This document is a technical specification for acoustical fiberglass batt insulation for interior wall assemblies, issued by the US Department of Veterans Affairs. The specification details requirements for Owens Corning's PINK Next Gen Fiberglas Sound Attenuation Batts Insulation, which must comply with multiple ASTM standards. The insulation is specified in two thickness options (3 1/2 and 2 1/2 inches), with dimensions of 16-24 inches wide and 96 inches long, and must be noncombustible with flame spread less than 25 and smoke development less than 50.
The specification provides comprehensive installation guidelines, including requirements for examination of installation areas, proper fitting techniques, and protection methods. Key installation instructions include friction-fitting insulation in stud cavities without gaps, carefully cutting around penetrations, providing supplementary support where needed, and securing the insulation using methods such as friction fit, stapling, taping, or using wire mesh. The document emphasizes the importance of following manufacturer instructions and protecting the insulation from damage until permanent construction is in place.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US Department of Veteran Affairs
07 21 16 - 1
SECTION 07 21 16
ACOUSTICAL FIBERGLASS BATT INSULATION
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies Fiberglass batt insulation for interior wall assemblies that require acoustical insulation with an STC rating.
1.2 RELATED WORK
A. Section 09 06 00, SCHEDULE FOR FINISHES
B. Section 09 22 16, NON-STRUCTURAL METAL FRAMING
C. SECTION 09 29 00 GYPSUM BOARD
1.3 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Manufacturers Literature and Data: Each material, indicating compliance with specification requirements.
C. Installer qualifications.
D. Manufacturer warranty.
E. Sustainable design certifications of each product.
1.4 DELIVERY AND STORAGE:
A. Delivery: Deliver materials to the job site in original packages, containers, or bundles bearing the brand name and manufacturer’s identification.
B. Storage: Store materials in dry locations with adequate ventilation, free from water, and in such a manner to permit easy access for inspection and handling.
C. Handling: Handle using procedures recommended by the manufacturer for materials and personnel.
1.5 ENVIRONMENTAL REQUIREMENTS
A. Do not proceed with application of materials when ambient temperature is less or greater than that recommended by the manufacturer.
1.6 SAFETY REQUIREMENTS
A. Protect insulation from weather and physical abuse until protected by permanent construction.
1.7 QUALITY ASSURANCE
A. Installer’s Qualifications: Work to be performed by installer having three (3) years’ experience for work relating to this section.
07 21 16 - 2
1.8 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by basic designation only.
B. ASTM International (ASTM):
ASTM E84…………….Flame Spread Surface Burning Characteristics
ASTM E136………..Combustion Characteristics
ASTM E119………….Fire Tested Wall Assemblies
ASTM C423………….Sound Transmission Class (STC)
PART 2 - PRODUCTS
2.1 MANUFACTURER
A. Basis-of-Design Manufacturer: Owens Corning Insulating Systems, LLC, Toledo, OH 43659; www.owenscorning.com.
2.2 MATERIALS
A. Basis of Design Product: PINK Next Gen Fiberglas Sound Attenuation
Batts Insulation
1. Unfaced glass-fiber acoustical insulation, complying with ASTM C665, Type I
2. Noncombustible per ASTM E 136.
3. Flame spread less than 25, smoke developed less than 50 per ASTM
E84.
4. Thickness: 3 1/2 inches (89 mm).
5. Thickness: 2 1/2 inches (64 mm).
6. Width: 16 to 24 inches (406 to 609 mm).
7. Length: 96 inches (2438 mm).
8. Dimensional Stability: Linear Shrinkage less than 0.1%
07 21 16 - 3
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine the areas and conditions under which work of this section will be installed. Verify that adjacent materials are dry and ready to receive insulation. Verify mechanical and electrical services within walls have been tested and inspected.
B. Provide written report listing conditions detrimental to performance of work in this section. Do not proceed with installation until unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Comply with manufacturer's installation instructions. Do not use unfaced insulation in exposed applications where there is potential for skin contact and irritation. Friction-fit blanket insulation in place, until the interior finish is applied. Install batts to fill entire stud cavity, with no gaps, voids, or areas of compression. If stud cavity is less than 8 feet in height, cut lengths to friction fit against floor and ceiling tracks. Walls with penetrations require that insulation be carefully cut to fit around outlets, junction boxes, and other irregularities.
B. Where walls are not finished on both sides or where insulation does not fill the cavity depth, install supplementary support to hold product in place.
C. Where insulation must extend higher than 8 feet, provide temporary support to hold product in place, until finish material is applied.
D. Secure insulation in place using one of the following methods: Friction fit; staple or nail facing flanges in place as needed, tape in place, retain in place with spindle fasteners, retain in place with wire mesh secured to framing members.
3.3 PROTECTION
A. Protect installed insulation from damage due to weather and physical abuse until protected by permanent construction.
- - - E N D - - -