05 1200392 VA Bldg 20 FIRE 05 13 2021.pdf

PDF 3 MB Posted

Attached to
Z2DZ-36C249-21-AP-3182 - 621-15-101 - Correct Admin Bldg. -20 Environment & Condition Deficiencies
Solicitation number
36C24921B0014
Issued by

About this file

This presolicitation notice is for a construction project to correct environment and condition deficiencies at the Administration Building 20 at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The project scope includes reconstructing space for police staff with new offices, a conference room, observation room, interview room, evidence room, locker rooms, storage, electrical and mechanical rooms, an armory, lounge areas, waiting and reception areas, restrooms, corridors and circulation areas. Work will also include demolishing existing structures and materials. The estimated value is between $1 million to $5 million. The requirement will use NAICS code 236220 and be set aside 100% for Service-Disabled Veteran Owned Small Businesses. The solicitation is expected to post on October 20, 2021 and close on November 20, 2021, following FAR Part 14.1 sealed bidding procedures. Questions must be submitted in writing by email to the listed contracting specialist by the solicitation posting date. Only SDVOSBs verified in the CVE database and listed in SAM will be considered for award.

View the file

Other files

File Type Posted
36C24921B0014 0007.pdf PDF
S04- SITE VISIT ATTENDEES - Bldg 20 - 621-15-101.pdf PDF
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-16-2021.pdf PDF
36C24921B0014 0006.pdf PDF
S05 - VA Comprehensive Asbestos Containing Materials Inspection Report January 2010 - 2.pdf PDF
S06 - AMENDMENT 5 - 36C24921B0014 0005.pdf PDF
S05-Mountain Home TN - VA Asbestos O AND M Plan January 2010 -1.pdf PDF
S05-RFI RESPONSE QUESTIONS - B20 Correct FCA Deficiencies 12-23-2021.pdf PDF
S02-LBP DOC-Building 20 - 36C24921B0014.pdf PDF
S02-Building 20 ACM Report - 36C24921B0014.pdf PDF
S02- Solicitation - 36C24921B0014 - 621-15-101 - Amendment - 0004.pdf PDF
36C24921B0014 0003.pdf PDF
S06- AMENDMENT2 - CO AND PROJECT CONFIRMATION DATES - 36C24921B0014 0002.pdf PDF
S02-AMENDMENT1 - 621-15-101 CORRECT ADMIN BLDG 20 ENVIRONMENT COND DEF - BID SPECIFICATIONS.pdf PDF
S02- AMENDMENT 1 - 03 1200392 VA Bldg 20 ARCH 05 13 2021 Part 1.pdf PDF
S02- AMENDMENT 1 - 06 1200392 VA Bldg 20 PLMB 05 13 2021 Part 1.pdf PDF
S06-AMENDMENT 01 - 621-15-101 - 36C24921B0014 0001 - WB.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1D.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1A.pdf PDF
06 1200392 VA Bldg 20 PLMB 05 13 2021 Part 2.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 2D.pdf PDF
08 1200392 VA Bldg 20 ELEC 05 13 2021.pdf PDF
07 1200392 VA Bldg 20 MECH 05 13 2021.pdf PDF
09 1200392 VA Bldg 20 COMM 05 13 2021.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 2C.pdf PDF
S02-Contractor EMR Certification Form - 36C24921B0014.docx DOCX document
04 1200392 VA Bldg 20 INT 05 13 2021.pdf PDF
S02-TECHNICAL SPECS - Project 621-15-101.pdf PDF
02 1200392 VA Bldg 20 CIVIL 05 13 2021.pdf PDF
S02-621-15-101 - Correct Admin Bldg 20 .pdf PDF
01 1200392 VA Bldg 20 GEN 05 13 2021.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1B.pdf PDF
S02-WD - WASHINGTON TN - TN20210111 - JAN 2021.pdf PDF
03 1200392 VA Bldg 20 ARCH 05 13 2021 Part 2.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1C.pdf PDF
36C24921B0014.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 10, "PORTABLE FIRE EXTINGUISHERS", 2018 EDITION; NFPA 13, "STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS", 2019 EDITION; NFPA 24, "STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES", 2019 EDITION; NFPA 25, "STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER- BASED FIRE PROTECTION SYSTEMS", 2017 EDITION; NFPA 70, "NATIONAL ELECTRICAL CODE", 2020 EDITION; NFPA 72, "NATIONAL FIRE ALARM AND SIGNALING CODE", 2019 EDITION; NFPA 90A "STANDARD FOR THE INSTALLATON OF AIR-CONDITIONING AND VENTILATION SYSTEMS" 2018 EDITION. NFPA 101, "LIFE SAFETY CODE" 2018 EDITION; NFPA 241, "SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS" 2019 EDITION; AND VA FIRE PROTECTION DESIGN MANUAL (VAFPDM), SEVENTH EDITION, DECEMBER 2015; IBC, "INTERNATIONAL BUILDING CODE", 2018 EDITION.

THE INTENT, AND EXTENT OF THE FIRE PROTECTION SYSTEM DESIGN IS PERFORMANCE-BASED IN NATURE, AND IS DIAGRAMMATIC ONLY. IT IS NOT INTENDED TO SHOW EVERY PIPE, FITTING, DEVICE, APPLIANCE, COMPONENT, ETC. FIRE ALARM FLOOR PLANS AND RISER DIAGRAM ARE DIAGRAMMATIC AND NOT INTENDED TO SHOW EACH AND EVERY COMPONENT, DEVICE, APPLIANCE, ETC. CONDUIT PATHWAYS AND INTERCONNECTIONS SHALL BE DETERMINED BY THE BUILDING FEATURES, NFPA 70, NFPA 72, SYSTEM MANUFACTURER REQUIREMENTS AND

RECOMMENDATIONS.

CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID WITH THE PROJECT DOCUMENTS AND SPECIFICATIONS TO BECOME FAMILIAR WITH THE SITE AND SCOPE OF WORK. NOTIFY ENGINEER OF RECORD WITH ANY DISCREPANCIES OUTSIDE THIS DESIGN INTENT. ANY CHANGE ORDER

REQUEST AS A RESULT OF COORDINATION BETWEEN TRADES SHALL BE DENIED.

ADHERE TO AND OBTAIN ALL PERMITS, LICENSES, AND ALL FEDERAL GOVERNMENT REQUIREMENTS.

DO NOT SCALE PLANS FOR THE PURPOSE OF ESTABLISHING DIMENSIONS. FIELD DIMENSIONS GOVERN.

FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE PARTITIONS. FIRE STOPPING SHALL BE OF UL LISTED ASSEMBLY.

1.

2.

3.

4.

5.

6.

GENERAL NOTESFIRE PROTECTION LEGEND

MANUAL FIRE ALARM PULL STATION,

MOUNT 42" - 48" AFF TO TOP OF

HANDLE

VALVE SUPERVISORY SWITCH

WATER FLOW DETECTOR/SWITCH

SMOKE DETECTOR-PHOTOELECTRIC

F

S

CONTRACTOR SHALL SUBMIT COMPLETE BATTERY CALCULATIONS, VOLTAGE DROP CALCULATIONS, MATERIAL DATA SHEETS, AND SHOP DRAWINGS TO CONTRACTING OFFICERS REPRESENTATIVE FOR REVIEW PRIOR TO COMMENCING FABRICATION AND

INSTALLATION. FAILURE TO COMPLY IS AT THE RISK OF THE CONTRACTOR.

REFER TO PLAN DRAWINGS AND PROJECT DOCUMENTS FOR APPROXIMATE FIRE ALARM SYSTEM QUANTITIES AND LOCATIONS, NOT ALL SITE CONDITIONS ARE SHOWN. FIRE ALARM CONTRACTOR SHALL VISIT JOB SITE WITH ALL PROJECT DOCUMENTS PRIOR TO BID TO BECOME FAMILIAR WITH PROJECT DESIGN, INSTALLATION, TESTING AND COMMISSIONING REQUIREMENTS, SITE CONDITIONS FOR NEW SYSTEM INSTALLATION, TO PROVIDE A COMPREHENSIVE AND COMPLETE BID, CODE COMPLIANT SYSTEM DESIGN, INSTALLATION, TESTING, COMMISSIONING AND APPROVAL REQUIREMENTS.

FIRE ALARM SIGNALS AND EMERGENCY COMMUNICATIONS SHALL TAKE PRECEDENCE OVER ALL OTHER SIGNALS, SUCH AS BUT NOT

LIMITED TO PUBLIC ADDRESS SYSTEMS.

ALL NOTIFICATION APPLIANCES CIRCUITS (NAC) SHALL PERFORM TO CLASS B AS DEFINED BY NFPA 70 AND NFPA 72.

ALL SIGNALING LINE CIRCUITS (SLC) SHALL PERFORM TO CLASS B AS DEFINED BY NFPA 70 AND NFPA 72.

ALL INDICATING DEVICE CIRCUITS SHALL PERFORM TO CLASS B AS DEFINED BY NFPA 70 AND NFPA 72.

THE INSTALLATION OF WIRING BETWEEN THE FACP AND RELAY MODULES OR APPLIANCES SHALL PERFORM TO CLASS "B" AS DEFINED

BY NFPA 70 AND NFPA 72.

ALL CONDUCTORS FOR THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN EMT CONDUIT AND IN ACCORDANCE WITH NFPA 70. THE CONDUCTORS SHALL NOT BE INSTALLED WITH CONDUCTORS OF LIGHTING OR POWER SYSTEMS. THE SUM OF THE CROSS-AREA OF INDIVIDUAL CONDUCTORS SHALL NOT EXCEED 40% OF THE INTERIOR CROSS SECTION OF THE CONDUIT. ALL FIRE ALARM SYSTEM

CONDUIT SHALL NOT BE LESS THAN 3/4".

WALL MOUNTED FIRE ALARM DEVICES IN UNFINISHED AREAS MAY BE SURFACED MOUNTED, THE CONDUIT MAY BE INSTALLED

EXPOSED ON WALLS AND ON CEILINGS.

IN FINISHED AREAS, WALL MOUNTED DEVICES SHALL BE FLUSH MOUNTED. THE CONDUIT SHALL BE INSTALLED CONCEALED IN THE

WALLS AND CEILINGS UNLESS REFERENCED AS CEILING MOUNTED.

FIRE ALARM CONTRACTORS SHALL COORDINATE WITH FIRE ALARM VENDOR FOR SYSTEM OPERATING INSTRUCTIONS AND WIRING

DIAGRAMS.

ALL DUCT DETECTORS SHALL BE PROVIDED WITH REMOTE STATUS INDICATION. PROVIDE INDICATING LAMP FOR ALL CONCEALED

DETECTORS.

DUCT SMOKE SENSORS SHALL BE IN ACCORDANCE WITH NFPA 72, 90A, AND AS INDICATED ON THE CONTRACT DOCUMENTS.

DUCT DETECTORS SHALL BE PROVIDED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000-CFM. ACCESS TO DETECTORS SHALL BE PROVIDED FOR INSPECTION AND MAINTENANCE PURPOSES. ACTUATION OF THE DUCT DETECTOR SYSTEM

SHALL SHUT DOWN ALL OPERATIONAL CAPABILITIES OF THE AFFECTED UNIT.

FIRE ALARM MANUAL PULL STATIONS AT DOOR OPENINGS SHALL BE WITHIN 5' - 0" HORIZONTALLY OF THE DOOR OPENING.

PROVIDE SYNCHRONIZATION FOR ALL NEW VISIBLE (STROBE) NOTIFICATION APPLIANCES WHERE THERE ARE MORE THAN TWO DEVICES IN THE SAME ROOM OR IN AN ADJACENT SPACE WITHIN THE FIELD OF VIEW TO COMPLY WITH THE REQUIREMENTS OF NFPA 72.

PROVIDE SYNCHRONIZATION FOR ALL NEW AUDIBLE (SPEAKER) NOTIFICATION APPLIANCES WITHIN A NOTIFICATION ZONE TO COMPLY

WITH THE REQUIREMENTS OF NFPA 72.

PROVIDE TRANSIENT VOLT SURGE SUPPRESSION DEVICE WHERE CIRCUITS PENETRATE THE BUILDING ENVELOPE AND, FIRE ALARM EQUIPMENT SUPPLIED FROM THE BUILDING ELECTRICAL SYSTEM, (I.E DOOR HOLDERS, NAC BOOSTER PANELS, ETC), IN ACCORDANCE

WITH NFPA 70 AND NFPA 72 REQUIREMENTS.

STROBE FOR VISUAL FIRE ALARM APPLIANCES SHALL HAVE WHITE/ CLEAR LENS AND BE LABELED "FIRE".

INSTALL SMOKE DETECTORS NO CLOSER THAN 3' - 0" TO HVAC AIR SUPPLY DIFFUSERS

ALL FIRE ALARM PANELS AND EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH NFPA 70 ARTICLE 250 AND 800 REQUIREMENTS.

CONTRACTOR SHALL PROVIDE A DOCUMENTATION CABINET AT THE SYSTEM CONTROL PANEL IN THE BUILDING WITH ALL REQUIRED

DOCUMENTATION AND SOFTWARE REQUIRED BY NFPA 72 SECTIONS 7.7.2 AND 23.2.2.

REFER TO FIRE ALARM SYSTEM SPECIFICATION 28 31 00 FOR ADDITIONAL REQUIREMENTS AND INFORMATION.

CONTRACTOR SHALL PROVIDE PATHWAY SURVIVABILITY OF LEVEL 1 IN ACCORDANCE WITH NFPA 72.

DEMOLISH EXISTING FIRE ALARM SYSTEM IN ITS ENTIRETY. CONTRACTOR SHALL REPAIR IN KIND ANY DAMAGES THE BUILDING SUSTAINS DURING DEMOLITION. DISPOSE OF ALL DEMOLISHED EQUIPMENT AND MATERIAL IN ACCORDANCE WITH LOCAL AND STATE REQUIREMENTS. EXISTING MANUAL PULL STATIONS MAY BE REUSED IF CONTRACTOR CONSIDERS THEM TO BE IN ACCEPTABLE

CONDITION.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

FIRE ALARM CLEAR VISUAL STROBE. WALL

MOUNT AT 80" AFF TO BOTTOM OF LENS OR 6"

BELOW CEILING, WHICHEVER IS LOWER AND NOT

GREATER THAN 96". WP=WEATHER PROOF

FIRE ALARM CLEAR VISUAL STROBE AND

SPEAKER. WALL MOUNT AT 80" AFF TO BOTTOM

OF LENS OR 6" BELOW CEILING, WHICHEVER IS

LOWER AND NOT GREATER THAN 96".

CONTRACTOR SHALL SUBMIT COMPLETE SHOP DRAWINGS WITH HYDRAULIC CALCULATIONS, MATERIAL SPECIFICATION BROCHURE AND A COPY OF THEIR WATER SUPPLY RESULTS TO CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE FOR REVIEW PRIOR TO COMMENCING

FABRICATION AND INSTALLATION.

FIRE SPRINKLER CONTRACTOR SHALL INSTALL SYSTEM PIPING AND COMPONENTS IN A WORKMANSHIP LIKE MANNER. CHANGES IN INSTALLATION AS A RESULT OF POOR CRAFTSMANSHIP SHALL BE AS DIRECTED BY CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE

AND SHALL BE AT NO ADDITIONAL COST TO THE OWNER.

ANY ADDITIONAL OFFSETS OR FITTINGS REQUIRED FOR PROPER INSTALLATION, COORDINATION WITH OTHER TRADES, AND/OR TO MAINTAIN

PROPER CLEARANCES SHALL BE PROVIDED FOR A COMPLETE AND WORKING SYSTEM.

REFER TO WET-PIPE SPRINKLER SYSTEM SPECIFICATION 21 13 13 FOR ADDITIONAL REQUIREMENTS AND INFORMATION.

ALL CONTROL VALVES ON THE FIRE PROTECTION SYSTEM SHALL BE ELECTRICALLY SUPERVISED. COORDINATE THE TYPE AND EXACT LOCATION OF FLOW AND SUPERVISORY SWITCHES BETWEEN FIRE PROTECTION AND FIRE ALARM CONTRACTORS. FIRE ALARM SYSTEM, SUPERVISION AND WIRING SHALL BE PROVIDED UNDER THE SAFETY AND SECURITY DIVISION.

SPRINKLER SYSTEM(S) SHALL BE DESIGNED FOR A MAXIMUM WORKING PRESSURE OF 175 PSI IN ACCORDANCE WITH NFPA 13.

SPRINKLER SYSTEM(S) SHALL BE HYDROSTATICALLY TESTED IN ACCORDANCE WITH NFPA 13.

ALL VALVES SHALL HAVE A PERMANENTLY AFFIXED SIGN PER NFPA 13 INDICATING ITS FUNCTION AND SECURED TO THE VALVE WITH

SUITABLE CHAIN.

HANGER MATERIAL, SPACING AND METHOD OF ATTACHMENT SHALL BE IN ACCORDANCE WITH NFPA 13 AND MANUFACTURER'S REQUIREMENTS. PROVIDE EARTHQUAKE PROTECTION IN ACCORDANCE WITH NFPA 13 REQUIREMENTS.

MAINTAIN A MINIMUM OF 18" CLEARANCE BELOW SPRINKLER DEFLECTOR(S) AND ANY PERMANENT OR TEMPORARY OBSTRUCTION(S) PER

NFPA 13.

ONLY LISTED OR APPROVED DEVICES AND MATERIALS AS SPECIFIED IN NFPA 13 SHALL BE INSTALLED THROUGHOUT THE SYSTEM.

ALL SPRINKLERS SHALL BE INSTALLED ACCORDING TO THEIR LISTED SPACING AND OBSTRUCTION REQUIREMENTS.

CONTRACTOR SHALL COORDINATE INSTALLATION OF ALL FIRE PROTECTION DEVICES WITH ALL OTHER TRADES.

PROVIDE SYSTEM(S) WITH FLUSHING CONNECTIONS PER NFPA 13.

SPRINKLER SYSTEM PIPING IS REQUIRED TO BE PROVIDED WITH SEISMIC BRACING AS THE SITE IS SEISMIC DESIGN CATEGORY D.

PROVIDE A PERMANENTLY ATTACHED AND STENCILED PLACARD TO THE RISER STATING THE REQUIRED DESIGN CRITERIA FOR EACH

DESIGNED SYSTEM PER NFPA 13. THE USE OF INDELIBLE MARKER IS PROHIBITED.

AT LEAST SIX (6) SPARE SPRINKLERS OF EACH TYPE, TEMPERATURE, AND ORIFICE SIZE USED IN THE SYSTEM INCLUDING A SPECIAL WRENCH FOR EACH FIRE SPRINKLER SHALL BE KEPT IN A CABINET WHERE AMBIENT TEMPERATURE WILL AT NO TIME EXCEED 100°F PER NFPA 13.

PIPE, FITTING, SPRINKLERS, HANGERS, AND COMPONENTS INSTALLED IN CORROSIVE ATMOSPHERES (I.E COMPARTMENTS CONTAINING CORROSIVE MATERIALS AND/OR FUMES, OR EXTERIOR WEATHER CONDITIONS, ETC.) SUCH AS DRAIN PIPES, HANGER ALL-THREAD ROD, ETC., SHALL BE AN APPROVED CORROSION RESISTANT MATERIAL.

PROVIDE AIR VENTING OF THE SPRINKLER SYSTEM PER NFPA 13 SECTION 8.1.5 AT A LOCATION NEAR THE HIGH POINT OF THE SYSTEM.

SPRINKLER PIPING 2-IN. AND LESS MUST BE A MINIMUM OF SCH. 40 BLACK STEEL PIPE. PIPING LARGER THAN 2-IN. MUST BE A MINIMUM OF

SCH. 10 BLACK STEEL PIPE.

PIPING WITH A WALL THICKNESS LESS THAN SCH. 40 MUST NOT BE THREADED.

SPRINKLER PROTECTION IS REQUIRED IN COMBUSTIBLE CONCEALED SPACES PER NFPA 13.

FITTING AND COUPLING HOUSINGS SHALL BE MALLEABLE IRON CONFORMING TO ASTM A47/A47M.

DEMOLISH EXISTING FIRE STANDPIPE SYSTEM IN ITS ENTIRETY. CONTRACTOR SHALL REPAIR IN KIND ANY DAMAGES THE BUILDING SUSTAINS DURING DEMOLITION. DISPOSE OF ALL DEMOLISHED MATERIAL IN ACCORDANCE WITH LOCAL AND STATE REQUIREMENTS.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

FIRE SUPPRESSION NOTES

FIRE ALARM NOTES

SIMPLEX 4100ES FIRE ALARM CONTROL PANEL FACP

VS

WF

WATER SUPPLY INFORMATION

THE EXISTING WATER SUPPLY IS PROVIDED FROM THE

EXISTING CAMPUS DOMESTIC WATER DISTRIBUTION

SYSTEM. A FIRE FLOW TEST FOR THE WATER

DISTRIBUTION SYSTEM AT THE PROJECT SITE WAS

CONDUCTED ON JANUARY 23, 2020 BY DOUG BALDWIN

(POND & COMPANY) UNDER THE SUPERVISION OF

BRANDON HOFSTEAD P.E. (POND & COMPANY). THE FIRE

FLOW TEST DATA IS AS FOLLOWS;

FLOW: 769-GPM

STATIC PRESSURE: 79 PSI

RESIDUAL PRESSURE: 62 PSI

COEFFICIENT: 0.9

FLOW AT 20 PSI: 1,506 GPM

TIME OF TEST: 10:30AM

FIRE ALARM ANNUNCIATORANN

LH

LIGHT HAZARD

0.10 GPM/SQ.FT. OVER 1500 SQ.FT.

100 GPM HOSE ALLOWANCE

K-FACTOR: 5.6

OH2

ORDINARY HAZARD

0.20 GPM/SQ.FT. OVER 1500 SQ.FT.

250 GPM HOSE ALLOWANCE

K-FACTOR: 5.6

BATT BATTERY CABINET

FIRE ALARM DUCT MOUNTED SMOKE

DETECTOR

S= SUPPLY

S S

RECESSED PENDENT

SPRINKLER

UPRIGHT SPRINKLER

NS NOT SPRINKLERED

F V

WP ELECTRIC ALARM BELL

WP=WEATHER PROOF

WP

AT

ATTIC-LIGHT HAZARD

0.10 GPM/SQ.FT. OVER 1950 SQ.FT.

(SLOPE EXCEEDS 1 IN 6)

100 GPM HOSE ALLOWANCE

K-FACTOR: 5.6

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

FULLY SPRINKLERED F-001

FIRE PROTECTION GENERAL NOTES &

LEGEND

DBNDS

REVISIONS DATE

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

OH2

NS

NS

NS

NS

NS NS NS NS NS

F1

F-501

OH2

NS

MECHANICAL ROOM

B01

STORAGE

B02

67 SF

CORRIDOR

B00

ARMORY /

WEAPONS

B04

CORRIDOR

B03

OH2

LH

SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.

FIRE SUPPRESSION SYSTEM SHALL BE DESIGNED IN ACCORDANCE

WITH NFPA 13 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN

MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:

A. VAFPDM

B. NFPA 13

CONTRACTOR SHALL COORDINATE ALL NEW SPRINKLER WORK

WITH OTHER TRADES AND EXISTING CONDITIONS.

CONTRACTOR SHALL PROVIDE FM APPROVED QUICK RESPONSE,

SEMI-RECESSED PENDENT SPRINKLERS IN AREAS WITH

SUSPENDED CEILINGS, AND FM APPROVED QUICK RESPONSE

UPRIGHT SPRINKLERS IN AREAS WITH NO CEILINGS.

PROVIDE SPRINKLER PROTECTION BENEATH STAIRWAYS OF

COMBUSTIBLE CONSTRUCTION PER NFPA 13.

SHEET NOTES:

1.

2.

3.

4.

5.

SUPPLY FROM NEW 4" UNDERGROUND SERVICE MAIN ROUTED

FROM EXISTING 4" UNDERGROUND WATER SERVICE PIPE.

ROUTING FROM EXISTING 4" UNDERGROUND WATER SERVICE

PIPE TO BUILDING SHALL BE PROVIDED UNDER THE CIVIL SCOPE

OF THIS PROJECT. REFER TO SHEET C-110 FOR CONTINUATION.

4" PIPE ROUTED TO FDC.

4" WET-PIPE RISER SERVING SPRINKLERS THROUGHOUT THE

BUILDING INCLUDING THE ATTIC.

INSPECTOR'S TEST CONNECTION AND DRAIN TO DRAIN INTO

BASEMENT FLOOR DRAIN.

4" DOUBLE CHECK VALVE BACKFLOW PREVENTER.

4" PIPE ROUTED TO BACKFLOW PREVENTER TEST HEADER.

SPRINKLER PROTECTION IS NOT REQUIRED BELOW GROUND

FLOOR IN THIS AREA PER NFPA 13 CHAPTER 9.2.2.

4 X 2-1/2" X 2-1/2" WALL MOUNTED FIRE DEPARTMENT

CONNECTION.

WALL MOUNTED BACKFLOW PREVENTER TEST HEADER.

KEYNOTES:#

1.

2.

3.

4.

5.

6.

7.

8.

9.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

DECEMBER 7, 2020

BID DOCUMENTS 621-15-101

FULLY SPRINKLERED F-100

BASEMENT FIRE PROTECTION PLAN

DBNDS

SCALE: 3/8" = 1'-0"

F1

BASEMENT FIRE PROTECTION PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

REVISIONS DATE

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100

770-483-9592 MARCH 15, 2021

LH

LH

LH

LH

LH

LH

LH

OH2

LH

LH

NS

LHLH

LH

OH

LH

NS

NS

NS

NS

NS

NS

NS

F V

WP

OFFICE

OFFICE

107 WOMEN RESTROOM

STAFF LOUNGE

MEN RESTROOM

CORRIDOR

CORRIDOR

OFFICER WORK

ROOM

INTERVIEW ROOM

EVIDENCE

PROCESSING

EVIDENCE ROOM

OFFICE

HOUSE KEEPING

WAITING ROOM

RECEPTION

ELECT.

OFFICE

OFFICE

LH

NS

NS

NS

SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.

FIRE SUPPRESSION SYSTEM SHALL BE DESIGNED IN ACCORDANCE

WITH NFPA 13 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN

MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:

A. VAFPDM

B. NFPA 13

CONTRACTOR SHALL COORDINATE ALL NEW SPRINKLER WORK

WITH OTHER TRADES.

CONTRACTOR SHALL PROVIDE FM APPROVED QUICK RESPONSE,

SEMI-RECESSED PENDENT SPRINKLERS IN AREAS WITH

SUSPENDED CEILINGS, AND FM APPROVED QUICK RESPONSE

UPRIGHT SPRINKLERS IN AREAS WITH NO CEILINGS.

SHEET NOTES:

1.

2.

3.

4.

DEMOLISH EXISTING FIRE PROTECTION

CABINET. REPAIR IN KIND THE EXTERIOR

WALL BEHIND CABINET.

KEYNOTES:#

1.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

DECEMBER 7, 2020

BID DOCUMENTS 621-15-101

FULLY SPRINKLERED F-101

FIRST FLOOR FIRE PROTECTION PLAN

DBNDS

SCALE: 3/8" = 1'-0"

F1

FIRST FLOOR FIRE PROTECTION PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

REVISIONS DATE

DECEMBER 7, 2020MARCH 15, 2021

LH LH

LH

LH

LH

LH LH LH

LHLH

OH2

OH2NS

LH

LH

NS

NS

CONFERENCE

ROOM

CHIEF OFFICE

ELECT.

LOBBY

200 MECHANICAL ROOM

HOUSE KEEPING

OFFICE

OFFICE

CORRIDOR

OFFICE

210OFFICE

MEN RESTROOM

MEN SHOWER &

LOCKER ROOM

WOMEN SHOWER &

LOCKER ROOM

206A

WOMEN RESTROOM

OIT

DEPUTY CHIEF

OFFICE

CORRIDOR

CORRIDOR

NS

NSNS

NS

NS NS

NSNSNS

SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.

FIRE SUPPRESSION SYSTEM SHALL BE DESIGNED IN ACCORDANCE

WITH NFPA 13 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN

MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:

A. VAFPDM

B. NFPA 13

CONTRACTOR SHALL COORDINATE ALL NEW SPRINKLER WORK

WITH OTHER TRADES AND EXISTING CONDITIONS.

CONTRACTOR SHALL PROVIDE FM APPROVED QUICK RESPONSE,

SEMI-RECESSED PENDENT SPRINKLERS IN AREAS WITH

SUSPENDED CEILINGS, AND FM APPROVED QUICK RESPONSE

UPRIGHT SPRINKLERS IN AREAS WITH NO CEILINGS.

SHEET NOTES:

1.

2.

3.

4.

ATTIC LEVEL SPRINKLER WATER SUPPLY. REFER TO F-103 FOR

CONTINUATION.

KEYNOTES:#

1.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

FULLY SPRINKLERED F-102

SECOND FLOOR FIRE PROTECTION

PLAN

DBNDS

SCALE: 3/8" = 1'-0"F1

SECOND FLOOR FIRE PROTECTION PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

REVISIONS DATE

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100

SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.

FIRE SUPPRESSION SYSTEM SHALL BE DESIGNED IN ACCORDANCE

WITH NFPA 13 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN

MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:

A. VAFPDM

B. NFPA 13

CONTRACTOR SHALL COORDINATE ALL NEW SPRINKLER WORK

WITH OTHER TRADES.

CONTRACTOR SHALL PROVIDE FM APPROVED QUICK RESPONSE,

SEMI-RECESSED PENDENT SPRINKLERS IN AREAS WITH

SUSPENDED CEILINGS, AND FM APPROVED QUICK RESPONSE

UPRIGHT SPRINKLERS IN AREAS WITH NO CEILINGS.

SHEET NOTES:

1.

2.

3.

4.

WALL SEPARATING COMBUSTIBLE ATTIC FROM COMBUSTIBLE

CONCEALED SPACE. BOTH REQUIRE SPRINKLER PROTECTION.

KEYNOTES:

ATTIC LEVEL SPRINKLER SUPPLY UP FROM SECOND FLOOR.

REFER TO F-102 FOR CONTINUATION.

1.

2.

AT

B3

F-103

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

FULLY SPRINKLERED F-103

ATTIC FIRE PROTECTION PLAN

DBNDS

SCALE: 3/8" = 1'-0"F1

ATTIC FIRE PROTECTION PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

SCALE: 1/4" = 1'-0"B3

ATTIC SPRINKLER SECTION VIEW

SCALE: = 1'-0"

0 4 84

1/4"

REVISIONS DATE

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100

F

VS

VS

VS

WF

S

VS

RTSRTS

S

MECHANICAL ROOM

B01

STORAGE

B02

CORRIDOR

B00

ARMORY /

WEAPONS

B04

CORRIDOR

B03

FA100

A1

FA100

A3

FA100

B5

SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.

FIRE ALARM SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH

NFPA 72 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN

MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:

A. VAFPDM

B. NFPA 72

SHEET NOTES:

1.

2.

WET-PIPE RISER FLOW SWITCH AND CONTROL VALVE

SUPERVISORY SWITCH.

BACKFLOW PREVENTER CONTROL VALVE SUPERVISORY

SWITCHES.

BACKFLOW PREVENTER TEST CONNECTION CONTROL

VALVE SUPERVISORY SWITCH.

APPROXIMATE LOCATION OF EXISTING VA FIRE ALARM

NETWORK FIBER OPTIC LOOP BUILDING ENTRANCE POINT

TO REMAIN. SEE KEYNOTE #3 ON F-501 FOR DEMOLITION

AND SYSTEM DOWNTIME NOTES.

3/4" GALVANIZED RIGID STEEL CONDUIT TO PIV

SUPERVISORY SWITCH. SEE SHEET C-110 FOR CONDUIT

ROUTE TO PIV.

KEYNOTES:

PLAN LEGEND

AREA OF NO FIRE ALARM

WORK

1.

2.

3.

4.

5.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

FULLY SPRINKLERED FA100

BASEMENT FIRE ALARM PLAN

DBNDS

SCALE: 3/8" = 1'-0"F1

BASEMENT FIRE ALARM PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

SCALE: N.T.S.

A1

FIBER OPTIC LINE

SCALE: N.T.S.

A3

FIBER OPTIC LOOP BOX

SCALE: N.T.S.

B5

EXISTING FACP AND FIBER OPTIC INTERFACE TO BE DEMOLISHED

REVISIONS DATE

SCALE: N.T.S.A1

FIBER OPTIC LINE

SCALE: N.T.S.A3

FIBER OPTIC LOOP BOX

SCALE: N.T.S.B5

EXISTING FACP AND FIBER OPTIC INTERFACE TO BE DEMOLISHED

A N

N

F

F

F

F A

C P

B A

T T S

CM

OFFICE

OFFICE

WOMEN RESTROOM

STAFF LOUNGE

MEN RESTROOM

CORRIDOR

CORRIDOR

OFFICER WORK

ROOM

INTERVIEW ROOM

EVIDENCE

PROCESSING

EVIDENCE ROOM

OFFICE

HOUSE KEEPING

WAITING ROOM

RECEPTION

ELECT.

OFFICE

OFFICE

15 15

SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.

FIRE ALARM SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH

NFPA 72 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN

MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:

A. VAFPDM

B. NFPA 72

SHEET NOTES:

1.

2.

CONTROL MODULE FOR ACTIVATION OF SMOKE CURTAIN.

KEYNOTES:#

1.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

FULLY SPRINKLERED FA101

FIRST FLOOR FIRE ALARM PLAN

DBNDS

SCALE: 3/8" = 1'-0"F1

FIRST FLOOR FIRE ALARM PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

REVISIONS DATE

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100

S

RTSRTS

S

CONFERENCE

ROOM

CHIEF OFFICE

ELECT.

LOBBY

MECHANICAL ROOM

HOUSE KEEPING

OFFICE

212 OFFICE

CORRIDOR

OFFICE

OFFICE

MEN RESTROOM

MEN SHOWER &

LOCKER ROOM

WOMEN SHOWER &

LOCKER ROOM

206A

WOMEN RESTROOM

OIT

DEPUTY CHIEF

OFFICE

CORRIDOR

CORRIDOR

WP

WP

SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.

FIRE ALARM SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH

NFPA 72 AND VETERANS AFFAIRS FIRE PROTECTION DESIGN

MANUAL. THE ORDER OF PREFERENCE OF CODE SHALL BE:

A. VAFPDM

B. NFPA 72

SHEET NOTES:

1.

2.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

FULLY SPRINKLERED FA102

SECOND FLOOR FIRE ALARM PLAN

DBNDS

SCALE: 3/8" = 1'-0"F1

SECOND FLOOR FIRE ALARM PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

REVISIONS DATE

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100

SIMPLEX

4100ES

FIRE

ALARM

CONTROL

PANEL

(FACP)

S

BATTERIES

SS

SIGNALING LINE CIRCUIT

(SLC)

NOTIFICATION

APPLIANCE CIRCUIT

(NAC)

SPEAKER CIRCUIT

120 VAC

F

VS WF

WET PIPE

SPRINKLER

SYSTEM

ANN

VS VS

BACKFLOW

PREVENTER

F V

VS

BACKFLOW

PREVENTER

TEST

HEADER

BREAKER POWER

PANEL

POWER

WP

VA FIBER OPTIC

FIRE ALARM

NETWORK

S S

RTS

VS

POST

INDICATOR

VALVE

CM

SMOKE

CURTAIN

SEE SHEET F-001 FOR GENERAL NOTES AND LEGEND.

FIRE ALARM FLOOR PLANS AND RISER DIAGRAM ARE

DIAGRAMMATIC AND NOT INTENDED TO SHOW EACH AND EVERY

COMPONENT, DEVICE, APPLIANCE, ETC. CONDUIT PATHWAYS

AND INTERCONNECTIONS SHALL BE DETERMINED BY THE

BUILDING FEATURES, VAFPDM, NFPA 70, NFPA 72, SYSTEM

MANUFACTURER REQUIREMENTS AND RECOMMENDATIONS.

SHEET NOTES

1.

2.

BREAKER SERVING THE FACP SHALL HAVE A RED MARKING

PER NFPA 72 SECTION 10.6.2.3 AND 10.6.5.2.4 AND PROVIDED

WITH A NON-SWEEP DEVICE (LOCK) PER NFPA 72; SECTION

10.6.5.4 IN ADDITION, MEET THE REQUIREMENTS OF NFPA 72;

SECTION 10.6.5.2.2, 10.6.5.2.5, AND 10.6.5.3.

FACP SHALL INDICATE THE LOCATION AND IDENTIFICATION

OF THE POWER PANEL WHERE THE POWER BREAKER IS

LOCATED PER NFPA 72 REQUIREMENTS.

THE CONTRACTOR SHALL MINIMIZE DOWNTIME OF THE VA

MEDICAL CENTER'S FIRE ALARM SYSTEMS BY PROVIDING A

TEMPORARY FIBER OPTIC CONNECTION TO BYPASS THE

EXISTING 4010 SIMPLEX PANEL DURING DEMOLITION OF THE

EXISTING FIRE ALARM SYSTEM TO MAINTAIN THE

OPERATION OF THE VA FIRE ALARM FIBER OPTIC LOOP.

AFTER THE NEW 4100ES FIRE ALARM CONTROL PANEL IS

INSTALLED, THE CONTRACTOR SHALL COMPLETE THE FIBER

OPTIC LOOP THROUGH THE NEW SIMPLEX 4100ES SYSTEM.

CONTRACTOR SHALL COORDINATE FIRE ALARM SYSTEM

DOWNTIME WITH THE VA MEDICAL CENTER.

REFER TO CIVIL DRAWING C-110 FOR ROUTING OF CONDUIT

TO POST INDICATOR VALVE SUPERVISORY DEVICE AND FOR

LOCATION OF THE POST INDICATOR VALVE.

KEYNOTES:#

1.

2.

3.

4.

S O

U N

D G

E N

E R

A L B

U

IL

D

IN

G A

L A

R M

A

F1 AREA SMOKE DETECTOR

FIRE ALARMS

SUPERVISORY SIGNALS

SYSTEM INPUTS

DUCT SMOKE DETECTOR S1

F2

SYSTEM OUTPUTS

F3

MANUAL PULL STATION

SPRINKLER WATERFLOW SWITCH

WATER CONTROL VALVE TAMPERS2

X X X

B

T R

A N

S M

IT

A

L A

R M

S

IG

N A

L T

O P

O L

IC

E

D

IS

P A

T C

H O

F F

IC

E

I N

B U

IL

D

IN

G

A

G

IN

E

E R

IN

G

B U

IL

D

IN

G

C X X X

D

X

S H

U T

D O

W N

A

IR

H A

N D

L E

R S

E R

V E

D B

Y T

H

T

E C

T O

R

X

X

T R

A N

S M

IT

S

U P

E R

V

IS

O R

Y S

IG

N

A L T

O

P O

L

IC

E D

IS

P

A T

C H

O F

F

IC

E I N

B U

IL

D

IN

G

A

D E

N G

IN

E

E R

IN

G

B U

IL

D

IN

G

E

A C

T

IV

A T

E S

M O

K E

C U

R T

A

IN

X X X

FIRST FLOOR

2' - 6 5/8"

Basement -7' - 3 5/8"

CHECK VALVE

4" PIPE TO FIRE

DEPARTMENT

CONNECTION

4" BUILDING

FIRE WATER

SUPPLY

4" DOUBLE

CHECK

BACKFLOW

PREVENTER

4" TO BACKFLOW

PREVENTER TEST

CONECTION

FLOW

SWITCH

INSPECTORS TEST

CONNECTION AND

DRAIN

BUTTERFLY

CONTROL

VALVE

TO ALL

BUILDING

SPRINKLERS

NORMALLY

CLOSED NORMALLY

OPEN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

FULLY SPRINKLERED F-501

FIRE PROTECTION DETAILS

DBNDS

SCALE: N.T.S.C1

FIRE ALARM RISER DIAGRAM

SCALE: N.T.S.E6

FIRE ALARM SEQUENCE OF OPERATIONS

SCALE: 1" = 1'-0"F1

WET-PIPE RISER DETAIL

SCALE: = 1'-0"

0 1 21

1"

REVISIONS DATE

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100

Sheets
F-001 - FIRE PROTECTION GENERAL NOTES & LEGEND
F-100 - BASEMENT FIRE PROTECTION PLAN
F-101 - FIRST FLOOR FIRE PROTECTION PLAN
F-102 - SECOND FLOOR FIRE PROTECTION PLAN
F-103 - ATTIC FIRE PROTECTION PLAN
FA100 - BASEMENT FIRE ALARM PLAN
FA101 - FIRST FLOOR FIRE ALARM PLAN
FA102 - SECOND FLOOR FIRE ALARM PLAN
F-501 - FIRE PROTECTION DETAILS