087100 Door Hardware Revised.pdf

PDF 84 KB Posted

Attached to
Y1DA--Project No. 580-17-121 Upgrade/Renovate/Relocate Sterile Processing Services (SPS)
Solicitation number
36C25621R0014
Issued by

About this file

This solicitation requests proposals for an upgrade, renovation, and relocation project for Sterile Processing Services (SPS) at the Michael E. DeBakey Veterans Affairs Medical Center in Houston, Texas. The project scope includes renovating approximately 16,500 square feet of space for SPS, logistics, and laundry in the basement of Building 100. All construction work must adhere to the latest JCAHO, NFPA, and life safety standards and be performed without disrupting medical center operations. Proposals are due by the date specified in the solicitation. The awarded firm will be responsible for renovating the designated areas to support SPS operations in compliance with regulatory requirements. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16 is the contracting agency.

View the file

Other files

File Type Posted
36C25621R0014 0005.docx DOCX document
580-17-12_Renovate SPS_Project Drawings_1-15-21.pdf PDF
36C25621R0014 0004.docx DOCX document
36C25621R0014 0003.docx DOCX document
QH102.pdf PDF
36C25621R0014 0002.pdf PDF
Area B-F-compressed.pdf PDF
S3185_Steris_Vision1327-CartWash.pdf PDF
S9610_Steris_PrepTable.pdf PDF
S5505A_STERRAD-100NX.pdf PDF
S0235_Steris_Amsco400.pdf PDF
Area B-G-compressed.pdf PDF
Slab Infill Detail.pdf PDF
S0940_Steris_Amsco7052HPWasher.pdf PDF
105113 MetalLockers.docx DOCX document
Clarifications 12-15-2020.pdf PDF
S9815B_Steris_Amsco600.pdf PDF
Equipment Drawing - Vision 1327 - STEAM PIT.pdf PDF
S5505B_STERRAD-100S.pdf PDF
20201211_ADDENDUM_1.pdf PDF
Site Visit Attendees.docx DOCX document
DE-1R.pdf PDF
S5505C_STERRAD-NX.pdf PDF
36C25621R0014 0001.pdf PDF
580-17-121_Renovate SPS_Combined Specifications.pdf PDF
DOL Wate Determinations TX20200253 dated 9-11-20.pdf PDF
36C25621R0014.pdf PDF
580-17-121_Renovate SPS_Specifications.pdf PDF
Site Visit Instructions _ Renovate SPS_1.docx DOCX document
580-17-121 _ Renovate SPS _ Statement of Work.docx DOCX document
SF24 BID BOND.pdf PDF
580-17-121 _ Renovate SPS _ Drawings.pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Michael E. Debakey VAMC August 21, 2020 Upgrade/Renovate/Relocate SPS Bid Documents Houston, TX Project No. 580-17-121

08-01-19

08 71 00-1

SECTION 08 71 00

DOOR HARDWARE

PART 1 - GENERAL

1.1 DESCRIPTION

A. Door hardware and related items necessary for co mplete installation and operation of doors.

1.2 RELATED WORK

A. Caulking: Section 07 92 00 JOINT SEALANTS.

B. Application of Hardware: Section 08 14 00, WOOD DOORS Section 08 11 13, HOLLOW METAL DOORS AND FRAMES Section 08 71 13, AUT OMATIC DOOR

OPERATORS Section

C. Finishes: Section 09 06 00, SCHEDULE FOR FINISHE S.

D. Painting: Section 09 91 00, PAINTING.

E. Card Readers: Section 28 13 00, PHYSICAL ACCESS CONTROL SYSTEMS.

F. Electrical: Division 26, ELECTRICAL.

G. Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.

1.3 GENERAL

A. All hardware shall comply with UFAS, (Uniform Fe deral Accessible

Standards) unless specified otherwise.

B. Provide rated door hardware assemblies where req uired by most current version of the International Building Code (IBC).

C. Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 f or exit doors, as well as to other requirements specified. Provide ha rdware listed by UL, except where heavier materials, large size, or bett er grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recogni zed testing agency may be submitted showing that hardware has been tes ted in accordance with UL test methods and that it conforms to NFPA r equirements.

D. Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to th e fabricator of these items in sufficient time so as not to delay t he construction.

E. The following items shall be of the same manufac turer, except as otherwise specified:

1. Mortise locksets.

2. Hinges for hollow metal and wood doors.

3. Surface applied overhead door closers.

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-2

4. Exit devices.

5. Floor closers.

1.4 WARRANTY

A. Automatic door operators shall be subject to the terms of FAR Clause

52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:

1. Locks, latchsets, and panic hardware: 5 years.

2. Door closers and continuous hinges: 10 years.

1.5 MAINTENANCE MANUALS

A. In accordance with Section 01 00 00, GENERAL REQ UIREMENTS Article titled "INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instruction s with the submittal documentation.

1.6 SUBMITTALS

A. Submittals shall be in accordance with Section 0 1 33 23, SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. Submit 6 copies of the sc hedule per Section

01 33 23. Submit 2 final copies of the final approv ed schedules to VAMC

Locksmith as record copies (VISN Locksmith if the V AMC does not have a locksmith).

B. Hardware Schedule: Prepare and submit hardware s chedule in the following form:

Hardware Item

Quantity Size Reference Publication Type No.

Finish Mfr.

Name and Catalog No.

Key Control Symbols

UL Mark (if fire rated and listed)

ANSI/BHMA

Finish Designation

C. Samples and Manufacturers' Literature:

1. Samples: All hardware items (proposed for the pr oject) that have not been previously approved by Builders Hardware Manuf acturers

Association shall be submitted for approval. Tag an d mark all items with manufacturer's name, catalog number and projec t number.

2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-3

D. Certificate of Compliance and Test Reports: Subm it certificates that hardware conforms to the requirements specified her ein. Certificates shall be accompanied by copies of reports as refere nced. The testing shall have been conducted either in the manufacture r's plant and certified by an independent testing laboratory or c onducted in an independent laboratory, within four years of submit tal of reports for approval.

1.7 DELIVERY AND MARKING

A. Deliver items of hardware to job site in their o riginal containers, complete with necessary appurtenances including scr ews, keys, and instructions. Tag one of each different item of har dware and deliver to the COR for reference purposes. Tag shall identify items by Project

Specification number and manufacturer's catalog num ber. These items shall remain on file in the COR's office until all other similar items have been installed in project, at which time the C OR will deliver items on file to Contractor for installation in pre determined locations on the project.

1.8 PREINSTALLATION MEETING

A. Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contracto r and Installer, Architect, Project Engineer and VA Locksmith, Hardw are Consultant, and

Hardware Manufacturer’s Representative. Review the following:

1. Inspection of door hardware.

2. Job and surface readiness.

3. Coordination with other work.

4. Protection of hardware surfaces.

5. Substrate surface protection.

6. Installation.

7. Adjusting.

8. Repair.

9. Field quality control.

10. Cleaning.

1.9 INSTRUCTIONS

A. Hardware Set Symbols on Drawings: Except for pro tective plates, door stops, mutes, thresholds and the like specified her ein, hardware requirements for each door are indicated on drawing s by symbols.

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-4

Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware it ems applicable to a door type.

B. Keying: All cylinders shall be keyed into existi ng Grand Master Key

System. Provide removable core cylinders that are r emovable only with a special key or tool without disassembly of knob or lockset. Cylinders shall be 7 pin type. Keying information shall be furnished at a later date by the COR.

C. Keying: A new Great Grandmaster key shall be est ablished for this project. The key system shall be small format (Best size and profile) removable core type as previously described. The ke y blanks shall be protected by a utility patent with a minimum seven years remaining on the patent from the start of construction, and prot ected by contract-controlled distribution. The manufacturer shall fur nish code pattern listings in both paper and electronic formats so ke ys may be reproduced by code.; provide electronic format in file type re quired by project’s key control software. The manufacturer shall desig n the new key system with the capacity to rekey the existing system and also provide for 25 percent expansion capability beyond this requiremen t. Submit a keying chart for approval showing proposed keying layout a nd listing expansion capacity.

1. Keying information will be furnished to the Cont ractor by the COR.

2. Supply information regarding key control of cyli nder locks to manufacturers of equipment having cylinder type loc ks. Notify the

COR immediately when and to whom keys or keying inf ormation is supplied. Return all such keys to the Resident Engi neer.

1.10 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of thi s specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.

B. American Society for Testing and Materials (ASTM ):

E2180-07................Standard Test Method for De termining the

Activity of Incorporated Antimicrobial Agent(s)

In Polymeric or Hydrophobic Materials

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-5

C. American National Standards Institute/Builders H ardware Manufacturers

Association (ANSI/BHMA):

A156.1-06...............Butts and Hinges

A156.2-03...............Bored and Pre-assembled Loc ks and Latches

A156.4-08...............Door Controls (Closers)

A156.5-14...............Cylinders and Input Devices for Locks.

A156.8-05...............Door Controls-Overhead Stop s and Holders

A156.11-14..............Cabinet Locks

A156.13-05..............Mortise Locks and Latches S eries 1000

A156.16-08..............Auxiliary Hardware

A156.17-04 .............Self-Closing Hinges and Piv ots

A156.18-06..............Materials and Finishes

A156.22-05..............Door Gasketing and Edge Sea l Systems

A156.23-04..............Electromagnetic Locks

A156.25-07 .............Electrified Locking Devices

A156.26-06..............Continuous Hinges

A156.28-07 .............Master Keying Systems

A156.30-03 .............High Security Cylinders

A156.31-07 .............Electric Strikes and Frame Mounted Actuators

A156.36-10..............Auxiliary Locks

A250.8-03...............Standard Steel Doors and Fr ames

D. National Fire Protection Association (NFPA):

80-10...................Fire Doors and Other Openin g Protectives

101-09..................Life Safety Code

E. Underwriters Laboratories, Inc. (UL):

Building Materials Directory (2008)

PART 2 - PRODUCTS

2.1 BUTT HINGES

A. ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version (e.g., some types of swing-clear hinges). T he following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:

1. Exterior Doors: Type A2112/A5112 for doors 900 m m (3 feet) wide or less and Type A2111/A5111 for doors over 900 mm (3 feet) wide.

Hinges for exterior outswing doors shall have non-r emovable pins.

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-6

Hinges for exterior fire-rated doors shall be of st ainless steel material.

2. Interior Doors: Type A8112/A5112 for doors 900 m m (3 feet) wide or less and Type A8111/A5111 for doors over 900 mm (3 feet) wide.

Hinges for doors exposed to high humidity areas (sh ower rooms, toilet rooms, kitchens, janitor rooms, etc. shall b e of stainless steel material.

B. Provide quantity and size of hinges per door lea f as follows:

1. Doors up to 1210 mm (4 feet) high: 2 hinges.

2. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.

3. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.

4. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm

(4-1/2 inches x 4-1/2 inches) hinges.

5. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inc hes) wide, standard weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).

6. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).

7. Provide heavy-weight hinges where specified.

8. At doors weighing 330 kg (150 lbs.) or more, furnis h 127 mm

(5 inch) high hinges.

C. See Articles "MISCELLANEOUS HARDWARE" and "HARDW ARE SETS" for pivots and hinges other than butts specified above and con tinuous hinges specified below.

2.2 CONTINUOUS HINGES

A. ANSI/BHMA A156.26, Grade 1-600.

1. Listed under Category N in BHMA's "Certified Pro duct Directory."

B. General: Minimum 0.120-inch- (3.0-mm-) thick, h inge leaves with minimum overall width of 4 inches (102 mm); fabrica ted to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete

C. Continuous, Barrel-Type Hinges: Hinge with knuc kles formed around a

Teflon-coated 6.35mm (0.25-inch) minimum diameter p in that extends entire length of hinge.

1. Base Metal for Interior Hinges: Stainless steel.

2. Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel.

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-7

3. Provide with non-removable pin (hospital tip opt ion) at lockable outswing doors.

4. Where required to clear adjacent casing, trim, a nd wall conditions and allow full door swing, provide wide throw hinge s of minimum width required.

5. Provide with manufacturer’s cut-outs for separat e mortised power transfers and/or mortised automatic door bottoms wh ere they occur.

6. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy a ccess to wiring connections.

7. Where models are specified that provide an integ ral wrap-around edge guard for the hinge edge of the door, provide manuf acturer’s adjustable threaded stud and machine screw mechanis m to allow the door to be adjusted within the wrap-around edge gua rd.

2.3 DOOR CLOSING DEVICES

A. Closing devices shall be products of one manufac turer for each type specified.

2.4 DOOR STOPS

A. Conform to ANSI A156.16.

B. Provide door stops wherever an opened door or an y item of hardware thereon would strike a wall, column, equipment or o ther parts of building construction. For concrete, masonry or qua rry tile construction, use lead expansion shields for mounti ng door stops.

C. Where cylindrical locks with turn pieces or push buttons occur, equip wall bumpers Type L02251 (rubber pads having concav e face) to receive turn piece or button.

D. Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere.

E. Provide stop Type L02011, as applicable for exte rior doors. At outswing doors where stop can be installed in concr ete, provide stop mated to concrete anchor set in 76mm (3-inch) core- drilled hole and filled with quick-setting cement.

F. Provide appropriate door mounted stop on doors i n individual toilets where floor or wall mounted stops cannot be used.

G. Provide overhead surface applied stop Type C0254 1, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-8

H. Provide door stops on doors where combination cl oser magnetic holders are specified, except where wall stops cannot be us ed or where floor stops cannot be installed within 4-inches of the wa ll.

K. Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where con cealed cannot be used).

2.5 OVERHEAD DOOR STOPS AND HOLDERS

A. Conform to ANSI Standard A156.8. Overhead holder s shall be of sizes recommended by holder manufacturer for each width o f door. Set overhead holders for 110 degree opening, unless limited by b uilding construction or equipment. Provide Grade 1 overhead concealed sl ide type: stop-only at rated doors and security doors, hold-open type w ith exposed hold-open on/off control at all other doors requiring ov erhead door stops.

2.7 LOCKS AND LATCHES

A. Conform to ANSI A156.2. Locks and latches for do ors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylin ders shall have not less than seven pins . Cylinders for all locksets shall be removable core type. Cylinders shall be furnished with constr uction removable cores and construction master keys. Cylinder shall be removable by special key or tool. Construct all cores so that th ey will be interchangeable into the core housings of all morti se locks, rim locks, cylindrical locks, and any other type lock included in the Great Grand

Master Key System. Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door man ufacturer’s fire label. Provide temporary keying device or construct ion core to allow opening and closing during construction and prior t o the installation of final cores.

B. In addition to above requirements, locks and lat ches shall comply with following requirements:

1. Mortise Lock and Latch Sets: Conform to ANSI/BHM A A156.13. Mortise locksets shall be series 1000, minimum Grade 2. All locksets and latchsets, except on designated doors in Psychiatri c (Mental Health) areas, shall have lever handles fabricated from cas t stainless steel. No substitute lever material shall be accep ted. All locks and latchsets shall be furnished with 122.55 mm (4- 7/8-inch) curved

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-9 lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-in ch) lip-to-center dimension. Lock function F02 shall be furnished wi th emergency tools/keys for emergency entrance. All lock cases i nstalled on lead lined doors shall be lead lined before applying fin al hardware finish. Furnish armored fronts for all mortise lock s. Where mortise locks are installed in high-humidity locations or w here exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case.

2. Cylindrical Lock and Latch Sets: levers shall me et ADA (Americans with Disabilities Act) requirements. Cylindrical lo cksets shall be series 4000 Grade I. All locks and latchsets shall be furnished with

122.55 mm (4-7/8-inch) curved lip strike and wrough t box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Prov ide lever design to match design selected by Architect or to match e xisting lever design. Where two turn pieces are specified for lo ck F76, turn piece on inside knob shall lock and unlock inside k nob, and turn piece on outside knob shall unlock outside knob whe n inside knob is in the locked position. (This function is intended to allow emergency entry into these rooms without an emergen cy key or any special tool.)

3. Auxiliary locks shall be as specified under hard ware sets and conform to ANSI A156.36.

2.8 PUSH-BUTTON COMBINATION LOCKS

A. ANSI/BHMA A156.5, Grade 1. Battery operated push button entry.

B. Construction: Heavy duty mortise lock housing c onforming to ANSI/BHMA

A156.13, Grade 1. Lever handles and operating comp onents in compliance with the UFAS and the ADA Accessibility Guidelines. Match lever handles of locks and latchsets on adjacent doors.

C. Special Features: Key override to permit a mast er keyed security system and a pushbutton security code activated pas sage feature to allow access without using the entry code.

2.09 ELECTROMAGNETIC LOCKS

A. ANSI/BHMA A156.23; electrically powered, of stre ngth and configuration indicated; with electromagnet attached to frame and armature plate

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-10 attached to door. Listed under Category E in BHMA's "Certified Product

Directory."

1. Type: Full exterior or full interior, as requir ed by application indicated.

2. Strength Ranking: 1500 lbf (6672 N.

3. Inductive Kickback Peak Voltage: Not more than 53 V.

4. Residual Magnetism: Not more than 4 lbf (18 N) t o separate door from magnet.

2.10 ELECTRIC STRIKES

A. ANSI/ BHMA A156.31 Grade 1.

B. General: Use fail-secure electric strikes at fi re-rated doors.

2.11 KEYS

A. Stamp all keys with change number and key set sy mbol. Furnish keys in quantities as follows:

Locks/Keys Quantity

Cylinder locks 2 keys each

Cylinder lock change key blanks

100 each different key way

Master-keyed sets 6 keys each

Grand Master sets 6 keys each

Great Grand Master set 5 keys

Control key 2 keys

2.13 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING

A. Conform to ANSI Standard A156.6.

B. Provide protective plates and door edging as spe cified below:

1. Kick plates, mop plates and armor plates of meta l, Type J100 series.

2. Provide kick plates and mop plates where specifi ed. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) h igh. Mop plates shall be 152 mm (6 inches) high. Both kick and mop plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of door s where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inc hes) less than width of door, except pairs of metal doors which sh all have plates

25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each ed ge of doors. Kick

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-11 and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.

3. Kick plates and/or mop plates are not required o n following door sides:

a. Armor plate side of doors;

b. Exterior side of exterior doors;

c. Closet side of closet doors;

d. Both sides of aluminum entrance doors.

4. Armor plates for doors are listed under Article "Hardware Sets".

Armor plates shall be thickness as noted in the har dware set, 875 mm

(35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plate s beveled on all

4 edges (B4E). Plates on pairs of metal doors shal l be 25 mm (1 inch) less than width of each door. Where top of in termediate rail of door is less than 875 mm (35 inches) from door b ottom, extend armor plates to within 13 mm (1/2 inch) of top of i ntermediate rail.

On doors equipped with panic devices, extend armor plates to within

13 mm (1/2 inch) of panic bolt push bar.

5. Where louver or grille occurs in lower portion o f doors, substitute stretcher plate and kick plate in place of armor pl ate. Size of stretcher plate and kick plate shall be 254 mm (10 inches) high.

6. Provide stainless steel edge guards where so spe cified at wood doors. Provide mortised type instead of surface typ e except where door construction and/or ratings will not allow. P rovide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does no t allow; in such cases, provide edge guards to height of bottom of t ypical lockset armor front. Forward edge guards to wood door manu facturer for factory installation on doors.

2.14 FLUSH BOLTS (AUTOMATIC)

A. Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI

A115. Bolts shall conform to Underwriters Laborator ies, Inc., requirements for fire door hardware. Flush bolts sh all automatically latch and unlatch. Furnish dustproof strikes confor ming to ANSI A156.16

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-12 for bottom flushbolt. Face plates for dustproof str ike shall be rectangular and not less than 38 mm by 90 mm (1-1/2 by 3-1/2 inches).

B. At interior doors, provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire -rating greater than

20 minutes; provide fire pins as required by auto f lush bolt and door fire labels.

2.15 DOOR PULLS WITH PLATES

A. Conform to ANSI A156.6. Pull Type J401, 152 mm C TC (6 inches CTC) length by 19 mm (3/4 inches) diameter minimum with plate Type J302, 90 mm by 381 mm (3-1/2 inches by 15 inches), unless otherwise specified. Provide pull with projection of 57.2 mm (2 1/4 inches) minimum and a clearance of 38.1 mm (1 1/2 inches) m inimum. Cut plates of door pull plate for cylinders, or turn pieces wh ere required.

2.16 PUSH PLATES

A. Conform to ANSI A156.6. Metal, Type J302, 203 mm (8 inches) wide by

406.4 mm (16 inches) high. Provide metal Type J302 plates 102 mm

(4 inches) wide by 406.4 mm (16 inches) high where push plates are specified for doors with stiles less than 203 mm (8 inches) wide. Cut plates for cylinders, and turn pieces where require d.

2.17 COMBINATION PUSH AND PULL PLATES

A. Conform to ANSI 156.6. Type J303, stainless stee l 3 mm (1/8 inch) thick, 80 mm (3-1/3 inches) wide by 800 mm (16 inch es) high), top and bottom edges shall be rounded. Secure plates to woo d doors with 38 mm

(1-1/2 inch) long No. 12 wood screws. Cut plates fo r turn pieces, and cylinders where required. Pull shall be mounted dow n.

2.18 COORDINATORS

A. Conform to ANSI A156.16. Coordinators, when spec ified for fire doors, shall comply with Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on e xterior pairs of doors where either door will close independently re gardless of the position of the other door. Coordinator may be omit ted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors. Paint co ordinators to match door frames, unless coordinators are plated. Provi de bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-13 full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic str ikes.

2.19 THRESHOLDS

A. Conform to ANSI A156.21, mill finish extruded al uminum, except as otherwise specified. In existing construction, thre sholds shall be installed in a bed of sealant with ¼-20 stainless s teel machine screws and expansion shields. In new construction, embed a luminum anchors coated with epoxy in concrete to secure thresholds. Furnish thresholds for the full width of the openings.

B. For thresholds at elevators entrances see other sections of specifications.

C. At exterior doors and any interior doors exposed to moisture, provide threshold with non-slip abrasive finish.

D. Provide with miter returns where threshold exten ds more than 12 mm

(0.5 inch) beyond face of frame.

2.20 MISCELLANEOUS HARDWARE

A. Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types):

Except for fire-rated doors and doors to Temperatur e Control Cabinets, equip each single or double metal access door with Lock Type E07213, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer.

B. Cylinders for Various Partitions and Doors: Key cylinders same as entrance doors of area in which partitions and door occur, except as otherwise specified. Provide cylinders to operate l ocking devices where specified for following partitions and doors:

1. Fire-rated access doors-Engineer's key set.

C. Mutes: Conform to ANSI A156.16. Provide door mut es or door silencers

Type L03011 or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, excep t at fire-rated frames, lead-lined frames and frames for sound-resi stant, lightproof and electromagnetically shielded doors. Furnish 3 m utes for single doors and 2 mutes for each pair of doors, except do uble-acting doors.

Provide 4 mutes or silencers for frames for each Du tch type door.

Provide 2 mutes for each edge of sliding door which would contact door frame.

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-14

2.21 FINISHES

A. Exposed surfaces of hardware shall have ANSI A15 6.18, finishes as specified below. Finishes on all hinges, pivots, cl osers, thresholds, etc., shall be as specified below under "Miscellane ous Finishes." For field painting (final coat) of ferrous hardware, se e Section 09 91 00, PAINTING.

B. 626 or 630: All surfaces on exterior and interio r of buildings, except where other finishes are specified.

C. Miscellaneous Finishes:

1. Hinges --interior doors: 652 or 630.

2. Door Closers: Factory applied paint finish. Dull or Satin Aluminum color.

5. Thresholds: Mill finish aluminum.

D. Hardware Finishes for Existing Buildings: U.S. S tandard finishes shall match finishes of hardware in (similar) existing sp aces except where otherwise specified.

E. Special Finish: Exposed surfaces of hardware for dark bronze anodized aluminum doors shall have oxidized oil rubbed bronz e finish (dark bronze) finish on door closers shall closely match doors.

F. Anti-microbial Coating: All hand-operated hardwa re (levers, pulls, push bars, push plates, paddles, and panic bars) shall b e provided with an anti-microbial/anti-fungal coating that has passed ASTM E2180 tests.

Coating to consist of ionic silver (Ag+). Silver i ons surround bacterial cells, inhibiting growth of bacteria, mol d, and mildew by blockading food and respiration supplies.

2.22 BASE METALS

A. Apply specified U.S. Standard finishes on differ ent base metals as following:

Finish Base Metal

652 Steel

626 Brass or bronze

630 Stainless steel

PART 3 - EXECUTION

3.1 HARDWARE HEIGHTS

A. For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the s ite, verify location

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-15 of existing hardware and submit locations to VA Res ident Engineer for approval.

B. Hardware Heights from Finished Floor:

1. Locksets and latch sets centerline of strike 102 4 mm (40-5/16 inches).

2. Deadlocks centerline of strike 1219 mm (48 inche s).

3. Hospital arm pull 1168 mm (46 inches) to centerl ine of bottom supporting bracket.

4. Centerline of door pulls to be 1016 mm (40 inche s).

5. Push plates and push-pull shall be 1270 mm (50 i nches) to top of plate.

6. Push-pull latch to be 1024 mm (40-5/16 inches) t o centerline of strike.

7. Locate other hardware at standard commercial hei ghts. Locate push and pull plates to prevent conflict with other hard ware.

3.2 INSTALLATION

A. Closer devices, including those with hold-open f eatures, shall be equipped and mounted to provide maximum door openin g permitted by building construction or equipment. Closers shall b e mounted on side of door inside rooms, inside stairs, and away from cor ridors. At exterior doors, closers shall be mounted on interior side. W here closers are mounted on doors they shall be mounted with hex nut s and bolts; foot shall be fastened to frame with machine screws.

B. Hinge Size Requirements:

Door Thickness Door Width Hinge Height

45 mm (1-3/4 inch) 900 mm (3 feet) and less 113 mm (4-1/2 inches)

45 mm (1-3/4 inch) Over 900 mm (3 feet) but not more than 1200 mm (4 feet)

125 mm (5 inches)

35 mm (1-3/8 inch) (hollow core wood doors)

Not over 1200 mm (4 feet) 113 mm (4-1/2 inches)

C. Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.

D. Where new hinges are specified for new doors in existing frames or existing doors in new frames, sizes of new hinges s hall match sizes of existing hinges; or, contractor may reuse existing hinges provided

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-16 hinges are restored to satisfactory operating condi tion as approved by

Resident Engineer. Existing hinges shall not be reu sed on door openings having new doors and new frames. Coordinate prepara tion for hinge cut-outs and screw-hole locations on doors and frames.

E. Hinges Required Per Door:

Door Description Number butts

Doors 1500 mm (5 ft) or less in height 2 butts

Doors over 1500 mm (5 ft) high and not over 2280 mm (7 ft 6 in) high

3 butts

Doors over 2280 mm (7 feet 6 inches) high 4 butts

Dutch type doors 4 butts

Doors with spring hinges 1370 mm (4 feet 6 inches) high or less

2 butts

Doors with spring hinges over 1370 mm (4 feet 6 inc hes) 3 butts

F. Fastenings: Suitable size and type and shall har monize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or rawl plugs and adhesives are not permitted.

All fastenings exposed to weather shall be of nonfe rrous metal.

G. After locks have been installed; show in presenc e of Resident Engineer that keys operate their respective locks in accorda nce with keying requirements. (All keys, Master Key level and above shall be sent

Registered Mail to the Medical Center Director alon g with the bitting list. Also a copy of the invoice shall be sent to t he Resident Engineer for his records.) Installation of locks which do no t meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.

3.3 FINAL INSPECTION

A. Installer to provide letter to the COR that upon completion, installer has visited the Project and has accomplished the fo llowing:

1. Re-adjust hardware.

2. Evaluate maintenance procedures and recommend ch anges or additions, and instruct VA personnel.

3. Identify items that have deteriorated or failed.

4. Submit written report identifying problems.

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-17

3.4 DEMONSTRATION

A. Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment a nd maintenance procedures, to satisfaction of the COR and VA Locks mith.

3.5 HARDWARE SETS

A. Following sets of hardware correspond to hardwar e symbols shown on drawings. Only those hardware sets that are shown o n drawings will be required. Disregard hardware sets listed in specifi cations but not shown on drawings.

B. Hardware Consultant working on a project will be responsible for providing additional information regarding these ha rdware sets. The numbers shown in the following sets come from BHMA standards.

INTERIOR SINGLE DOORS

HW-1

Each Door to Have: NON-RATED

1 Continuous Hinge

1 Door Pull w/ Plate J401 x J302

1 Push Plate J302

1 Kick Plate J102

1 Mop Plate (@ Inswing Doors) J103

1 Closer C02011/C02021

1 Floor Stop L02121 x 3 FASTENERS

3 Silencers L03011

ELECTRIC HARDWARE ABBREVIATIONS LEGEND:

ADO = Automatic Door Operator

EMCH = Electro-Mechanical Closer-Holder

MHO = Magnetic Hold-Open (wall- or floor-mounted)

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-18

HW-1A

Each Door to Have: RATED

Hinges QUANTITY & TYPE AS REQUIRED

X HOSPITAL TIPS @ INSWING DOORS

1 Latchset F01

1 Closer C02011/C02021 x INSTALL OUTSIDE ROOM

1 Kick Plate J102

1 Mop Plate (@ Inswing Doors) J103

1 Floor Stop L02121 x 3 FASTENERS

1 Threshold J32300 x 57 MM WIDTH (2-1/4 INCHES)

1 Auto Door Bottom R0Y346 – HEAVY DUTY

1 Set Seals R0Y164

HW-1E

1 Continuous Hinge x INTEGRAL HINGE GUARD CHANNE L

X SWING-CLEAR X ADJUSTA-SCREWS

1 Hospital Latch F01 x PADDLES POINTING DOWN

1 Closer C02011/C02021

1 Armor Plate J101 x 1.275 MM (0.050 INCH) THICK NESS

1 Edge Guard (@ Wood Doors) J208M / J211 (VERIFY), CUT: HARDWARE

1 Wall Stop (@ Inswing Doors) L02101 CONVEX

1 Set Self-Adhesive Seals R0Y154

HW-2C

Each Door to Have: NON-RATED

1 Privacy Lock F02-MOD X OCCUPANCY INDICATOR

1 Kick Plate J102

1 Mop Plate (@ Inswing Doors) J103

1 Wall Stop L02101 CONVEX

3 Silencers L03011

STONE THRESHOLD BY OTHER TRADES.

HW-3

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-19

1 Office Lock F04

1 Closer C02011/C02021

1 Kick Plate J102

1 Floor Stop L02121 x 3 FASTENERS

1 Set Self-Adhesive Seals R0Y154

HW-4E

Each Door to Have: NON-RATED/RATED

1 Utility Lock F09

1 Closer (@ rated doors) C02011/C02021

1 Closer (@ non-rated doors) CO2051/CO2061

1 Kick Plate J102

1 Floor Stop L02121 x 3 FASTENERS

1 Threshold J32300 x 57 MM WIDTH (2-1/4 INCHES)

1 Auto Door Bottom R0Y346 – HEAVY DUTY

2 Sets Self-Adhesive Seals R0Y154

HW-4F

X ADJUSTA-SCREWS

1 Utility Lock F09

1 Closer C02011/C02021

1 Armor Plate J101 x 1.275 MM (0.050 INCH) THICK NESS

1 Edge Guard (@ Wood Doors) J208M / J211 (VERIFY), CUT: HARDWARE

1 Wall Stop (@ Inswing Doors) L02101 CONVEX

1 Set Self-Adhesive Seals R0Y154

HW-5

1 Storeroom Lock F07

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-20

1 Closer C02011/C02021

1 Kick Plate J102 (@ STORAGE, EVM, & HAC ROOMS O NLY)

1 Floor Stop L02121 x 3 FASTENERS

1 Set Self-Adhesive Seals R0Y154

HW-8B

Each Pair to Have: NON-RATED

2 Continuous Hinge

2 Door Pull w/ Plate J401 x J302

2 Push Plate J302

2 Hospital Grip J401

2 Kick Plate J102

2 Mop Plate (@ Inswing Doors) J103

2 Closer C02011/C02021

2 Floor Stop L02121 x 3 FASTENERS

2 Silencers L03011

HW-8F

Each [ADO] Pair to Have: NON-RATED

2 Continuous Hinges x INTEGRAL HINGE GUARD CHANN EL

X ADJUSTA-SCREWS x 4-THRUWIRE TRANSFERS

X IN-HINGE ACCESS PANEL

2 Push Plate J304 8” x 16”

2 Hospital Grip J401

2 Kick Plate J102

2 Mop Plate (@ Inswing Doors) J103

2 Edge Guard (@ Wood Doors) J208M / J211 (VERIFY), CUT: HARDWARE

2 Floor Stop L02121 x 3 FASTENERS

1 Threshold J32300 x 57 MM WIDTH (2-1/4 INCHES)

2 Auto Door Bottoms R0Y346 – HEAVY DUTY

2 Set Self-Adhesive Seals R0Y154

AUTOMATIC DOOR OPERATORS AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR

OPERATORS.

POWER TRANSFERS FOR RE-ACTIVATION SENSOR WIRING (RE-ACTIVATION SENSORS

PROVIDED BY SECTION 08 71 13).

HW-10A

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-21

Each [ADO] Pair to Have: NON-RATED

X ADJUSTA-SCREWS x 8-THRUWIRE

TRANSFER X IN-HINGE ACCESS PANEL

1 Continuous Hinge x INTEGRAL HINGE GUARD CHANNE L

X ADJUSTA-SCREWS X 4-THRUWIRE

TRANSFER X IN-HINGE ACCESS PANEL

1 Set Auto Flush Bolts TYPE 25 LESS BOTTOM BOLT

1 Classroom Lock F08

1 Electric Unlatch Strike E09321 (FAIL SECURE)

1 Power Supply REGULATED, FILTERED, 24VDC, AMPERA GE

AS REQUIRED

1 Coordinator TYPE 21A

1 Overlapping Astragal with R0Y634 x R0Y154 x THRU- BOLTS

Self-Adhesive Seal

2 Armor Plates J101 x 1.275 MM (0.050 INCH) THICK NESS

2 Floor Stops L02121 x 3 FASTENERS

2 Auto Door Bottoms R0Y346 – HEAVY DUTY

2 Set Self-Adhesive Seals R0Y154

AUTOMATIC DOOR OPERATORS AND CONTROLS BY SECTION 08 71 13, AUTOMATIC DOOR

OPERATORS.

POWER TRANSFER SHARED BY ELECTRIC STRIKE AND RE-ACTIVATION SENSOR WIRING

(RE-ACTIVATION SENSORS PROVIDED BY SECTION 08 71 13 ).

HW-SH-3

Each [AC, EL, REX, DPS] Door to Have: RATED/NON -RATED

1 Transfer Hinge 4-WIRE TYPE AS REQUIRED

1 Electrified Lock F07 (E01-REX, E06) 24VDC

1 Power Supply REGULATED, FILTERED, 24VDC, AMPERA GE

AS REQUIRED

1 Closer C02011/C02021

1 Floor Stop L02121 x 3 FASTENERS

1 Threshold J32300 x 57 MM WIDTH (2-1/4 INCHES)

1 Auto Door Bottom R0Y346 – HEAVY DUTY

2 Sets Self-Adhesive Seals R0Y154

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-22

1 Alarm Contact

120VAC POWER, CONDUIT, AND WIRING BY DIVISION 26.

CARD READER BY DIVISION 28.

- - - E N D - - -

Houston, TX Project No. 580-17-121

08-01-19

08 71 00-23

---INTENTIONALLY BLANK---