Amendment 0003_Attachment AE. 100P DESIGN FOR CONSTRUCTION- 2012.05.16.pdf
PDF 46 MB Posted
- Solicitation number
- 36C26224B0001_1
About this file
This solicitation is for construction services to replace an aging roof and install lightning protection at the Veterans Affairs Loma Linda Medical Center in Loma Linda, California. The contractor will be responsible for furnishing all labor, equipment, materials, and supervision necessary to replace the existing PVC roofing system with a new TPO roof system. Additional requirements include preparation and performance of submittals, change orders, site visits, meetings, and providing construction meeting minutes to the VA Contracting Officer's Representative. All work must be performed according to the general specifications, statement of work, design, schedule, and other supporting documents while the medical center remains operational. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYSTEM SUMMARY:
LOCATION
LATITUDE 34.050216° N
LONGITUDE 117.250537° W
AVERAGE LOW 4°C
RECORD LOW -7°C
AVERAGE HIGH 36°C
SOLAR MODULE
MANUFACTURER SAMSUNG
MODEL LPC247M-08
STC WATTAGE 247W
TOTAL QUANTITY 6,888
SYSTEM
SYSTEM DC RATING 1,701 kW-DC STC SYSTEM AC RATING 1,490 kW-AC CEC INVERTER RATING 1,420 kW-AC
ARRAY TILT 5° (CARPORTS); 10° (ROOFTOPS);
7° (PARKING GARAGE)
ARRAY AZIMUTH BETWEEN 180° AND 270°, MOSTLY 180° (82%)
OWNER:
DEPARTMENT OF VETERANS AFFAIRS
SITE CONTACT: LARRY BARRETT - ENERGY MANAGER / COTR
TEL: 909.825.7084 x 2925 - EMAIL: LARRY.BARRETT@VA.GOV
SUMMARY DESCRIPTION:
THE PROJECT CONSISTS OF A GRID-TIED SOLAR PHOTOVOLTAIC
SYSTEM CONNECTED TO THE FACILITY'S 480V SERVICE BAYS.
NO ENERGY STORAGE OR BACKUP FEATURES ARE INCLUDED.
THE SYSTEM CONSIST OF SEVEN SOLAR ARRAYS: THREE
ARRAYS ON THE ROOFTOP OF THE MAIN BUILDING AND NURSING
HOME; THREE ARRAYS MOUNTED ON CARPORTS IN THE
NORTHEAST AND SOUTHWEST PARKING AREAS AND ONE ARRAY
MOUNTED ON THE PARKING GARAGE.
LOMA LINDA VA MEDICAL CENTER
GRID-TIED SOLAR PHOTOVOLTAIC SYSTEM - PHASE II
11201 BENTON STREET, LOMA LINDA, CA 92357
CODE REFERENCE:
1. ALL MATERIALS AND EQUIPMENT SHALL BE
INSTALLED PER MANUFACTURER'S INSTRUCTIONS,
AND IN ACCORDANCE WITH THE REQUIREMENTS OF
THE 2008 NATIONAL ELECTRICAL CODE, DEPT. OF VA
SPECIFICATIONS AND LOCAL CODES.
2. STRUCTURES SHALL BE INSTALLED PER 2010
CALIFORNIA BUILDING CODE, ACI 318.
CONTRACTOR:
SUNWIZE TECHNOLOGIES
111 W. ST. JOHN STREET, SAN JOSE, CA 95113
CONTACT: ROBERT HLAVATY - PROJECT MANAGER
845.336.0146 ext. 7120 - BHLAVATY@SUNWIZE.COM
CONTACT: ALBERTO GONZALEZ - PROJECT ENGINEER
408.510.5070 - AGONZALEZ@SUNWIZE.COM
TITLE SHEET
G-101
G-101
ARCH D (36"X24")ARCH D (36"X24")
B
A
C
D
E
F
G
H
I
J
K
L
THIS DRAWING IS THE CONFIDENTIAL
PROPERTY OF SUNWIZE TECHNOLOGIES
WWW.SUNWIZE.COM
SHEET NO:
B
A
C
D
E
F
G
H
I
J
K
L
21 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PAPER SIZE:
DRAWING NUMBER:
PROJECT NUMBER:
SHEET TITLE:
PROJECT / CUSTOMER INFORMATION:
PROJECT NAME:
LOMA LINDA VA MEDICAL CENTER
PHOTOVOLTAIC SYSTEM
LOMA LINDA VA MEDICAL CENTER
11201 BENTON STREET,
LOMA LINDA, CA 92357
503-6032
REV BY CHK
50% DESIGNA AG
REV. C
BH 2011.12.20
DESCRIPTION DATE
100% DESIGNB AG BH 2012.03.30
100% DESIGN FOR CONSTRUCTIONC AG CC 2012.05.10
LOMA LINDA VA
MEDICAL CENTER
VICINITY MAP
AERIAL VIEW
N
N
NAME DATE SIGNATURE
DONALD F. MOORE
MEDICAL CENTER DIRECTOR
DWIGHT EVANS, M.D.
CHIEF OF STAFF
ANNE GILLESPIE
ASSOCIATE DIRECTOR FOR PATIENT
AND NURSING SERVICES
SHANE ELLIOTT
ASSOCIATE DIRECTOR FOR
ADMINISTRATION
PRACHI ASHER
ASSISTANT DIRECTOR
ROBERT BARTOLINA
CHIEF, FACILITY
MANAGEMENT SERVICES (FMS)
LARRY BARRETT
ENERGY MANAGER
DAVE SCHUELKE
SUPERVISOR OF PROJECTS, FMS
RANDY REYNOLDS
MAINTENANCE AND OPERATIONS
MANAGER, FMS
DOUGLAS WIRTHGEN
CHIEF, OFFICE OF INFORMATION
& TECHNOLOGY (OI&T)
ROBERT MCCRAY
ACTING SAFETY MANAGER, FMS
MICHAEL ING, M.D.
CHIEF, INFECTIOUS DISEASE
/ INFECTION CONTROL
SUSIE O'NEAL
INFECTION CONTROL COORDINATOR
CONTRACTING OFFICER
PROJECT ENGINEER /COTR
VA LOMA LINDA SOLAR SYSTEM - PHASE II
SIGNATURE APPROVAL BLOCK
LOMA LINDA VA MEDICAL CENTER
GRID-TIED SOLAR PHOTOVOLTAIC SYSTEM - PHASE II
11201 BENTON STREET, LOMA LINDA, CA 92357
SITE GENERAL
G-101 TITLE SHEET
G-101 INDEX INDEX SHEET
G-102 NOTES AND SYMBOLS
A-101 EXISTING SITE AND UTILITIES PLAN
A-201 PV LAYOUT AND INTERCONNECTION - SITE PLAN
A-202 PV SYSTEM SUMMARY
A-301 DEMOLITION AND LANDSCAPING - SITE PLAN
S1 TO S6 SKYLINE STEEL - PARKING CANOPIES STRUCTURAL DRAWINGS
S1 TO S8 SKYLINE STEEL - PARKING GARAGE STRUCTURAL DRAWINGS
SL0 SUNLINK COVER SHEET
SL1.0 SUNLINK ARRAY LAYOUT PLAN
E-601 DATA ACQUISITION AND MONITORING - GENERAL PLAN
L-101 NEW LIGHTING - GENERAL PLAN
E-701 VA EXTRAS - 120V/240V CIRCUITS IN CARPORTS - SITE PLAN
E-705 VA EXTRAS - SPARE CONDUITS IN CARPORTS - SITE PLAN
ARRAY 1
A-203 PV LAYOUT AND INTERCONNECTION - ARRAY 1
SL1.1 SUNLINK ARRAY LAYOUT PLAN - SUBARRAY 1A
SL1.2 SUNLINK ARRAY LAYOUT PLAN - SUBARRAY 1B
E-101 SLD AND EQUIPMENT SCHEDULE - ARRAY 1
E-201 DC 3-LINE DIAGRAMS AND ELECTRICAL SCHEDULES - ARRAY 1
E-301 AC 3-LINE DIAGRAMS AND ELECTRICAL SCHEDULES - ARRAY 1
E-401 DC AND AC RUN SCHEDULES - ARRAY 1
E-421 SOURCE CIRCUIT MAP - ARRAY 1
S-201 EQUIPMENT LAYOUT - ARRAY 1
E-602 DATA ACQUISITION AND MONITORING - SLD ARRAY #1 & PHASE I
E-603 DAS EQUIPMENT WIRING SCHEDULE - ARRAY 1 & PHASE I
E-801 LABELS AND PLACARDS - ARRAY 1
E-802 LABELS AND PLACARDS - ARRAY 1
ARRAYS 3&9
A-204 PV LAYOUT AND INTERCONNECTION - ARRAYS 3 AND 9
A-304 DEMOLITION AND LANDSCAPING - NURSING HOME AREA
A-305 DEMOLITION - PARKING GARAGE
SL1.3 SUNLINK ARRAY LAYOUT PLAN - SUBARRAY 3A AND 3B(PARTIAL)
SL1.4 SUNLINK ARRAY LAYOUT PLAN - SUBARRAY 3B(PARTIAL) AND 3C
E-102 SLD AND EQUIPMENT SCHEDULE - ARRAYS 3 AND 9
E-202 DC 3-LINE DIAGRAMS AND ELECTRICAL SCHEDULES - ARRAYS 3 AND 9
E-302 AC 3-LINE DIAGRAMS AND ELECTRICAL SCHEDULES - ARRAYS 3 AND 9
E-402 DC AND AC RUN SCHEDULES - ARRAY 3
E-407 DC AND AC RUN SCHEDULES - ARRAY 9
E-422 SOURCE CIRCUIT MAP - ARRAY 3
E-426 SOURCE CIRCUIT MAP - ARRAY 9
S-202 EQUIPMENT LAYOUT - ARRAY 3
S-206 EQUIPMENT PAD LAYOUT - ARRAY 9
E-709 VA EXTRAS - SPARE CONDUITS - PARKING GARAGE
E-604 DATA ACQUISITION AND MONITORING - SLD ARRAYS 3&9
E-605 DAS EQUIPMENT WIRING SCHEDULE - ARRAYS 3&9
L-105 NEW LIGHTING PLAN AND SCHEDULE -ARRAY 9
L-108 PHOTOMETRIC MARK POINTS - PARKING GARAGE
E-803 LABELS AND PLACARDS - ARRAYS 3&9
E-804 LABELS AND PLACARDS - ARRAYS 3&9
ARRAY 4
A-205 PV LAYOUT AND INTERCONNECTION - ARRAY 4
A-302 DEMOLITION AND LANDSCAPING - NORTH PARKING
E-103 SLD AND EQUIPMENT SCHEDULE - ARRAY 4
E-203 DC 3-LINE DIAGRAMS AND ELECTRICAL SCHEDULES - ARRAY 4
E-303 AC 3-LINE DIAGRAMS AND ELECTRICAL SCHEDULES - ARRAY 4
E-403 DC AND AC RUN SCHEDULES - ARRAY 4
E-423 SOURCE CIRCUIT MAP - ARRAY 4
S-203 EQUIPMENT PAD LAYOUT - ARRAY 4
E-606 DATA ACQUISITION AND MONITORING - SLD ARRAY 4
E-607 DAS EQUIPMENT WIRING SCHEDULE - ARRAY 4
L-102 NEW LIGHTING PLAN AND SCHEDULE -ARRAY 4
L-106 PHOTOMETRIC MARK POINTS - NORTH CARPORTS
E-702 VA EXTRAS - 120V/240V CIRCUITS IN CARPORTS - ARRAY 4
E-706 VA EXTRAS - SPARE CONDUITS IN CARPORTS - ARRAY 4
E-805 LABELS AND PLACARDS - ARRAY 4
E-806 LABELS AND PLACARDS - ARRAY 4
ARRAY 5
A-206 PV LAYOUT AND INTERCONNECTION - ARRAY 5
A-303 DEMOLITION AND LANDSCAPING - NORTHEAST PARKING
E-104 SLD AND EQUIPMENT SCHEDULE - ARRAY 5
E-204 DC 3-LINE DIAGRAMS AND ELECTRICAL SCHEDULES - ARRAY 5
E-304 AC 3-LINE DIAGRAMS AND ELECTRICAL SCHEDULES - ARRAY 5
E-404 DC AND AC RUN SCHEDULES - ARRAY 5
E-405 DC AND AC RUN SCHEDULES - ARRAY 5 (EQUIPMENT PAD AND POCC RUNS)
E-424 SOURCE CIRCUIT MAP - ARRAY 5
S-204 EQUIPMENT PAD LAYOUT - ARRAY 5
E-608 DATA ACQUISITION AND MONITORING - SLD ARRAY 5
E-609 DAS EQUIPMENT WIRING SCHEDULE - ARRAY 5
L-103 NEW LIGHTING PLAN AND SCHEDULE -ARRAY 5
L-106 PHOTOMETRIC MARK POINTS - NORTH CARPORTS
E-703 VA EXTRAS - 120V/240V CIRCUITS IN CARPORTS - ARRAY 5
E-707 VA EXTRAS - SPARE CONDUITS IN CARPORTS - ARRAY 5
E-807 LABELS AND PLACARDS - ARRAY 5
E-808 LABELS AND PLACARDS - ARRAY 5
ARRAYS 7&8
A-207 PV LAYOUT AND INTERCONNECTION - ARRAYS 7 AND 8
A-306 DEMOLITION AND LANDSCAPING - SOUTHWEST PARKING
E-105 SLD AND EQUIPMENT SCHEDULE - ARRAYS 7 AND 8
E-205 DC 3-LINE DIAGRAMS AND ELECTRICAL SCHEDULES - ARRAYS 7 AND 8
E-305 AC 3-LINE DIAGRAMS AND ELECTRICAL SCHEDULES - ARRAYS 7 AND 8
E-406 DC AND AC RUN SCHEDULES - ARRAYS 7&8
E-425 SOURCE CIRCUIT MAP - ARRAY 7&8
S-205 EQUIPMENT PAD LAYOUT - ARRAY 7&8
E-610 DATA ACQUISITION AND MONITORING - SLD ARRAYS 7&8
E-611 DAS EQUIPMENT WIRING SCHEDULE - ARRAYS 7&8
L-104 NEW LIGHTING PLAN AND SCHEDULE -ARRAYS 7&8
L-107 PHOTOMETRIC MARK POINTS - SOUTH CARPORTS
E-704 VA EXTRAS - 120V/240V CIRCUITS IN CARPORTS - ARRAY 7&8
E-708 VA EXTRAS - SPARE CONDUITS IN CARPORTS - ARRAY 7&8
E-809 LABELS AND PLACARDS - ARRAYS 7&8
E-810 LABELS AND PLACARDS - ARRAYS 7&8
DETAILS
E-901 ELECTRICAL DETAILS
E-902 ELECTRICAL DETAILS
E-903 ELECTRICAL DETAILS
SL2.0 SUNLINK SECTIONS AND DETAILS
A-901 NEW SUNLINK STANDOFFS ATTACHMENT TO MAIN BUILDING STRUCTURE
A-902 NEW EQUIPMENT PAD ATTACHMENT TO MAIN BUILDING STRUCTURE
A-903 NEW SUNLINK STANDOFFS ATTACHMENT TO NURSING HOME STRUCTURE
A-904 NEW EQUIPMENT PAD ATTACHMENT TO NURSING HOME STRUCTURE
A-905 NOTES TO NEW ATTACHMENTS TO EXISTING STRUCTURES
A-906 NEW EQUIPMENT ATTACHMENT TO PARKING GARAGE AND GROUND
MOUNTED INSTALLATIONS.
A-907 NOTES TO NEW EQUIPMENT ATTACHMENT TO PARKING GARAGE AND
GROUND MOUNTED INSTALLATIONS.
A-908 WATERPROOFING AND FLASHING FOR NEW STANDOFFS ON EXISTING
STRUCTURES.
A-909 WATERPROOFING AND FLASHING FOR NEW EQUIPMENT PADS ON
EXISTING STRUCTURES.
A-910 WATERPROOFING AND FLASHING FOR NEW CONDUIT PENETRATIONS ON
EXISTING STRUCTURES.
A-911 MECHANICAL INSTALLATION OF CONDUITS AND EQUIPMENT.
A-912 PROSOLAR CLAMP ATTACHMENT TO PURLIN WITH TEK SCREWS
CODE REFERENCE:
1. ALL MATERIALS AND EQUIPMENT SHALL BE
INSTALLED PER MANUFACTURER'S INSTRUCTIONS,
AND IN ACCORDANCE WITH THE REQUIREMENTS OF
THE 2008 NATIONAL ELECTRICAL CODE, DEPT. OF VA
SPECIFICATIONS AND LOCAL CODES.
2. STRUCTURES SHALL BE INSTALLED PER 2010
CALIFORNIA BUILDING CODE, ACI 318.
INDEX SHEET
G-101 INDEX
G-101 INDEX
ARCH D (36"X24")ARCH D (36"X24")
B
A
C
D
E
F
G
H
I
J
K
L
THIS DRAWING IS THE CONFIDENTIAL
PROPERTY OF SUNWIZE TECHNOLOGIES
WWW.SUNWIZE.COM
SHEET NO:
B
A
C
D
E
F
G
H
I
J
K
L
21 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PAPER SIZE:
DRAWING NUMBER:
PROJECT NUMBER:
SHEET TITLE:
PROJECT / CUSTOMER INFORMATION:
PROJECT NAME:
LOMA LINDA VA MEDICAL CENTER
PHOTOVOLTAIC SYSTEM
LOMA LINDA VA MEDICAL CENTER
11201 BENTON STREET,
LOMA LINDA, CA 92357
503-6032
REV BY CHK
50% DESIGNA AG
REV. C
BH 2011.12.20
DESCRIPTION DATE
100% DESIGNB AG BH 2012.03.30
100% DESIGN FOR CONSTRUCTIONC AG CC 2012.05.10
SHEET INDEX
ARCH D (36"X24")
SYMBOLS
Ø: ELECTRICAL PHASE
AC: ALTERNATING CURRENT
AWG: AMERICAN WIRE GAUGE
AHJ: AUTHORITY HAVING JURISDICTION
APPOX: APPROXIMATE
AIC: AMPERES INTERRUPTING CAPACITY
BAS: BUILDING AUTOMATION SYSTEM
BRK: BREAKER
C/L: CENTER LINE
CB COMBINER BOX
CB/DCD: COMBINER BOX / DC DISCONNECT
CEC: CALIFORNIA ENERGY COMMISION
COTM: CONTRACTING OFFICER'S TECHNICAL MONITOR
COTR: CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE
DAS: DATA ACQUISITION SYSTEM
DC: DIRECT CURRENT
DCD: DC DISCONNECT
DC DISCO: DC DISCONNECT
DI: DROP INLET
DISC: DISCONNECT
(E): EXISTING
EL: ELEVATION
EMCS: ENERGY MONITORING AND CONTROL SYSTEM.
EQ: EQUAL
GE: GROUNDING ELECTRODE
GEC: GROUNDING ELECTRODE CONDUCTOR
EGC: EQUIPMENT GROUND CONDUCTOR
ID: INSIDE DIAMETER
Imp, IMP: MAXIMUM OPERATING CURRENT Is, ISC: SHORT CIRCUIT CURRENT
JB: JUNCTION BOX
MCC: MOTOR CONTROL CENTER
MFR: MANUFACTURER
MIN: MINIMUM
MISC: MISCELLANEOUS
(N): NEW
NEC: NATIONAL ELECTRICAL CODE
NEG: NEGATIVE
NEMA: NATIONAL ELECTRIC MANUFACTURERS ASSOCIATION
OAE: OR APPROVED EQUAL
OC: ON CENTER
OD: OUTSIDE DIAMETER
POCC: POINT OF COMMON COUPLING
POS: POSITIVE
PTC: PERFORMANCE TEST CONDITIONS
PV: PHOTOVOLTAIC
PYR: PYRANOMETER
QTY: QUANTITY
SD: STORM DRAIN
SF: SQUARE FOOT/FEET
SIM: SIMILAR
SS: STAINLESS STEEL
STC: STANDARD TEST CONDITIONS
TBD: TO BE DETERMINED
TOF: TOP OF FOOTING
TYP: TYPICAL
UON: UNLESS OTHERWISE NOTED
VIF: VERIFY IN FIELD
Vmp, VMP: MAXIMUM OPERATING VOLTAGE Voc, VOC: OPEN CIRCUIT VOLTAGE
XFMR, X-FMR: TRANSFORMER
ABBREVIATIONS
NOTES AND SYMBOLS
G-102
G-102
PV MODULE
FUSE
DISCONNECT SWITCH
CURRENT TRANSFORMER
CIRCUIT BREAKER
TRANSFORMER
ELECTRICAL CONNECTION
GROUNDING ELECTRODE
SURGE ARRESTER
CURRENT CARRYING CONDUCTOR
GROUND CONDUCTOR
DATA CONDUCTOR
CONTACTOR
SHEET WHERE
SECTION IS LOCATED
DETAIL ID NUMBER
DETAIL ID NUMBER
SECTION
ELEVATION
DETAIL SHEET WHERE
DETAIL IS LOCATED
DETAIL ID NUMBERDETAIL
(ENLARGED
PLAN)
SHEET WHERE
DETAIL IS LOCATED
AREA TO
BE ENLARGED
KEYED NOTE
REVISIONS
GROUND TERMINAL
STRING
INTERCONNECTION
STRING ID
NUMBER
SOURCE
CIRCUIT
STRING
ID NUMBER
COMBINER BOX
DC DISCONNECTDC TO AC INVERTER
AC NEUTRAL BAR
NEUTRAL CONDUCTOR
DC NEGATIVE BUS
JUNCTION BOX
DAS METER
W/ CURRENT TRANSFORMER
AND VOLTAGE TAP
CHRISTY BOX
X
X-XX
X
X-XX
X
X-XX
X
X-XX
X
XXX
XXX
CB-0X
DCD-X
M
AC
DC
NEG
N
X
G
JB
COMBINER BOX
W/ DISCONNECT
CBD-X
ARCH D (36"X24")ARCH D (36"X24")
B
A
C
D
E
F
G
H
I
J
K
L
THIS DRAWING IS THE CONFIDENTIAL
PROPERTY OF SUNWIZE TECHNOLOGIES
WWW.SUNWIZE.COM
SHEET NO:
B
A
C
D
E
F
G
H
I
J
K
L
21 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PAPER SIZE:
DRAWING NUMBER:
PROJECT NUMBER:
SHEET TITLE:
PROJECT / CUSTOMER INFORMATION:
PROJECT NAME:
LOMA LINDA VA MEDICAL CENTER
PHOTOVOLTAIC SYSTEM
LOMA LINDA VA MEDICAL CENTER
11201 BENTON STREET,
LOMA LINDA, CA 92357
503-6032
REV BY CHK
50% DESIGNA AG
REV. C
BH 2011.12.20
DESCRIPTION DATE
100% DESIGNB AG BH 2012.03.30
100% DESIGN FOR CONSTRUCTIONC AG CC 2012.05.10
GENERAL NOTES:
1. CONTRACTOR TO OBTAIN COTR'S NOTICE TO PROCEED BEFORE
COMMENCING WORK.
2. ALL WORK SHALL BE IN COMPLETE COMPLIANCE WITH THE
2008 EDITION OF THE NATIONAL ELECTRIC CODE, THE 2010
CALIFORNIA BUILDING CODE, AND ALL REGULATIONS, LAWS,
SAFETY ORDERS, ORDINANCES, OR AUTHORITIES HAVING
JURISDICTION. IN THE EVENT OF CONFLICT, THE MOST
RESTRICTIVE CODE SHALL PREVAIL.
3. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND LISTED
BY A RECOGNIZED ELECTRICAL TESTING LABORATORY OR
APPROVED BY THE AHJ. CUSTOM MADE EQUIPMENT SHALL
HAVE COMPLETE TEST DATA SUBMITTED BY THE
MANUFACTURER ATTESTING TO ITS SAFETY. ALL THE
MATERIALS MUST COMPLY WITH BUY AMERICAN AND TRADE
AGREEMENTS CLAUSES OF CONTRACT.
4. ALL EQUIPMENT TO BE INSTALLED PER MANUFACTURER'S
INSTRUCTIONS. CONTRACTOR TO UNDERSTAND ALL THE
EQUIPMENT USER MANUALS.
5. ANY AMBIGUITIES OR CONFLICTS SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER. THE CONTRACTOR SHALL
NOTIFY ELECTRICAL ENGINEER TO VALIDATE THE WIRE AND
CONDUIT SIZE WHEN WIRING LENGTHS EXCEED THE ONES
SPECIFIED IN THIS PLANS SET. THE CONTRACTOR ASSUMES
ALL LIABILITY IF THIS PLANS SET IS NOT FOLLOW WITHOUT
THE ENGINEER’S WRITTEN AUTHORIZATION.
6. THE CONTRACTOR SHALL FOLLOW OSHA AND SUNWIZE’S
SAFETY PLAN REQUIREMENTS.
7. THE CONTRACTOR SHALL PERFORM CONTINUITY AND
INSULATION TEST TO ALL MODULE STRINGS AND ALL
CONDUCTORS. INSULATION TEST TO PASS 5 MEGA OHMS
RESISTANCE TO GROUND AT 1,000VDC. SUNWIZE SHALL
PROVIDE DETAILED PROCEDURE FOR THE INSULATION TESTS.
8. APPLY COLD GALVANIZING COMPOUND FOR CORROSION
CONTROL AFTER CUTTING GALVANIZED STEEL.
9. ROOF MEMBRANE CUTTING AND WATERPROOFING BY A
CERTIFIED ROOFING CONTRACTOR ONLY.
10. OPERATION MANUAL WILL BE SUBMITTED TO CUSTOMER UPON
COMPLETION OF WORK.
ELECTRICAL NOTES
11. ALL SPECIFIED WIRING IS BASED ON THE USE OF COPPER
UNLESS OTHERWISE SPECIFIED.
12. PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL
EQUIPMENT SHALL BE PERMITTED AS PER NEC 2008 110.26F(1).
13. COMBINER BOX FUSES SHALL BE PROVIDED WITH REJECTION
TYPE FUSE HOLDERS.
14. PV ARRAYS SHALL BE PROVIDED WITH DC GROUND-FAULT
PROTECTION. INVERTERS USED ARE EQUIPPED WITH
INTEGRATED GFDI DEVICE. PV SYSTEM GROUNDING TO COMPLY
WITH NEC 690.5, 690.45 AND 690.47.
15. SHORT CIRCUIT RATINGS OF THE ELECTRICAL COMPONENTS
SHALL MEET OR EXCEED THE AVAILABLE FAULT CURRENT
CALCULATED AT THAT COMPONENT.
16. OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED MIN.
17. EMT CONDUIT SHALL BE ACCEPTABLE TO BE RUN ONLY INSIDE
INTERSTITIAL SPACES AND UNDER CARPORTS FOR LIGHTING,
24V AND DATA. FOR SOLAR DC AND AC CIRCUITS ONLY IMC
SHALL BE USED.
18. ALL EXTERIOR ELECTRICAL CONDUIT FITTINGS SHALL BE
RAINTIGHT TYPE. USE MYERS HUBS WHEN CONNECTIONS ARE
MADE ON THE TOP SIDE OF ENCLOSURES.
19. ALL CONNECTIONS TO EXISTING MAIN SWITCHGEAR REQUIRE
CERTIFICATION AND APPROVAL. WHERE HOT-TAPS AND/OR
BUS-TAPS ARE REQUIRED, FABRICATION AND CERTIFICATION
SHALL BE FURNISHED BY A CONTRACTOR AND APPROVED BY
THE APPLICABLE UTILITY.
20. DC OVERCURRENT EQUIPMENT SHALL BE RATED FOR DC
CURRENT AS PER 690.9(D) AT MIN VOLTAGE OF 600 VDC.
21. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER
TRADES AT THE SITE.
22. BEFORE MAKING ANY WALL PENETRATIONS LOCATE AND AVOID
EXISTING EQUIPMENT, UTILITIES, AND STRUCTURAL
COMPONENTS. PERFORM CORING, SAW-CUTTING, PATCHING,
AND REFINISHING OF EXISTING WALLS AND SURFACES
WHEREVER IT IS NECESSARY TO PENETRATE. OPENINGS
SHALL BE SEALED IN AN APPROVED METHOD TO MATCH THE
FIRE AND WEATHER RATING OF THE PARTICULAR WALL, FLOOR
OR CEILING AS PER NFPA 101.
23. NO CONDUIT SHALL LEFT EXPOSED ON WALLS. PERMANENT
COVER SHALL BE PROVIDED IN COMPLIANCE WITH BUILDING
AND ELECTRICAL CODES. MATERIALS AND TERMINATION SHALL
MATCH WITH EXISTING FINISHED WALLS.
24. INSTALL LABELS ACCORDING TO NEC 690.17, 690.53, 690.64(B),
LOCAL AUTHORITIES REQUIREMENTS AND THE SYSTEM LABELS
SHEETS ON THIS SET OF DRAWINGS.
25. CONDUIT RUNS SHALL BE PROVIDED WITH SUFFICIENT
WEATHERPROOF PULL BOXES OR JUNCTION BOXES PER
APPROPRIATE NEC REQUIREMENTS.
26. METALLIC CONDUIT TO BE BONDED TO METALLIC ENCLOSURES
WITH BONDING BUSHINGS WHERE APPLICABLE.
27. CONDUCTORS TO BE PERMANENT LABELED WITH CIRCUIT
NUMBER / POLARITY NEAR TERMINATIONS.
28. USE PERMANENT MEANS TO IDENTIFY CONDUCTORS PER NEC
200.6 AND 200.7. GROUNDED CONDUCTORS: WHITE.
UNGROUNDED DC CONDUCTORS: BLACK. EQUIPMENT
GROUNDING: GREEN OR BARE. 480Y/277V: BROWN, ORANGE,
YELLOW. 208Y/120V: BLACK, RED, BLUE.
29. ALL PV SYSTEM COMPONENTS SHALL BE LISTED AND COMPLY
WITH UL 1741. AN INVERTER OR AN AC MODULE IN AN
INTERACTIVE SOLAR PHOTOVOLTAIC SYSTEM SHALL
AUTOMATICALLY DE-ENERGIZE ITS OUTPUT TO THE CONNECTED
ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK UPON
LOSS OF VOLTAGE IN THAT SYSTEM AND SHALL REMAIN IN
THAT STATE UNTIL THE ELECTRICAL PRODUCTION AND
DISTRIBUTION NETWORK VOLTAGE HAS BEEN RESTORED. 690.61.
30. JUNCTION, PULL AND OUTLET BOXES LOCATED BEHIND
MODULES OR PANELS SHALL BE INSTALLED SO THAT THE
WIRING CONTAINED IN THEM CAN BE RENDERED ACCESSIBLE
DIRECTLY OR BY DISPLACEMENT OF A MODULE(S) OR PANEL(S)
SECURED BY REMOVABLE FASTENERS AND CONNECTED BY A
FLEXIBLE WIRING SYSTEM. (NEC 690.34)
31. CONTRACTOR SHALL COORDINATE ALL INSPECTIONS, TESTING,
COMMISSIONING AND ACCEPTANCE WITH THE CLIENT, UTILITY
CO. AND CITY INSPECTORS AS NEEDED.
32. ALL INTERRUPTION OF ELECTRICAL POWER SHALL BE KEPT TO
A MINIMUM. HOWEVER, WHEN AN INTERRUPTION IS NECESSARY,
THE SHUTDOWN MUST BE COORDINATED WITH THE PROJECT
MANAGER, THE SITE SUPERINTENDENT, AND THE COTR. WORK
IN THE EXISTING SWITCHBOARDS OR PANELBOARDS SHALL BE
COORDINATED WITH THE COTR PRIOR TO REMOVING ACCESS
PANELS.
33. ATTENTION IS CALLED TO THE FACT THAT THERE ARE
EXISTING UNDERGROUND UTILITY LINES. THE CONTRACTOR IS
RESPONSIBLE FOR NOTIFICATION AND COORDINATION WITH ALL
PROPERTY OWNERS, UTILITIES UNDERGROUND MARKING
AGENCIES AND DIG-ALERT AND APPROPRIATE COMPANIES. THE
CONTRACTOR SHALL ALWAYS USE EXTREME CAUTION WHEN
TRENCHING FOR HIS WORK.
34. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER
AND APPROVED REPAIR OF ANY AND ALL DAMAGES CAUSED
DURING THE COURSE OF HIS WORK.
35. ALL FINAL CONNECTIONS TO OWNER-FURNISHED EQUIPMENT
SHALL BE MADE BY THE CONTRACTOR.
LIGTH POLE IN PARKING AREAS
LIGHT POLE IN PARKING GARAGE
SPARE
120V RUN FOR VA EXTRA CIRCUITS
240V RUN FOR VA EXTRA CIRCUITS
SPARE CONDUIT RUN FOR VA FUTURE CIRCUITS
SB-8
SB-7
SB-6
SB-4
SB-2
SB-5
SB-3
SB-1
BEHAVIORAL
HEALTH (FUTURE)
13 FEET HIGH
CANCER
CENTER
(FUTURE)
DR
AIN
MAIN STORM DRAIN
LINE. 8' DEEP
L L
L
L
L L
L
L
L
L L L
L
L
L
L L L L L
L
L
L
L
L
S
S
S
S
S
E E E E E
E
E
E E
E
ARCH D (36"X24")
EXISTING SITE AND UTILITIES PLAN
A-101
A-101
ARCH D (36"X24")ARCH D (36"X24")
B
A
C
D
E
F
G
H
I
J
K
L
THIS DRAWING IS THE CONFIDENTIAL
PROPERTY OF SUNWIZE TECHNOLOGIES
WWW.SUNWIZE.COM
SHEET NO:
B
A
C
D
E
F
G
H
I
J
K
L
21 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PAPER SIZE:
DRAWING NUMBER:
PROJECT NUMBER:
SHEET TITLE:
PROJECT / CUSTOMER INFORMATION:
PROJECT NAME:
LOMA LINDA VA MEDICAL CENTER
PHOTOVOLTAIC SYSTEM
LOMA LINDA VA MEDICAL CENTER
11201 BENTON STREET,
LOMA LINDA, CA 92357
503-6032
REV BY CHK
50% DESIGNA AG
REV. C
BH 2011.12.20
DESCRIPTION DATE
100% DESIGNB AG BH 2012.03.30
100% DESIGN FOR CONSTRUCTIONC AG CC 2012.05.10
N
SCALE 1" = 65'
LEGEND
EXISTING PV
SERVICE BAY (POINT OF
INTERCONNECTION)
STORM DRAIN LINE. USUALLY
2.5 TO 3 FEET DEEP UNLESS
OTHERWISE SPECIFIED
STREET DRAINAGE
SEWAGE LINE
LIGHTING LINE
POWER LINE (SCE)
ELECT. UTILITY VAULT
SB-01
DRAIN
S
L
E
V
SB-6
SB-4
SB-2
SB-5
SB-3
SB-1
ARRAY 8
ARRAY 5
ARRAY 4
8B
7A
8A
7B
7C
BEHAVIORAL
HEALTH (FUTURE)
41" (H)
28"(H)
5in.(H)
13 FEET HIGH
W
ALKING MAT
ARRAY 1
4 FLOORS PLUS BASEMENT
AC RUN DOWN: 16FT*5=80FT
ONE FLOOR RUN
UP:16FT
RUN DOWN TO
BASEMENT : 16FT
CANCER
CENTER
(FUTURE)
4A
4C
4D
4E
4F 4B
ARRAY 7
WALL
GLASS WALL
(E) ACCESS DOOR FROM
MAIN BLDG TO NURSING
HOME ROOF
5A
5B
5C
5D
5E
5F
5G5H
5J
5K
5L 5M
RUN INSIDE INTERSTITIAL
SPACE TO REC A1
RUN INSIDE INTERSTITIAL
SPACE TO REC A1
STUB UPS FROM
INTERSTITIAL SPACE
1 FLOOR + BASEMENT RUN
DOWN: 16FT*2=32FT
1A
1B
3A
3B
3C
INVERTER INTERCONNECTION SCHEDULE
SERVICE BAY SPECS SUNWIZE INTERCONNECTION PROPOSAL
SERVICE
BAY
BUSBAR
RATING, A
MAIN BREAKER
RATINGS
SOLAR
ARRAY
ARRAY MAX.
CURRENT, A
SPB-100 BREAKER
FRAME RATINGS,
A
SPB-100 BREAKER
TRIP RATINGS
(LTPU), A
2 2500 SPB-100
2500AF / 2250AT 4 750 800 760
3 2500 DS-632
3200AF / 2400AT 1 152 400 200
4 2500 DS-632
3200AF / 2400AT 3&9 579 800 640
6 2500 DS-632
3200AF / 2400AT 5 500 800 560
7 2500 SPB-100
2500AF / 2250AT 7&8 318 400 350
ARCH D (36"X24")
PV LAYOUT AND INTERCONNECTION
PLAN
A-201
A-201
ARCH D (36"X24")ARCH D (36"X24")
B
A
C
D
E
F
G
H
I
J
K
L
THIS DRAWING IS THE CONFIDENTIAL
PROPERTY OF SUNWIZE TECHNOLOGIES
WWW.SUNWIZE.COM
SHEET NO:
B
A
C
D
E
F
G
H
I
J
K
L
21 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PAPER SIZE:
DRAWING NUMBER:
PROJECT NUMBER:
SHEET TITLE:
PROJECT / CUSTOMER INFORMATION:
PROJECT NAME:
LOMA LINDA VA MEDICAL CENTER
PHOTOVOLTAIC SYSTEM
LOMA LINDA VA MEDICAL CENTER
11201 BENTON STREET,
LOMA LINDA, CA 92357
503-6032
REV BY CHK
50% DESIGNA AG
REV. C
BH 2011.12.20
DESCRIPTION DATE
100% DESIGNB AG BH 2012.03.30
100% DESIGN FOR CONSTRUCTIONC AG CC 2012.05.10
N
SCALE 1" = 70'
LEGEND
PV MODULE
OMITTED MODULE IN SUNLINK
ROOFTOP ARRAYS
BLANK MODULE IN CARPORT
ARRAYS
EXISTING PV (PHASE I)
SERVICE BAY (POCC)SB-#
SYSTEM SUMMARY
SITE ADDRESS 11201 BENTON ST., LOMA LINDA, CA 92357 PV MODULE COUNT 6,888
SITE COORDINATES LAT 34.050216°, LON -117.250537° SOURCE CIRCUIT COUNT 492
SITE RECORD LOW TEMP, °C / °F -7 / 19.4 BLANK MODULE COUNT 69
SITE AVERAGE LOW TEMP, °C / °F 4 / 39.2 4-MODULE PANEL COUNT 1,739
SITE RECORD HIGH TEMP, °C / °F 48 / 118.4 POWER, MWDC STC 1.70
SITE AVERAGE HIGH TEMP, °C / °F 36 / 96.8 POWER, MWDC PTC 1.53
SITE MAX. CELL TEMP, °C / °F 61 / 141.8 AC POWER, MW CEC 1.49
Note: Site temperatures from www.weather.com
SAMSUNG LCP247SM-08 PV MODULE
POWER DC STC, W 247.0
POWER DC PTC, W 222.8
MAX. POWER TRACKING VOLTAGE, V 30.4
MAX. POWER TRACKING CURRENT, A 8.14
OPEN CIRCUIT VOLTAGE, V 37.6
SHORT CIRCUIT CURRENT, A 8.62
MODULE QUANTITY 6,888
INVERTER TYPE OUTPUT
POWER, kW
OUTPUT
VOLTAGE, V EFFICIENCY, % QUANTITY COMMON
COUPLING TYPE
AEI SOLARON 500kW/480V 500
480/3P
97.50 1
NEC 690.64(B)
AEI SOLARON 333kW/480V 333 97.50 1
AEI SOLARON 250kW/480V 250 97.50 1
SATCON PVS 135kW/480V 135 96.00 2
SATCON PVS 100kW/480V 100 96.00 1
SATCON PVS 75kW/480V 75 96.00 1
SUPPORTING STRUCTURE SUNLINK SUNLINK SUNLINK SUNLINK SUNLINK CARPORT CARPORT CARPORT CARPORT CARPORT ARRAY / SUB-ARRAY 1 / 1A 1 / 1B 3 / 3A 3 / 3B 3 / 3C 4 / 4A 4 / 4B 4 / 4C 4 / 4D 4 / 4E
AZIMUTH 180 180 180 180 180 180 165 180 180 180
TILT 10 10 10 10 10 5 5 5 5 5
PV MODULE COUNT 168 280 224 224 238 252 84 574 574 448
SOURCE CIRCUIT COUNT 12 20 16 16 17 18 6 41 41 32
BLANK MODULE COUNT 4 6 12 2 3 0 0 2 2 8
4-MODULE PANEL COUNT 43 72 59 57 60 63 21 144 144 114
POWER, WDC STC 41,496 69,160 55,328 55,328 58,786 62,244 20,748 141,778 141,778 110,656 POWER, WDC PTC 37,430 62,384 49,907 49,907 53,026 56,146 18,715 127,887 127,887 99,814 AC POWER, W CEC 35,933 59,889 47,911 47,911 50,905 54,742 18,247 124,690 124,690 97,319
SUPPORTING STRUCTURE CARPORT CARPORT CARPORT CARPORT CARPORT CARPORT CARPORT CARPORT CARPORT CARPORT ARRAY / SUB-ARRAY 4 / 4F 5 / 5A 5 / 5B 5 / 5C 5 / 5D 5 / 5E 5 / 5F 5 / 5G 5 / 5H 5 / 5J
AZIMUTH 180 198 210 222 234 246 259 270 270 250
TILT 5 5 5 5 5 5 5 5 5 5
PV MODULE COUNT 420 84 84 84 84 84 84 322 336 98
SOURCE CIRCUIT COUNT 30 6 6 6 6 6 6 23 24 7
BLANK MODULE COUNT 0 0 0 0 0 0 0 2 0 10
4-MODULE PANEL COUNT 105 21 21 21 21 21 21 81 84 27
POWER, kWDC STC 103,740 20,748 20,748 20,748 20,748 20,748 20,748 79,534 82,992 24,206 POWER, kWDC PTC 93,576 18,715 18,715 18,715 18,715 18,715 18,715 71,742 74,861 21,834 AC POWER, kW CEC 91,237 18,247 18,247 18,247 18,247 18,247 18,247 69,948 72,989 21,289
SUPPORTING STRUCTURE CARPORT CARPORT CARPORT CARPORT CARPORT CARPORT CARPORT CARPORT PARKING
GARAGE
ARRAY / SUB-ARRAY 5 / 5K 5 / 5L 5 / 5M 7 / 7A 7 / 7B 7 / 7C 8 / 8A 8 / 8B 9 / 9
AZIMUTH 230 210 190 180 180 180 270 270 180
TILT 5 5 5 5 5 5 5 5 7
PV MODULE COUNT 56 56 84 168 196 238 126 210 1008
SOURCE CIRCUIT COUNT 4 4 6 12 14 17 9 15 72
BLANK MODULE COUNT 0 0 0 0 8 2 2 6 0
4-MODULE PANEL COUNT 14 14 21 42 51 60 32 54 252
POWER, kWDC STC 13,832 13,832 20,748 41,496 48,412 58,786 31,122 51,870 248,976 POWER, kWDC PTC 12,477 12,477 18,715 37,430 43,669 53,026 28,073 46,788 224,582 AC POWER, kW CEC 12,165 12,165 17,967 35,933 41,922 50,905 26,950 45,618 218,968
ARCH D (36"X24")
PV LAYOUT AND INTERCONNECTION
PLAN
SUMMARY
A-202
A-202
ARCH D (36"X24")ARCH D (36"X24")
B
A
C
D
E
F
G
H
I
J
K
L
THIS DRAWING IS THE CONFIDENTIAL
PROPERTY OF SUNWIZE TECHNOLOGIES
WWW.SUNWIZE.COM
SHEET NO:
B
A
C
D
E
F
G
H
I
J
K
L
21 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PAPER SIZE:
DRAWING NUMBER:
PROJECT NUMBER:
SHEET TITLE:
PROJECT / CUSTOMER INFORMATION:
PROJECT NAME:
LOMA LINDA VA MEDICAL CENTER
PHOTOVOLTAIC SYSTEM
LOMA LINDA VA MEDICAL CENTER
11201 BENTON STREET,
LOMA LINDA, CA 92357
503-6032
REV BY CHK
50% DESIGNA AG
REV. C
BH 2011.12.20
DESCRIPTION DATE
100% DESIGNB AG BH 2012.03.30
SB-6
SB-4
SB-2
SB-5
SB-3
SB-1
ARRAY 8
ARRAY 5
ARRAY 4
8B
7A
8A
7B
7C
BEHAVIORAL
HEALTH (FUTURE) ST
AG
IN
G
AR
EA
41" (H)
28"(H)
5in.(H)
13 FEET HIGH
W
ALKING MAT
ARRAY 1
REMOVE
REMOVE
REMOVE
REMOVE
20FT40FT
50FT
50FT
50FT40FT
30FT
REMOVE
PINETREE
REMOVE
PINETREE
GROUP OF SIX TREES TO BE
REMOVED AND REPLACED
(E) "LOWBOY" SINGLE
LIGHT POLE
CANCER
CENTER
(FUTURE)
4A
4C
4D
4E
4F 4B
ARRAY 7
REMOVE
AND
REPLACE
5A 5B
5C
5D
5E
5F
5G5H
5J
5K
5L 5M
31'-1"
31'-3"
30'-412"
30'-612"
30'-11"
30'-10"
28'-8"
41'-712"
29'-712"
1A
1B
3A
3B
3C L
L
L
L
L L
L
L
L
L L L
L
L
L L L L
L
L
L
L
DEMOLITION AND LANDSCAPING
PLAN
A-301
A-301
ARCH D (36"X24")ARCH D (36"X24")
B
A
C
D
E
F
G
H
I
J
K
L
THIS DRAWING IS THE CONFIDENTIAL
PROPERTY OF SUNWIZE TECHNOLOGIES
WWW.SUNWIZE.COM
SHEET NO:
B
A
C
D
E
F
G
H
I
J
K
L
21 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PAPER SIZE:
DRAWING NUMBER:
PROJECT NUMBER:
SHEET TITLE:
PROJECT / CUSTOMER INFORMATION:
PROJECT NAME:
LOMA LINDA VA MEDICAL CENTER
PHOTOVOLTAIC SYSTEM
LOMA LINDA VA MEDICAL CENTER
11201 BENTON STREET,
LOMA LINDA, CA 92357
503-6032
REV BY CHK
50% DESIGNA AG
REV. C
BH 2011.12.20
DESCRIPTION DATE
100% DESIGNB AG BH 2012.03.30
100% DESIGN FOR CONSTRUCTIONC AG CC 2012.05.10
N
SCALE 1" = 70'
NOTES
THE EXISTING EQUIPMENT CURRENTLY
INSTALLED ON THE LIGHT POLES TO BE
REMOVED, WILL BE RELOCATED AS
COORDINATED BETWEEN THE COTR AND
THE CONTRACTOR
20FT
REMOVE
LEGEND
TREES TO BE REMOVED
TREES TO BE TRIMMED TO
INDICATED HEIGHT.
TREES TO BE REPLACED WITH LOW
MATURE HEIGHT SPECIES
LIGHT POLE TO BE REMOVED FROM
PARKING AREAS.
EXISTING CCTV CAMERAS.
EXISTING EMERGENCY PHONES
EXISTING RADIO FREQUENCY
IDENTIFICATION DEVICE
LIGHTING POLE TO BE REMOVED
FROM PARKING GARAGE.
LIGHTING LINE
CCTV
PHONE
RFID
REMOVE
AND
REPLACE
L
General Notes:
1. These drawings show the required location of SunLink RMS components for this project. The layout is based on existing conditions information provided to SunLink by the customer and has not been verified by SunLink. Verify key dimensions and existing conditions in the field prior to beginning installation.
2. Obtain SunLink approval before modifying the layout shown, or relocating, omitting, or modifying any SunLink component. Install all SunLink components per the latest edition of the SunLink assembly instructions available at sunlink.com.
3. Any additional installation requirements, such as roofing protection, electrical components, waterproofing, and connector attachment, are not by SunLink. Refer to other project documents.
4. The installer is responsible for worker safety and for maintaining a safe worksite.
5. Shading is calculated by SunLink based on information provided by the customer. Shading is calculated for 2 hours before until 2 hours after solar noon on December 22 nd at project latitude.
6. For array weight and roof loading information, refer to the SunLink Structural Engineering Load Advisory provided for this project.
7. SunLink required clearances:
Clearance between components on different sub-arrays 6" Wire slack - between arrays 18" Wire slack - between panels 18" Wire slack - between arrays and other components 18"
Aerial View
Design Loads:
Design conforms to the California Building Code, 2010 Edition.
Code 3 sec Wind Speed (ASCE 7-05 Figure 6-1) V3S = mph Wind Importance Factor (ASCE 7-05 Table 6-1) IW = Wind Topographic Factor (ASCE 7-05 Section 6.5.7.2) Kzt = Wind Exposure (ASCE 7-05 Section 6.5.6.2)
Ground snow load (ASCE 7-05 Figure 7-1) Pg = psf
Seismic Importance Factor (ASCE 7-05, Table 11.5-1) I = Occupancy Category (ASCE 7-05, Table 1-1)
Site Location, Latitude Site Location, Longitude
Spectral Accel., Short Period, S S (ASCE 7-05, Section 11.4.1) SS = g Design Response, Short Period, S DS (ASCE 7-05, Section 11.4.4) SDS= g Site Classification (ASCE 7-05, Section 11.4.2 ) Seismic Design Category (ASCE 7, Table 11.6-1)
Seismic Analysis Procedure: Static lateral force procedure
Analysis/deisgn: Utilizes the SAP computer software.
1.15 1.0 B
1.5
IV
34° 02' 59.9" N 117° 15' 00.2" W
1.75 1.17 D D
SUNLINK ROOF MOUNT SYSTEM FOR PHOTOVOLTAIC SOLAR ARRAY AT
VA Loma Linda Medical Center Phase II 11201 Benton Street, Loma Linda, CA 92354
© 2011 SunLink Corporation The information on this drawing is proprietary to SunLink Corporation. It is provided on the condition that it is used only to facilitate the installation of the SunLink Photovoltaic Module Mounting System shown. Do not copy or distribute except for the use stated above.
SUNLINK CORPORATION
1010 B STREET, SUITE 400
SAN RAFAEL, CA 94901
(T) 415.925.9650 (F) 415.925.9636
WWW.SUNLINK.COM
su nw iz e us er v si on c :\d oc um en ts a nd s et tin gs
\s un w iz e us er \m y do cu m en ts
\0 p ro je ct s\ lo m a lin da ii \d es ig n\ pl an s fro m s ub co nt ra ct or s\ su nl in k\ su nl in k or ig in al s\
4-va lo m al in da -1
1-en g-r3
_2
2.
.0 3.
dw g
Sheet NumberIssue
No. of Modules Pwr. Output (DC)
Module
Tilt Angle
Location
Project
Customer
Quote Reference No.
Sales Order No.
Sheet Title
SUNLINK
ROOF MOUNT
SYSTEM
Sheets
DC String Length No. of StringsWattage kW
Issue DateDescription Drawn By Checked By
SOLAR PV ARRAY MOUNTING SYSTEMS
Samsung LPC247SM-08S
10° 247 1,134 14 81 280.1
COVER SHEET
1 of 7 R3 SL0
Array Information:
Assembly Number Tilt Angle Spacing Type Row Spacing in Planform Area sqft Interior Tilt Bracket Base Size End-Row Tilt Bracket Base Size Modification
Building Information:
Roof Height ft Roof Area sqft Maximum Roof Slope Roofing Contact Surface
Ballast Information:
Ballast Pan Type Type I Type II Type III Ballast Pan Size Pavers Per Ballast Pan Maximum Paver Size Required Min. Ballast Paver Weight lbs
Connector Information:
ZCA Assembly Number WRA Assembly Number
1001-181-01-10 Standard 54.6 28799 17.75" x 11.25" 15.5" x 11.25"
72 Max 217291 2.1%
PVC
0 0 0 0 0 0
600-65-S-Z13
Abbeviations:
CONN Connection
(E) Existiing Max. Maximum Min. Minimum No. Number U.O.N. Unless Otherwise Noted RMS SunLink Roof Mount System Req'd Required w/ With Rev Revision V.I.F Verify in field
TBC Tilt Bracket Cover TBB Tilt Bracket Base Typ. Typical Lat. Lateral Link FPA Flashable Post Anchor ZCA Z-Clamp Arm mph Miles per hour psf Pounds per square foot lbs Pounds DC Direct Current
Module
Tilt Bracket
Longitudinal Link
Lateral Link
Type I Ballast Pan
Type II Ballast Pan
Type III Ballast Pan
Field Drill
Z-Clamp Arm Connector (ZCA)
Wire Rope Assembly Connector(WRA)
Omitted Module
Layout Plan Symbol Legend:
RMS
COMPONENT
BY
SUB-ARRAY
Modules 2x1 Panels
3x1 Panels
4x1 Panels
Omitted Modules
Interior TBs
End-Row TBs
Long Links End-Row Long Links
Lateral Links
North Row Deflectors
End Deflectors Field Drills
Type I Ballast Pans
Type II Ballast Pans
Type III Ballast Pans
Pavers ZCA Conn. WRA Conn.
1 168 0 8 37 4 78 24 90 0 41 12 2 0 0 0 0 0 24 0
2 280 0 62 25 6 160 28 174 0 57 14 5 0 0 0 0 0 34 0
3 101 0 17 14 6 56 12 62 0 16 6 2 0 0 0 0 0 15 0
4 101 0 17 14 6 56 12 62 0 16 6 2 0 0 0 0 0 15 0
5 212 0 10 46 2 98 28 112 0 50 14 1 0 0 0 0 0 26 0
6 62 0 13 6 1 33 12 38 0 14 6 2 1 0 0 0 0 14 0
7 210 0 24 35 2 104 28 118 0 54 14 0 0 0 0 0 0 26 0
Total 1134 0 151 177 27 585 144 656 0 248 72 14 1 0 0 0 0 154 0
ZCA CONNECTOR, TYP.
0 Ft.
SCALE: " = 1'-0"
ARRAY LAYOUT PLAN
1/32
8 32 64
© 2011 SunLink Corporation The information on this drawing is proprietary to SunLink Corporation. It is provided on the condition that it is used only to facilitate the installation of the SunLink Photovoltaic Module Mounting System shown. Do not copy or distribute except for the use stated above.
SUNLINK CORPORATION
1010 B STREET, SUITE 400
SAN RAFAEL, CA 94901
(T) 415.925.9650 (F) 415.925.9636
WWW.SUNLINK.COM
su nw iz e si on oc um en ts a nd s et tin gs
\s un w iz e us er \m y do cu m en ts
\0 p ro je ct s\ lo m a lin da ii \d es ig n\ pl an s fro m s ub co nt ra ct or s\ su nl in k\ su nl in k or ig in al s\
4-va lo m al in da -1
1-en g-r3
_2
2.
.0 3.
dw g
Sheet NumberIssue
No. of Modules Pwr. Output (DC)
Module
Tilt Angle
Location
Project
Customer
Quote Reference No.
Sales Order No.
Sheet Title
SUNLINK
ROOF MOUNT
SYSTEM
Sheets
DC String Length No. of StringsWattage kW
Issue DateDescription Drawn By Checked By
SOLAR PV ARRAY MOUNTING SYSTEMS
Samsung LPC247SM-08S
10° 247 1,134 14 81 280.1
ARRAY LAYOUT PLAN
2 of 7 R3 SL1.0
NORTH ROW
DEFLECTORS
LATERAL LINKS,
REQUIRED AS SHOWN
12'-3" MIN. SUNLINK
REQUIRED SETBACK FROM
ALL 72' ROOF EDGES TO
ALL MODULES, V.I.F.
6'-0" SETBACK FROM
INSIDE OF PARAPET
WALLS TO ARRAY PER
CAL FIRE PV GUIDELINE
OMITTED MODULE, TYP.
END DEFLECTOR
SHADE AFFECTED
ZONE
(E) ROOF EQUIPMENT,
TYP.
FACE OF BUILDING
3'-1" MIN. SUNLINK
REQUIRED SETBACK FROM
ALL 18' ROOF EDGES TO
ALL MODULES, V.I.F.
6'-0" SETBACK FROM
INSIDE OF PARAPET
WALLS TO ARRAY PER
CAL FIRE PV GUIDELINE
SL1.1
SL1.2
SL1.3
SL1.4
ARRAY 8
ARRAY 5
ARRAY 4
8B
7A
8A
7B
7C
13 FEET HIGH
ARRAY 1
4A
4C
4D
4E
4F 4B
ARRAY 7
5A
5B
5C
5D
5E
5F
5H
5J
5K
5L 5M
1A
1B
3A
3B
3C
CB A1
CB A2
CB B3
CB B2
CB B1
CB H1
CB H6
CB H5
CB H4
CB H3
CB H2
CB C1
CB C2
CB C3
CB C5 CB C6
CB C4 CB C8
CB C7
CB D1
CB D6
CB D5
CB D2
CB D4
CB D3
CB G1
CB F1
CB F2
CB F3
INV G
INV F
INV A
INV B
INV H
INV D
INV C
EM-1
EM-1
EM-2
EM-2
EM-2
EM-2
EM-1
DAS EQUIPMENTEM-2
A
B
C
D
E G K
J
H
L
M
F
DAS EQUIPMENT
A
B
C
E
D
F
DAS
G
N
ARCH D (36"X24")
DATA ACQUISITION AND MONITORING
GENERAL PLAN
E-601
E-601
ARCH D (36"X24")ARCH D (36"X24")
B
A
C
D
E
F
G
H
I
J
K
L
THIS DRAWING IS THE CONFIDENTIAL
PROPERTY OF SUNWIZE TECHNOLOGIES
WWW.SUNWIZE.COM
SHEET NO:
B
A
C
D
E
F
G
H
I
J
K
L
21 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PAPER SIZE:
DRAWING NUMBER:
PROJECT NUMBER:
SHEET TITLE:
PROJECT / CUSTOMER INFORMATION:
PROJECT NAME:
LOMA LINDA VA MEDICAL CENTER
PHOTOVOLTAIC SYSTEM
LOMA LINDA VA MEDICAL CENTER
11201 BENTON STREET,
LOMA LINDA, CA 92357
503-6032
REV BY CHK
50% DESIGNA AG
REV. A
BH 2011.12.20
DESCRIPTION DATE
100% DESIGNB AG BH 2012.03.30
100% DESIGN FOR CONSTRUCTIONC AG CC 2012.05.10
LEGEND
(N) PV STRUCTURE
EXISTING PV (PHASE I)
EXISTING DAS (FAT SPANIEL
FOR PHASE I)
FIBER OPTICS
WIRED DATA CONNECTION
WIRED DATA IN INTERSTITIAL
SPACE
WIRELESS DATA CONNECTION
N
SCALE 1" = 60'
SB-6
SB-4
SB-2
SB-5
SB-3
SB-1
ARRAY 8
ARRAY 5
ARRAY 4
8B
7A
8A
7B
7C
BEHAVIORAL
HEALTH (FUTURE)
41" (H)
28"(H)
5in.(H)
13 FEET HIGH
W
ALKING MAT
ARRAY 1
CANCER
CENTER
(FUTURE)
120120 120 120
4A
4C
4D
4E
4F 4B
ARRAY 7
WALL
GLASS WALL
(E) ACCESS DOOR FROM
MAIN BLDG TO NURSING
HOME ROOF
5A
5B
5C
5D
5E
5F
5G5H
5J
5K
5L 5M
1A
1B
3A
3B
3C
120V/240V CIRCUITS IN CARPORTS
(NON-PV RELATED)
E-701
E-701
ARCH D (36"X24")ARCH D (36"X24")
B
A
C
D
E
F
G
H
I
J
K
L
THIS DRAWING IS THE CONFIDENTIAL
PROPERTY OF SUNWIZE TECHNOLOGIES
WWW.SUNWIZE.COM
SHEET NO:
B
A
C
D
E
F
G
H
I
J
K
L
21 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PAPER SIZE:
DRAWING NUMBER:
PROJECT NUMBER:
SHEET TITLE:
PROJECT / CUSTOMER INFORMATION:
PROJECT NAME:
LOMA LINDA VA MEDICAL CENTER
PHOTOVOLTAIC SYSTEM
LOMA LINDA VA MEDICAL CENTER
11201 BENTON STREET,
LOMA LINDA, CA 92357
503-6032
REV BY CHK
50% DESIGNA AG
REV. C
BH 2011.12.20
DESCRIPTION DATE
100% DESIGNB AG BH 2012.03.30
100% DESIGN FOR CONSTRUCTIONC AG CC 2012.05.10
N
SCALE 1" = 70'
LEGEND
(2)#10AWG THWN + (1) #10AWG
THWN (NEUTRAL) + (1) #10AWG
THWN (GND) IN (1) 1" CONDUIT.
(1)#10AWG THWN + (1) #10AWG
THWN (NEUTRAL) + (1) #10AWG
THWN (GND) IN (1) 1" CONDUIT.
PULL BOX FOR 120V/240V
CIRCUITS
(N) FOUR DUPLEX 120V/20A
OUTLETS IN RAIN TIGHT
ELECTRICAL BOX (ONE AT EACH
END OF EACH CARPORT
STRUCTURE)
(N) DOUBLE-GANG RAIN TIGHT
ELECTRICAL BOX WITH 240V/20A
CIRCUIT CONDUCTORS (ONE PER
CARPORT SITE)
120V
240V
240V
PB
NOTES
1. ELECTRICAL POWER FOR THE EXTRA
CIRCUITS IN CARPORTS WILL BE
PROVIDED BY DEDICATED AC POWER
CENTERS INSTALLED IN CARPORT
EQUIPMENT PADS. THE AC POWER
CENTERS ARE POWERED BY THE
ARRAY INVERTERS.
2. VERIFY AND MARK LOCATION OF
UNDERGROUND UTILITIES PREVIOUS TO
RUN NEW UNDERGROUND CONDUITS.
SB-6
SB-4
SB-2
SB-5
SB-3
SB-1
ARRAY 8
ARRAY 5
ARRAY 4
8B
7A
8A
7B
7C
BEHAVIORAL
HEALTH (FUTURE)
41" (H)
28"(H)
5in.(H)
13 FEET HIGH
W
ALKING MAT
ARRAY 1
CANCER
CENTER
(FUTURE)
SP
AR
E
SPARE
SP
AR
E
SPARE
SPARE
SP
AR
E
SP
AR
E4A
4C
4D
4E
4F 4B
ARRAY 7
WALL
GLASS WALL
(E) ACCESS DOOR FROM
MAIN BLDG TO NURSING
HOME ROOF
SP
AR
E
SP
AR
E
SP
AR
E
SP
AR
E
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE SPARE
SP
AR
E
SP
AR
E
SP
AR
E
5A
5B
5C
5D
5E
5F
5G5H
5J
5K
5L 5M
1A
1B
3A
3B
3C
SPARE CONDUIT RUNS
E-705
E-705
ARCH D (36"X24")ARCH D (36"X24")
B
A
C
D
E
F
G
H
I
J
K
L
THIS DRAWING IS THE CONFIDENTIAL
PROPERTY OF SUNWIZE TECHNOLOGIES
WWW.SUNWIZE.COM
SHEET NO:
B
A
C
D
E
F
G
H
I
J
K
L
21 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PAPER SIZE:
DRAWING NUMBER:
PROJECT NUMBER:
SHEET TITLE:
PROJECT / CUSTOMER INFORMATION:
PROJECT NAME:
LOMA LINDA VA MEDICAL CENTER
PHOTOVOLTAIC SYSTEM
LOMA LINDA VA MEDICAL CENTER
11201 BENTON STREET,
LOMA LINDA, CA 92357
503-6032
REV BY CHK
50% DESIGNA AG
REV. C
BH 2011.12.20
DESCRIPTION DATE
100% DESIGNB AG BH 2012.03.30
100% DESIGN FOR CONSTRUCTIONC AG CC 2012.05.10
N
SCALE 1" = 70'
LEGEND
(1) 2" + (1) 1" SPARE CONDUITS
(CAPPED OFF)
PULL BOX FOR SPARE CONDUITS
SPARE
SPARES
PB
NOTES
1. VERIFY AND MARK LOCATION OF
UNDERGROUND UTILITIES PREVIOUS TO
RUN NEW UNDERGROUND CONDUITS.
SB-6
SB-4
SB-2
SB-5
SB-3
SB-1
5in.(H)
13 FEET HIGH
W
ALKING MAT
ARRAY 1
4 FLOORS PLUS BASEMENT
AC RUN DOWN: 16FT*5=80FT
ONE FLOOR RUN
UP:16FT
RUN DOWN TO
BASEMENT : 16FT
3'-2 1 2"
HD
G
UN
IS
TR
UT
S
UP
PO
RT
F
OR
EQ
UI
PM
EN
T
W
AL
L
MO
UN
T
RO
OF
A
TT
AC
HM
EN
T
PE
R
ST
RU
CT
UR
AL
D
ET
AI
L
SA
TC
ON
P
VS
kW
AC
D
IS
CO
0A
/6
V
NO
N-
FU
SE
D
NE
MA
-3 R
DC
R
EC
OM
BI
NE
R A1
NE
MA
-3 R
AC DISCO 1
REC A1
INV. A
SATCON PVS-100
INV. B
SATCON PVS 135
PHASE I
INVERTER
REC B1
LOAD CENTER 1
CB A2
CB A1
PA
NE
LB
OA
RD
0A N
EM
A-
3R
HDG UNISTRUT SUPPORT FOR
EQUIPMENT WALL MOUNT
RUN INSIDE INTERSTITIAL
SPACE TO REC A1
RUN INSIDE INTERSTITIAL
SPACE TO REC A1
STUB UPS FROM
INTERSTITIAL SPACE
1 FLOOR + BASEMENT RUN
DOWN: 16FT*2=32FT
1A
1B
DA
TA
A
CQ
UI
SI
TI
ON
SY
ST
EM
SA
TC
ON
P
VS
5/
AC
P
AN
EL
BO
AR
D #1
0A
N
EM
A- 3R
AC
D
IS
CO
NN
EC
T #2
0A
N
EM
A- 3R
DA
TA
A
CQ
UI
SI
TI
ON
SY
ST
EM
DA
TA
A
CQ
UI
SI
TI
ON
SY
ST
EM
AC
P
AN
EL
BO
AR
D #1
0A
N
EM
A- 3R
AC
D
IS
CO
NN
EC
T #2
0A
N
EM
A- 3R
DA
TA
A
CQ
UI
SI
TI
ON
SY
ST
EM
DA
TA
A
CQ
UI
SI
TI
ON
SY
ST
EM
ARCH D (36"X24")
PV LAYOUT AND INTERCONNECTION
PLAN
ARRAY 1 TO SERVICE BAY 6
A-203
A-203
ARCH D (36"X24")ARCH D (36"X24")
B
A
C
D
E
F
G
H
I
J
K
L
THIS DRAWING IS THE CONFIDENTIAL
PROPERTY OF SUNWIZE TECHNOLOGIES
WWW.SUNWIZE.COM
SHEET NO:
B
A
C
D
E
F
G
H
I
J
K
L
21 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PAPER SIZE:
DRAWING NUMBER:
PROJECT NUMBER:
SHEET TITLE:
PROJECT / CUSTOMER INFORMATION:
PROJECT NAME:
LOMA LINDA VA MEDICAL CENTER
PHOTOVOLTAIC SYSTEM
LOMA LINDA VA MEDICAL CENTER
11201 BENTON STREET,
LOMA LINDA, CA 92357
503-6032
REV BY CHK
50% DESIGNA AG
REV. C
BH 2011.12.20
DESCRIPTION DATE
100% DESIGNB AG BH 2012.03.30
100% DESIGN FOR CONSTRUCTIONC AG CC 2012.05.10
N
SCALE 1" = 25'
LEGEND
PV MODULE
OMITTED MODULE IN SUNLINK
ROOFTOP ARRAYS
© 2011 SunLink Corporation The information on this drawing is proprietary to SunLink Corporation. It is provided on the condition that it is used only to facilitate the installation of the SunLink Photovoltaic Module Mounting System shown. Do not copy or distribute except for the use stated above.
SUNLINK CORPORATION
1010 B STREET, SUITE 400
SAN RAFAEL, CA 94901
(T) 415.925.9650 (F) 415.925.9636
WWW.SUNLINK.COM
su nw iz e si on oc um en ts a nd s et tin gs
\s un w iz e us er \m y do cu m en ts
\0 p ro je ct s\ lo m a lin da ii \d es ig n\ pl an s fro m s ub co nt ra ct or s\ su nl in k\ su nl in k or ig in al s\
4-va lo m al in da -1
1-en g-r3
_2
2.
.0 3.
dw g
Sheet NumberIssue
No. of Modules Pwr. Output (DC)
Module
Tilt Angle
Location
Project
Customer
Quote Reference No.
Sales Order No.
Sheet Title
SUNLINK
ROOF MOUNT
SYSTEM
Sheets
DC String Length No. of StringsWattage kW
Issue DateDescription Drawn By Checked By
SOLAR PV ARRAY MOUNTING SYSTEMS
Samsung LPC247SM-08S
10° 247 1,134 14 81 280.1
ARRAY LAYOUT PLAN
3 of 7 R3 SL1.1
0 Ft.2 8 16
1/8" = 1'-0"SCALE:
ARRAY LAYOUT PLAN
NORTH ROW
DEFLECTORS
LATERAL LINKS,
REQUIRED AS SHOWN
12'-3" MIN. SUNLINK
REQUIRED SETBACK FROM
ALL 72' ROOF EDGES TO
ALL MODULES, V.I.F.
6'-0" SETBACK FROM
INSIDE OF PARAPET
WALLS TO ARRAY PER
CAL FIRE PV GUIDELINE
OMITTED MODULE, TYP.
END DEFLECTOR
SHADE AFFECTED
ZONE
(E) ROOF EQUIPMENT,
TYP.
FACE OF BUILDING
SUB-ARRAY 1
168 MODULES
12 14-MODULE STRINGS
37 4x1 PANELS 8 3x1 PANELS
4 MODULES OMITTED
The information on this drawing is proprietary to SunLink Corporation. It is provided on the condition that it is used only to facilitate the installation of the SunLink Photovoltaic Module Mounting System shown. Do not copy or distribute except for the use stated above.
SUNLINK CORPORATION
1010 B STREET, SUITE 400
SAN RAFAEL, CA 94901
(T) 415.925.9650 (F) 415.925.9636
WWW.SUNLINK.COM
su nw iz e si on oc um en ts a nd s et tin gs
\s un w iz e us er \m y do cu m en ts
\0 p ro je ct s\ lo m a lin da ii \d es ig n\ pl an s fro m s ub co nt ra ct or s\ su nl in k\ su nl in k or ig in al s\
4-va lo m al in da -1
1-en g-r3
_2
2.
.0 3.
dw g
Sheet NumberIssue
No. of Modules Pwr. Output (DC)
Module
Tilt Angle
Location
Project
Customer
Quote Reference No.
Sales Order No.
Sheet Title
SUNLINK
ROOF MOUNT
SYSTEM
Sheets
DC String Length No. of StringsWattage kW
Issue DateDescription Drawn By Checked By
SOLAR PV ARRAY MOUNTING SYSTEMS
Samsung LPC247SM-08S
10° 247 1,134 14 81 280.1
ARRAY LAYOUT PLAN
4 of 7 R3 SL1.2
0 Ft.2 8 16
1/8" = 1'-0"SCALE:
ARRAY LAYOUT PLAN
NORTH ROW
DEFLECTORS
LATERAL LINKS,
REQUIRED AS SHOWN
12'-3" MIN. SUNLINK
REQUIRED SETBACK FROM
ALL 72' ROOF EDGES TO
ALL MODULES, V.I.F.
OMITTED MODULE, TYP.
END DEFLECTOR
SHADE AFFECTED
ZONE
(E) ROOF EQUIPMENT,
TYP.
FACE OF BUILDING
6'-0" SETBACK FROM
INSIDE OF PARAPET
WALLS TO ARRAY PER
CAL FIRE PV GUIDELINE
SUB-ARRAY 2
280 MODULES
20 14-MODULE STRINGS
25 4x1 PANELS 62 3x1 PANELS
6 MODULES OMITTED
(E) DEDICATED 400A SPARE CIRCUIT
BREAKER FOR SOLAR SYSTEM
INTERCONNECTION IN (E) SERVICE PANEL.
12314
12314
AC
DC
DATA
SUB-ARRAY A1
(NEG. GND.)
SUB-ARRAY A2
(NEG. GND.)
12KV-3ɸ-3W
FROM SCEDS-632
3200AF
2400AT
MAIN
BREAKER
SPB-100
400AF
200AT 12KV PANEL 1200A
SCE METER
V345M 000015
Y
EXISTING
EQUIPMENT
SERVICE BAY SB-3
INVERTER A
SATCON PVS-100/480
AR
RA
Y
NON-FUSIBLE
LOCKABLE
AC DISCONNECT
AC DISCO #1
NEW
EQUIPMENT
POINT OF COMMON COUPLING
(POCC) AS PER NEC 690.64B.
DATA
LOGGER
WEATHER
STATION
TO AC POWER
SOURCE
TO WEATHER
SENSORS
STRING COMBINER BOX / DC
DISCONNECT
NEMA-3R/600VDC
PV STRING
14 SAMSUNG LCP-247W
PV MODULES
RECOMBINER BOX
NEMA-3R/600VDC 125AF
UNIT SUBSTATION
TRANSFORMER
WEST CLE-2
125A
CB/DCD A1
CB/DCD A2
REC A1
TO NETWORK
EQUIPMENT IN
SERVICE BAY 3
DATA
DATA
M
1 2 3
250A 480V
Δ Y
GFDI
TO INV.
E-STOP
INVERTER TYPE SATCON POWERGATE PVS-100kW/480V
ID A
MAX. INPUT CURRENT, ADC 331
OUTPUT POWER, kW 100
OUTPUT VOLTAGE, V 480/277
MAX. OUTPUT CURRENT PER PHASE @480VAC, A 121
CEC-WEIGHTED EFFICIENCY, % 96
SUBARRAY A1 A2 ARRAY 1
SUBARRAY AZIMUTH 180° (S) 180° (S) 180° (S)
SUBARRAY TILT 10° 10° 10°
PV MODULE COUNT 168 280 448
MODULES PER SOURCE CIRCUIT 14 14 14
SOURCE CIRCUIT COUNT 12 20 32
POWER, WDC STC 41,496 69,160 110,656
POWER, WDC PTC 37,430 62,384 99,814
AC POWER, W 35,933 59,889 95,822
ITEM ID BRAND AND MODEL SPECIFICATIONS
COMBINER BOX / DC DISCONNECT CB-DCD A1 AMTEC PR-12M-250-PS-FG-SPL
CB-DCD A2 AMTEC PR-20M-400-PS-FG-SPL
RECOMBINER BOX REC A1 AMTEC EQ750-1x175-1x300
INVERTER A SATCON PVS100/480 UL NEG ARRA
MAIN AC DISCONNECT #1 SQUARE D HU364RB 200A/600VAC NON FUSED, NEMA 3R
DATA ACQUISITION SYSTEM #1 ARGUS ON INCLUDES WEATHER AND SYSTEM
SENSORS AND PERFORMANCE METER
GROUND FAULT MONITORING A BENDER RCMA423 MONITOR+W60AB CURRENT
TRANSDUCER
E-101
E-101
ARCH D (36"X24")ARCH D (36"X24")
B
A
C
D
E
F
G
H
I
J
K
L
THIS DRAWING IS THE CONFIDENTIAL
PROPERTY OF SUNWIZE TECHNOLOGIES
WWW.SUNWIZE.COM
SHEET NO:
B
A
C
D
E
F
G
H
I
J
K
L
21 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PAPER SIZE:
DRAWING NUMBER:
PROJECT NUMBER:
SHEET TITLE:
PROJECT / CUSTOMER INFORMATION:
PROJECT NAME:
LOMA LINDA VA MEDICAL CENTER
PHOTOVOLTAIC SYSTEM
LOMA LINDA VA MEDICAL CENTER
11201 BENTON STREET,
LOMA LINDA, CA 92357
503-6032
REV BY CHK
50% DESIGNA AG
REV. C
BH 2011.12.20
DESCRIPTION DATE
100% DESIGNB AG BH 2012.03.30
100% DESIGN FOR CONSTRUCTIONC AG CC 2012.05.10
SINGLE LINE DIAGRAM
ARRAY 1
KEYED NOTES (REFER ONLY TO
THOSE THAT APPLY):
1. EACH SOURCE CIRCUIT CONSISTS OF 14 SAMSUNG 247W
MODULES CONNECTED IN SERIES. HOME RUN WIRES FROM
SOURCE CIRCUITS TO COMBINER BOXES ARE RATED FOR
OUTDOOR EXPOSURE UNLESS SPECIFIED OTHERWISE.
2. COMBINER BOX WITH INTEGRAL DC DISCONNECT: UL LISTED,
RATED 600VDC, NEMA 3R OR BETTER; FUSES TYPE KLKD
(OAE), 15A. DC DISCONNECT: NON-FUSED, 600VDC,
INTEGRATED INTO THE COMBINER ENCLOSURE. REFER TO
SCHEDULES FOR INDIVIDUAL RATINGS.
3. RECOMBINER BOX: UL LISTED, RATED 600VDC, NEMA 3R OR
BETTER. REFER TO SCHEDULE FOR INDIVIDUAL RATINGS.
4. DC DISCONNECTS IN SOLARON INVERTERS WITHOUT DC/AC
SWITCHGEAR. TYP. OF ONE DC DISCONNECT FOR EACH POLE.
5. INVERTER: UL1741 LISTED WITH INTEGRAL ANTI-ISLANDING
PROTECTION FEATURES. UL1741 LISTING INCLUDES
COMPLIANCE WITH IEEE519 FOR POWER QUALITY, IEEE929 FOR
INTERCONNECTION SAFETY, AND THE NEC APPLICABLE
SECTIONS. THIS INVERTER IS TESTED AND LISTED AS A
PACKAGE IN A SINGLE ENCLOSURE WITH AC AND DC
DISCONNECTS AND THE UTILITY REQUIRED ISOLATION
TRANSFORMER.
6. AC LOAD CENTER. UL LISTED MLO RATED FOR 480VAC WITH
NEMA 3R OR BETTER ENCLOSURE WITH BREAKERS RATED
FOR BACKFEED OPERATION.
7. AC MAIN DISCONNECT SWITCH LOCKABLE NEMA 3R
8. (E) MAIN SOLAR AC BREAKER WITH ADJUSTABLE SETTINGS.
INSTALLED IN SWITCHGEAR AT SERVICE BAYS. RATED FOR
BACKFEED OPERATION.
9. DATA ACQUISITION AND MONITORING SYSTEM. ONE WEATHER
STATION ON MAIN BUILDING ROOFTOP. THE DATA LOGGED
FROM THE DIFFERENT SITES WILL BE REPORTED ON A
WEB-BASED PORTAL. SYSTEM PROJECT, INSTALLATION
SUPPORT AND SETUP BY POWER ONE, ARGUSON, DRAKER
OR APPROVED EQUAL
NOTES:
1. SEE GENERAL NOTES ON DRAWING G-102.
2. ALL CONDUIT ON ROOFS, WALLS AND INSIDE BUILDINGS
SHALL BE IMC ASSEMBLED WITH UL LISTED FITTINGS
SUITABLE FOR THE APPLICATION (INDOOR/OUTDOOR). REFER
TO G-102 NOTE 17 FOR CONDUIT ACCEPTANCE OTHER THAN
IMC.
3. CONDUIT RUNS ON ROOFS SHALL BE SUPPORTED MORE
THAN 3 1/2” OFF THE ROOF SURFACE USING COOPER
DURABLOK SUPPORTS OR EQUIVALENT PRODUCT. MAXIMUM
SPACING BETWEEN SUPPORTS 8 FT ON CENTERS AS PER
VA SECTION 260533 ARTICLE 3.2.C.6.
4. IMC CONDUIT SUPPORTS IN EXTERIOR AND INTERIOR WALLS
SHALL BE SUPPORTED IN ACCORDANCE WITH NEC 2008.
5. FOR ALL THWN-2 WIRES. VERIFY THE TYPE OF WIRE
IMPRINTED IN THE WIRE JACKET BEFORE USE. THE USE OF
OTHER TYPE OF WIRES NOT SUITABLE FOR THIS
APPLICATION WILL CAUSE OVERHEATING, ELECTRIC SHOCK
AND FIRE HAZARDS.
6. REFER TO G-102 NOTE 22 FOR ROOFS AND WALLS
PENETRATION REQUIREMENTS.
ARRAY 1 - MAIN BUILDING ROOFTOP - SINGLE LINE DIAGRAM AND EQUIPMENT SCHEDULE
12314 ...
12314 ...
175A
GROUND
15A
15A
300A
GROUND
GROUND
DATA
DATA
24V
24V
TO AC/DC POWER SUPPLY
SEE DRAWING E-501
TO DAS MANAGEMENT CONSOLE
SEE DRAWING E-301
200A
400A
TO DAS MANAGEMENT CONSOLE
SEE DRAWING E-301
DATA
GROUND GROUND
BA C D
SOURCE CIRCUITS
1 TO 12
SUBARRAY A1
12 CIRCUITS
COMBINER BOX-DC DISCONNECT A1
SEE DRAWING
E-301 FOR
AC CONNECTIONS
TO INVERTER
INVERTER A - SATCON PVS 100Kw/480V
RECOMBINER BOX A1
COMBINER BOX-DC DISCONNECT A2 TO GROUND THRU GFI CIRCUIT
SUBARRAY A2
20 CIRCUITS
SOURCE CIRCUITS
13 TO 32
POS./NEG. DC PAIR
THRU ONE CT. TYP.
GFDI TO INV.
E-STOP
TYP.
E-901
TYP.
E-901
TYP.
E-901
TYP.
E-901
SECTIONS A & B: PV MODULE/ PV STRING (ALL EXPOSED CONDUCTORS) FOR SUNWIZE-PROSOLAR 4-MODULE PANELS
DC-STC DC-PTC Voc Vmp Isc Imp Series Fuse
Max System Voltage
Max.
Voc
Min.
Vmp
Max.
Vmp
CURRENT
CARRYING
CONDUCTORS
GROUND METHOD
ITEM W W VDC VDC A A A VDC V V V
LPC247SM-08 PV MODULE IN SUNWIZE PANEL 247 223 37.60 30.40 8.62 8.14 15 600 41.80 26.60 32.60 #10 USE-2 WEEB-PMC GND WASHER
14-MODULE STRING 3,458 3,119 526 426 8.62 8.14 15 600 585 372 456 #10 USE-2 #6 BARE Cu / WEEB L6.7 LUG
SECTION C: DC STRING COMBINERS (ALL THWN-2 WIRES) SECTION D: DC RECOMBINERS (ALL THWN-2 WIRES)
ARRAY CB-DCD MODULES STRINGS
GROUND
POLARITY
DC DISCO
RATING, A
CURRENT CARRYING
CONDUCTORS
GND
CONDUCTORS
CONDUIT
TYPE
CONDUIT
SIZE, IN.
DISTANCE CB/DCD
to REC, FT.
VOLTAGE
DROP, %
MIN. Vmp AFTER
VDROP, V RECOMBINER
INPUT
FUSES, A
CURRENT CARRYING
CONDUCTORS
GND
CONDUCTORS
CONDUIT
TYPE
CONDUIT
SIZE, IN.
DISTANCE REC
to INV, FT.
VOLTAGE
DROP, %
MIN. Vmp AFTER
VDROP, V TOTAL MAX. DC VDROP, %
A1 168 12 NEG 250 (2) #4/0 (1) #6 IMC (1) 1.5 270 1.31 352
REC A1
(4) 4/0 (1) #2 IMC (1) 2.5 15 0.07 356 1.38
A2 280 20 NEG 400 (4) #1/0 (1) #4 IMC (1) 2.0 250 1.89 350 300
SECTION D: DC RECOMBINERS AND DC DISCONNECTS (ALL THWN-2 WIRES)
DC 3-LINE SCHEMATICS AND
WIRING SCHEDULE
ARRAY 1
E-201
E-201
ARCH D (36"X24")ARCH D (36"X24")
B
A
C
D
E
F
G
H
I
J
K
L
THIS DRAWING IS THE CONFIDENTIAL
PROPERTY OF SUNWIZE TECHNOLOGIES
WWW.SUNWIZE.COM
SHEET NO:
B
A
C
D
E
F
G
H
I
J
K
L
21 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PAPER SIZE:
DRAWING NUMBER:
PROJECT NUMBER:
SHEET TITLE:
PROJECT / CUSTOMER INFORMATION:
PROJECT NAME:
LOMA LINDA VA MEDICAL CENTER
PHOTOVOLTAIC SYSTEM
LOMA LINDA VA MEDICAL CENTER
11201 BENTON STREET,
LOMA LINDA, CA 92357
503-6032
REV BY CHK
50% DESIGNA AG
REV. C
BH 2011.12.20
DESCRIPTION DATE
100% DESIGNB AG BH 2012.03.30
100% DESIGN FOR CONSTRUCTIONC AG CC 2012.05.10
ARRAY 1 - DC WIRING DIAGRAM AND SCHEDULES
NOTES
1. FOR ALL THWN-2 WIRES. VERIFY THE TYPE OF WIRE IMPRINTED
IN THE WIRE JACKET BEFORE USE. THE USE OF OTHER TYPE OF
WIRES NOT SUITABLE FOR THIS APPLICATION WILL CAUSE
OVERHEATING, ELECTRIC SHOCK AND FIRE HAZARDS.
1 2 8 9 10
KEYED NOTES
1. STANDARD TEST CONDITIONS (STC) ARE:
IRR=1000W/m², CELL TEMPERATURE=25°C AND
AIR MASS=1.5
2. PERFORMANCE TEST CONDITIONS (PTC) ARE:
IRR=1000W/m², AMBIENT TEMPERATURE=20°C AND
WIND SPEED=1 METER/SEC.
3. EACH MODULE INCLUDES OUTDOOR RATED QUICK CONNECTORS
FOR INTERCONNECTION. REMOVING THE CONNECTORS WILL
INVALIDATE THE MODULE WARRANTY AND THE UL LISTING
UNLESS REPLACED WITH CONNECTORS IN ACCORDANCE WITH
MANUFACTURER APPROVED METHOD.
4. ALL USE-2 WIRES ARE RATED FOR DIRECT SUNLIGHT
EXPOSURE. TO AVOID OVERHEATING, POWER LOSSES AND
FIRE HAZARD DO NOT RUN USE-2 WIRES IN CONDUITS
WITHOUT CONSULTING PROJECT ENGINEER.
5. FUSED SOURCE CIRCUIT SMART COMBINER BOXES ARE UL-1741
LISTED IN NEMA 3R OR BETTER ENCLOSURE. SOURCE CIRCUIT
COMBINER BOXES INCORPORATE A D.C. DISCONNECT
FEATURING MULTIPLE DISCONNECT SAFETY SYSTEM (MDSS)
FOR SAFE ISOLATION DURING UNDER-LOAD ON/OFF
OPERATIONS.
6. RECOMBINER BOXES ARE UL-1741 LISTED IN NEMA 3R OR
BETTER ENCLOSURE.
7. INVERTER(S): UL1741 LISTED…
This is the start of the file's text. The full file is on GovTribe.