This presolicitation notice is for a construction project to correct environment and condition deficiencies at the Administration Building 20 at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The project scope includes reconstructing space for police staff with new offices, a conference room, observation room, interview room, evidence room, locker rooms, storage, electrical and mechanical rooms, an armory, lounge areas, waiting and reception areas, restrooms, corridors and circulation areas. Work will also include demolishing existing structures and materials. The estimated value is between $1 million to $5 million. The requirement will use NAICS code 236220 and be set aside 100% for Service-Disabled Veteran Owned Small Businesses. The solicitation is expected to post on October 20, 2021 and close on November 20, 2021, following FAR Part 14.1 sealed bidding procedures. Questions must be submitted in writing by email to the listed contracting specialist by the solicitation posting date. Only SDVOSBs verified in the CVE database and listed in SAM will be considered for award.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 10, "PORTABLE FIRE EXTINGUISHERS", 2018 EDITION; NFPA 13, "STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS", 2019 EDITION; NFPA 24, "STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES", 2019 EDITION; NFPA 25, "STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER- BASED FIRE PROTECTION SYSTEMS", 2017 EDITION; NFPA 70, "NATIONAL ELECTRICAL CODE", 2020 EDITION; NFPA 72, "NATIONAL FIRE ALARM AND SIGNALING CODE", 2019 EDITION; NFPA 90A "STANDARD FOR THE INSTALLATON OF AIR-CONDITIONING AND VENTILATION SYSTEMS" 2018 EDITION. NFPA 101, "LIFE SAFETY CODE" 2018 EDITION; NFPA 241, "SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS" 2019 EDITION; AND VA FIRE PROTECTION DESIGN MANUAL (VAFPDM), SEVENTH EDITION, DECEMBER 2015; IBC, "INTERNATIONAL BUILDING CODE", 2018 EDITION.
THE INTENT, AND EXTENT OF THE FIRE PROTECTION SYSTEM DESIGN IS PERFORMANCE-BASED IN NATURE, AND IS DIAGRAMMATIC ONLY. IT IS NOT INTENDED TO SHOW EVERY PIPE, FITTING, DEVICE, APPLIANCE, COMPONENT, ETC. FIRE ALARM FLOOR PLANS AND RISER DIAGRAM ARE DIAGRAMMATIC AND NOT INTENDED TO SHOW EACH AND EVERY COMPONENT, DEVICE, APPLIANCE, ETC. CONDUIT PATHWAYS AND INTERCONNECTIONS SHALL BE DETERMINED BY THE BUILDING FEATURES, NFPA 70, NFPA 72, SYSTEM MANUFACTURER REQUIREMENTS AND
RECOMMENDATIONS.
CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID WITH THE PROJECT DOCUMENTS AND SPECIFICATIONS TO BECOME FAMILIAR WITH THE SITE AND SCOPE OF WORK. NOTIFY ENGINEER OF RECORD WITH ANY DISCREPANCIES OUTSIDE THIS DESIGN INTENT. ANY CHANGE ORDER
REQUEST AS A RESULT OF COORDINATION BETWEEN TRADES SHALL BE DENIED.
ADHERE TO AND OBTAIN ALL PERMITS, LICENSES, AND ALL FEDERAL GOVERNMENT REQUIREMENTS.
DO NOT SCALE PLANS FOR THE PURPOSE OF ESTABLISHING DIMENSIONS. FIELD DIMENSIONS GOVERN.
FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE PARTITIONS. FIRE STOPPING SHALL BE OF UL LISTED ASSEMBLY.
1.
2.
3.
4.
5.
6.
GENERAL NOTESFIRE PROTECTION LEGEND
MANUAL FIRE ALARM PULL STATION,
MOUNT 42" - 48" AFF TO TOP OF
HANDLE
VALVE SUPERVISORY SWITCH
WATER FLOW DETECTOR/SWITCH
SMOKE DETECTOR-PHOTOELECTRIC
F
S
CONTRACTOR SHALL SUBMIT COMPLETE BATTERY CALCULATIONS, VOLTAGE DROP CALCULATIONS, MATERIAL DATA SHEETS, AND SHOP DRAWINGS TO CONTRACTING OFFICERS REPRESENTATIVE FOR REVIEW PRIOR TO COMMENCING FABRICATION AND
INSTALLATION. FAILURE TO COMPLY IS AT THE RISK OF THE CONTRACTOR.
REFER TO PLAN DRAWINGS AND PROJECT DOCUMENTS FOR APPROXIMATE FIRE ALARM SYSTEM QUANTITIES AND LOCATIONS, NOT ALL SITE CONDITIONS ARE SHOWN. FIRE ALARM CONTRACTOR SHALL VISIT JOB SITE WITH ALL PROJECT DOCUMENTS PRIOR TO BID TO BECOME FAMILIAR WITH PROJECT DESIGN, INSTALLATION, TESTING AND COMMISSIONING REQUIREMENTS, SITE CONDITIONS FOR NEW SYSTEM INSTALLATION, TO PROVIDE A COMPREHENSIVE AND COMPLETE BID, CODE COMPLIANT SYSTEM DESIGN, INSTALLATION, TESTING, COMMISSIONING AND APPROVAL REQUIREMENTS.
FIRE ALARM SIGNALS AND EMERGENCY COMMUNICATIONS SHALL TAKE PRECEDENCE OVER ALL OTHER SIGNALS, SUCH AS BUT NOT
LIMITED TO PUBLIC ADDRESS SYSTEMS.
ALL NOTIFICATION APPLIANCES CIRCUITS (NAC) SHALL PERFORM TO CLASS B AS DEFINED BY NFPA 70 AND NFPA 72.
ALL SIGNALING LINE CIRCUITS (SLC) SHALL PERFORM TO CLASS B AS DEFINED BY NFPA 70 AND NFPA 72.
ALL INDICATING DEVICE CIRCUITS SHALL PERFORM TO CLASS B AS DEFINED BY NFPA 70 AND NFPA 72.
THE INSTALLATION OF WIRING BETWEEN THE FACP AND RELAY MODULES OR APPLIANCES SHALL PERFORM TO CLASS "B" AS DEFINED
BY NFPA 70 AND NFPA 72.
ALL CONDUCTORS FOR THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN EMT CONDUIT AND IN ACCORDANCE WITH NFPA 70. THE CONDUCTORS SHALL NOT BE INSTALLED WITH CONDUCTORS OF LIGHTING OR POWER SYSTEMS. THE SUM OF THE CROSS-AREA OF INDIVIDUAL CONDUCTORS SHALL NOT EXCEED 40% OF THE INTERIOR CROSS SECTION OF THE CONDUIT. ALL FIRE ALARM SYSTEM
CONDUIT SHALL NOT BE LESS THAN 3/4".
WALL MOUNTED FIRE ALARM DEVICES IN UNFINISHED AREAS MAY BE SURFACED MOUNTED, THE CONDUIT MAY BE INSTALLED
EXPOSED ON WALLS AND ON CEILINGS.
IN FINISHED AREAS, WALL MOUNTED DEVICES SHALL BE FLUSH MOUNTED. THE CONDUIT SHALL BE INSTALLED CONCEALED IN THE
WALLS AND CEILINGS UNLESS REFERENCED AS CEILING MOUNTED.
FIRE ALARM CONTRACTORS SHALL COORDINATE WITH FIRE ALARM VENDOR FOR SYSTEM OPERATING INSTRUCTIONS AND WIRING
DIAGRAMS.
ALL DUCT DETECTORS SHALL BE PROVIDED WITH REMOTE STATUS INDICATION. PROVIDE INDICATING LAMP FOR ALL CONCEALED
DETECTORS.
DUCT SMOKE SENSORS SHALL BE IN ACCORDANCE WITH NFPA 72, 90A, AND AS INDICATED ON THE CONTRACT DOCUMENTS.
DUCT DETECTORS SHALL BE PROVIDED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000-CFM. ACCESS TO DETECTORS SHALL BE PROVIDED FOR INSPECTION AND MAINTENANCE PURPOSES. ACTUATION OF THE DUCT DETECTOR SYSTEM
SHALL SHUT DOWN ALL OPERATIONAL CAPABILITIES OF THE AFFECTED UNIT.
FIRE ALARM MANUAL PULL STATIONS AT DOOR OPENINGS SHALL BE WITHIN 5' - 0" HORIZONTALLY OF THE DOOR OPENING.
PROVIDE SYNCHRONIZATION FOR ALL NEW VISIBLE (STROBE) NOTIFICATION APPLIANCES WHERE THERE ARE MORE THAN TWO DEVICES IN THE SAME ROOM OR IN AN ADJACENT SPACE WITHIN THE FIELD OF VIEW TO COMPLY WITH THE REQUIREMENTS OF NFPA 72.
PROVIDE SYNCHRONIZATION FOR ALL NEW AUDIBLE (SPEAKER) NOTIFICATION APPLIANCES WITHIN A NOTIFICATION ZONE TO COMPLY
WITH THE REQUIREMENTS OF NFPA 72.
PROVIDE TRANSIENT VOLT SURGE SUPPRESSION DEVICE WHERE CIRCUITS PENETRATE THE BUILDING ENVELOPE AND, FIRE ALARM EQUIPMENT SUPPLIED FROM THE BUILDING ELECTRICAL SYSTEM, (I.E DOOR HOLDERS, NAC BOOSTER PANELS, ETC), IN ACCORDANCE
WITH NFPA 70 AND NFPA 72 REQUIREMENTS.
STROBE FOR VISUAL FIRE ALARM APPLIANCES SHALL HAVE WHITE/ CLEAR LENS AND BE LABELED "FIRE".
INSTALL SMOKE DETECTORS NO CLOSER THAN 3' - 0" TO HVAC AIR SUPPLY DIFFUSERS
ALL FIRE ALARM PANELS AND EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH NFPA 70 ARTICLE 250 AND 800 REQUIREMENTS.
CONTRACTOR SHALL PROVIDE A DOCUMENTATION CABINET AT THE SYSTEM CONTROL PANEL IN THE BUILDING WITH ALL REQUIRED
DOCUMENTATION AND SOFTWARE REQUIRED BY NFPA 72 SECTIONS 7.7.2 AND 23.2.2.
REFER TO FIRE ALARM SYSTEM SPECIFICATION 28 31 00 FOR ADDITIONAL REQUIREMENTS AND INFORMATION.
CONTRACTOR SHALL PROVIDE PATHWAY SURVIVABILITY OF LEVEL 1 IN ACCORDANCE WITH NFPA 72.
DEMOLISH EXISTING FIRE ALARM SYSTEM IN ITS ENTIRETY. CONTRACTOR SHALL REPAIR IN KIND ANY DAMAGES THE BUILDING SUSTAINS DURING DEMOLITION. DISPOSE OF ALL DEMOLISHED EQUIPMENT AND MATERIAL IN ACCORDANCE WITH LOCAL AND STATE REQUIREMENTS. EXISTING MANUAL PULL STATIONS MAY BE REUSED IF CONTRACTOR CONSIDERS THEM TO BE IN ACCEPTABLE
CONDITION.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
FIRE ALARM CLEAR VISUAL STROBE. WALL
MOUNT AT 80" AFF TO BOTTOM OF LENS OR 6"
BELOW CEILING, WHICHEVER IS LOWER AND NOT
GREATER THAN 96". WP=WEATHER PROOF
FIRE ALARM CLEAR VISUAL STROBE AND
SPEAKER. WALL MOUNT AT 80" AFF TO BOTTOM
OF LENS OR 6" BELOW CEILING, WHICHEVER IS
LOWER AND NOT GREATER THAN 96".
CONTRACTOR SHALL SUBMIT COMPLETE SHOP DRAWINGS WITH HYDRAULIC CALCULATIONS, MATERIAL SPECIFICATION BROCHURE AND A COPY OF THEIR WATER SUPPLY RESULTS TO CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE FOR REVIEW PRIOR TO COMMENCING
FABRICATION AND INSTALLATION.
FIRE SPRINKLER CONTRACTOR SHALL INSTALL SYSTEM PIPING AND COMPONENTS IN A WORKMANSHIP LIKE MANNER. CHANGES IN INSTALLATION AS A RESULT OF POOR CRAFTSMANSHIP SHALL BE AS DIRECTED BY CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE
AND SHALL BE AT NO ADDITIONAL COST TO THE OWNER.
ANY ADDITIONAL OFFSETS OR FITTINGS REQUIRED FOR PROPER INSTALLATION, COORDINATION WITH OTHER TRADES, AND/OR TO MAINTAIN
PROPER CLEARANCES SHALL BE PROVIDED FOR A COMPLETE AND WORKING SYSTEM.
REFER TO WET-PIPE SPRINKLER SYSTEM SPECIFICATION 21 13 13 FOR ADDITIONAL REQUIREMENTS AND INFORMATION.
ALL CONTROL VALVES ON THE FIRE PROTECTION SYSTEM SHALL BE ELECTRICALLY SUPERVISED. COORDINATE THE TYPE AND EXACT LOCATION OF FLOW AND SUPERVISORY SWITCHES BETWEEN FIRE PROTECTION AND FIRE ALARM CONTRACTORS. FIRE ALARM SYSTEM, SUPERVISION AND WIRING SHALL BE PROVIDED UNDER THE SAFETY AND SECURITY DIVISION.
SPRINKLER SYSTEM(S) SHALL BE DESIGNED FOR A MAXIMUM WORKING PRESSURE OF 175 PSI IN ACCORDANCE WITH NFPA 13.
SPRINKLER SYSTEM(S) SHALL BE HYDROSTATICALLY TESTED IN ACCORDANCE WITH NFPA 13.
ALL VALVES SHALL HAVE A PERMANENTLY AFFIXED SIGN PER NFPA 13 INDICATING ITS FUNCTION AND SECURED TO THE VALVE WITH
SUITABLE CHAIN.
HANGER MATERIAL, SPACING AND METHOD OF ATTACHMENT SHALL BE IN ACCORDANCE WITH NFPA 13 AND MANUFACTURER'S REQUIREMENTS. PROVIDE EARTHQUAKE PROTECTION IN ACCORDANCE WITH NFPA 13 REQUIREMENTS.
MAINTAIN A MINIMUM OF 18" CLEARANCE BELOW SPRINKLER DEFLECTOR(S) AND ANY PERMANENT OR TEMPORARY OBSTRUCTION(S) PER
NFPA 13.
ONLY LISTED OR APPROVED DEVICES AND MATERIALS AS SPECIFIED IN NFPA 13 SHALL BE INSTALLED THROUGHOUT THE SYSTEM.
ALL SPRINKLERS SHALL BE INSTALLED ACCORDING TO THEIR LISTED SPACING AND OBSTRUCTION REQUIREMENTS.
CONTRACTOR SHALL COORDINATE INSTALLATION OF ALL FIRE PROTECTION DEVICES WITH ALL OTHER TRADES.
PROVIDE SYSTEM(S) WITH FLUSHING CONNECTIONS PER NFPA 13.
SPRINKLER SYSTEM PIPING IS REQUIRED TO BE PROVIDED WITH SEISMIC BRACING AS THE SITE IS SEISMIC DESIGN CATEGORY D.
PROVIDE A PERMANENTLY ATTACHED AND STENCILED PLACARD TO THE RISER STATING THE REQUIRED DESIGN CRITERIA FOR EACH
DESIGNED SYSTEM PER NFPA 13. THE USE OF INDELIBLE MARKER IS PROHIBITED.
AT LEAST SIX (6) SPARE SPRINKLERS OF EACH TYPE, TEMPERATURE, AND ORIFICE SIZE USED IN THE SYSTEM INCLUDING A SPECIAL WRENCH FOR EACH FIRE SPRINKLER SHALL BE KEPT IN A CABINET WHERE AMBIENT TEMPERATURE WILL AT NO TIME EXCEED 100°F PER NFPA 13.
PIPE, FITTING, SPRINKLERS, HANGERS, AND COMPONENTS INSTALLED IN CORROSIVE ATMOSPHERES (I.E COMPARTMENTS CONTAINING CORROSIVE MATERIALS AND/OR FUMES, OR EXTERIOR WEATHER CONDITIONS, ETC.) SUCH AS DRAIN PIPES, HANGER ALL-THREAD ROD, ETC., SHALL BE AN APPROVED CORROSION RESISTANT MATERIAL.
PROVIDE AIR VENTING OF THE SPRINKLER SYSTEM PER NFPA 13 SECTION 8.1.5 AT A LOCATION NEAR THE HIGH POINT OF THE SYSTEM.
SPRINKLER PIPING 2-IN. AND LESS MUST BE A MINIMUM OF SCH. 40 BLACK STEEL PIPE. PIPING LARGER THAN 2-IN. MUST BE A MINIMUM OF
SCH. 10 BLACK STEEL PIPE.
PIPING WITH A WALL THICKNESS LESS THAN SCH. 40 MUST NOT BE THREADED.
SPRINKLER PROTECTION IS REQUIRED IN COMBUSTIBLE CONCEALED SPACES PER NFPA 13.
FITTING AND COUPLING HOUSINGS SHALL BE MALLEABLE IRON CONFORMING TO ASTM A47/A47M.
DEMOLISH EXISTING FIRE STANDPIPE SYSTEM IN ITS ENTIRETY. CONTRACTOR SHALL REPAIR IN KIND ANY DAMAGES THE BUILDING SUSTAINS DURING DEMOLITION. DISPOSE OF ALL DEMOLISHED MATERIAL IN ACCORDANCE WITH LOCAL AND STATE REQUIREMENTS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
FIRE SUPPRESSION NOTES
FIRE ALARM NOTES
SIMPLEX 4100ES FIRE ALARM CONTROL PANEL FACP
VS
WF
WATER SUPPLY INFORMATION
THE EXISTING WATER SUPPLY IS PROVIDED FROM THE
EXISTING CAMPUS DOMESTIC WATER DISTRIBUTION
SYSTEM. A FIRE FLOW TEST FOR THE WATER
DISTRIBUTION SYSTEM AT THE PROJECT SITE WAS
CONDUCTED ON JANUARY 23, 2020 BY DOUG BALDWIN
(POND & COMPANY) UNDER THE SUPERVISION OF
BRANDON HOFSTEAD P.E. (POND & COMPANY). THE FIRE
FLOW TEST DATA IS AS FOLLOWS;
FLOW: 769-GPM
STATIC PRESSURE: 79 PSI
RESIDUAL PRESSURE: 62 PSI
COEFFICIENT: 0.9
FLOW AT 20 PSI: 1,506 GPM
TIME OF TEST: 10:30AM
FIRE ALARM ANNUNCIATORANN
LH
LIGHT HAZARD
0.10 GPM/SQ.FT. OVER 1500 SQ.FT.
100 GPM HOSE ALLOWANCE
K-FACTOR: 5.6
OH2
ORDINARY HAZARD
0.20 GPM/SQ.FT. OVER 1500 SQ.FT.
250 GPM HOSE ALLOWANCE
K-FACTOR: 5.6
BATT BATTERY CABINET
FIRE ALARM DUCT MOUNTED SMOKE
DETECTOR
S= SUPPLY
S S
RECESSED PENDENT
SPRINKLER
UPRIGHT SPRINKLER
NS NOT SPRINKLERED
F V
WP ELECTRIC ALARM BELL
WP=WEATHER PROOF
WP
AT
ATTIC-LIGHT HAZARD
0.10 GPM/SQ.FT. OVER 1950 SQ.FT.
(SLOPE EXCEEDS 1 IN 6)
100 GPM HOSE ALLOWANCE
K-FACTOR: 5.6
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
FULLY SPRINKLERED F-001
FIRE PROTECTION GENERAL NOTES &
LEGEND
DBNDS
REVISIONS DATE
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
OH2
NS
NS
NS
NS
NS NS NS NS NS
F1
F-501
OH2
NS
MECHANICAL ROOM
B01
STORAGE
B02
67 SF
CORRIDOR
B00
ARMORY /
WEAPONS
B04
CORRIDOR
B03
OH2
LH
SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.
FIRE SUPPRESSION SYSTEM SHALL BE DESIGNED IN ACCORDANCE
WITH NFPA 13 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN
MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:
A. VAFPDM
B. NFPA 13
CONTRACTOR SHALL COORDINATE ALL NEW SPRINKLER WORK
WITH OTHER TRADES AND EXISTING CONDITIONS.
CONTRACTOR SHALL PROVIDE FM APPROVED QUICK RESPONSE,
SEMI-RECESSED PENDENT SPRINKLERS IN AREAS WITH
SUSPENDED CEILINGS, AND FM APPROVED QUICK RESPONSE
UPRIGHT SPRINKLERS IN AREAS WITH NO CEILINGS.
PROVIDE SPRINKLER PROTECTION BENEATH STAIRWAYS OF
COMBUSTIBLE CONSTRUCTION PER NFPA 13.
SHEET NOTES:
1.
2.
3.
4.
5.
SUPPLY FROM NEW 4" UNDERGROUND SERVICE MAIN ROUTED
FROM EXISTING 4" UNDERGROUND WATER SERVICE PIPE.
ROUTING FROM EXISTING 4" UNDERGROUND WATER SERVICE
PIPE TO BUILDING SHALL BE PROVIDED UNDER THE CIVIL SCOPE
OF THIS PROJECT. REFER TO SHEET C-110 FOR CONTINUATION.
4" PIPE ROUTED TO FDC.
4" WET-PIPE RISER SERVING SPRINKLERS THROUGHOUT THE
BUILDING INCLUDING THE ATTIC.
INSPECTOR'S TEST CONNECTION AND DRAIN TO DRAIN INTO
BASEMENT FLOOR DRAIN.
4" DOUBLE CHECK VALVE BACKFLOW PREVENTER.
4" PIPE ROUTED TO BACKFLOW PREVENTER TEST HEADER.
SPRINKLER PROTECTION IS NOT REQUIRED BELOW GROUND
FLOOR IN THIS AREA PER NFPA 13 CHAPTER 9.2.2.
4 X 2-1/2" X 2-1/2" WALL MOUNTED FIRE DEPARTMENT
CONNECTION.
WALL MOUNTED BACKFLOW PREVENTER TEST HEADER.
KEYNOTES:#
1.
2.
3.
4.
5.
6.
7.
8.
9.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
DECEMBER 7, 2020
BID DOCUMENTS 621-15-101
FULLY SPRINKLERED F-100
BASEMENT FIRE PROTECTION PLAN
DBNDS
SCALE: 3/8" = 1'-0"
F1
BASEMENT FIRE PROTECTION PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
REVISIONS DATE
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100
770-483-9592 MARCH 15, 2021
LH
LH
LH
LH
LH
LH
LH
OH2
LH
LH
NS
LHLH
LH
OH
LH
NS
NS
NS
NS
NS
NS
NS
F V
WP
OFFICE
OFFICE
107 WOMEN RESTROOM
STAFF LOUNGE
MEN RESTROOM
CORRIDOR
CORRIDOR
OFFICER WORK
ROOM
INTERVIEW ROOM
EVIDENCE
PROCESSING
EVIDENCE ROOM
OFFICE
HOUSE KEEPING
WAITING ROOM
RECEPTION
ELECT.
OFFICE
OFFICE
LH
NS
NS
NS
SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.
FIRE SUPPRESSION SYSTEM SHALL BE DESIGNED IN ACCORDANCE
WITH NFPA 13 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN
MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:
A. VAFPDM
B. NFPA 13
CONTRACTOR SHALL COORDINATE ALL NEW SPRINKLER WORK
WITH OTHER TRADES.
CONTRACTOR SHALL PROVIDE FM APPROVED QUICK RESPONSE,
SEMI-RECESSED PENDENT SPRINKLERS IN AREAS WITH
SUSPENDED CEILINGS, AND FM APPROVED QUICK RESPONSE
UPRIGHT SPRINKLERS IN AREAS WITH NO CEILINGS.
SHEET NOTES:
1.
2.
3.
4.
DEMOLISH EXISTING FIRE PROTECTION
CABINET. REPAIR IN KIND THE EXTERIOR
WALL BEHIND CABINET.
KEYNOTES:#
1.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
DECEMBER 7, 2020
BID DOCUMENTS 621-15-101
FULLY SPRINKLERED F-101
FIRST FLOOR FIRE PROTECTION PLAN
DBNDS
SCALE: 3/8" = 1'-0"
F1
FIRST FLOOR FIRE PROTECTION PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
REVISIONS DATE
DECEMBER 7, 2020MARCH 15, 2021
LH LH
LH
LH
LH
LH LH LH
LHLH
OH2
OH2NS
LH
LH
NS
NS
CONFERENCE
ROOM
CHIEF OFFICE
ELECT.
LOBBY
200 MECHANICAL ROOM
HOUSE KEEPING
OFFICE
OFFICE
CORRIDOR
OFFICE
210OFFICE
MEN RESTROOM
MEN SHOWER &
LOCKER ROOM
WOMEN SHOWER &
LOCKER ROOM
206A
WOMEN RESTROOM
OIT
DEPUTY CHIEF
OFFICE
CORRIDOR
CORRIDOR
NS
NSNS
NS
NS NS
NSNSNS
SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.
FIRE SUPPRESSION SYSTEM SHALL BE DESIGNED IN ACCORDANCE
WITH NFPA 13 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN
MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:
A. VAFPDM
B. NFPA 13
CONTRACTOR SHALL COORDINATE ALL NEW SPRINKLER WORK
WITH OTHER TRADES AND EXISTING CONDITIONS.
CONTRACTOR SHALL PROVIDE FM APPROVED QUICK RESPONSE,
SEMI-RECESSED PENDENT SPRINKLERS IN AREAS WITH
SUSPENDED CEILINGS, AND FM APPROVED QUICK RESPONSE
UPRIGHT SPRINKLERS IN AREAS WITH NO CEILINGS.
SHEET NOTES:
1.
2.
3.
4.
ATTIC LEVEL SPRINKLER WATER SUPPLY. REFER TO F-103 FOR
CONTINUATION.
KEYNOTES:#
1.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
FULLY SPRINKLERED F-102
SECOND FLOOR FIRE PROTECTION
PLAN
DBNDS
SCALE: 3/8" = 1'-0"F1
SECOND FLOOR FIRE PROTECTION PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
REVISIONS DATE
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100
SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.
FIRE SUPPRESSION SYSTEM SHALL BE DESIGNED IN ACCORDANCE
WITH NFPA 13 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN
MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:
A. VAFPDM
B. NFPA 13
CONTRACTOR SHALL COORDINATE ALL NEW SPRINKLER WORK
WITH OTHER TRADES.
CONTRACTOR SHALL PROVIDE FM APPROVED QUICK RESPONSE,
SEMI-RECESSED PENDENT SPRINKLERS IN AREAS WITH
SUSPENDED CEILINGS, AND FM APPROVED QUICK RESPONSE
UPRIGHT SPRINKLERS IN AREAS WITH NO CEILINGS.
SHEET NOTES:
1.
2.
3.
4.
WALL SEPARATING COMBUSTIBLE ATTIC FROM COMBUSTIBLE
CONCEALED SPACE. BOTH REQUIRE SPRINKLER PROTECTION.
KEYNOTES:
ATTIC LEVEL SPRINKLER SUPPLY UP FROM SECOND FLOOR.
REFER TO F-102 FOR CONTINUATION.
1.
2.
AT
B3
F-103
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
FULLY SPRINKLERED F-103
ATTIC FIRE PROTECTION PLAN
DBNDS
SCALE: 3/8" = 1'-0"F1
ATTIC FIRE PROTECTION PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
SCALE: 1/4" = 1'-0"B3
ATTIC SPRINKLER SECTION VIEW
SCALE: = 1'-0"
0 4 84
1/4"
REVISIONS DATE
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100
F
VS
VS
VS
WF
S
VS
RTSRTS
S
MECHANICAL ROOM
B01
STORAGE
B02
CORRIDOR
B00
ARMORY /
WEAPONS
B04
CORRIDOR
B03
FA100
A1
FA100
A3
FA100
B5
SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.
FIRE ALARM SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
NFPA 72 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN
MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:
A. VAFPDM
B. NFPA 72
SHEET NOTES:
1.
2.
WET-PIPE RISER FLOW SWITCH AND CONTROL VALVE
SUPERVISORY SWITCH.
BACKFLOW PREVENTER CONTROL VALVE SUPERVISORY
SWITCHES.
BACKFLOW PREVENTER TEST CONNECTION CONTROL
VALVE SUPERVISORY SWITCH.
APPROXIMATE LOCATION OF EXISTING VA FIRE ALARM
NETWORK FIBER OPTIC LOOP BUILDING ENTRANCE POINT
TO REMAIN. SEE KEYNOTE #3 ON F-501 FOR DEMOLITION
AND SYSTEM DOWNTIME NOTES.
3/4" GALVANIZED RIGID STEEL CONDUIT TO PIV
SUPERVISORY SWITCH. SEE SHEET C-110 FOR CONDUIT
ROUTE TO PIV.
KEYNOTES:
PLAN LEGEND
AREA OF NO FIRE ALARM
WORK
1.
2.
3.
4.
5.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
FULLY SPRINKLERED FA100
BASEMENT FIRE ALARM PLAN
DBNDS
SCALE: 3/8" = 1'-0"F1
BASEMENT FIRE ALARM PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
SCALE: N.T.S.
A1
FIBER OPTIC LINE
SCALE: N.T.S.
A3
FIBER OPTIC LOOP BOX
SCALE: N.T.S.
B5
EXISTING FACP AND FIBER OPTIC INTERFACE TO BE DEMOLISHED
REVISIONS DATE
SCALE: N.T.S.A1
FIBER OPTIC LINE
SCALE: N.T.S.A3
FIBER OPTIC LOOP BOX
SCALE: N.T.S.B5
EXISTING FACP AND FIBER OPTIC INTERFACE TO BE DEMOLISHED
A N
N
F
F
F
F A
C P
B A
T T S
CM
OFFICE
OFFICE
WOMEN RESTROOM
STAFF LOUNGE
MEN RESTROOM
CORRIDOR
CORRIDOR
OFFICER WORK
ROOM
INTERVIEW ROOM
EVIDENCE
PROCESSING
EVIDENCE ROOM
OFFICE
HOUSE KEEPING
WAITING ROOM
RECEPTION
ELECT.
OFFICE
OFFICE
15 15
SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.
FIRE ALARM SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
NFPA 72 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN
MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:
A. VAFPDM
B. NFPA 72
SHEET NOTES:
1.
2.
CONTROL MODULE FOR ACTIVATION OF SMOKE CURTAIN.
KEYNOTES:#
1.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
FULLY SPRINKLERED FA101
FIRST FLOOR FIRE ALARM PLAN
DBNDS
SCALE: 3/8" = 1'-0"F1
FIRST FLOOR FIRE ALARM PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
REVISIONS DATE
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100
S
RTSRTS
S
CONFERENCE
ROOM
CHIEF OFFICE
ELECT.
LOBBY
MECHANICAL ROOM
HOUSE KEEPING
OFFICE
212 OFFICE
CORRIDOR
OFFICE
OFFICE
MEN RESTROOM
MEN SHOWER &
LOCKER ROOM
WOMEN SHOWER &
LOCKER ROOM
206A
WOMEN RESTROOM
OIT
DEPUTY CHIEF
OFFICE
CORRIDOR
CORRIDOR
WP
WP
SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.
FIRE ALARM SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
NFPA 72 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN
MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:
A. VAFPDM
B. NFPA 72
SHEET NOTES:
1.
2.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
FULLY SPRINKLERED FA102
SECOND FLOOR FIRE ALARM PLAN
DBNDS
SCALE: 3/8" = 1'-0"F1
SECOND FLOOR FIRE ALARM PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
REVISIONS DATE
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100
SIMPLEX
4100ES
FIRE
ALARM
CONTROL
PANEL
(FACP)
S
BATTERIES
SS
SIGNALING LINE CIRCUIT
(SLC)
NOTIFICATION
APPLIANCE CIRCUIT
(NAC)
SPEAKER CIRCUIT
120 VAC
F
VS WF
WET PIPE
SPRINKLER
SYSTEM
ANN
VS VS
BACKFLOW
PREVENTER
F V
VS
BACKFLOW
PREVENTER
TEST
HEADER
BREAKER POWER
PANEL
POWER
WP
VA FIBER OPTIC
FIRE ALARM
NETWORK
S S
RTS
VS
POST
INDICATOR
VALVE
CM
SMOKE
CURTAIN
SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.
FIRE ALARM FLOOR PLANS AND RISER DIAGRAM ARE
DIAGRAMMATIC AND NOT INTENDED TO SHOW EACH AND EVERY
COMPONENT, DEVICE, APPLIANCE, ETC. CONDUIT PATHWAYS
AND INTERCONNECTIONS SHALL BE DETERMINED BY THE
BUILDING FEATURES, VAFPDM, NFPA 70, NFPA 72, SYSTEM
MANUFACTURER REQUIREMENTS AND RECOMMENDATIONS.
SHEET NOTES
1.
2.
BREAKER SERVING THE FACP SHALL HAVE A RED MARKING
PER NFPA 72 SECTION 10.6.2.3 AND 10.6.5.2.4 AND PROVIDED
WITH A NON-SWEEP DEVICE (LOCK) PER NFPA 72; SECTION
10.6.5.4 IN ADDITION, MEET THE REQUIREMENTS OF NFPA 72;
SECTION 10.6.5.2.2, 10.6.5.2.5, AND 10.6.5.3.
FACP SHALL INDICATE THE LOCATION AND IDENTIFICATION
OF THE POWER PANEL WHERE THE POWER BREAKER IS
LOCATED PER NFPA 72 REQUIREMENTS.
THE CONTRACTOR SHALL MINIMIZE DOWNTIME OF THE VA
MEDICAL CENTER'S FIRE ALARM SYSTEMS BY PROVIDING A
TEMPORARY FIBER OPTIC CONNECTION TO BYPASS THE
EXISTING 4010 SIMPLEX PANEL DURING DEMOLITION OF THE
EXISTING FIRE ALARM SYSTEM TO MAINTAIN THE
OPERATION OF THE VA FIRE ALARM FIBER OPTIC LOOP.
AFTER THE NEW 4100ES FIRE ALARM CONTROL PANEL IS
INSTALLED, THE CONTRACTOR SHALL COMPLETE THE FIBER
OPTIC LOOP THROUGH THE NEW SIMPLEX 4100ES SYSTEM.
CONTRACTOR SHALL COORDINATE FIRE ALARM SYSTEM
DOWNTIME WITH THE VA MEDICAL CENTER.
REFER TO CIVIL DRAWING C-110 FOR ROUTING OF CONDUIT
TO POST INDICATOR VALVE SUPERVISORY DEVICE AND FOR
LOCATION OF THE POST INDICATOR VALVE.
KEYNOTES:#
1.
2.
3.
4.
S O
U N
D G
E N
E R
A L B
U
IL
D
IN
G A
L A
R M
A
F1 AREA SMOKE DETECTOR
FIRE ALARMS
SUPERVISORY SIGNALS
SYSTEM INPUTS
DUCT SMOKE DETECTOR S1
F2
SYSTEM OUTPUTS
F3
MANUAL PULL STATION
SPRINKLER WATERFLOW SWITCH
WATER CONTROL VALVE TAMPERS2
X X X
B
T R
A N
S M
IT
A
L A
R M
S
IG
N A
L T
O P
O L
IC
E
D
IS
P A
T C
H O
F F
IC
E
I N
B U
IL
D
IN
G
A
G
IN
E
E R
IN
G
B U
IL
D
IN
G
C X X X
D
X
S H
U T
D O
W N
A
IR
H A
N D
L E
R S
E R
V E
D B
Y T
H
T
E C
T O
R
X
X
T R
A N
S M
IT
S
U P
E R
V
IS
O R
Y S
IG
N
A L T
O
P O
L
IC
E D
IS
P
A T
C H
O F
F
IC
E I N
B U
IL
D
IN
G
A
D E
N G
IN
E
E R
IN
G
B U
IL
D
IN
G
E
A C
T
IV
A T
E S
M O
K E
C U
R T
A
IN
X X X
FIRST FLOOR
2' - 6 5/8"
Basement -7' - 3 5/8"
CHECK VALVE
4" PIPE TO FIRE
DEPARTMENT
CONNECTION
4" BUILDING
FIRE WATER
SUPPLY
4" DOUBLE
CHECK
BACKFLOW
PREVENTER
4" TO BACKFLOW
PREVENTER TEST
CONECTION
FLOW
SWITCH
INSPECTORS TEST
CONNECTION AND
DRAIN
BUTTERFLY
CONTROL
VALVE
TO ALL
BUILDING
SPRINKLERS
NORMALLY
CLOSED NORMALLY
OPEN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
FULLY SPRINKLERED F-501
FIRE PROTECTION DETAILS
DBNDS
SCALE: N.T.S.C1
FIRE ALARM RISER DIAGRAM
SCALE: N.T.S.E6
FIRE ALARM SEQUENCE OF OPERATIONS
SCALE: 1" = 1'-0"F1
WET-PIPE RISER DETAIL
SCALE: = 1'-0"
0 1 21
1"
REVISIONS DATE
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100
| Sheets |
| F-001 - FIRE PROTECTION GENERAL NOTES & LEGEND |
| F-100 - BASEMENT FIRE PROTECTION PLAN |
| F-101 - FIRST FLOOR FIRE PROTECTION PLAN |
| F-102 - SECOND FLOOR FIRE PROTECTION PLAN |
| F-103 - ATTIC FIRE PROTECTION PLAN |
| FA100 - BASEMENT FIRE ALARM PLAN |
| FA101 - FIRST FLOOR FIRE ALARM PLAN |
| FA102 - SECOND FLOOR FIRE ALARM PLAN |
| F-501 - FIRE PROTECTION DETAILS |