This is a technical drawing document detailing environmental hazards and abatement requirements for Building 109 at the Michael E. DeBakey Veterans Affairs Medical Center (VAMC) in Houston, Texas, as part of a construction project involving the installation of a new overhead paging system.

The project, identified as Drawing Number H1091 (Project 580-25-101), requires contractors to perform work within Building 109 across three levels while managing significant asbestos-containing material (ACM) hazards. The scope includes approximately 160 penetrations across the three levels (18 on Level 0, 42 on Level 1, and 20 on Level 2) plus 80 negative pressure mini-enclosures to accommodate new telecommunications infrastructure for the paging system. All drywall walls and ceilings contain applied ACM joint compound and texture; penetrations must be made using manual means within negative pressure enclosures, with encapsulant applied at all through-penetrations in double-sided drywall walls. The existing ceiling grid and wall angle edging must be maintained. Additional hazardous materials present throughout the building but not anticipated to be impacted include black mastic underlying floor tile (presumed asbestos-containing), all beige 12" x 12" floor tile (ACM with underlying asbestos black mastic), and mastic on wooden beams at the penthouse level. Work likely to impact these materials must be performed by a licensed abatement contractor. The document requires contractors to replace ceiling tiles at the end of each work shift outside rated construction barriers or implement 1-hour fire-rated separation between construction areas and occupied portions of the building.

View the file

Other files

File Type Posted
36C25626R0067 0005.docx DOCX document
36C25626R0067 0004.docx DOCX document
36C25626R0067 0003.docx DOCX document
36C25626R0067 0002.docx DOCX document
Sign in Sheet 580-25-101.jpg JPG image
DOL Wage Determinations dated 5-18-26.pdf PDF
36C25626R0067 0001.docx DOCX document
SF24 Bid Bond.pdf PDF
580-25-101 Project Specifications.pdf PDF
36C25626R0067_1.docx DOCX document
DOL Wage Determinations TX20260253 dated 1-2-26.pdf PDF
580-25-101 Statement of Work.docx DOCX document
580-25-101 Project Drawings.pdf PDF
36C25626R0067.docx DOCX document
Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

Veterans Health

Administration

VA FORM 08-6231

DRAWING TITLE PROJECT TITLE

LOCATION

DATE CHECKED DRAWN

PROJECT NUMBERCONSULTANTS:

DRAWING #

VA HEALTH CARE SYSTEM APPROVAL:

ARCHITECT:

FULLY SPRINKLERED

1 2 � 4 � 6 � 8 �

1 2 � 4 � 6 � 8 �

STAMP:

DRAWING NUMBER

BUILDING NUMBER

ARCHITECT MECH / ELEC / PLUMB / TELECOM

SPUR DESIGN

2519 MADISON AVE., STE 100

KANSAS CITY, MO 64108

(913) 369-7200

SPUR DESIGN

312 SW 25TH STREET

OKLAHOMA CITY, OK 73109

(405) 842-6100

FIRE PROTECTION ENGINEER

RATED ENGINEERING

609 S. KELLY AVENUE, STE H2

EDMOND, OK 73003

(405) 210-5814

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

11140 S TOWNE SQUARE, STE 100

ST. LOUIS, MO 63123

(314) 917-0148

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

H2B ENGINEERS, INC.

1225 NORTH LOOP WEST, # 800

HOUSTON, TEXAS 77008

(713) 864-2900

TEXAS FIRM REGISTRATION #: 8856

H2B#: 23-133

2/1 9/2

4 9

:13 :29

A M

BUILDING 109 - ENVIRONMENTAL HAZARDS

AND ABATEMENT

CD 13 OF 231JR

OVERHEAD PAGING SYSTEM

07/21/2025

580-25-101

MICHAEL E. DEBAKEY VAMC

2002 HOLCOMBE BLVD

HOUSTON, TX 77030 H1091

No. REVISION DESCRIPTION DATE

ENVIRONMENTAL HAZARDS - BUILDING 109 - LEVEL 01ENVIRONMENTAL HAZARDS - BUILDING 109 - LEVEL 12

ENVIRONMENTAL HAZARDS - BUILDING 109 - LEVEL 23

HAZARDOUS MATERIAL KEYNOTES

DRYWALL WALLS AND CEILINGS HAVE APPLIED ACM DRYWALL JOINT COMPOUND

AND/OR INFREQUENT APPLICATION OF ACM TEXTURE. USING MANUAL MEANS WITHIN A

NEGATIVE PRESSURE ENCLOSURE, PROVIDE PENETRATIONS THROUGH THE DRYWALL

AS NECESSARY TO WIRE AND INSTALL FIXTURES FOR NEW OVERHEAD PAGING

SYSTEM AS SHOWN BY TELECOMMUNICATIONS DRAWINGS. APPLY ENCAPSULANT AT

AND WITHIN THROUGH NORMALLY DOUBLE SIDED DRYWALL WALLS. EXISTING CEILING

GRID IS TO BE MAINTAINED, INCLUDING CEILING GRID WALL ANGLE (EDGING) AS

ATTACHED TO ACM DRYWALL WALL SYSTEM. COORDINATE LOCATION AND EXTENTS

OF PENETRATIONS WITH THE GENERAL CONTRACTOR AND INSTALL PENETRATIONS IN

THE APPROXIMATE QUANTITIES OF, 18 PENETRATIONS ON LEVEL 0, 42 PENETRATIONS

ON LEVEL 1, 20 PENETRATIONS ON LEVEL 2 AND 80 NEGATIVE PRESSURE

MINI-ENCLOSURES.

ASBESTOS DRYWALL CEILING SYSTEM. WHERE KEYNOTE H1 IS PRESENT, PERFORM

WORK IN ACCORDANCE WITH KEYNOTE H1 AND THE CEILING PENETRATIONS ARE

INCLUDED IN ESTIMATED TOTALS.

INTERMITTENT SMALL NUMBERS OF DRYWALL CEILING PANELS MAY BE PRESENT IN

SUSPENDED ACOUSTICAL CEILING GRID. WHERE A DRYWALL PANEL IS ENCOUNTERED

WITH APPLIED DRYWALL JOINT COMPOUND AND/OR TEXTURE, DO NOT DISTURB AND

REMOVAL IS TO BE PERFORMED BY THE LICENSED ABATEMENT CONTRACTOR.

H1

12010

108A

FH

FH

FH2

KEY PLAN - BLDG 109

H1 H1

H1

H1

H1

H1H1

H1

H1

H1

H1

H1

H1

H1

H1

H1 H1 H1

H1

H1

H1 H1

H1

H1

H1 H1 H1

H1H1

H1

H1H1 H1 H1

H1

H1

H1

H1

H1

H1 H1 H1 H1H1

H1

H1

H1

H1

100% BID DOCUMENTS

H2

H3

HAZARDOUS MATERIAL NOTES

THE FOLLOWING HAZARDOUS MATERIALS ARE PRESENT THROUGHOUT BUILDING 109

BUT ARE NOT ANTICIPATED TO BE IMPACTED WITHIN THE TARGETED SCOPE OF WORK.

SHOULD THESE MATERIALS OR ADDITIONAL SUSPECT MATERIALS BE ENCOUNTERED,

STOP WORK IMMEDIATELY AND CONTACT VA COR FOR DIRECTION.

DRYWALL WITH JOINT COMPOUND AND TEXTURE IS ASBESTOS CONTAINING. ANY

WORK LIKELY TO IMPACT WALL SYSTEMS THROUGHOUT WILL REQUIRE

ABATEMENT BY A LICENSED ABATEMENT CONTRACTOR

BLACK MASTIC UNDERLYING FLOOR TILE OR OTHER COVERINGS IS GENERALLY

PRESENT THROUGHOUT BUILDING AND PRESUMED TO BE ASBESTOS

CONTAINING. WORK LIKELY TO IMPACT ASBESTOS BLACK MASTIC ON FLOOR IS

TO BE PERFORMED BY A LICENSED ABATEMENT CONTRACTOR. ALL BEIGE 12" X

12" FLOOR TILE IS CONSIDERED AN ASBESTOS CONTAINING MATERIAL(ACM) AND

ASBESTOS BLACK MASTIC (PACM) WILL BE UNDERLYING.

MASTIC ON WOODEN BEAMS AT THE PENTHOUSE LEVEL IS ASBESTOS

CONTAINING.

NOTE: AT END OF EACH SHIFT, THE REPLACEMENT OF CEILING TILES IS REQUIRED

WITHIN WORK AREAS OUTSIDE OF A RATED CONSTRUCTION BARRIER. IF THE TILES

CANNOT BE REPLACED, THE SPRINKLER SYSTEM MAY BE CONSIDERED OUT OF

SERVICE IN THESE AREAS AND 1-HOUR FIRE RATED SEPARATION WILL BE REQUIRED

BETWEEN THE CONSTRUCTION AREA AND THE OCCUPIED PORTIONS OF THE BUILDING.

H1 H2

H1

H1 H1 H1

H1

H3

H2

H1

H1

H1

H1H1

H1

H1 H1

H2 H2 H2 H2 H2 H2

H2 H2

H2

H2

H2

H2

H2

H2

H2 H2 H2 H2 H2 H2

H2

H2 H2 H2

H2 H2 H2 H2 H2

H2

H2

H2 H2

H2 H2

H2

H2

H2 H2 H2 H2

H1

H1

1 BUILDING 109 ABATEMENT UPDATE 06/26/2026