The document is a mechanical plan drawing for Building T-7 at the Walla Walla Veterans Affairs facility, depicting second floor and attic mechanical system layouts. The drawing, prepared by GDM, Inc. for the Veterans Health Administration VISN 20, shows detailed HVAC and refrigerant piping configurations, including specific air handling units (0T7-IU-1, 0T7-IU-2, 0T7-IU-5, 0T7-IU-6), air terminal units, and associated ductwork with airflow volumes ranging from 25 to 3500 CFM. The plan includes notations for new temperature sensor installations, existing access hatches, and specifies refrigerant piping details such as liquid and gas line sizes, with the project identified as a mechanical and plumbing systems replacement for Building T-7.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(E) 10"ø SA
(E) REFRIGERANT PIPING DN
TE
(E) INDOOR UNIT 0T7-IU-1
16"x26"SD-2
1510 CFM
24"x14"RG-2
1500 CFM
24"x14"RG-2
1500 CFM
16"x26"SD-2
1510 CFM
18"x14" SA
16"x14" RA
14"x18" SA
16"x14" RA
24"x18" SA
18"x14" SA
REFRIGERANT PIPING UP/DN
1/4" RS (LIQUID)
3/8" RR (GAS)
0T7-IU-6
0T7-IU-5
24"x18" OSA
36"x36"0T7-L-2
3500 CFM
24"x18" EA
REFRIGERANT PIPING DN
0T7-IU-2
T7.1
T7.A
(E) ACCESS HATCH
TE
MH006
(TYP)
MH007
(TYP)
6"x6"SD-2
25 CFM
(E) SPEAKER BOX
(E) ACCESS HATCH
(E) 24"x48"
GRILLE
6"x6"SD-2
25 CFM
6"x6"EG-2
25 CFM
6"x6"EG-2
25 CFM
MH006
(TYP)
6"x6" EA UP/DN
6"x6" OSA UP/DN
MH007
(TYP)
3/4" COND DN
REFRIGERANT PIPING
42"x36"0T7-L-1
3500 CFM
MH007
(TYP)
0T7-DH-1
T7.1
T7.A
0T7-ERV-1
(E) ACCESS HATCH
T7-WC-2
T7-WC-1
6"x6" EA DN
6"x6" OSA DN
6"x6" OSA
6"x6" EA
6"x6" EA DN TO
AIR TERMINAL
6"x6" EA DN TO
AIR TERMINAL
6"x6" OA DN TO
AIR TERMINAL
6"x6" OA DN TO
AIR TERMINAL
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
2025/03/17
100% CONSTRUCTION
DOCUMENTS
CONSULTANT
2025/03/17
GDM, Inc.
1308 NE 134th St, Suite A
Vancouver, WA 98685
P: 541.436.4723
ADAM GODDIN, PE
WWW.GDM-AE.COM
VETERANS HEALTH
ADMINISTRATION
VISN 20
A u to d e s k D o c s /2
-0
W a lla
W a lla
R e p la c e
M e c h a n ic a l S y s te m s /2
-0
W a lla W a lla
S y s te m R e p la c e m e n t_
M e c h a n ic a l_
.r v t
/3
/2
:2
:2
P
M
0T7-MH-102
BLDG T-7 MECHANICAL PLANS REPLACE MECHANICAL AND
PLUMBING SYSTEMS
WALLA WALLA, WASHINGTON
687-21-106
KTJB
A/E
FULLY SPRINKLERED
1/4" = 1'-0"1
BLDG T-7 SECOND FLOOR MECHANICAL PLAN
T-7
PLAN NOTES
1 PROVIDE NEW TEMPERATURE SENSOR INSTALLED AT 4'-6"AFF. CONNECT TO
DDC SYSTEM.
1/4" = 1'-0"2
BLDG T-7 ATTIC MECHANICAL PLAN
NORTH
NORTH
Revisions: Date: