07 1200392 VA Bldg 20 MECH 05 13 2021.pdf

PDF 2 MB Posted

Attached to
Z2DZ-36C249-21-AP-3182 - 621-15-101 - Correct Admin Bldg. -20 Environment & Condition Deficiencies
Solicitation number
36C24921B0014
Issued by

About this file

This presolicitation notice is for a construction project to correct environment and condition deficiencies at the Administration Building 20 at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The project involves modifications and demolition work to reconstruct space for police staff offices, conference rooms, evidence processing areas, locker rooms, mechanical and electrical rooms, and finish replacements. The work is estimated to cost between $1 million and $5 million. The NAICS code is 236220 and the small business size standard is $39.5 million. The solicitation will be posted on October 20, 2021 and close on November 20, 2021, following FAR Part 14.101 sealed bidding procedures. This is a 100% SDVOSB set-aside requiring active SAM and CVE registrations. Questions must be submitted in writing to the contract specialist by the specified date and include the project number, name, and solicitation number.

View the file

Other files

File Type Posted
36C24921B0014 0007.pdf PDF
S04- SITE VISIT ATTENDEES - Bldg 20 - 621-15-101.pdf PDF
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-16-2021.pdf PDF
36C24921B0014 0006.pdf PDF
S05 - VA Comprehensive Asbestos Containing Materials Inspection Report January 2010 - 2.pdf PDF
S06 - AMENDMENT 5 - 36C24921B0014 0005.pdf PDF
S05-Mountain Home TN - VA Asbestos O AND M Plan January 2010 -1.pdf PDF
S05-RFI RESPONSE QUESTIONS - B20 Correct FCA Deficiencies 12-23-2021.pdf PDF
S02-LBP DOC-Building 20 - 36C24921B0014.pdf PDF
S02-Building 20 ACM Report - 36C24921B0014.pdf PDF
S02- Solicitation - 36C24921B0014 - 621-15-101 - Amendment - 0004.pdf PDF
36C24921B0014 0003.pdf PDF
S06- AMENDMENT2 - CO AND PROJECT CONFIRMATION DATES - 36C24921B0014 0002.pdf PDF
S02-AMENDMENT1 - 621-15-101 CORRECT ADMIN BLDG 20 ENVIRONMENT COND DEF - BID SPECIFICATIONS.pdf PDF
S02- AMENDMENT 1 - 03 1200392 VA Bldg 20 ARCH 05 13 2021 Part 1.pdf PDF
S02- AMENDMENT 1 - 06 1200392 VA Bldg 20 PLMB 05 13 2021 Part 1.pdf PDF
S06-AMENDMENT 01 - 621-15-101 - 36C24921B0014 0001 - WB.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1D.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1A.pdf PDF
05 1200392 VA Bldg 20 FIRE 05 13 2021.pdf PDF
06 1200392 VA Bldg 20 PLMB 05 13 2021 Part 2.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 2D.pdf PDF
08 1200392 VA Bldg 20 ELEC 05 13 2021.pdf PDF
09 1200392 VA Bldg 20 COMM 05 13 2021.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 2C.pdf PDF
S02-Contractor EMR Certification Form - 36C24921B0014.docx DOCX document
04 1200392 VA Bldg 20 INT 05 13 2021.pdf PDF
S02-TECHNICAL SPECS - Project 621-15-101.pdf PDF
02 1200392 VA Bldg 20 CIVIL 05 13 2021.pdf PDF
S02-621-15-101 - Correct Admin Bldg 20 .pdf PDF
01 1200392 VA Bldg 20 GEN 05 13 2021.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1B.pdf PDF
S02-WD - WASHINGTON TN - TN20210111 - JAN 2021.pdf PDF
03 1200392 VA Bldg 20 ARCH 05 13 2021 Part 2.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1C.pdf PDF
36C24921B0014.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET NAMING CONVENTION

M-001A

2 DIGIT SEQUENTIAL # (01-99)

(FIRST DIGIT INDICATES PLAN

TYPE. SECOND DIGIT INDICATES

FLOOR)

1 DIGIT SHEET TYPE DESIGNATOR

0 - GENERAL

1 - PLANS

2 - ELEVATIONS

3 - SECTIONS

4 - ENLARGED PLANS

5 - DETAILS

6 - SCHEDULES AND DIAGRAMS

7 - VARIES

8 - VARIES

9 - 3D VIEWS (ISO, PERSPECTIVES)

2 DIGIT DISCIPLINE

DESIGNATOR

(IF ONLY ONE LETTER IS

USED, THE SECOND

LETTER IS REPLACED

WITH A DASH "-" AS A

PLACEHOLDER)**

1 DIGIT AREA

DESIGNATOR

(AREA DESIGNATOR

ONLY USED WHEN

PLANS ARE SUBDIVIDED

INTO AREAS.)

1. EXISTING EQUIPMENT IS SHOWN WITH THIN LINEWORK.

2. DEMOLISHED EQUIPMENT IS SHOWN WITH BOLD LINEWORK,

DASHED, AND HATCHED.

3. NEW OR RELOCATED EQUIPMENT IS SHOWN WITH BOLD

LINEWORK.

4. BELOW IS AN EXAMPLE OF EACH:

EXISTING EQUIPMENT

EQUIPMENT TO BE DEMOLISHED

NEW OR RELOCATED EQUIPMENT

NOTES:

GENERAL MECHANICAL NOTES

1. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY INSTALLATION IS MADE. DUCTWORK SHOWN ON PLANS IS SCHEMATIC. DUCTWORK SHALL BE INSTALLED TIGHT TO STRUCTURE. ALL TRANSITIONS, ELBOWS, ETC.

REQUIRED TO AVOID CONFLICTS & MAXIMIZE CEILING HEIGHTS. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER

TRADES SHALL BE RELOCATED AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER.

2. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT IS NOT LOCATED

OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.

3. WRITTEN DIMENSIONS ON DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

4. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE, UNIFIED FACILITIES

CRITERIA, AND INTERNATIONAL BUILDING CODE / INTERNATIONAL MECHANICAL CODE.

5. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT NECESSITATING

REMOVAL OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.

6. CEILING-MOUNTED EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC., DO NOT

BLOCK ACCESS TO EQUIPMENT AND RELATED ACCESSORIES.

7. COORDINATE WALL, FLOOR AND ROOF PENETRATIONS WITH THE GENERAL CONTRACTOR.

8. CAULK WITH SILICONE ALL GAPS BETWEEN WALL, CEILING AND FLOOR OPENINGS AND HVAC EQUIPMENT PENETRATIONS.

PATCH LARGE GAPS BEFORE CAULKING IS APPLIED.

9. DUCTWORK AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS AND THE PRESSURE

CLASSIFICATION OF EACH INDIVIDUAL DUCTWORK SYSTEM.

10. SQUARE ELBOWS SHALL ONLY BE USED WHERE SPACE LIMITATIONS PREVENT USE OF 1.5 RADIUS ELBOW AND ONLY UPON APPROVAL OF CONTRACTING OFFICER. PROVIDE TURNING VANES IN ALL 45° AND 90° SQUARE ELBOWS. TURNING VANES SHALL BE SINGLE THICKNESS TYPE WITHOUT RAILING EDGE. TURNING VANES LONGER THAN 36 INCHES SHALL BE DOUBLE THICKNESS

TYPE.

11. DUCTWORK RUNOUTS TO AIR DISTRIBUTION DEVICES SHALL BE SAME DIAMETER AS AIR DISTRIBUTION DEVICE INLET

CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.

12. FLEXIBLE DUCTWORK RUNOUTS FROM BRANCH DUCTS TO AIR DISTRIBUTION DEVICES SHALL NOT EXCEED 5 FEET IN LENGTH.

BENDS IN FLEXIBLE DUCTWORK SHALL NOT EXCEED A MAXIMUM OF 45 DEGREE CHANGE OF DIRECTION AND BE SUPPORTED SUCH THAT THE BEND RADIUS IS NOT RESTRICTIVE TO AIR FLOW THROUGH THE DUCT. FLEXIBLE DUCTWORK SHALL NOT BE

CRUSHED OR DISTORTED IN ITS FINAL CONFIGURATION.

13. ROUND DUCTWORK CONNECTIONS BETWEEN MAIN DUCT AND TERMINAL UNITS SHALL BE RIGID DUCT OF THE SAME DIAMETER

AS TERMINAL UNIT INLET CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.

14. PROVIDE SHEET METAL TRANSITIONS AT AIR HANDLING UNITS, HEAT PUMP UNITS, FANS, AND OTHER SIMILAR HVAC EQUIPMENT.

TRANSITION TO FULL SIZE OF CONNECTION ON UNIT. FLEXIBLE DUCT CONNECTORS SHALL BE USED ON FINAL CONNECTION TO

AIR HANDLING EQUIPMENT.

15. EXACT LOCATION OF CEILING DIFFUSERS, GRILLES AND REGISTERS SHALL BE DETERMINED BY ARCHITECTURAL REFLECTED

CEILING PLAN.

16. BLANK OFF AND INSULATE INACTIVE PORTIONS OF LOUVERS. ENTIRE LOUVERS NOT UTILIZED SHALL BE BLANKED OFF AND INSULATED BY THE LOUVER MANUFACTURER. REFER TO ARCHITECTURAL DRAWINGS FOR LOUVER LOCATIONS AND HVAC

DRAWINGS FOR HVAC EQUIPMENT CONNECTIONS.

17. LOUVER PLENUMS SHALL BE PITCHED DOWN TOWARD THE BOTTOM OF THE LOUVER. WHERE THIS IS NOT POSSIBLE, PROVIDE 3/4" DRAIN PIPING WITH P-TRAP FROM BOTTOM OF LOUVER TO NO MORE THAN 6" ABOVE NEAREST SANITARY DRAIN. DRAIN LINE SHALL SLOPE DOWN TOWARDS DISCHARGE LOCATION AT A MINIMUM OF 1/8" PER LINEAR FOOT.

18. PROVIDE ACCESS PANELS TO ACCESS DAMPERS, EQUIPMENT, AND VALVES LOCATED ABOVE HARD CEILINGS OR IN WALLS.

ACTUAL LOCATIONS SHALL BE FIELD DETERMINED.

19. EXACT LOCATIONS OF THERMOSTATS, CO2 SENSORS, AND EMCS SENSORS SHALL BE COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND ELECTRICAL EQUIPMENT. MOUNT THERMOSTATS AND CO2 SENSORS MINIMUM 48" AFF.

20. AIR HANDLING UNITS SERVING OCCUPIED AREAS SHALL HAVE MINIMUM MERV 13 FILTERS. UNITS NOT SERVING OCCUPIED ZONES SHALL HAVE MINIMUM MERV 8 FILTER. FILTERS SHALL BE INDUSTRY STANDARD SIZE. FILTERS SHALL NOT CREATE PRESSURE DROP EXCEEDING 10% OF EXTERNAL STATIC PRESSURE (ESP) CAPACITY LISTED IN EQUIPMENT SCHEDULE.

21. SUPPLY, RETURN, AND OUTDOOR AIR DUCTWORK SHALL BE INSULATED TO MEET OR EXCEED ASHRAE 90.1. EXTERIOR SUPPLY

AND RETURN AIR DUCTWORK SHALL BE PROVIDED WITH WEATHER-PROOF COVER.

22. COORDINATE LOCATIONS OF CONDENSATE DRAIN PIPING. PROVIDE CONDENSATE PUMPS AS REQUIRED WHERE SUFFICIENT SLOPE IS NOT AVAILABLE FOR STANDARD GRAVITY DRAIN, WITH OVERRIDE SWITCH TO POWER DOWN THE ASSOCIATED AIR HANDLING EQUIPMENT IN CASE OF CONDENSATE PUMP FAILURE. CONDENSATE DRAIN LINE SHALL SLOPE DOWN TOWARDS DISCHARGE LOCATION AT A MINIMUM OF 1/8" PER LINEAR FOOT. INSULATE INDOOR CONDENSATE PIPING WITH 3/4" CLOSED CELL

FOAM INSULATION.

23. PROVIDE SUPPORTS FOR PIPING AND DUCTWORK IN ACCORDANCE WITH SPECIFICATIONS.

24. PROVIDE HOUSEKEEPING PADS FOR MECHANICAL EQUIPMENT.

25. FOR WALL, FLOOR, AND SLAB PENETRATIONS SEAL AND PATCH ALL UNUSED PENETRATION SPACE TO MATCH EXISTING OR AS

SHOWN ON MECHANICAL DETAILS SHEET.

26. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN FOR INFORMATION ONLY. REFER TO SPECIFICATIONs FOR COMPLETE REQUIREMENTS.

27. PIPING INSULATION SHALL BE PROVIDED ON ALL PIPING SYSTEMS INCLUDING (BUT NOT LIMITED TO) CONDENSER WATER, REFRIGERANT, AND CONDENSATE DRAIN IN ACCORDANCE WITH ASHRAE 90.1.

28. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE

OVER SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.

29. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED LITERATURE.

30. DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.

31. EXPOSED DUCTWORK, WITH THE EXCEPTION OF DUCTWORK IN MECHANICAL ROOMS SHALL BE DOUBLE-WALL, SPIRAL

DUCTWORK WITH COATING.

32. IF ASBESTOS IS FOUND, STOP WORK IMMEDIATELY AND NOTIFY OWNER AND GENERAL CONTRACTOR. OWNER IS RESPONSIBLE

FOR ABATEMENT OF ASBESTOS.

33. NOT ALL MECHANICAL ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.

34. THE OUTDOOR DESIGN CONDITIONS AT JOHNSON CITY, TN ARE AS FOLLOWS PER VA HVAC DESIGN MANUAL, CHAPTER 7.1:

SUMMER: 90.5°F DRY BULB (0.4% OCCURRENCE)

71.8°F WET BULB (0.4% OCCURRENCE)

WINTER: 12.9°F DRY BULB (99.6% OCCURRENCE)

35. INDOOR DESIGN CONDITIONS WILL BE IN ACCORDANCE WITH CHAPTER 6 ROOM DATA SHEETS FROM VA HVAC DESIGN MANUAL.

OFFICE SPACES: 75°F (COOLING)

70°F (HEATING)

60%-20% RH

MAX NC LEVEL 40

CONFERENCE ROOM:75°F (COOLING)

70°F (HEATING)

60%-20% RH

MAX NC LEVEL 35

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

M-001

MECHANICAL GENERAL NOTES

ANCH

REVISIONS DATE

GENERAL MECHANICAL ABBREVIATIONS

@ AT

& AND

AFF ABOVE FINISHED FLOOR

A/C ABOVE CEILING

AC AIR CONDITIONER

AD AUTOMATIC DAMPER

ADJ ADJUSTABLE

AFMS AIRFLOW MEASURING STATION

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY

AHU AIR HANDLING UNIT

AMB AMBIENT

AMCA AIR MOVEMENT AND CONTROL ASSOCIATION

ARCH ARCHITECT, ARCHITECTURAL

AS AIR SEPARATOR

ASHRAE AMERICAN SOCIETY OF HEATING,

REFRIGERATING, AND AIR CONDITIONING

ENGINEERS

ASTM AMERICAN SOCIETY FOR TESTING AND

MATERIALS

AUX AUXILIARY

AWS AMERICAN WELDING SOCIETY

AWG AMERICAN WIRE GAUGE

B BOILER

BD BACKDRAFT DAMPER

BLDG BUILDING

BOD BOTTOM OF DUCT

B/F BELOW FLOOR

B/S BELOW SLAB

BT BUFFER TANK

BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR

CA COMBUSTION AIR INTAKE

CAV CONSTANT AIR VOLUME

CD CONDENSATE DRAIN

CFM CUBIC FEET PER MINUTE

CH CHILLER

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CLG COOLING

CMU CONCRETE MASONRY UNIT

CO CLEANOUT

CO2 CARBON DIOXIDE

CONC CONCRETE

CONN CONNECT, CONNECTING, CONNECTION

CONT CONTINUED

COP COEFFICIENT OF PERFORMANCE

COR CONTRACTING OFFICER'S REPRESENTATIVE

CT COOLING TOWER

CU CONDENSING UNIT

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

D DEPTH

DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS

DDC DIRECT DIGITAL CONTROLS

DEG. F (°F) DEGREES FAHRENHEIT

DF DESTRATIFICATION FAN

DH DEHUMIDIFIER

DIA DIAMETER

DIV DIVISION

DN DOWN

DP, PD DIFFERENTIAL PRESSURE, PRESSURE DROP

DSCU DUCTLESS SPLIT CONDENSING UNIT

DSHP DUCTLESS SPLIT HEAT PUMP

DSS DUCTLESS SPLIT SYSTEM (INDOOR UNIT)

DWG DRAWING

DX DIRECT EXPANSION

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EFF EFFICIENCY

ELEC ELECTRICAL

ERU ENERGY RECOVERY UNIT

ERV ENERGY RECOVERY VENTILATOR

ET EXPANSION TANK

ESP EXTERNAL STATIC PRESSURE

EUH ELECTRIC UNIT HEATER

EWT ENTERING WATER TEMPERATURE

EXT EXTERIOR

EXH EXHAUST

EXST, (E) EXISTING

FCU FAN COIL UNIT

FD FIRE DAMPER

FFE FINISHED FLOOR ELEVATION

FLA FULL LOAD AMPS

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

FPM FEET PER MINUTE

FSD FIRE SMOKE DAMPER

FT FOOT, FEET

FT WG FEET WATER GAUGE

FV FLUE VENT

GA GAGE

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

H HEIGHT

HGRH HOT GAS REHEAT

HP HEAT PUMP

HR HOUR

HSPF HEATING SEASONAL PERFORMANCE FACTOR

HTG HEATING

HTR HEATER

HVAC HEATING, VENTILATING, AND AIR CONDITIONING

HX HEAT EXCHANGER

HZ HERTZ

IMC INTERNATIONAL MECHANICAL CODE

IN INCH, INCHES

IN WC INCHES WATER COLUMN

IN WG INCHES WATER GAUGE

IPLV INTEGRATED PART LOAD VALUE

KW KILOWATTS

L LENGTH, LOUVER (WALL)

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LBF/IN2 POUNDS FORCE PER SQUARE INCH

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH 1000 BRITISH THERMAL UNITS

MCA MINIMUM CIRCUIT AMPACITY

MERV MINIMUM EFFICIENCY REPORTING VALUE

MECH MECHANICAL

MFR, MFG MANUFACTURER, MANUFACTURING

MIN MINIMUM

MOCP MAXIMUM OVER CURRENT PROTECTION

MOD MOTOR OPERATED DAMPER

MSS MANUFACTURER'S STANDARDIZATION SOCIETY

MTD MOUNTED

MUW MAKE-UP WATER (POTABLE/ DOMESTIC)

MVD MANUAL VOLUME DAMPER

NC NOISE CRITERIA

N.C. NORMALLY CLOSED

NO. NUMBER

N.O. NORMALLY OPEN

NPLV NET PART LOAD VALUE

NTS NOT TO SCALE

OA OUTSIDE AIR

OD OUTSIDE DAMPER

PD PRESSURE DROP

PH PHASE

PLBG PLUMBING

PPM PARTS PER MILLION

PRV PRESSURE RELIEF VALVE

QTY QUANTITY

RA RETURN AIR

RG RETURN GRILLE

RH RELATIVE HUMIDITY, ROOF HOOD

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID

RM ROOM

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

SA SUPPLY AIR

SD SMOKE DAMPER, SMOKE DETECTOR

SEER SEASONAL ENERGY EFFICIENCY RATIO

SF SUPPLY FAN

SMACNA SHEET METAL AND AIR CONDITIONING

CONTRACTOR'S NATIONAL ASSOCIATION

SP STATIC PRESSURE

SS STAINLESS STEEL

TSTAT THERMOSTAT

TEMP TEMPERATURE

TG TRANSFER GRILLE

THA TOTAL HEAT ABSORPTION

THR TOTAL HEAT REJECTION

TP TEMPERATURE/ PRESSURE TEST PORT

TYP TYPICAL

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UMCS UTILITY MONITORING AND CONTROL SYSTEM

V VOLTAGE, VOLTS

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VELO VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VSD VARIABLE SPEED DRIVE

W WATT(S)

W/ WITH

W/O WITHOUT

WB, Twb WET BULB (TEMPERATURE)

WD WIDE, WIDTH

WMS WIRE MESH SCREEN

AIR DISTRIBUTION DEVICE TAGS

DIFFUSER TYPE

A

400 AIRFLOW (CFM), "PLENUM", OR "TRANSFER"

A1

M-501

DRAWING REFERENCE KEY

REFER TO

DETAIL NUMBER

SHEET NUMBER OF DETAIL

RE:A1/M-501

NORTH ARROW

A

J

SD

SP

F

CO

DUCT SMOKE DETECTOR

CARBON MONOXIDE SENSOR

OVAL OR FLAT OVAL

CONTROL WIRING

STATIC PRESSURE SENSOR

ROUND

FIRESTAT

TEMPERATURE SENSOR

MISCELLANEOUS LEGEND

T

120 VOLT STAND BY POWER JUNCTION

BOX PROVIDED BY THE ELECTRICAL

CONTRACTOR JUNCTION BOX IS

DEDICATED FOR USE BY THE CONTROLS

CONTRACTOR.

VARIABLE FREQUENCY DRIVEVFD

M

FIRE DAMPER

H

DUCT MOUNTED HUMIDIFIER

EXHAUST AIR DUCT DOWN

EXHAUST AIR DUCT UP

RETURN AIR DUCT DOWN

30"x14"

SQUARE TO ROUND DUCT BRANCH TAKE-OFF

WITH 45 DEGREE BRANCH INLET

FLARED SPIN-IN WITH DAMPER AND

FLEX DUCT (DIFFUSER CONNECTION)

ROUND DUCT BRANCH TAKE-OFF FROM

RECTANGULAR MAIN WITH CONICAL TAP

FLEXIBLE DUCT CONNECTION

FLOW ARROW

DUCT SIZE TRANSITION

RECTANGULAR DUCT BRANCH TAKE-OFF

WITH 45 DEGREE BRANCH INLET

90 DEGREE DUCT ELBOW WITH TURNING VANES

24"Ø

DUCTWORK LEGEND

RETURN AIR DEVICE

ROUND DUCT. DIAMETER INDICATED IN INCHES.

IN-LINE 90 DEGREE RISE/DROP IN

SUPPLY DUCT (RIGHT SIDE IS HIGHER)

IN-LINE 90 DEGREE RISE/DROP IN

SUPPLY DUCT (LEFT SIDE IS HIGHER)

FD

SD

P - PNEUMATIC-ACTUACTED DAMPER

DAMPER TYPE:

M - MOTORIZED DAMPER (ELECTRIC)

VD

SMOKE DAMPER

VOLUME/BALANCING DAMPER

(LABEL MAY BE OMITTED)

BD

BACKDRAFT DAMPER

(COUNTER-BALANCED UNLESS

OTHERWISE NOTED)

RADIUS DUCT ELBOW - ROUND OR

RECTANGULAR (MIN. 1.5 RADIUS UNLESS

OTHERWISE NOTED)

RECTANGULAR DUCT. SIZE INDICATED IN

INCHES, FIRST NUMBER IS SIDE SHOWN.

DASHED LINES INDICATE ACOUSTICAL LINER

SUPPLY AIR DIFFUSER -

FLOW ARROWS INDICATE AIR PATTERN.

NO FLOW ARROWS SHOWN INDICATES

4-WAY PATTERN.

FSD

COMBINATION

FIRE/SMOKE DAMPER

EXHAUST AIR DEVICE

RC REMOTE CONTROLLER (VRF SYSTEM)

SERVICE CLEARANCE

T THERMOSTAT

H HUMIDISTAT

$ START/ STOP SWITCH

TH THERMOSTAT/ HUMIDISTAT

HUMIDITY SENSORH

DEMOLISHED

CONNECT TO EXISTING

DISCONNECT FROM EXISTING

IN-LINE 90 DEGREE RISE/DROP IN

RETURN DUCT (RIGHT SIDE IS HIGHER)

DUCT SIZE TRANSITION RECTANGULAR TO

ROUND

30"/14" FLAT OVAL DUCT. SIZE INDICATED IN INCHES,

FIRST NUMBER IS SIDE SHOWN

RETURN AIR DUCT UP

SUPPLY OR OUTSIDE AIR DUCT DOWN

SUPPLY OR OUTSIDE AIR DUCT UP

IN-LINE 90 DEGREE RISE/DROP IN

RETURN DUCT (LEFT SIDE IS HIGHER)

IN-LINE 90 DEGREE RISE/DROP IN

EXHAUST DUCT (RIGHT SIDE IS HIGHER)

IN-LINE 90 DEGREE RISE/DROP IN

EXHAUST DUCT (LEFT SIDE IS HIGHER)

DEMOLITION KEY

CONNECTION SIZE

(X"xX" INDICATES RECTANGULAR, X"/X"

INDICATES OVAL, X"Ø INDICATES ROUND)

X"xX"

TYP. OF #

TYPICAL OF QUANTITY INDICATED

DP DIFFERENTIAL PRESSURE SENSOR

C CARBON DIOXIDE SENSOR

AQ AIR QUALITY SENSOR

SKD

DUCT MOUNTED SMOKE DETECTOR

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

M-002

MECHANICAL ABBREVIATIONS AND

LEGENDS

ANCH

GENERAL

STORAGE

STORAGE

CLOSET

STEAM LINE, TO BE CAPPED

FIBER OPTIC GOING OUT OF BLDG.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

MD100

BASEMENT MECHANICAL DEMOLITION

PLAN

ANCH

SCALE: 3/8" = 1'-0"F1

BASEMENT MECHANICAL DEMOLITION PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

DEMOLITION WORK

DUCT TO BE DEMOLISHED

DEMOLITION LEGEND

EXISTING DUCT TO REMAIN

1. DEMOLISH EXISTING OUTSIDE AIR DUCT AND ASSOCIATED DAMPER. CAP EXISTING OUTSIDE AIR LOUVER TO REMAIN FOR

FUTURE USE.

2. DEMOLISH EXISTING AHU AND REPLACE IT WITH NEW AHU-1. REFER TO M-101 AND M-601 FOR INFORMATION ON AHU-1.

DEMOLISH ALL EXISTING ASSOCIATED CONTROLS, EQUIPMENT AND DUCT SUPPORT, CONDENSATE PAN AND PIPING.

3. DEMOLISH EXISTING RETURN DUCT AND SUPPLY DUCT TO EXISTING AHU.

4. DEMOLISH EXISTING STEAM LINE AND CAP THE OPENINGS. REFER TO E8/MD100.

5. DEMOLISH EXISTING REFRIGERANT LINES AND CONDENSING UNITS. EVACUATE THE REFRIGERANT FROM THE SYSTEM

AND DISPOSE OF IT APPROPRIATELY.

# KEYNOTES:

SCALE: N.T.S.E9

STEAM PIPE PICTURE

5 5

OFFICE

STORAGE

TOILET

COPY RM

OFFICE

OFFICE

OFFICE

HSK

OFFICE

OFFICEOFFICE

RECEPTION

OFFICEOFFICE

STORAGE

EQUIP RM

CORRIDOR

LOBBY

CORRIDOR

CORRIDOR

116117

103104

101A

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

MD101

FIRST FLOOR MECHANICAL

DEMOLITION PLAN

ANCH

SCALE: 3/8" = 1'-0"F1

FIRST FLOOR MECHANICAL DEMOLITION PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

DEMOLITION WORK

DUCT TO BE DEMOLISHED

DEMOLITION LEGEND

EXISTING DUCT TO REMAIN

1. DEMOLISH ALL SUPPLY, EXHAUST, AND RETURN DUCTWORK AS SHOWN.

2. DEMOLISH ALL SUPPLY DIFFUSERS, RETURN AND EXHAUST GRILLES, BRANCH

DUCTWORK, FLEX DUCTS AND VOLUME DAMPERS AS SHOWN.

3. DEMOLISH SUPPLY DUCT AND RETURN DUCT THROUGH THE CHASE BACK TO THE

AHU IN THE BASEMENT.

4. LOCATION OF RETURN GRILLES SHOULD BE FIELD VERIFIED BY THE CONTRACTOR.

# KEYNOTES:

M

CLOSET

204A

CONFERENCE RM

KITCHEN

203A

OFFICE

CLOSET

CORRIDOR

LOBBY

CORRIDOR

STORAGE

TOILET

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

MECH RM

HSK

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

MD102

SECOND FLOOR MECHANICAL

DEMOLITION PLAN

ANCH

SCALE: 3/8" = 1'-0"F1

SECOND FLOOR MECHANICAL DEMOLITION PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

DEMOLITION WORK

DUCT TO BE DEMOLISHED

DEMOLITION LEGEND

EXISTING DUCT TO REMAIN

(E) AHU

1. DEMOLISH ALL SUPPLY, EXHAUST, AND RETURN DUCTWORK AS SHOWN.

2. DEMOLISH ALL SUPPLY DIFFUSERS, RETURN AND EXHAUST GRILLES, BRANCH

DUCTWORK, FLEX DUCTS AND VOLUME DAMPERS AS SHOWN.

3. DEMOLISH EXISTING AHU AND REPLACE IT WITH NEW AHU-2. REFER TO M-102

AND M-601 FOR INFORMATION ON AHU-2. DEMOLISH ALL EXISTING ASSOCIATED

CONTROLS, EQUIPMENT AND DUCT SUPPORT, CONDENSATE PAN AND PIPING.

4. DEMOLISH OUTSIDE AIR DAMPER, LOUVER, AND ASSOCIATED CONTROLS.

5. LOCATION OF RETURN GRILLES SHOULD BE FIELD VERIFIED BY THE

CONTRACTOR.

# KEYNOTES:

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

MD103

ATTIC MECHANICAL DEMOLITION

PLAN

ANCH

SCALE: 3/8" = 1'-0"E1

ATTIC MECHANICAL DEMOLITION PLAN

1. ALL EXISTING ABANDONED MECHANICAL EQUIPMENT AND DUCTWORK NOT SERVING THE

BUILDING SHALL BE DEMOLISHED.

2. ALL EXISTING OPENINGS THROUGH ROOF AND SIDEWALL SHALL BE REPAIRED AND PATCHED

AFTER DEMOLITION TO MATCH ROOF.

# KEYNOTES:

SCALE: = 1'-0"3/8"

0 2 4 62

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

MD104

ROOF MECHANICAL DEMOLITION PLAN

ANCH

SCALE: 3/8" = 1'-0"F1

ROOF MECHANICAL DEMOLITION PLAN

1. DEMOLISH ALL EXISTING MECHANICAL EQUIPMENT ON ROOF AS SHOWN.

# KEYNOTES:

SCALE: = 1'-0"3/8"

"x

AHU

MECHANICAL

ROOM

B01

STORAGE

B02

ARMORY /

WEAPONS

B04

CORRIDOR

B03

8"x6"

EG-2

75 CFM

"ø

FD

AC

OUTDOOR UNIT FOR

FD

WATER HEATER

6"ø8"ø

8"x6"

"x

8"x8"

"x

DH

FD

CONCRETE PADS. SEE DETAIL F1/M-502

FD

42"x18"

VD

VD

PLENUM

CRAWL SPACE

CRAWL SPACE

CRAWL SPACE

CRAWL SPACE

CRAWL

SPACE

CRAWL

SPACE

CRAWL

SPACE

CRAWL

SPACE

AREAWAY

SD

14"x20"

20"x16"

FD

FD

CU

CU

REFRIGERANT

PIPING FROM

AHU-1 TO CU-1

REFRIGERANT

PIPING UP FROM

AC-1 ON SECOND

FLOOR TO THE

OUTDOOR UNIT

REFRIGERANT

PIPING UP FROM

AHU-2 ON

SECOND FLOOR

TO THE CU-2

' A

F F

' A

F F

8"x6"

SD-4

50 CFM

8"x6"

SD-4

50 CFM

10"x6"

SD-5

100 CFM

8"x6"

EG-2

125 CFM

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

M-100

BASEMENT MECHANICAL NEW WORK

PLAN

ANCH

SCALE: 3/8" = 1'-0"E1

BASEMENT MECHANICAL NEW WORK PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

SCALE: = 1'-0"3/8"

0 2 4 62

SHEET NOTES:

1. COORDINATE SLAB PENETRATION LOCATIONS AND SIZES WITH EXISTING

STRUCTURAL.

2. BALANCE THE AIRFLOWS AT THE SUPPLY DIFFUSERS, RETURN REGISTERS AND

EXHAUST REGISTERS VIA MANUAL VOLUME DAMPERS WHICH ARE TO BE PROVIDED

AS REQUIRED FOR BALANCING THE AIR DEVICES WITHIN SPECIFIED TOLERANCE

LIMITS .

3. ACCESS TO BE PROVIDED TO DAMPERS IN THE GYPSUM BOARD CELING.

1. CONNECT 12X10 OUTSIDE AIR DUCT TO EXISTING LOUVER. ENSURE 1 SQ.FT OF NET FREE AREA AT

THE LOUVER FACE. TRANSITION AS REQUIRED FOR TERMINATION.

2. PROVIDE MOTORIZED DAMPER AND INTERLOCK IT OPEN WITH THE OPERATION OF AHU-1.

3. 30x12 SUPPLY DUCT TO FIRST FLOOR. PROVIDE FIRE DAMPER AT FIRST FLOOR SLAB PENETRATION

WITH ACCESS PANEL IN DUCT. REFER TO M-101 FOR CONTINUATION.

4. 28x12 RETURN DUCT FROM FIRST FLOOR. PROVIDE FIRE DAMPER AT FIRST FLOOR SLAB

PENETRATION WITH ACCESS PANEL IN DUCT. REFER TO M-101 FOR CONTINUATION.

5. CONNECT UNIT TO THE NEW REFRIGERANT PIPING. ROUTE 3/4" CONDENSATE PIPING TO FLOOR DRAIN IN ROOM. SEE P-100 FOR FLOOR DRAIN LOCATION. SEE NOTE 7 BELOW FOR ADDITIONAL

INFORMATION ON REFRIGERANT PIPING.

6. 8X8 EXHAUST DUCT TO FIRST FLOOR. REFER M-101 FOR CONTINUATION. PROVIDE FIRE DAMPER AT

FIRST FLOOR SLAB PENETRATION WITH ACCESS PANEL IN DUCT.

7. PROVIDE NEW CONDENSING UNITS WITH ASSOCIATED REFRIGERANT PIPING AND ALL PIPING

ACCESSORIES AS NECESSARY AS PER MECHANICAL SCHEDULE M-601. PROVIDE CONCRETE PADS

TO SUPPORT THE NEW UNITS AS NECESSARY.

8. DUCTWORK IN CRAWL SPACE - SOME EXCAVATION MAY BE REQUIRED.

KEYNOTES:#

7 7

9. MOUNT DH-1 ON WALL AT 5' AFF. ROUTE CONDENSATE DRAIN TO A CONNECTION POINT PROVIDED

BY DIV. 22 AT THE SINK IN THE ROOM.

10. THERMOSTAT WIRING FROM AHU- 1 TO FIRST FLOOR. REMOTE SENSING BULB FOR THERMOSTAT TO

BE PLACED IN 14 X 20 RETURN DUCT.

F A

C P

OFFICE

OFFICE

WOMEN

RESTROOM

STAFF

LOUNGE

MEN

RESTROOM

CORRIDOR

CORRIDOR

OFFICER

WORK

ROOM

INTERVIEW

ROOM

EVIDENCE

PROCESSING

EVIDENCE

ROOM

OFFICE

HOUSE

KEEPING

WAITING

ROOM

RECEPTION

ELECT.

OFFICE

OFFICE

8"ø

SD-1

150 CFM

6"ø

SD-1

100 CFM 10"ø

SD-1

350 CFM

8"ø

SD-1

150 CFM

8"ø

SD-1

150 CFM

8"ø

SD-1

150 CFM

6"ø

SD-1

100 CFM

6"ø

SD-1

100 CFM

8"ø

SD-1

150 CFM

6"ø

SD-1

120 CFM

8"x8"

RG-1

150 CFM

6"x6"

RG-1

100 CFM

8"x8"

RG-1

300 CFM

10"x10"

RG-1

300 CFM

8"x8"

RG-1

150 CFM6"x6"

RG-1

50 CFM

6"x6"

RG-1

100 CFM

8"x8"

RG-1

150 CFM

8"ø

EG-3

150 CFM 8"ø

EG-3

150 CFM

6"ø

SD-1

100 CFM

6"ø

SD-1

50 CFM

6"x6"

RG-1

100 CFM

6"ø

SD-1

50 CFM

10"ø

SD-1

250 CFM

8"x8"

RG-1

120 CFM

6"x6"

RG-1

50 CFM

8"ø

SD-2

200 CFM

6"x6"

RG-1

100 CFM

6"x6"

RG-1

50 CFM

"x

"x

6"x36"

RG-2

200 CFM

"x

"x

"8 "x

"x

"x

16"x12"

"x

"x

"x

"x

14"x10"12"x10" 12"x10"14"x10"

"ø

6"x6"10"x10"

"x

8"x6"

EG-2

50 CFM

14"x10"20"x12"

"x

"x

8"ø 8"ø 8"x10"

"x

"ø

"ø

"x

6"ø

"x

14"x10" 8"x10"

10"x8"12"x8"

"x

"ø

"ø

"ø

6"x6"

"x

"ø

FSD

8"ø

10"ø

"x

FSD

8"ø

"ø

8"x8"

16"x12"12"x16"

14"x20" 20"x16"

FSD

2-SLOT, 4' LONG, 1" SLOT WIDTH

8"ø

12"x8"

T

TO AHU-1

FSD

FSD

FSD

FSD

FSD

6"ø

SD-3

75 CFM 6"ø

SD-3

75 CFM

"ø6

"ø

6"ø

EG-3

50 CFM

"ø

FD

FD

FD

FD

H

TO AHU-1

10"x10"

REFRIGERANT

LINE FROM AC-1

ON SECOND

FLOOR

REFRIGERANT LINE

FROM AHU-2 ON

SECOND FLOOR

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

M-101

FIRST FLOOR MECHANICAL NEW

WORK PLAN

ANCH

SCALE: 3/8" = 1'-0"F1

FIRST FLOOR MECHANICAL NEW WORK PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

SHEET NOTES:

1. COORDINATE FINAL LOCATIONS AND HEIGHTS OF DIFFUSERS, REGISTERS AND

GRILLES WITH ARCHITECTURAL REFLECTED CEILING PLANS.

2. COORDINATE SLAB PENETRATION LOCATIONS AND SIZES WITH EXISTING

STRUCTURAL.

3. BALANCE THE AIRFLOWS AT THE SUPPLY DIFFUSERS, RETURN REGISTERS AND

EXHAUST REGISTERS VIA MANUAL VOLUME DAMPERS WHICH ARE TO BE PROVIDED

AS REQUIRED FOR BALANCING THE AIR DEVICES WITHIN SPECIFIED TOLERANCE

LIMITS .

1. 10X10 AND 8X8 EXHAUST DUCTS UP TO FLOOR ABOVE. REFER TO M-102 AND M-103 FOR CONTINUATION.

2. 20X16 SUPPLY DUCT FROM AHU-1 IN THE BASEMENT. REFER TO M-100 FOR CONTINUATION.

3. 14X20 RETURN DUCT TO AHU-1 IN THE BASEMENT. REFER TO M-100 FOR CONTINUATION.

4. PROVIDE LINEAR SLOT DIFFUSER. REFER TO MECHANICAL SCHEDULES ON SHEET M-601 FOR MORE INFORMATION.

COORDINATE FINISH WITH ARCHITECT.

5. REMOTE SENSING BULB FOR THERMOSTAT TO BE PLACED IN THE 14 X 20 RETURN DUCT AT THE BASEMENT TO AHU-1.

REFER TO M-100 FOR CONTINUATION.

6. 8X8 EXHAUST DUCTS DN TO FLOOR BELOW. REFER TO M-100 FOR CONTINUATION.

# KEYNOTES:

AHU

CONFERENCE

ROOM

203 CHIEF

OFFICE

ELECT.

LOBBY

MECHANICAL

ROOM

OFFICE

OFFICE

CORRIDOR

OFFICE

OFFICE

MEN

RESTROOM

208MEN

SHOWER &

LOCKER

ROOM

WOMEN

SHOWER &

LOCKER

ROOM

206A

WOMEN

RESTROOM

OIT

DEPUTY

CHIEF

OFFICE

CORRIDOR

CORRIDOR

HOUSE

KEEPING

8"ø

SD-1

200 CFM

6"ø

SD-1

75 CFM 8"ø

SD-1

100 CFM

6"ø

SD-1

100 CFM

8"ø

SD-1

150 CFM

8"ø

SD-1

200 CFM

8"ø

SD-1

150 CFM

8"x8"

RG-1

200 CFM

6"x6"

RG-1

100 CFM

8"x8"

RG-1

150 CFM

8"x8"

RG-1

200 CFM

8"x8"

RG-1

150 CFM

10"x10"

RG-1

250 CFM

8"ø

EG-1

120 CFM

8"ø

EG-3

75 CFM

8"ø

EG-3

75 CFM

8"ø

SD-1

250 CFM

6"x6"

RG-1

50 CFM

8"ø

EG-1

130 CFM

8"ø

SD-1

250 CFM

10"x10"

RG-1

250 CFM

8"ø

SD-2

200 CFM

8"ø

SD-2

200 CFM

8"ø

SD-1

100 CFM

8"ø

SD-1

175 CFM

"x

12"x8"

AC

"x

6"x6"

"x

"x

"x

6"x48"

RG-2

400 CFM

12"x10"14"x10"

"x

20"x10"

"ø

"ø

"x

8"x6"

EG-2

50 CFM

10"x12"12"x12"

14"x10"

12"x10"

"ø

"ø

"ø

14"x10"

"x

"ø

"ø

8"x10"

"x

"x

"ø 8 "ø

"x

8"ø

6"ø

8"ø

"x

8"x10"

"x

10"x10"

8"x10"

24"x12" 8 "x

8"x8"

14"x16"

2-SLOT, 4' LONG, 1" SLOT WIDTH,

"x

18"x10"

16"x10"

"x

T

FSD

10"x8"

FSD

FSD

T

VD

VD

58"x22" PLENUM

6"ø

SD-3

50 CFM

6"ø

SD-3

50 CFM

"ø6 "ø

6"x6"

RG-1

50 CFM

6"x6"

SD

FD

REFRIGERANT

PIPING DN TO

BASEMENT

REFRIGERANT

PIPING DN TO

BASEMENT

H

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

M-102

SECOND FLOOR MECHANICAL NEW

WORK PLAN

ANCH

SCALE: 3/8" = 1'-0"F1

SECOND FLOOR MECHANICAL NEW WORK PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

4 4

SHEET NOTES:

1. COORDINATE FINAL LOCATION AND HEIGHTS OF DIFFUSERS AND GRILLES WITH ARCHITECTURAL

REFLECTED CEILING PLANS.

2. COORDINATE SLAB PENETRATION LOCATIONS AND SIZES WITH EXISTING STRUCTURAL.

3. BALANCE THE AIRFLOWS AT THE SUPPLY DIFFUSERS, RETURN REGISTERS AND EXHAUST GRILLES VIA

MANUAL VOLUME DAMPERS WHICH ARE TO BE PROVIDED AS REQUIRED FOR BALANCING THE AIR

DEVICES WITHIN SPECIFIED TOLERANCE LIMITS.

1. 14X12 OUTSIDE AIR DUCT UP TO THE ATTIC. SEE M-103 FOR CONTINUATION.

2. REMOTE SENSING BULB FOR THERMOSTAT TO BE PLACED IN THE 24X14

RETURN DUCT TO AHU-2.

3. 10X10 GENERAL EXHAUST DOWN TO FIRST FLOOR AND 14x16 EXHAUST DUCT

UP TO EXHAUST FAN EF-1 IN THE ATTIC.

4. PROVIDE LINEAR SLOT DIFFUSERS AS SHOWN. COORDINATE COLOR AND

FINISH WITH ARCHITECT.

5. PROVIDE REFRIGERANT PIPING. ROUTE 3/4" CONDENSATE DRAIN TO FLOOR

DRAIN IN ROOM. SEE P-102 FOR LOCATION OF FLOOR DRAIN.

6. INSTALL AC-1 AT 7' A.F.F. PROVIDE REFRIGERANT PIPING TO CONNECT TO THE

OUTDOOR UNIT AND SIZE THE PIPING PER MANUFACTURER'S

RECOMMENDATIONS. PROVIDE ACCESSORIES AND SERVICE CLEARANCE AS

NECESSARY. ROUTE 3/4" CONDENSATE DRAIN TO FLOOR DRAIN IN ROOM. SEE

P-102 FOR LOCATION OF FLOOR DRAIN.

7. 8X8 GENERAL EXHAUST DOWN TO FIRST FLOOR AND 8X8 EXHAUST DUCT UP

TO EXHAUST FAN EF-2 IN THE ATTIC.

# KEYNOTES:

"x

"x

EUH

EUH

T

T "x

"x

8"x8"

FD

FD

EF

"x

TG-1

12"x8"

TYP. 18

EF

FD

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

M-103

ATTIC MECHANICAL NEW WORK PLAN

ANCH

SCALE: = 1'-0"3/8"

0 2 4 62

SCALE: 3/8" = 1'-0"F1

ATTIC MECHANICAL NEW WORK PLAN

1. GENERAL EXHAUST FAN EF-1 IN THE ATTIC. REFER TO MECHANICAL SCHEDULE M-601 FOR MORE INFORMATION.

2. GENERAL EXHAUST FAN EF-2 IN THE ATTIC. REFER TO MECHANICAL SCHEDULE M-601 FOR MORE INFORMATION.

3. PROVIDE MOTORIZED DAMPER AND INTERLOCK IT WITH AHU-2.

4. COORDINATE PENTHOUSE LOUVER LOCATION ON ROOF AND ROOF OPENING SIZE WITH ARCHITECTURAL.

5. 14X12 OUTSIDE AIR DUCT DOWN TO THE SECOND FLOOR. SEE M-102 FOR CONTINUATION.

6. 14X16 EXHAUST DUCT DOWN TO THE SECOND FLOOR. SEE M-102 FOR CONTINUATION.

7. 8X8 EXHAUST DUCT DOWN TO THE SECOND FLOOR. SEE M-102 FOR CONTINUATION.

# KEYNOTES:

LV

LV

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

M-104

ROOF MECHANICAL NEW WORK PLAN

ANCH

SCALE: 3/8" = 1'-0"F1

ROOF MECHANICAL NEW WORK PLAN

1. COORDINATE PENETRATION LOCATIONS WITH ARCHITECTURAL. COORDINATE PENETRATION SIZES WITH MECHANICAL SCHEDULES M-601.

# KEYNOTES:

SCALE: = 1'-0"3/8"

FROM STRUCTURE

SAME AS DIFFUSER

INLET: 5'-0" MAX

FLEXIBLE DUCT SIZE

LENGTH.

12"

CEILING

SUPPORT SADDLE

VOLUME DAMPER W/

LOCKING QUADSADDLE

SHEET METAL

CONICAL OUTLET

BRANCH DUCT

ONLY FOR CHANGE OF

DIRECTION GREATER

USE RIGID ELBOWS

THAN 45°

SEE SPECIFICATIONS FOR CLAMPS

AND SEALANT (TYP.)

TYPICAL

DIFFUSER OR

REGISTER IN

LAY-IN CLG.

THERMAL INSULATION

SEE SPECIFICATIONS

DRAW THRU

BLOW THRU

2" PLUS X

1" MINIMUM

X

2X

UNIT TYPE A B

WHERE X = STATIC PRESSURE IN PAN

DRAIN LINE SHALL BE AT LEAST THE SAME

SIZE AS THE NIPPLE ON THE DRAIN PAN

PIPING SHALL BE RIGID COPPER TYPE L

OR TYPE M UNLESS NOTE BELOW IS MET

PITCH DOWN

TOWARD DRAIN

CLEAN OUT

FLOOR SINK

DRAIN

PAN

NOTE:

1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND IS

INDOORS AND DOES NOT PASS THROUGH RATED BARRIERS.

2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE

TO BE CONNECTED.

DIELECTRIC

FITTING

A B

MAIN EXHAUST OR RETURN

PLAN VIEW

AIR

FLOW AIR

FLOW

PROVIDE VOLUME DAMPER

AT EACH BRANCH DUCT

1/4W OR 4" MIN.

BRANCH DUCT

VD

W

420ONE 1 x 18 GA STRAP36

TWO 1/2. RODS

TWO 3/8. RODS

ONE 1 x 16 GA STRAP

50 700

ONE 1 x 22 GA STRAP

QUANTITY/SIZEMAX. DUCT

HANGER STRAPS OR RODS

MAX. LOAD

LBS.

MAX.

IN.

SPACING

IN. IN.

NOTE:

TABULATED DATA FROM SMACNA

ALLOWS FOR DUCT REINFORCING AND

INSULATION, BUT NO EXTERNAL LOAD.

BAND

OVER 50"

HANGER RODS

BAND OF SAME

SIZE AS HANGER

STRAP

LOAD RATED

FASTENERS

50" & UNDER

NOTE:

1.

2.

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR

MULTI-BLADE DAMPERS & ROUND DAMPERS.

INSULATION SEE

SPECIFICATION

DAMPER BLADE

1/8" CLEARANCE

ALL AROUND

OUTSIDE END BEARING

INSIDE END BEARING

HANDLE WITH

LOCKING

QUADRANT

INSULATION

STAND-OFF

1/2" ROUND ROD

PIN

DUCT

STIFFEN BLADE

AS REQUIRED

SIDE ELEVATION SECTION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

M-501

MECHANICAL DETAILS

ANCH

SCALE: N.T.S.C1

FLEXIBLE AIR DUCT CONNECTOR

SCALE: N.T.S.D4

AHU DRAIN TRAP

SCALE: N.T.S.C8

EXHAUST OR RETURN BRANCHWORK

SCALE: N.T.S.F1

ROUND DUCT HANGER

SCALE: N.T.S.F5

VOLUME DAMPER DETAIL

NOTE:

UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.

M

AX.

M A

X

E Q

U

IP

M E

N T

AIR

FLOW

AIR

FLOW

TYPICAL DUCTWORK TRANSITION

PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH

EQUIPMENT MOUNTED IN DUCT

PLAN OR SIDE VIEW

M

AX.

M A

X

M A

X

M A

X

15°

NOTES:

1.

2.

3.

4.

5.

6.

A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION IS SIMILAR. FOLLOW

DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR

SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION OR

FLOOR AND NOT OUTSIDE THE PENETRATION.

GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER

FRAME AND TO PERIMETER ANGLES.

PERIMETER ANGLES: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2", 14 GAGE, TO PROVIDE 1"

MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.

BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.

ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.

PROVIDE 1/4" TO 1/2" CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH ROCK WOOL

FIRESTOP FIBER.

ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND

MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" HIGH CONCRETE CURB AROUND

OPENING FOR DUCT.

SLEEVE, NOTE 2

DUCT

CONNECTION

NOTE 4

DAMPER,

NOTE 1

DAMPER COLLAR

EXTENSION INTEGRAL

PART OF SLEEVE

SLEEVE, NOTE 2

NOTE 6FIRE BARRIER

PARTITION OR CHASE

TYPICAL DUCT

INSULATION

PERIMETER ANGLE, NOTE 3 (NOTE

FASTENED TO PARTITION)

ACCESS

PANEL

NOTE 5

INSULATION SHIELD

AT HANGER

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9

PSF MIN. DENSITY) UNDER

INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

6"

MINIMUM 6" TO EDGE OF EQUIPMENT FRAME

THREADED BOLT

AND WASHER

THRU. PIPE

SLEEVE

CONCRETE TOPPING

NO. 4 DOWELS AT 12"

W.W.F 6" X 7" TWO-WAY

REINFORCING

BOLT CENTERLINE

12"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

M-502

MECHANICAL DETAILS

ANCH

SCALE: N.T.S.C1

DUCTWORK TRANSITIONS

SCALE: N.T.S.E6

SECTION THRU FIRE DAMPER INSTALLATION

SCALE: N.T.S.E1

PIPE HANGER DETAIL

SCALE: N.T.S.F1

HOUSEKEEPING PAD

STRUCTURAL JOIST

1/2" THREADED

ROD (TYP).

1-1/4 X 1-1/4 X 3/16

ANGLE IRON SUPPORTS.

1/2" BOLT AND NUT

W/ 2" 1/2 WASHER.

NUTS AND WASHERS BOTH

SIDES OF ANGLE (TYP).

MOUNTING BRACKET

FLEX. CONNECTION (TYP)

AIR FLOW

DUCTWORK

MOUNTING BRACKET

FAN BOLTS

STEEL SPRING ANC RUBBER IN

SHEAR TYPE VIBRATION ISOLATORS

CONNECT DUCTWORK TO FAN

WITH 1/8" THICK NEOPRENE

GASKET

SWAY BRACE,

3/8" THREADED STEEL RODS

SUPPORT FROM BLDG

STRUCTURE LENGTHS OF RODS

TO SUIT SPACE AVAILABLE

BOTH DIRECTIONS @ 90°

TYP. FOR SIX

EXPANSION BOLTS

WASHERS

FRAME WITH LOCK

RECOMMENDATIONS

A MINIMUM OF TWO BRACKETS.

SECURED TO WALL WITH

UNIT HEATER SHALL BE

SEISMIC BRACE

UNIT HEATER

EACH SIDE OF

BRACKETS PER MANUFACTURERS

TWO 5/8" BOLTS,

5/8"

NOTE:

1. APPLICABLE TO PENETRATIONS OF ALL

FIRE RATED MEMBRANES, IN

ACCORDANCE WITH NFPA 101. REFER

TO SPECIFICATIONS SECTION 07 84 00,

FIRE STOPPING SYSTEMS.

INSULATED PIPE

OR DUCT

FLOOR

FIRESTOP MATERIAL

3/4" APPROVED

FIRESTOP INSULATION

WITH VAPOR BARRIER

PIPE SLEEVE WHERE

SPECIFIED

1/4" DIA ANCHOR ROD

FOR NEW

CONSTRUCTION

WELD

FLOOR OR DECK PENETRATION

PARTITION OR CHASE PENETRATION

MASONRY

PARTITION

PARTITION SUPPORT

FIRESTOP

MATERIAL

3/4" APPROVED FIRESTOP

INSULATION WITH VAPOR

BARRIER

DRYWALL PARTITION

INSULATED

PIPE OR

DUCT

6" 6"

6" 6"

ELECTRICAL HEATER

SUPPLY OPENING

RETURN OPENING

1" DRAIN CONNECTION REFRIGERANT

CONNECTIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

M-503

MECHANICAL DETAILS

ANCH

SCALE: N.T.S.C1

DUCT HANGER DETAIL - RECTANGULAR

SCALE: N.T.S.C4

EXHAUST FAN DETAIL

SCALE: 12" = 1'-0"C8

ELECTRIC UNIT HEATER DETAIL

SCALE: 1" = 1'-0"F1

PIPE/DUCT PENETRATION OF SMOKE/FIRE BARRIERS

SCALE: N.T.S.F7

AHU DETAIL

1. REFER TO SPECIFICATIONS FOR FILTER TYPES. PROJECT ELEVATION 1100FT ABOVE SEA LEVEL.

2. TOTAL UNIT STATIC PRESSURE INCLUDES ESP, DIRTY COILS & DIRTY FILTERS.

3. AHU ON MOUNTING RAILS WITH DRIP PAN AND FLOAT SWITCH.

4. PROVIDE CONDENSATE DRAIN TRAP.

AHU-2 LEVEL 2 LEVEL 2 CENTRIFUGAL 2,250 450 0.7 833 0.97 18 55.0 77 290 80.0 67.0 56 56 74.89 TRANE TWE 07243BAA 1,2,3,4,5

NOTES:

AHU-1 BASEMENT LEVEL 1 CENTRIFUGAL 2,520 600 0.7 853 1.16 18 55.0 77 324 80.0 67.0 58 57.2 75.70 TRANE TWE 07243BAA 1,2,4,5,6

ESP (in.wg)

DB

(°F)

WB

(°F)

DB

(°F)

WB

(°F)

AIR HANDLING UNIT SCHEDULE

TAG LOCATION SERVICE

SUPPLY FAN HEATING COIL(ELECTRIC) COOLING COIL

BASIS OF

DESIGN

NOTES

FAN MOTOR AIRSIDE AIRSIDE

TYPE

OPER.

DESIGN

AIRFLOW

(CFM)

OA

AIRFLOW

(CFM)

STATIC

PRESS.

RPM HP

HEATING

(kW)

EAT DB

(°F)

LAT DB

(°F)

MAX.

FACE

VEL.

(FPM)

EAT LAT TOTAL

CAP.

(MBTUH)

SEN CAP.

(MBTUH)

LAT CAP.

(MBTUH)

18.53

16.27

59.43

63.11

5. ELECTRICAL TO PROVIDE STARTER/DISCONNECT.

WEIGHT

(LBS)

ELECTRICAL DATA

AHU ELECTRIC HEATER

V/PH/HZ V/PH/HZMCA MCA

208/3/60 208/3/6077 87

208/3/60 208/3/6077 87

6. AHU ON 4" HOUSEKEEPING PAD.

EUH-1 ATTIC SPACE HEATING 1/3 208 1 7.5 TASK MASTER 5100 25 1,2

NOTES:

HP VOLTS PHASE

1. HORIZONTAL UNIT HEATER.

2. PROVIDE UNIT WITH DISCONNECT, PACKAGED CONTROL AND THERMOSTAT.

ELECTRIC UNIT HEATER SCHEDULE

TAG LOCATION SERVICE

ELECTRICAL DATA MIN.

HEATING

CAP.(KW)

BASIS OF

DESIGN WEIGHT (lbs) NOTES

EUH-2 ATTIC SPACE HEATING 1/3 208 1 5 TASK MASTER 5100 25 1,2

EF-1 ATTIC LOCKERS, TOILETS 900 850 0.5 1,176 523 HORIZONTAL INLINE 0.14 1/2 6.2 115/60/1 GREENHECK-SQ-120-VG 1,2,3,4

2. REFER TO LOUVERED PENTHOUSE SCHEDULE FOR EXHAUST PENTHOUSE SIZE.

3. MANUFACTURER TO PROVIDE MOTOR WITH VARIABLE SPEED DUTY.

NOTES:

1. MANUFACTURER TO PROVIDE STARTER/DISCONNECT.

EXHAUST FAN SCHEDULE

TAG LOCATION SERVICE

FAN MOTOR

BASIS OF DESIGN NOTES

MAX. DESIGN

AIRFLOW

(CFM)

OPER. DESIGN

AIRFLOW

(CFM)

EX S.P.

(in wg)

RPM

MAX. OUTLET

VELOCITY

(FPM)

FAN

DISCHARGE

ORIENTATION

OPER.

BHP

HP FLA V/C/P

EF-2 ATTIC BASEMENT 240 200 0.5 1,635 240 HORIZONTAL INLINE 0.06 1/10 1.38 115/60/1 GREENHECK-SQ-80-VG 1,2,3,4

4.PROVIDE WITH INTEGRAL BACK DRAFT DAMPER.

4. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL ELEVATIONS.

5. PROVIDE GALVANIZED PLENUM WITH TRANSITION TO DUCT CONNECTION SIZE AS INDICATED ON THE PLAN.

SD-1 SUPPLY CEILING 24X24 AL RADIAL HORIZONTAL SQUARE PLAQUE DIFFUSER TITUS OMNI 1,2,3,4

SD-2 SUPPLY CEILING SEE DWGS AL LINEAR SLOT DIFFUSER, TWO(2) 1" SLOTS TITUS TBDI-10 1,2,3,4

SD-3 SUPPLY CEILING 12X12 AL RADIAL HORIZONTAL SQUARE PLAQUE DIFFUSER TITUS OMNI 1,2,3,4

EG-1 EXHAUST CEILING 24X24 AL 1/2"X1/2"X1/2" GRID EGGCRATE FACE EXAHUST GRILLE TITUS 50F 1,2,3,4,5

EG-2 EXHAUST SIDEWALL SEE DWGS AL SIDEWALL EXHAUST GRILLE TITUS 350RL 1,3,5

EG-3 EXHAUST CEILING 12X12 AL 1/2"X1/2"X1/2" GRID EGGCRATE FACE EXHAUST GRILLE TITUS 50F 1,2,3,4,5

1. REFER TO DRAWINGS FOR NECK SIZES.

2. REFER TO ARCHITECTURAL RCP DRAWINGS FOR COORDINATION WITH CEILING.

3. COORDINATE FINISH WITH ARCHITECT.

RG-1 RETURN CEILING 24X24 AL 1/2"X1/2"X1/2" GRID EGGCRATE FACE RETURN REGISTER TITUS 50F 1,2,3,4

RG-2 RETURN CEILING SEE DWGS AL SLOT RETURN, 1/2" SPACING WIDTH TITUS CT-580 1,2,3,4

NOTES:

GRILLE AND DIFFUSER SCHEDULE

TAG SERVICE MOUNTING MODULE SIZE (in. x in.) MATERIAL DESCRIPTION BASIS OF DESIGN NOTES

TG-1 TRANSFER SIDEWALL SEE DWGS AL SIDEWALL TRANSFER GRILLE TITUS 350RL 1,3,4

SD-4 SUPPLY WALL SEE DWGS AL WALL MOUNTED SUPPLY GRILLE TITUS 300FL 1,2,3,4

SD-5 SUPPLY DUCT SEE DWGS AL DUCT MOUNTED SUPPLY GRILLE, 3/4" SPACING TITUS S300FL 1,2,3,4

LV-1 38 26 24 12 2 1050 GREENHECK WRH-12X24

LOUVERED PENTHOUSE SCHEDULE

TAG

LENGTH

(IN)

WIDTH

(IN)

THROAT

LENGTH

(IN)

THROAT

WIDTH (IN)

THROAT

AREA (FT^2)

AIR

VOLUME

(CFM)

BASIS OF DESIGN APPLICATION

LV-2 28 28 14 14 1 450 GREENHECK ESD-635PD-14X14

WEIGHT

(LBS)

29 EXHAUST

INTAKE

AC-1 OIT ROOM 205 DUCTLESS SPLIT 887 0 0 9,800 30,700 16 80 67 95 N/A 1.00 0.76 21.00 0.93 208 60 1 MITSUBISHI MSY-D30NA, MUY-D30NA

SPLIT SYSTEM AIR CONDITIONER SCHEDULE

DB

(F)

WB

(F) MCA FLA MCA FLA

MIN

CAPACITY

(BTU/H)

RATED

CAPACITY

(BTU/H)

SEER

EAT OSA

DESIGN

TEMP (F)

INDOOR UNIT OUTDOOR UNIT

VOLT HZ PHASE

TAG SERVICE TYPE

TOTAL

SUPPLY

AIRFLOW

(CFM)

MIN.

OUTSIDE

AIR FLOW

(CFM)

EXT

STATIC

PRESSUR

E (IN)

COOLING CAPACITY

HEATING

CAPACITY

ELECTRICAL DATA

BASIS OF

DESIGN

NOTES

1. MANUFACTURER TO PROVIDE MHK1 BACKLIT WIRELESS WALL-MOUNTED THERMOSTAT.

NOTES:

DH-1 ARMORY ARMORY 155 29.5 R134A 190G 3/4" 120/1/60 2.8 39.0 IW25-4 1

VOLTS/PH/HZ FLA

1. WALL MOUNTED DEHUMIDIFIER AT 5' AFF.

NOTES

DEHUMIDIFIER SCHEDULE

TAG LOCATION SERVICE AIRFLOW

(CFM)

CONDENSATE

CAPACITY (PPD) REFRIGERANT

DRAIN

CONNECTION

(IN)

ELECTRICAL

DATA

WEIGHT

LBS

BASIS OF

DESIGN

NOTES

VOLTS/

PH/HZ

MCA STAGES

CU-1 EXTERIOR AHU-1 208/3/60 35 2.0

CU-2 EXTERIOR AHU-2 208/3/60 35 2.0

NOTES:

NEW CONDENSER UNIT SCHEDULE

TAG LOCATION SERVICE

TOTAL

COOLING

CAPACITY

(TON)

COMPRESSORS

ELECTRICAL DATA

BASIS OF DESIGN NOTES

6 2 6 2

REFRIGERANT

R-410A

R-410A TWA07243DAA

TWA07243DAA

1. ELECTRICAL TO PROVIDE STARTER/DISCONNECT.

HEATING CAPACITY

OUTDOOR

TEMP (F)

INDOOR DB

(F)

MBH

12 60 33.6 12 60 33.6

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

M-601

MECHANICAL SCHEDULES AND

SEQUENCE OF OPERATION

ANCH

AIR HANDLERS AHU/CU-1 & AHU/CU-2

1. THE UNITS SHALL OPERATE AS SCHEDULED BY THE BUILDING MANAGEMENT SYSTEM (BMS)

a. DURING OCCUPIED THE SYSTEMS SHALL OPERATE WITH LOCAL CONTROLS AS NOTED HERE IN AFTER.

b. DURING UNOCCUPIED HOURS, A SPACE TEMPERATURE SENSOR SHALL SIGNAL TO THE BMS TO OPERATE THE SYSTEMS AS NEEDED TO

MAINTAIN 60 DEGREES F (ADJ.) IN THE WINTER AND 80 DEGREES F (ADJ.) IN THE SUMMER.

2. A SPACE THERMOSTAT SHALL CYCLE THE UNIT IN HEATING OR COOLING AS NEEDED TO MAINTAIN SET POINT TEMPERATURE. THE SENSOR

FOR THE THERMOSTAT SHALL BE IN THE ASSOCIATED AIR HANDLER RETURN DUCTWORK AS NOTED ON THE DRAWINGS.

a. THE THERMOSTAT SHALL OPERATE THE EMERGENCY STRIP HEAT AS NEEDED TO MAINTAIN SPACE SET POINT TEMPERATURE UPON

FAILURE OF THE COMPRESSOR TO MAINTAIN SET POINT TEMPERATURE OR DEHUMIDIFICATION OPERATION.

3. MOTORIZED DAMPERS IN THE OUTSIDE AIR DUCTWORK SHALL OPEN DURING OCCUPIED HOURS AND REMAIN CLOSED DURING SET UP OR SET

BACK TEMPERATURE OPERATION AND UNOCCUPIED CONDITIONS.

4. A SMOKE DETECTOR IN THE RETURN AIR DUCTWORK SHALL STOP THE UNIT, CLOSE THE OUTSIDE AIR DAMPER, AND ALARM THE BUILDING

FIRE ALARM AND BMS SYSTEMS UPON ACTIVATION.

5. A SPACE HUMIDISTAT SHALL ENERGIZE THE COOLING FUNCTION FOR UNITS AS NEEDED TO MAINTAIN SPACE HUMIDITY LEVELS AT 60% RH

(ADJ.). THE EMERGENCY STRIP HEAT SHALL CYCLE BY THE ROOM THERMOSTAT AS NEEDED TO MAINTAIN SPACE TEMPERATURE.

6. AHU-2 WILL BE INSTALLED IN AN AUXILIARY DRAIN PAN WITH A FLOAT SWITCH TO DEENERGIZE THE UNIT UPON ACTIVATION.

EXHAUST FANS EF-1 & EF-2

1. THE EXHAUST FAN EF-1 SHALL OPERATE WHEN AHU-1 &/OR AHU-2 ARE OPERATING AND THE AHU’S OUTSIDE AIR DAMPERS ARE OPEN. THE

FAN SHALL BE DEENERGIZED DURING UNOCCUPIED CONDITIONS.

2. THE EXHAUST FAN EF-2 SHALL OPERATE WHEN AHU-1 IS OPERATING, AND THE OUTSIDE AIR DAMPER IS OPEN. THE FAN SHALL BE

DEENERGIZED DURING UNOCCUPIED CONDITIONS.

UNIT HEATERS EUH-1 & EUH-2

1. THE UNITS SHALL CYCLE AS NEEDED, BY A SPACE THERMOSTAT, TO MAINTAIN SET POINT OF 45 DEGREES F (ADJ.) IN THE ATTIC.

DUCTLESS SPLIT SYSTEM AC-1

1. THE UNIT SHALL CYCLE AS NEEDED TO MAINTAIN ROOM THERMOSTAT SET POINT OF 72 DEGREES F (ADJ.). THE UNIT SHALL OPERATE

CONTINUOUSLY. A SPACE TEMPERATURE SENSOR IN THE ROOM SHALL ALARM THE BMS UPON SPACE TEMPERATURES ABOVE 75 DEGREES F

(ADJ.).

DEHUMIDIFER DH-1

1. THE UNIT SHALL OPERATE AS NEEDED WITH UNIT CONTROLS TO MAINTAIN ROOM AT 50% RH (ADJ.). A HUMIDITY SENSOR SHALL ALARM THE

BMS UPON SPACE HUMIDITY ABOVE 65% RH (ADJ.).

SEQUENCE OF OPERATION

Sheets
M-001 - MECHANICAL GENERAL NOTES
M-002 - MECHANICAL ABBREVIATIONS AND LEGENDS
MD100 - BASEMENT MECHANICAL DEMOLITION PLAN
MD101 - FIRST FLOOR MECHANICAL DEMOLITION PLAN
MD102 - SECOND FLOOR MECHANICAL DEMOLITION PLAN
MD103 - ATTIC MECHANICAL DEMOLITION PLAN
MD104 - ROOF MECHANICAL DEMOLITION PLAN
M-100 - BASEMENT MECHANICAL NEW WORK PLAN
M-101 - FIRST FLOOR MECHANICAL NEW WORK PLAN
M-102 - SECOND FLOOR MECHANICAL NEW WORK PLAN
M-103 - ATTIC MECHANICAL NEW WORK PLAN
M-104 - ROOF MECHANICAL NEW WORK PLAN
M-501 - MECHANICAL DETAILS
M-502 - MECHANICAL DETAILS
M-503 - MECHANICAL DETAILS
M-601 - MECHANICAL SCHEDULES AND SEQUENCE OF OPERATION