Attachment 21 - Schedules Walla Walla System Replacement_Me.pdf

PDF 180 KB Posted

Attached to
J045--CON-NRM-687-21-106 Replace Mechanical and Plumbing Systems in Multiple Buildings
Solicitation number
36C26025R0065
Issued by

About this file

This document is a comprehensive mechanical and plumbing systems replacement schedule for the Veterans Health Administration (VISN 20) at the Walla Walla medical facility. The detailed technical schedules include multiple equipment specifications across various buildings, with a focus on HVAC, ventilation, heating, and cooling systems. Key equipment types documented include VRF (Variable Refrigerant Flow) indoor and outdoor units, energy recovery ventilators, split system heat pumps, steam unit heaters, electric duct heaters, make-up air units, and various air inlets, outlets, and louver systems. The schedules provide extensive technical details such as manufacturer models, electrical specifications, cooling/heating capacities, airflow measurements, filter efficiencies, and mounting configurations for equipment in Buildings 63, 65, 74, 81, 140, and T-7. The documentation represents 100% construction documents dated March 17, 2025, prepared by GDM, Inc. for a mechanical and plumbing system replacement project at the Walla Walla, Washington VA facility.

View the file

Other files

File Type Posted
36C26025R0065 0006.docx DOCX document
36C26025R0065 0004.docx DOCX document
Attachment 23 - WWMC- Topology - All Utilities 02.pdf PDF
Attachment 19 - Building T7 Walla Walla VAMC Electrical Plan.pdf PDF
Attachment 15 - Building 82 Walla Walla VAMC - Final Rev 1.pdf PDF
Attachment 14 - Building 81 Walla Walla VAMC - Final Rev 1.pdf PDF
Attachment 12 - Building 66 Walla Walla VAMC - Final Rev 1.pdf PDF
Attachment 10 - Building 63 Walla Walla VAMC - Final Rev 1.pdf PDF
Attachment 11 - Building 65 Walla Walla VAMC - Final Rev 1.pdf PDF
Attachment 16 - Building T1 Walla Walla VAMC - Final Rev 1.pdf PDF
36C26025R0065 0003.docx DOCX document
Attachment 22 - Photos Walla Walla VAMC.pdf PDF
Attachment 17 - Building T2 Walla Walla VAMC - Final Rev 1.pdf PDF
Attachment 20 - Building T7 Walla Walla System Replacement M.pdf PDF
Attachment 18 - Building T7 Walla Walla VAMC - Final Rev 1.pdf PDF
Attachment 13 - Building 74A Walla Walla VAMC - Final Rev 1.pdf PDF
Attachment 23 - WWMC- Topology - All Utilities.pdf PDF
36C26025R0065 0002.docx DOCX document
36C26025R0065 0001.docx DOCX document
Attachment 9 - PPQ NCO 20 687-21-106 CON Replace Mechanical and Plumbing.docx DOCX document
Attachment 6 - Contractor Rules of Behavior.pdf PDF
Attachment 5 - Wage Determination 6-06-2025.pdf PDF
36C26025R0065_1.docx DOCX document
Attachment 3 - DWGS 687-21-106 Replace Mechanical and Plumbing 06-20-2025.pdf PDF
Attachment 1 - SOW CON Replace Mechanical and Plumbing Systems 687-21-106_R0V2 02.pdf PDF
Attachment 8 - Limitations on Subcontracting 687-21-106 Mech and Plumbing.docx DOCX document
Attachment 7 - Divisional Price Breakout.xlsx XLSX spreadsheet
Attachment 4 - Calculations 687-21-106 WWW Replace Mechanical and Plumbing 03-17-2025.pdf PDF
Attachment 2 - SPECS 687-21-106 Replace Mechanical and Plumbing 06-25-2025.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT NUMBER

BUILDING NUMBER

DRAWING NUMBER

PROJECT TITLE

LOCATION

ISSUE DATE CHECKED BY DRAWN BY

DRAWING TITLE

APPROVED:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHASE

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

FLS

2025/03/17

100% CONSTRUCTION

DOCUMENTS

CONSULTANT

2025/03/17

GDM, Inc.

1308 NE 134th St, Suite A

Vancouver, WA 98685

P: 541.436.4723

ADAM GODDIN, PE

WWW.GDM-AE.COM

VETERANS HEALTH

ADMINISTRATION

VISN 20

A u to d e s k D o c s /2

-0

W a lla

W a lla

R e p la c e

M e c h a n ic a l S y s te m s /2

-0

W a lla W a lla

S y s te m R e p la c e m e n t_

M e c h a n ic a l_

.r v t

/3

/2

:5

:5

P

M

MH004

SCHEDULES REPLACE MECHANICAL AND

PLUMBING SYSTEMS

WALLA WALLA, WASHINGTON

687-21-106

KTJB

A/E

FULLY SPRINKLERED

6. PROVIDE CEILING PAN FOR T-BAR.

5. COORDINATE DIFFUSER TYPE WITH THE ARCHITECTURAL REFLECTED CEILING PLAN.

4. ALL SUPPLY AIR DIFFUSERS ARE 4-WAY DISTRIBUTION PATTERN UNLESS SHOWN OTHERWISE.

3. PROVIDE MANUAL AIR DAMPERS AT EACH BRANCH DUCT TO A SINGLE DIFFUSER, REGISTER, OR GRILLE.

2. FURNISH ALL PRODUCTS OF A SINGLE MANUFACTURER.

1. REFER TO PLANS FOR SIZE AND QUANTITY.

NOTES:

RG-2 PRICE 80 RETURN DUCT / GYP BOARD EGG CRATE ALUMINUM WHITE 1, 2, 3, 5

RG-1 PRICE 80 RETURN T-BAR EGG CRATE ALUMINUM WHITE 1, 2, 3, 5, 6

EG-2 PRICE 80 EXHAUST DUCT / GYP BOARD EGG CRATE ALUMINUM WHITE 1, 2, 3, 5

EG-1 PRICE 80 EXHAUST T-BAR EGG CRATE ALUMINUM WHITE 1, 2, 3, 5, 6

SD-2 PRICE 30 SUPPLY GYP BOARD GRILLE ALUMINUM WHITE 1, 2, 3, 5

SD-1 PRICE AMCD SUPPLY T-BAR MODULAR CORE ALUMINUM WHITE 1, 2, 3, 4, 5, 6

SYMBOL MANUFACTURER MODEL SERVICE MOUNTING TYPE STYLE MATERIAL FINISH NOTES

AIR INLETS AND OUTLETS SCHEDULE

3. PROVIDE WITH FACTORY PAINTED FINISH, COLOR SELECTED FROM MANUFACTURER'S STANDARD COLOR PALETTE. CONFIRM COLOR SELECTION WITH ARCHITECT.

2. PROVIDE LOUVER WITH SHEET METAL PLENUM BEHIND FULL LOUVER AREA, MINIMUM 6" DEPTH.

1. PROVIDE LOUVER WITH BIRD SCREEN ON INSIDE OF LOUVER.

NOTES:

65-L-4 GREENHECK ESD-435 EXHAUST AIR 210 12.00 12.00 6.00 50.00 0.50 0.08 980 SEE NOTES 1,2,3

65-L-3 GREENHECK ESD-435 OUTSIDE AIR 210 12.00 12.00 6.00 50.00 0.50 0.08 980 SEE NOTES 1,2,3

65-L-2 GREENHECK ESD-435 EXHAUST AIR 370 18.00 12.00 6.00 50.00 0.75 0.08 980 SEE NOTES 1,2,3

65-L-1 GREENHECK ESD-435 OUTSIDE AIR 370 18.00 12.00 6.00 50.00 0.75 0.08 980 SEE NOTES 1,2,3

63-L-2 GREENHECK ESD-435 EXHAUST AIR 310 12.00 18.00 6.00 50.00 0.75 0.08 980 SEE NOTES 1,2,3

63-L-1 GREENHECK ESD-435 OUTSIDE AIR 310 12.00 18.00 6.00 50.00 0.75 0.08 980 SEE NOTES 1,2,3

0T7-L-2 GREENHECK ESD-435 EXHAUST AIR 3,500 36.00 36.00 6.00 50.00 4.50 0.08 980 SEE NOTES 1,2,3

0T7-L-1 GREENHECK ESD-435 OUTSIDE AIR 3,500 42.00 36.00 6.00 50.00 5.25 0.08 980 SEE NOTES 1,2,3

LENGTH HEIGHT DEPTH % SQ FT (IN) (FPM)

SYMBOL MANUFACTURER MODEL SERVICE CFM SIZE (IN) FREE AREA MAX PD MAX VELOCITY FINISH NOTES

WEATHERPROOF LOUVER SCHEDULE

7. PROVIDE ELECTRICAL DISCONNECT, TO BE FIELD INSTALLED BY ELECTRICAL CONTRACTOR.

6. PROVIDE WITH CONDENSATE PUMP, TO BE POWERED BY INDOOR UNIT.

5. INDOOR UNITS ARE EQUIPED WITH AN INTERNAL WATER LEVEL DETECTION DEVICE CONFORMING TO UL 508 PER IPC 314.2.3.

4. THE CORRECTED CAPACITIES INCLUDE THE DE-RATE ASSOCIATED WITH INDOOR UNITS VS. OUTDOOR UNITS CONNECTED CAPACITY INDICATED ON THE OUTDOOR UNIT SCHEDULE FOR ASSOCIATED SYSTEMS.

3. SEE OUTDOOR UNIT SCHEDULE FOR OUTDOOR AMBIENT CONDITIONS, CONNECTED CAPACITY, AND OTHER FACTORS ASSOCIATED WITH CORRECTED CAPACITIES.

2. NOMINAL HEATING CAPACITIES ARE BASED ON INDOOR COIL EAT OF 70 °F (DB), OUTDOOR OF 43 °F (WB).

1. NOMINAL COOLING CAPACITIES ARE BASED ON INDOOR COIL EAT OF 80/67 °F (DB/WB), OUTDOOR AMBIENT TEMPERATURE OF 95 °F (DB).

NOTES:

65-IU-8 MITSUBISHI TPLFY008FM140A CEILING CASSETTE 65-OU-1 65-BC-1 315 - - - 8 6.41 5.70 80.1 66.8 62.4 75 97 67 9.00 4.29 68 - 81.2 70 80 25 - 208 1 0.28 15 28.9 1,2,3,4,5,6,7

65-IU-7 MITSUBISHI TPEFYP027MA144A DUCTED 65-OU-1 65-BC-1 880 - 0.60 - 27 21.63 18.60 80.1 66.8 59.5 75 97 67 30.00 14.30 69 - 84.3 70 80 45 MERV 13 208 1 2.88 15 67 1,2,3,4,5,6,7

65-IU-6 MITSUBISHI TPKFYP024KM142A WALL MOUNTED 65-OU-1 65-BC-1 915 - - - 24 19.28 17.83 80 67 61 75 97 67 27.00 12.85 70 - 83.5 70 80 200 - 208 1 0.63 15 46 1,2,3,4,5,6,7

65-IU-5 MITSUBISHI TPKFYP012LM140A WALL MOUNTED 65-OU-1 65-BC-1 295 - - - 12 9.64 7.11 80 67 56.5 75 97 67 13.50 6.42 70 - 90.8 70 80 35 - 208 1 0.24 15 24.5 1,2,3,4,5,6,7

65-IU-4 MITSUBISHI TPKFYP012LM140A WALL MOUNTED 65-OU-1 65-BC-1 295 - - - 12 9.64 7.11 80 67 56.5 75 97 67 13.50 6.42 70 - 90.8 70 80 45 - 208 1 0.24 15 24.5 1,2,3,4,5,6,7

65-IU-3 MITSUBISHI TPKFYP006LM140A WALL MOUNTED 65-OU-1 65-BC-1 190 - - - 6 4.82 3.78 80 67 60.6 75 97 67 6.70 3.19 70 - 86.1 70 80 105 - 208 1 0.24 15 24.5 1,2,3,4,5,6,7

65-IU-2 MITSUBISHI TPEFYP027MA144A DUCTED 65-OU-1 65-BC-1 880 - 0.60 - 27 21.60 18.77 80.2 66.7 59.4 75 97 67 30.00 14.30 67 - 82.6 70 80 90 MERV 13 208 1 2.88 15 67 1,2,3,4,5,6,7

UNIT) CONTROLLER) MBH (TOTAL) MBH (TOTAL) MBH (SENS) ( °F) ( °F) LAT ( °F) SP ( °F) DB WB MBH (TOTAL) MBH (TOTAL) ( °F) ( °F) LAT ( °F) SP ( °F) DB ( °F) (CFM)

(OUTDOOR (BC CFM RPM ESP HP NOMINAL CORRECTED CORRECTED EDB EWB DESIGN RM OA ( °F) NOMINAL CORRECTED EDB EWB DESIGN RM OA OA EFF VOLT PHASE MCA MOCP (LBS)

SYMBOL MANUFACTURER MODEL TYPE SERVED BY SERVED BY SUPPLY FAN COOLING HEATING MIN FILTER ELECTRICAL WEIGHT NOTES

VRF INDOOR FAN COIL UNIT SCHEDULE

1. PROVIDE WITH DIAMONDBACK BALL VALVES BV-SERIES, 700 PSIG WORKING PRESSURE, FULL PORT, R410A RATED TO ISOLATE INDIVIDUAL REFRIGERANT LINES AT UNIT.

NOTES:

65-BC-1 MITSUBISHI TCMBG0108SJ21N4 65-OU-1 SINGLE 8 116 208 1 0.74 15 64 1

CAPACITY (MBH) VOLT PHASE MCA MOCP (LBS)

SYMBOL MANUFACTURER MODEL SERVED BY TYPE PORTS CONNECTED ELECTRICAL WEIGHT NOTES

VRF BRANCH CIRCUIT CONTROLLER SCHEDULE

2. PROVIDE ELECTRICAL DISCONNECT, TO BE FIELD INSTALLED BY ELECTRICAL CONTRACTOR.

1. PROVIDE WITH MANUFACTURER'S DDC INTERFACE.

NOTES:

65-OU-1 MITSUBISHI TURYE0963ANF0AN BLDG 65 96 108 97 23.35 11.85 - 4.10 - 208 3 45 70 1,2

COOLING (MBH) (MBH) (DB) EER SEER IPLV COP HSPF VOLT PHASE MCA MOCP (LBS)

SYMBOL MANUFACTURER MODEL SERVES NOMINAL HEATING OA EFFICIENCY RATINGS ELECTRICAL WEIGHT NOTES

VRF OUTDOOR UNIT SCHEDULE

NOTES:

81-DSC-1 TRANE DNSB12020G0AA085 1,200 20 12 53 100 0.30 720.00 61.17 63.59 225 5.00 0.37 1.00 30.5

(IN) (IN) ( °F) ( °F) FPM ( °F) PSIG PSIG (IN)

WIDTH HEIGHT EDB LDB PD (IN) VELOCITY MBH LBS/HR TEMP INLET PRESSURE STEAM PD PIPE SIZE (LBS)

SYMBOL MANUFACTURER MODEL CFM DUCT SIZE AIR CAPACITY STEAM WEIGHT NOTES

DUCT STEAM HEATING COIL SCHEDULE

7. PROVIDE WITH DIRTY FILTER CONTACTS, LOW AIRFLOW SWITCH, PHASE LOSS DETECTION, MOTORIZED EXHAUST AIR DAMPER, WHEEL ROTATION DETECTION SENSOR, AND INDEPENDENT BLOWER CONTROL OPTIONS.

6. PROVIDE WITH EC FAN MOTORS AND DIRECT DRIVE PLENUM FANS.

5. PROVIDE WITH MERV 14 OPTION.

4. PROVIDE WITH NEW ROOF CURB.

3. PROVIDE WITH 120V CONVENIENCE/SERVICE RECEPTACLE MOUNTED TO UNIT EXTERIOR. POWER TO RECEPTACLE SHALL BE PROVIDED SEPARATELY FROM UNIT BY DIVISION 26 CONTRACTOR.

2. PROVIDE WITH LONWORKS DDC INTERFACE.

1. PROVIDE SINGLE POINT POWER SUPPLY CONFIGURATION.

NOTES:

140-ERV-3 ALDES PW15 BLDG 140 1,200 1.00 1,540 1.00 1,075 0.75 1,290 0.50 82.20 77.20 91.50 83.10 77.90 81.80 53.00 42.60 82.40 65.40 - - - MERV 13 MERV 13 480 3 2.8 3.5 15 ROOF 800 1,2,3,4,6,7

140-ERV-2 ALDES PW15 BLDG 140 1,350 1.50 1,566 1.00 1,190 1.00 1,320 0.50 82.20 76.80 80.80 81.20 76.10 90.70 51.50 41.70 82.80 65.40 - - - MERV 13 MERV 13 480 3 3.6 4.5 15 ROOF 800 1,2,3,4,6,7

140-ERV-1 ALDES PW15 BLDG 140 1,200 0.75 1,800 1.00 1,075 0.75 1,800 0.50 82.20 77.20 91.50 83.10 77.90 81.80 53.00 42.60 82.40 65.40 - - - MERV 13 MERV 13 480 3 3 3.5 15 ROOF 800 1,2,3,4 6,7

81-ERV-1 FANTECH VER BLDG 81 50 - - 0.56 - - - - - - - - - - - - - - 63.00 43.00 47.00 MERV 6 MERV 6 120 1 1.6 - 15 SUSPENDED -

65-ERV-2 MITSUBISHI TLGHF0300R BLDG 65 210 - - 0.56 - - - - - - - - - - 49.80 - 81.30 64.70 70.00 53.50 66.50 MERV 14 - 208 1 - 4.3 15 SUSPENDED 75 1,2,5

65-ERV-1 MITSUBISHI TLGHF0470R BLDG 65 370 - - 0.56 - - - - - - - - - - 49.80 - 81.10 64.60 73.00 57.00 69.00 MERV 14 - 208 1 - 5.1 15 SUSPENDED 110 1,2,5

63-ERV-1 MITSUBISHI TLGHF0470R BLDG 63 305 - - 0.56 - - - - - - - - - - 52.20 - 80.60 64.40 73.00 57.00 69.00 MERV 14 - 208 1 - 5.1 15 SUSPENDED 110 1,2,5

0T7-ERV-1 MITSUBISHI TLGHF0300R BLDG T-7 100 - - 0.56 - - - - - - - - - - 56.40 - 79.30 64.30 70.00 53.50 66.50 MERV 14 - 208 1 - 4.3 15 SUSPENDED 75 1,2,5

(IN) (IN) DB WB DB WB COOLING HEATING

CFM HP RPM ESP CFM HP RPM ESP SENSIBLE LATENT TOTAL SENSIBLE LATENT TOTAL WINTER SUMMER TEMPERATURE ENTHALPY ENTHALPY FILTER 1 FILTER 2 VOLT PHASE FLA MCA MOCP (LBS)

SYMBOL MANUFACTURER MODEL SERVES SUPPLY FAN EXHAUST FAN HEATING EXCHANGE EFFICIENCY (%) COOLING EXCHANGE EFFICIENCY (%) LEAVING SUPPLY TEMPERATURE TOTAL EXCHANGE EFFICIENCY (%) FILTER EFFICIENCY ELECTRICAL MOUNTING WEIGHT NOTES

ENERGY RECOVERY VENTILATOR SCHEDULE

2. PROVIDE WITH ALUMINUM EXTERIOR JACKET.

1. ASJ SHALL INCLUDE VAPOR BARRIER.

NOTES:

RETURN DUCTS, EXTERIOR, FROM UNIT TO BUILDING 12.00 - - 2.00 - X POLYISO BOARD 1,2

SUPPLY DUCTS, EXTERIOR, FROM UNIT TO BUILDING 12.00 - - 2.00 - X POLYISO BOARD 1,2

EXHAUST DUCTS INSIDE BUILDINGS (ERV SYSTEMS) 8.00 - - 3.00 - X FIBERGLASS WITH ASJ 1

OUTSIDE AIR DUCTS INSIDE BUILDING 12.00 - - 4.40 - X FIBERGLASS WITH ASJ 1

SUPPLY & RETURN AIR DUCTS INSIDE BUILDING 8.00 - - 3.00 - X FIBERGLASS WITH ASJ 1

SUPPLY & RETURN AIR DUCTS IN UNCONDITIONED SPACE 6.00 - - 2.50 - X FIBERGLASS WITH ASJ 1

(MIN) (MAX) (MIN, 1") (IN) INSIDE DUCT OUTSIDE DUCT

APPLICATION R-VALUE K-VALUE NRC THICKNESS INSULATION LOCATION TYPE NOTES

DUCT INSULATION & LINING SCHEDULE

1. PROVIDE WITH STEAM PRESSURE REDUCING VALVE AT UNIT INLET.

NOTES:

65-UH-1 BLDG 65 101 MODINE HSB24 CEILING/ HORIZONTAL THROW 8.75 18 12-3/8 13 5 0.04 1550 370 695 5 3/4" 23,280 24,000 225 10.00 70 °F 129 24 120 1 - 20 20 1

63-UH-3 BLDG 63 CRAWLSPACE MODINE HSB24 CEILING/ HORIZONTAL THROW 8.75 18 12-3/8 13 5 0.04 1550 370 695 5 3/4" 35,040 24,000 225 10.00 10 °F 88.47 36 120 1 - 20 20 1

63-UH-2 BLDG 63 B101 MODINE HSB24 CEILING/ HORIZONTAL THROW 8.75 18 12-3/8 13 5 0.04 1550 370 695 5 3/4" 35,040 24,000 225 10.00 10 °F 88.47 36 120 1 - 20 20 1

TYPE MAX HEIGHT (FT) THROW @ MAX HEIGHT HEIGHT LENGTH DEPTH HP RPM CFM VELOCITY (FPM) ID (IN) CORRECTED TOTAL TEMP VOLT PHASE MCA MOCP (LBS)

SYMBOL SERVICE ROOM MANUFACTURER MODEL MOUNTING DIMENSIONS (IN) FAN INLET

PRESSURE

(PSI)

ELEMENT OUTPUT (BTUH) ENTERING TD EAT LAT LBS/HR ELECTRICAL WEIGHT NOTES

STEAM UNIT HEATER SCHEDULE

3. PROVIDE WITH NEW ROOF CURB.

2. PROVIDE WITH 120V CONVENIENCE/SERVICE RECEPTACLE MOUNTED TO UNIT EXTERIOR. POWER TO RECEPTACLE SHALL BE PROVIDED SEPARATELY FROM UNIT BY DIVISION 26 CONTRACTOR.

1. PROVIDE WITH LONWORKS DDC INTERFACE.

NOTES:

140-MAU-1 AAON RQA-004-A-A-3 BLDG 140 1,380 1.00 1,224 0.50 63.00 43.00 47.00 100 81.00 21 19 75.2 49.4 MERV 8 MERV 14 480 3 4 5 15 582 1,2,3

(IN) (MBH) (MBH) ( °F) ( °F) ( °F) ( °F)

CFM HP RPM ESP TEMPERATURE ENTHALPY COOLING ENTHALPY HEATING INPUT OUTPUT EDB EWB LDB LWB FILTER 1 FILTER 2 VOLT PHASE FLA MCA MOCP (LBS)

SYMBOL MANUFACTURER MODEL SERVES SUPPLY FAN EXCHANGE EFFICIENCY (%) GAS HEATING FILTER EFFICIENCY ELECTRICAL WEIGHT NOTES

MAKE-UP AIR UNIT

NOTES:

140-FB-1 FANTECH FB6 6 MERV 13 11.5

SYMBOL MANUFACTURER MODEL DUCT SIZE FILTER EFFICIENCY WEIGHT NOTES

FILTER BOX SCHEDULE

7. PROVIDE WITH AIRFLOW MONITORING STATION AT VAV BOX INLET OR INTEGRATED WITH VAV BOX ASSEMBLY.

6. COORDINATE FIELD INSTALLATION WITH ELECTRICAL/LOW-VOLTAGE. ROUTE 16 GAUGE WIRE TO NEAREST ELECTRICAL SERVICE PANAL TO PROVIDE POWER TO EQUIPMENT.

5. PROVIDE TITUS ACOUSTIC LINING OR EQUIVALENT SOUND ATTENUATOR DUCT SECTION.

4. PROVIDE W/ NEMA 1 CONTROL BOX, ALLOW 36" CLEAR SPACE AT BOX FOR SERVICING.

3. PROVIDE WITH 24 V CONTROL TRANSFORMER FOR ACTUATOR.

2. MAX APD TO BE 0.25" APD.

1. MAX DISCHARGE/RADIATED NC TO BE 35.

NOTES:

140-VAV-134 ENVIRO-TEC SDR-WC BLDG 140: RM 134 225 30 0.02 4 100 180.00 150.00 55.00 105.00 1 0.5 0.3 5.5 1,2,3,4,5,6,7

74-VAV-13 TITUS DESV BLDG 074: RM 143, RM 141, RM 111, CORRIDOR 1,400 145 0.01 10 1,010 - - - - - - - - 1,2,3,4,5,6,7

74-VAV-12 TITUS DESV BLDG 074: RM 126 225 30 0.03 4 125 - - - - - - - - 1,2,3,4,5,6,7

74-VAV-11 TITUS DESV BLDG 074: WAITING AREA 1,050 120 0.05 9 920 - - - - - - - - 1,2,3,4,5,6,7

74-VAV-10 TITUS DESV BLDG 074: RM 108, RM 107 350 40 0.03 5 260 - - - - - - - - 1,2,3,4,5,6,7

74-VAV-09 TITUS DESV BLDG 074: RM 109, RM 109B 1,050 120 0.04 9 850 - - - - - - - - 1,2,3,4,5,6,7

74-VAV-08 TITUS DESV BLDG 074: RM 109, RM 109C, RM 190D 1,050 120 0.05 9 905 - - - - - - - - 1,2,3,4,5,6,7

74-VAV-07 TITUS DESV BLDG 074: RM 125, RM 124, RM 123 500 45 0.13 6 375 - - - - - - - - 1,2,3,4,5,6,7

74-VAV-06 TITUS DESV BLDG 074: RM 120, RM 118, CORRIDOR 650 70 0.07 7 450 - - - - - - - - 1,2,3,4,5,6,7

74-VAV-05 TITUS DESV BLDG 074: WAITING AREA 4,000 385 0.05 16 3,700 - - - - - - - - 1,2,3,4,5,6,7

74-VAV-04 TITUS DESV

BLDG 074: RM 138, RM 137, RM 136, RM 133, RM

132, RM 130

1,050 120 0.06 9 930 - - - - - - - - 1,2,3,4,5,6,7

74-VAV-03 TITUS DESV BLDG 074: RM 131, RM 130, RM 129, RM 127 650 70 0.09 7 500 - - - - - - - - 1,2,3,4,5,6,7

74-VAV-02 TITUS DESV BLDG 074: NURSE'S STATION, CORRIDOR 650 70 0.10 7 540 - - - - - - - - 1,2,3,4,5,6,7

74-VAV-01 TITUS DESV

BLDG 074: RM 128, RM 116, RM 115, RM 114, RM

113, RM 112, RM 110

900 90 0.02 8 695 - - - - - - - - 1,2,3,4,5,6,7

SERVED MAX CFM MIN CFM MIN PD IN UNIT (IN WG) SIZE (IN) EWT ( °F) LWT ( °F) EAT ( °F) LAT ( °F) ROWS GPM WPD (FT.W.G.) MBH

SYMBOL MANUFACTURER MODEL AREA AIR VALVE INLET

DESIGN CFM

HEATING COIL NOTES

VAV BOX SCHEDULE

Revisions: Date:

BID UPDATE 07/31/2025

3. OUTDOOR UNIT SHALL POWER INDOOR UNIT.

2. PROVIDE AND ATTACH LABEL TO UNIT WITH SYSTEM AND SPACE SERVED.

1. PROVIDE WITH INTERCONNECTION POWER & CONTROL WIRING BETWEEN INDOOR AND OUTDOOR UNITS.

NOTES:

81-OU-2 BLDG 81 TRANE/MITSUBISHI R-454B MXZ-2D20NLHZ 1.6 20,000 97 25,500 12.25 - 16.5 3.83 9.35 208 1 26.9 40 190 1,2

63-OU-2 BLDG 63 TRANE/MITSUBISHI R-454B MXZ-4D30NL 2.5 28,400 97 36,000 10.10 - 17.6 3.75 9.4 208 1 14 25 145 1,2,3

0T7-OU-3 T-7 EAST TRANE/MITSUBISHI R-454B MXZ-5D36NL 3 36,000 97 43,000 9.05 - 17.6 3.38 9.65 208 1 14 25 145 1,2,3

0T7-OU-2 T-7 WEST TRANE/MITSUBISHI R-454B TWA120K3DAA 10 129,000 97 105,000 11.50 14.10 - 3.4 - 208 3 39 50 432 1,2

TONS COOLING (BTUH) (DB) (BTUH) EER IEER SEER COP HSPF VOLT PHASE MCA MOCP (LBS)

SYMBOL SERVICE MANUFACTURER REFRIGERANT MODEL NOMINAL NOMINAL OSA HEATING EFFICIENCY RATINGS ELECTRICAL WEIGHT NOTES

SPLIT SYSTEM HEAT PUMP OUTDOOR UNIT SCHEDULE

6. PROVIDE WITH INTEGRAL DUCT SMOKE DETECTOR IN RETURN SIDE OF UNIT.

5. PROVIDE WITH MERV 13 FILTER.

4. INDOOR UNIT POWERED BY ASSOCIATED OUTDOOR UNIT.

3. PROVIDE WITH MANUFACTURERE'S WIRED WALL THERMOSTAT & CONTROLLER UNIT WITH INTEGRAL DIGITAL DISPLAY.

2. PROVIDE WITH LONWORKS DDC INTERFACE.

1. PROVIDE WITH CONDENSATE PUMP. CONDENSATE PUMP SHALL BE POWERED BY THE INDOOR UNIT.

NOTES:

81-IU-3 BLDG 81 81-OU-2 101M TRANE/MITSUBISHI SLZ-AF09NL CEILING R-454B 9,000.0 7,736.0 11,000.0 9,684.0 300 - - 25 208 1 - 0.29 1.0 15 31 1,2,3

81-IU-2 BLDG 81 81-OU-2 101K TRANE/MITSUBISHI SLZ-AF09NL CEILING R-454B 9,000.0 7,736.0 11,000.0 9,684.0 300 - - 25 208 1 - 0.29 1.0 15 31 1,2,3

63-IU-4 BLDG 63 63-OU-2 101C TRANE/MITSUBISHI SLZ-AF09NL CEILING R-454B 9,000.0 7,193.3 11,000.0 3,107.4 335 - - - 208 1 - 0.29 1.0 15 31 1,2,3,4

63-IU-3 BLDG 63 63-OU-2 101A TRANE/MITSUBISHI MSZ-GX12NL WALL R-454B 12,000.0 8,736.8 10,700.0 4,374.1 390 - - - 208 1 - 0.50 1.0 15 23 1,2,3,4

63-IU-2 BLDG 63 63-OU-2 101 TRANE/MITSUBISHI MSZ-GX15NL WALL R-454B 13,000.0 10,517.5 13,400.0 5,482.8 500 - - - 208 1 - 0.50 1.0 15 23 1,2,3,4

0T7-IU-6 T-7 0T7-OU-3 201 TRANE/MITSUBISHI MSZ-GX12NL WALL R-454B 12,000.0 11,264.7 14,100.0 9,057.4 390 - - - 208 1 - 0.50 1.0 15 23 1,2,3,4

0T7-IU-5 T-7 0T7-OU-3 202 TRANE/MITSUBISHI MSZ-GX06NL WALL R-454B 6,000.0 5,654.0 7,200.0 2,942.0 390 - - - 208 1 - 0.50 1.0 15 23 1,2,3,4

0T7-IU-4 T-7 0T7-OU-3 109 TRANE/MITSUBISHI MSZ-GX06NL WALL R-454B 6,000.0 5,654.0 7,200.0 2,942.0 390 - - - 208 1 - 0.50 1.0 15 23 1,2,3,4

0T7-IU-3 T-7 0T7-OU-3 101 TRANE/MITSUBISHI MSZ-GX06NL WALL R-454B 6,000.0 5,654.0 7,200.0 2,942.0 390 - - - 208 1 - 0.50 1.0 15 23 1,2,3,4

0T7-IU-2 T-7 0T7-OU-2 103 TRANE/MITSUBISHI TWE120K3BAA DUCTED R-545B 124,140.0 98,100.0 105,000.0 69,740.0 3500 1 926 1300 208 3 2 6.8 9.0 15 454 1,2,3,5,6

TYPE BTUH COOLING (BTUH) BTUH BTUH OSA VOLT PHASE HP FLA MCA MOCP (LBS)

SYMBOL SERVICE SERVED BY ROOM MANUFACTURER MODEL TYPE REFRIGERANT TOTAL COOLING CORRECTED SENSIBLE HEATING CORRECTED HEATING CFM ESP RPM MIN ELECTRICAL WEIGHT NOTES

SPLIT SYSTEM HEAT PUMP INDOOR UNIT SCHEDULE

2. LOCATE DUCT HEATER ON OUTSIDE AIR DUCT SERVING 0T7-IU-2.

1. PROVIDE WITH DOOR INTERLOCKING DISCONNECT SWITCH, FAN INTERLOCK CIRCUIT, ADJUSTABLE AIRFLOW PROVING SWITCH, & DUCT

THERMOSTAT OPTIONS.

NOTES:

65-DH-2 GREENHECK IDHE 10x10 210 3.00 1 208 1 - 1

65-DH-1 GREENHECK IDHE 10x10 370 5.00 1 208 1 - 1

0T7-DH-1 GREENHECK IDHE 24x18 3500 14.00 1 480 3 - 1,2

SIZE (IN) KW STAGES VOLT PHASE (LBS)

SYMBOL MANUFACTURER MODEL DUCT CFM ELECTRICAL WEIGHT NOTES

ELECTRIC DUCT HEATER SCHEDULE

Sheets
MH004 - SCHEDULES