08 1200392 VA Bldg 20 ELEC 05 13 2021.pdf

PDF 3 MB Posted

Attached to
Z2DZ-36C249-21-AP-3182 - 621-15-101 - Correct Admin Bldg. -20 Environment & Condition Deficiencies
Solicitation number
36C24921B0014
Issued by

About this file

This presolicitation notice is for a construction project to correct environment and condition deficiencies at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The project scope includes modifying existing areas and demolishing structures to provide offices, conference rooms, locker rooms, storage, and mechanical/electrical rooms for police staff, along with finish upgrades per VA standards. The estimated construction cost is between $1 million and $5 million. The requirement will be competitively procured using sealed bidding per FAR Part 14 and is reserved exclusively for SDVOSBs listed in the CVE database. The solicitation is expected to be issued on or around October 20, 2021 with responses due by November 20, 2021. Questions must be submitted in writing to the named contracting officer.

View the file

Other files

File Type Posted
36C24921B0014 0007.pdf PDF
S04- SITE VISIT ATTENDEES - Bldg 20 - 621-15-101.pdf PDF
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-16-2021.pdf PDF
36C24921B0014 0006.pdf PDF
S05 - VA Comprehensive Asbestos Containing Materials Inspection Report January 2010 - 2.pdf PDF
S06 - AMENDMENT 5 - 36C24921B0014 0005.pdf PDF
S05-Mountain Home TN - VA Asbestos O AND M Plan January 2010 -1.pdf PDF
S05-RFI RESPONSE QUESTIONS - B20 Correct FCA Deficiencies 12-23-2021.pdf PDF
S02-LBP DOC-Building 20 - 36C24921B0014.pdf PDF
S02-Building 20 ACM Report - 36C24921B0014.pdf PDF
S02- Solicitation - 36C24921B0014 - 621-15-101 - Amendment - 0004.pdf PDF
36C24921B0014 0003.pdf PDF
S06- AMENDMENT2 - CO AND PROJECT CONFIRMATION DATES - 36C24921B0014 0002.pdf PDF
S02-AMENDMENT1 - 621-15-101 CORRECT ADMIN BLDG 20 ENVIRONMENT COND DEF - BID SPECIFICATIONS.pdf PDF
S02- AMENDMENT 1 - 03 1200392 VA Bldg 20 ARCH 05 13 2021 Part 1.pdf PDF
S02- AMENDMENT 1 - 06 1200392 VA Bldg 20 PLMB 05 13 2021 Part 1.pdf PDF
S06-AMENDMENT 01 - 621-15-101 - 36C24921B0014 0001 - WB.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1D.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1A.pdf PDF
05 1200392 VA Bldg 20 FIRE 05 13 2021.pdf PDF
06 1200392 VA Bldg 20 PLMB 05 13 2021 Part 2.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 2D.pdf PDF
07 1200392 VA Bldg 20 MECH 05 13 2021.pdf PDF
09 1200392 VA Bldg 20 COMM 05 13 2021.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 2C.pdf PDF
S02-Contractor EMR Certification Form - 36C24921B0014.docx DOCX document
04 1200392 VA Bldg 20 INT 05 13 2021.pdf PDF
S02-TECHNICAL SPECS - Project 621-15-101.pdf PDF
02 1200392 VA Bldg 20 CIVIL 05 13 2021.pdf PDF
S02-621-15-101 - Correct Admin Bldg 20 .pdf PDF
01 1200392 VA Bldg 20 GEN 05 13 2021.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1B.pdf PDF
S02-WD - WASHINGTON TN - TN20210111 - JAN 2021.pdf PDF
03 1200392 VA Bldg 20 ARCH 05 13 2021 Part 2.pdf PDF
621 15 101 CORRECT ADMIN BLDG 20 ENVIR COND DEF BID DOCUMENTS SPECIFICATIONS VOL 1C.pdf PDF
36C24921B0014.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL ABBREVIATIONS

A OR AMP

ACC

AC

AC

AF

AFF

AFG

AHU

AIC

AL

AM

ASYM

AT

ATS

AUTO

AWG

B

BC

BCW

BFF

BFG

BLDG

C

CAT

CB

CCT

CCTV

CFCI

CH

CHWCP

CHWP

CHWSP

CKT

CMH

COR

CP

CPT

CRAC

CRI

CT

CT

CU

CWP

D

DC

DF

DH or DUH

DHWCP

DISC

DOAS

DPST

DPDT

DSCU

DSHP

DSS

DWBP

DX

EC

EC

EF

ELEC

EMH

EMT

E or EMER

EPA

EQUIP

ERV

ERU

EXIST or EX

EUH

EXP

EWC

EWH

F

FACP

FCU

FLEX

FSD

FWE

G OR GND

GFGI

GFI

GRS

GUH

GWH

H or HT

HAC

HOA

HP

HP

HT

HVU

HWCP

HWP

AMPERE(S)

AIR COOLED CHILLER

ALTERNATING CURRENT

AIR COMPRESSOR / AIR CURTAIN

AMP FRAME

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERE INTERRUPTING CAPACITY

ALUMINUM

AMMETER

ASYMMETRICAL

AMP TRIP

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AMERICAN WIRE GAUGE

BOILER

BRANCH CONTROLLER

BARE COPPER WIRE

BELOW FINISHED FLOOR

BELOW FINISHED GRADE

BUILDING

CONDUIT

CATEGORY

CIRCUIT BREAKER

CORRELATED COLOR TEMPERATURE

CLOSED CIRCUIT TELEVISION

CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

CHILLER

CHILLED WATER CIRCULATING PUMP IN A

PRIMARY-SECONDARY SYSTEM

CHILLED WATER PUMP

CHILLED WATER SUPPLY PUMP IN A PRIMARY-

SECONDARY SYSTEM

CIRCUIT

COMMUNICATIONS MANHOLE

CONTRACTING OFFICER'S REPRESENTATIVE

CONDENSATE PUMP

CONTROL POWER TRANSFORMER

COMPUTER ROOM AC UNIT

COLOR RENDERING INDEX

CURRENT TRANSFORMER

COOLING TOWER

COPPER OR CONDENSING UNIT

CONDENSER WATER PUMP

DEPTH

DIRECT CURRENT

DESTRATIFICATION FAN

DUCT HEATERS

DOMESTIC HOT WATER CIRCULATING PUMP

DISCONNECT SWITCH

DEDICATED OUTSIDE AIR SYSTEM (UNIT)

DOUBLE POLE SINGLE THROW

DOUBLE POLE DOUBLE THROW

DUCTLESS SPLIT CONDENSING UNIT (POWERS

THE DSS INDOOR UNIT)

DUCTLESS SPLIT HEAT PUMP (POWERS THE

DSS INDOOR UNIT)

DUCTLESS SPLIT SYSTEM (INDOOR UNIT)

DOMESTIC WATER BOOSTER PUMP

DIRECT EXPANSION (DX) COOLING COIL

EMPTY CONDUIT

ELECTRICAL CONTRACTOR

EXHAUST FAN

ELECTRICAL

ELECTRICAL MANHOLE

ELECTRICAL METALLIC TUBING

EMERGENCY

EFFECTIVE PROJECTED AREA

EQUIPMENT

ENERGY RECOVERY VENTILATOR

ENERGY RECOVERY UNIT

EXISTING

ELECTRIC UNIT HEATER

EXPLOSION PROOF

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

FUSE

FIRE ALARM CONTROL PANEL

FAN COIL UNIT

FLEXIBLE

FIRE SMOKE DAMPER

FURNISHED WITH EQUIPMENT

GROUND

GOVERNMENT FURNISHED GOVERNMENT

INSTALLED

GROUND FAULT INTERRUPTER

GALVANIZED RIGID STEEL CONDUIT

GAS UNIT HEATER

GAS WATER HEATER

HEIGHT

HEATED AIR CURTAIN

HAND-OFF AUTOMATIC

HORSE POWER

HEAT PUMP (OUTDOOR PORTION OF SPLIT

SYSTEM HEAT PUMP, USE CU FOR STANDARD

DX OUTDOOR UNIT)

HEAT TRACKING

HEATING/VENTILATING UNIT

HEATING WATER CIRCULATING PUMP IN A

PRIMARY-SECONDARY SYSTEM

HEATING WATER SUPPLY IN A PRIMARY-ONLY

SYSTEM

HWRP

HWSP

HWUH

HZ

IDS

IMC

IRH

J OR JB

K

KAIC

KCM OR KCMIL

KEF

KH

KV

KVA

KW

KWHR

L

LA

LAN

LAV

LTG

MAU

MAX

MCA

MCB or MB

MCC

MGB

MH

MIN

MLO

MOD

MT or MTD

MRS

N

NEC

NEMA

NFPA

NC

NESC

NL

NO

NTS

P

PA

PDU

PF

PH

PIU

PMT

PNL

PTAC

PVC

RECEPT or RECP

RF

RH

RMC

RMS

RTU

RVNR

SA

SCCR

SD

SF

S/N

SP

SPD

SPDT

SPEC

SPST

SWBD

SWGR

TMGB

TOL

TP

TYP

U

UH

UG

UIO

UL

UNV

UTP

V

VA

VAV

VEF

VM

VRF

W

WC

WEF

WH

WHDM

WSHP

WP

XFMR

Z

HOT WATER RECIRCULATION PUMP

HEATING WATER SUPPLY PUMP IN A PRIMARY-

SECONDARY SYSTEM

HOT WATER UNIT HEATER

HERTZ

INTRUSION DETECTION SYSTEM

INTERMEDIATE METAL CONDUIT

INFRARED HEATER

JUNCTION BOX

KILO

THOUSAND AMPERE INTERRUPTING CAPACITY

THOUSAND OF CIRCULAR MILS

KITCHEN EXHAUST FAN

KITCHEN HOOD

KILOVOLT

KILOVOLT-AMPERES

KILOWATT

KILOWATT-HOUR

LENGTH

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

LAVATORY

LIGHTING

MAKE-UP AIR UNIT

MAXIMUM

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN GROUND BAR

MANHOLE or MOUNTING HEIGHT

MINIMUM

MAIN LUGS ONLY

MOTOR OPERATED DAMPER

MOUNT or MOUNTED

MOTOR RATED SWITCH

NEUTRAL

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURER'S

ASSOCIATION

NATIONAL FIRE PROTECTION ASSOCIATION

NORMALLY CLOSED

NATIONAL ELECTRICAL SAFETY CODE

NIGHT LIGHT

NORMALLY OPEN

NOT TO SCALE

POLE(S) or PUMP

PUBLIC ADDRESS

POWER DISTRIBUTION UNIT

POWER FACTOR

PHASE

VAV TERMINAL UNIT WITH PARALLEL OR

SERIES FAN (PRIMARY INDUCTION UNIT)

PAD MOUNTED TRANSFORMER

PANEL OR PANELBOARD

PACKAGED THRU-WALL AIR CONDITIONER

POLYVINYL CHLORIDE

RECEPTACLE

RETURN FAN

RADIANT HEATERS (ELECTRIC)

RIGID METAL CONDUIT

ROOT MEAN SQUARE

ROOF TOP UNIT

REDUCED VOLTAGE NON-REVERSING

SURGE ARRESTOR

SHORT CIRCUIT CURRENT RATING

SMOKE DAMPER

SUPPLY FAN

SOLID NEUTRAL

SUMP PUMP

SURGE PROTECTIVE DEVICE

SINGLE POLE DOUBLE THROW

SPECIFICATIONS

SINGLE POLE SINGLE THROW

SWITCHBOARD

SWITCHGEAR

TELECOMMUNICATIONS MAIN GROUNDING

BUSBAR

THERMAL OVERLOAD

TWISTED PAIR

TYPICAL

URINAL

UNIT HEATER

UNDERGROUND

UNLESS INDICATED OTHERWISE

UNDERWRITERS LABORATORY

UNIVERSAL

UNSHIELDED TWISTED PAIR

VOLTS

VOLT AMPERES

VAV TERMINAL UNIT

VEHICLE EXHAUST FAN

VOLTMETER

VARIABLE REFRIGERANT FLOW SYSTEM

WATTS or WIRE or WIDTH

WATER CLOSET

WELDING EXHAUST FAN

WATER HEATER

WATTHOUR DEMAND METER

WATER SOURCE HEAT PUMP

WEATHERPROOF

TRANSFORMER

IMPEDANCE

ELECTRICAL GENERAL NOTES:

1. THE WORK SHALL CONFORM WITH ALL REQUIREMENTS OF:

A. NFPA 70-2017 (NATIONAL ELECTRICAL CODE)

B. ANSI C2-2017 (NATIONAL ELECTRICAL SAFETY CODE)

C. APPLICABLE LOCAL CODES AND FEDERAL AND STATE LAWS.

D. PG-18-10 VA ELECTRICAL DESIGN MANUAL

E. PG-18-9 CHAPTER 279: POLICE SERVICE

2. MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS

REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40% FULL.

3. CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER

TRADES THROUGH THE GENERAL CONTRACTOR AND SHALL BE

RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL

EQUIPMENT CLEARANCE FOR RECESSED LUMINARIES AND CORRECT

ROUGH-IN LOCATIONS OF ELECTRICAL CONNECTIONS.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CATALOG

NUMBERS ON THESE DRAWINGS TO MATCH WITH MATERIAL

DESCRIPTIONS INDICATED.

5. VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND BACKSPLASH ON

ARCHITECTURAL DETAILS AND/OR CASE WORK SHOP DRAWINGS AND

ADJUST SPECIFIED MOUNTING HEIGHT OF WALL OUTLETS TO LOCATE

BOTTOM OF OUTLET BOX 4" ABOVE TOP OF BACKSPLASH. IF NO

BACKSPLASH IS USED, LOCATE BOTTOM OF OUTLET BOX 6" ABOVE

COUNTERTOP.

6. VERIFY DOOR SWINGS WITH ARCHITECTURAL DRAWINGS BEFORE

ROUGHING IN WALL SWITCHES. SWITCHES IN THE SAME LOCATION

SHALL BE GANGED TOGETHER IN ONE COMMON BACKBOX AND SHALL

HAVE ONE COMMON FACE PLATE.

7. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN

INSULATED GROUND CONDUCTOR, SIZE PER NATIONAL ELECTRICAL

CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX

ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE A

DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT.

MULTIPLE BRANCH CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE

GROUND CONDUCTOR.

8. VERIFY LUMINAIRE, CEILING MOUNTED OCCUPANCY SENSOR

LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS FOR

EXACT LOCATIONS AND DIMENSIONS PRIOR TO INSTALLATION. VERIFY

EXACT LOCATIONS OF MOTORS AND EQUIPMENT BEFORE ROUGHING-IN.

9. EXISTING ELECTRICAL WORK (NOT SHOWN) SHALL REMAIN, UNLESS

INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER,

LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED,

DISCONNECTED OR DELETED IN THE PROCESS OF CONSTRUCTION OR

REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND

SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE

DRAWINGS TO BE DELETED, THEN SAID CIRCUIT OR FEEDER SHALL BE

RESTORED TO WORKING CONDITION. THE RESTORATION SHALL

INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR

REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH

WORK REQUIRED SHALL BE INCLUDED IN THE CONTRACT AND NO

EXTRA COMPENSATION WILL BE GRANTED.

10. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM

MANNER, SIMILAR ITEMS OF NEW WORK SHALL BE CHECKED AGAINST

EXISTING WORK FOR TYPE MOUNTING, MOUNTING HEIGHTS, ETC. ITEMS

SHOWN IN NEW WORK AT VARIANCE FROM THE EXISTING SHALL BE

REFERRED TO THE ARCHITECT FOR DECISION BEFORE ROUGH-IN.

11. REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER DIAGRAMS

FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.

12. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE

WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO

STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER

EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED

TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE

DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF

WORK.

13. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF

THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO

REQUIRE CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL

CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN

ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND

ORDINANCES. COST OF DISPOSAL IS ENTIRELY THE CONTRACTOR'S

RESPONSIBILITY.

14. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS

ALUMINUM.

15. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS,

DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY

MATERIALS AND DEVELOPMENT OF ANY SHOP DRAWINGS OR

SUBMITTALS.

16. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT

SWITCHES/OCCUPANCY SENSORS AND JUNCTION BOXES INDICATING

THE SOURCE PANEL & CIRCUIT(S). TEXT SHALL BE BLACK, 1/8” IN

HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE NOT

PERMITTED EXCEPT FOR JUNCTION BOXES LOCATED ABOVE FINISHED

CEILING WHICH CAN BE HANDWRITTEN WITH AN INDELIBLE MARKER.

17. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT SHALL

EXTEND 2” BEYOND THE FOOTPRINT OF THE EQUIPMENT.

ELECTRICAL DEMOLITION NOTES:

1. PRIOR TO SUBMITTING A PROPOSAL THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND CAREFULLY INVESTIGATE THE EXISTING AREAS AFFECTED BY THIS WORK IN ORDER TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND THE DIFFICULTIES THAT WILL AFFECT THE EXECUTION OF THIS WORK. THE CONTRACTOR SHALL BASE HIS BID ACCORDINGLY. SUBMISSION OF PROPOSAL WILL BE CONSTRUED AS CONFIRMATION THAT A THOROUGH EXAMINATION OF THE SITE HAS BEEN

MADE BY THE CONTRACTOR. LATER CLAIMS FOR UNFORESEEN EXTRA LABOR, EQUIPMENT, OR

MATERIALS WILL NOT BE ACCEPTED IF SAID CLAIMS COULD HAVE BEEN FORESEEN DURING THE

SITE INVESTIGATION.

2. CONTRACTORS WORK SHALL COMPLY WITH ALL SAFETY RELATED WORK PRACTICES DETAILED IN

THE LASTEST EDITION OF NFPA 70E.

3. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL OF ALL ELECTRICAL FACILITIES

RENDERED INACTIVE OR OBSOLETE BY THE SCOPE OF THE ARCHITECTURAL, MECHANICAL, AND

PLUMBING DEMOLITION WORK. THE CONTRACT IS ALTERED THAT SUCH ELECTRICAL FACILITIES

MAY NOT BE EXPLICITLY SHOWN ON THE ARCHITECTURAL DEMOLITION DRAWINGS. THE

CONTRACTOR SHALL VISIT THE SITE, REFER TO THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS, AND COORDINATE WITH THE GENERAL, MECHANICAL, AND PLUMBING

CONTRACTORS. THE CONTRACT INCLUDES ALL ELECTRICAL DEMOLITION WORK, HOWEVER NOT

NECESSARILY LIMITED TO, THE COMPLETE ELECTRICAL AND CONTROL WIRE, CONDUIT, JUNCTION

BOXES, ENCLOSURE, AND RACEWAY SUPPORT SYSTEM, DISCONNECT SWITCHES, CIRCUIT

BREAKERS, ETC INTENDED FOR REMOVAL AS REQUIRED TO COMPLETE THE WORK.

4. THE INTENT OF THE DEMOLITION WORK REQUIREMENTS INCLUDE ALL LABOR AND EQUIPMENT REQUIRED TO ATTAIN THE FINAL CONDITION AS SHOWN ON THE ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL NEW WORK PLANS. THE CONTRACTOR SHALL REVIEW ALL OTHER

TRADE DRAWINGS, AND COORDINATE WITH ALL OTHER TRADE CONTRACTORS, AND BASE HIS BID

ACCORDINGLY.

5. WHERE THE REMOVAL OF EXISTING FACILITIES RESULT IN THE DE-ENERGIZATION OF EXISTING

REMAINING FACILITIES, THE CONTRACTOR SHALL INSTALL JUNCTION BOXES AND OR OTHER

DEVICES, PROVIDE BYPASS CONNECTIONS NECESSARY TO MAKE THE EFFECTED CIRCUITS

CONTINUOUS AND READY FOR OPERATION OR AS OTHERWISE INDICATED OR INTENDED.

6. THE CONTRACTOR SHALL REMOVE AND/OR RELOCATE ALL EXISTING ELECTRICAL FACILITIES THAT INTERFERE WITH THE NEW ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL LAYOUTS AND SCHEMES. REFER TO THE ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS

AND COORDINATE WITH THE GENERAL, MECHANICAL, PLUMBING CONTRACTORS.

7. PRIOR TO THE COMMENCEMENT OF WORK, ELECTRICAL POWER SHALL BE DISCONNECTED AND

OR SWITCHED OFF AS REQUIRED. TEMPORARY LIGHTING AND POWER FOR ALL TRADES,

REMAINING BUILDING OCCUPANTS, AND CRITICAL BUILDING SERVICES SHALL BE PROVIDED AS

REQUIRED WITHOUT EXCEPTION. UNDER NO CIRCUMSTANCES SHALL POWER BE INTERRUPTED TO

ANY AREA WITHOUT PRIOR WRITTEN APPROVAL FROM BUILDING MANAGEMENT.

8. TEMPORARY LIGHT STRINGERS WHERE SPLICED ARE TO EMPLOY COMPRESSION TYPE FITTINGS

OR SOLDERED CONNECTIONS AND MADE UP NEATLY AND SAFELY AS REQUIRED.

9. MAINTAIN CONTINUOUS ELECTRICAL SERVICE TO ALL ACTIVE AREAS AT ALL TIMES EXCEPT

WHERE GIVEN WRITTEN PERMISSION BY BUILDING PROPERTY MANAGEMENT FOR A SCHEDULED

OUTAGE FOR A DECLARED OUTAGE DURATION.

10. REMOVE EXPOSED CONDUITS, WIREWAYS, OUTLET BOXES, HANGERS, SUPPORTS, AND DEVICES

MADE OBSOLETE BY THIS WORK UNLESS BEING REUTILIZED FOR THE NEW INSTALLATION. THE

REUTILIZATION OF EXISTING FACILITIES BY THE CONTRACTOR SHALL RENDER A FINISHED

INSTALLATION IN STRICT ACCORDANCE WITH THE NEC WITHOUT EXCEPTION.

11. ALL ADJACENT FACILITIES IMPACTED OR TEMPORARILY DISCONNECTED TO FACILITATE

DEMOLITION WORK SHALL BE RECONNECTED AND RESTORED TO A CONDITION EQUAL TO OR

BETTER THAN ORIGINALLY FOUND PRIOR TO THE COMMENCEMENT OF WORK. WHERE EXISTING

CONDITIONS DO NOT MEET NEC REQUIREMENTS, THE CONTRACTOR SHALL NOTIFY THE PROJECT

OWNER PRIOR TO THE COMMENCEMENT OF WORK.

12. PRIOR TO THE COMMENCEMENT OF WORK THE CONTRACTOR SHALL TRACE EXISTING CIRCUITS

AND CONFIRM OR IDENTIFY TYPE AND LOCATION OF LOAD SERVED.

13. WHERE EXISTING ELECTRICAL PANELS ARE CALLED FOR REMOVAL AND OR REPLACEMENT, THE CONTRACTOR SHALL REMOVE ALL SERVING FEEDER WIRE AND CONDUIT BACK TO ITS RESPECTIVE

SOURCE OF POWER OR AS OTHERWISE INDICATED.

14. ALL OPEN FLOOR OUTLETS SHALL BE PLUGGED. ANY AND ALL PANEL ENCLOSURE OR

EQUIPMENT TERMINAL BOX COMPARTMENTS WITH UNOCCUPIED KNOCKOUTS, RACEWAY OR

CABLE ASSEMBLY PENETRATIONS SHALL BE PLUGGED WITH A LISTED DEVICE. ANY AND ALL

UNOCCUPIED BREAKER SPACES IN EXISTING AND OR NEW PANELS SHALL BE PLUGGED WITH A

LISTED DEVICE OR FURNISHED WITH A SPARE, OPERABLE CIRCUIT BREAKER LISTED FOR USE IN

THE PANEL. PROVIDE LISTED PLATES ON ALL UNUSED OUTLET AND JUNCTION BOXES.

15. ELECTRICAL PANEL COVERS ARE NOT TO BE LEFT OFF AT ANY TIME UNLESS MEN ARE WORKING

ON, ADEQUATELY PROTECTING AND BARRICADING THEM AS REQUIRED. COVERS SHALL BE

REPLACED EACH NIGHT BEFORE LEAVING JOB SITE.

16. REMOVE AND PROPERLY DISPOSE OF ALL REMOVALS IN ACCORDANCE WITH APPLICABLE LAWS

AND ENVIRONMENTAL RESTRICTIONS.

17. THE REMOVAL AND OR RELOCATION OF ALL FIRE ALARM COMMUNICATIONS, DATA AND SECURITY

EQUIPMENT AND ASSOCIATED CABLING SHALL BE COORDINATED WITH BUILDING OPERATIONAL

PERSONNEL. EXISTING BASE BUILDING FIRE ALARM SYSTEM (AND FLOOR SECURITY SYSTEM

WHERE APPLICABLE) INTEGRITY SHALL BE MAINTAINED AT ALL TIMES BEFORE, DURING, AND

AFTER DEMOLITION.

18. CONTRACTOR SHALL PERFORM THE FOLLOWING PRIOR TO START ANY TRADES DEMOLITION:

A. TRACE ALL INCOMING AND OUTGOING FEEDS (LOW VOLTAGE AND HIGH VOLTAGE) AS WELL AS

LIGHTING CIRCUITS BACK TO THEIR ORIGINAL SOURCE OF POWER (I.E. SWITCHBOARDS,

PANELBOARDS, ETC.)

B. IDENTIFY ALL CONDUITS, CABLES, ETC. WITH CLEARLY IDENTIFIABLE MARKINGS. IDENTIFICATION

SHALL BE PROVIDED FROM EACH LOAD TO THE MOST UPSTREAM SOURCE PANEL.

IDENTIFICATION SHALL BE PROVIDED AT ALL JUNCTION AND PULL BOXES,

TERMINATIONS/SPLICES AND PANEL LOCATIONS AS REQUIRED.

C. REVIEW LOCATIONS, CONFIGURATION, AND SERVICE LOCATIONS OF ALL FEEDER AND BRANCH

CIRCUIT SOURCES WITH GENERAL CONTRACTOR SO AS TO ENSURE SERVICES WILL REMAIN

CONNECTED OR INTERRUPTED AS ANTICIPATED. REFER TO EXISTING BUILDING RECORD

DRAWINGS PRIOR TO COMMENCEMENT OF WORK.

D. COORDINATE ALL WORK WITH BUILDING PROPERTY MANAGEMENT.

E. EXISTING ELECTRICAL EQUIPMENT FACILITIES WHEN REUSED, SHALL BE THOROUGHLY CLEANED

AND REFURBISHED PRIOR TO RE-USE. ANY AND ALL EXISTING RE-USED SET SCREW TYPE

CONDUIT CONNECTORS SHALL BE THOROUGHLY TIGHTENED.

SHEET NAMING CONVENTION

E - 001

2 DIGIT SEQUENTIAL # (01-99)

1 DIGIT SHEET TYPE DESIGNATOR

0 - GENERAL (LEGEND, GENERAL NOTES)

1 - PLANS

2 - ELEVATIONS

3 - SECTIONS

4 - ENLARGED PLANS

5 - DETAILS

6 - SCHEDULES AND DIAGRAMS

7 - VARIES

8 - VARIES

9 - 3D VIEWS (ISO, PERSPECTIVES)

2 DIGIT DESCIPLINE DESIGNATOR

(IF ONLY ONE LETTER IS USED, THE

SECOND LETTER IS REPLACED

WITH A DASH "-" AS A

PLACEHOLDER)**

NOTES:

1. ALL EXISTING EQUIPMENT IS SHOWN IN HALFTONE LINEWORK.

ALL DEMOLISHED EQUIPMENT IS SHOWN IN BOLD LINEWORK,

DASHED AND HATCHED. ALL NEW OR RELOCATED EQUIPMENT

IS SHOWN IN BOLD LINEWORK. BELOW IS AN EXAMPLE OF

EACH:

EXISTING EQUIPMENT

NEW OR RELOCATED EQUIPMENT

HATCH INDICATES EQUIPMENT TO BE DEMOLISHED

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

E-001

ELECTRICAL NOTES & ABBREVIATIONS

EOFK

NOTE:

1. NOT ALL ABBREVIATIONS SHOWN WILL BE USED ON THIS

PROJECT.

WIRE SIZE FOR ALL 120V, 20A CIRCUITS,

UIO:

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 75 FT,

PROVIDE 2#12 & 1#12G, 3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 125 FT

AND GREATER THAN OR EQUAL TO 75 FT, PROVIDE 2#10 & 1#10G,

3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 190 FT

AND GREATER THAN OR EQUAL TO 125 FT, PROVIDE 2#8 & 1#8G,

3/4"C.

FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 300 FT

AND GREATER THAN OR EQUAL TO 190 FT, PROVIDE 2#6 & 1#6G,

3/4"C.

REVISIONS DATE

1/2

B

W

SB

M

M

2/60/40/1

60/40/3/3R

40/3/3R

CB

T

M

EM

J J

J

G

G4

A

AE

M

X X

C

D a b

LUMINAIRES

LUMINAIRE AND OUTLET BOX. LETTER

INDICATES LUMINAIRE TYPE. SEE LUMINAIRE

SCHEDULE.

LUMINAIRE AND OUTLET BOX WIRED FOR

MULTILEVEL SWITCHING, LOWER CASE LETTER

INDICATES SWITCHLEG DESTINATION.

LUMINAIRE AND OUTLET BOX, WITH PROVISIONS

FOR EMERGENCY LIGHTING. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

WALL MOUNTED LUMINAIRE AND OUTLET BOX.

LETTER INDICATES LUMINAIRE TYPE. SEE

LUMINAIRE SCHEDULE.

CEILING OR WALL MOUNTED EXIT SIGN AND

OUTLET BOX. PROVIDE NUMBER OF ARROWS

AND FACES INDICATED. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

WALL MOUNT AT 96" ABOVE FINISHED FLOOR.

RECESSED OR PENDANT MOUNTED LUMINAIRE

AND OUTLET BOX. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

WALL MOUNTED LUMINAIRE AND OUTLET BOX.

LETTER INDICATES LUMINAIRE TYPE. SEE

LUMINAIRE SCHEDULE.

CEILING OR WALL MOUNTED LUMINAIRE AND

OUTLET BOX WITH PROVISIONS FOR

EMERGENCY LIGHTING. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

EMERGENCY LIGHT UNIT. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

REMOTE HEAD OR FLOOD LUMINAIRE. LETTER

INDICATES LUMINAIRE TYPE. SEE LUMINAIRE

SCHEDULE.

WALL WASH DOWNLIGHT. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

POLE MOUNTED LUMINAIRE. LETTER INDICATES

LUMINAIRE TYPE. SEE LUMINAIRE SCHEDULE.

POST-TOP OR BOLLARD LUMINAIRE. LETTER

INDICATES LUMINAIRE TYPE. SEE LUMINAIRE

SCHEDULE.

EQUIPMENT

MOTOR, HORSEPOWER AS INDICATED

MOTORIZED DAMPER

3-POLE COMBINATION MAGNETIC MOTOR

STARTER/ DISCONNECT (NEMA SIZE/ FUSE SIZE/

NEMA ENCLOSURE) NF = NONFUSED

DISCONNECT SWITCH, (SWITCH AMPS/ FUSE

SIZE/ POLES/ NEMA ENCLOSURE) NF = NON-

FUSED

INDIVIDUALLY MOUNTED CIRCUIT BREAKER,

(CIRCUIT BREAKER SIZE/ POLES/ NEMA

ENCLOSURE)

DRY TYPE TRANSFORMER, KVA AS INDICATED

METER

ELECTRONIC METER

PANELBOARD, SEE SCHEDULES

DISTRIBUTION PANELBOARD, SEE SCHEDULES

EQUIPMENT AS INDICATED

CEILING OR WALL MOUNTED JUNCTION BOX

PULL OR JUNCTION BOX

CEILING MOUNTED BLUE LIGHT SYSTEM

ROTATING BEACON

WHITE NOISE PLENUM SPEAKER; MOUNT ABOVE

DROP CEILING

BLUE LIGHT LOCAL CONTROL SWITCH; MOUNT

48" ABOVE FINISHED FLOOR, UNLESS INDICATED

OTHERWISE

WHITE NOISE ROTARY VOLUME CONTROL;

MOUNT 48" ABOVE FINISHED FLOOR, UNLESS

INDICATED OTHERWISE.

CR

ST

TR

M

R

LA-1,3,5

WIRING DEVICES

LOW VOLTAGE ON/OFF WALL SWITCH, WALL

MOUNT 48" ABOVE FINISHED FLOOR. PROVIDE

DIMMER CONTROL WITH DIMMABLE FIXTURES

INTEGRAL WITH SWITCH.

CEILING MOUNTED DUAL TECHNOLOGY

OCCUPANCY SENSOR

CEILING MOUNTED DUAL TECHNOLOGY

VACANCY SENSOR

CEILING MOUNTED DAYLIGHT SENSOR

PHOTOELECTRIC CELL

WIRING

CIRCUIT HOMERUN TO PANELBOARD, LA-1,3,5

ADJACENT TO ARROW INDICATES HOMERUN

OF CIRCUITS, 1,3,5 TO PANEL LA. MARKS

ACROSS RACEWAY INDICATE THE NUMBER OF

PHASE CONDUCTORS AND NEUTRAL IN

RACEWAY. GROUND CONDUCTORS ARE

INDICATED BY LONGER HASHMARKS. NO

MARKS ACROSS RACEWAY INDICATES 2#12

CONDUCTORS AND 1#12 GROUND

CONDUCTOR. CONDUCTOR SIZE #12 UNLESS

INDICATED OTHERWISE. MINIMUM RACEWAY

SIZE SHALL BE 3/4"

RACEWAY EXPOSED TO VIEW

CONCEALED RACEWAY, LOCATED IN WALL OR

ABOVE FINISHED CEILING

UNDERGROUND RACEWAY, LOCATED BELOW

GRADE OR CONCRETE SLAB

FLEXIBLE RACEWAY

RACEWAY TURNED TOWARD VIEWER

RACEWAY TURNED AWAY FROM VIEWER

RACEWAY TERMINATION, STUB-OUT AND CAP

PLUG-IN BUSWAY, UNLESS INDICATED

OTHERWISE

SURFACE METAL RACEWAY OR MULTIOUTLET

ASSEMBLY AS INDICATED

LADDER TYPE CABLE TRAY (SIZE AS

INDICATED ON PLAN)

DUCTBANK, TEXT INDICATES QUANTITY AND

SIZE OF DUCTS (I.E. 2W4" = TWO 4" DUCTS)

LIGHTNING PROTECTION

3/4" x 10'-0" COPPERCLAD GROUND ROD, 18"

BFG

GROUND ROD TEST WELL

BARE COPPER GROUND CONDUCTOR, 1/0

UNLESS INDICATED OTHERWISE.

4/0 BARE COPPER GROUND CONDUCTOR

LIGHTNING PROTECTION SYSTEM AIR

TERMINAL

LIGHTNING PROTECTION ROOF CONDUCTOR

ELECTRICAL CONNECTION

2W4"

WIRING DEVICES

SIMPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"

ABOVE FINISHED FLOOR, UNLESS INDICATED

OTHERWISE.

DUPLEX RECEPTACLE NEMA 5-20R, MOUNT 18"

ABOVE FINISHED FLOOR, UNLESS INDICATED

OTHERWISE

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT 48"

ABOVE FINISHED FLOOR OR ABOVE COUNTER

TOP/BACKSPLASH

DUPLEX GFI RECEPTACLE NEMA 5-20R, MOUNT

18" ABOVE FINISHED FLOOR, UNLESS INDICATED

OTHERWISE

DUPLEX GFI RECEPTACLE NEMA 5-20R, MOUNT

48" ABOVE FINISHED FLOOR OR ABOVE

COUNTER TOP/BACKSPLASH

DOUBLE-DUPLEX RECEPTACLE NEMA 5-20R,

MOUNT 18" ABOVE FINISHED FLOOR, UNLESS

INDICATED OTHERWISE

SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,

MOUNT 18" ABOVE FINISHED FLOOR, UNLESS

INDICATED OTHERWISE

SWITCHED DUPLEX RECEPTACLE NEMA 5-20R,

MOUNT 48" ABOVE FINISHED FLOOR OR ABOVE

COUNTER TOP/BACKSPLASH

SWITCHED DUPLEX GFI RECEPTACLE NEMA

5-20R, MOUNT 18" ABOVE FINISHED FLOOR,

UNLESS INDICATED OTHERWISE

SWITCHED DUPLEX GFI RECEPTACLE NEMA

5-20R, MOUNT 48" ABOVE FINISHED FLOOR OR

ABOVE COUNTER TOP/BACKSPLASH

DOUBLE-DUPLEX GFI RECEPTACLE, NEMA

5-20R, MOUNTED CONCEALED BEHIND ELECTRIC

WATER COOLER

FLOOR BOX WITH DUPLEX RECEPTACLE NEMA

5-20R. PROVIDE FIRE RATED POKE THRU

DEVICES ON ALL FLOORS ABOVE GROUND

LEVEL.

SPECIAL RECEPTACLE, NEMA TYPE AS

INDICATED, MOUNT 18" ABOVE FINISHED FLOOR,

UNLESS INDICATED OTHERWISE

CEILING BOX WITH DUPLEX RECEPTACLE, NEMA

5-20R

RECEPTACLE WP = IN-USE WEATHER PROOF

SUBSCRIPTS TR = TAMPER RESISTANT

TV = TELEVISION, MOUNT AT 60" ABOVE

FINISHED FLOOR

AFCI = ARC FAULT CIRCUIT INTERRUPTER

FLOOR BOX SUITABLE FOR CONCRETE FLOOR

POUR; TWO COMPARTMENTS - POWER AND

TELECOMMUNICATIONS; FLUSH COVER/FLANGE

WITH HINGED ACCESS TO RECEPTACLES AND

JACKS RECESSED BELOW COVER IN FLOOR

BOX. PROVIDE 8" FIRE RATED POKE THRU

ABOVE GROUND FLOOR.

WALL SWITCH, AC TYPE, SPST, MOUNT 48"

ABOVE FINISHED FLOOR

WALL SWITCH, AC TYPE, DPDT, MOUNT 48"

ABOVE FINISHED FLOOR

3-WAY WALL SWITCH, MOUNT 48" ABOVE

FINISHED FLOOR

4-WAY WALL SWITCH, MOUNT 48" ABOVE

FINISHED FLOOR

SLIDE DIMMER, MOUNT 48" ABOVE FINISHED

FLOOR

MOTOR RATED DISCONNECT SWITCH WITH

THERMAL OVERLOADS, SINGLE POLE SINGLE

THROW, MOUNT ON UNIT, UNLESS INDICATED

OTHERWISE.

WALL MOUNTED, DUAL TECHNOLOGY VACANCY

SWITCH, MOUNT 48" ABOVE FINISHED FLOOR

WALL MOUNTED, DUAL TECHNOLOGY

OCCUPANCY SWITCH, MOUNT 48" ABOVE

FINISHED FLOOR

ELECTRICAL LEGEND

D

M

V

O

LV

OS

DS

PE

5-30R

EWC

ONE-LINE

TRANSFORMER

CURRENT TRANSFORMER

FUSE

ELECTRICAL CONNECTION

CIRCUIT BREAKER

SWITCH

SURGE ARRESTORS

SEPARABLE CONNECTION

DRY TYPE TRANSFORMER, K-4 RATED, KVA AS

INDICATED

GROUND

SCHEMATIC

PILOT LIGHT (G=GREEN, R=RED, Y=AMBER)

CONTROL RELAY COIL

SHUNT TRIP COIL

TIME DELAY RELAY COIL

MOTOR STARTER COIL

SW

S

S

S

S

S

S

S

S

S

VS

D

F

G

H

P

J

LP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

E-002

ELECTRICAL LEGEND

EOFK

NOTE:

1. NOT ALL SYMBOLS SHOWN WILL BE USED ON THIS PROJECT.

UP

GENERAL

STORAGE

STORAGE

CLOSET

PLAN LEGEND

AREA OF NO WORK

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

ED100

ELECTRICAL BASEMENT DEMOLITION

PLAN

EOFK

SCALE: 3/8" = 1'-0"F1

ELECTRICAL BASEMENT DEMOLITION PLAN

1. DISCONNECT AND REMOVE ALL EXISTING

RECEPTACLES ALONG WITH WIRING, CONDUIT AND

ALL ACCESSORIES BACK TO SOURCE.

2. DISCONNECT AND REMOVE ALL LIGHT FIXTURES

INCLUDING EXIT AND EMERGENCY FIXTURES AND

LIGHT SWITCHES ALONG WITH WIRING, CONDUIT

AND ALL ACCESSORIES BACK TO SOURCE.

3. EXISTING PANELBOARD MDP TO BE DEMOLISHED

AND REPLACED WITH NEW. ALL EXISTING FEEDER

AND CONDUIT SHALL REMAIN INTACT. CONTRACTOR

SHALL PLACE A PULLBOX WHERE EXISTING MDP

PANEL IS CURRENTLY LOCATED THEN EXTEND AND

SPLICE CONDUIT AND FEEDER IN PULLBOX FROM

EXISTING LOCATION OF MDP TO NEW LOCATION OF

MDP AS INDICATED ON EP100. SPLICING SHALL BE

DONE PER SPECIFICATION 26 05 19 PART 2 AND

PART 3.

4. POWER FOR EXISTING WATER HEATER SHALL BE

DISCONNECTED FROM EXISTING MDP PANEL TO BE

DEMOLISHED.

KEYNOTES:

SCALE: = 1'-0"3/8"

0 2 4 62

1 2

1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL

NOTES, ABBREVIATIONS & LEGEND.

SHEET NOTES:

DN

DN

CR

CR

CR

CR

CR

CR

CR

P1

OFFICE OFFICE

STORAGE

TOILET

COPY RM OFFICE OFFICE OFFICE

HSK

OFFICE

OFFICEOFFICE

RECEPTION

OFFICEOFFICE

STORAGE

EQUIP RM

CORRIDOR

LOBBY

CORRIDOR

CORRIDOR

107106 109 111 112 113

116117

103104

101A

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

ED101

ELECTRICAL FIRST FLOOR

DEMOLITION PLAN

EOFK

SCALE: 3/8" = 1'-0"F1

ELECTRICAL FIRST FLOOR DEMOLITION PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

1. DISCONNECT AND REMOVE ALL EXISTING

RECEPTACLES ALONG WITH WIRING, CONDUIT

AND ALL ACCESSORIES BACK TO SOURCE.

2. DISCONNECT AND REMOVE ALL LIGHT FIXTURES

INCLUDING EXIT AND EMERGENCY FIXTURES AND

LIGHT SWITCHES ALONG WITH WIRING, CONDUIT

AND ALL ACCESSORIES BACK TO SOURCE.

REFER TO TELECOM DRAWINGS TD-101 AND

TD-102 FOR LOCATION OF EXISTING WIFI ACCESS

POINT DEVICES TO BE SALVAGED.

3. EXISTING PANEL P1 IS TO BE DEMOLISHED.

REMOVE ALL EXISTING FEEDERS AND CONDUITS

BACK TO SOURCE.

4. EXISTING EXTERIOR LIGHTS SHALL REMAIN AND

BE PROTECTED DURING CONSTRUCTION.

KEYNOTES:#

1 2 1 2 1 2 1 2 1 2 1 2

1 2 1 2

1 2

1 2 1 2

1 2

1 2

1 2

1 2 1 2

1 2

1 2

1 2

1 2

1 2

1. REFER TO E-001 & E-002 FOR ELECTRICAL

GENERAL NOTES, ABBREVIATIONS & LEGEND.

SHEET NOTES:

4 4

OFFICE

CLOSET

CONFERENCE RM

KITCHEN

OFFICE

CLOSET

CORRIDOR

LOBBY

CORRIDOR

STORAGE

TOILET

OFFICE OFFICE OFFICE OFFICE

OFFICEOFFICEMECH RM

HSK

204A

203A

206 208 209 210

211212213

P2

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

ED102

ELECTRICAL SECOND FLOOR

DEMOLITION PLAN

EOFK

SCALE: 3/8" = 1'-0"F1

ELECTRICAL SECOND FLOOR DEMOLITION PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

1. DISCONNECT AND REMOVE ALL EXISTING

RECEPTACLES ALONG WITH WIRING, CONDUIT

AND ALL ACCESSORIES BACK TO SOURCE.

2. DISCONNECT AND REMOVE ALL LIGHT FIXTURES

INCLUDING EXIT AND EMERGENCY FIXTURES AND

LIGHT SWITCHES ALONG WITH WIRING, CONDUIT

AND ALL ACCESSORIES BACK TO SOURCE.

REFER TO TELECOM DRAWINGS TD-101 AND

TD-102 FOR LOCATION OF EXISTING WIFI ACCESS

POINT DEVICES TO BE SALVAGED.

3. EXISTING PANEL P2 IS TO BE DEMOLISHED.

REMOVE ALL EXISTING FEEDERS AND CONDUITS

BACK TO SOURCE.

1 2

1 2 1 2 1 2 1 2

1 2

1 2

1 2

1 2

1 2

1 2

1 2 1 2 1 2 1 2

1 2

1 2

1 2 1 2

1 2 1 2

1 2

1. REFER TO E-001 & E-002 FOR ELECTRICAL

GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. FINISH DISTURBED AREAS TO MATCH EXISTING

CONDITIONS.

KEYNOTES:#

SHEET NOTES:

O

OS

OS

K4

K4

K4E

K4

K4E

K4

K4E

K4E

K4E

K4E

F4E

F4E

K4

X1S

MDP-7

MDP-7

MDP-7

MDP-7

MDP-7

MDP-7

MDP-7

MDP-7

MDP-7

MDP-7

MDP-7

MDP-7

MDP-7

MDP-7

LX

MDP-7

b

NL

b b b

ARMORY /

WEAPONS

B04

CORRIDOR

B00

X1W

MDP-7

STORAGE

B02

MECHANICAL

ROOM

B01

CORRIDOR

B03

PLAN LEGEND

AREA OF NO WORK

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

EL100

ELECTRICAL BASEMENT LIGHTING

PLAN

EOFK

SCALE: 3/8" = 1'-0"F1

ELECTRICAL BASEMENT LIGHTING PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

1. REFER TO E-001 & E-002 FOR ELECTRICAL

GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. REFER TO LIGHTING FIXTURE SCHEDULE ON

E-611.

3. PROVIDE UNSWITCHED POWER TO NIGHT LIGHT

FIXTURES. PROVIDE UL-924 90 MINS BATTERY

BACKUP TO ALL EMERGENCY FIXTURES SHOWN.

4. ALL STAIRWELL LIGHT FIXTURES SHALL OPERATE

AT 50% OUTPUT CONTINUOUSLY, AND INCREASE

TO 100% OUTPUT UPON ACTIVATION OF

ONBOARD OCCUPANCY SENSOR. PROVIDE 24-

HOUR, UNSWITCHED POWER.

SHEET NOTES:

# KEYNOTES:

1. EXTERIOR LIGHTS SHALL BE CONTROLLED VIA

PHOTOCELL. TYPICAL FOR ALL EXTERIOR LIGHTS.

DO

OS

OS

OS

DO

DO DO

DO

D O

DO

DO

DO

DO

OS

D

OS

OS

OS

OS

D

OS

A A

A

A A

A A

A

A

AE

A

A A A

A A

AE

AE

A

A A

AE A

AE

AE

AE

A

AE

AE

AE AE

K4E

X1S

X1S

X1S

X1S

X1W

DD

DDDD

AE

A

A A

K3

X1S

P1-3 P1-3

P1-3 P1-3

P1-5 P1-5

P1-3 P1-3

P1-3 P1-3

P1-5

P1-3

P1-3

P1-3

P1-3

P1-5

P1-3

P1-3

P1-3

P1-3

P1-1

P1-1

P1-5

P1-1

P1-1

P1-1

P1-1

P1-1

P1-1

P1-1 P1-1

P1-1

P1-1

P1-1

P1-1

P1-5P1-5

P1-5

P1-5

P1-5

P1-5

P1-1

P1-3

DD

DDDD

DD

P1-5 P1-5

P1-5

P1-5 P1-5

P1-5

G

G

G G

P1-5 P1-5

P1-5

P1-5 b a b a

XE

XE

XE

P1-19

P1-19

P1-19

P1

X1W

P1-5

P1-5 F4E

P1-5

F4E a a a bb b

NL NL

NL

NL

NL

OFFICE

OFFICE

CORRIDOR

OFFICE

OFFICE

RECEPTION

CORRIDOR

WOMEN

RESTROOM

STAFF

LOUNGE

MEN

RESTROOM

OFFICE

EVIDENCE

PROCESSING

EVIDENCE

ROOM

INTERVIEW

ROOM

OFFICER

WORK

ROOM

HOUSE

KEEPING

WAITING

ROOM

LXP1-19

P1-19

XE

P1-5

P1-5

P1-5

P1-5

E4

E4

E4

E4

LX

LX

P1-19

P1-19 LX P1-19

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

EL101

ELECTRICAL FIRST FLOOR LIGHTING

PLAN

EOFK

SCALE: = 1'-0"3/8"

0 2 4 62

SCALE: 3/8" = 1'-0"F1

ELECTRICAL FIRST FLOOR LIGHTING PLAN

# KEYNOTES:

1. COORDINATE FINAL LOCATION OF LIGHT

CONTROL SWITCHES AND DIMMERS WITH COR

PRIOR TO ROUGH-IN.

2. EXTERIOR LIGHTS SHALL BE CONTROLLED VIA

PHOTOCELL. TYPICAL FOR ALL EXTERIOR LIGHTS.

3. EXISTING EXTERIOR LIGHT SHALL BE CLEANED,

RE-LAMPED WITH LED BULB AND VERIFIED THAT

THEY ARE IN GOOD WORKING CONDITION. LIGHT

FIXTURES SHALL BE REPLACED IF THEY ARE NOT

IN GOOD WORKING CONDITION. COORDINATE

FIXTURE SELECTION WITH COR.

4. EXTERIOR LIGHT FIXTURE SHALL BE 7' ABOVE

STAIR LANDING LOCATED BETWEEN FIRST AND

SECOND FLOOR. SEE ARCHITECTURAL EXTERIOR

ELEVATION DRAWINGS FOR MORE DETAILS.

1. REFER TO E-001 & E-002 FOR ELECTRICAL

GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. REFER TO BOTH INTERIOR AND ARCHITECTURAL

REFLECTED CEILING PLAN FOR EXACT

LOCATIONS AND MOUNTING HEIGHTS OF ALL

LIGHT FIXTURES SHOWN.

3. REFER TO LIGHTING FIXTURE SCHEDULES ON

E-611.

4. PROVIDE UNSWITCHED POWER TO NIGHT LIGHT

FIXTURES. PROVIDE UL-924 90 MINS BATTERY

BACKUP TO ALL EMERGENCY FIXTURES SHOWN.

5. ALL STAIRWELL LIGHT FIXTURES SHALL OPERATE

AT 50% OUTPUT CONTINUOUSLY, AND INCREASE

TO 100% OUTPUT UPON ACTIVATION OF

ONBOARD OCCUPANCY SENSOR. PROVIDE 24-

HOUR, UNSWITCHED POWER.

SHEET NOTES:

TYP.

TYP.

TYP.

7' AFF

8' AFF

DO DO

DO DO

OS

OSOS

OSOS

DO DO

D O

D

OS

D D

OS

3 3

D

OS

OS

OS OS

A A A

A2

A

A A

A

A A

AE

A

A

A A

AE

A2E

AE

A A

AE

AE

AE

A A

AEA

AE

AAE

K4E

X1S

X1S

X1S

BE B B B

B

BBBEB

B

DD

AE

A

A AE

A2

A2E

A2

A2E

K3

P2-1

P2-1

P2-1

P2-1

P2-5 P2-5

P2-1

P2-1

P2-1

P2-1

P2-3 P2-3

P2-3 P2-3

P2-3

P2-3

P2-3

P2-3

P2-3

P2-3

P2-5P2-5P2-5P2-5P2-5P2-5

P2-5

P2-5

P2-5 P2-5

P2-5 P2-5

P2-3P2-3

P2-3 P2-3

P2-3

P2-3

P2-5

P2-5

P2-5

P2-5

P2-1

P2-1

P2-1

P2-1 P2-1

P2-1 P2-1

P2-1

P2-1

P2-1

P2-1 P2-1 P2-1 P2-1

P2-1 P2-1

P2-1P2-1P2-1

P2-1

P2-5

X1S

CE

C

CE

C CE C

CE

CE

CEC

G

G

G G

G

P2-5

P2-5

P2-5

P2-5P2-5

G

G

P2-5

P2-5 a a b b

PP

P2-1

LX

P1-19

P2 aaaa a a NL ab b b b b bb

NL

NL

NL

NL

a b ab a a a a a a a aaa b aaa a a a a a a a b

LX

P1-19

P2-1

DEPUTY

CHIEF

OFFICE

OIT

CORRIDOR

CONFERENCE

ROOM

CHIEF

OFFICE

LOBBY

MECHANICAL

ROOM

OFFICE

OFFICE

OFFICE

OFFICE

CORRIDOR

CORRIDOR

MEN

RESTROOM

MEN

SHOWER &

LOCKER

ROOM

WOMEN

RESTROOM

WOMEN

SHOWER &

LOCKER

ROOM

206A

ELECT.

HOUSE

KEEPING

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

EL102

ELECTRICAL SECOND FLOOR

LIGHTING PLAN

EOFK

SCALE: = 1'-0"3/8"

0 2 4 62

SCALE: 3/8" = 1'-0"F1

ELECTRICAL SECOND FLOOR LIGHTING PLAN

# KEYNOTES:

1. COORDINATE FINAL LOCATION OF LIGHT CONTROL

SWITCHES AND DIMMERS WITH COR PRIOR TO ROUGH-IN.

2. EXTERIOR LIGHTS SHALL BE CONTROLLED VIA PHOTOCELL.

TYPICAL FOR ALL EXTERIOR LIGHTS.

SHEET NOTES:

1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,

ABBREVIATIONS & LEGEND.

2. REFER TO BOTH INTERIOR AND ARCHITECTURAL REFLECTED

CEILING PLAN FOR EXACT LOCATIONS AND MOUNTING

HEIGHTS OF ALL LIGHT FIXTURES SHOWN.

3. REFER TO LIGHTING FIXTURE SCHEDULES ON E-611.

4. PROVIDE UNSWITCHED POWER TO NIGHT LIGHT FIXTURES.

PROVIDE UL-924 90 MINS BATTERY BACKUP TO ALL

EMERGENCY FIXTURES SHOWN.

5. ALL STAIRWELL LIGHT FIXTURES SHALL OPERATE AT 50%

OUTPUT CONTINUOUSLY, AND INCREASE TO 100% OUTPUT

UPON ACTIVATION OF ONBOARD OCCUPANCY SENSOR.

PROVIDE 24-HOUR, UNSWITCHED POWER.

8' AFF

8' AFF

OS OS OS

P2-19

P2-19

P2-19

P2-19 P2-19

P2-19 P2-19

P2-19

P2-19

P2-19

K4

K4E

K4

K4E K4

K4 K4E

K4

K4E

K4

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

EL103

ELECTRICAL ATTIC LIGHTING PLAN

EOFK

SCALE: 3/8" = 1'-0"F1

ELECTRICAL ATTIC LIGHTING PLAN

SHEET NOTES:

1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES,

ABBREVIATIONS & LEGEND.

2. REFER TO BOTH INTERIOR AND ARCHITECTURAL REFLECTED

CEILING PLAN FOR EXACT LOCATIONS AND MOUNTING

HEIGHTS OF ALL LIGHT FIXTURES SHOWN.

3. REFER TO LIGHTING FIXTURE SCHEDULES ON E-611.

4. PROVIDE UL-924 90 MINS BATTERY BACKUP TO ALL

EMERGENCY FIXTURES SHOWN.

5. ALL STAIRWELL LIGHT FIXTURES SHALL OPERATE AT 50%

OUTPUT CONTINUOUSLY, AND INCREASE TO 100% OUTPUT

UPON ACTIVATION OF ONBOARD OCCUPANCY SENSOR.

PROVIDE 24-HOUR, UNSWITCHED POWER.

SCALE: = 1'-0"3/8"

0 2 4 62

J

J

MDP

MDP-9

MDP-9

MDP-9

MDP-9

MDP-9

MDP-13

MDP-9

MDP-11

MDP-11

MDP-11

MDP-11

MDP-11

MDP-14

MOD

EWH

1 AHU

DH

MDP-11

MDP-11

MDP-11

MDP-25

IDS PANEL

MECHANICAL

ROOM

B01

STORAGE

B02

CORRIDOR

B03

ARMORY /

WEAPONS

B04

CORRIDOR

B00

PLAN LEGEND

AREA OF NO WORK

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

EP100

ELECTRICAL BASEMENT POWER PLAN

EOFK

SCALE: 3/8" = 1'-0"F1

ELECTRICAL BASEMENT POWER PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

1. REFER TO E-001 & E-002 FOR ELECTRICAL

GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. ELECTRICAL CONTRACTOR SHALL PROVIDE

TYPED UPDATED PANEL DIRECTORIES FOR ALL

PANELS AFFECTED DURING CONSTRUCTION.

3. ALL GFI RECEPTACLES SHALL BE SELF-TESTING.

4. ALL WIRING TO BE DONE WITH COPPER WIRE

UNLESS OTHERWISE NOTED.

5. FIELD VERIFY EXACT LOCATION OF ALL DEVICES

AND EQUIPMENT PRIOR TO ROUGH IN.

6. SEE MECHANICAL EQUIPMENT SCHEDULE ON

E-611.

SHEET NOTES:

# KEYNOTES:

1. ELECTRICAL CONTRACTOR SHALL EXTEND AND

SPLICE CONDUIT FROM EXISTING LOCATION OF

MDP ON SHEET ED100 TO NEW LOCATION OF MDP

AS INDICATED. SPLICING SHALL BE DONE IN A

PULLBOX TO BE LOCATED AT THE CURRENT

LOCATION OF THE EXISTING MDP PANEL AS

SHOWN ON ED100. SPLICING SHALL BE DONE PER

SPECIFICATION 26 05 19 PART 2 AND PART 3.

F A

C P

J J

J

J J

J

J

J

J J

J

J

J J

J

P1

TV

TV

MICROWAVE 65" AFF

COFFEE MAKER

P1-12

P1-13

P1-14

P1-15

P1-14

P1-14

P1-14

P1-17

P1-17

P1-17

P1-16

P1-16

P1-16

P1-2

P1-16

P1-2

P1-2

P1-6

P1-4

P1-4

P1-4

P1-4 P1-18

P1-18

P1-18

P1-18

P1-7

P1-7

P1-7

P1-7

P1-7

P1-7

P1-7

P1-6

P1-6

P1-6

P1-9

P1-9

P1-9

P1-9

P1-6

P1-11

P1-11

P1-11

P1-11

P1-11

P1-11

P1-11

P1-8 P1-10

P1-10

P1-10

P1-8

P1-8

P1-8

P1-6

P1-6

CU

AC

P1-8

P1-10

CU

P1-2

P1-11

P1-11

REFRIGERATOR

P1-21

P1-23

P1-14

P1-25

STAFF

LOUNGE

OFFICE

CORRIDOR

OFFICE

OFFICE

OFFICE

WOMEN

RESTROOM

OFFICER

WORK

ROOM

MEN

RESTROOM

INTERVIEW

ROOM

EVIDENCE

PROCESSING

EVIDENCE

ROOM

114RECEPTION

HOUSE

KEEPING

OFFICE

CORRIDOR

P2-14

P2-14

P2-14

P2-14

P2-14

P2-14

WP

P1-27

WAITING

ROOM

P1-29

P1-29

P1-29 P1-29 P1-29

FSD

P1-29P1-29

FSD

FSD

FSD FSD FSD

P1-29

FSD FSD

P1-31

5ELECT.

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

EP101

ELECTRICAL FIRST FLOOR POWER

PLAN

EOFK

SCALE: 3/8" = 1'-0"F1

ELECTRICAL FIRST FLOOR POWER PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

1. REFER TO E-001 & E-002 FOR ELECTRICAL

GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. ELECTRICAL CONTRACTOR SHALL PROVIDE

TYPED UPDATED PANEL DIRECTORIES FOR ALL

PANELS AFFECTED DURING CONSTRUCTION.

3. ALL GFI RECEPTACLES SHALL BE SELF-TESTING.

4. ALL WIRING TO BE DONE WITH COPPER WIRE

UNLESS OTHERWISE NOTED.

5. FIELD VERIFY EXACT LOCATION OF ALL DEVICES

AND EQUIPMENT PRIOR TO ROUGH IN.

6. CONFIRM FINAL LOCATIONS OF RECEPTACLES

WITH COR AND GOVERNMENT PROVIDED

FURNITURE LAYOUTS PRIOR TO INSTALLATION.

7. SEE MECHANICAL EQUIPMENT SCHEDULE ON

E-611.

SHEET NOTES:

# KEYNOTES:

1. COORDINATE FINAL VENDING MACHINE

RECEPTACLE LOCATIONS IN FIELD WITH COR

PRIOR TO ROUGH-IN.

2. COORDINATE FINAL LOCATION OF TV

RECEPTACLE WITH OWNER PRIOR TO ROUGH IN.

3. ALL RECEPTACLES IN THIS ROOM SHALL BE

TAMPER RESISTANT WITH STAINLESS STEEL

COVER PLATES.

4. HARDWIRE CONNECTION FOR ACTIVE INFRARED

SENSOR FOR AUTOMATIC OPERATION OF

PLUMBING FIXTURE. SEE P-001 FOR MORE

INFORMATION.

5. POWER FOR FIRE RATED CURTAIN WALL.

J

J J

J J

J

J J

P2

TV

P2-2

P2-2

P2-2

P2-2

P2-16

P2-16

P2-2

P2-16

P2-32

P2-4

P2-4

P2-4

P2-4

P2-4 P2-4

P2-4

P2-12

P2-12

P2-12

P2-12

P2-12

P2-12

P2-6 P2-6

P2-6

P2-6

P2-6

P2-6

P2-8

P2-8

P2-8

P2-8

P2-8

P2-6

P2-10

P2-10

P2-7

P2-7 P2-7

P2-7

P2-11

P2-11

P2-11

P2-11

P2-11

P2-9

P2-9

P2-9

P2-9

P2-9

P2-10

P2-10

P2-10

P2-6

P2-6

P2-29

MOD

AHU

AC

P2-4

P2-27

P2-28

CCTV PANEL

ACS PANEL

DEPUTY

CHIEF

OFFICE

OIT

CORRIDOR

CONFERENCE

ROOM

WOMEN

RESTROOM

CORRIDOR

CHIEF

OFFICE

LOBBY

MECHANICAL

ROOM

OFFICE

OFFICE

OFFICE

OFFICE

CORRIDOR

MEN

RESTROOM

MEN

SHOWER &

LOCKER

ROOM

WOMEN

SHOWER &

LOCKER

ROOM

206A

ELECT.

HOUSE

KEEPING

P2-30

P2-30

P2-30

P2-30

3 2

P2-15 P2-17

P2-32

P2-32

P2-37

P2-37 P2-37

FSD

FSD FSD

TV

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

EP102

ELECTRICAL SECOND FLOOR POWER

PLAN

EOFK

SCALE: 3/8" = 1'-0"F1

ELECTRICAL SECOND FLOOR POWER PLAN

SCALE: = 1'-0"3/8"

0 2 4 62

1. REFER TO E-001 & E-002 FOR ELECTRICAL

GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. ELECTRICAL CONTRACTOR SHALL PROVIDE

TYPED UPDATED PANEL DIRECTORIES FOR ALL

PANELS AFFECTED DURING CONSTRUCTION.

3. ALL GFI RECEPTACLES SHALL BE SELF-TESTING.

4. ALL WIRING TO BE DONE WITH COPPER WIRE

UNLESS OTHERWISE NOTED.

5. FIELD VERIFY EXACT LOCATION OF ALL DEVICES

AND EQUIPMENT PRIOR TO ROUGH IN.

6. CONFIRM FINAL LOCATIONS OF RECEPTACLES

WITH COR AND GOVERNMENT PROVIDED

FURNITURE LAYOUTS PRIOR TO INSTALLATION.

7. SEE MECHANICAL EQUIPMENT SCHEDULE ON

E-611.

SHEET NOTES:

# KEYNOTES:

1. INDOOR UNIT IS POWERED FROM OUTDOOR UNIT.

PROVIDE ALL WIRES, CONDUITS AND

ACCESSORIES REQUIRED FOR COMPLETE

INSTALLATION. INSTALL PER MANUFACTURE'S

RECOMMENDATION.

2. ELECTRICAL CONTRACTOR SHALL CONFIRM

FINAL LOCATION OF POWER AND DATA POKE-

THRU DEVICE WITH FURNITURE VENDOR PRIOR

TO INSTALLATION.

3. COORDINATE FINAL LOCATION OF TV

RECEPTACLE WITH COR PRIOR TO ROUGH IN.

4. QUAD RECEPTACLES SHALL BE MOUNTED ON

RACKS. COORDINATE FINAL LOCATION WITH

TELECOM CONTRACTOR. SEE TELECOM

DRAWING T-401 FOR MORE INFORMATION.

5. HARDWIRE CONNECTION FOR ACTIVE INFRARED

SENSOR FOR AUTOMATIC OPERATION OF

PLUMBING FIXTURE. SEE P-001 FOR MORE

INFORMATION.

EUH

EUH

P2-19

P2-19

EF

EF

MOD

P2-31

ATTIC

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

EP103

ELECTRICAL ATTIC POWER PLAN

EOFK

SCALE: 3/8" = 1'-0"F1

ELECTRICAL ATTIC POWER PLAN

1. REFER TO E-001 & E-002 FOR ELECTRICAL

GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. ELECTRICAL CONTRACTOR SHALL PROVIDE

TYPED UPDATED PANEL DIRECTORIES FOR ALL

PANELS AFFECTED DURING CONSTRUCTION.

3. ALL WIRING TO BE DONE WITH COPPER WIRE

UNLESS OTHERWISE NOTED.

4. FIELD VERIFY EXACT LOCATION OF ALL DEVICES

AND EQUIPMENT PRIOR TO ROUGH IN.

5. SEE MECHANICAL EQUIPMENT SCHEDULE ON

E-611.

SHEET NOTES:

SCALE: = 1'-0"3/8"

0 2 4 62

A

C

A C

A A

A

B

A

C

C

C

A A

STRAP EVERY 3'-0" INTERVAL

SECURE TO ROOF WITH

ADHESIVE BASE

ROOF CONDUCTOR

M

IN

COPPER DOWNLEAD CABLE. COURSE CABLE

BELOW GRADE. CADWELD TO GROUND RING.

SEE LAYOUT FOR LOCATIONS.

"TURN" CONDUIT TO EXIT

BUILDING A MINIMUM OF

12"

BELOW FINISHED GRADE

COPPER LOOP TYPE PROTECTOR

PIPE ANCHOR FURNISHED WITH

1/4" X 1-1/4" MASONRY DRIVE

ANCHOR. FOUR REQUIRED PER

PROTECTOR SPACE EVENLY IN A

SIMILAR MANNER AS SHOWN.

1" PVC PROTECTOR PIPE. ONE

REQUIRED PER EACH DOWNLEAD

TO EXTEND FROM ROOF TO

BELOW GRADE. SEAL ENDS OF

PROTECTOR PERMANENTLY

WATER TIGHT WITH DUCT SEAL.

CONCEAL PIPE IN WALL

ROOF

SLAB ON

GRADE

TR TR

TR

A

A

A

A

A

A A A

A AA

AA A

EAVE

EL. ±26'-4"

T.O.P.

EL. ±32'-4"

EAVE

EL. ±26'-4"

T.O.P.

EL. ±32'-4"

EAVE

EL. ±26'-4"

EAVE

EL. ±26'-4"

T.O.P.

EL. ±32'-4"

T.O.P.

EL. ±32'-4"

BURY 1'-6" MIN. BELOW

FINISHED GRADE & 2'-0" MIN.

FROM FOUNDATION WALL, TYP.

LOCATION OF THRU-ROOF CONNECTIONS TO

BE FIELD DETERMINED, USE EXISTING

CONDUITS FOR NEW DOWNLEADS

G G

G

A

A

A

A

A A

A A

B B

TR

LEGEND

AIR TERMINAL

MECHANICAL CONNECTION

MISC. BONDING

THRU-ROOF

CONNECTION

GROUND BAR

CLASS I ALUMINUM MAIN CONDUCTOR

CLASS I COPPER MAIN CONDUCTOR

COPPER CLAD GROUND ROD WITH

EXOTHERMIC WELD CONNECTIONG

GB

FASTEN CABLE 3'-0"

O.C. MAX, WITH

APPROPRIATE

CABLE FASTENER.

NOTE: CONDUCTOR SHALL INTERCONNECT ALL AIR

TERMINALS AND SHALL FORM A TWO-WAY PATH

FROM EACH AIR TERMINAL HORIZONTALLY,

DOWNWARD OR RISING AT A RATE NOT EXCEEDING

3" PER FOOT (76.2mm) TO CONNECTIONS WITH

GROUND TERMINALS.

R 8"

90°

NOTE:

NO BEND OF A CONDUCTOR SHALL FORM

AN INCLUDED ANGLE OF LESS THAN 90

DEGREES, NOR SHALL IT HAVE A RADIUS

OF BEND LESS THAN 203mm (8").

NO. LC2414A, CLASS I

ALUMINUM MAIN CONDUCTOR

NO. TRC114B, BI-METAL

THRU-ROOF CONNECTOR

NO. LC2917C, CLASS I

COPPER MAIN CONDUCTOR

M

IN

MIN.

3'-0"

BLDG. COLUMN OR WALL

NEW LIGHTNING PROTECTION

SYSTEM DOWN CONDUCTOR IN

1" PVC MOUNTED EXPOSED

FIN. GRADE

LIGHTNING PROTECTION

SYSTEM DOWN

CONDUCTOR

CADWELD TO EXISTING COUNTERPOISE

GROUND ROD & CONNECTOR

EXISTING COUNTERPOISE

CONCRETE SLAB

RAFTERS

MAIN CONDUCTOR

CABLE CONNECTOR

RISER BAR

SEALING WASHER

AIR TERMINAL

ROOF

CLIP CABLE SUPPORT

M

IN

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved: Chief Engineering

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

VAMC MOUNTAIN HOME, TN

CORRECT ADMIN BLDG 20

ENVIRONMENT AND

CONDITION DEFICIENCIES

MARCH 15, 2021

BID DOCUMENTS 621-15-101

E-131

LIGHTNING PROTECTION PLAN

EOFK

SHEET NOTES:

1. REFER TO E-001 & E-002 FOR ELECTRICAL GENERAL NOTES, ABBREVIATIONS & LEGEND.

2. THE LIGHTNING PROTECTION SHALL REQUIRE AN INSPECTION PRIOR TO ACCEPTANCE.

THE SYSTEM SHALL BE INSPECTED BY A COMMERCIAL, THIRD PARTY INSPECTOR WHOSE

SOLE WORK IS LIGHTNING PROTECTION, AND SHALL BE CERTIFIED BY THIS THIRD PARTY

INSPECTOR AS COMPLIANT WITH NFPA 780 AND NFPA 70.

3. THE USE OF BUILDING STEEL AS DOWN CONDUCTORS IS NOT PERMITTED.

4. INSTALLATION OF THE LIGHTNING PROTECTION SYSTEM SHALL NOT VOID THE

WARRANTY OF THE ROOF.

5. LOCATE AIR TERMINALS AS SHOWN. TAKE CARE TO ENSURE THAT ALL POINTS ARE

WITHIN 2'-0" OF OUTSIDE BUILDING EDGE, OUTSIDE CORNERS, RIDGE ENDS, AND THAT

MAX SPACING DOES NOT EXCEED 20'-0" , AND THAT MIN PROJECTION ABOVE OBJECT

PROTECTED IS 10" ; POINTS PROJECTING 24" MAY BE SPACED AT 25'-0" MAX.

6. MAINTAIN HORIZONTAL OR DOWNWARD COURSING OF MAIN CONDUCTOR. ENSURE THAT

ALL BENDS HAVE AT LEAST AN 8" RADIUS AND DO NOT EXCEED 90 DEGREES.

7. ATTACH ALL EXPOSED ROOF, DOWN LEAD AND BONDING CABLES AT 3'-0" ON CENTER

MAX. VERIFY COMPATIBILITY OF ADHESIVE ON MEMBRANE ROOF APPLICATION PRIOR TO

INSTALLATION.

8. GROUND ROD ELECTRODES SHALL BE INSTALLED AS SHOWN, BUT IN NO INSTANCE

SHALL THEY BE LESS THAN 1'-0" BELOW GRADE AND 2'-0" FROM FOUNDATION WALL.

DRIVEN RODS SHALL PENETRATE THE EARTH AT LEAST 10'-0".

9. BOND TO WATER SERVICE AND OTHER PIPING SYSTEMS AS SHOWN AND AS REQUIRED

BY CODE.

10. MAIN SIZE LIGHTNING CONDUCTOR BONDED TO MAIN GROUND

11. BUS FIELD VERIFY LOCATION 1 1/4" CONDUIT FOR ACCESS, INSTALLED BY OTHERS.

INTERCONNECT LIGHTNING PROTECTION GROUND TO TELEPHONE AND OTHER BUILDING

GROUND SYSTEMS LOCATION FIELD DETERMINED OR AS REQUIRED BY CODE.

12. LB'S AND SIMILAR CONDUIT BODIES MAY NOT BE USED IN THE INSTALLATION OF

DOWNLEAD CONDUITS, AS THEY DO NOT ADHERE TO THE REQUIRED 8" MINIMUM BEND

RADIUS.

13. SYSTEM SHALL BE INSTALLED AS SHOWN TO ENSURE PROPER CODE COMPLIANCE AND

SYSTEM CERTIFICATION. ANY MAJOR VARIANCE SHALL BE RESUBMITTED FOR

APPROVAL.

14. ALL MATERIALS TO BE UNDERWRITER'S LABORATORIES APPROVED WITH APPROPRIATE

UL96 MARKINGS.

15.