This presolicitation notice is for a construction project to correct environment and condition deficiencies at the Administration Building 20 at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The project involves modifications and demolition work to reconstruct space for police staff offices, conference rooms, evidence processing areas, locker rooms, mechanical and electrical rooms, and finish replacements. The work is estimated to cost between $1 million and $5 million. The NAICS code is 236220 and the small business size standard is $39.5 million. The solicitation will be posted on October 20, 2021 and close on November 20, 2021, following FAR Part 14.101 sealed bidding procedures. This is a 100% SDVOSB set-aside requiring active SAM and CVE registrations. Questions must be submitted in writing to the contract specialist by the specified date and include the project number, name, and solicitation number.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NAMING CONVENTION
M-001A
2 DIGIT SEQUENTIAL # (01-99)
(FIRST DIGIT INDICATES PLAN
TYPE. SECOND DIGIT INDICATES
FLOOR)
1 DIGIT SHEET TYPE DESIGNATOR
0 - GENERAL
1 - PLANS
2 - ELEVATIONS
3 - SECTIONS
4 - ENLARGED PLANS
5 - DETAILS
6 - SCHEDULES AND DIAGRAMS
7 - VARIES
8 - VARIES
9 - 3D VIEWS (ISO, PERSPECTIVES)
2 DIGIT DISCIPLINE
DESIGNATOR
(IF ONLY ONE LETTER IS
USED, THE SECOND
LETTER IS REPLACED
WITH A DASH "-" AS A
PLACEHOLDER)**
1 DIGIT AREA
DESIGNATOR
(AREA DESIGNATOR
ONLY USED WHEN
PLANS ARE SUBDIVIDED
INTO AREAS.)
1. EXISTING EQUIPMENT IS SHOWN WITH THIN LINEWORK.
2. DEMOLISHED EQUIPMENT IS SHOWN WITH BOLD LINEWORK,
DASHED, AND HATCHED.
3. NEW OR RELOCATED EQUIPMENT IS SHOWN WITH BOLD
LINEWORK.
4. BELOW IS AN EXAMPLE OF EACH:
EXISTING EQUIPMENT
EQUIPMENT TO BE DEMOLISHED
NEW OR RELOCATED EQUIPMENT
NOTES:
GENERAL MECHANICAL NOTES
1. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY INSTALLATION IS MADE. DUCTWORK SHOWN ON PLANS IS SCHEMATIC. DUCTWORK SHALL BE INSTALLED TIGHT TO STRUCTURE. ALL TRANSITIONS, ELBOWS, ETC.
REQUIRED TO AVOID CONFLICTS & MAXIMIZE CEILING HEIGHTS. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER
TRADES SHALL BE RELOCATED AS REQUIRED AT NO ADDITIONAL COST TO THE OWNER.
2. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT IS NOT LOCATED
OVER OR ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.
3. WRITTEN DIMENSIONS ON DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.
4. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE, UNIFIED FACILITIES
CRITERIA, AND INTERNATIONAL BUILDING CODE / INTERNATIONAL MECHANICAL CODE.
5. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT NECESSITATING
REMOVAL OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.
6. CEILING-MOUNTED EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC., DO NOT
BLOCK ACCESS TO EQUIPMENT AND RELATED ACCESSORIES.
7. COORDINATE WALL, FLOOR AND ROOF PENETRATIONS WITH THE GENERAL CONTRACTOR.
8. CAULK WITH SILICONE ALL GAPS BETWEEN WALL, CEILING AND FLOOR OPENINGS AND HVAC EQUIPMENT PENETRATIONS.
PATCH LARGE GAPS BEFORE CAULKING IS APPLIED.
9. DUCTWORK AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS AND THE PRESSURE
CLASSIFICATION OF EACH INDIVIDUAL DUCTWORK SYSTEM.
10. SQUARE ELBOWS SHALL ONLY BE USED WHERE SPACE LIMITATIONS PREVENT USE OF 1.5 RADIUS ELBOW AND ONLY UPON APPROVAL OF CONTRACTING OFFICER. PROVIDE TURNING VANES IN ALL 45° AND 90° SQUARE ELBOWS. TURNING VANES SHALL BE SINGLE THICKNESS TYPE WITHOUT RAILING EDGE. TURNING VANES LONGER THAN 36 INCHES SHALL BE DOUBLE THICKNESS
TYPE.
11. DUCTWORK RUNOUTS TO AIR DISTRIBUTION DEVICES SHALL BE SAME DIAMETER AS AIR DISTRIBUTION DEVICE INLET
CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.
12. FLEXIBLE DUCTWORK RUNOUTS FROM BRANCH DUCTS TO AIR DISTRIBUTION DEVICES SHALL NOT EXCEED 5 FEET IN LENGTH.
BENDS IN FLEXIBLE DUCTWORK SHALL NOT EXCEED A MAXIMUM OF 45 DEGREE CHANGE OF DIRECTION AND BE SUPPORTED SUCH THAT THE BEND RADIUS IS NOT RESTRICTIVE TO AIR FLOW THROUGH THE DUCT. FLEXIBLE DUCTWORK SHALL NOT BE
CRUSHED OR DISTORTED IN ITS FINAL CONFIGURATION.
13. ROUND DUCTWORK CONNECTIONS BETWEEN MAIN DUCT AND TERMINAL UNITS SHALL BE RIGID DUCT OF THE SAME DIAMETER
AS TERMINAL UNIT INLET CONNECTION UNLESS OTHERWISE NOTED ON THE DRAWINGS.
14. PROVIDE SHEET METAL TRANSITIONS AT AIR HANDLING UNITS, HEAT PUMP UNITS, FANS, AND OTHER SIMILAR HVAC EQUIPMENT.
TRANSITION TO FULL SIZE OF CONNECTION ON UNIT. FLEXIBLE DUCT CONNECTORS SHALL BE USED ON FINAL CONNECTION TO
AIR HANDLING EQUIPMENT.
15. EXACT LOCATION OF CEILING DIFFUSERS, GRILLES AND REGISTERS SHALL BE DETERMINED BY ARCHITECTURAL REFLECTED
CEILING PLAN.
16. BLANK OFF AND INSULATE INACTIVE PORTIONS OF LOUVERS. ENTIRE LOUVERS NOT UTILIZED SHALL BE BLANKED OFF AND INSULATED BY THE LOUVER MANUFACTURER. REFER TO ARCHITECTURAL DRAWINGS FOR LOUVER LOCATIONS AND HVAC
DRAWINGS FOR HVAC EQUIPMENT CONNECTIONS.
17. LOUVER PLENUMS SHALL BE PITCHED DOWN TOWARD THE BOTTOM OF THE LOUVER. WHERE THIS IS NOT POSSIBLE, PROVIDE 3/4" DRAIN PIPING WITH P-TRAP FROM BOTTOM OF LOUVER TO NO MORE THAN 6" ABOVE NEAREST SANITARY DRAIN. DRAIN LINE SHALL SLOPE DOWN TOWARDS DISCHARGE LOCATION AT A MINIMUM OF 1/8" PER LINEAR FOOT.
18. PROVIDE ACCESS PANELS TO ACCESS DAMPERS, EQUIPMENT, AND VALVES LOCATED ABOVE HARD CEILINGS OR IN WALLS.
ACTUAL LOCATIONS SHALL BE FIELD DETERMINED.
19. EXACT LOCATIONS OF THERMOSTATS, CO2 SENSORS, AND EMCS SENSORS SHALL BE COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND ELECTRICAL EQUIPMENT. MOUNT THERMOSTATS AND CO2 SENSORS MINIMUM 48" AFF.
20. AIR HANDLING UNITS SERVING OCCUPIED AREAS SHALL HAVE MINIMUM MERV 13 FILTERS. UNITS NOT SERVING OCCUPIED ZONES SHALL HAVE MINIMUM MERV 8 FILTER. FILTERS SHALL BE INDUSTRY STANDARD SIZE. FILTERS SHALL NOT CREATE PRESSURE DROP EXCEEDING 10% OF EXTERNAL STATIC PRESSURE (ESP) CAPACITY LISTED IN EQUIPMENT SCHEDULE.
21. SUPPLY, RETURN, AND OUTDOOR AIR DUCTWORK SHALL BE INSULATED TO MEET OR EXCEED ASHRAE 90.1. EXTERIOR SUPPLY
AND RETURN AIR DUCTWORK SHALL BE PROVIDED WITH WEATHER-PROOF COVER.
22. COORDINATE LOCATIONS OF CONDENSATE DRAIN PIPING. PROVIDE CONDENSATE PUMPS AS REQUIRED WHERE SUFFICIENT SLOPE IS NOT AVAILABLE FOR STANDARD GRAVITY DRAIN, WITH OVERRIDE SWITCH TO POWER DOWN THE ASSOCIATED AIR HANDLING EQUIPMENT IN CASE OF CONDENSATE PUMP FAILURE. CONDENSATE DRAIN LINE SHALL SLOPE DOWN TOWARDS DISCHARGE LOCATION AT A MINIMUM OF 1/8" PER LINEAR FOOT. INSULATE INDOOR CONDENSATE PIPING WITH 3/4" CLOSED CELL
FOAM INSULATION.
23. PROVIDE SUPPORTS FOR PIPING AND DUCTWORK IN ACCORDANCE WITH SPECIFICATIONS.
24. PROVIDE HOUSEKEEPING PADS FOR MECHANICAL EQUIPMENT.
25. FOR WALL, FLOOR, AND SLAB PENETRATIONS SEAL AND PATCH ALL UNUSED PENETRATION SPACE TO MATCH EXISTING OR AS
SHOWN ON MECHANICAL DETAILS SHEET.
26. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN FOR INFORMATION ONLY. REFER TO SPECIFICATIONs FOR COMPLETE REQUIREMENTS.
27. PIPING INSULATION SHALL BE PROVIDED ON ALL PIPING SYSTEMS INCLUDING (BUT NOT LIMITED TO) CONDENSER WATER, REFRIGERANT, AND CONDENSATE DRAIN IN ACCORDANCE WITH ASHRAE 90.1.
28. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE
OVER SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.
29. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED PUBLISHED LITERATURE.
30. DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
31. EXPOSED DUCTWORK, WITH THE EXCEPTION OF DUCTWORK IN MECHANICAL ROOMS SHALL BE DOUBLE-WALL, SPIRAL
DUCTWORK WITH COATING.
32. IF ASBESTOS IS FOUND, STOP WORK IMMEDIATELY AND NOTIFY OWNER AND GENERAL CONTRACTOR. OWNER IS RESPONSIBLE
FOR ABATEMENT OF ASBESTOS.
33. NOT ALL MECHANICAL ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.
34. THE OUTDOOR DESIGN CONDITIONS AT JOHNSON CITY, TN ARE AS FOLLOWS PER VA HVAC DESIGN MANUAL, CHAPTER 7.1:
SUMMER: 90.5°F DRY BULB (0.4% OCCURRENCE)
71.8°F WET BULB (0.4% OCCURRENCE)
WINTER: 12.9°F DRY BULB (99.6% OCCURRENCE)
35. INDOOR DESIGN CONDITIONS WILL BE IN ACCORDANCE WITH CHAPTER 6 ROOM DATA SHEETS FROM VA HVAC DESIGN MANUAL.
OFFICE SPACES: 75°F (COOLING)
70°F (HEATING)
60%-20% RH
MAX NC LEVEL 40
CONFERENCE ROOM:75°F (COOLING)
70°F (HEATING)
60%-20% RH
MAX NC LEVEL 35
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
M-001
MECHANICAL GENERAL NOTES
ANCH
REVISIONS DATE
GENERAL MECHANICAL ABBREVIATIONS
@ AT
& AND
AFF ABOVE FINISHED FLOOR
A/C ABOVE CEILING
AC AIR CONDITIONER
AD AUTOMATIC DAMPER
ADJ ADJUSTABLE
AFMS AIRFLOW MEASURING STATION
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
AHU AIR HANDLING UNIT
AMB AMBIENT
AMCA AIR MOVEMENT AND CONTROL ASSOCIATION
ARCH ARCHITECT, ARCHITECTURAL
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING,
REFRIGERATING, AND AIR CONDITIONING
ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
AUX AUXILIARY
AWS AMERICAN WELDING SOCIETY
AWG AMERICAN WIRE GAUGE
B BOILER
BD BACKDRAFT DAMPER
BLDG BUILDING
BOD BOTTOM OF DUCT
B/F BELOW FLOOR
B/S BELOW SLAB
BT BUFFER TANK
BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR
CA COMBUSTION AIR INTAKE
CAV CONSTANT AIR VOLUME
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CLG COOLING
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
CO2 CARBON DIOXIDE
CONC CONCRETE
CONN CONNECT, CONNECTING, CONNECTION
CONT CONTINUED
COP COEFFICIENT OF PERFORMANCE
COR CONTRACTING OFFICER'S REPRESENTATIVE
CT COOLING TOWER
CU CONDENSING UNIT
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DEPTH
DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS
DDC DIRECT DIGITAL CONTROLS
DEG. F (°F) DEGREES FAHRENHEIT
DF DESTRATIFICATION FAN
DH DEHUMIDIFIER
DIA DIAMETER
DIV DIVISION
DN DOWN
DP, PD DIFFERENTIAL PRESSURE, PRESSURE DROP
DSCU DUCTLESS SPLIT CONDENSING UNIT
DSHP DUCTLESS SPLIT HEAT PUMP
DSS DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
DWG DRAWING
DX DIRECT EXPANSION
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
ELEC ELECTRICAL
ERU ENERGY RECOVERY UNIT
ERV ENERGY RECOVERY VENTILATOR
ET EXPANSION TANK
ESP EXTERNAL STATIC PRESSURE
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
EXT EXTERIOR
EXH EXHAUST
EXST, (E) EXISTING
FCU FAN COIL UNIT
FD FIRE DAMPER
FFE FINISHED FLOOR ELEVATION
FLA FULL LOAD AMPS
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FPM FEET PER MINUTE
FSD FIRE SMOKE DAMPER
FT FOOT, FEET
FT WG FEET WATER GAUGE
FV FLUE VENT
GA GAGE
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
H HEIGHT
HGRH HOT GAS REHEAT
HP HEAT PUMP
HR HOUR
HSPF HEATING SEASONAL PERFORMANCE FACTOR
HTG HEATING
HTR HEATER
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
HX HEAT EXCHANGER
HZ HERTZ
IMC INTERNATIONAL MECHANICAL CODE
IN INCH, INCHES
IN WC INCHES WATER COLUMN
IN WG INCHES WATER GAUGE
IPLV INTEGRATED PART LOAD VALUE
KW KILOWATTS
L LENGTH, LOUVER (WALL)
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LBF/IN2 POUNDS FORCE PER SQUARE INCH
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH 1000 BRITISH THERMAL UNITS
MCA MINIMUM CIRCUIT AMPACITY
MERV MINIMUM EFFICIENCY REPORTING VALUE
MECH MECHANICAL
MFR, MFG MANUFACTURER, MANUFACTURING
MIN MINIMUM
MOCP MAXIMUM OVER CURRENT PROTECTION
MOD MOTOR OPERATED DAMPER
MSS MANUFACTURER'S STANDARDIZATION SOCIETY
MTD MOUNTED
MUW MAKE-UP WATER (POTABLE/ DOMESTIC)
MVD MANUAL VOLUME DAMPER
NC NOISE CRITERIA
N.C. NORMALLY CLOSED
NO. NUMBER
N.O. NORMALLY OPEN
NPLV NET PART LOAD VALUE
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DAMPER
PD PRESSURE DROP
PH PHASE
PLBG PLUMBING
PPM PARTS PER MILLION
PRV PRESSURE RELIEF VALVE
QTY QUANTITY
RA RETURN AIR
RG RETURN GRILLE
RH RELATIVE HUMIDITY, ROOF HOOD
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RM ROOM
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
SA SUPPLY AIR
SD SMOKE DAMPER, SMOKE DETECTOR
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SUPPLY FAN
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTOR'S NATIONAL ASSOCIATION
SP STATIC PRESSURE
SS STAINLESS STEEL
TSTAT THERMOSTAT
TEMP TEMPERATURE
TG TRANSFER GRILLE
THA TOTAL HEAT ABSORPTION
THR TOTAL HEAT REJECTION
TP TEMPERATURE/ PRESSURE TEST PORT
TYP TYPICAL
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UMCS UTILITY MONITORING AND CONTROL SYSTEM
V VOLTAGE, VOLTS
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VELO VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VSD VARIABLE SPEED DRIVE
W WATT(S)
W/ WITH
W/O WITHOUT
WB, Twb WET BULB (TEMPERATURE)
WD WIDE, WIDTH
WMS WIRE MESH SCREEN
AIR DISTRIBUTION DEVICE TAGS
DIFFUSER TYPE
A
400 AIRFLOW (CFM), "PLENUM", OR "TRANSFER"
A1
M-501
DRAWING REFERENCE KEY
REFER TO
DETAIL NUMBER
SHEET NUMBER OF DETAIL
RE:A1/M-501
NORTH ARROW
A
J
SD
SP
F
CO
DUCT SMOKE DETECTOR
CARBON MONOXIDE SENSOR
OVAL OR FLAT OVAL
CONTROL WIRING
STATIC PRESSURE SENSOR
ROUND
FIRESTAT
TEMPERATURE SENSOR
MISCELLANEOUS LEGEND
T
120 VOLT STAND BY POWER JUNCTION
BOX PROVIDED BY THE ELECTRICAL
CONTRACTOR JUNCTION BOX IS
DEDICATED FOR USE BY THE CONTROLS
CONTRACTOR.
VARIABLE FREQUENCY DRIVEVFD
M
FIRE DAMPER
H
DUCT MOUNTED HUMIDIFIER
EXHAUST AIR DUCT DOWN
EXHAUST AIR DUCT UP
RETURN AIR DUCT DOWN
30"x14"
SQUARE TO ROUND DUCT BRANCH TAKE-OFF
WITH 45 DEGREE BRANCH INLET
FLARED SPIN-IN WITH DAMPER AND
FLEX DUCT (DIFFUSER CONNECTION)
ROUND DUCT BRANCH TAKE-OFF FROM
RECTANGULAR MAIN WITH CONICAL TAP
FLEXIBLE DUCT CONNECTION
FLOW ARROW
DUCT SIZE TRANSITION
RECTANGULAR DUCT BRANCH TAKE-OFF
WITH 45 DEGREE BRANCH INLET
90 DEGREE DUCT ELBOW WITH TURNING VANES
24"Ø
DUCTWORK LEGEND
RETURN AIR DEVICE
ROUND DUCT. DIAMETER INDICATED IN INCHES.
IN-LINE 90 DEGREE RISE/DROP IN
SUPPLY DUCT (RIGHT SIDE IS HIGHER)
IN-LINE 90 DEGREE RISE/DROP IN
SUPPLY DUCT (LEFT SIDE IS HIGHER)
FD
SD
P - PNEUMATIC-ACTUACTED DAMPER
DAMPER TYPE:
M - MOTORIZED DAMPER (ELECTRIC)
VD
SMOKE DAMPER
VOLUME/BALANCING DAMPER
(LABEL MAY BE OMITTED)
BD
BACKDRAFT DAMPER
(COUNTER-BALANCED UNLESS
OTHERWISE NOTED)
RADIUS DUCT ELBOW - ROUND OR
RECTANGULAR (MIN. 1.5 RADIUS UNLESS
OTHERWISE NOTED)
RECTANGULAR DUCT. SIZE INDICATED IN
INCHES, FIRST NUMBER IS SIDE SHOWN.
DASHED LINES INDICATE ACOUSTICAL LINER
SUPPLY AIR DIFFUSER -
FLOW ARROWS INDICATE AIR PATTERN.
NO FLOW ARROWS SHOWN INDICATES
4-WAY PATTERN.
FSD
COMBINATION
FIRE/SMOKE DAMPER
EXHAUST AIR DEVICE
RC REMOTE CONTROLLER (VRF SYSTEM)
SERVICE CLEARANCE
T THERMOSTAT
H HUMIDISTAT
$ START/ STOP SWITCH
TH THERMOSTAT/ HUMIDISTAT
HUMIDITY SENSORH
DEMOLISHED
CONNECT TO EXISTING
DISCONNECT FROM EXISTING
IN-LINE 90 DEGREE RISE/DROP IN
RETURN DUCT (RIGHT SIDE IS HIGHER)
DUCT SIZE TRANSITION RECTANGULAR TO
ROUND
30"/14" FLAT OVAL DUCT. SIZE INDICATED IN INCHES,
FIRST NUMBER IS SIDE SHOWN
RETURN AIR DUCT UP
SUPPLY OR OUTSIDE AIR DUCT DOWN
SUPPLY OR OUTSIDE AIR DUCT UP
IN-LINE 90 DEGREE RISE/DROP IN
RETURN DUCT (LEFT SIDE IS HIGHER)
IN-LINE 90 DEGREE RISE/DROP IN
EXHAUST DUCT (RIGHT SIDE IS HIGHER)
IN-LINE 90 DEGREE RISE/DROP IN
EXHAUST DUCT (LEFT SIDE IS HIGHER)
DEMOLITION KEY
CONNECTION SIZE
(X"xX" INDICATES RECTANGULAR, X"/X"
INDICATES OVAL, X"Ø INDICATES ROUND)
X"xX"
TYP. OF #
TYPICAL OF QUANTITY INDICATED
DP DIFFERENTIAL PRESSURE SENSOR
C CARBON DIOXIDE SENSOR
AQ AIR QUALITY SENSOR
SKD
DUCT MOUNTED SMOKE DETECTOR
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
M-002
MECHANICAL ABBREVIATIONS AND
LEGENDS
ANCH
GENERAL
STORAGE
STORAGE
CLOSET
STEAM LINE, TO BE CAPPED
FIBER OPTIC GOING OUT OF BLDG.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
MD100
BASEMENT MECHANICAL DEMOLITION
PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
BASEMENT MECHANICAL DEMOLITION PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
DEMOLITION WORK
DUCT TO BE DEMOLISHED
DEMOLITION LEGEND
EXISTING DUCT TO REMAIN
1. DEMOLISH EXISTING OUTSIDE AIR DUCT AND ASSOCIATED DAMPER. CAP EXISTING OUTSIDE AIR LOUVER TO REMAIN FOR
FUTURE USE.
2. DEMOLISH EXISTING AHU AND REPLACE IT WITH NEW AHU-1. REFER TO M-101 AND M-601 FOR INFORMATION ON AHU-1.
DEMOLISH ALL EXISTING ASSOCIATED CONTROLS, EQUIPMENT AND DUCT SUPPORT, CONDENSATE PAN AND PIPING.
3. DEMOLISH EXISTING RETURN DUCT AND SUPPLY DUCT TO EXISTING AHU.
4. DEMOLISH EXISTING STEAM LINE AND CAP THE OPENINGS. REFER TO E8/MD100.
5. DEMOLISH EXISTING REFRIGERANT LINES AND CONDENSING UNITS. EVACUATE THE REFRIGERANT FROM THE SYSTEM
AND DISPOSE OF IT APPROPRIATELY.
# KEYNOTES:
SCALE: N.T.S.E9
STEAM PIPE PICTURE
5 5
OFFICE
STORAGE
TOILET
COPY RM
OFFICE
OFFICE
OFFICE
HSK
OFFICE
OFFICEOFFICE
RECEPTION
OFFICEOFFICE
STORAGE
EQUIP RM
CORRIDOR
LOBBY
CORRIDOR
CORRIDOR
116117
103104
101A
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
MD101
FIRST FLOOR MECHANICAL
DEMOLITION PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
FIRST FLOOR MECHANICAL DEMOLITION PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
DEMOLITION WORK
DUCT TO BE DEMOLISHED
DEMOLITION LEGEND
EXISTING DUCT TO REMAIN
1. DEMOLISH ALL SUPPLY, EXHAUST, AND RETURN DUCTWORK AS SHOWN.
2. DEMOLISH ALL SUPPLY DIFFUSERS, RETURN AND EXHAUST GRILLES, BRANCH
DUCTWORK, FLEX DUCTS AND VOLUME DAMPERS AS SHOWN.
3. DEMOLISH SUPPLY DUCT AND RETURN DUCT THROUGH THE CHASE BACK TO THE
AHU IN THE BASEMENT.
4. LOCATION OF RETURN GRILLES SHOULD BE FIELD VERIFIED BY THE CONTRACTOR.
# KEYNOTES:
M
CLOSET
204A
CONFERENCE RM
KITCHEN
203A
OFFICE
CLOSET
CORRIDOR
LOBBY
CORRIDOR
STORAGE
TOILET
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
MECH RM
HSK
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
MD102
SECOND FLOOR MECHANICAL
DEMOLITION PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
SECOND FLOOR MECHANICAL DEMOLITION PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
DEMOLITION WORK
DUCT TO BE DEMOLISHED
DEMOLITION LEGEND
EXISTING DUCT TO REMAIN
(E) AHU
1. DEMOLISH ALL SUPPLY, EXHAUST, AND RETURN DUCTWORK AS SHOWN.
2. DEMOLISH ALL SUPPLY DIFFUSERS, RETURN AND EXHAUST GRILLES, BRANCH
DUCTWORK, FLEX DUCTS AND VOLUME DAMPERS AS SHOWN.
3. DEMOLISH EXISTING AHU AND REPLACE IT WITH NEW AHU-2. REFER TO M-102
AND M-601 FOR INFORMATION ON AHU-2. DEMOLISH ALL EXISTING ASSOCIATED
CONTROLS, EQUIPMENT AND DUCT SUPPORT, CONDENSATE PAN AND PIPING.
4. DEMOLISH OUTSIDE AIR DAMPER, LOUVER, AND ASSOCIATED CONTROLS.
5. LOCATION OF RETURN GRILLES SHOULD BE FIELD VERIFIED BY THE
CONTRACTOR.
# KEYNOTES:
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
MD103
ATTIC MECHANICAL DEMOLITION
PLAN
ANCH
SCALE: 3/8" = 1'-0"E1
ATTIC MECHANICAL DEMOLITION PLAN
1. ALL EXISTING ABANDONED MECHANICAL EQUIPMENT AND DUCTWORK NOT SERVING THE
BUILDING SHALL BE DEMOLISHED.
2. ALL EXISTING OPENINGS THROUGH ROOF AND SIDEWALL SHALL BE REPAIRED AND PATCHED
AFTER DEMOLITION TO MATCH ROOF.
# KEYNOTES:
SCALE: = 1'-0"3/8"
0 2 4 62
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
MD104
ROOF MECHANICAL DEMOLITION PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
ROOF MECHANICAL DEMOLITION PLAN
1. DEMOLISH ALL EXISTING MECHANICAL EQUIPMENT ON ROOF AS SHOWN.
# KEYNOTES:
SCALE: = 1'-0"3/8"
"x
AHU
MECHANICAL
ROOM
B01
STORAGE
B02
ARMORY /
WEAPONS
B04
CORRIDOR
B03
8"x6"
EG-2
75 CFM
"ø
FD
AC
OUTDOOR UNIT FOR
FD
WATER HEATER
6"ø8"ø
8"x6"
"x
8"x8"
"x
DH
FD
CONCRETE PADS. SEE DETAIL F1/M-502
FD
42"x18"
VD
VD
PLENUM
CRAWL SPACE
CRAWL SPACE
CRAWL SPACE
CRAWL SPACE
CRAWL
SPACE
CRAWL
SPACE
CRAWL
SPACE
CRAWL
SPACE
AREAWAY
SD
14"x20"
20"x16"
FD
FD
CU
CU
REFRIGERANT
PIPING FROM
AHU-1 TO CU-1
REFRIGERANT
PIPING UP FROM
AC-1 ON SECOND
FLOOR TO THE
OUTDOOR UNIT
REFRIGERANT
PIPING UP FROM
AHU-2 ON
SECOND FLOOR
TO THE CU-2
' A
F F
' A
F F
8"x6"
SD-4
50 CFM
8"x6"
SD-4
50 CFM
10"x6"
SD-5
100 CFM
8"x6"
EG-2
125 CFM
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
M-100
BASEMENT MECHANICAL NEW WORK
PLAN
ANCH
SCALE: 3/8" = 1'-0"E1
BASEMENT MECHANICAL NEW WORK PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
SCALE: = 1'-0"3/8"
0 2 4 62
SHEET NOTES:
1. COORDINATE SLAB PENETRATION LOCATIONS AND SIZES WITH EXISTING
STRUCTURAL.
2. BALANCE THE AIRFLOWS AT THE SUPPLY DIFFUSERS, RETURN REGISTERS AND
EXHAUST REGISTERS VIA MANUAL VOLUME DAMPERS WHICH ARE TO BE PROVIDED
AS REQUIRED FOR BALANCING THE AIR DEVICES WITHIN SPECIFIED TOLERANCE
LIMITS .
3. ACCESS TO BE PROVIDED TO DAMPERS IN THE GYPSUM BOARD CELING.
1. CONNECT 12X10 OUTSIDE AIR DUCT TO EXISTING LOUVER. ENSURE 1 SQ.FT OF NET FREE AREA AT
THE LOUVER FACE. TRANSITION AS REQUIRED FOR TERMINATION.
2. PROVIDE MOTORIZED DAMPER AND INTERLOCK IT OPEN WITH THE OPERATION OF AHU-1.
3. 30x12 SUPPLY DUCT TO FIRST FLOOR. PROVIDE FIRE DAMPER AT FIRST FLOOR SLAB PENETRATION
WITH ACCESS PANEL IN DUCT. REFER TO M-101 FOR CONTINUATION.
4. 28x12 RETURN DUCT FROM FIRST FLOOR. PROVIDE FIRE DAMPER AT FIRST FLOOR SLAB
PENETRATION WITH ACCESS PANEL IN DUCT. REFER TO M-101 FOR CONTINUATION.
5. CONNECT UNIT TO THE NEW REFRIGERANT PIPING. ROUTE 3/4" CONDENSATE PIPING TO FLOOR DRAIN IN ROOM. SEE P-100 FOR FLOOR DRAIN LOCATION. SEE NOTE 7 BELOW FOR ADDITIONAL
INFORMATION ON REFRIGERANT PIPING.
6. 8X8 EXHAUST DUCT TO FIRST FLOOR. REFER M-101 FOR CONTINUATION. PROVIDE FIRE DAMPER AT
FIRST FLOOR SLAB PENETRATION WITH ACCESS PANEL IN DUCT.
7. PROVIDE NEW CONDENSING UNITS WITH ASSOCIATED REFRIGERANT PIPING AND ALL PIPING
ACCESSORIES AS NECESSARY AS PER MECHANICAL SCHEDULE M-601. PROVIDE CONCRETE PADS
TO SUPPORT THE NEW UNITS AS NECESSARY.
8. DUCTWORK IN CRAWL SPACE - SOME EXCAVATION MAY BE REQUIRED.
KEYNOTES:#
7 7
9. MOUNT DH-1 ON WALL AT 5' AFF. ROUTE CONDENSATE DRAIN TO A CONNECTION POINT PROVIDED
BY DIV. 22 AT THE SINK IN THE ROOM.
10. THERMOSTAT WIRING FROM AHU- 1 TO FIRST FLOOR. REMOTE SENSING BULB FOR THERMOSTAT TO
BE PLACED IN 14 X 20 RETURN DUCT.
F A
C P
OFFICE
OFFICE
WOMEN
RESTROOM
STAFF
LOUNGE
MEN
RESTROOM
CORRIDOR
CORRIDOR
OFFICER
WORK
ROOM
INTERVIEW
ROOM
EVIDENCE
PROCESSING
EVIDENCE
ROOM
OFFICE
HOUSE
KEEPING
WAITING
ROOM
RECEPTION
ELECT.
OFFICE
OFFICE
8"ø
SD-1
150 CFM
6"ø
SD-1
100 CFM 10"ø
SD-1
350 CFM
8"ø
SD-1
150 CFM
8"ø
SD-1
150 CFM
8"ø
SD-1
150 CFM
6"ø
SD-1
100 CFM
6"ø
SD-1
100 CFM
8"ø
SD-1
150 CFM
6"ø
SD-1
120 CFM
8"x8"
RG-1
150 CFM
6"x6"
RG-1
100 CFM
8"x8"
RG-1
300 CFM
10"x10"
RG-1
300 CFM
8"x8"
RG-1
150 CFM6"x6"
RG-1
50 CFM
6"x6"
RG-1
100 CFM
8"x8"
RG-1
150 CFM
8"ø
EG-3
150 CFM 8"ø
EG-3
150 CFM
6"ø
SD-1
100 CFM
6"ø
SD-1
50 CFM
6"x6"
RG-1
100 CFM
6"ø
SD-1
50 CFM
10"ø
SD-1
250 CFM
8"x8"
RG-1
120 CFM
6"x6"
RG-1
50 CFM
8"ø
SD-2
200 CFM
6"x6"
RG-1
100 CFM
6"x6"
RG-1
50 CFM
"x
"x
6"x36"
RG-2
200 CFM
"x
"x
"8 "x
"x
"x
16"x12"
"x
"x
"x
"x
14"x10"12"x10" 12"x10"14"x10"
"ø
6"x6"10"x10"
"x
8"x6"
EG-2
50 CFM
14"x10"20"x12"
"x
"x
8"ø 8"ø 8"x10"
"x
"ø
"ø
"x
6"ø
"x
14"x10" 8"x10"
10"x8"12"x8"
"x
"ø
"ø
"ø
6"x6"
"x
"ø
FSD
8"ø
10"ø
"x
FSD
8"ø
"ø
8"x8"
16"x12"12"x16"
14"x20" 20"x16"
FSD
2-SLOT, 4' LONG, 1" SLOT WIDTH
8"ø
12"x8"
T
TO AHU-1
FSD
FSD
FSD
FSD
FSD
6"ø
SD-3
75 CFM 6"ø
SD-3
75 CFM
"ø6
"ø
6"ø
EG-3
50 CFM
"ø
FD
FD
FD
FD
H
TO AHU-1
10"x10"
REFRIGERANT
LINE FROM AC-1
ON SECOND
FLOOR
REFRIGERANT LINE
FROM AHU-2 ON
SECOND FLOOR
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
M-101
FIRST FLOOR MECHANICAL NEW
WORK PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
FIRST FLOOR MECHANICAL NEW WORK PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
SHEET NOTES:
1. COORDINATE FINAL LOCATIONS AND HEIGHTS OF DIFFUSERS, REGISTERS AND
GRILLES WITH ARCHITECTURAL REFLECTED CEILING PLANS.
2. COORDINATE SLAB PENETRATION LOCATIONS AND SIZES WITH EXISTING
STRUCTURAL.
3. BALANCE THE AIRFLOWS AT THE SUPPLY DIFFUSERS, RETURN REGISTERS AND
EXHAUST REGISTERS VIA MANUAL VOLUME DAMPERS WHICH ARE TO BE PROVIDED
AS REQUIRED FOR BALANCING THE AIR DEVICES WITHIN SPECIFIED TOLERANCE
LIMITS .
1. 10X10 AND 8X8 EXHAUST DUCTS UP TO FLOOR ABOVE. REFER TO M-102 AND M-103 FOR CONTINUATION.
2. 20X16 SUPPLY DUCT FROM AHU-1 IN THE BASEMENT. REFER TO M-100 FOR CONTINUATION.
3. 14X20 RETURN DUCT TO AHU-1 IN THE BASEMENT. REFER TO M-100 FOR CONTINUATION.
4. PROVIDE LINEAR SLOT DIFFUSER. REFER TO MECHANICAL SCHEDULES ON SHEET M-601 FOR MORE INFORMATION.
COORDINATE FINISH WITH ARCHITECT.
5. REMOTE SENSING BULB FOR THERMOSTAT TO BE PLACED IN THE 14 X 20 RETURN DUCT AT THE BASEMENT TO AHU-1.
REFER TO M-100 FOR CONTINUATION.
6. 8X8 EXHAUST DUCTS DN TO FLOOR BELOW. REFER TO M-100 FOR CONTINUATION.
# KEYNOTES:
AHU
CONFERENCE
ROOM
203 CHIEF
OFFICE
ELECT.
LOBBY
MECHANICAL
ROOM
OFFICE
OFFICE
CORRIDOR
OFFICE
OFFICE
MEN
RESTROOM
208MEN
SHOWER &
LOCKER
ROOM
WOMEN
SHOWER &
LOCKER
ROOM
206A
WOMEN
RESTROOM
OIT
DEPUTY
CHIEF
OFFICE
CORRIDOR
CORRIDOR
HOUSE
KEEPING
8"ø
SD-1
200 CFM
6"ø
SD-1
75 CFM 8"ø
SD-1
100 CFM
6"ø
SD-1
100 CFM
8"ø
SD-1
150 CFM
8"ø
SD-1
200 CFM
8"ø
SD-1
150 CFM
8"x8"
RG-1
200 CFM
6"x6"
RG-1
100 CFM
8"x8"
RG-1
150 CFM
8"x8"
RG-1
200 CFM
8"x8"
RG-1
150 CFM
10"x10"
RG-1
250 CFM
8"ø
EG-1
120 CFM
8"ø
EG-3
75 CFM
8"ø
EG-3
75 CFM
8"ø
SD-1
250 CFM
6"x6"
RG-1
50 CFM
8"ø
EG-1
130 CFM
8"ø
SD-1
250 CFM
10"x10"
RG-1
250 CFM
8"ø
SD-2
200 CFM
8"ø
SD-2
200 CFM
8"ø
SD-1
100 CFM
8"ø
SD-1
175 CFM
"x
12"x8"
AC
"x
6"x6"
"x
"x
"x
6"x48"
RG-2
400 CFM
12"x10"14"x10"
"x
20"x10"
"ø
"ø
"x
8"x6"
EG-2
50 CFM
10"x12"12"x12"
14"x10"
12"x10"
"ø
"ø
"ø
14"x10"
"x
"ø
"ø
8"x10"
"x
"x
"ø 8 "ø
"x
8"ø
6"ø
8"ø
"x
8"x10"
"x
10"x10"
8"x10"
24"x12" 8 "x
8"x8"
14"x16"
2-SLOT, 4' LONG, 1" SLOT WIDTH,
"x
18"x10"
16"x10"
"x
T
FSD
10"x8"
FSD
FSD
T
VD
VD
58"x22" PLENUM
6"ø
SD-3
50 CFM
6"ø
SD-3
50 CFM
"ø6 "ø
6"x6"
RG-1
50 CFM
6"x6"
SD
FD
REFRIGERANT
PIPING DN TO
BASEMENT
REFRIGERANT
PIPING DN TO
BASEMENT
H
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
M-102
SECOND FLOOR MECHANICAL NEW
WORK PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
SECOND FLOOR MECHANICAL NEW WORK PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
4 4
SHEET NOTES:
1. COORDINATE FINAL LOCATION AND HEIGHTS OF DIFFUSERS AND GRILLES WITH ARCHITECTURAL
REFLECTED CEILING PLANS.
2. COORDINATE SLAB PENETRATION LOCATIONS AND SIZES WITH EXISTING STRUCTURAL.
3. BALANCE THE AIRFLOWS AT THE SUPPLY DIFFUSERS, RETURN REGISTERS AND EXHAUST GRILLES VIA
MANUAL VOLUME DAMPERS WHICH ARE TO BE PROVIDED AS REQUIRED FOR BALANCING THE AIR
DEVICES WITHIN SPECIFIED TOLERANCE LIMITS.
1. 14X12 OUTSIDE AIR DUCT UP TO THE ATTIC. SEE M-103 FOR CONTINUATION.
2. REMOTE SENSING BULB FOR THERMOSTAT TO BE PLACED IN THE 24X14
RETURN DUCT TO AHU-2.
3. 10X10 GENERAL EXHAUST DOWN TO FIRST FLOOR AND 14x16 EXHAUST DUCT
UP TO EXHAUST FAN EF-1 IN THE ATTIC.
4. PROVIDE LINEAR SLOT DIFFUSERS AS SHOWN. COORDINATE COLOR AND
FINISH WITH ARCHITECT.
5. PROVIDE REFRIGERANT PIPING. ROUTE 3/4" CONDENSATE DRAIN TO FLOOR
DRAIN IN ROOM. SEE P-102 FOR LOCATION OF FLOOR DRAIN.
6. INSTALL AC-1 AT 7' A.F.F. PROVIDE REFRIGERANT PIPING TO CONNECT TO THE
OUTDOOR UNIT AND SIZE THE PIPING PER MANUFACTURER'S
RECOMMENDATIONS. PROVIDE ACCESSORIES AND SERVICE CLEARANCE AS
NECESSARY. ROUTE 3/4" CONDENSATE DRAIN TO FLOOR DRAIN IN ROOM. SEE
P-102 FOR LOCATION OF FLOOR DRAIN.
7. 8X8 GENERAL EXHAUST DOWN TO FIRST FLOOR AND 8X8 EXHAUST DUCT UP
TO EXHAUST FAN EF-2 IN THE ATTIC.
# KEYNOTES:
"x
"x
EUH
EUH
T
T "x
"x
8"x8"
FD
FD
EF
"x
TG-1
12"x8"
TYP. 18
EF
FD
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
M-103
ATTIC MECHANICAL NEW WORK PLAN
ANCH
SCALE: = 1'-0"3/8"
0 2 4 62
SCALE: 3/8" = 1'-0"F1
ATTIC MECHANICAL NEW WORK PLAN
1. GENERAL EXHAUST FAN EF-1 IN THE ATTIC. REFER TO MECHANICAL SCHEDULE M-601 FOR MORE INFORMATION.
2. GENERAL EXHAUST FAN EF-2 IN THE ATTIC. REFER TO MECHANICAL SCHEDULE M-601 FOR MORE INFORMATION.
3. PROVIDE MOTORIZED DAMPER AND INTERLOCK IT WITH AHU-2.
4. COORDINATE PENTHOUSE LOUVER LOCATION ON ROOF AND ROOF OPENING SIZE WITH ARCHITECTURAL.
5. 14X12 OUTSIDE AIR DUCT DOWN TO THE SECOND FLOOR. SEE M-102 FOR CONTINUATION.
6. 14X16 EXHAUST DUCT DOWN TO THE SECOND FLOOR. SEE M-102 FOR CONTINUATION.
7. 8X8 EXHAUST DUCT DOWN TO THE SECOND FLOOR. SEE M-102 FOR CONTINUATION.
# KEYNOTES:
LV
LV
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
M-104
ROOF MECHANICAL NEW WORK PLAN
ANCH
SCALE: 3/8" = 1'-0"F1
ROOF MECHANICAL NEW WORK PLAN
1. COORDINATE PENETRATION LOCATIONS WITH ARCHITECTURAL. COORDINATE PENETRATION SIZES WITH MECHANICAL SCHEDULES M-601.
# KEYNOTES:
SCALE: = 1'-0"3/8"
FROM STRUCTURE
SAME AS DIFFUSER
INLET: 5'-0" MAX
FLEXIBLE DUCT SIZE
LENGTH.
12"
CEILING
SUPPORT SADDLE
VOLUME DAMPER W/
LOCKING QUADSADDLE
SHEET METAL
CONICAL OUTLET
BRANCH DUCT
ONLY FOR CHANGE OF
DIRECTION GREATER
USE RIGID ELBOWS
THAN 45°
SEE SPECIFICATIONS FOR CLAMPS
AND SEALANT (TYP.)
TYPICAL
DIFFUSER OR
REGISTER IN
LAY-IN CLG.
THERMAL INSULATION
SEE SPECIFICATIONS
DRAW THRU
BLOW THRU
2" PLUS X
1" MINIMUM
X
2X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
DRAIN LINE SHALL BE AT LEAST THE SAME
SIZE AS THE NIPPLE ON THE DRAIN PAN
PIPING SHALL BE RIGID COPPER TYPE L
OR TYPE M UNLESS NOTE BELOW IS MET
PITCH DOWN
TOWARD DRAIN
CLEAN OUT
FLOOR SINK
DRAIN
PAN
NOTE:
1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND IS
INDOORS AND DOES NOT PASS THROUGH RATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE
TO BE CONNECTED.
DIELECTRIC
FITTING
A B
MAIN EXHAUST OR RETURN
PLAN VIEW
AIR
FLOW AIR
FLOW
PROVIDE VOLUME DAMPER
AT EACH BRANCH DUCT
1/4W OR 4" MIN.
BRANCH DUCT
VD
W
420ONE 1 x 18 GA STRAP36
TWO 1/2. RODS
TWO 3/8. RODS
ONE 1 x 16 GA STRAP
50 700
ONE 1 x 22 GA STRAP
QUANTITY/SIZEMAX. DUCT
HANGER STRAPS OR RODS
MAX. LOAD
LBS.
MAX.
IN.
SPACING
IN. IN.
NOTE:
TABULATED DATA FROM SMACNA
ALLOWS FOR DUCT REINFORCING AND
INSULATION, BUT NO EXTERNAL LOAD.
BAND
OVER 50"
HANGER RODS
BAND OF SAME
SIZE AS HANGER
STRAP
LOAD RATED
FASTENERS
50" & UNDER
NOTE:
1.
2.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR
MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION SEE
SPECIFICATION
DAMPER BLADE
1/8" CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
INSULATION
STAND-OFF
1/2" ROUND ROD
PIN
DUCT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
M-501
MECHANICAL DETAILS
ANCH
SCALE: N.T.S.C1
FLEXIBLE AIR DUCT CONNECTOR
SCALE: N.T.S.D4
AHU DRAIN TRAP
SCALE: N.T.S.C8
EXHAUST OR RETURN BRANCHWORK
SCALE: N.T.S.F1
ROUND DUCT HANGER
SCALE: N.T.S.F5
VOLUME DAMPER DETAIL
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
M
AX.
M A
X
E Q
U
IP
M E
N T
AIR
FLOW
AIR
FLOW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
M
AX.
M A
X
M A
X
M A
X
15°
NOTES:
1.
2.
3.
4.
5.
6.
A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION IS SIMILAR. FOLLOW
DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR
SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION OR
FLOOR AND NOT OUTSIDE THE PENETRATION.
GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER
FRAME AND TO PERIMETER ANGLES.
PERIMETER ANGLES: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2", 14 GAGE, TO PROVIDE 1"
MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.
BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.
ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.
PROVIDE 1/4" TO 1/2" CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE WITH ROCK WOOL
FIRESTOP FIBER.
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND
MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" HIGH CONCRETE CURB AROUND
OPENING FOR DUCT.
SLEEVE, NOTE 2
DUCT
CONNECTION
NOTE 4
DAMPER,
NOTE 1
DAMPER COLLAR
EXTENSION INTEGRAL
PART OF SLEEVE
SLEEVE, NOTE 2
NOTE 6FIRE BARRIER
PARTITION OR CHASE
TYPICAL DUCT
INSULATION
PERIMETER ANGLE, NOTE 3 (NOTE
FASTENED TO PARTITION)
ACCESS
PANEL
NOTE 5
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9
PSF MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
6"
MINIMUM 6" TO EDGE OF EQUIPMENT FRAME
THREADED BOLT
AND WASHER
THRU. PIPE
SLEEVE
CONCRETE TOPPING
NO. 4 DOWELS AT 12"
W.W.F 6" X 7" TWO-WAY
REINFORCING
BOLT CENTERLINE
12"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
M-502
MECHANICAL DETAILS
ANCH
SCALE: N.T.S.C1
DUCTWORK TRANSITIONS
SCALE: N.T.S.E6
SECTION THRU FIRE DAMPER INSTALLATION
SCALE: N.T.S.E1
PIPE HANGER DETAIL
SCALE: N.T.S.F1
HOUSEKEEPING PAD
STRUCTURAL JOIST
1/2" THREADED
ROD (TYP).
1-1/4 X 1-1/4 X 3/16
ANGLE IRON SUPPORTS.
1/2" BOLT AND NUT
W/ 2" 1/2 WASHER.
NUTS AND WASHERS BOTH
SIDES OF ANGLE (TYP).
MOUNTING BRACKET
FLEX. CONNECTION (TYP)
AIR FLOW
DUCTWORK
MOUNTING BRACKET
FAN BOLTS
STEEL SPRING ANC RUBBER IN
SHEAR TYPE VIBRATION ISOLATORS
CONNECT DUCTWORK TO FAN
WITH 1/8" THICK NEOPRENE
GASKET
SWAY BRACE,
3/8" THREADED STEEL RODS
SUPPORT FROM BLDG
STRUCTURE LENGTHS OF RODS
TO SUIT SPACE AVAILABLE
BOTH DIRECTIONS @ 90°
TYP. FOR SIX
EXPANSION BOLTS
WASHERS
FRAME WITH LOCK
RECOMMENDATIONS
A MINIMUM OF TWO BRACKETS.
SECURED TO WALL WITH
UNIT HEATER SHALL BE
SEISMIC BRACE
UNIT HEATER
EACH SIDE OF
BRACKETS PER MANUFACTURERS
TWO 5/8" BOLTS,
5/8"
NOTE:
1. APPLICABLE TO PENETRATIONS OF ALL
FIRE RATED MEMBRANES, IN
ACCORDANCE WITH NFPA 101. REFER
TO SPECIFICATIONS SECTION 07 84 00,
FIRE STOPPING SYSTEMS.
INSULATED PIPE
OR DUCT
FLOOR
FIRESTOP MATERIAL
3/4" APPROVED
FIRESTOP INSULATION
WITH VAPOR BARRIER
PIPE SLEEVE WHERE
SPECIFIED
1/4" DIA ANCHOR ROD
FOR NEW
CONSTRUCTION
WELD
FLOOR OR DECK PENETRATION
PARTITION OR CHASE PENETRATION
MASONRY
PARTITION
PARTITION SUPPORT
FIRESTOP
MATERIAL
3/4" APPROVED FIRESTOP
INSULATION WITH VAPOR
BARRIER
DRYWALL PARTITION
INSULATED
PIPE OR
DUCT
6" 6"
6" 6"
ELECTRICAL HEATER
SUPPLY OPENING
RETURN OPENING
1" DRAIN CONNECTION REFRIGERANT
CONNECTIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
M-503
MECHANICAL DETAILS
ANCH
SCALE: N.T.S.C1
DUCT HANGER DETAIL - RECTANGULAR
SCALE: N.T.S.C4
EXHAUST FAN DETAIL
SCALE: 12" = 1'-0"C8
ELECTRIC UNIT HEATER DETAIL
SCALE: 1" = 1'-0"F1
PIPE/DUCT PENETRATION OF SMOKE/FIRE BARRIERS
SCALE: N.T.S.F7
AHU DETAIL
1. REFER TO SPECIFICATIONS FOR FILTER TYPES. PROJECT ELEVATION 1100FT ABOVE SEA LEVEL.
2. TOTAL UNIT STATIC PRESSURE INCLUDES ESP, DIRTY COILS & DIRTY FILTERS.
3. AHU ON MOUNTING RAILS WITH DRIP PAN AND FLOAT SWITCH.
4. PROVIDE CONDENSATE DRAIN TRAP.
AHU-2 LEVEL 2 LEVEL 2 CENTRIFUGAL 2,250 450 0.7 833 0.97 18 55.0 77 290 80.0 67.0 56 56 74.89 TRANE TWE 07243BAA 1,2,3,4,5
NOTES:
AHU-1 BASEMENT LEVEL 1 CENTRIFUGAL 2,520 600 0.7 853 1.16 18 55.0 77 324 80.0 67.0 58 57.2 75.70 TRANE TWE 07243BAA 1,2,4,5,6
ESP (in.wg)
DB
(°F)
WB
(°F)
DB
(°F)
WB
(°F)
AIR HANDLING UNIT SCHEDULE
TAG LOCATION SERVICE
SUPPLY FAN HEATING COIL(ELECTRIC) COOLING COIL
BASIS OF
DESIGN
NOTES
FAN MOTOR AIRSIDE AIRSIDE
TYPE
OPER.
DESIGN
AIRFLOW
(CFM)
OA
AIRFLOW
(CFM)
STATIC
PRESS.
RPM HP
HEATING
(kW)
EAT DB
(°F)
LAT DB
(°F)
MAX.
FACE
VEL.
(FPM)
EAT LAT TOTAL
CAP.
(MBTUH)
SEN CAP.
(MBTUH)
LAT CAP.
(MBTUH)
18.53
16.27
59.43
63.11
5. ELECTRICAL TO PROVIDE STARTER/DISCONNECT.
WEIGHT
(LBS)
ELECTRICAL DATA
AHU ELECTRIC HEATER
V/PH/HZ V/PH/HZMCA MCA
208/3/60 208/3/6077 87
208/3/60 208/3/6077 87
6. AHU ON 4" HOUSEKEEPING PAD.
EUH-1 ATTIC SPACE HEATING 1/3 208 1 7.5 TASK MASTER 5100 25 1,2
NOTES:
HP VOLTS PHASE
1. HORIZONTAL UNIT HEATER.
2. PROVIDE UNIT WITH DISCONNECT, PACKAGED CONTROL AND THERMOSTAT.
ELECTRIC UNIT HEATER SCHEDULE
TAG LOCATION SERVICE
ELECTRICAL DATA MIN.
HEATING
CAP.(KW)
BASIS OF
DESIGN WEIGHT (lbs) NOTES
EUH-2 ATTIC SPACE HEATING 1/3 208 1 5 TASK MASTER 5100 25 1,2
EF-1 ATTIC LOCKERS, TOILETS 900 850 0.5 1,176 523 HORIZONTAL INLINE 0.14 1/2 6.2 115/60/1 GREENHECK-SQ-120-VG 1,2,3,4
2. REFER TO LOUVERED PENTHOUSE SCHEDULE FOR EXHAUST PENTHOUSE SIZE.
3. MANUFACTURER TO PROVIDE MOTOR WITH VARIABLE SPEED DUTY.
NOTES:
1. MANUFACTURER TO PROVIDE STARTER/DISCONNECT.
EXHAUST FAN SCHEDULE
TAG LOCATION SERVICE
FAN MOTOR
BASIS OF DESIGN NOTES
MAX. DESIGN
AIRFLOW
(CFM)
OPER. DESIGN
AIRFLOW
(CFM)
EX S.P.
(in wg)
RPM
MAX. OUTLET
VELOCITY
(FPM)
FAN
DISCHARGE
ORIENTATION
OPER.
BHP
HP FLA V/C/P
EF-2 ATTIC BASEMENT 240 200 0.5 1,635 240 HORIZONTAL INLINE 0.06 1/10 1.38 115/60/1 GREENHECK-SQ-80-VG 1,2,3,4
4.PROVIDE WITH INTEGRAL BACK DRAFT DAMPER.
4. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL ELEVATIONS.
5. PROVIDE GALVANIZED PLENUM WITH TRANSITION TO DUCT CONNECTION SIZE AS INDICATED ON THE PLAN.
SD-1 SUPPLY CEILING 24X24 AL RADIAL HORIZONTAL SQUARE PLAQUE DIFFUSER TITUS OMNI 1,2,3,4
SD-2 SUPPLY CEILING SEE DWGS AL LINEAR SLOT DIFFUSER, TWO(2) 1" SLOTS TITUS TBDI-10 1,2,3,4
SD-3 SUPPLY CEILING 12X12 AL RADIAL HORIZONTAL SQUARE PLAQUE DIFFUSER TITUS OMNI 1,2,3,4
EG-1 EXHAUST CEILING 24X24 AL 1/2"X1/2"X1/2" GRID EGGCRATE FACE EXAHUST GRILLE TITUS 50F 1,2,3,4,5
EG-2 EXHAUST SIDEWALL SEE DWGS AL SIDEWALL EXHAUST GRILLE TITUS 350RL 1,3,5
EG-3 EXHAUST CEILING 12X12 AL 1/2"X1/2"X1/2" GRID EGGCRATE FACE EXHAUST GRILLE TITUS 50F 1,2,3,4,5
1. REFER TO DRAWINGS FOR NECK SIZES.
2. REFER TO ARCHITECTURAL RCP DRAWINGS FOR COORDINATION WITH CEILING.
3. COORDINATE FINISH WITH ARCHITECT.
RG-1 RETURN CEILING 24X24 AL 1/2"X1/2"X1/2" GRID EGGCRATE FACE RETURN REGISTER TITUS 50F 1,2,3,4
RG-2 RETURN CEILING SEE DWGS AL SLOT RETURN, 1/2" SPACING WIDTH TITUS CT-580 1,2,3,4
NOTES:
GRILLE AND DIFFUSER SCHEDULE
TAG SERVICE MOUNTING MODULE SIZE (in. x in.) MATERIAL DESCRIPTION BASIS OF DESIGN NOTES
TG-1 TRANSFER SIDEWALL SEE DWGS AL SIDEWALL TRANSFER GRILLE TITUS 350RL 1,3,4
SD-4 SUPPLY WALL SEE DWGS AL WALL MOUNTED SUPPLY GRILLE TITUS 300FL 1,2,3,4
SD-5 SUPPLY DUCT SEE DWGS AL DUCT MOUNTED SUPPLY GRILLE, 3/4" SPACING TITUS S300FL 1,2,3,4
LV-1 38 26 24 12 2 1050 GREENHECK WRH-12X24
LOUVERED PENTHOUSE SCHEDULE
TAG
LENGTH
(IN)
WIDTH
(IN)
THROAT
LENGTH
(IN)
THROAT
WIDTH (IN)
THROAT
AREA (FT^2)
AIR
VOLUME
(CFM)
BASIS OF DESIGN APPLICATION
LV-2 28 28 14 14 1 450 GREENHECK ESD-635PD-14X14
WEIGHT
(LBS)
29 EXHAUST
INTAKE
AC-1 OIT ROOM 205 DUCTLESS SPLIT 887 0 0 9,800 30,700 16 80 67 95 N/A 1.00 0.76 21.00 0.93 208 60 1 MITSUBISHI MSY-D30NA, MUY-D30NA
SPLIT SYSTEM AIR CONDITIONER SCHEDULE
DB
(F)
WB
(F) MCA FLA MCA FLA
MIN
CAPACITY
(BTU/H)
RATED
CAPACITY
(BTU/H)
SEER
EAT OSA
DESIGN
TEMP (F)
INDOOR UNIT OUTDOOR UNIT
VOLT HZ PHASE
TAG SERVICE TYPE
TOTAL
SUPPLY
AIRFLOW
(CFM)
MIN.
OUTSIDE
AIR FLOW
(CFM)
EXT
STATIC
PRESSUR
E (IN)
COOLING CAPACITY
HEATING
CAPACITY
ELECTRICAL DATA
BASIS OF
DESIGN
NOTES
1. MANUFACTURER TO PROVIDE MHK1 BACKLIT WIRELESS WALL-MOUNTED THERMOSTAT.
NOTES:
DH-1 ARMORY ARMORY 155 29.5 R134A 190G 3/4" 120/1/60 2.8 39.0 IW25-4 1
VOLTS/PH/HZ FLA
1. WALL MOUNTED DEHUMIDIFIER AT 5' AFF.
NOTES
DEHUMIDIFIER SCHEDULE
TAG LOCATION SERVICE AIRFLOW
(CFM)
CONDENSATE
CAPACITY (PPD) REFRIGERANT
DRAIN
CONNECTION
(IN)
ELECTRICAL
DATA
WEIGHT
LBS
BASIS OF
DESIGN
NOTES
VOLTS/
PH/HZ
MCA STAGES
CU-1 EXTERIOR AHU-1 208/3/60 35 2.0
CU-2 EXTERIOR AHU-2 208/3/60 35 2.0
NOTES:
NEW CONDENSER UNIT SCHEDULE
TAG LOCATION SERVICE
TOTAL
COOLING
CAPACITY
(TON)
COMPRESSORS
ELECTRICAL DATA
BASIS OF DESIGN NOTES
6 2 6 2
REFRIGERANT
R-410A
R-410A TWA07243DAA
TWA07243DAA
1. ELECTRICAL TO PROVIDE STARTER/DISCONNECT.
HEATING CAPACITY
OUTDOOR
TEMP (F)
INDOOR DB
(F)
MBH
12 60 33.6 12 60 33.6
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
M-601
MECHANICAL SCHEDULES AND
SEQUENCE OF OPERATION
ANCH
AIR HANDLERS AHU/CU-1 & AHU/CU-2
1. THE UNITS SHALL OPERATE AS SCHEDULED BY THE BUILDING MANAGEMENT SYSTEM (BMS)
a. DURING OCCUPIED THE SYSTEMS SHALL OPERATE WITH LOCAL CONTROLS AS NOTED HERE IN AFTER.
b. DURING UNOCCUPIED HOURS, A SPACE TEMPERATURE SENSOR SHALL SIGNAL TO THE BMS TO OPERATE THE SYSTEMS AS NEEDED TO
MAINTAIN 60 DEGREES F (ADJ.) IN THE WINTER AND 80 DEGREES F (ADJ.) IN THE SUMMER.
2. A SPACE THERMOSTAT SHALL CYCLE THE UNIT IN HEATING OR COOLING AS NEEDED TO MAINTAIN SET POINT TEMPERATURE. THE SENSOR
FOR THE THERMOSTAT SHALL BE IN THE ASSOCIATED AIR HANDLER RETURN DUCTWORK AS NOTED ON THE DRAWINGS.
a. THE THERMOSTAT SHALL OPERATE THE EMERGENCY STRIP HEAT AS NEEDED TO MAINTAIN SPACE SET POINT TEMPERATURE UPON
FAILURE OF THE COMPRESSOR TO MAINTAIN SET POINT TEMPERATURE OR DEHUMIDIFICATION OPERATION.
3. MOTORIZED DAMPERS IN THE OUTSIDE AIR DUCTWORK SHALL OPEN DURING OCCUPIED HOURS AND REMAIN CLOSED DURING SET UP OR SET
BACK TEMPERATURE OPERATION AND UNOCCUPIED CONDITIONS.
4. A SMOKE DETECTOR IN THE RETURN AIR DUCTWORK SHALL STOP THE UNIT, CLOSE THE OUTSIDE AIR DAMPER, AND ALARM THE BUILDING
FIRE ALARM AND BMS SYSTEMS UPON ACTIVATION.
5. A SPACE HUMIDISTAT SHALL ENERGIZE THE COOLING FUNCTION FOR UNITS AS NEEDED TO MAINTAIN SPACE HUMIDITY LEVELS AT 60% RH
(ADJ.). THE EMERGENCY STRIP HEAT SHALL CYCLE BY THE ROOM THERMOSTAT AS NEEDED TO MAINTAIN SPACE TEMPERATURE.
6. AHU-2 WILL BE INSTALLED IN AN AUXILIARY DRAIN PAN WITH A FLOAT SWITCH TO DEENERGIZE THE UNIT UPON ACTIVATION.
EXHAUST FANS EF-1 & EF-2
1. THE EXHAUST FAN EF-1 SHALL OPERATE WHEN AHU-1 &/OR AHU-2 ARE OPERATING AND THE AHU’S OUTSIDE AIR DAMPERS ARE OPEN. THE
FAN SHALL BE DEENERGIZED DURING UNOCCUPIED CONDITIONS.
2. THE EXHAUST FAN EF-2 SHALL OPERATE WHEN AHU-1 IS OPERATING, AND THE OUTSIDE AIR DAMPER IS OPEN. THE FAN SHALL BE
DEENERGIZED DURING UNOCCUPIED CONDITIONS.
UNIT HEATERS EUH-1 & EUH-2
1. THE UNITS SHALL CYCLE AS NEEDED, BY A SPACE THERMOSTAT, TO MAINTAIN SET POINT OF 45 DEGREES F (ADJ.) IN THE ATTIC.
DUCTLESS SPLIT SYSTEM AC-1
1. THE UNIT SHALL CYCLE AS NEEDED TO MAINTAIN ROOM THERMOSTAT SET POINT OF 72 DEGREES F (ADJ.). THE UNIT SHALL OPERATE
CONTINUOUSLY. A SPACE TEMPERATURE SENSOR IN THE ROOM SHALL ALARM THE BMS UPON SPACE TEMPERATURES ABOVE 75 DEGREES F
(ADJ.).
DEHUMIDIFER DH-1
1. THE UNIT SHALL OPERATE AS NEEDED WITH UNIT CONTROLS TO MAINTAIN ROOM AT 50% RH (ADJ.). A HUMIDITY SENSOR SHALL ALARM THE
BMS UPON SPACE HUMIDITY ABOVE 65% RH (ADJ.).
SEQUENCE OF OPERATION
| Sheets |
| M-001 - MECHANICAL GENERAL NOTES |
| M-002 - MECHANICAL ABBREVIATIONS AND LEGENDS |
| MD100 - BASEMENT MECHANICAL DEMOLITION PLAN |
| MD101 - FIRST FLOOR MECHANICAL DEMOLITION PLAN |
| MD102 - SECOND FLOOR MECHANICAL DEMOLITION PLAN |
| MD103 - ATTIC MECHANICAL DEMOLITION PLAN |
| MD104 - ROOF MECHANICAL DEMOLITION PLAN |
| M-100 - BASEMENT MECHANICAL NEW WORK PLAN |
| M-101 - FIRST FLOOR MECHANICAL NEW WORK PLAN |
| M-102 - SECOND FLOOR MECHANICAL NEW WORK PLAN |
| M-103 - ATTIC MECHANICAL NEW WORK PLAN |
| M-104 - ROOF MECHANICAL NEW WORK PLAN |
| M-501 - MECHANICAL DETAILS |
| M-502 - MECHANICAL DETAILS |
| M-503 - MECHANICAL DETAILS |
| M-601 - MECHANICAL SCHEDULES AND SEQUENCE OF OPERATION |