06 1200392 VA Bldg 20 PLMB 05 13 2021 Part 2.pdf

PDF 5 MB Posted

Attached to
Z2DZ-36C249-21-AP-3182 - 621-15-101 - Correct Admin Bldg. -20 Environment & Condition Deficiencies
Solicitation number
36C24921B0014
Issued by

About this file

This document package includes construction drawings and specifications for plumbing work on a federal building project. The project involves correcting environment and condition deficiencies at the Administration Building 20 on the campus of the James H. Quillen VA Medical Center in Mountain Home, Tennessee. Work includes office, conference room, locker room, storage, mechanical and electrical room modifications along with finish material replacements. The estimated construction cost range is between $1 million and $5 million. The solicitation will be released on or around October 20, 2021 and bids will be due on or around November 20, 2021. This requirement is a 100% set-aside for Service-Disabled Veteran Owned Small Businesses. The awarded contractor must be verified in the CVE database and registered in SAM at time of proposal submission and award.

View the file

Other files

File Type Posted
36C24921B0014 0007.pdf PDF
S04- SITE VISIT ATTENDEES - Bldg 20 - 621-15-101.pdf PDF
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-16-2021.pdf PDF
36C24921B0014 0006.pdf PDF
S05 - VA Comprehensive Asbestos Containing Materials Inspection Report January 2010 - 2.pdf PDF
S06 - AMENDMENT 5 - 36C24921B0014 0005.pdf PDF
S05-Mountain Home TN - VA Asbestos O AND M Plan January 2010 -1.pdf PDF
S05-RFI RESPONSE QUESTIONS - B20 Correct FCA Deficiencies 12-23-2021.pdf PDF
S02-LBP DOC-Building 20 - 36C24921B0014.pdf PDF
S02-Building 20 ACM Report - 36C24921B0014.pdf PDF
S02- Solicitation - 36C24921B0014 - 621-15-101 - Amendment - 0004.pdf PDF
36C24921B0014 0003.pdf PDF
S06- AMENDMENT2 - CO AND PROJECT CONFIRMATION DATES - 36C24921B0014 0002.pdf PDF
S02-AMENDMENT1 - 621-15-101 CORRECT ADMIN BLDG 20 ENVIRONMENT COND DEF - BID SPECIFICATIONS.pdf PDF
S02- AMENDMENT 1 - 03 1200392 VA Bldg 20 ARCH 05 13 2021 Part 1.pdf PDF
S02- AMENDMENT 1 - 06 1200392 VA Bldg 20 PLMB 05 13 2021 Part 1.pdf PDF
S06-AMENDMENT 01 - 621-15-101 - 36C24921B0014 0001 - WB.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1D.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1A.pdf PDF
05 1200392 VA Bldg 20 FIRE 05 13 2021.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 2D.pdf PDF
08 1200392 VA Bldg 20 ELEC 05 13 2021.pdf PDF
07 1200392 VA Bldg 20 MECH 05 13 2021.pdf PDF
09 1200392 VA Bldg 20 COMM 05 13 2021.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 2C.pdf PDF
S02-Contractor EMR Certification Form - 36C24921B0014.docx DOCX document
04 1200392 VA Bldg 20 INT 05 13 2021.pdf PDF
S02-TECHNICAL SPECS - Project 621-15-101.pdf PDF
02 1200392 VA Bldg 20 CIVIL 05 13 2021.pdf PDF
S02-621-15-101 - Correct Admin Bldg 20 .pdf PDF
01 1200392 VA Bldg 20 GEN 05 13 2021.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1B.pdf PDF
S02-WD - WASHINGTON TN - TN20210111 - JAN 2021.pdf PDF
03 1200392 VA Bldg 20 ARCH 05 13 2021 Part 2.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1C.pdf PDF
36C24921B0014.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P-502

P-418

P-202

P-103P-103

P-103

P-418

P-601

P-528

1 1/2"ø V DN

2"ø UP TO FD-1 2"ø W DN

& 1 1/2" V UP

2" W A/C

OFFICE

OFFICE

WOMEN

RESTROOM

STAFF

LOUNGE

MEN

RESTROOM

CORRIDOR

CORRIDOR

OFFICER

WORK

ROOM

INTERVIEW

ROOM

EVIDENCE

PROCESSING

EVIDENCE

ROOM

OFFICE

HOUSE

KEEPING

WAITING

ROOM

RECEPTION

ELECT.

OFFICE

OFFICE

3" W UP TO P-502

ON SECOND FLOOR

P-TRAP

3" W DN

AND 2" V UP 2" W A/C

2" W UP TO FD-1 W/TP

4" W DN & 3" W UP

1 1/2"ø V A/C

2" W UP TO P-702

2"ø W A/C

2" W UP TO P-702

4"ø W

4" W IN CHASE

1 1/2" V IN CHASE

4" W UP

3" V UP

WCO

4"ø W

4"ø W

3" V UP

2"ø W

4" W IN CHASE

1 1/2" V IN

CHASE

4" W DN & 3" V UP

4"ø W

2"ø W 2"ø W

1 1/4" ARM OVER

TO P-601

WCO

WCO

WCO

OFF SET VENT LINE

AROUND DUCTWORK

AS NEEDED

2" W UP

4" W UP

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

P-101

FIRST FLOOR PLUMBING SANITARY &

VENT NEW WORK PLAN

ANCH

SCALE: 3/8" = 1'-0"F1

FIRST FLOOR PLUMBING SANITARY AND VENT NEW WORK PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

1. FOR PIPING UP, SEE P-102 FOR CONTINUATION.

2. FOR PIPING DN, SEE P-100 FOR CONTINUATION.

GENERAL NOTES:

REVISIONS DATE

veerendra Image

P-502

P-418

P-103

P-702

P-418

P-103

2"ø V A/C

FD-1

1 1/2"ø V UP

CONFERENCE

ROOM

CHIEF

OFFICE

ELECT.

LOBBY

MECHANICAL

ROOM

HOUSE

KEEPING

OFFICE

OFFICE

OFFICE

OFFICE

209MEN

RESTROOM

MEN

SHOWER &

LOCKER

ROOM

WOMEN

SHOWER &

LOCKER

ROOM

206A

WOMEN

RESTROOM

OIT

DEPUTY

CHIEF

OFFICE

CORRIDOR

FD-1

3"ø V A/C

3" V DN & UP

3" W DN & 3" V UP

1 1/2" ARM OVER

3" V A/C

3" V DN

4" W DN

2" V

3" V UP

& DN

3" W DN

2" V A/C

2" W DN

1 1/2"ø V

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

P-102

SECOND FLOOR PLUMBING SANITARY

& VENT NEW WORK PLAN

ANCH

SCALE: 3/8" = 1'-0"F1

SECOND FLOOR PLUMBING SANITARY AND VENT NEW WORK PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

1. FOR PIPING DN, SEE P-101 FOR CONTINUATION.

2. FOR PIPING UP, SEE P-103 FOR CONTINUATION.

GENERAL NOTES:

REVISIONS DATE

3" VTR

1 1/2"ø V DN

3" V DN3" VTR

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

P-103

ATTIC PLUMBING SANITARY AND VENT

NEW WORK PLAN

ANCH

SCALE: = 1'-0"3/8"

0 2 4 62

SCALE: 3/8" = 1'-0"F1

ATTIC PLUMBING SANITARY AND VENT NEW WORK PLAN

1. FOR PIPING DN, SEE P-102 FOR CONTINUATION.

GENERAL NOTES:

REVISIONS DATE

2"ø DCW

3/4"ø DHW

P-528

3/4"ø DHW UP

3/4"ø DCW UP

1/2"ø DCW

1/2"ø DHW

1"ø DCW

1"ø DCW

3/4"ø DHW

EWH-1

HB-1

1/2"ø DCW

1/2"ø DCW

BFP

WITH ISO VALVE

WITH ISO VALVE

2"ø DCW

MECHANICAL

ROOM

B01

STORAGE

B02

ARMORY /

WEAPONS

B04

CORRIDOR

B03

TP

1/2" DCW TO TRAP

PRIMER W/ ISOLATION

VALVE. EXTEND 1/2"

DRAIN LINE TO FD-1.

CRAWL SPACE

CRAWL SPACE

CRAWL SPACE

CRAWL SPACE

SLAB ON GRADE

2"ø DCW UP

3/4"ø DHW UP

2"ø DCW 3/4"ø DHW

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

P-200

BASEMENT PLUMBING WATER NEW

WORK PLAN

ANCH

SCALE: 3/8" = 1'-0"F1

BASEMENT PLUMBING WATER NEW WORK PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

1. CONNECT NEW 3/4" DCW & DHW TO EWH-1.

2. NEW BACKFLOW PREVENTER ASSEMBLY. INSTALL ABOVE THE BACKFLOW

PREVENTER FOR FIRE PROTECTION

3. CONNECT EXISTING COLD WATER SERVICE TO NEW BACKFLOW PREVENTER.

4. EXISTING COLD WATER SERVICE TO THE BUILDING.

5. ROUTE PIPES BELOW THE CELIING.

KEYNOTES:#

1. FOR PIPING UP, SEE P-201 FOR CONTINUATION.

GENERAL NOTES:

REVISIONS DATE

P-103

P-103

P-202

P-418P-418

P-502

P-528

3/4"ø DHW DN & 1/2"ø

DHW UP

3/4"ø DCW DN & 1/2"ø

DCW UP

P-601

OFFICE

OFFICE

107 WOMEN

RESTROOM

STAFF

LOUNGE

MEN

RESTROOM

CORRIDOR

CORRIDOR

OFFICER

WORK

ROOM

INTERVIEW

ROOM

EVIDENCE

PROCESSING

EVIDENCE

ROOM

OFFICE

HOUSE

KEEPING

WAITING

ROOM

RECEPTION

ELECT.

OFFICE

OFFICE

1"ø DCW

1/2"ø DCW

1"ø DCW

1/2"ø DCW

1"ø DCW

1/2"ø DCW

1/2"ø DHW

1/2"ø DHW

1/2"ø DHW

1 1/2"ø DCW A/C

2"ø DCW DN

3/4"ø DHW DN

"ø

D C

W A

/C

1"ø DCW UP

1 1/4"ø DCW A/C 2"ø DCW A/C

3/4"ø DHW A/C

3/4"ø DCW UP 3/4"ø DHW UP

1 1/2"ø DCW A/C 1"ø DCW

1"ø DCW UP

3/4"ø DCW

3/4"ø DCW

1/2"ø DCW

1/2"ø DHW

/4

"ø D

H W

A /C

/4

"ø D

C W

A /C

/4

"ø D

H W

A /C

/4

"ø D

C W

A /C

3/4"ø DHW UP

3/4"ø DCW UP

1/2"ø DHW UP

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

P-201

FIRST FLOOR PLUMBING WATER NEW

WORK PLAN

ANCH

SCALE: 3/8" = 1'-0"F1

FIRST FLOOR PLUMBING WATER NEW WORK PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

1. FOR PIPING UP, SEE P-202 FOR CONTINUATION.

2. FOR PIPING DN, SEE P-200 FOR CONTINUATION.

GENERAL NOTES:

REVISIONS DATE

P-418 P-418

P-702

P-103

P-502

P-702

1/2"ø DHW 1/2"ø DCW

1/2"ø DCW

1/2"ø DCW

1/2"ø DHW

1/2"ø DHW

1/2"ø DHW

1/2"ø DCW

3/4"ø DCW DN

CONFERENCE

ROOM

CHIEF

OFFICE

ELECT.

LOBBY

MECHANICAL

ROOM

HOUSE

KEEPING

OFFICE

OFFICE

CORRIDOR

OFFICE

OFFICE

209MEN

RESTROOM

MEN

SHOWER &

LOCKER

ROOM

WOMEN

SHOWER &

LOCKER

ROOM

206A

WOMEN

RESTROOM

OIT

DEPUTY

CHIEF

OFFICE

CORRIDOR

CORRIDOR

TP

1/2" DCW TO TRAP

PRIMER W/

ISOLATION VALVE.

EXTEND 1/2" DRAIN

LINE TO FD-1.

1/2"ø DCW A/C

TP

1/2" DCW TO TRAP

PRIMER W/

ISOLATION VALVE.

EXTEND 1/2" DRAIN

LINE TO FD-1.

3/4"ø DHW DN

3/4"ø DCW DN

3/4"ø DHW DN

1/2"ø DHW DN

1/2"ø DCW DN

1"ø DCW DN

1"ø DCW

1"ø DCW DN

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

P-202

SECOND FLOOR PLUMBING WATER

NEW WORK PLAN

ANCH

SCALE: 3/8" = 1'-0"F1

SECOND FLOOR PLUMBING WATER NEW WORK PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

1. FOR PIPING DN, SEE P-201 FOR CONTINUATION.

GENERAL NOTES:

REVISIONS DATE

COMBINATION

CHECK-STOP

VALVES

SHOWER

CONTROL

VALVE TYPE

T/P

FINISHED

FLOOR

EDGE OF

SHOWER

INSTITUTIONAL

SHOWER HEAD

BALL TYPE

SHUTOFF

VALVE IN BOX

8"x8"x3"

ACCESS BOX

W/S.S. LOCKING

DOOR ON OPP.

WALL. SEE

DETAIL AT LEFT

TILE WALL

ALT HANDLE

POSITION

(CLOSED)

SHUTOFF

VALVE

SUPPLY

PIPE

ELEVATION

AA

S.S. DOOR W/VANDAL-PROOF

LOCK (KEYED)

SECTION A

ACCESS BOX W/VALVE

/2

15"

2'-0"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

P-601

PLUMBING DETAILS

ANCH

SCALE: NTSF7

FLOOR CLEANOUT DETAIL

SCALE: NTSD6

VENT THROUGH ROOF DETAIL

SCALE: NTSF1

WALL CLEANOUT WITH ACCESS COVER

SCALE: NTSF4

BACKFLOW PREVENTER

SCALE: 1" = 1'-0"D1

SHOWER DETAIL

DETAIL F7 KEYNOTE LEGEND

DETAIL D6 KEYNOTE LEGEND

DETAIL F1 KEYNOTE LEGEND

DETAIL F4 KEYNOTE LEGEND

REVISIONS DATE

2" ARM OVER

SINK

3/4" INSULATED

PIPE IN WALL

TRANSITION

TO 1 1/2" PIPE

COORDINATE INLET ELEVATION WITH

DIV. 23 AND DH-1 CONDENSATE DRAIN

FURR OUT WALL

HOT WATER SUPPLY

ISOLATION GATE

VALVE (TYP)

HEATER

DRAIN

FIN. FLOOR

THERMOMETER POSITIONED TO BE

COLD WATER SUPPLY

PIPE UNION (TYP)

FULL SIZE OF VALVE

OUTLET TO 15 CM OFF FLOOR

OR TO FLOOR DRAIN WHEN AVAILABLE

ROUTE TEMPT. AND PRESS. VALVE

READ FROM FLOOR (RANGE 0-200°F)

P&T RELIEF VALVE

(SETTING BY MFR. OF HEATER)

OUTLETELECTRIC WATER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

P-602

PLUMBING DETAILS

ANCH

SCALE: N.T.S.D6

CONDENSATE DRAIN CONNECTION FOR DEHUMIDIFIER DH-1

SCALE: N.T.S.D1

WATER HEATER DETAIL

REVISIONS DATE

FIRST FLOOR

BASEMENT

SECOND FLOOR

BFP

WATER HEATER

P-418

P-528

P-103 P-103

P-502

P-528

ROOF

P-502

P-702

P-418

P-103

1/2" DCW (2 FU)

1/2" DHW (2 FU)

1/2" DCW (2 FU)

1/2" DHW (2 FU)

1/2" DCW (2 FU)

1/2" DHW (2 FU)

1/2 " DCW (2 FU)

1/2 " DHW (2 FU)

3/4" DCW (4 FU)

3/4" DHW (4 FU)

1 " DCW (6 FU)

1" DCW (6 FU)

1 1/2" DCW

(12 FU)

1/2" DCW (3 FU)

1/2" DHW (3 FU)

1/2" DCW (3 FU)

1/2" DHW (3 FU)

3/4" DCW (6 FU)

3/4" DHW (6 FU)

1/2" DHW (2 FU)

1/2" DCW (2 FU)

2" DCW 3/4" DHW

HB-1

1/2" DCW (2 FU)

1 " DCW (6 FU)

P-601

1/2" DCW (1 FU)

P-103

1 " DCW (6 FU)

P-418

P-202

3/4" DCW (4 FU)

1/2" DCW (2 FU)

1/2" DHW (2 FU)

P-418

P-702

1/2" DCW (2 FU)

1/2" DHW (2 FU)

1/2" DCW (2 FU)

1/2" DHW (2 FU)

3/4" DCW (4 FU)

3/4" DHW (4 FU)

3/4" DHW

3/4" DHW

2" DCW

1" DCW

1 1/2 " DCW

1/2 " DHW

1 1/4 " DCW

3/4 " DHW

3/4" DHW

2" DCW

1/2" DHW

1 1/2" DCW

3/4 " DCW

3/4 " DHW

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

P-603

COLD AND HOT WATER RISER

SCHEMATIC

ANCH

SCALE: N.T.S.F2

COLD AND HOT WATER RISER SCHEMATIC

REVISIONS DATE

P-103 P-418

P-702

P-103 P-528 P-103 P-418 P-601

BASEMENT

ROOF

P-502

P-502

P-528

V T

R

V T

R

V

V

V

V

/2

V

/2

V

3" W

3" W

2" W

2" W

2" W

4" W

4" W 2" W 4" W 2" W

FD-1

FD-1

/2

V 2"

W

2" W

4" W UNDERFLOOR

FIRST FLOOR

SECOND FLOOR

ATTIC

FD-1

4" W

3" W

V

3" W

V

P-103 P-418

P-702

P-103 P-418 P-601

V

V

/2

V 2" W

2" W

2" W4" W 2" W

4" W

3" W

V

P-202

2" W

3" W

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

P-604

WASTE AND VENT RISER SCHEMATIC

ANCH

SCALE: N.T.S.E2

WASTE AND VENT RISER SCHEMATIC

REVISIONS DATE

Sheets
P-101 - FIRST FLOOR PLUMBING SANITARY & VENT NEW WORK PLAN
P-102 - SECOND FLOOR PLUMBING SANITARY & VENT NEW WORK PLAN
P-103 - ATTIC PLUMBING SANITARY AND VENT NEW WORK PLAN
P-200 - BASEMENT PLUMBING WATER NEW WORK PLAN
P-201 - FIRST FLOOR PLUMBING WATER NEW WORK PLAN
P-202 - SECOND FLOOR PLUMBING WATER NEW WORK PLAN
P-601 - PLUMBING DETAILS
P-602 - PLUMBING DETAILS
P-603 - COLD AND HOT WATER RISER SCHEMATIC
P-604 - WASTE AND VENT RISER SCHEMATIC

File details come from the government source that posted it. Updated .