This document outlines requirements for renovating inpatient wards at a Veterans Affairs medical center. The Department of Veterans Affairs will issue a solicitation as a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses to renovate wards 6W, 7W, and 8W at the Overton Brooks VA Medical Center in Shreveport, Louisiana. Renovations include revising restroom layouts to meet ADA requirements, modifying medical gas demolition, and revising finish schedules. The solicitation number is 36C25620R0128, with a proposal due date of September 10, 2020. The contract award date is anticipated within 30 days thereafter. The contract performance period is 810 calendar days from notice to proceed. The construction cost range is between $5-10 million. Offerors must represent SDVOSB status and size standard compliance, and be verified in the Vendor Information Pages database.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REVISE LAYOUT OF PUBLIC RESTROOMS 6W36, 7W36 & 8W36 TO MEET ADA/ABA REQUIREMENTS:
Reference Supplemental Drawing Sheets 1-SD-001, 1-SD-002, 1-SD-003, & 1-SD-004
1. Provide additional demolition, new work, and relocation of existing work in Public Toilet 6W36 as shown on drawings 1-SD-001, 1-SD-002, 1-SD-003, & 1-SD-004 included. Include additional work in Public Toilet 7W36 and Public Toilet 8W36 equal to that shown for 6W36.
2. Provide revised equipment locations as required for indicated on drawings 1-SD-001, 1-SD-002, 1-SD-003, & 1-SD-004 included. Include additional work in Public Toilet 7W36 and Public Toilet 8W36 equal to that shown for 6W36.
3. Provide revised finishes as required for indicated on drawings 1-SD-001, 1-SD-002, 1-SD-003, & 1-SD-004 included. Include additional work in Public Toilet 7W36 and Public Toilet 8W36 equal to that shown for 6W36.
4. Provide additional demolition, relocation, and new plumbing work as required in Public Toilet 6W36 as shown on drawings 1-SD-001, 1-SD-002, 1-SD-003, & 1-SD-004 included. Include additional work in Public Toilet 7W36 and Public Toilet 8W36 equal to that shown for 6W36.
a. Modify the existing plumbing piping in the wall, below the floor and above the ceiling. Rough-in 2" waste piping to new sink. Connect vent piping to plumbing piping thru the roof. Contractor to field verify the existing waste piping, vent piping, hot water supply, cold water piping, sanitary stack, and vent stack up through the roof.
b. Route 1/2" hot and 1/2" cold water supply down in wall and connect to each sink or lavatory. Install fixture per manufacturer's recommendations.
5. Provide additional demolition, relocation, and new HVAC work as required in Public Toilet 6W36 as shown on drawings 1-SD-001, 1-SD-002, 1-SD-003, & 1-SD-004 included. Include additional work in Public Toilet 7W36 and Public Toilet 8W36 equal to that shown for 6W36.
6. Provide additional demolition, relocation, and new electrical work as required in Public Toilet 6W36 as shown on drawings 1-SD-001, 1-SD-002, 1-SD-003, & 1-SD-004 included. Include additional work in Public Toilet 7W36 and Public Toilet 8W36 equal to that shown for 6W36. At each restroom:
a. Demo and remove (3) existing duplex receptacles and (2) data outlets on west side of existing wall that is being demolished.
b. Demo and remove (1) existing GFCI receptacle on east side of existing wall that is being demolished.
c. Install new (2) duplex receptacles and (2) GFCI duplex receptacles in similar locations at new wall location. Connect to existing circuits with 2-#12, 1-#12G.
d. Install new data/network combination devices in similar locations at new wall location. Reinstall existing network wiring and terminate at new devices.
e. Install new fire alarm signaling device in similar locations at new wall location.
7. The Supplemental Drawings provided (1-SD-001, 1-SD-002, 1-SD-003, & 1-SD-004) are of Public Toilet 6W36; however, this change shall also be applied to the associated work in Public Toilet 7W36 and Public Toilet 8W36 equal to that shown for 6W36.
REVISE MED GAS DEMOLITION REQUIREMENTS FOR 6W, 7W & 8W
Reference Supplemental Drawing Sheet 1-SD-005
1. The Supplemental Drawing 1-SD-005. Deletes the numbered note 1 on sheets 1-PL-2 for 6W, 1-PL-6 for 7W and 1-PL-10 for 8W. In lieu of capping the existing med gas outlets at each location, the existing med gases will be isolated at their associated zone valves.
2. Numbered Note 1 shall be replaced as annotated on Supplemental Drawing Sheet 1-SD-005.
REVISE NEW FINISHES SCHEDULES AND MATERIAL FINISH LEGEND
Reference Supplemental Drawing Sheet 1-SD-006
1. The Supplemental Drawing 1-SD-006 modifies the finish and material schedules for 6W, 7W and 8W on sheet 1-AS-900.