621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1D.pdf

PDF 4 MB Posted

Attached to
Z2DZ-36C249-21-AP-3182 - 621-15-101 - Correct Admin Bldg. -20 Environment & Condition Deficiencies
Solicitation number
36C24921B0014
Issued by

About this file

This is a presolicitation notice for a construction project to correct environment and condition deficiencies at an administration building at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The project scope includes office space, conference rooms, observation and interview rooms, evidence and storage rooms, locker rooms, mechanical and electrical rooms, an armory, lounge areas, waiting areas, restrooms, and replacement of finish materials. The construction range is estimated between $1 million and $5 million. The solicitation will be issued on or around October 20, 2021, with responses due on or around November 20, 2021. This will be procured as a 100% set-aside for SDVOSBs using sealed bidding per FAR Part 14.101. The NAICS code is 236220 and the size standard is $39.5 million. Questions must be submitted in writing to the identified contracting specialist by the specified date.

View the file

Other files

File Type Posted
36C24921B0014 0007.pdf PDF
S04- SITE VISIT ATTENDEES - Bldg 20 - 621-15-101.pdf PDF
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-16-2021.pdf PDF
36C24921B0014 0006.pdf PDF
S05 - VA Comprehensive Asbestos Containing Materials Inspection Report January 2010 - 2.pdf PDF
S06 - AMENDMENT 5 - 36C24921B0014 0005.pdf PDF
S05-Mountain Home TN - VA Asbestos O AND M Plan January 2010 -1.pdf PDF
S05-RFI RESPONSE QUESTIONS - B20 Correct FCA Deficiencies 12-23-2021.pdf PDF
S02-LBP DOC-Building 20 - 36C24921B0014.pdf PDF
S02-Building 20 ACM Report - 36C24921B0014.pdf PDF
S02- Solicitation - 36C24921B0014 - 621-15-101 - Amendment - 0004.pdf PDF
36C24921B0014 0003.pdf PDF
S06- AMENDMENT2 - CO AND PROJECT CONFIRMATION DATES - 36C24921B0014 0002.pdf PDF
S02-AMENDMENT1 - 621-15-101 CORRECT ADMIN BLDG 20 ENVIRONMENT COND DEF - BID SPECIFICATIONS.pdf PDF
S02- AMENDMENT 1 - 03 1200392 VA Bldg 20 ARCH 05 13 2021 Part 1.pdf PDF
S02- AMENDMENT 1 - 06 1200392 VA Bldg 20 PLMB 05 13 2021 Part 1.pdf PDF
S06-AMENDMENT 01 - 621-15-101 - 36C24921B0014 0001 - WB.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1A.pdf PDF
05 1200392 VA Bldg 20 FIRE 05 13 2021.pdf PDF
06 1200392 VA Bldg 20 PLMB 05 13 2021 Part 2.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 2D.pdf PDF
08 1200392 VA Bldg 20 ELEC 05 13 2021.pdf PDF
07 1200392 VA Bldg 20 MECH 05 13 2021.pdf PDF
09 1200392 VA Bldg 20 COMM 05 13 2021.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 2C.pdf PDF
S02-Contractor EMR Certification Form - 36C24921B0014.docx DOCX document
04 1200392 VA Bldg 20 INT 05 13 2021.pdf PDF
S02-TECHNICAL SPECS - Project 621-15-101.pdf PDF
02 1200392 VA Bldg 20 CIVIL 05 13 2021.pdf PDF
S02-621-15-101 - Correct Admin Bldg 20 .pdf PDF
01 1200392 VA Bldg 20 GEN 05 13 2021.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1B.pdf PDF
S02-WD - WASHINGTON TN - TN20210111 - JAN 2021.pdf PDF
03 1200392 VA Bldg 20 ARCH 05 13 2021 Part 2.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1C.pdf PDF
36C24921B0014.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TECHNICAL SPECIFICATIONS

VOLUME 1 OF 2 (Divisions 00-09)

Correct Admin Bldg. 20 Environment and

Condition Deficiencies

VA Project Number: 621-15-101

Department of Veterans Affairs MidSouth Healthcare Network

Quillen VA Medical Center

Lamont Street & Veterans Way Johnson City, TN 37604

Bid Documents

March 15, 2021

36C24919D0021 36C24919N0640 Raymond-Pond SDVOSB JV, LLC

1224 Royal Drive Suite 100

Conyers, GA 30094

RAYMOND PROJECT NUMBER – 1418.020

POND PROJECT NUMBER – 1200392

This Page Intentionally Left Blank

Project No. 621-15-101 March 15, 2021

Correct Admin Bldg.20 Environment and Condition Deficiencies Bid Documents

00 01 07 - 1

SECTION 00 01 07

PROFESSIONAL SEALS

1.1 DESIGN PROFESSIONALS OF RECORD

A. Architect:

1. Richard K. Perkins

2. Virginia #0401006332

3. Responsible for Divisions 02-12.

B. Fire Protection Engineer:

1. Brandon T. Hofstead

2. Georgia #037581

3. Responsible for Division 21 and Section 28 31 00.

C. Mechanical Engineer:

1. Charles A. Hanning III

2. Alabama #29025-E

3. Responsible for Divisions 22-23.

D. Electrical Engineer:

1. Floyd A. Keels

2. Tennessee #114650

3. Responsible for Division 26.

E. Telecommunication Designer:

1. Thomas Higgins

2. RCDD #348504

3. Responsible for Divisions 27-28.

F. Civil Engineer:

1. Tanya L. Norman

2. Georgia #038055

3. Responsible for Divisions 31-34.

- - - E N D - - -

03/15/2021

00 01 10 - 1

DEPARTMENT OF VETERANS AFFAIRS

VHA MASTER SPECIFICATIONS

TABLE OF CONTENTS

Section 00 01 10

SECTION NO. DIVISION AND SECTION TITLES DATE

VOLUME 1

DIVISION 00 - SPECIAL SECTIONS

00 01 07 Professional Seals

00 01 10 Table of Contents

00 01 15 List of Drawing Sheets 05-20

DIVISION 01 - GENERAL REQUIREMENTS

01 00 00 General Requirements (VISN 9 Mountain Home) 03-20

01 32 16.15 Project Schedules (Small Projects – Design/Bid/Build) 03-20

01 33 23 Shop Drawings, Product Data, and Samples 05-17

Submittal Register

01 35 26 Safety Requirements 02-20

01 42 19 Reference Standards 09-19

01 45 00 Quality Control 03-19

01 45 29 Testing Laboratory Services 11-18

01 57 19 Temporary Environmental Controls 01-11

01 58 16 Temporary Interior Signage 07-15

01 74 19 Construction Waste Management 09-13

DIVISION 02 – EXISTING CONDITIONS

02 41 00 Demolition 08-17

02 82 11 Traditional Asbestos Abatement 04-19

02 83 33.13 Lead-Based Paint Removal and Disposal 08-16

DIVISION 03 – CONCRETE

03 30 00 Cast-in-Place Concrete 07-19

DIVISION 04 – MASONRY

04 20 00 Unit Masonry 08-17

DIVISION 05 – METALS

05 12 00 Structural Steel Framing 11-18

05 50 00 Metal Fabrications 08-18

05 51 00 Metal Stairs 10-15

00 01 10 - 2

DIVISION 06 – WOOD, PLASTICS AND COMPOSITES

06 10 00 Rough Carpentry 10-17

06 20 00 Finish Carpentry 08-16

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

07 01 50.19 Preparation for Re-Roofing 02-16

07 21 13 Thermal Insulation 10-17

07 22 00 Roof and Deck Insulation 02-16

07 31 26 Slate Shingles 02-16

07 54 23 Thermoplastic Polyolefin (TPO) Roofing 08-16

07 60 00 Flashing and Sheet Metal 07-14

07 71 00 Roof Specialties 10-15

07 72 00 Roof Accessories 10-15

07 84 00 Firestopping 02-16

07 92 00 Joint Sealants 10-17

DIVISION 08 - OPENINGS

08 11 13 Hollow Metal Doors and Frames 08-16

08 14 00 Interior Wood Doors 02-16

08 31 13 Access Doors and Frames 02-16

08 56 19 Pass Windows 02-16

08 71 00 Door Hardware 04-20

08 80 00 Glazing 10-15

08 90 00 Louvers and Vents 05-15

DIVISION 09 – FINISHES

09 05 16 Subsurface Preparation for Floor Finishes 02-15

09 06 00 Schedule for Finishes 04-15

09 22 16 Non-Structural Metal Framing 06-18

09 29 00 Gypsum Board 04-20

09 30 13 Ceramic Tiling 09-15

09 51 00 Acoustical Ceilings 12-18

09 65 13 Resilient Base and Accessories 02-16

09 65 19 Resilient Tile Flooring 05-18

09 68 00 Carpeting 10-15

09 91 00 Painting 01-16

VOLUME 2

DIVISION 10 – SPECIALTIES

10 14 00 Signage 10-15

10 21 13 Toilet Compartments 12-15

10 21 16 Shower and Dressing Compartments 08-16

10 26 00 Wall and Door Protection 10-15

10 28 00 Toilet, Bath, and Laundry Accessories 02-16

10 44 13 Fire Extinguisher Cabinets 08-18

00 01 10 - 3

DIVISION 11 – EQUIPMENT (NOT USED)

DIVISION 12 – FURNISHINGS

12 24 00 Window Shades 08-17

12 36 00 Countertops 12-18

DIVISION 13 - SPECIAL CONSTRUCTION (NOT USED)

DIVISION 14 – CONVEYING EQUIPMENT (NOT USED)

DIVISION 21 - FIRE SUPPRESSION

21 13 13 Wet-Pipe Sprinkler Systems 06-15

DIVISION 22 – PLUMBING

22 05 11 Common Work Results for Plumbing 07-16

22 05 12 General Motor Requirements for Plumbing Equipment 09-15

22 05 19 Meters and Gages for Plumbing Piping 09-15

22 05 23 General-Duty Valves for Plumbing Piping 09-15

22 07 11 Plumbing Insulation 09-19

22 11 00 Facility Water Distribution 11-19

22 11 23 Domestic Water Pumps 09-15

22 13 00 Facility Sanitary and Vent Piping 09-15

22 33 00 Electric Domestic Water Heaters 09-15

22 40 00 Plumbing Fixtures 09-15

DIVISION 23 – HEATING, VENTILATING, AND AIR CONDITIONING

23 05 11 Common Work Results for HVAC 02-20

23 05 12 General Motor Requirements for HVAC and Steam Generation

Equipment

02-20

23 05 41 Noise and Vibration Control for HVAC Piping and Equipment 02-20

23 05 93 Testing, Adjusting, and Balancing for HVAC 02-20

23 07 11 HVAC and Boiler Plant Insulation 02-20

23 09 23 Direct-Digital Control System for HVAC 09-11

23 23 00 Refrigerant Piping 02-20

23 31 00 HVAC Ducts and Casings 02-20

23 34 00 HVAC Fans 02-20

23 37 00 Air Outlets and Inlets 02-20

23 82 00 Convection Heating and Cooling Units 03-20

DIVISION 25 – INTEGRATED AUTOMATION (NOT USED)

DIVISION 26 – ELECTRICAL

26 05 11 Requirements for Electrical Installations 01-16

26 05 19 Low-Voltage Electrical Power Conductors and Cables 01-17

26 05 26 Grounding and Bonding for Electrical Systems 01-17

26 05 33 Raceway and Boxes for Electrical Systems 01-18

26 09 23 Lighting Controls 01-18

00 01 10 - 4

26 24 16 Panelboards 01-18

26 27 26 Wiring Devices 01-18

26 29 21 Enclosed Switches and Circuit Breakers 01-17

26 41 00 Facility Lightning Protection 01-17

26 43 13 Surge Protective Devices 01-17

26 51 00 Interior Lighting 01-18

26 56 00 Exterior Lighting 01-18

DIVISION 27 – COMMUNICATIONS

27 05 11 Requirements for Communications Installations 09-19

27 05 26 Grounding and Bonding for Communications Systems 06-15

27 05 33 Raceways and Boxes for Communications Systems 10-18

27 10 00 Control, Communication and Signal Wiring 06-15

27 11 00 Communications Equipment Room Fittings 06-15

27 15 00 Communications Structured Cabling 01-16

DIVISION 28 – ELECTRONIC SAFETY AND SECURITY

28 05 00 Common Work Results for Electronic Safety and Security 04-18

28 05 26 Grounding and Bonding for Electronic Safety and Security 09-11

28 05 28.33 Conduits and Backboxes for Electronic Safety and Security 09-11

28 31 00 Fire Detection and Alarm 10-11

DIVISION 31 – EARTHWORK

31 20 11 Earthwork (Short Form) 10-12

DIVISION 32 – EXTERIOR IMPROVEMENTS

32 05 23 Cement and Concrete for Exterior Improvements 08-16

32 12 16 Asphalt Paving 09-15

32 17 23 Pavement Markings 08-16

DIVISION 33 – UTILITIES

33 10 00 Water Utilities 03-17

DIVISION 34 – TRANSPORTATION

34 71 13 Passive Vehicle Barriers 04-18

DIVISION 48 – ELECTRICAL POWER GENERATION (NOT USED)

08 80 00 - 1

SECTION 08 80 00

GLAZING

PART 1 - GENERAL

1.1 DESCRIPTION:

A. This section specifies the following:

1. Glass.

2. Plastic glazing.

3. Glazing materials and accessories for both factory and field glazed assemblies.

1.2 RELATED WORK:

A. Factory glazed by manufacturer in following units:

1. Sound resistant doors: Section 08 11 13, HOLLOW METAL DOORS AND

FRAMES, and Section 08 14 00, WOOD DOORS.

2. Mirrors: Section 10 28 00, TOILET, BATH, AND LAUNDRY ACCESSORIES.

1.3 LABELS:

A. Temporary labels:

1. Provide temporary label on each light of glass and plastic material identifying manufacturer or brand and glass type, quality and nominal thickness.

2. Label in accordance with NFRC label requirements.

3. Temporary labels are to remain intact until glass and plastic material is approved by Contracting Officer Representative (COR).

B. Permanent labels:

1. Locate in corner for each pane.

2. Label in accordance with ANSI Z97.1 and SGCC label requirements.

a. Tempered glass.

b. Laminated glass or have certificate for panes without permanent label.

c. Organic coated glass.

3. Bullet resistance glass or plastic assemblies:

a. Bullet resistance glass or plastic assemblies in accordance with

UL 752 requirements for power rating specified.

b. Identify each security glazing permanently with glazing manufacturer's name, date of manufacture, product number, and DOS

Code number inconspicuously located in lower corner on protective side and visible after glazing is framed.

08 80 00 - 2

c. The "attack (threat) side" is to be identified in bold lettering on each side of glazing with removable label.

4. Fire rated glazing assemblies: Mark in accordance with IBC.

1.4 PERFORMANCE REQUIREMENTS:

A. General: Design glazing system consistent with guidance and practices presented in the GANA Glazing Manual, GANA Laminated Glazing Manual, and GANA Sealant Manual, as applicable to project. Installed glazing is to withstand applied loads, thermal stresses, thermal movements, building movements, permitted tolerances, and combinations of these conditions without failure, including loss or glass breakage attributable to defective manufacture, fabrication, or installation;

failure of sealants or gaskets to remain watertight and airtight;

deterioration of glazing materials; unsafe engagement of the framing system; deflections beyond specified limits; or other defects in construction.

B. Glazing Unit Design: Design glass, including engineering analysis meeting requirements of authorities having jurisdiction. Thicknesses listed are minimum. Coordinate thicknesses with framing system manufacturers.

1. Design glass in accordance with ASTM E1300, and for conditions beyond the scope of ASTM E1300, by a properly substantiated structural analysis.

2. Design Wind Pressures: In accordance with applicable code.

3. Wind Design Data: In accordance with applicable code.

4. Maximum Lateral Deflection: For glass supported on all four edges, limit center-of-glass deflection at design wind pressure to not more than the structural capacity of the glazing unit, the threshold at which frame engagement is no longer safely assured, 1/100 times the short-side length.

C. Ballistic- and Blast- resistant glass or plastic glazing assemblies:

1. For blast-resistant and ballistic-resistant units comply with requirements in UFC 4-010-01, Physical Security Design Manual for VA

Facilities, and project-specific criteria provided by VA.

2. Spall Resistance: Laminated glazing is not permitted to produce spall to interior (protected side) when impacted with scheduled ballistics.

3. Tolerances:

08 80 00 - 3

a. Outside dimensions: Overall outside dimensions (height and width) of laminated security glazing is to maintain tolerance of 3 mm

( 0.12 inch).

b. Warpage: Out-of-flat (warpage or bowing) condition of laminates is not to exceed 2.5 mm per lineal meter (0.10 inch per

3.3 lineal foot). The condition, if present, is to be localized to extent not greater than 0.75 mm (0.03 inch) for any 0.3 meter

(0.98 feet) section.

D. Windborne-Debris-Impact Resistance: Comply with enhanced-protection testing requirements in ASTM E1996 for project wind zone when tested according to ASTM E1886, based upon testing of specimens not less than the size required for project and utilizing installation method identical to that specified for project.

1. Project Wind Zone: Wind Zone 1.

2. Large-Missile Test: For glazing located within 9.1 m (30 feet) of grade.

3. Small-Missile Test: For glazing located more than 9.1 m (30 feet) above grade.

E. Building Enclosure Vapor Retarder and Air Barrier:

1. Utilize the inner pane of multiple pane sealed units for the continuity of the air barrier and vapor retarder seal.

2. Maintain a continuous air barrier and vapor retarder throughout the glazed assembly from glass pane to heel bead of glazing sealant.

1.5 SUBMITTALS:

A. In accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND

SAMPLES.

B. Sustainable Design Submittals (NOT USED)

C. Manufacturer's Certificates:

1. Certificate stating that fire-protection and fire-resistive glazing units meet code requirements for fire-resistance-rated assembly and applicable safety glazing requirements.

2. Certificate on solar heat gain coefficient when value is specified.

3. Certificate on "R" value when value is specified.

4. Certificate test reports confirming compliance with specified bullet resistive rating.

5. Certificate that blast resistant glass meets the specified requirements.

D. Manufacturer Warranty.

08 80 00 - 4

E. Manufacturer's Literature and Data:

1. Glass, each kind required.

2. Insulating glass units.

3. Transparent (one-way vision glass) mirrors.

4. Elastic compound for metal sash glazing.

5. Putty, for wood sash glazing.

6. Glazing cushion.

7. Sealing compound.

8. Bullet resistive material.

9. Plastic glazing material, each type required.

F. Samples:

1. Size: 305 mm by 305 mm (12 inches by 12 inches).

2. Tinted glass.

3. Reflective glass.

4. Transparent (one-way vision glass) mirrors.

G. Preconstruction Adhesion and Compatibility Test Report: Submit glazing sealant manufacturer’s test report indicating glazing sealants were tested for adhesion to glass and glazing channel substrates and for compatibility with glass and other glazing materials.

1.6 DELIVERY, STORAGE AND HANDLING:

A. Delivery: Schedule delivery to coincide with glazing schedules so minimum handling of crates is required. Do not open crates except as required for inspection for shipping damage.

B. Storage: Store cases according to printed instructions on case, in areas least subject to traffic or falling objects. Keep storage area clean and dry.

C. Handling: Unpack cases following printed instructions on case. Stack individual windows on edge leaned slightly against upright supports with separators between each.

D. Protect laminated security glazing units against face and edge damage during entire sequence of fabrication, handling, and delivery to installation location. Provide protective covering on exposed faces of glazing plastics, and mark inside as "INTERIOR FACE" or "PROTECTED

FACE":

1. Treat security glazing as fragile merchandise, and packaged and shipped in export wood cases with width end in upright position and blocked together in a mass. Storage and handling to comply with manufacturer's directions and as required to prevent edge damage or

08 80 00 - 5 other damage to glazing resulting from effects of moisture, condensation, temperature changes, direct exposure to sun, other environmental conditions, and contact with chemical solvents.

2. Protect sealed-air-space insulating glazing units from exposure to abnormal pressure changes, as could result from substantial changes in altitude during delivery by air freight. Provide temporary breather tubes which do not nullify applicable warranties on hermetic seals.

3. Temporary protections: The glass front and polycarbonate back of glazing are to be temporarily protected with compatible, peelable, heat-resistant film which will be peeled for inspections and re-applied and finally removed after doors and windows are installed at destination. Since many adhesives will attack polycarbonate, the film used on exposed polycarbonate surfaces is to be approved and applied by manufacturer.

4. Edge protection: To cushion and protect glass clad, and polycarbonate edges from contamination or foreign matter, the four (4) edges are to be sealed the depth of glazing with continuous standard-thickness thermoplastic rubber tape. Alternatively, continuous channel shaped extrusion of thermoplastic rubber are to be used, with flanges extending into face sides of glazing.

5. Protect "Constant Temperature" units including every unit where glass sheet is directly laminated to or directly sealed with metal-tube type spacer bar to polycarbonate sheet, from exposures to ambient temperatures outside the range of 16 to 24 degrees C (60 to

75 degrees F), during the fabricating, handling, shipping, storing, installation, and subsequent protection of glazing.

1.7 PROJECT CONDITIONS:

Field Measurements: Field measure openings before ordering tempered glass products to assure for proper fit of field measured products.

1.8 WARRANTY:

A. Construction Warranty: Comply with the FAR clause 52.246-21 “Warranty of Construction”.

B. Manufacturer Warranty: Manufacturer shall warranty their glazing from the date of installation and final acceptance by the Government as follows. Submit manufacturer warranty.

1. Bullet resistive plastic material to remain visibly clear without discoloration for 10 years.

08 80 00 - 6

2. Insulating glass units to remain sealed for ten (10) years.

3. Laminated glass units to remain laminated for five (5) years.

4. Polycarbonate to remain clear and ultraviolet light stabilized for five (5) years.

5. Insulating plastic to not have more than 6 percent decrease in light transmission and be ultraviolet light stabilized for ten (10) years.

1.9 APPLICABLE PUBLICATIONS:

A. Publications listed below form a part of this specification to extent referenced. Publications are referenced in text by basic designation only.

B. American Architectural Manufacturers Association (AAMA):

800.....................Test Methods for Sealants

810.1-77................Expanded Cellular Glazing Tape

C. American National Standards Institute (ANSI):

Z97.1-14................Safety Glazing Material Used in

Building - Safety Performance Specifications and Methods of Test

D. American Society of Civil Engineers (ASCE):

7-10....................Wind Load Provisions

E. ASTM International (ASTM):

C542-05(R2011)..........Lock-Strip Gaskets

C716-06.................Installing Lock-Strip Gaskets and Infill

Glazing Materials

C794-10.................Adhesion-in-Peel of Elastomeric Joint Sealants

C864-05(R2011)..........Dense Elastomeric Compression Seal Gaskets, Setting Blocks, and Spacers

C920-14a................Elastomeric Joint Sealants

C964-07(R2012)..........Standard Guide for Lock-Strip Gasket Glazing

C1036-11(R2012).........Flat Glass

C1048-12................Heat-Treated Flat Glass-Kind HS, Kind FT Coated and Uncoated Glass.

C1172-14................Laminated Architectural Flat Glass

C1349-10................Standard Specification for Architectural Flat

Glass Clad Polycarbonate

C1376-10................Pyrolytic and Vacuum Deposition Coatings on

Flat Glass

08 80 00 - 7

D635-10.................Rate of Burning and/or Extent and Time of

Burning of Self-Supporting Plastic in a

Horizontal Position

D4802-10................Poly (Methyl Methacrylate) Acrylic Plastic

Sheet

E84-14..................Surface Burning Characteristics of Building

Materials

E119-14.................Standard Test Methods for Fire Test of Building

Construction and Material

E1300-12a...............Load Resistance of Glass in Buildings

E1886-13a...............Standard Test Method for Performance of

Exterior Windows, Curtain Walls, Doors, and

Impact Protective Systems Impacted by

Missile(s) and Exposed to Cyclic Pressure

Differentials

E1996-14a...............Standard Specification for Performance of

Exterior Windows, Curtain Walls, Doors, and

Impact Protective Systems Impacted by Windborne

Debris in Hurricanes

E2141-12................Test Methods for Assessing the Durability of

Absorptive Electrochromic Coatings on Sealed

Insulating Glass Units

E2190-10................Insulating Glass Unit

E2240-06................Test Method for Assessing the Current-Voltage

Cycling Stability at 90 Degree C (194 Degree F) of Absorptive Electrochromic Coatings on Sealed

Insulating Glass Units

E2241-06................Test Method for Assessing the Current-Voltage

Cycling Stability at Room Temperature of

Absorptive Electrochromic Coatings on Sealed

Insulating Glass Units

E2354-10................Assessing the Durability of Absorptive

Electrochromic Coatings within Sealed

Insulating Glass Units

E2355-10................Test Method for Measuring the Visible Light

Transmission Uniformity of an Absorptive

Electrochromic Coating on a Glazing Surface

08 80 00 - 8

F1233-08................Standard Test Method for Security Glazing

Materials and Systems

F1642-12................Test Method for Glazing and Glazing Systems

Subject to Airblast Loadings

E. Code of Federal Regulations (CFR):

16 CFR 1201-10..........Safety Standard for Architectural Glazing

Materials

F. Glass Association of North America (GANA):

2010 Edition............GANA Glazing Manual

2008 Edition............GANA Sealant Manual

2009 Edition............GANA Laminated Glazing Reference Manual

2010 Edition............GANA Protective Glazing Reference Manual

G. International Code Council (ICC):

IBC.....................International Building Code

H. Insulating Glass Certification Council (IGCC)

I. Insulating Glass Manufacturer Alliance (IGMA):

TB-3001-13..............Guidelines for Sloped Glazing

TM-3000.................North American Glazing Guidelines for Sealed

Insulating Glass Units for Commercial and

Residential Use

J. Intertek Testing Services – Warnock Hersey (ITS-WHI)

K. National Fire Protection Association (NFPA):

80-16...................Fire Doors and Windows

252-12..................Fire Tests of Door Assemblies

257-12..................Standard on Fire Test for Window and Glass

Block Assemblies

L. National Fenestration Rating Council (NFRC)

M. Safety Glazing Certification Council (SGCC) 2012:

Certified Products Directory (Issued Semi-Annually).

N. Underwriters Laboratories, Inc. (UL):

9-08(R2009).............Fire Tests of Window Assemblies

263-14..................Fire Tests of Building Construction and

Materials

752-11..................Bullet-Resisting Equipment.

O. Unified Facilities Criteria (UFC):

4-010-01-03(R2007)......DOD Minimum Antiterrorism Standards for

Buildings

P. U.S. Veterans Administration:

08 80 00 - 9

Physical Security Design Manual for VA Facilities (VAPSDG); Life Safety

Protected

Physical Security Design Manual for VA Facilities (VAPSDG); Mission

Critical Facilities

Architectural Design Manual for VA Facilities (VASDM)

Q. Environmental Protection Agency (EPA):

40 CFR 59(2014).........National Volatile Organic Compound Emission

Standards for Consumer and Commercial Products

PART 2 - PRODUCT

2.1 GLASS:

A. Provide minimum thickness stated and as additionally required to meet performance requirements.

1. Provide minimum 6 mm (1/4 inch) thick glass units unless otherwise indicated.

B. Obtain glass units from single source from single manufacturer for each glass type.

C. Clear Glass:

1. ASTM C1036, Type I, Class 1, Quality q3.

D. Ultra-clear-Low-Iron Float Glass:

1. ASTM C1036, Type I, Class 1, Quality q3 and with visible light transmission of not less than 90 percent.

E. Tinted Heat reflective and low emissivity coated glass:

1. ASTM C1036, Type I, Class 2, Quality q3.

F. Patterned and Wired Flat Glass:

1. ASTM C1036, Type II, Class 1, Pattern Pl, Finish F1, Quality Q5, Mesh m1.

2.2 HEAT-TREATED GLASS:

A. Roller Wave Limits for Heat-Treated Glass: Orient all roller wave distortion parallel to bottom surface of glazing, and provide units complying with the following limitations:

1. Measurement Parallel to Line: Maximum peak to valley 0.203 mm

(0.008 inch).

2. Measurement Perpendicular to Line: Maximum 0.0254 mm (0.001 inch).

3. Bow/Warp: Maximum 50 percent of bow and warp allowed by ASTM C1048.

B. Clear Heat Strengthened Glass:

1. ASTM C1048, Kind HS, Condition A, Type I, Class 1, Quality q3.

C. Tinted Heat Strengthened Glass:

1. ASTM C1048, Kind HS, Condition A, Type I, Class 2, Quality q3.

08 80 00 - 10

D. Clear Tempered Glass:

1. ASTM C1048, Kind FT, Condition A, Type I, Class 1, Quality q3.

E. Tinted Tempered Glass.

1. ASTM C1048, Kind FT, Condition A, Type I, Class 2, Quality q3.

F. Tempered Patterned Glass:

1. ASTM C1048, Kind FT, Type II, Class 1, Form 3, finish, pattern and quality as scheduled.

2.3 COATED GLASS:

A. Reflective-Coated Spandrel Glass:

1. ASTM C1376, Kind CS and ASTM C1048, Kind HS, Condition B, Type I.

B. Reflective-Coated Low-E Coated Tempered Glass:

1. ASTM C1376 and ASTM C1048, Kind FT, Condition C, Type I, Class 1, Quality q3 with reflective metallic coating.

C. Ceramic Coated Vision Glass:

1. ASTM C1048, Kind HS or FT, Condition C, Type I, Quality q3 with ceramic coating applied by silk-screen process.

2. Pattern as scheduled.

D. Silicone Coated Spandrel Glass:

1. ASTM C1048, Kind HS or FT, Condition B, Type I, Quality q3 with silicone coating applied over glass surface.

2. Pattern as scheduled.

E. Transparent Mirror (One-Way-Vision Glass):

1. ASTM C1036, Type I, Class 1, Quality q2 or Class 3, Quality q3; Grey

Glass.

2. Thickness, 6 mm (1/4 inch).

3. Coated one face with a hard adherent reflective film of chromium or other coating of proven equivalent durability.

4. Visible light transmittance; eight percent, plus or minus two percent.

5. Visible reflectance; sixty percent, plus or minus five percent.

6. Light ratio; mirror side 10 or more; observer side one or less.

7. Assemble with coating covered and protected with a layer of clear glass not less than 3 mm (1.8 inch) thick.

8. Clean interface glass prior to assembly.

9. Tape edge to seal interface and hold panes together.

2.4 ELECTROCHROMIC COATED GLASS (NOT USED)

2.5 PLASTIC GLAZING:

08 80 00 - 11

Thickness Long Dimension of Sheet

3 mm (0.125 inch)

610 mm (24 inches or less)

5 mm (0.187 inch)

610 - 915 mm (24 through 36 inches)

6.5 mm (0.250 inch)

915 – 1524 mm (36 through 60 inches)

1. For polycarbonate use not less than the following minimum thickness:

Thickness Long

Dimension of Sheet

Edge Lap

3 mm (0.125 in ch)

610 – 1219 mm (24 through 48 inches)

19 mm (3/4 inch)

9.5 mm (0.375 inch)

1219 – 1524 mm (48 through 60 inches)

25 mm (3/4 inch)

13 mm (Over 0.50 inch)

1524 mm (Over 60 inches)

25 mm (1 inch)

2. Check: Window, door, and plastic manufacturer for glazing rabbet depth allowing for expansion and edge lap required for plastic.

3. Acrylic plastics have flame spreads that limit use on interior spaces.

A. Clear Acrylic Sheet:

1. ASTM D4802. Type UVF, Category A-1, clear, smooth both sides, and formulated with ultraviolet absorber.

2. Thickness, as scheduled.

B. Clear Acrylic Sheet, Abrasion Resistant:

1. ASTM D4802. Type UVF, Category A-1, Finish 3, clear, smooth, formulated with ultraviolet absorber, and having an abrasive resistant coating on both sides.

2. Thickness, as scheduled.

C. Clear Polycarbonate Sheet:

1. ASTM C1349, Appendix X1, Type II, (coated mar-resistant, UV stabilized), with coating on both sides. Flame spread of 10 or less when tested per ASTM E84.

08 80 00 - 12

2. Thickness, as scheduled.

2.6 LAMINATED GLASS:

A. Laminated Glass: ASTM C1172. Two or more lites of glass bonded with polyvinyl butyral, ionomeric polymer, or cast-in-place and cured-transparent-resin interlayer complying with interlayer manufacturer's written instructions.

B. Interlayer: Use min. 0.75 mm (0.030 inch) thick interlayer for vertical glazing unless otherwise scheduled.

C. Interlayer: Use 1.5 mm (0.060 inch) thick interlayer for:

1. Horizontal or sloped glazing.

2. Acoustical glazing.

3. Assemblies requiring heat strengthened or fully tempered glass.

D. Interlayer: Use 2.28 mm (0.090 inch) thick interlayer where required to meet performance requirements.

E. Interlayer Color: Clear, unless otherwise scheduled.

2.7 SECURITY GLAZING ASSEMBLY:

A. Provide ballistic level as scheduled in accordance with UL 752.

B. Forced Entry Resistance: As scheduled, in accordance with ASTM F1233.

C. Blast Resistance: Provide exterior glazing units and interior security glazing units providing protection based upon hazard rating as scheduled, in accordance with ASTM F1642, and peak pressure and positive phase impulse indicated.

D. Laminated Glass Security Glazing Units: Fabricate from multiple lites of scheduled glass with polyvinyl butyral, ionomeric polymer, or cast-in-place and cured-transparent resin interlayers between the layers of glazing.

2.8 INSULATING GLASS UNITS:

A. Provide factory fabricated, hermetically sealed glass unit consisting of two panes of glass separated by a dehydrated air space and comply with ASTM E2190.

B. Assemble units using glass types specified in Insulating Glass

Schedule.

2.9 FIRE PROTECTION AND FIRE RESISTANCE GLAZING:

A. Fire-Protection-Rated Glazing: Glazing units tested for use in fire door assemblies or fire windows, UL, ITS-WHI or equivalent listed and labeled by testing agency in accordance with IBC, for fire-protection ratings as scheduled, based upon positive-pressure testing per NFPA 257 or UL 9, and complying with NFPA 80.

08 80 00 - 13

1. Hose-Stream Test: Units must comply, except units having fire-protection rating of 20 minutes.

2. Temperature Rise Limitation: Units over 0.065 sq. m (100 sq. in.)

must comply with 232 deg. C (450 deg. F) limitation.

3. Labeling: Permanently label fire-protection-rated glazing units in accordance with IBC.

4. Safety Glazing: Comply with 16 CFR 1201, Category II.

5. Fire-Protection-Rated Tempered Glass: For 20-minute fire-protection-rated door assemblies, of thickness scheduled.

6. Fire-Protection-Rated Laminated Ceramic Glazing: Units made from two lites of clear, ceramic glass, 8 mm (5/16 inch) total thickness, for rating scheduled.

7. Fire-Protection-Rated Laminated Glass with Intumescent Interlayers:

Units made from multiple lites of uncoated, ultra-clear (low-iron) float glass, in intumescent interlayers, of thickness and rating scheduled.

B. Fire-Resistance-Rated Glazing: Glazing units tested for use in fire wall assemblies, UL, ITS-WHI or equivalent listed and labeled by testing agency in accordance with IBC for fire-resistance ratings of wall assemblies as, based upon testing according to NFPA 252 and ASTM

E119 or UL 263.

1. Labeling: Permanently label fire-resistance-rated glazing units in accordance with IBC.

2. Safety Glazing: Comply with 16 CFR 1201, Category II.

3. Fire-Resistance-Rated Laminated Glass with Intumescent Interlayers:

Units made from multiple lites of uncoated, ultra-clear low-iron float glass, in intumescent interlayers, of thickness and rating scheduled.

4. Fire-Resistance-Rated Double Glazing Units with Gel Fill: Units made from two lites of uncoated, fully tempered, ultra-clear (low-iron) float glass, with perimeter metal spacer and edge seal forming cavity filled with clear, fully transparent, heat-absorbing gel, of thickness and fire-protection rating scheduled.

2.10 SWITCHABLE PRIVACY GLASS (NOT USED)

2.11 INSULATING PLASTIC SHEETS:

A. Homogenous polycarbonate assembly integrally joined face sheets separated by either vertical or angled ribs forming airspace cells between face sheets:

08 80 00 - 14

1. Treated to prevent ultraviolet light discoloration and mar-resistant coated on both sides.

2. Flammability Rating: Combustibility classification CC1 by UL, ITS-WHI or any other certified testing agency when tested in accordance with ASTM D635 showing a burn rating of 25.4 mm (1 inch) or less.

3. Flame-spread index: 25.

4. Thickness: 9.5 mm (3/8 inch) minimum, 17.4 mm (11/16 inch) maximum.

5. Thermal: Maximum U factors 0.55 when tested in accordance with

ASTM C236.

6. Impact Resistance: No rupture when subjected to a falling dart with

13 mm (1/2 inch) radius tip at 298 J (220 ft. lbs.).

B. Clear:

1. Light Transmission: Not less than 70 percent.

2. Shading Coefficient: Not less than 50 percent.

2.12 GLAZING ACCESSORIES:

A. As required to supplement the accessories provided with the items to be glazed and to provide a complete installation. Ferrous metal accessories exposed in the finished work are to have a finish that will not corrode or stain while in service. Fire rated glazing to be installed with glazing accessories in accordance with the manufacturer’s installation instructions.

B. Setting Blocks: ASTM C864:

1. Silicone type.

2. Channel shape; having 6 mm (1/4 inch) internal depth.

3. Shore A hardness of 80 to 90 Durometer.

4. Block lengths: 50 mm (2 inches) except 100 to 150 mm (4 to 6 inches) for insulating glass.

5. Block width: Approximately 1.6 mm (1/16 inch) less than the full width of the rabbet.

6. Block thickness: Minimum 4.8 mm (3/16 inch). Thickness sized for rabbet depth as required.

C. Spacers: ASTM C864:

1. Channel shape having a 6 mm (1/4 inch) internal depth.

2. Flanges not less 2.4 mm (3/32 inch) thick and web 3 mm (1/8 inch) thick.

3. Lengths: 25 to 76 mm (1 to 3 inches).

4. Shore A hardness of 40 to 50 Durometer.

08 80 00 - 15

D. Glazing Tapes:

1. Semi-solid polymeric based closed cell material exhibiting pressure-sensitive adhesion and withstanding exposure to sunlight, moisture, heat, cold, and aging.

2. Shape, size and degree of softness and strength suitable for use in glazing application to prevent water infiltration.

3. Complying with AAMA 800 for the following types:

a. AAMA 810.1, Type 1, for glazing applications in which tape acts as the primary sealant.

b. AAMA 810.1, Type 2, for glazing applications in which tape is used in combination with a full bead of liquid sealant.

E. Spring Steel Spacer: Galvanized steel wire or strip designed to position glazing in channel or rabbeted sash with stops.

F. Glazing Clips: Galvanized steel spring wire designed to hold glass in position in rabbeted sash without stops.

G. Glazing Points (Sprigs): Pure zinc stock, thin, flat, triangular or diamond shaped pieces, 6 mm (1/4 inch) minimum size.

H. Glazing Gaskets: ASTM C864:

1. Firm dense wedge shape for locking in sash.

2. Soft, closed cell with locking key for sash key.

3. Flanges may terminate above the glazing-beads or terminate flush with top of beads.

I. Lock-Strip Glazing Gaskets: ASTM C542, shape, size, and mounting as indicated.

J. Glazing Sealants: ASTM C920, silicone neutral cure:

1. Type S.

2. Class 25 or 50 as recommended by manufacturer for application.

3. Grade NS.

4. Shore A hardness of 25 to 30 Durometer.

5. VOC Content: For sealants used inside the weatherproofing system, not more than 250 g/L or less when calculating according to 40 CFR

59, (EPA Method 24).

K. Structural Sealant: ASTM C920, silicone acetoxy cure:

1. Type S.

2. Class 25.

3. Grade NS.

4. Shore a hardness of 25 to 30 Durometer.

08 80 00 - 16

L. Neoprene, EPDM, or Vinyl Glazing Gasket: ASTM C864.

1. Channel shape; flanges may terminate above the glazing channel or flush with the top of the channel.

2. Designed for dry glazing.

M. Color:

1. Color of glazing compounds, gaskets, and sealants used for aluminum color frames to match color of the finished aluminum and be nonstaining.

2. Color of other glazing compounds, gaskets, and sealants which will be exposed in the finished work and unpainted are to be black, gray, or neutral color.

N. Smoke Removal Unit Targets: Adhesive targets affixed to glass to identify glass units intended for removal for smoke control. Comply with requirements of local Fire Department.

PART 3 - EXECUTION

3.1 EXAMINATION:

A. Verification of Conditions:

1. Examine openings for glass and glazing units; determine they are proper size; plumb; square; and level before installation is started.

2. Verify that glazing openings conform with details, dimensions and tolerances indicated on manufacturer is approved shop drawings.

B. Review for conditions which may adversely affect glass and glazing unit installation, prior to commencement of installation. Do not proceed with installation until unsatisfactory conditions have been corrected.

C. Verify that wash down of adjacent masonry is completed prior to erection of glass and glazing units.

3.2 PREPARATION:

A. For sealant glazing, prepare glazing surfaces in accordance with

GANA Sealant Manual.

B. Determine glazing unit size and edge clearances by measuring the actual unit to receive the glazing.

C. Shop fabricate and cut glass with smooth, straight edges of full size required by openings to provide GANA recommended edge clearances.

D. Verify that components used are compatible.

E. Clean and dry glazing surfaces.

08 80 00 - 17

F. Prime surfaces scheduled to receive sealants, as determined by preconstruction sealant-substrate testing.

3.3 INSTALLATION – GENERAL:

A. Install in accordance with GANA Glazing Manual, GANA Sealant Manual, IGMA TB-3001, and IGMA TM-3000 unless specified otherwise.

B. Glaze in accordance with recommendations of glazing and framing manufacturers, and as required to meet the Performance Test

Requirements specified in other applicable sections of specifications.

C. Set glazing without bending, twisting, or forcing of units.

D. Do not allow glass to rest on or contact any framing member.

E. Glaze doors and operable sash, in a securely fixed or closed and locked position, until sealant, glazing compound, or putty has thoroughly set.

F. Patterned Glass:

1. Install units with one patterned surface with smooth surface on the weather side.

2. Install units in interior partitions with pattern in same direction in all openings.

G. Tempered Glass: Install with roller distortions in horizontal position unless otherwise directed.

H. Transparent (One-Way Vision Glass) Mirror: Use continuous channel glazing gasket.

I. Plastic:

1. Use dry glazing method.

2. Use only neoprene or EPDM gaskets.

J. Laminated Glass:

1. Tape edges to seal interlayer and protect from glazing sealants.

2. Do not use putty or glazing compounds.

K. Insulating Glass Units:

1. Glaze in compliance with glass manufacturer's written instructions.

2. When glazing gaskets are used, they are to be of sufficient size and depth to cover glass seal or metal channel frame completely.

3. Do not use putty or glazing compounds.

4. Do not grind, nip, cut, or otherwise alter edges and corners of fused glass units after shipping from factory.

5. Install with tape or gunnable sealant in wood sash.

L. Fire Protective and Fire Resistance Glass:

1. Wire Glass: Glaze in accordance with NFPA 80.

08 80 00 - 18

2. Other fire protective and fire resistant glass: Glaze in accordance with manufacturer’s installation instructions and NFPA 80.

M. Bullet Resisting Material:

1. Glaze as recommended by manufacturer, using glazing material which will permit expansion and contraction of the bullet resistive material in the frame.

2. The polycarbonate surface is not to be cleaned by scraping, razor blade, squeegee, or use of highly alkaline cleaner.

3. At no time is polycarbonate material be exposed to chemical solvents

(benzene, gasoline, acetone, paint thinners) or aromatic hydrocarbons (toluene or xylene), nor should any of these solvents or fumes by used or present in confined area such as a security guard booth.

4. Due care is to be exercised (paint formula, ventilation, protection of polycarbonate) when painting becomes necessary to interiors of rooms of hardline glazed units; exposure to chemical solvents could result in irreparable damage to security glazings (delaminations, distortions, cracks, severe stress crazing, air bubbles, etc.).

3.4 INSTALLATION – ELECTROCHROMIC GLAZING (NOT USED)

3.5 INSTALLATION - DRY METHOD (TAPE AND GASKET SPLINE GLAZING):

A. Cut glazing tape to length; install on glazing pane. Seal corners by butting and sealing junctions with butyl sealant.

B. Place setting blocks at 1/4 points with edge block no more than 150 mm (6 inches) from corners.

C. Rest glazing on setting blocks and push against fixed stop with sufficient pressure to attain full contact.

D. Install removable stops without displacing glazing spline. Exert pressure for full continuous contact.

E. Do not exceed edge pressures stipulated by glass manufacturers for installing glass lites.

F. Trim protruding tape edge.

3.6 INSTALLATION - WET/DRY METHOD (PREFORMED TAPE AND SEALANT):

A. Cut glazing tape to length and set against permanent stops, 5 mm

(3/16 inch) below sight line. Seal corners by butting tape and dabbing with butyl sealant.

08 80 00 - 19

B. Apply heel bead of butyl sealant along intersection of permanent stop with frame ensuring full perimeter seal between glass and frame to complete the continuity of the air and vapor seal.

C. Place setting blocks at 1/4 points with edge block no more than 152 mm (6 inches) from corners.

D. Rest glazing on setting blocks and push against tape and heel bead of sealant with sufficient pressure to achieve full contact at perimeter of pane or glass unit.

E. Install removable stops, with spacer strips inserted between glazing and applied stops, 6 mm (1/4 inch) below sight line. Place glazing tape on glazing pane or unit with tape flush with sight line.

F. Fill gap between glazing and stop with sealant to depth equal to bite of frame on glazing, but not more than 9 mm (3/8 inch) below sight line. Sealant type is to be compatible with glazing tape.

G. Apply cap bead of sealant along void between the stop and the glazing, to uniform line, flush with sight line. Tool or wipe sealant surface smooth.

3.7 INSTALLATION - WET METHOD (SEALANT AND SEALANT):

A. Place setting blocks at 1/4 points and install glazing pane or unit.

B. Install removable stops with glazing centered in space by inserting spacer shims both sides at 600 mm (24 inch) intervals, 6 mm (1/4 inch) below sight line.

C. Fill gaps between glazing and stops with sealant to depth of bite on glazing, but not more than 9 mm (3/8 inch) below sight line to ensure full contact with glazing and continue the air and vapor seal.

D. Apply sealant to uniform line, flush with sight line. Tool or wipe sealant surface smooth.

3.8 INSTALLATION - EXTERIOR BUTT GLAZED METHOD (SEALANT ONLY):

A. Perform adhesion testing in accordance with ASTM C794. Provide primer per sealant manufacturer’s recommendations. Submit test results.

B. Temporarily brace glass in position for duration of glazing process.

Mask edges of glass at adjoining glass edges and between glass edges and framing members.

C. Temporarily secure a small diameter non-adhering foamed rod on back side of joint.

D. Apply sealant to open side of joint in continuous operation; thoroughly fill the joint without displacing the foam rod. Tool the sealant surface smooth to concave profile.

08 80 00 - 20

E. Permit sealant to cure then remove foam backer rod. Apply sealant to opposite side, tool smooth to concave profile.

F. Remove masking tape.

3.9 INSTALLATION - INTERIOR WET/DRY METHOD (TAPE AND SEALANT):

A. Cut glazing tape to length and install against permanent stops, projecting 1.6 mm (1/16 inch) above sight line.

B. Place setting blocks at 1/4 points with edge block no more than 150 mm

(6 inches) from corners.

C. Rest glazing on setting blocks and push against tape to ensure full contact at perimeter of pane or unit.

D. Install removable stops, spacer shims inserted between glazing and applied stops at 600 mm (24 inch) intervals, 6 mm (1/4 inch) below sight line.

E. Fill gaps between pane and applied stop with sealant to depth equal to bite on glazing, to uniform and level line. Sealant type is to be compatible with glazing tape.

F. Trim protruding tape edge.

3.10 INSTALLATION - INTERIOR WET METHOD (COMPOUND AND COMPOUND):

A. Install glazing resting on setting blocks. Install applied stop and center pane by use of spacer shims at 600 mm (24 inch) centers, kept 6 mm (1/4 inch) below sight line.

B. Locate and secure glazing pane using glazers' clips.

C. Fill gaps between glazing and stops with glazing compound until flush with sight line. Tool surface to straight line.

3.11 INSTALLATION - REGLAZING HISTORIC FRAMING:

A. Steel Windows: For glazing with glazing beads: ASTM C920.

B. Wood Sash: For glazing with glazing beads: Tape or ASTM C920, gunnable sealant.

C. Lock-strip Gaskets: Follow ASTM C716 for installation.

3.12 COMMISSIONING – ELECTROCHROMIC GLAZING (NOT USED)

3.13 REPLACEMENT AND CLEANING:

A. Clean new glass surfaces removing temporary labels, paint spots, and defacement after approval by COR.

B. Replace cracked, broken, and imperfect glass, or glass which has been installed improperly.

C. Leave glass, putty, and other setting material in clean, whole, and acceptable condition.

08 80 00 - 21

3.14 PROTECTION:

A. Protect finished surfaces from damage during erection, and after completion of work. Strippable plastic coatings on colored anodized finish are not acceptable.

3.15 MONOLITHIC GLASS SCHEDULE:

A. Clear fully tempered float glass.

1. Unit Thickness: 6 mm (0.23 inch.

2. Safety glazing label required.

3.16 LAMINATED GLASS SCHEDULE:

A. Low-E-coated, laminated vision glass with two (2) lites of clear fully tempered.

1. Minimum Thickness of Each Glass Lite: (0.12 inch.

2. Interlayer Thickness: 0.76 mm (0.030 inch).

3. Low-E Coating: Sputtered on second surface.

4. Visible Light Transmittance: 62 percent minimum.

5. Solar Heat Gain Coefficient: 0.27 maximum.

6. Safety glazing label required.

7. Windborne debris-resistant glazing unit required.

3.17 INSULATING GLASS SCHEDULE:

A. High performance low-E-coated, clear insulating glass.

1. Overall Unit Thickness: 25 mm (1 inch).

2. Minimum Thickness of Each Glass Lite: 3 mm (0.12 inch).

3. Outdoor Lite: Annealed float glass, except heat-strengthened float glass where required, and fully tempered float glass where indicated.

4. Interspace Content: Argon.

5. Indoor Lite: Fully tempered float glass.

6. Low-E Coating: Sputtered on second.

7. Visible Light Transmittance: 62 percent minimum.

8. Solar Heat Gain Coefficient: 0.27 maximum.

3.18 INSULATING LAMINATED GLASS SCHEDULE (FORCE PROTECTION AND PHYSICAL

SAFETY):

A. Low-E-coated, clear insulating laminated glass.

1. Overall Unit Thickness: 25 mm (1 inch).

2. Outdoor Lite: Clear annealed float glass, except heat-strengthened float glass where required, and fully tempered float glass where indicated.

08 80 00 - 22

a. Minimum Thickness of Outdoor Lite: 3 mm (0.12 inch).

3. Interspace Content: Argon.

4. Indoor Lite: Clear laminated glass with two lites of annealed float glass, except heat-strengthened float glass where required, and fully tempered float glass where indicated.

a. Minimum Thickness of Each Glass Lite: 3 mm (0.12 inch.

5. Low-E Coating: Sputtered on second surface.

6. Visible Light Transmittance: 62 percent minimum.

7. Solar Heat Gain Coefficient: 0.27 maximum.

8. Safety glazing label required.

9. Windborne debris-resistant glazing unit required.

10. Blast Resistance: Provide units meeting the following:

a. GP Value furnished by VA.

3.19 ELECTROCHROMIC LAMINATED INSULATING GLASS SCHEDULE (NOT USED)

3.20 FIRE-PROTECTIVE AND FIRE-RESISTANCE GLAZING SCHEDULE:

A. Fire-protection-rated tempered glass.

1. Thickness: 6 mm (0.23 inch).

2. Rating: 20 minutes.

3. Application: Fire-protection-rated door assemblies with openings not over 0.65 sq. m (100 sq. in.).

3.21 SECURITY GLAZING SCHEDULE:

A. Tinted reflective-coated symmetrical glass-clad polycarbonate, ASTM

C1349.

1. Overall Unit Thickness: 13.3 mm (0.52 inch).

2. Outer Lite: 6 mm (0.23 inch) heat-strengthened tinted float glass.

b. Glass Tint Color: Gray.

c. Tinted Glass Location: Outer lite.

d. Coating Color: Silver.

e. Coating Location: Second surface.

f. Visible Light Transmittance of Outer Lite: 11 percent.

3. Single Core: Polycarbonate, 3 mm (0.12 inch) thick.

4. Inner Lite: Heat-strengthened float glass, 1.3 mm (0.05 inch).

5. Interlayer Type and Thickness: Clear, 1.52 mm (0.06 inch).

6. Application: Security glazing for observation window.

08 90 00 - 1

SECTION 08 90 00

LOUVERS AND VENTS

1.1 DESCRIPTION:

A. This section specifies fixed and operable wall louvers, door louvers and wall vents.

1.2 RELATED WORK:

A. Louvers in Steel Doors: Section 08 11 13, HOLLOW METAL DOORS AND

FRAMES.

1.3 SUBMITTALS:

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, AND SAMPLES.

B. Shop Drawings:

1. Each type, showing material, finish, size of members, operating devices, method of assembly, and installation and anchorage details.

C. Manufacturer's Literature and Data:

1. Each type of louver and vent.

D. Color samples.

1.4 APPLICABLE PUBLICATIONS:

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

B. The Master Painters Institute (MPI):

Approved Product List – Updated Monthly

C. ASTM International (ASTM):

A240/A240M-14...........Chromium and Chromium-Nickel Stainless Steel

Plate, Sheet, and Strip for Pressure Vessels and for General Applications

A653/A653M-13...........Steel Sheet Zinc-Coated (Galvanized) or Zinc-

Iron Alloy Coated (Galvannealed) by the Hot Dip

Process

A1008/A1008M-13.........Steel, Sheet, Carbon, Cold Rolled, Structural, and High Strength Low-Alloy with Improved

Formability

B209-14.................Aluminum and Aluminum Alloy, Sheet and Plate

B209M-14................Aluminum and Aluminum Alloy, Sheet and Plate

(Metric)

08 90 00 - 2

B221-14.................Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes

B221M-13................Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes (Metric)

D1187/D1187M-97(R2011)..Asphalt-Base Emulsions for Use as Protective

Coatings for Metal

D. National Association of Architectural Metal Manufacturers (NAAMM):

AMP 500-06..............Metal Finishes Manual

E. National Fire Protection Association (NFPA):

90A-15..................Installation of Air Conditioning and

Ventilating Systems

F. American Architectural Manufacturers Association (AAMA):

2605-13.................High Performance Organic Coatings on

Architectural Extrusions and Panels

G. Air Movement and Control Association, Inc. (AMCA):

500-L-07................Testing Louvers

PART 2 - PRODUCTS

2.1 MATERIALS:

A. Aluminum, Extruded: ASTM B221M (B221).

B. Stainless Steel: ASTM A240/A240M, Type 302B.

C. Galvanized Steel Sheet: ASTM A653/A653M; G90 min.

D. Carbon Steel and Sheet: ASTM A1008/A1008M (interior use louvers only).

E. Aluminum, Plate and Sheet: ASTM B209M (B209); alloy 3003 or 5005 with temper as required for forming.

F. Fasteners: Fasteners for securing louvers and wall vents to adjoining construction, except as otherwise specified or indicated in construction documents, to be toggle or expansion bolts of size and type as required for each specific type of installation and service condition.

1. Where type, size, or spacing of fasteners is not shown or specified, submit shop drawings showing proposed fasteners, and method of installation.

2. Fasteners for louvers, louver frames, and wire guards to be of stainless steel or aluminum with same finish as louvers.

3. Fasteners for louvers, louver frames and wire guards within mental health areas to be non-removable/tamper-proof type.

G. Inorganic Zinc Primer: MPI No. 19.

08 90 00 - 3

H. Bituminous Coating: ASTM D1187/D1187M; cold applied asphalt mastic emulsion.

2.2 EXTERIOR WALL LOUVERS:

A. General:

1. Provide fixed and operable type louvers of size and design shown.

2. Heads, sills and jamb sections are to have formed caulking slots or be…

This is the start of the file's text. The full file is on GovTribe.