-0"

TYPICAL INTERIOR FLOOR CLEANOUT5

N

12" = 1'-0"

TYPICAL INTERIOR WALL CLEANOUT6

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR SBBL COLLABORATIVE JN, INC.

100 N. STONE AVE STE 1102

TUCSON, AZ 85701-1524

(520) 620-0255

NM ARCH - SETH CAVIN #005667 EXP. 12/31/2023

NM MECH - JAMES R. MYLES #25930 EXP. 12/31/2024

NM ELEC - EVANS SORDIASHIE #22917 EXP. 12/31/2023

CIVIL / STRUCTURAL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

HEALTHCARE PLANNER

THE INNOVA GROUP

3196 NORTH SWAN ROAD

TUCSON, AZ 85712

(520) 886-8650

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

/1

/2

:3

:1

A

M

PLUMBING SCHEDULES

GH 56RJS

BID DOCUMENTS

REPAIR SPS SEWER AND

UPGRADE EQUIPMENT AREA

08/11/23

501-21-101

RAYMOND G. MURPHY VAMC

1501 SAN PEDRO DRIVE SE

ALBUQUERQUE, NM 87108

P-601

SPUR #: 1993.10

PLUMBING FIXTURE SCHEDULE

MARK FIXTURE

BASIS OF DESIGN PIPING ROUGH-IN WASTE FIXTURE

UNITS WATER FIXTURE UNITS DESCRIPTIONMANUFACTURER MODEL WASTE (IN) VENT (IN) CW (IN) HW (IN)

P-418 Lavatory, Handwash Elkay ELV2219SACC 2 1-1/2 1/2 1/2 2 2 Stainless steel wall hung sink with Sloan SF-2250-4-BAT sensor operated faucet. Faucet to have laminar flow

P-502 Service Sink Acorn Engineering TNC24-TF2 3 2 3/4 3/4 3 4 Square front, corner terrazzo mop basin, fiat white. Includes integral stainless steel drain assembly.

P-707…