This document outlines a federal contract opportunity for construction services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9 is seeking a contractor to correct environment and condition deficiencies at the Administration Building 20 of the James H. Quillen VA Medical Center in Mountain Home, Tennessee. Work includes office space modifications, conference rooms, locker rooms, storage areas, and mechanical/electrical rooms for a police staff as well as demolition, finishes, and compliance with VA standards. The estimated value is between $1 million and $5 million. The solicitation will be released on October 20, 2021 and close on November 20, 2021, following FAR Part 14 sealed bid procedures. This is a 100% SDVOSB set-aside requiring registration in SAM and VETS4212. The NAICS code is 236220 and size standard is $39.5 million. Questions must be submitted in writing to the listed contracting specialist by the solicitation release date.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYMBOLS:
SECTION NUMBER
DWG. NO. WHERE
SECTION IS DRAWN
A1
A-101
SIM
DETAIL NUMBER
DWG. NO. WHERE
SECTION IS DRAWN
DETAIL SECTION MARK
A1
A-101
SIM
WALL SECTION MARK
ELEVATION
NUMBER (TYP.)
DWG. NO. WHERE
ELEVATION IS DRAWN
A-101
INTERIOR ELEVATION MARK
DWG. NO. WHERE
DETAIL IS DRAWN
DETAIL
NUMBER (TYP.)
AREA COVERED
BY DETAIL
A-101
SIM
CALLOUT HEAD
ROOM TAG
ROOM
NAME
DOOR TAG
WINDOW &
LOUVER TAG
A
PARTITION TYPE
X
PARTITION
TYPE
KEYNOTE
TAG
CEILING HGT.
CEILING TYPE
1t 12'-0"
CEILING TAG
(TYPE & HEIGHT)
EQUIPMENT
TAG
1i
REVISION
TAG
NORTH ARROWS
N
DETAIL IDENTIFIER (MODULE LETTER AND NUMBER)
A1
ELEVATIONS, DETAILS & CALLOUTS
SCALE: 1/8" = 1'-0"
PLAN SYMBOLS:
VIEW TITLES:
PLUMBING ABBREVIATIONS
A/C ABOVE CEILING
A/E ARCHITECT / ENGINEER
AFF ABOVE FINISH FLOOR
AG AIR GAP
AS AUTOMATIC SPRINKLER
ASHRAE AMERICAN SOCIETY OF HEATING
REFRIGERATION, AIR CONDITIONING
ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
ASPE AMERICAN SOCIETY OF PLUMBING
ENGINEERS
BFP REDUCED PRESSURE BACKFLOW
PREVENTER
BSP BLACK STEEL PIPE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CELSIUS
CO CLEANOUT
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DHWS DOMESTIC HOT WATER SUPPLY
DN DOWN
DOE DEPARTMENT OF ENERGY
DWG DRAWINGS
EL ELEVATION
EWH ELECTRIC WATER HEATER
EPA ENVIRONMENTAL PROTECTION AGENCY
(E) EXISTING
F FAHRENHEIT
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FM FLOW METER
GCO GRADE CLEANOUT
H&CW HOT AND COLD WATER
ISO ISOLATION
HB HOSE BIBB
HYD HYDRANT
M METER
NIC NOT IN CONTRACT
NTS NOT TO SCALE
IPC INTERNATIONAL PLUMBING CODE
PDI PLUMBING AND DRAINAGE INSTITUTE
PG PRESSURE GAGE
PRV PRESSURE REDUCING VALVE
TP TRAP PRIMER
TYP TYPICAL
T/P TEMPERATURE AND PRESSURE
UG UNDER GROUND
V VENT
VTR VENT THROUGH ROOF
W WASTE
WCO WALL CLEANOUT
WG WATER GAGE
WH WALL HYDRANT
WH WATER HEATER
WL WATER LINE
WM WATER METER
WSFU WATER SUPPLY FIXTURE UNITS
YH YARD HYDRANT
SD SD
DIRECTION OF PIPE PITCH (DOWN)
DIRECTION OF FLOW
ANCHOR
REDUCER OF INCREASER
ECCENTRIC REDUCER
TOP CONNECTION, 45° OR 90°
BOTTOM CONNECTION, 45° OR 90°
SIDE CONNECTION
CAPPED OUTLET
RISE OR DROP IN PIPE
UNION
PIPE UP
PIPE DOWN
LIMIT OF DEMOLITION
STRAINER
THERMOMETER
PRESSURE GAUGE
HOSE BIBB
DOMESTIC COLD WATER, COLD WATER
GENERAL PLUMBING SYMBOLS
PIPE DROP AND CONTINUED
POINT OF CONNECTION BETWEEN NEW AND EXISTING WORK
DOMESTIC HOT WATER, HOT WATER
DOMESTIC HOT WATER RETURN, HOT WATER RETURN
VENT PIPING
SANITARY WASTE PIPING
STORM WATER PIPING
NON-FREEZE WALL HYDRANT
TP TRAP PRIMER
AV
GATE VALVE
GLOBE VALVE
GATE VALVE WITH 3/4" HOSE ADAPTER
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
BALL VALVE
MODULATING CONTROL VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL
VALVE
THREE-WAY TWO POSITION CONTROL
VALVE
PRESSURE REGULATING VALVE
AUTOMATIC FLOW CONTROL VALVE
PRESSURE RELIEF VALVE
MANUAL AIR VENT
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENT
PLUMBING VALVE SYMBOLS
PLUMBING GENERAL NOTES
1. PLUMBING WORK SHALL BE IN ACCORDANCE WITH THE 2018 IBC, 2018 IPC, AND 2018 IFGC.
2. SLOPES AND INVERT ELEVATIONS SHALL BE ESTABLISHED BEFORE ANY PIPE IS INSTALLED IN ORDER TO MAINTAIN PROPER
SLOPES. ANY DISCREPANCIES SHALL BE REPORTED TO CONTRACTING OFFICER'S REPRESENTATIVE. ALL PIPING SHALL BE
LOCATED AND DETERMINED WHEN TO BE INSTALLED TO AVOID CONFLICT WITH OTHER TRADES.
3. PIPING SHALL BE CONCEALED UNLESS OTHERWISE NOTED.
4. KEEP ALL BURIED PIPING CLEAR OF FOOTINGS.
5. ALL WALL CLEANOUTS SHALL BE PROVIDED WITH WALL COVERS AND MOUNTED IN UNOBTRUSIVE LOCATIONS WHILE MAINTAINING
ACCESSIBILITY. ALL FLOOR CLEANOUTS SHOWN SHALL BE SET FLUSH WITH FLOOR AREAS OR FINISHED GRADE.
6. COORDINATE LOCATION OF PIPING AND DRAINS WITH ALL MECHANICAL AND ELECTRICAL EQUIPMENT. NO PIPING SHALL BE
INSTALLED ABOVE ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT OR PANELS. COMPLY WITH ARCHITECTURAL PLANS FOR
EXACT LOCATION OF PLUMBING FIXTURES, COMPLIANCE TO ADA CLEARANCES, AND FINISHES.
7. PROVIDE REQUIRED WATER, WASTE, AND VENT PIPING, FITTINGS, AND INSULATION, AND MAKE FINAL CONNECTIONS TO EQUIPMENT. THESE PLANS ARE SCHEMATIC AND DIAGRAMMATIC ONLY. THEY DO NOT SHOW ALL REQUIRED BENDS, OFFSETS, VALVES, AND MISCELLANEOUS FITTINGS FOR A COMPLETE INSTALLATION. ALL PIPING, EQUIPMENT, AND CONNECTIONS SHALL BE INSTALLED IN ACCORDANCE WITH SPECIFICATIONS, LOCAL CODES AND ORDINANCES, AND MANUFACTURER'S INSTRUCTIONS.
8. SANITARY SEWER PIPING SHALL BE INSTALLED TO PROVIDE A MINIMUM SLOPE OF 1%. WASTE PIPING 3" AND SMALLER SHALL BE
INSTALLED TO PROVIDE A MINIMUM SLOPE OF 2%.
9. DO NOT SCALE DRAWINGS. REFER TO ARCHITECTURE DRAWINGS FOR EXACT DIMENSIONS, FIXTURE LOCATIONS, ROOM NAMES, AND NUMBERS.
10. EXTENSION OF EQUIPMENT DRAINS TO FLOOR DRAINS, FLOOR SINKS, AND OPEN SITE DRAINS SHALL BE PROVIDED BY
EQUIPMENT CONTRACTOR.
11. WHERE POSSIBLE, INSTALL SHUT-OFF VALVES AND EQUIPMENT REQUIRING MAINTENANCE, CLEANING AND ADJUSTMENT ABOVE ACCESSIBLE CEILINGS OR IN SERVICE AREAS SUCH AS JANITOR'S CLOSETS. IN OTHER LOCATIONS, PROVIDE ACCESS PANELS IN
INCONSPICUOUS LOCATIONS WITH FINISH TO MATCH ARCHITECTURAL.
12. ALL HOSE BIBBS, WALL HYDRANTS, AND VALVES WITH THREADED HOSE CONNECTIONS SHALL BE EQUIPPED WITH VACUUM
BREAKER.
13. WHERE CONNECTING TO A UTILITY OR SERVICE, VERIFY LOCATION, SIZES, MATERIALS, FLUID BEING HANDLED, AND INVERTS OF ALL EXISTING UTILITIES AND CONFIRM THAT NEW PIPES BEING ROUTED TO EXISTING UTILITIES CAN BE INSTALLED CONFORMING TO CODE AND AS SHOWN. NOTIFY CONTRACTING OFFICER OF ANY CONFLICTS OR DISCREPANCIES PRIOR TO PURCHASING ANY MATERIALS OR PERFORMING ANY WORK OR EXTENSION OF CONNECTION, WITH THE EXCEPTION OF EXCAVATION OR OTHER
WORK TO PROVIDE ACCESS TO THE CONCEALED UTILITY.
14. PROVIDE INSULATION, PIPE IDENTIFICATION, AND OTHER REQUIREMENTS AS LISTED IN SPECIFICATIONS.
15. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND ELEVATIONS OF ALL PLUMBING FIXTURES.
16. ALL PIPING ABOVE GRADE SHALL BE PROPERLY SUPPORTED FROM THE BUILDING STRUCTURE AND SHALL NOT REST ON CEILING
TILES OR BE SUPPORTED FROM CEILING TILES.
17. WATER PIPING ROUTED ABOVE CEILINGS AND IN EXTERIOR WALLS SHALL BE ROUTED ON HEATED SIDE (UNDERSIDE) OF CEILING
INSULATION AND HEATED SIDE (INSIDE) OF WALL INSULATION.
18. TOPS OF ALL FLOOR DRAINS AND CLEANOUTS SHALL BE SET FLUSH WITH FINISHED FLOOR, UNLESS NOTED OTHERWISE.
19. LOCATE ALL SECTIONAL OR MAIN CONTROL VALVES WITHIN 1'-0" FROM ACCESS PANELS, CEILING TILES, OR OTHER POINT OF
ACCESS.
20. PROVIDE WATER HAMMER ARRESTORS SIZED PER PDI SPECIFICATIONS ON ALL DOMESTIC WATER LINES SERVING FLUSH VALVE
FIXTURES, WASHING MACHINES SUPPLIES, PRV STATIONS, AND OTHER INSTALLATIONS WITH QUICK CLOSING VALVES.
21. PROVIDE A MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSION LOOP ON ALL PIPING SYSTEMS CROSSING BUILDING
EXPANSION JOINTS.
22. COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL PLUMBING EQUIPMENT WITH THE ELECTRICAL
DRAWINGS AND THE ELECTRICAL CONTRACTOR, AND FURNISH EQUIPMENT WIRED FOR THE VOLTAGES SHOWN THEREIN.
23. ALL PLUMBING EQUIPMENT AND SYSTEMS SHALL BE GUARANTEED FOR A MINIMUM PERIOD OF ONE YEAR AFTER OWNER'S FINAL
ACCEPTANCE.
24. ALL PIPE PENETRATIONS OF FIRE AND/OR SMOKE-RATED ASSEMBLIES SHALL BE FIRE-STOPPED AS REQUIRED TO RESTORE
ASSEMBLY TO ORIGINAL INTEGRITY. FIRE BARRIER PRODUCTS SHALL BE AS MANUFACTURED BY 3M COMPANY, CP25 CAULK, CS195 COMPOSITE PANEL, FS195 WRAP/STRIP, OR PSS 7900 SERIES SYSTEMS AS RECOMMENDED BY MANUFACTURER FOR PARTICULAR APPLICATION, OR EQUIVALENT SYSTEM AS APPROVED BY LOCAL CODE OFFICIALS.
25. ALL WATER CLOSET FLUSH VALVE LEVERS SHALL BE LOCATED ON THE APPROACH SIDE OF THE WATER CLOSET.
26. ALL VENTS THROUGH ROOF SHALL BE LOCATED A MINIMUM OF 10'-0" FROM ANY OUTSIDE AIR INTAKE.
27. ALL COLD WATER, HOT WATER, AND DRAIN PIPING AT HANDICAPPED FIXTURES SHALL BE INSULATED WITH HANDI-LAV GUARD
MODELS 102 AND 105 (OR APPROVED EQUAL) INSULATION KITS.
28. NOT ALL PLUMBING ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.
PLUMBING FIXTURES SCHEDULE
MARK DESCRIPTION CW HW VENT WASTE
P-103
WATER CLOSET -
WALL HUNG
P-601
DRINKING
FOUNTAIN
1" 2" 4"
1/2" 1 1/2" 2"
WASTE
FIXTURE
UNITS
WATER
FIXTURE
UNITS
ELECTRIC
SENSOR
REMARKS
WATER CLOSET,WALL HUNG,
ELONGATED BOWL, 1.28 GPFYES
P-702 1/2" 1 1/2" 2"SHOWER 1/2"
6 6
1/2
FD-1
FLOOR DRAIN W
TRAP PRIMER
1 1/2" 2" 22
SEE SPEC 22 40 00
HB-1 HOSE BIBB 1/2" 2 NON FREEZE HOSE BIBB
P-202 1 1/2" 2"URINAL 3/4" 54 YES
P-418 1 1/2" 2"
LAVATORY -
WALL HUNG 1/2" 1/2" YES2 2
P-502 MOP SINK 1/2" 1/2" 1 1/2" 3" 32
P-528 1 1/2" 2"SINK- SINGLE BOWL 1/2" 1/2" 2 2 DROP IN SS SINK
WITH 1/2" TRAP PRIMER CONNECTION
ELECTRIC WATER HEATER SCHEDULE
MARK LOCATION
BASIS OF
DESIGN
EWH-1 BASEMENT
REMARKS
SERVICE
HOT
WATER
RHEEM
ELD40-TB
VOLUME
(GAL)
ELEMENT
WATTAGE
V/PH
208/1
ELECTRICAL
DIA HEIGHT
DIMENSIONS (IN)
20.25 48.25
WEIGHT
(LBS)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
P-001
PLUMBING SYMBOLS, ABBREVIATIONS
& SCHEDULES
ANCH
REVISIONS DATE
veerendra Image
CR
3"ø W (E) UNDERFLOOR
6"ø W (E) UNDERFLOOR
GENERAL
STORAGE
STORAGE
CLOSET
CRAWL SPACE
CRAWL SPACE
CRAWL SPACE
CRAWL SPACE
SLAB ON GRADE
DEMOLITION WORK
PIPE TO BE DEMOLISHED
DEMOLITION LEGEND
EXISTING PIPE TO REMAIN
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
PD100
BASEMENT PLUMBING SANITARY &
VENT DEMOLITION PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
BASEMENT PLUMBING SANITARY AND VENT DEMOLITION PLAN
1. POINT OF CONNECTION TO THE BUILDING.
2. EXISTING 5" SANITARY PIPE UP TO FIRST FLOOR TO BE DEMOLISHED.
3. EXISTING 3" SANITARY PIPE UP TO FIRST FLOOR TO BE DEMOLISHED.
4. EXISTING 6" SANITARY PIPE UP TO FIRST FLOOR TO BE DEMOLISHED.
5. REMOVE PIPE AS NEEDED FOR NEW WORK. REMAINING PIPE TO BE ABANDONED
IN PLACE AND SEAL BOTH ENDS.
KEYNOTES:#
SCALE: = 1'-0"3/8"
0 2 4 62
REVISIONS DATE
3"ø (E)
OFFICE OFFICE
STORAGE
TOILET
COPY RM OFFICE OFFICE OFFICE
HSK
OFFICE
OFFICEOFFICE
RECEPTION
OFFICEOFFICE
STORAGE
EQUIP RM
CORRIDOR
LOBBY
CORRIDOR CORRIDOR
107106 109 111 112 113
116117
103104
101A
DEMOLITION WORK
PIPE TO BE DEMOLISHED
DEMOLITION LEGEND
EXISTING PIPE TO REMAIN
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
PD101
FIRST FLOOR PLUMBING SANITARY &
VENT DEMOLITION PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
FIRST FLOOR PLUMBING SANITARY AND VENT DEMOLITION PLAN
1. EXISTING 6" SANITARY RISER TO BE DEMOLISHED.
2. DEMOLISH SANITARY AND VENT.
3. DEMOLISH FIXTURES AS SHOWN.
KEYNOTES:#
SCALE: = 1'-0"3/8"
0 2 4 62
REVISIONS DATE
OFFICE
CLOSET
204A
CONFERENCE RM
KITCHEN
203A
OFFICE
CLOSET
CORRIDOR
LOBBY
CORRIDOR
STORAGE
TOILET
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
MECH RM
HSK
DEMOLITION WORK
PIPE TO BE DEMOLISHED
DEMOLITION LEGEND
EXISTING PIPE TO REMAIN
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
PD102
SECOND FLOOR PLUMBING SANITARY
& VENT DEMOLITION PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
SECOND FLOOR PLUMBING SANITARY AND VENT DEMOLITION PLAN
1. DEMOLISH SANITARY AND VENT PIPING AS SHOWN.
2. DEMOLISH SANITARY BACK TO BASEMENT. DEMOLISH VENT PIPE UP AND VTR.
3. DEMOLISH FIXTURES AS SHOWN.
KEYNOTES:#
SCALE: = 1'-0"3/8"
0 2 4 62
REVISIONS DATE
CR
1/2" CW UP TO DRINKING FOUNTAINS
TO BE DEMOLISHED.
1 1/2" CW & 3/4" HW
UP TO BE
DEMOLISHED.
3/4" HW & CW UP TO
BE DEMOLISHED.
GENERAL
STORAGE
STORAGE
CLOSET
CRAWL SPACE
CRAWL SPACE
CRAWL SPACE
CRAWL SPACE
SLAB ON GRADE
DEMOLITION WORK
PIPE TO BE DEMOLISHED
DEMOLITION LEGEND
EXISTING PIPE TO REMAIN
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
PD200
BASEMENT PLUMBING WATER
DEMOLITION PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
BASEMENT PLUMBING WATER DEMOLITION PLAN
1. DEMOLISH DOMESTIC HOT AND COLD WATER PIPING IN BUILDING.
2. EXISTING WATER HEATER TO BE DEMOLISHED.
3. EXISTING BACK FLOW PREVENTER ASSEMBLY TO BE DEMOLISHED.
4. EXISTING CW SERVICE TO REMAIN.
KEYNOTES:#
SCALE: = 1'-0"3/8"
0 2 4 62
REVISIONS DATE
OFFICE OFFICE
STORAGE
TOILET
COPY RM OFFICE OFFICE OFFICE
HSK
OFFICE
OFFICEOFFICE
RECEPTION
OFFICEOFFICE
STORAGE
EQUIP RM
CORRIDOR
LOBBY
CORRIDOR CORRIDOR
107106 109 111 112 113
116117
103104
101A
DEMOLITION WORK
PIPE TO BE DEMOLISHED
DEMOLITION LEGEND
EXISTING PIPE TO REMAIN
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
PD201
FIRST FLOOR PLUMBING WATER
DEMOLITION PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
FIRST FLOOR PLUMBING WATER DEMOLITION PLAN
2 2
1. DEMOLISH EXISTING PIPING AS SHOWN.
2. DEMOLISH FIXTURES AS SHOWN.
KEYNOTES:#
SCALE: = 1'-0"3/8"
0 2 4 62
REVISIONS DATE
OFFICE
CLOSET
204A
CONFERENCE RM
KITCHEN
203A
OFFICE
CLOSET
CORRIDOR
LOBBY
CORRIDOR
STORAGE
TOILET
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
MECH RM
HSK
DEMOLITION WORK
PIPE TO BE DEMOLISHED
DEMOLITION LEGEND
EXISTING PIPE TO REMAIN
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
PD202
SECOND FLOOR PLUMBING WATER
DEMOLITION PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
SECOND FLOOR PLUMBING WATER DEMOLITION PLAN
1. DEMOLISH PIPING AS SHOWN.
2. DEMOLISH FIXTURES AS SHOWN.
KEYNOTES:#
SCALE: = 1'-0"3/8"
0 2 4 62
REVISIONS DATE
3"ø W UNDERFLOOR
4"ø W UP
P-528
2"ø W UNDERFLOOR
FD-1
1 1/2"ø V UP
2"ø W UP
EWH-1
INSTALL 3/4" CONNECTION
ON SINK TAIL PIECE AHEAD
OF P TRAP. EXTEND
PIPING IN WALL AS SHOWN
IN DETAIL D6/P-601.
6"ø W UNDERFLOOR (E)
2" DRAIN PIPE
FROM BACKFLOW
PREVENTER
4"ø W UNDERFLOOR
4"ø W UNDERFLOOR
MECHANICAL
ROOM
B01
CORRIDOR
B00
STORAGE
B02
ARMORY /
WEAPONS
B04
CRAWL SPACE
CRAWL SPACE
CRAWL SPACECRAWL SPACE
4"ø W IN CRAWL
SPACE
AREAWAY
4" W DROP BELOW
BASEMENT FLOOR
3"ø W A/C
3" W UP TO P-502
ON FIRST FLOOR
P-TRAP3" W UP
SLAB ON GRADE
2"ø W
CO
4"ø W
4"ø W
CO
CO
PENETRATE EXISTING
FOUNDATION WALL UNDER
SLAB
3"ø W
FCO
4"ø W UP
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
P-100
BASEMENT PLUMBING SANITARY &
VENT NEW WORK PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
BASEMENT PLUMBING SANITARY AND VENT NEW WORK PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
1. FOR PIPING UP, SEE P-101 FOR CONTINUATION.
GENERAL NOTES:
REVISIONS DATE
| Sheets |
| P-001 - PLUMBING SYMBOLS, ABBREVIATIONS & SCHEDULES |
| PD100 - BASEMENT PLUMBING SANITARY & VENT DEMOLITION PLAN |
| PD101 - FIRST FLOOR PLUMBING SANITARY & VENT DEMOLITION PLAN |
| PD102 - SECOND FLOOR PLUMBING SANITARY & VENT DEMOLITION PLAN |
| PD200 - BASEMENT PLUMBING WATER DEMOLITION PLAN |
| PD201 - FIRST FLOOR PLUMBING WATER DEMOLITION PLAN |
| PD202 - SECOND FLOOR PLUMBING WATER DEMOLITION PLAN |
| P-100 - BASEMENT PLUMBING SANITARY & VENT NEW WORK PLAN |