Amendment 0001_Attachment G. Electrical Drawings.pdf
PDF 4 MB Posted
- Solicitation number
- 36C26224B0001_1
About this file
This is an Invitation for Bid (IFB) for construction services to replace an existing PVC roofing system with a new TPO roofing system at the Veterans Affairs Loma Linda Medical Center located in Loma Linda, California. The scope of work includes preparation, submittals, change orders, site visits, meetings, phasing and scheduling, utility shut-downs, and infection control measures. All work must be performed in accordance with project specifications, statement of work, design documents, schedule, and other supporting documents while the hospital remains operational. Bids are due by [date redacted] and the contract is to be awarded by [date redacted]. The contractor must furnish all labor, equipment, certifications, supervision, and materials to complete the roof replacement and install lightning protection at the medical center.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
L L
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BIPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
R RELOCATE/RELOCATED
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
2W TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCT CORRELATED COLOR TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
D DEMOLITION
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FU FUSE
FUDS FUSED SAFETY DISCONNECT
SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA
STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL
ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO
SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING
CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW
TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR
FINAL CONNECTIONS.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD
PARTY TESTING AGENCY.
17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.
PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE
PROVIDED.
19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
21. FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.
SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE PERFORMED ON THE ELECTRICAL SYSTEM USING A BOLTED THREE PHASE FAULT CONDITION FOR CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS TO THE SYSTEM FOR CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT VALUES WILL BE USED OUTSIDE THE WORK
AREA, FOR THE STARTING POINT OF THE CALCULATIONS.
METHOD OF SHORT CIRCUIT CURRENT CALCULATIONS
USING OHM'S LAW AND THE KNOWN RESISTIVITY CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM PER FOOT) FOR COPPER CONDUCTORS, CALCULATE THE REQUIRED WIRE SIZE NECESSARY SO AS NOT TO EXCEED THE
RECOMMENDED VOLTAGE DROP OF 3% FOR BRANCH CIRCUIT CONDUCTORS.
METHOD OF VOLTAGE DROP CALCULATIONS
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SPECIAL RECEPTACLE
EQUIPMENT CONNECTION
AS
NOTED
E
208V DUPLEX RECEPTACLE18"
18"
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
120V SIMPLEX RECEPTACLE18"2' X 2' RECESSED ARCHITECTURAL TROFFER
2' X 4' RECESSED ARCHITECTURAL TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT LENS TROFFER
2' LINEAR - WALL MOUNTED
7'-0"
CENTER
4' LINEAR - WALL MOUNTED
7'-0"
CENTER
WALL SCONCE
6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
VS: VACANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
DR: DUAL RELAY
VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER
OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
4: 4 WAY
48"
CENTER
OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, LOW VOLTAGE, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
OS
OS
LS
4' LINEAR STRIP - SUSPENDED---
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK AT AREAS NOTED AS HAZARDOUS OR RADIATION HAZARD AREAS.
THERE IS A RADIATION HAZARD FOR WORKERS WORKING ON PENTHOUSES LOCATED ON MAIN HOSPITAL ROOF. THE CONTRACTOR SHALL COORDINATE WITH THE COR AND FACILITY SAFETY FOR ALL REQUIREMENTS FOR WORKING IN THESE AREAS. THE CONTRACTOR SHALL PROVIDE A SAFETY PLAN FOR WORK IN THE AREAS OF RADIATION HAZARDS THAT IS SUBMITTED AND APPROVED BY THE VA. THE CONTRACTOR, AND ALL PERSONNEL WORKING ON THE ROOF AREAS SHALL BE REQUIRED TO ATTEND FACILITY REQUIRED TRAINING REGRADING WORKING AROUND RADIATING EQUIPMENT TO BE PROVIDED
BY THE FACILITY SAFETY DEPARTMENT
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:1
:1
P M
C U s e rs
\h ts e n g \D o c u m e n ts
\E
-3
-V
A L o m a L in d a
R e p la c e
R o o f_ h ts e n g
M R
C W
.r v t
E-001
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
1 7JWB
ROOF REPLACEMENT AND
LIGHTNING PROTECTION
VA LOMA LINDA HEALTHCARE SYSTEM
11201 BENTON ST, LOMA LINDA,
CA 92357 OCTOBER 12, 2022
100% BID DOCUMENTS
605-20-41121-330-Q31
JDM
ELECTRICAL ABBREVIATIONS LIST
ELECTRICAL SYMBOL NOTES
ELECTRICAL GENERAL NOTES
ELECTRICAL SYMBOL LEGENDLIGHTING SYMBOL LEGEND
RADIATION HAZARD SAFETY
DocuSign Envelope ID: A4390503-3B47-43AE-8776-FFA73EEE7A82
10/10/2022
A
ANNEX
CLC
N.I.C. N.I.C.
N.I.C.
22 2 3 4 5 6 7 8 9 10 11 13 14 AA
B
C
D
F
G
H
I
J
K
LL
R
N
O
P
Q
1 5
1 5
1 5
1 5
1 5
1 5
1 5
1 5
1 5
1 5
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:1
:2
P M
C U s e rs
\h ts e n g \D o c u m e n ts
\E
-3
-V
A L o m a L in d a
R e p la c e
R o o f_ h ts e n g
M R
C W
.r v t
ED101
ELECTRICAL ROOF DEMOLITION PLAN
2 7JWB
ROOF REPLACEMENT AND
LIGHTNING PROTECTION
VA LOMA LINDA HEALTHCARE SYSTEM
11201 BENTON ST, LOMA LINDA,
CA 92357 OCTOBER 12, 2022
100% BID DOCUMENTS
605-20-41121-330-Q31
JDM
NORTH
0 4 8 16
1 DISCONNECT AND REMOVE EXISTING SOLAR
ARRAY, COMPLETE. TURN-OFF TIE-IN
CIRCUIT BREAKER IN EXISTING
SWITCHBOARD AND REMOVE ASSOCIATED
CONDUCTORS.
2 REMOVE AND PROTECT EXISTING
ROOF-MOUNT ANTENNA FOR
RE-INSTALLATION AFTER NEW ROOF IS
APPLIED.
3 DISCONNECT AND REMOVE SOLAR SYSTEM
COMPONENTS (DISCONNECT SWITCH,
JUNCTION BOX, ETC.).
4 DISCONNECT AND REMOVE SOLAR SYSTEM
CONNECTIONS (CONDUITS AND
CONDUCTORS).
5 APPROXIMATE EXTENT / FOOTPRINT OF
EXISTING INSTALLED SOLAR ARRAY
STRINGS.
6 OPEN AREAS OF ROOF TO COURTYEARD
BELOW.
7 EXISTING INVERTER AND ELECTRICAL
EQUIPMENT TO REMAIN. SEE SHEET E-401.
Scale: 1" = 20'-0"
ELECTRICAL ROOF DEMOLITION PLAN
N
KEY PLAN
SCALE: NO SCALE
A. EXISTING PV/SOLAR-ARRAY SYSTEM TO BE
DISCONNECTED, REMOVED COMPLETELY AND
DISPOSED OF. REMOVE ALL PANELS,
MOUNTING BRACKETS, ASSOCIATED
CONDUITS & CONDUCTORS, DISCONNECTING
MEANS, COMBINING-BOXES, ETC. COVER, AND
DISCONNECT SOLAR PANELS DURING
DECONSTRUCTION. SOLAR PANELS REMAIN
ACTIVE DISCONNECTED AND PROPER STEPS
FOR DE-ENERGIZING THEM MUST BE TAKEN.
CERTAIN PV/SOLAR EQUIPMENT IS TO
REMAIN.
B. ACTIVE WIRELESS TELECOMMUNICATION
ANTENNAS POSE HEALTH-RISK TO
PERSONNEL. PROVIDE TRAINING ON SAFE
TECHNIQUES AND PROCEDURES FOR DE-
ENERGIZING AND REMOVING EQUIPMENT ON
HOSPTIAL ROOF.
C. SEE ARCHITECTURAL AND MECHANICAL ROOF
PLANS TO IDENTIFY EQUIPMENT NOT NOTED
HERE.
D. CONTRACTOR SHALL RECYCLE ALL SOLAR
PANELS, CONDUIT, EQUIPMENT, ETC. AND
PROVIDE CERTIFICATION OF RECYCLED
MATERIAL TO THE COR.
MAIN
BUILDING
AA
G
R
MAIN
BUILDING
Q
L
M
16 20 28 29 30
1 5
1 51 5
1 51 5
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:1
:2
P M
C U s e rs
\h ts e n g \D o c u m e n ts
\E
-3
-V
A L o m a L in d a
R e p la c e
R o o f_ h ts e n g
M R
C W
.r v t
ED102
ROOF ELECTRICAL DEMOLITION PLANS
- CLC & ANNEX
3 7JWB
ROOF REPLACEMENT AND
LIGHTNING PROTECTION
VA LOMA LINDA HEALTHCARE SYSTEM
11201 BENTON ST, LOMA LINDA,
CA 92357 OCTOBER 12, 2022
100% BID DOCUMENTS
605-20-41121-330-Q31
JDM
NORTH
0 2010 40
N
KEY PLAN
SCALE: NO SCALE
Scale: 1" = 20'-0"
ROOF ELECTRICAL DEMOLITION PLAN - ANNEX
Scale: 1" = 20'-0"
ROOF ELECTRICAL DEMOLITION PLAN - CLC
NORTH
0 2010 40
1 DISCONNECT AND REMOVE EXISTING SOLAR
ARRAY, COMPLETE. TURN-OFF TIE-IN
CIRCUIT BREAKER IN EXISTING
SWITCHBOARD AND REMOVE ASSOCIATED
CONDUCTORS.
2 REMOVE AND PROTECT EXISTING
ROOF-MOUNT ANTENNA FOR
RE-INSTALLATION AFTER NEW ROOF IS
APPLIED.
3 DISCONNECT AND REMOVE SOLAR SYSTEM
COMPONENTS (DISCONNECT SWITCH,
JUNCTION BOX, ETC.).
4 DISCONNECT AND REMOVE SOLAR SYSTEM
CONNECTIONS (CONDUITS AND
CONDUCTORS).
5 APPROXIMATE EXTENT / FOOTPRINT OF
EXISTING INSTALLED SOLAR ARRAY
STRINGS.
6 OPEN AREAS OF ROOF TO COURTYEARD
BELOW.
7 EXISTING INVERTER AND ELECTRICAL
EQUIPMENT TO REMAIN. SEE SHEET E-401.
A. EXISTING PV/SOLAR-ARRAY SYSTEM TO BE
DISCONNECTED, REMOVED COMPLETELY AND
DISPOSED OF. REMOVE ALL PANELS,
MOUNTING BRACKETS, ASSOCIATED
CONDUITS & CONDUCTORS, DISCONNECTING
MEANS, COMBINING-BOXES, ETC. COVER, AND
DISCONNECT SOLAR PANELS DURING
DECONSTRUCTION. SOLAR PANELS REMAIN
ACTIVE DISCONNECTED AND PROPER STEPS
FOR DE-ENERGIZING THEM MUST BE TAKEN.
B. ACTIVE WIRELESS TELECOMMUNICATION
ANTENNAS POSE HEALTH-RISK TO
PERSONNEL. PROVIDE TRAINING ON SAFE
TECHNIQUES AND PROCEDURES FOR DE-
ENERGIZING AND REMOVING EQUIPMENT ON
HOSPTIAL ROOF.
C. SEE ARCHITECTURAL AND MECHANICAL ROOF
PLANS TO IDENTIFY EQUIPMENT NOT NOTED
HERE.
D. CONTRACTOR SHALL RECYCLE ALL SOLAR
PANELS, CONDUIT, EQUIPMENT, ETC. AND
PROVIDE CERTIFICATION OF RECYCLED
MATERIAL TO THE COR.
2 2
A
CLC
ANNEX
22 2 3 4 5 6 7 8 9 10 11 13 14 AA
B
C
D
F
G
H
I
J
K
LL
R
N
O
P
Q
GROUNDING RING
(TYPICAL)
AIR-TERMINAL
(TYPICAL)
EXOTHERMIC WELD
(TYPICAL)
GROUND WELL /
GROUND ROD
(TYPICAL)
DOWN
CONDUCTOR
(TYPICAL)
EXISTING TELE-
COMMUNICAITONS
GROUND BUS
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:1
:2
P M
C U s e rs
\h ts e n g \D o c u m e n ts
\E
-3
-V
A L o m a L in d a
R e p la c e
R o o f_ h ts e n g
M R
C W
.r v t
EG101
ROOF ELECTRICAL - LIGHTNING
PROTECTION PLAN
4 7JWB
ROOF REPLACEMENT AND
LIGHTNING PROTECTION
VA LOMA LINDA HEALTHCARE SYSTEM
11201 BENTON ST, LOMA LINDA,
CA 92357 OCTOBER 12, 2022
100% BID DOCUMENTS
605-20-41121-330-Q31
JDM
1 PROVIDE GROUND RODS AS NECESSARY.
BREAKOUT CONCRETE AT GRADE CONTROL
JOINTS AND DIG A 14"Φ x 36"D POST HOLE.
INSTALL GROUND ENHANCEMENT MATERIALS
AND DRIVE GROUND ROD. INSTALL A 12"Φ x
18"D CIRCULAR CONCRETE HANDHOLE FOR
GROUNDING WELL WITH STEEL LID. BOND
DOWN-CONDUCTOR TO GROUND-ROD
BELOW GRADE. REPAIR CONCRETE TO BE
FLUSH WITH NEW GROUND-WELL
INSTALLATION.
2 PROVIDE CONCEALED DOWN-CONDUCTOR IN
EXTERIOR WALL AND BOND TO
GROUNDING-LOOP AND GROUNDING-WELL
INSTALLATION.
3 PROVIDE A PARRAPET LOOP CONDUCTOR
AROUND THE PERIMETER PORTIONS OF THE
NEW AND EXISTING ROOF.
4 PROVIDE AIR-TERMINAL EQUIPMENT AND
BOND TO THE PERIMETER-LOOP
CONDCUTOR.
5 BOND LIGHTNING-PROTECTION
CONDUCTORS USING EXOTHERMIC-WELD.
6 OPEN TO SECOND FLOOR COURTYARD
BELOW.
7 PROVIDE BONDED CONNECTION TO
TELE-COMMINICATIONS GROUND BUS.
N
KEY PLAN
SCALE: NO SCALE
Scale: 1" = 20'-0"
ROOF ELECTRICAL LIGHTNING PROTECTION PLAN
A. LIGHTNING PROTECTION ELEMENTS SHOWN
DEPICT APPROXIMATE EXPECTED
REQUIREMENTS. FINAL INSTALLATION
REQUIREMENTS SHALL BE DETERMINED BY A
CONTRACTOR PROVIDED LIGHTNING
PROTECTION SYSTEM DESIGN THAT MEETS VA
SPECIFICATION 26 41 00 "FACILITY LIGHTNING
PROTECTION" AND ALL NFPA RELATED
DOCUMENTS. LIGHTNING PROTECTION SYSTEM
SHALL MEET U.L. REQUIREMENTS SUCH THAT
THE SYSTEM SHALL HAVE A MASTER LABEL
CERTIFICATE. THE COMPLETED INSTALLATION
SHALL MEET THE REQUIREMENTS OF THE
NATIONAL FIRE PROTECTION ASSOCIATION'S
LIGHTING PROTECTION CODE - 2020 (NFPA 780),
IAW UFC 3-600-01, 03 AND THE INSTALLATION
REQUIREMENTS FOR LIGHTING PROTECTION
SYSTEMS, UL 96A' OF UNDERWRITERS
LABORATORIES INC. THE MASTER LABEL SHALL
BE FURNISHED TO THE OWNER UPON
COMPLETION.
B. LIGHTNING PROTECTION SHALL BE CONNECTED
CONTINUOUSLY IN A LOOP RUNNING ON THE
PARAPET OF THE ROOF PERIMETER. INSTALL
LIGHTING PROTECTION SYSTEM DOWN
CONDUCTORS FOR CONNECTION TO NEW
SYSTEM COMPONENTS. FOR LIGHTNING
PROTECTION ELEMENTS TO BE INSTALLED, SEE
ELECTRICAL DETAILS FOR ADDITIONAL
REQUIREMENTS.
C. LIGHTNING PROTECTION CONDUCTORS SHALL
BE SIZED PER NFPA 780-20. PROVIDE A
LIGHTNING PROTECTION GROUND BUS.
D. UNDERGROUND METALLIC PIPING ENTERING
THE BUILDING SHALL BE BONDED TO THE
NEAREST DOWN-CONDUCTOR OR GROUND
ELECTRODE.
E. AIR TERMINALS HAVE BEEN LOCATED ON THE
ROOF TOP EQUIPMENT AS REQUIRED. IF THE
METAL THICKNESS OF AN OBJECT IS 3/18" OR
GREATER, AIR TERMINALS MAY BE ELIMINATED
IF THE OBJECT IS PROPERLY CONNECTED TO
THE SYSTEM.
NORTH
0 2010 40
MAIN
BUILDING
AA
G
R
GROUNDING RING
(TYPICAL) 3
GROUND WELL /
GROUND ROD
(TYPICAL)
DOWN
CONDUCTOR
(TYPICAL)
EXOTHERMIC WELD
(TYPICAL)
4AIR-TERMINAL
(TYPICAL)
MAIN
BUILDING
Q
L
M
16 20 28 29 30
GROUND WELL /
GROUND ROD
(TYPICAL)
DOWN
CONDUCTOR
(TYPICAL)
EXOTHERMIC WELD
(TYPICAL)
GROUNDING RING
(TYPICAL)
4AIR-TERMINAL
(TYPICAL)
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:1
:2
P M
C U s e rs
\h ts e n g \D o c u m e n ts
\E
-3
-V
A L o m a L in d a
R e p la c e
R o o f_ h ts e n g
M R
C W
.r v t
EG102
ROOF ELECTRICAL - LIGHTNING
PROTECTION PLAN - CLC & ANNEX
5 7JWB
ROOF REPLACEMENT AND
LIGHTNING PROTECTION
VA LOMA LINDA HEALTHCARE SYSTEM
11201 BENTON ST, LOMA LINDA,
CA 92357 OCTOBER 12, 2022
100% BID DOCUMENTS
605-20-41121-330-Q31
JDM
NORTH
0 2010 40
1 PROVIDE GROUND RODS AS NECESSARY.
BREAKOUT CONCRETE AT GRADE CONTROL
JOINTS AND DIG A 14"Φ x 36"D POST HOLE.
INSTALL GROUND ENHANCEMENT MATERIALS
AND DRIVE GROUND ROD. INSTALL A 12"Φ x
18"D CIRCULAR CONCRETE HANDHOLE FOR
GROUNDING WELL WITH STEEL LID. BOND
DOWN-CONDUCTOR TO GROUND-ROD BELOW
GRADE. REPAIR CONCRETE TO BE FLUSH
WITH NEW GROUND-WELL INSTALLATION.
2 PROVIDE CONCEALED DOWN-CONDUCTOR IN
EXTERIOR WALL AND BOND TO
GROUNDING-LOOP AND GROUNDING-WELL
INSTALLATION.
3 PROVIDE A PARRAPET LOOP CONDUCTOR
AROUND THE PERIMETER PORTIONS OF THE
NEW AND EXISTING ROOF.
4 PROVIDE AIR-TERMINAL EQUIPMENT AND
BOND TO THE PERIMETER-LOOP
CONDCUTOR.
5 BOND LIGHTNING-PROTECTION CONDUCTORS
USING EXOTHERMIC-WELD.
6 OPEN TO GROUND LEVEL COURTYARD
BELOW.
7 BOND ROOF-LIGHTNING PROTECTION
GROUNDING WITH OTHER PORTIONS OF THE
SYSTEM INSTALLED ELSEWHERE.
N
KEY PLAN
SCALE: NO SCALE
A. LIGHTNING PROTECTION ELEMENTS SHOWN
DEPICT APPROXIMATE EXPECTED
REQUIREMENTS. FINAL INSTALLATION
REQUIREMENTS SHALL BE DETERMINED BY A
CONTRACTOR PROVIDED LIGHTNING
PROTECTION SYSTEM DESIGN THAT MEETS VA
SPECIFICATION 26 41 00 "FACILITY LIGHTNING
PROTECTION" AND ALL NFPA RELATED
DOCUMENTS. LIGHTNING PROTECTION SYSTEM
SHALL MEET U.L. REQUIREMENTS SUCH THAT
THE SYSTEM SHALL HAVE A MASTER LABEL
CERTIFICATE. THE COMPLETED INSTALLATION
SHALL MEET THE REQUIREMENTS OF THE
NATIONAL FIRE PROTECTION ASSOCIATION'S
LIGHTING PROTECTION CODE - 2020 (NFPA 780),
IAW UFC 3-600-01, 03 AND THE INSTALLATION
REQUIREMENTS FOR LIGHTING PROTECTION
SYSTEMS, UL 96A' OF UNDERWRITERS
LABORATORIES INC. THE MASTER LABEL SHALL
BE FURNISHED TO THE OWNER UPON
COMPLETION.
B. LIGHTNING PROTECTION SHALL BE CONNECTED
CONTINUOUSLY IN A LOOP RUNNING ON THE
PARAPET OF THE ROOF PERIMETER. INSTALL
LIGHTING PROTECTION SYSTEM DOWN
CONDUCTORS FOR CONNECTION TO NEW
SYSTEM COMPONENTS. FOR LIGHTNING
PROTECTION ELEMENTS TO BE INSTALLED, SEE
ELECTRICAL DETAILS FOR ADDITIONAL
REQUIREMENTS.
C. LIGHTNING PROTECTION CONDUCTORS SHALL
BE SIZED PER NFPA 780-20. PROVIDE A
LIGHTNING PROTECTION GROUND BUS.
D. UNDERGROUND METALLIC PIPING ENTERING
THE BUILDING SHALL BE BONDED TO THE
NEAREST DOWN-CONDUCTOR OR GROUND
ELECTRODE.
E. AIR TERMINALS HAVE BEEN LOCATED ON THE
ROOF TOP EQUIPMENT AS REQUIRED. IF THE
METAL THICKNESS OF AN OBJECT IS 3/18" OR
GREATER, AIR TERMINALS MAY BE ELIMINATED
IF THE OBJECT IS PROPERLY CONNECTED TO
THE SYSTEM.
Scale: 1" = 20'-0"
FIRST FLOOR POWER PLAN
Scale: 1" = 20'-0"
SECOND FLOOR POWER PLAN
NORTH
0 2010 40 1 1
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:1
:1
P M
C U s e rs
\h ts e n g \D o c u m e n ts
\E
-3
-V
A L o m a L in d a
R e p la c e
R o o f_ h ts e n g
M R
C W
.r v t
E-401
ELECTRICAL ENLARGEMENTS
6 7JWB
ROOF REPLACEMENT AND
LIGHTNING PROTECTION
VA LOMA LINDA HEALTHCARE SYSTEM
11201 BENTON ST, LOMA LINDA,
CA 92357 OCTOBER 12, 2022
100% BID DOCUMENTS
605-20-41121-330-Q31
JDM
Scale: No Scale
MAIN HOSPITAL ROOF ELECTRICAL EQUIPMENT
Scale: No Scale
CLC ROOF ELECTRICAL EQUIPMENT
3 3
1 COORDINATE WORK AROUND ANTENNAE
ARRAYS WITH OWNERS.
2 COORDINATE CONDUITS TO REMAIN WITH
ROOF WORK. CONDUITS FROM SOLAR
ARRAYS TO BE REMOVED.
3 EXISTING WALL-MOUNTED EQUIPMENT TO
REMAIN.
4 PAD MOUNTED EQUIPMENT TO REMAIN.
A. EXISTING PV/SOLAR-ARRAY SYSTEM TO BE
DISCONNECTED, REMOVED COMPLETELY AND
DISPOSED OF. REMOVE ALL PANELS,
MOUNTING BRACKETS, ASSOCIATED
CONDUITS & CONDUCTORS, DISCONNECTING
MEANS, COMBINING-BOXES, ETC. COVER, AND
DISCONNECT SOLAR PANELS DURING
DECONSTRUCTION. SOLAR PANELS REMAIN
ACTIVE DISCONNECTED AND PROPER STEPS
FOR DE-ENERGIZING THEM MUST BE TAKEN.
CERTAIN PV/SOLAR EQUIPMENT IS TO
REMAIN.
B. ACTIVE WIRELESS TELECOMMUNICATION
ANTENNAS POSE HEALTH-RISK TO
PERSONNEL. PROVIDE TRAINING ON SAFE
TECHNIQUES AND PROCEDURES FOR DE-
ENERGIZING AND REMOVING EQUIPMENT ON
HOSPTIAL ROOF.
C. SEE ARCHITECTURAL AND MECHANICAL ROOF
PLANS TO IDENTIFY EQUIPMENT NOT NOTED
HERE.
ECLEUL
FINISHED GRADE
TOP OF GROUND ROD, 24" BELOW FINAL
GRADE
GROUND ROD SHALL NOT BE ANGLED MORE
THAN 30° FROM VERTICAL WHERE POSSIBLE.
EXOTHERMIC WELD CONNECTION
TREATED WITH TWO (2) COATS COLD
GALVANIZED PAINT
3/4" DIAMETER COPPER CLAD STEEL GROUND
ROD 10' LONG.
30° MAX
AIR TERMINAL
NOTES:
A. ALL SPLICES BELOW GRADE SHALL BE THE EXOTHERMIC
WELD TYPE.
B. AIR TERMINALS SHALL EXTEND NO LESS THAN 24 INCHES
ABOVE THE ROOF.
C. ALL METAL EQUIPMENT ON THE ROOF SHALL BE BONDED
TO THE LIGHTNING PROTECTION SYSTEM.
D. THRU ROOF FLASHING SHALL BE COPPER WITH 8 INCH
ROUND BASE AND VERTICAL TUBE WITH NEOPRENE SEAL.
FLASHING SHALL BE THE PRODUCT OF THE
MANUFACTURER OF THE LIGHTNING PROTECTION SYSTEM.
A MEMBRANE FLASHING SHALL BE PROVIDED OVER THE
THRU ROOF FLASHING.
MAIN CONDUCTOR
CLIP CABLE SUPPORT
SEALING WASHER
(M
IN
TELEPHONE GROUNDING CONDUCTOR
GROUNDING ELECTRODE CONDUCTOR
CATV GROUNDING CONDUCTOR
LIGHTNING PROTECTION DOWN CONDUCTOR
NEMA 3R ENCLOSURE
MOUNTED TO EXTERIOR OF
BUILDING PER MANUFACTURER
STANDARDS
COPPER GROUND BAR
PER MANUFACTURER
STANDARDS
LIGHTNING PROTECTION
GROUND BUS
COMPRESSION OR SCREW
TO HOLD CONDUCTOR
LIGHTNING
PROTECTION
CONDUCTOR
-6"
-6"
ADHESIVE
METAL
SURFACE
METALLIC ENCLOSURE SUCH
AS HVAC UNIT ON ROOF
BOLT TO METAL
TYPICAL ADHESIVE PARAPET AIR TERMINAL
PLACEMENT.
18" MIN. PER VA SPEC.
IF AL FLASH IS USED, ADHESIVE
CONNECTION BONDING OF LIGHTNING
PROTECTION EQUIPMENT TO PARAPET.
18" MIN. PER VA SPEC.
IF AL FLASH IS USED, ADHESIVE
CONNECTION BONDING OF LIGHTNING
PROTECTION EQUIPMENT TO PARAPET.
STEP 1. FILE STRUCTURE CONNECTION AREA (3 IN. X 3. IN. MIN)
TO BARE SHINY METAL AND CLEAN.
NOTES:
1. ALL CABLES AND WELDS SHALL BE MINIMUM 3 INCHES APART.
2. STANDARD WELD CARTRIDGES SHALL BE USED FOR STEEL SURFACES. FOR DIP USE XF-19
WELD CARTRIDGES.
STEP 2. STRIP INSULATION FROM WIRE. ATTACH SLEEVE
(REQUIRED ON NO.4 AWG WIRE AND SMALLER).
STEP 3. HOLD MOLD FIRMLY WITH OPENING AWAY FROM
OPERATOR AND IGNITE WITH FLINT GUN.
STEP 4. REMOVE SLAG FROM CONNECTION AND PEEN
WELD FOR SOUNDNESS.
STEP 5. COVER CONNECTION AND EXPOSED STRUCTURE
SURFACE WITH AN EPOXY COATING.
HANDLE
GRAPHITE COVER
STARTING POWDER
METAL WELDING POWDER
GRAPHITE MOLD
WIRE
PIPE WALL
METAL DISC
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTIO
N
NOT FOR
CONSTRUCTIO
N
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1 /2
:1
:2
P M
C U s e rs
\h ts e n g \D o c u m e n ts
\E
-3
-V
A L o m a L in d a
R e p la c e
R o o f_ h ts e n g
M R
C W
.r v t
E-501
ELECTRICAL LIGHTNING PROTECTION
DETAILS
7 7JWB
ROOF REPLACEMENT AND
LIGHTNING PROTECTION
VA LOMA LINDA HEALTHCARE SYSTEM
11201 BENTON ST, LOMA LINDA,
CA 92357 OCTOBER 12, 2022
100% BID DOCUMENTS
605-20-41121-330-Q31
JDM
A. COPPER LIGHTNING PROTECTION SYSTEM
COMPONENTS SHALL NOT BE MOUNTED TO
ALUMINUM SURFACES UNLESS THEY ARE
ISOLATED BY ADHESIVE.
B. GROUNDED METAL BODIES WITHIN THE
BONDING DISTANCE DETERMINED BY NFPA
780 - 2020 SHALL BE BONDED TO THE SYSTEM
IN ACCORDANCE WITH CODE REQUIREMENTS.
C. ADHESIVE USED WITH AIR TERMINAL BASES
AND CONDUCTOR FASTENERS SHALL BE
COMPATIBLE WITH ROOFING MEMBRANE -
VERIFY WITH ROOFING CONTRACTOR.
D. ALL LIGHTNING PROTECTION MATERIALS
SHALL BE CLASS 1 OR CLASS 2.
Scale: N.T.S.
GROUND ROD DETAIL
Scale: N.T.S.
LIGHTNING PROTECTION AIR TERMINAL
Scale: N.T.S.
LIGHTNING PROTECTION GROUND BUS
Scale: N.T.S.
CLAMP DETAIL
Scale: N.T.S.
METALLIC ENCLOSURE TERMINATIONS
Scale: N.T.S.
LIGHTNING PROTECTION AIR PARAPET
Scale: N.T.S.
LIGHTNING PROTECTION AIR PARAPET WALL
Scale: N.T.S.
EXOTHERMIC WELD DETAIL
| Sheets |
| E-001 - ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS |
| ED101 - ELECTRICAL ROOF DEMOLITION PLAN |
| ED102 - ROOF ELECTRICAL DEMOLITION PLANS - CLC & ANNEX |
| EG101 - ROOF ELECTRICAL - LIGHTNING PROTECTION PLAN |
| EG102 - ROOF ELECTRICAL - LIGHTNING PROTECTION PLAN - CLC & ANNEX |
| E-401 - ELECTRICAL ENLARGEMENTS |
| E-501 - ELECTRICAL LIGHTNING PROTECTION DETAILS |
| 2022-10-10T12:54:09-0700 | |