09 1200392 VA Bldg 20 COMM 05 13 2021.pdf

PDF 2 MB Posted

Attached to
Z2DZ-36C249-21-AP-3182 - 621-15-101 - Correct Admin Bldg. -20 Environment & Condition Deficiencies
Solicitation number
36C24921B0014
Issued by

About this file

This presolicitation notice is for a construction project to correct environment and condition deficiencies at the Administration Building 20 at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The project scope includes office renovations, a conference room, observation room, interview room, evidence processing room, locker rooms, storage, electrical and mechanical rooms, an armory with ammunition storage, lounge areas, waiting and reception areas, restrooms, corridors, and finish materials replacement. The estimated value is between $1 million and $5 million. The NAICS code is 236220. The solicitation will be issued on or around October 20, 2021 and close on November 20, 2021. This is a 100% SDVOSB set-aside per 38 U.S.C. 8127(d). Offerors must be listed in CVE and SAM. The awarded contractor must enroll in VETS4212. Questions must be submitted in writing to the contract specialist by the specified date and include the project number and name in the email subject line.

View the file

Other files

File Type Posted
36C24921B0014 0007.pdf PDF
S04- SITE VISIT ATTENDEES - Bldg 20 - 621-15-101.pdf PDF
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-16-2021.pdf PDF
36C24921B0014 0006.pdf PDF
S05 - VA Comprehensive Asbestos Containing Materials Inspection Report January 2010 - 2.pdf PDF
S06 - AMENDMENT 5 - 36C24921B0014 0005.pdf PDF
S05-Mountain Home TN - VA Asbestos O AND M Plan January 2010 -1.pdf PDF
S05-RFI RESPONSE QUESTIONS - B20 Correct FCA Deficiencies 12-23-2021.pdf PDF
S02-LBP DOC-Building 20 - 36C24921B0014.pdf PDF
S02-Building 20 ACM Report - 36C24921B0014.pdf PDF
S02- Solicitation - 36C24921B0014 - 621-15-101 - Amendment - 0004.pdf PDF
36C24921B0014 0003.pdf PDF
S06- AMENDMENT2 - CO AND PROJECT CONFIRMATION DATES - 36C24921B0014 0002.pdf PDF
S02-AMENDMENT1 - 621-15-101 CORRECT ADMIN BLDG 20 ENVIRONMENT COND DEF - BID SPECIFICATIONS.pdf PDF
S02- AMENDMENT 1 - 03 1200392 VA Bldg 20 ARCH 05 13 2021 Part 1.pdf PDF
S02- AMENDMENT 1 - 06 1200392 VA Bldg 20 PLMB 05 13 2021 Part 1.pdf PDF
S06-AMENDMENT 01 - 621-15-101 - 36C24921B0014 0001 - WB.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1D.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1A.pdf PDF
05 1200392 VA Bldg 20 FIRE 05 13 2021.pdf PDF
06 1200392 VA Bldg 20 PLMB 05 13 2021 Part 2.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 2D.pdf PDF
08 1200392 VA Bldg 20 ELEC 05 13 2021.pdf PDF
07 1200392 VA Bldg 20 MECH 05 13 2021.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 2C.pdf PDF
S02-Contractor EMR Certification Form - 36C24921B0014.docx DOCX document
04 1200392 VA Bldg 20 INT 05 13 2021.pdf PDF
S02-TECHNICAL SPECS - Project 621-15-101.pdf PDF
02 1200392 VA Bldg 20 CIVIL 05 13 2021.pdf PDF
S02-621-15-101 - Correct Admin Bldg 20 .pdf PDF
01 1200392 VA Bldg 20 GEN 05 13 2021.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1B.pdf PDF
S02-WD - WASHINGTON TN - TN20210111 - JAN 2021.pdf PDF
03 1200392 VA Bldg 20 ARCH 05 13 2021 Part 2.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1C.pdf PDF
36C24921B0014.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TELECOMMUNICATIONS GENERAL NOTES:

1. EQUIPMENT (PIPING, DUCTWORK, MACHINERY, ETC) THAT DOES NOT SERVE ENTRANCE FACILITY, EQUIPMENT ROOM OR

TELECOMMUNICATIONS ROOM(S) SHALL NOT BE INSTALLED ABOVE OR IN IT SPACES, NOR SHALL THIS EQUIPMENT PASS THROUGH

OR ENTER THE ENTRANCE FACILITY, EQUIPMENT ROOM OR TELECOMMUNICATIONS ROOM(S).

2. ANY MOTOR, TRANSFORMER OR OTHER ELECTRICAL DEVICE GREATER THAN 5KVA SHALL HAVE A MINIMUM OF 47" SPACE SEPARATION FROM ANY WALL OF ENTRANCE FACILITY, EQUIPMENT ROOM OR TELECOMMUNICATIONS ROOM(S).

3. CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR TELECOMMUNICATIONS EQUIPMENT CLEARANCE FOR RECESSED

LUMINAIRES AND CORRECT ROUGH-IN LOCATIONS OF TELECOMMUNICATIONS CONNECTIONS.

4. VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND BACKSPLASH ON ARCHITECTURAL DETAILS AND/OR CASE WORK SHOP DRAWINGS AND ADJUST SPECIFIED MOUNTING HEIGHT OF WALL OUTLETS TO LOCATE BOTTOM OF OUTLET BOX 4" ABOVE TOP OF BACKSPLASH. IF NO BACKSPLASH IS USED, LOCATE BOTTOM OF OUTLET BOX 6" ABOVE COUNTERTOP.

5. REFER TO DETAILS AND RISER DIAGRAMS FOR CABLE AND CONDUIT SIZES NOT SHOWN ON PLANS.

6. "PROVIDE" IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE TELECOMMUNICATIONS SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND

SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.

7. PROVIDE WELDED WIRE TYPE CABLE TRAY IN ALL AREAS EXCEPT TELECOMMUNICATIONS ROOM(S). PROVIDE LADDER TYPE CABLE

TRAY IN TELECOMMUNICATIONS ROOM(S).

8. FLOOR BOXES AND POKE THRU'S SHALL BE SIZED TO NOT EXCEED TELECOMMUNICATIONS CABLE MINIMUM BEND RADIUS.

9. REFER TO ARCHITECTURAL PLANS FOR LOCATIONS OF RATED WALLS. FIRESTOP FIRE RATED BARRIERS IN ACCORDANCE WITH FIRESTOPPING SPECIFICATIONS 07 84 00. SLEEVES AND SLOTS SHALL NOT BE LEFT OPEN AFTER CABLE INSTALLATION. ALL SLEEVES AND SLOTS SHALL BE FIRESTOPPED IN ACCORDANCE WITH FIRESTOPPING SPECIFICATION 07 84 00.

10. PROVIDE A MINIMUM OF 12" SEPARATION BETWEEN ALL DATA OUTLETS AND ANY POWER LOAD GREATER THAN 5KVA.

11. PROVIDE 3.28’ OF CLEAR, UNOBSTRUCTED SPACE FOR THE INSTALLATION OF ALL CABLING AND EQUIPMENT MOUNTED ON WALLS, RACKS (FRONT AND REAR), CABINETS (FRONT AND REAR) AND ENCLOSURES. PROVIDE AT LEAST 6” DEPTH OFF THE WALL FOR WALL- MOUNTED EQUIPMENT. ALLOCATE SPACE OF 3.28’ WIDE, 3.28’ DEEP AND 7.5’ HIGH FOR EACH EQUIPMENT RACK, CABINET OR ENCLOSURE. PROVIDE SPACE FOR AN AISLE OF AT LEAST 3.28’ WIDE IN THE FRONT AND IN THE REAR OF THE SPACE FOR EACH EQUIPMENT RACK, CABINET OR ENCLOSURE. THIS SPACE SHALL TAKE INTO ACCOUNT THE DEPTH OF RACK-MOUNTED EQUIPMENT

AS WELL AS WALL-MOUNTED EQUIPMENT AND HARDWARE.

12. LOCATE LIGHT SWITCHES NEAR THE ENTRANCE(S) TO THE TELECOMMUNICATION ROOM. DIMMERS AND VACANCY SENSORS ARE NOT PERMITTED TO BE USED WITHIN THE TELECOMMUNICATION ROOM. PROVIDE A MINIMUM OF 50 FOOT-CANDLES OF LIGHT AT THE

POINT OF CABLE TERMINATION.

13. PROVIDE TWO RACK UNITS OF HORIZONTAL CABLE MANAGEMENT FOR EVERY ONE RACK UNIT PATCH PANEL.

14. PROVIDE AT LEAST THREE WALLS IN EACH TELECOMMUNICATION ROOM WITH AC GRADE OR BETTER, FIRE-RESISTANT VOID FREE PLYWOOD. DO NOT PAINT. THE PLYWOOD SHOULD BE 8 FT. HIGH WITH A MINIMUM THICKNESS OF 3/4”. PLYWOOD SHOULD BE KILN-

DRIED TO MAXIMUM MOISTURE CONTENT OF 15%. MOUNT PLYWOOD AT 8” AFF MINIMUM.

15. COORDINATE CABLE TRAY, LUMINAIRE AND MECHANICAL UNIT INSTALLATION WITHIN A TELECOMMUNICATION ROOM WITH ALL

TRADES PRIOR TO INSTALLATION.

16. SLEEVES OR CONDUITS ENTERING INTO THE TELECOMMUNICATION ROOM SHALL EXTEND INTO THE SPACE A MINIMUM OF 1”, MAX

3" FROM THE FLOOR, WALL OR CEILING.

17. PROVIDE A MINIMUM OF (2) 3” CONDUITS BETWEEN ALL TELECOMMUNICATION ROOMS LOCATED ON THE SAME FLOOR. PROVIDE (3) 1-1/4” INNERDUCT IN ONE OF THE CONDUITS. PROVIDE PULLSTRING IN ALL EMPTY CONDUIT AND INNERDUCT.

18. BOND ALL TELECOMMUNICATIONS MAIN GROUND BARS AND TELECOMMUNICATIONS GROUND BARS TO STRUCTURAL STEEL, ALL DATA RACKS, CABINETS OR ENCLOSURES, CABLE TRAY AND THE ELECTRICAL PANEL GROUND BUS WITHIN THE TELECOMMUNICATION ROOMS AS APPLICABLE. ALL BONDING CONDUCTORS WITHIN A TELECOMMUNICATION ROOM SHALL BE #4 AWG COPPER, UNLESS INDICATED OTHERWISE. ALL BONDS TO THE TELECOMMUNICATIONS MAIN GROUND BAR OR TELECOMMUNICATIONS GROUND BAR SHALL BE BY IRREVERSIBLE COMPRESSION-TYPE CONNECTIONS.

TELECOMMUNICATIONS ABBREVIATIONS

A OR AMP

ACS

AFF

AWG

BLDG

C

CAT

CATV

CCTV

CFCI

CU

D

DDC

EC

EF

EIA

EMT

EQUIP

ER

ETR

EXIST or EX

FWE

G OR GND

GFGI

GFCI

GRS

H or HT

HVAC

IDF

IDS

IMC

J OR JB

K

KV

KVA

KW

L

LAN

MAX

MDF

MIN

MM

N

NEC

NEMA

NFPA

NIPR

NTS

PDS

PVC

RMC

RPP

RU

SA

SIPR

SM

SPEC

TGB

TIA

TMGB

TP

TR

TYP

UIO

UL

UTP

V

VA

W

WAP

WP

AMPERE(S)

ACCESS CONTROL SYSTEM

ABOVE FINISHED FLOOR

AMERICAN WIRE GAUGE

BUILDING

CONDUIT

CATEGORY

CABLE TELEVISION

CLOSED CIRCUIT TELEVISION

CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

COPPER

DEPTH

DIRECT DIGITAL CONTROL FOR HVAC

EMPTY CONDUIT

ENTRANCE FACILITY

ELECTRONICS INDUSTRIAL ALLIANCE

ELECTRICAL METALLIC TUBING

EQUIPMENT

EQUIPMENT ROOM

EXISTING TO REMAIN

EXISTING

FURNISHED WITH EQUIPMENT

GROUND

GOVERNMENT FURNISHED GOVERNMENT

INSTALLED

GOVERNMENT FURNISHED CONTRACTOR

INSTALLED

GALVANIZED RIGID STEEL CONDUIT

HEIGHT

HEATING, VENTILATION & AIR CONDITIONING

INTERMEDIATE DISTRIBUTION FRAME

INTRUSION DETECTION SYSTEM

INTERMEDIATE METAL CONDUIT

JUNCTION BOX

KILO

KILOVOLT

KILOVOLT-AMPERES

KILOWATT

LENGTH

LOCAL AREA NETWORK

MAXIMUM

MAIN DISTRIBUTION FRAME

MINIMUM

MULTIMODE

NEUTRAL

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURER'S

ASSOCIATION

NATIONAL FIRE PROTECTION ASSOCIATION

NON-SECURE INTERNET PROTOCOL ROUTER

NOT TO SCALE

PROTECTIVE DISTRIBUTION SYSTEM

POLYVINYL CHLORIDE

RIGID METAL CONDUIT

REMOTE POWER PANEL

RACK UNIT

SURGE ARRESTOR

SECRET INTERNET PROTOCOL ROUTER

SINGLE MODE

SPECIFICATIONS

TELECOMMUNICATIONS GROUND BAR

TELECOMMUNICATIONS INDUSTRIAL ALLIANCE

TELECOMMUNICATIONS MAIN GROUND BAR

TWISTED PAIR

TELECOMMUNICATIONS ROOM

TYPICAL

UNLESS INDICATED OTHERWISE

UNDERWRITERS LABORATORY

UNSHIELDED TWISTED PAIR

VOLTS

VOLT AMPERES

WATTS or WIRE or WIDTH

WIRELESS ACCESS POINT

WEATHER PROOF

TV

COMMUNICATIONS

COAXIAL CABLE TELEVISION OUTLET WALL MOUNTED 60"

ABOVE FINISHED FLOOR, UNLESS INDICATED OTHERWISE

COMMUNICATIONS COMBINATION VOICE/DATA OUTLET (ONE

VOICE & TWO DATA JACKS) MOUNT 18" ABOVE FINISHED

FLOOR, UNLESS INDICATED OTHERWISE

COMMUNICATIONS VOICE OUTLET MOUNT 48" ABOVE FINISHED

FLOOR, UNLESS INDICATED OTHERWISE

COMMUNICATIONS DATA OUTLET, MOUNT 18" ABOVE FINISHED

FLOOR, UNLESS INDICATED OTHERWISE

CEILING MOUNT CCTV CAMERA; # IS CAMERA SUBSCRIPT;

A - FIXED DOME

B - FISH EYE

C - 270° 3-WAY MULTISENSOR

D - 360° 3-WAY MULTISENSOR

WEATHER PROOF WALL MOUNT CLOSED CIRCUIT TELEVISION

CAMERA. MOUNT 10'-0" ABOVE FINISHED GRADE, UNLESS

INDICATED OTHERWISE

FLOOR BOX SUITABLE FOR CONCRETE FLOOR POUR; TWO

COMPARTMENTS - POWER AND TELECOMMUNICATIONS;

PROVIDE 8" FIRE RATED POKE THRU ABOVE GROUND FLOOR.

PROVIDE WITH CAT 6 CABLES FED FROM OIT 205.

WIRELESS ACCESS POINT

WIRING

RACEWAY EXPOSED TO VIEW

CONCEALED RACEWAY, LOCATED IN WALL OR ABOVE

FINISHED CEILING

UNDERGROUND RACEWAY, LOCATED BELOW GRADE OR

CONCRETE SLAB

FLEXIBLE RACEWAY

RACEWAY TURNED TOWARD VIEWER

RACEWAY TURNED AWAY FROM VIEWER

RACEWAY TERMINATION, STUB-OUT AND CAP

CABLE TRAY (SIZE AND TYPE AS INDICATED)

ELECTRONIC SECURITY

ACCESS CONTROL JUNCTION BOX

BALANCED MAGNETIC DOOR CONTACT

ELECTRIC STRIKE

SEISMIC VIBRATION SENSOR

CARD READER WITH KEYPAD

ELECTRIC LOCKSET

ELECTRIC HINGE

MOTION DETECTION SENSOR

INTRUSION DETECTION SYSTEM PANEL

ACCESS CONTROL SYSTEM PANEL

INFRARED REQUEST TO EXIT

IDS KEYPAD

MAGLOCK

DOOR RELEASE

BIOMETRIC READER

HIGH SECURITY SWITCH

ELECTRIC POWER TRANSFER

TELECOMMUNICATIONS LEGEND

DC

ES

S

CR

EL

EH

M

IDS

IR

KP

ML

DR

AC

BR

HSS

ACS

EPT

WAP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

T-001

TELECOM GENERAL NOTES,

ABBREVIATIONS & LEGEND

EACTEH

NOTE:

1. NOT ALL SYMBOLS OR ABBREVIATIONS SHOWN WILL BE USED

ON THIS PROJECT.

NOTES:

1. ALL EXISTING EQUIPMENT IS SHOWN IN HALFTONE LINEWORK.

ALL DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,

DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT

IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF

EACH:

EXISTING EQUIPMENT

NEW OR RELOCATED EQUIPMENT

HATCH INDICATES EQUIPMENT TO BE DEMOLISHED

REVISIONS DATE

UP

CR

GENERAL

STORAGE

STORAGE

CLOSET

EXISTING FIBER DEMARC CLOSURE 5

EXISTING COPPER SPLICE CASE200 PAIR COPPER

200 PAIR COPPER 12MM OM1

EXISTING COPPER DEMARC4

TD-100

A4

TD-100

A1

PLAN LEGEND

AREA OF NO WORK

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

TD-100

BASEMENT TELECOMMUNICATION

DEMOLITION PLAN

EACTEH

SCALE: 3/8" = 1'-0"F1

BASEMENT TELECOMMUNICATION DEMOLITION PLAN

1. REFER TO T-001 FOR TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND.

SHEET NOTES:

1. HATCHED AREA DENOTES AREA OF DEMOLITION. DEMOLISH ALL

TELECOMMUNICATION DEVICES, CONDUIT AND WIRING BACK TO SOURCE, UIO.

2. OSP COPPER AND FIBER COMMUNICATIONS CABLING ENTRANCE POINT.

3. EXISTING ACCESS CONTROL DEVICE TO BE SALVAGED AND RE-INSTALLED IN THE

SAME LOCATION. REFER TO T-110 FOR NEW WORK.

4. EXISTING COPPER DEMARC AND DISTRIBUTION TO REMAIN.RETAIN EQUIPMENT AND

50 PAIR DISTRIBUTION TO BUILDING 42.

5. EXISTING 12MM OM1 FIBER AND DEMARC TO REMAIN. RETAIN EQUIPMENT AND

DISTRIBUTION TO BUILDING 115.

KEYNOTES:

SCALE: = 1'-0"3/8"

0 2 4 62

SCALE: N.T.S.A1

EXISTING COPPER PET AND DEMARC CLOSURE

SCALE: N.T.S.A4

EXISTING FIBER DEMARC CLOSURE

DN

DN

DN

DN

DN

WAP

WAP

WAP

WAP

WAP

WAP

WAP

CR

WAP

CR

OFFICE OFFICE

STORAGE

TOILET

COPY RM OFFICE OFFICE OFFICE

HSK

OFFICE

OFFICEOFFICE

RECEPTION

OFFICEOFFICE

STORAGE

EQUIP RM

CORRIDOR

LOBBY

CORRIDOR CORRIDOR

107106 109 111 112 113

116117

103104

101A

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

TD-101

FIRST FLOOR TELECOMMUNICATION

DEMOLITION PLAN

EACTEH

1. REFER TO T-001 FOR TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND.

SHEET NOTES:

1. HATCHED AREA DENOTES AREA OF DEMOLITION. DEMOLISH ALL

TELECOMMUNICATION DEVICES, CONDUIT AND WIRING BACK TO SOURCE, UIO.

2. EXISTING WIRELESS ACCESS POINT TO BE SALVAGED AND REINSTALLED IN SAME

LOCATION. DEMOLISH CAT 6 CABLING AND CONDUIT BACK TO SOURCE.

3. EXISTING ACCESS CONTROL DEVICE TO BE SALVAGED AND RE-INSTALLED IN NEW

DOOR. REFER TO T-111 FOR NEW WORK.

KEYNOTES:

SCALE: 3/8" = 1'-0"F1

FIRST FLOOR TELECOMMUNICATION DEMOLITION PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

OFFICE

CLOSET

CONFERENCE RM

KITCHEN

OFFICE

CLOSET

CORRIDOR

LOBBY

CORRIDOR

STORAGE

TOILET

OFFICE OFFICE OFFICE OFFICE

OFFICEOFFICEMECH RM

HSK

204A

203A

206 208 209 210

211212213

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

TD-102

SECOND FLOOR

TELECOMMUNICATION DEMOLITION

PLAN

EACTEH

1. REFER TO T-001 FOR TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND.

SHEET NOTES:

1. HATCHED AREA DENOTES AREA OF DEMOLITION. DEMOLISH ALL

TELECOMMUNICATION DEVICES, CONDUIT AND WIRING BACK TO SOURCE, UIO.

2. EXISTING WIRELESS ACCESS POINT TO BE SALVAGED AND REINSTALLED IN SAME

LOCATION. DEMOLISH CAT 6 CABLING AND CONDUIT BACK TO SOURCE.

KEYNOTES:

SCALE: 3/8" = 1'-0"F1

SECOND FLOOR TELECOMMUNICATION DEMOLITION PLAN

SCALE: = 1'-0"3/8"

ARMORY /

WEAPONS

B04

STORAGE

B02

MECHANICAL

ROOM

B01

CORRIDOR

B03

CORRIDOR

B00

EXISTING COPPER SPLICE CASE

EXISTING COPPER DEMARC

EXISTING FIBER DEMARC CLOSURE

PLAN LEGEND

AREA OF NO WORK

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

T-100

BASEMENT TELECOMMUNICATION

PLAN

EACTEH

SCALE: 3/8" = 1'-0"F1

BASEMENT TELECOMMUNICATION PLAN

1. REFER TO T-001 FOR TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. ALL WIRING/CABLING AND OTHER TELECOM/DATA DEVICES SHALL BE PROVIDED BY

TELECOM/DATA CONTRACTOR. GENERAL CONTRACTOR SHALL VERIFY LOCATIONS

OF DEVICES AND PROVIDE NECESSARY ROUGH-INS.

3. COORDINATE HEIGHT AND LOCATION OF DATA OUTLETS AND CABLE BOXES WITH

ARCHITECTURAL DRAWINGS. FIELD VERIFY PRIOR TO INSTALLATION.

SHEET NOTES:

1. APPROXIMATE OSP COMMUNICATIONS ENTRANCE POINT.

2. TELECOMMUNICATIONS MAIN GROUND BAR (TMGB). SEE F8/T-501 FOR DETAILS.

3. 3/4'', AC GRADE, FIRE RATED PLYWOOD BACKBOARD SHALL BE EIGHT FEET HIGH

WITH BOTTOM OF PLYWOOD MOUNTED 6'' AFF, WITH A GRADE SIDE FACING ROOM.

FIRE RATING STAMP SHALL NOT BE COVERED BY PAINT.

4. 3'' SELF-SEALING, RE-ENTERABLE, MECHANICAL FIRE-STOPPING WALL SLEEVES.

(TYPICAL FOR 3).

5. ROUTE (3) 3" CONDUITS FOR BACKBONE CABLING AND BASEMENT HORIZONTAL

DISTRIBUTION UP SHAFT AND THEN TO OIT ROOM 205.

6. 6RU WALL MOUNTED TELECOM CABINET.

KEYNOTES:

SCALE: = 1'-0"3/8"

WAP

WAP

WAP

WAP

T V T V

WAP

J

WAP

+60" +60"

OFFICE

STAFF

LOUNGE

OFFICE

OFFICE

OFFICE

RECEPTION

OFFICE

EVIDENCE

ROOM

INTERVIEW

ROOM

EVIDENCE

PROCESSING

MEN

RESTROOM

OFFICER

WORK

ROOM

CORRIDOR

WOMEN

RESTROOM

HOUSE

KEEPING

WAITING

ROOM

WP

ELECT.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

T-101

FIRST FLOOR TELECOMMUNICATION

PLAN

EACTEH

1. REFER TO T-001 FOR TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. ALL WIRING/CABLING AND OTHER TELECOM/DATA DEVICES SHALL BE PROVIDED BY

TELECOM/DATA CONTRACTOR. GENERAL CONTRACTOR SHALL VERIFY LOCATIONS

OF DEVICES AND PROVIDE NECESSARY ROUGH-INS.

3. COORDINATE HEIGHT AND LOCATION OF DATA OUTLETS AND CABLE BOXES WITH

ARCHITECTURAL DRAWINGS. FIELD VERIFY PRIOR TO INSTALLATION.

SHEET NOTES:

1. RE-INSTALL WAP PREVIOUSLY REMOVED FROM THIS SPACE.

2. 4" X 12" WELDED WIRE CABLE TRAY. MOUNT AT 8'-10" AFF.

3. 3'' SELF-SEALING, RE-ENTERABLE, MECHANICAL FIRE-STOPPING FLOOR SLEEVES

BETWEEN FIRST AND SECOND FLOOR. (TYPICAL FOR 2).

4. (3) 3" CONDUITS, FOR BACKBONE CABLING AND BASEMENT HORIZONTAL

DISTRIBUTION, FROM BASEMENT TO SECOND FLOOR. REFER TO T-601.

5. PROVIDE STAINLESS STEEL FACE PLATE WITH TAMPER RESISTANT SCREWS ON

DATA OUTLET.

6. EXTEND HORIZONTAL DISTRIBUTION CABLING FOR FIRST FLOOR ABOVE CEILING

FROM OIT 205 FLOOR SLEEVES TO CABLE TRAY IN CORRIDOR VIA J-HOOKS. REFER

TO T-601.

KEYNOTES:

SCALE: 3/8" = 1'-0"F1

FIRST FLOOR TELECOMMUNICATION PLAN

SCALE: = 1'-0"3/8"

WAP

WAP

WAP

WAP

WAP

T V

WAP

TV

WAP

T-401

F5

+60"

+60"

DEPUTY

CHIEF

OFFICE

OIT

WOMEN

RESTROOM

WOMEN

SHOWER &

LOCKER

ROOM

206A

MEN

SHOWER &

LOCKER

ROOM

MEN

RESTROOM

OFFICE

OFFICE

CORRIDOR

CORRIDOR

CORRIDOR

CONFERENCE

ROOM

CHIEF

OFFICE

LOBBY

MECHANICAL

ROOM

HOUSE

KEEPING

OFFICE

OFFICE

ELECT.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

T-102

SECOND FLOOR

TELECOMMUNICATION PLAN

EACTEH

1. REFER TO T-001 FOR TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. ALL WIRING/CABLING AND OTHER TELECOM/DATA DEVICES SHALL BE PROVIDED BY

TELECOM/DATA CONTRACTOR. GENERAL CONTRACTOR SHALL VERIFY LOCATIONS

OF DEVICES AND PROVIDE NECESSARY ROUGH-INS.

3. COORDINATE HEIGHT AND LOCATION OF DATA OUTLETS AND CABLE BOXES WITH

ARCHITECTURAL DRAWINGS. FIELD VERIFY PRIOR TO INSTALLATION.

SHEET NOTES:

1. RE-INSTALL WAP PREVIOUSLY REMOVED FROM THIS SPACE.

2. ELECTRICAL CONTRACTOR SHALL CONFIRM FINAL LOCATION AND STYLE OF POWER

AND DATA POKE-THRU DEVICE WITH FURNITURE VENDOR PRIOR TO INSTALLATION.

3. 4" X 12" WELDED WIRE CABLE TRAY. MOUNT AT 8'-10" AFF.

4. CONDUIT FROM BASEMENT LEVEL. REFER TO T-601. EXTEND CONDUITS OVERHEAD

TO CABLE TRAY IN CORRIDOR.

KEYNOTES:

SCALE: 3/8" = 1'-0"F1

SECOND FLOOR TELECOMMUNICATION PLAN

SCALE: = 1'-0"3/8"

ES

ES

HSS

M

CR

KP

CR

D T-502

F7

TYP.

B04

ARMORY /

WEAPONS

B04

CORRIDOR

B00

MECHANICAL

ROOM

B01

STORAGE

B02

CORRIDOR

B03

A

WP

001A

PLAN LEGEND

AREA OF NO WORK

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

T-110

BASEMENT SECURITY PLAN

EACTEH

SCALE: 3/8" = 1'-0"F1

BASEMENT SECURITY PLAN

1. REFER TO T-001 FOR TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. COORDINATE HEIGHT AND LOCATION OF DATA OUTLETS AND CABLE BOXES WITH

ARCHITECTURAL DRAWINGS. FIELD VERIFY PRIOR TO INSTALLATION.

3. SEE C7/T-502 FOR ACCESS CONTROL RISER.

4. SEE C1/T-502 FOR CCTV RISER.

5. SEE C5/T-502 FOR IDS RISER.

6. NEW DEVICES SHOWN ON THIS PLAN INDICATE LOCATIONS ONLY FOR GFGI

EQUIPMENT. REFER TO E-502 FOR SYSTEM RISER.

SHEET NOTES:

SCALE: = 1'-0"3/8"

0 2 4 62

1. GFGI IDS PANEL.

2. RE-INSTALL ACCESS CONTROL DEVICE PREVIOUSLY REMOVED FROM THIS SPACE.

3. SURFACE MOUNT WEATHER PROOF CCTV CAMERA UNDER AWNING. SEE D1/T-501

FOR MOUNTING DETAIL.

KEYNOTES:

ML ML

ES

ES

ES

ES

ES

IR

CR

CR

CR

CR

CR

CR

CR

B

B

B

T-502

F1

TYP.

T-502

F7

TYP.

OFFICE

OFFICE

WOMEN

RESTROOM

STAFF

LOUNGE

MEN

RESTROOM

OFFICER

WORK

ROOM

INTERVIEW

ROOM

EVIDENCE

PROCESSING

EVIDENCE

ROOM

OFFICE

HOUSE

KEEPING

CORRIDOR

RECEPTION

OFFICE

OFFICE

CORRIDOR

WAITING

ROOM

ELECT.

105 112A 112B

109B

3 4

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

T-111

FIRST FLOOR SECURITY PLAN

EACTEH

1. REFER TO T-001 FOR TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. COORDINATE HEIGHT AND LOCATION OF DATA OUTLETS AND CABLE BOXES WITH

ARCHITECTURAL DRAWINGS. FIELD VERIFY PRIOR TO INSTALLATION.

3. SEE C6/T-502 FOR ACCESS CONTROL RISER.

4. SEE C1/T-502 FOR CCTV RISER.

5. NEW DEVICES SHOWN ON THIS PLAN INDICATE LOCATIONS ONLY FOR GFGI

EQUIPMENT. REFER TO E-502 FOR SYSTEM RISER.

SHEET NOTES:

SCALE: 3/8" = 1'-0"F1

FIRST FLOOR SECURITY PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

1. CCTV MONITOR AND DESKTOP CCTV CONTROLS. COORDINATE EXACT LOCATION

REQUIRED WITH COR PRIOR TO INSTALLATION.

2. RE-INSTALL ACCESS CONTROL DEVICE PREVIOUSLY REMOVED FROM THIS SPACE.

3. ACCESS CONTROL DEVICE SHALL BE INSTALLED IN SINGLED GANG JUNCTION BOX

RECESSED IN BRICK. CUT, PATCH, AND REPAIR BRICK AS REQUIRED.

4. REFER TO F1/T-501 FOR SECURITY CAMERA WALL MOUNTING DETAIL. BASIS OF

DESIGN: BOSCH #VGA-PEND-ARM WITH #VGA-PEND-WPLATE.

CR

CR

CR

ES

B

T-502

F7

TYP.

DEPUTY

CHIEF

OFFICE

OIT

CONFERENCE

ROOM

CORRIDOR

CHIEF

OFFICE

LOBBY

MECHANICAL

ROOM

OFFICE

OFFICE

CORRIDOR

OFFICE

209MEN

RESTROOM

MEN

SHOWER &

LOCKER

ROOM

207 OFFICE

WOMEN

SHOWER &

LOCKER

ROOM

206A

CORRIDOR

ELECT.

HOUSE

KEEPING

WOMEN

RESTROOM

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

T-112

SECOND FLOOR SECURITY PLAN

EACTEH

SCALE: 3/8" = 1'-0"F1

SECOND FLOOR SECURITY PLAN

1. REFER TO T-001 FOR TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. COORDINATE HEIGHT AND FINAL LOCATION OF DATA OUTLETS AND CABLE BOXES

WITH ARCHITECTURAL DRAWINGS AND OWNER. FIELD VERIFY PRIOR TO

INSTALLATION.

3. SEE C6/T-502 FOR ACCESS CONTROL RISER.

4. SEE C1/T-502 FOR CCTV RISER.

5. NEW DEVICES SHOWN ON THIS PLAN INDICATE LOCATIONS ONLY FOR GFGI

EQUIPMENT. REFER TO E-502 FOR SYSTEM RISER.

SHEET NOTES:

SCALE: = 1'-0"3/8"

0 2 4 62

REVISIONS DATE

1. ACCESS CONTROL DEVICE SHALL BE INSTALLED IN SINGLED GANG JUNCTION BOX

RECESSED IN BRICK. CUT, PATCH, AND REPAIR BRICK AS REQUIRED.

2. REFER TO F1/T-501 FOR SECURITY CAMERA WALL MOUNTING DETAIL. BASIS OF

DESIGN: BOSCH #VGA-PEND-ARM WITH #VGA-PEND-WPLATE.

FRONT

0' - 6"

FRONT

OIT

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

T-401

ENLARGED SECOND FLOOR

TELECOMMUNICATION ROOM

EACTEH

SCALE: 1" = 1'-0"F5

ENLARGED SECOND FLOOR TELECOMMUNICATION ROOM

1. REFER TO T-001 FOR TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. ALL WIRING/CABLING AND OTHER TELECOM/DATA DEVICES SHALL BE PROVIDED

BY TELECOM/DATA CONTRACTOR. GENERAL CONTRACTOR SHALL VERIFY

LOCATIONS OF DEVICES AND PROVIDE NECESSARY ROUGH-INS.

3. COORDINATE HEIGHT AND LOCATION OF DATA OUTLETS AND CABLE BOXES WITH

ARCHITECTURAL DRAWINGS. FIELD VERIFY PRIOR TO INSTALLATION.

SHEET NOTES:

1. TELECOMMUNICATIONS GROUND BAR (TGB). SEE F8/T-501 FOR DETAILS.

2. 3/4'', AC GRADE, FIRE RATED PLYWOOD BACKBOARD SHALL BE EIGHT FEET HIGH

WITH BOTTOM OF PLYWOOD MOUNTED 6'' AFF, WITH A GRADE SIDE FACING ROOM.

FIRE RATING STAMP SHALL NOT BE COVERED BY PAINT. TYPICAL FOR TWO

ADJACENT WALLS IN ROOM.

3. 3'' SELF-SEALING, RE-ENTERABLE, MECHANICAL FIRE-STOPPING FLOOR SLEEVES

FOR HORIZONTAL DISTRIBUTION CABLING FOR FLOOR BELOW, (TYPICAL FOR 2).

4. 12'' W X 4" H HORIZONTAL LADDER RACK CABLE TRAY. MOUNT AT 9'-0'' AFF. FASTEN

TO WALLS WITH HORIZONTAL SUPPORT BRACKETS.

5. TWO POST 19'' RACK.

6. GFGI CCTV HEADEND EQUIPMENT.

7. GFGI ACCESS CONTROL PANEL.

KEYNOTES:

SCALE: = 1'-0"

0 1 21

1"

MOUNT CONDUIT TO CABLE TRAY

OR 'J-HOOKS' WHERE PERMITTED.

MINIMUM 1" EMT CONDUIT

STUB-OUT TO CABLE TRAY.

ROUTE CABLE TO TR. ROOM.

SINGLE OR DOUBLE

GANG EXTENSION.

CONDUIT AND CABLE TRAY

CONNECTED BY BONDING

JUMPER

CABLE PATHWAY HOME

RUN TO TR. SEE FLOOR

PLANS FOR ROUTING.

(NOTE 4)

4" X 4" DEEP SET

JUNCTION BOX

1. MOUNT JUNCTION BOX SAME HEIGHT AS ELECTRICAL

OUTLET, UIO.

2. OUTLET CONFIGURATION SHALL BE AS INDICATED ON

PLANS.

3. OUTLETS TO BE LABELED IN ACCORDANCE WITH

TIA/EIA 606-A.

4. PROVIDE GROUNDING JUMPER AT EACH CABLE TRAY

MECHANICAL JOINT.

5. PROVIDE POWER OUTLET WITHIN 12" OF

COMMUNICATIONS OUTLET.

6. MAXIMUM DISTANCE FROM CONDUIT TO CABLE TRAY

SHALL BE 6".

NOTES:

L121-112

CABLE LABEL

(TYP)

JACK LABEL

(TYP)

L121-112 L121-111 L121-111

THREE CAT 6 - 1"C TO

CLOSEST CABLE TRAY

L121-113

L121-113

JACK COLOR:

• BLUE

JACK COLOR:

• RED

JACK COLOR:

• WHITE

RG 6 - 1"C TO

IN COMM ROOM VIA

CABLE TRAY

532-1

JACK LABEL

(ROOM#-

JACK#)

TV

532-3B-46

532-3B-46

ONE CAT 6 - 1"C TO

CLOSEST CABLE TRAY

CABLE LABEL

(TYP)

WALL PHONE MOUNTING STUD

(TYPICAL FOR 2)

JACK LABEL

(TYP)

COAXIAL TYPE F CONNECTOR

8 PIN / 8 POSITION, CATEGORY 6

UNKEYED, T568A PIN OUT ANGLED JACK

BLANK PLUG IN FACEPLATE PORT

JACK COLOR & JACKET COLOR

VOIP = WHITE

DATA = BLUE

APS = RED

WAP = GREEN

OUTLET JACK, PATCH PANEL JACK, AND CABLE LABELING

aaa - bc - dd aaa = ROOM NUMBER b = RACK NUMBER c = PATCH PANEL ID d = PORT NUMBER

IE: 532-3B-46 = ROOM 532, RACK 3, PATCH PANEL B, PORT 46

TYPICAL TMGB DRILLED HOLE DIMENSIONS

TYPICAL TGB DRILLED HOLE DIMENSIONS

2-HOLE LUG

COMPRESSION

CONNECTOR

1 1/2" NOMINAL

INSULATOR

STAINLESS STEEL

STANDOFF BRACKET

ELECTRO-TIN PLATED

COPPER GROUND BAR

STAINLESS STEEL HARDWARE

TYPE

TMGB

TGB

20"

20"

WIDTH

4"

2"

THICKNESS

1/4"

1/4"

MINIMUM

LENGTH

MINIMUM NUMBER OF

PAIRS OF 5/16"

DIAMETER HOLES

MINIMUM NUMBER OF

PAIRS OF 7/16"

DIAMETER HOLES

TELECOMMUNICATIONS MAIN GROUND BAR (TMGB) &

TELECOMMUNICATIONS GROUND BAR (TGB) SCHEDULE ANSI-J-STD-A-2002

5/16" DIAMETER HOLE PAIR (TYP)

7/16" DIAMETER HOLE PAIR (TYP)

2"

5/8".

1 1/8" TYP

1 1/8" TYP

5/16" DIAMETER HOLE PAIR (TYP)

7/16" DIAMETER HOLE PAIR (TYP)

5/8".

5/8".

1".

21 3

5 6

STORAGE BO2

OIT 205

NOTES:

1. EXISTING TO REMAIN OSP 12 STRAND MM FIBER OPTIC CABLE

FROM BUILDING 200.

2. EXISTING TO REMAIN OSP 100 PAIR COPPER BACKBONE CABLE

FROM BUILDING 200.

3. EXISTING TO REMAIN OSP 62.5 OM1 MM FIBER OPTIC CABLE

FROM BUILDING 200 TO BUILDING 115.

4. EXISTING TO REMAIN 50 PAIR COPPER BACKBONE CABLE FROM

BUILDING 200 TO BUILDING 42.

5. NEW 12 STRAND MM FIBER OPTIC CABLE.

6. NEW 100 PAIR COPPER BACKBONE CABLE.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

T-501

TELECOMMUNICATION DETAILS

EACTEH

SCALE: N.T.S.C8

WALL MOUNT COMMUNICATIONS OUTLET DETAIL

SCALE: N.T.S.F4

TYPICAL OUTLET

SCALE: N.T.S.F6

TYPICAL TV OUTLET

SCALE: N.T.S.D4

TYPICAL TELEPHONE OUTLET

SCALE: N.T.S.D6

JACK TYPES

SCALE: N.T.S.C4

LABELING AND COLOR CODING

SCALE: N.T.S.F8

TELECOMMUNICATIONS TGB & TMGB GROUND BAR DETAIL

1. REFER TO T-001 FOR TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND.

SHEET NOTES:

SCALE: N.T.S.C6

BACKBONE CABLE RISER DIAGRAM

REVISIONS DATE

SCALE: N.T.S.F1

SECURITY CAMERA (WALL MOUNTING DETAIL)

SCALE: N.T.S.D1

SECURITY CAMERA (DOME MOUNTING DETAIL)

FLOOR

EXTERIOR (NON-SECURE SIDE)

DOOR DETAIL

INTERIOR (SECURE SIDE)

DOOR DETAIL

CR

CEILING

HSS HSS

AC

IR

AC

ML ML

NOTE: NOT ALL DEVICES SHOWN ARE REQUIRED FOR EVERY DOOR. REFER TO T-110,

T-111, AND T-112 FOR INDIVIDUAL DOOR REQUIREMENTS.

PROVIDE 1-1/2"C. WITH PULLSTRING

FOR GFGI ACS CABLING

4"X4" JUNCTION BOX ABOVE

CEILING. JUNCTION BOX

SHALL BE LOCATED ON THE

SECURE SIDE OF THE DOOR.

PROVIDE 3/4"C. WITH

PULLSTRING FOR GFGI

ACS CABLING

SINGLE GANG BOX.

JUNCTION BOXES

SHALL BE LOCATED ON

THE SECURE SIDE OF

THE DOOR.

4"X4" JUNCTION BOX ABOVE

CEILING. JUNCTION BOX

SHALL BE LOCATED ON THE

SECURE SIDE OF THE DOOR.

PROVIDE 3/4"C. WITH

PULLSTRING FOR GFGI ACS

CABLING. ROUTE CONDUIT

CONCEALED IN THE WALL.

4" SQUARE, 2-5/8" DEEP

SINGE GANG (DEVICE).

LOCATE ADJACENT TO

THE DOOR FRAME.

FLOOR

EXTERIOR (NON-SECURE

SIDE) DOOR DETAIL

INTERIOR (SECURE SIDE)

DOOR DETAIL

CR

CEILING

AC

AC

NOTE: NOT ALL DEVICES SHOWN ARE REQUIRED FOR EVERY DOOR. REFER TO T-110,

T-111, AND T-112 FOR INDIVIDUAL DOOR REQUIREMENTS.

PROVIDE 1-1/2"C. WITH PULLSTRING

FOR GFGI ACS CABLING

4"X4" JUNCTION BOX ABOVE

CEILING. JUNCTION BOX

SHALL BE LOCATED ON THE

SECURE SIDE OF THE DOOR.

4"X4" JUNCTION BOX ABOVE

CEILING. JUNCTION BOX

SHALL BE LOCATED ON THE

SECURE SIDE OF THE DOOR.

PROVIDE 3/4"C. WITH

PULLSTRING FOR GFGI ACS

CABLING. ROUTE CONDUIT

CONCEALED IN THE WALL.

4" SQUARE, 2-5/8" DEEP

SINGE GANG (DEVICE).

LOCATE ADJACENT TO

THE DOOR HANDLE.

PROVIDE 3/4"C. WITH

PULLSTRING FOR GFGI

ACS CABLING

HSS

SINGLE GANG BOX.

JUNCTION BOXES

SHALL BE LOCATED ON

THE SECURE SIDE OF

THE DOOR.

ES

2ND FLOOR

1ST FLOOR

ACSP

OIT

BASEMENT

120VAC

J

JJ

J

J

CR

LOBBY

DOOR 200

ES

J

J

J

J

CR

ARMORY / WEAPONS

B04

DOOR B04

ES

J

J

CR ES

CORRIDOR

B00

DOOR 001A

J

J

CR

WAITING ROOM

DOOR 100

MLML

J

J

J

J

CR

EVIDENCE ROOM

DOOR 114

ES

J

J

CR

OFFICER WORK ROOM

DOOR 112A

ES

J

J

CR ES

ELECT.

DOOR 101

J

J

CR ES

CORRIDOR

DOOR 105

J

J

CR ES

STAFF LOUNGE

DOOR 109B

J

J

CR

CORRIDOR

DOOR 215

ES

J

J

CR ES

OIT

DOOR 205

J

J

CR

OFFICER WORK ROOM

DOOR 112B

ES

IR

KEYNOTES (THIS DETAIL):

1. 1"C WITH PULL STRING TO OIT 205 FOR GFGI CABLING.

2. ALL DEVICES AND EQUIPMENT ARE GFGI.

EXISTING

GFGI

CCTV VIDEO

MATRIX SWITCHER

GFGI

DESKTOP MOUNTED MONITOR

RECEPTION 102

GFGI

DESKTOP CCTV CONTROL

RECEPTION 102

GFGI

DVR

GFGI

UPS

120VAC

SURGE

STRIP

19" EQUIPMENT WALL MOUNT CABINET,

WITH SWING RACK.

LOCATE IN OIT ROOM 205

CAM 4

CAM 3

CAM 2

CAM 1EXTERIOR

CORRIDOR DOOR 001A

INTERIOR

CORRIDOR B00

INTERIOR

WAITING ROOM 100

INTERIOR

EVIDENCE PROCESSING

ROOM 115

CAM 5INTERIOR

INTERVIEW ROOM 113

MM FIBER OPTIC

PATCH PANEL

IN OIT

ROOM 205

INTERIOR

LOBBY 200

EXTERIOR

DOOR 109B

CAM 7

CAM 8

EXTERIOR

DOOR 112B

CAM 6

EXTERIOR

DOOR 214

CAM 9

TO TGB

KEYNOTES (THIS DETAIL):

1. COORDINATE EXACT LOCATION REQUIRED WITH COR PRIOR TO INSTALLATION.

2. 1"C WITH PULLSTRING FOR GFGI CABLING.

3. 1"C FOR GFGI 12 STRAND MM FIBER OPTIC CABLE.

4. ALL CAMERAS AND EQUIPMENT ARE GFGI.

#6G

CAM 10

EXTERIOR

DOOR 100

120VAC

DOOR

B04

MAIN

IDS

PANEL

J

KP

J

HSSM

ARMORY/

WEAPONS

B04

ARMORY/

WEAPONS

B04

KEYNOTES (THIS DETAIL):

1. 1"C WITH PULL STRING TO OIT 205 FOR GFGI CABLING.

2. ALL DEVICES AND EQUIPMENT ARE GFGI.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

T-502

SECURITY DETAILS

EACTEH

SCALE: N.T.S.F1

DOUBLE DOOR SECURITY DETAIL

SCALE: N.T.S.F7

SINGLE DOOR SECURITY DETAIL

SCALE: N.T.S.C7

ACCESS CONTROL RISER DIAGRAM

1. REFER TO T-001 FOR TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND.

SHEET NOTES:

SCALE: N.T.S.C1

CCTV RISER DIAGRAM

SCALE: N.T.S.C5

IDS RISER DIAGRAM

OIT ROOM 205

U

IO

U

IO

(TYP.)

(TYP.)

(TYP.)

TGB

G

G

G

#6G

TYP.

X

TYP. FOR 2

TV

J

WAP

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

1 3 5 7 9 11

2 4 6 8 10 12

13 15 17 19 21 23

14 16 18 20 22 24

25 27 29 31 33 35

26 28 30 32 34 36

37 39 41 43 45 47

38 40 42 44 46 48 49 51 53 55 57 59

50 52 54 56 58 60

61 63 65 67 69 71

62 64 66 68 70 72

73 75 77 79 81 83

74 76 78 80 82 84

85 87 89 91 93 95

86 88 90 92 94 96

TYP.

FOR 6

4 29 16

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

U

IO

TYP.

FOR 3

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

TYP.

FOR 5

TYP.

FOR 6

#6G

TYP.

SECOND FLOOR

FIRST FLOOR

BASEMENT

27 28

TMGB

G

(TYP.)24

U

IO

U

IO

U

IO

(TYP.)

(TYP.)

(TYP.)

TV

J

WAP

4 29 16

U

IO

(TYP.)24

U

IO

U

IO

(TYP.)1

(TYP.)

#6G

32 (TYP.)

CEILING

CEILING

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

#4/0G

#4/0G

#6G

CORRIDOR 217

ELECT. 202

ELECT. 101

STORAGE B02

EXISTING

COPPER DEMARC

CLOSURE

PET

1 2 3 4

25 26 27 28

5 6 7 8

29 30 31 32

9 10 11 12

33 34 35 36

13 14 15 16

37 38 39 40

17 18 19 20

41 42 43 44

21 22 23 24

45 46 47 48

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

T-601

TELECOMMUNICATION RISER

DIAGRAM

EACTEH

SHEET NOTES:

1. REFER TO T-001 FOR TELECOMMUNICATIONS GENERAL NOTES, ABBREVIATIONS

& LEGEND.

KEYNOTES:

1. TELECOMMUNICATION OUTLET (THREE CATEGORY 6, 8-PIN, 8-CONDUCTOR

UNKEYED ANGLED JACKS).

2. TELECOMMUNICATION OUTLET (ONE CATEGORY 6, 8-PIN, 8-CONDUCTOR UNKEYED

JACK).

3. TWO CATEGORY 6 UTP CABLE - 1" EMT CONDUIT.

4. ONE CATEGORY 6 UTP CABLE - 1" EMT CONDUIT.

5. 48 PORT CATEGORY 6 PATCH PANEL FOR HORIZONTAL VOICE AND DATA

DISTRIBUTION.

6. 1/4" x 5/8" x 72" COPPER VERTICAL RACK GROUND BAR, PREDRILLED WITH (26) 1/4"

TAPPED HOLES.

7. 2 POST EQUIPMENT RACK, 19" EIA RAILS, 45U SPACE, 21" WIDE.

8. WELDED WIRE CABLE TRAY, SIZE AS NOTED ON PLANS.

9. PROVIDE AT LEAST TWO WALLS IN EACH TELECOMMUNICATION ROOM WITH AC

GRADE OR BETTER, FIRE-RESISTANT VOID FREE PLYWOOD. DO NOT PAINT. THE

PLYWOOD SHOULD BE 8 FT. HIGH WITH A MINIMUM THICKNESS OF 3/4". PLYWOOD

SHOULD BE KILN-DRIED TO MAXIMUM MOISTURE CONTENT OF 15%. MOUNT

PLYWOOD AT 8"AFF MINIMUM.

10. TELECOMMUNICATIONS GROUNDING BUSBAR.

11. DOUBLE SIDED VERTICAL CABLE MANAGERS WITH DOORS. 7"H x 6"W x 20"D WITH

GUIDE FINGERS AT 1 RU INTERVALS IN FRONT AND BACK.

12. PROVIDE (1) NEMA 5-20R DOUBLE-DUPLEX ON WALL BEHIND EACH RACK.

13. 100 PAIR WALL MOUNTED 110 BLOCK.

14. HORIZONTAL CABLE MANAGERS 2RU.

15. EXISTING 150 PAIR PROTECTED ENTRANCE TERMINALS (PET) AND SPLICE

CHAMBER. INTERCEPT EXISTING 100PR COPPER BACKBONE CABLING AND

EXTEND TO OIT 205.

16. RG-6 CABLE - 1" EMT CONDUIT.

17. BOND TO CLOSEST STRUCTURAL STEEL.

18. COAXIAL, TYPE F CATV OUTLET. HEIGHT AS NOTED.

19. 20' MAINTENANCE LOOP.

20. 48 PORT CATEGORY 6 PATCH PANEL FOR VOICE CABLE PATCHING.

21. LADDER RACK CABLE TRAY SIZE AS NOTED ON PLANS.

22. 12-STRAND MM FIBER OPTIC CABLING FROM DEMARC TO GFGI ACTIVE NETWORK

EQUIPMENT IN OIT 205.

23. GFGI ACTIVE NETWORK EQUIPMENT.

24. TELECOMMUNICATION DATA OUTLET (ONE CATEGORY 6, 8-PIN, 8-CONDUCTOR

UNKEYED JACK).

25. MOUNT OUTLET ON CEILING OR WALL. REFER TO PLANS FOR LOCATIONS.

26. 100 PAIR CU

27. EXISTING OSP COPPER BACKBONE CABLING FROM BUILDING 77.

28. EXISTING OSP FIBER CABLING FROM BUILDING 200.

29. THREE CATEGORY 6 UTP CABLE - 1" EMT CONDUIT.

30. EXISTING WALL MOUNTED FIBER OPTIC DEMARC CLOSURE.

31. 48-PORT CATEGORY 6 PATCH PANEL FOR HORIZONTAL DISTRIBUTION.

32. CATEGORY 6 CABLE J-HOOK.

33. 3" EMT CONDUIT.

34. FIRE RATED POKE THROUGH MULTI-COMPARTMENT FLOOR BOX.

35. FOUR CATEGORY 6 UTP CABLE - 1' EMT CONDUIT.

36. EXISTING 50 PAIR COPPER TO BUILDING 42.

37. 3'' SELF-SEALING, RE-ENTERABLE, MECHANICAL FIRE-STOPPING FLOOR SLEEVES.

38. 6RU WALL MOUNTED TELECOM CABINET.

39. BOND TO NEW ELECTRICAL MGB.

40. BOND TO TMGB IN STORAGE B02.

SCALE: N.T.S.F1

TELECOMMUNICATIONS RISER DIAGRAM

Sheets
T-001 - TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND
TD-100 - BASEMENT TELECOMMUNICATION DEMOLITION PLAN
TD-101 - FIRST FLOOR TELECOMMUNICATION DEMOLITION PLAN
TD-102 - SECOND FLOOR TELECOMMUNICATION DEMOLITION PLAN
T-100 - BASEMENT TELECOMMUNICATION PLAN
T-101 - FIRST FLOOR TELECOMMUNICATION PLAN
T-102 - SECOND FLOOR TELECOMMUNICATION PLAN
T-110 - BASEMENT SECURITY PLAN
T-111 - FIRST FLOOR SECURITY PLAN
T-112 - SECOND FLOOR SECURITY PLAN
T-401 - ENLARGED SECOND FLOOR TELECOMMUNICATION ROOM
T-501 - TELECOMMUNICATION DETAILS
T-502 - SECURITY DETAILS
T-601 - TELECOMMUNICATION RISER DIAGRAM