This pre-solicitation notice announces a forthcoming solicitation for construction services. The James H. Quillen VA Medical Center in Mountain Home, TN requires renovations to Administration Building 20 including offices, meeting rooms, locker rooms, and replacement of finish materials. Work includes modifications to existing areas and demolition. The estimated range for construction costs is between $1,000,000 and $5,000,000. The solicitation will be open to SDVOSB concerns only and is set aside under 38 U.S.C. 8127(d). The solicitation is expected to be released on or around October 20, 2021 and close on or around November 20, 2021. The NAICS code for this requirement is 236220 and the size standard is $39.5M. Questions regarding this pre-solicitation notice should be submitted in writing and reference the project number, name, and solicitation number.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
G-001
COVER SHEET & SHEET INDEX
RAPJMC
Department of Veterans Affairs
CORRECT ADMIN BLDG 20 ENVIRONMENT
AND CONDITION DEFICIENCIES
BUILDING 20
VAMC MOUNTAIN HOME
MEMORIAL AVENUE AND 2ND STREET
JOHNSON CITY, TENNESSEE 37684
PROJECT # 621-15-101
PROJECT LOCATION
Date
Date
Date
Approved: Electrical Shop Supervisor Date
Approved: Contract Officer Date
Date
Date
Date
Approved: Medical Center Director Date
BID DOCUMENTS APPROVAL
Approved: Associate Director Date
Approved: FMS Chief
Approved: Energy Engineer
Approved: Project Supervisor
Approved: M & D
Approved: Safety Manager
Approved: Infection Control
MEMORIAL AVENUE AND 2ND STREET
JOHNSON CITY, TN 37684
PROJECT LOCATION
MEMORIAL AVENUE AND 2ND STREET
JOHNSON CITY, TN 37684
MARCH 15, 2021
LOCATION MAP
SCALE: N.T.S.
N
VICINITY MAP
SCALE: N.T.S.
N
BID DOCUMENTS
SHEET INDEX
SHEET NUMBER
COVER SHEET & SHEET INDEXG-001
GENERAL
SHEET NAME
GENERAL PROJECT NOTESG-002
BUILDING CODE SUMMARY & DEDUCTIVE ALTERNATESG-003
BASEMENT LIFE SAFETY PLANG-100
FIRST FLOOR LIFE SAFETY PLANG-101
SECOND FLOOR LIFE SAFETY PLANG-102
ARCHITECTURAL
ABBREVIATIONS & SYMBOLSA-001
BASEMENT DEMOLITION PLANAD100
FIRST FLOOR DEMOLITION PLANAD101
SECOND FLOOR DEMOLITION PLANAD102
BASEMENT DEMOLITION REFLECTED CEILING PLANAD130
FIRST FLOOR DEMOLITION REFLECTED CEILING PLANAD131
SECOND FLOOR DEMOLITION REFLECTED CEILING PLANAD132
BASEMENT NEW WORK PLANA-100
FIRST FLOOR NEW WORK PLANA-101
SECOND FLOOR NEW WORK PLANA-102
ATTIC NEW WORK PLANA-103
ROOF NEW WORK PLAN A-104
BASEMENT NEW WORK REFLECTED CEILING PLANA-130
FIRST FLOOR NEW WORK REFLECTED CEILING PLANA-131
SECOND FLOOR NEW WORK REFLECTED CEILING PLANA-132
EXTERIOR ELEVATIONSA-201
PARTITION TYPES & DETAILSA-501
REFLECTED CEILING DETAILSA-502
ACCESS WALL OPENING DETAILS
A-508
WINDOW SCHEDULE & DETAILSA-602
DOOR SCHEDULE, DOOR TYPES, & FRAME TYPESA-601
SHEET INDEX
SHEET NUMBER
FIRE PROTECTION GENERAL NOTES & LEGENDF-001
FIRE PROTECTION
SHEET NAME
BASEMENT FIRE PROTECTION PLANF-100
FIRST FLOOR FIRE PROTECTION PLANF-101
SECOND FLOOR FIRE PROTECTION PLANF-102
ATTIC FIRE PROTECTION PLANF-103
BASEMENT FIRE ALARM PLANFA100
FIRST FLOOR FIRE ALARM PLANFA101
SECOND FLOOR FIRE ALARM PLANFA102
PLUMBING SYMBOLS, ABBREVIATIONS, & SCHEDULESP-001
BASEMENT PLUMBING SANITARY & VENT DEMOLITION PLANPD100
FIRST FLOOR PLUMBING SANITARY & VENT DEMOLITION PLANPD101
SECOND FLOOR PLUMBING SANITARY & VENT DEMOLITION PLANPD102
BASEMENT PLUMBING WATER DEMOLITION PLANPD200
FIRST FLOOR PLUMBING WATER DEMOLITION PLANPD201
SECOND FLOOR PLUMBING WATER DEMOLITION PLANPD202
FIRST FLOOR PLUMBING SANITARY & VENT NEW WORK PLANP-101
SECOND FLOOR PLUMBING SANITARY & VENT NEW WORK PLANP-102
BASEMENT PLUMBING WATER NEW WORK PLANP-200
FIRST FLOOR PLUMBING WATER NEW WORK PLANP-201
SECOND FLOOR PLUMBING WATER NEW WORK PLANP-202
PLUMBING DETAILSP-601
ELECTRICAL NOTES & ABBREVIATIONSE-001
ELECTRICAL BASEMENT DEMOLITION PLANED100
ELECTRICAL FIRST FLOOR DEMOLITION PLANED101
ELECTRICAL SECOND FLOOR DEMOLITION PLANED102
ELECTRICAL BASEMENT LIGHTING PLANEL100
ELECTRICAL FIRST FLOOR LIGHTING PLANEL101
ELECTRICAL SECOND FLOOR LIGHTING PLANEL102
ELECTRICAL BASEMENT POWER PLANEP100
ELECTRICAL FIRST FLOOR POWER PLANEP101
ELECTRICAL SECOND FLOOR POWER PLANEP102
LIGHTING PROTECTION PLANE-131
ELECTRICAL DETAILSE-501
ELECTRICAL RISER DIAGRAM AND FEEDER SCHEDULEE-601
PLUMBING
LUMINAIRE AND MECHANICAL EQUIPMENT SCHEDULEE-611
FIRE PROTECTION DETAILSF-501
GENERAL NOTES, LEGEND, & ABBREVIATIONSC-001
CIVIL
DEMOLITION, SITE, UTILITY, & EROSION CONTROL PLANC-110
C-501
CONSTRUCTION & EROSION CONTROL DETAILSC-502
CONSTRUCTION & EROSION CONTROL DETAILS
ROOF DEMOLITION PLANAD104
ENLARGED PLAN, ELEVATION AND SECTION OF INTERIOR STAIRSA-401
ENLARGED PLAN, EXTERIOR STAIR, & ADA RAMP DETAILS
A-402
A-403
REFLECTED CEILING DETAILSA-503
MILLWORK DETAILSA-504
CORNER GUARD AND MISCELLANEOUS DETAILSA-505
MISCELLANEOUS DETAILSA-506
BASEMENT PLUMBING SANITARY & VENT NEW WORK PLANP-100
COLD AND HOT WATER RISER SCHEMATICP-603
WASTE AND VENT RISER SCHEMATICP-604
SHEET INDEX
SHEET NUMBER
ELECTRICAL
SHEET NAME
ELECTRICAL LEGENDE-002
ELECTRICAL ATTIC LIGHTING PLANEL103
ELECTRICAL ATTIC POWER PLANEP103
ELECTRICAL DETAILSE-502
E-621 PANEL SCHEDULES
TELECOM GENERAL NOTES, ABBREVIATIONS, & LEGENDT-001
TELECOMMUNICATIONS
FIRST FLOOR TELECOMMUNICATION DEMOLITION PLANTD-101
FIRST FLOOR TELECOMMUNICATION PLANT-101
SECOND FLOOR TELECOMMUNICATION PLANT-102
TELECOMMUNICATION DETAILST-501
STANDARD FIRE PROTECTION DETAILS
A-507
BASEMENT TELECOMMUNICATION DEMOLITION PLANTD-100
BASEMENT TELECOMMUNICATION PLANT-100
SECOND FLOOR TELECOMMUNICATION DEMOLITION PLANTD-102
BASEMENT SECURITY PLANT-110
FIRST FLOOR SECURITY PLANT-111
SECOND FLOOR SECURITY PLANT-112
ENLARGED SECOND FLOOR TELECOMMUNICATION ROOMT-401
TELECOMMUNICATION RISER DIAGRAMT-601
SECURITY DETAILST-502
BASEMENT PLAN - HAZARDOUS AREA REPORTAD110
FIRST FLOOR PLAN - HAZARDOUS AREA REPORTAD111
SECOND FLOOR PLAN - HAZARDOUS AREA REPORTAD112
ATTIC PLUMBING SANITARY AND VENT NEW WORK PLANP-103
PLUMBING DETAILSP-602
MECHANICAL GENERAL NOTESM-001
BASEMENT MECHANICAL DEMOLITION PLANMD100
FIRST FLOOR MECHANICAL DEMOLITION PLANMD101
SECOND FLOOR MECHANICAL DEMOLITION PLANMD102
ATTIC MECHANICAL DEMOLITION PLANMD103
BASEMENT MECHANICAL NEW WORK PLANM-100
MECHANICAL DETAILSM-503
FIRST FLOOR MECHANICAL NEW WORK PLANM-101
SECOND FLOOR MECHANICAL NEW WORK PLANM-102
ROOF MECHANICAL NEW WORK PLANM-104
MECHANICAL DETAILSM-501
MECHANICAL
MECHANICAL ABBREVIATIONS AND LEGENDSM-002
ROOF MECHANICAL DEMOLITION PLANMD104
ATTIC MECHANICAL NEW WORK PLANM-103
MECHANICAL DETAILSM-502
MECHANICAL SCHEDULES AND SEQUENCE OF OPERATIONM-601
INTERIORS
BASEMENT SIGNAGE PLANIG100
FIRST FLOOR SIGNAGE PLANIG101
SECOND FLOOR SIGNAGE PLANIG102
BASEMENT FINISH PLANIG160
FIRST FLOOR FINISH PLANIG161
SECOND FLOOR FINISH PLANIG162
SHOWER DRAIN, THRESHOLD, & TRANSITION DETAILSIG501
MOUNTING HEIGHTS & DETAILSIG571
SIGNAGE SCHEDULE & TYPICAL MOUNTING HEIGHTSIG601
SIGNAGE DETAILSIG602
ROOM FINISH SCHEDULE & LEGENDIG603
FIRST FLOOR ACCESSORY PLANIG171
SECOND FLOOR ACCESSORY PLANIG172
LOBBY ENLARGED PLANS & INTERIOR ELEVATIONSIG201
STAFF LOUNGE, WATER FOUNTAIN, & SHOWER ELEVATIONSIG202
ACCESSORY SCHEDULEIG604
FIRST FLOOR RESTROOM ELEVATIONSIG203
SECOND FLOOR RESTROOM ELEVATIONSIG204
GENERAL AND STRUCTURAL NOTESA-002
ATTIC DEMOLITION PLANAD103
DEMOLITION PHOTOSAD901
EXTERIOR ELEVATIONSA-202
MECHANICAL ROOM 212 ENLARGED PLAN & ATTIC ACCESS LADDER DETAILSA-404
ENLARGED PLAN, ELEVATION AND SECTION OF INTERIOR STAIRS
A-509 CONCRETE DETAILS
A-510 DOWNSPOUT AND GUTTER DETAILS
A-511 ROOF DETAILS
A-512 MISCELLANEOUS DETAILS
REVISIONS DATE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
G-002
GENERAL PROJECT NOTES
RAPJMC
GENERAL PROJECT NOTES:
23. DO NOT CUT INTO, REMOVE, OR ALTER ANY STRUCTURAL MEMBER OR PORTION
OF THE FLOOR SYSTEM.
24. INTERIOR PARTITION MOVEMENT CONTROL:
A. VERTICAL CONTROL JOINTS FOR ANY WALL LENGTH ARE TO OCCUR AT NOT
MORE THAN 30'-0" O.C. IN THE HORIZONTAL DIRECTION, UNLESS NOTED
OTHERWISE.
B. PROVISIONS SHALL BE MADE BY THE CONTRACTOR IN THE DESIGN,
FABRICATION, AND INSTALLATION OF INTERIOR PARTIONS FOR TYPICAL
FLOOR DEFLECTIONS OF THE STRUCTURE UNDER SUPERIMPOSED LOADS AS
FOLLOWS:TYPICAL ROOF/FLOOR MEMBERS: SPAN/360 BUT NOT LESS THAN
1/2”.
25. IF APPLICABLE THE CONTRACTOR SHALL COORDINATE THE PHASING OF THE
WORK TO BE PERFORMED IN OR ABOUT EXISTING FACILITIES, WITH THE COR
PRIOR TO START OF SUCH WORK.
26. CONTRACTOR TO FIELD VERIFY AND PROTECT EXISTING CONDUITS AND SYSTEMS
WHICH ARE TO REMAIN UNDISTURBED THROUGHOUT THE CONSTRUCTION
PERIOD. IMMEDIATELY REPORT DAMAGE TO THE ARCHITECT IN WRITING AND
REPAIR DAMAGES TO MEET CODES, MANUFACTURER'S SPECIFICATIONS AND
OWNER'S SATISFACTION. NOTIFY THE OWNER AND ARCHITECT OF ANY
DISCREPANCIES.
27. CONTRACTOR TO VERIFY DIMENSIONS/REQUIREMENTS OF THE REQUIRED SLAB
OPENINGS/DEPRESSIONS FOR EQUIPMENT (PLUMBING, ETC.) PRIOR TO
FABRICATION/CONSTRUCTION OF SLAB - TYP.
28. THE DOOR TO THE CONSTRUCTION AREA SHALL BE MIN. 36" WIDE WITH A CLOSER
AND LEVER HANDLE LATCHSET, EITHER EXISTING, NEW, OR TEMPORARY.
29. REMOVE AND STORE MATERIALS AND EQUIPMENT INDICATED TO BE REUSED OR
RELOCATED IN A COOL DRY PLACE TO PREVENT DAMAGE.
30. CONTRACTOR RESPONSIBLE FOR COORDINATING INTERIOR FINISHES LISTED IN
PLANS, SCHEDULES, NOTES, AND ELEVATIONS. NOTIFY ARCHITECT OF ANY
CONFLICTS, INCONSISTENCIES, OR DEVIATIONS IN WRITING PRIOR TO
CONSTRUCTION.
31. THE GENERAL CONTRACTOR AND SUBCONTRACTOR TO COORDINATE FINISH
HARDWARE AND KEYING WITH OWNER. CONTRACTOR TO PROVIDE A COMPLETE
AND OPERATIONAL SYSTEM - APPROVED BY OWNER.
32. CONSTRUCTION LIMITS - ALL CONTRACTOR VEHICLES AND TRAFFIC SHALL
REMAIN WITHIN THE DESIGNATED CONSTRUCTION AREAS, STAGING AREAS, OR
HAUL ROUTES.
33. ACCESS TO THE SITE - CONTRACTOR'S ACCESS TO THE SITE SHALL BE AS
DIRECTED BY THE OWNER. THE CONTRACTOR SHALL NOT PERMIT ANY
UNAUTHORIZED CONSTRUCTION PERSONNEL OR TRAFFIC ON THE SITE. THE
CONTRACTOR IS RESPONSIBLE FOR THE IMMEDIATE CLEAN-UP OF ANY DEBRIS
DEPOSITED ALONG THE ACCESS ROAD AS A RESULT OF HIS/HER CONSTRUCTION
TRAFFIC. DIRECTIONAL SIGNING AT THE ACCESS GATE AND ALONG THE DELIVERY
ROUTE TO THE STORAGE AREA OR WORK SITE SHALL BE AS DIRECTED BY THE
OWNER.
34. MATERIALS DELIVERY TO THE SITE - ALL CONTRACTOR'S MATERIAL ORDERS FOR
DELIVERY TO THE SITE WILL USE THE ACCESS POINT AT THE CONTRACTOR'S
STORAGE SITE AS APPROVED BY OWNER. THE CONTRACTOR SHALL PROVIDE
ADEQUATE ROADWAY SIGNS TO DIRECT DELIVERIES.
35. CONSTRUCTION AREA LIMITS - THE LIMITS OF CONSTRUCTION , MATERIAL
STORAGE AREAS, EQUIPMENT STORAGE AREA, PARKING AREA AND OTHER AREAS
DEFINED AS REQUIRED FOR THE CONTRACTOR'S EXCLUSIVE USE DURING
CONSTRUCTION SHALL BE MARKED BY THE CONTRACTOR AND APPROVED BY THE
OWNER. THE CONTRACTOR SHALL ERECT AND MAINTAIN AROUND THE
PERIMETER OF THESE AREAS SUITABLE FENCING, SIGNAGE, AND WARNING
DEVICES VISIBLE FOR BOTH DAY/NIGHT USE TO DELINEATE THE PERIMETER OF
ALL SUCH AREAS.
36. SUBMIT LIGHT GAUGE METAL FRAMING SHOP DRAWINGS SIGNED AND SEALED BY
A PROFESSIONAL ENGINEER LICENSED FOR APPROVAL.
37. PREPARE, APPLY, AND/OR INSTALL MATERIALS TO MEET ALL MANUFACTURER'S
WARRANTIES AND SPECIFICATIONS.
38. THE AVAILABILITY OF ALL MATERIALS DESIGNATED ON PLANS SHALL BE VERIFIED
BY CONTRACTOR AND SUBCONTRACTORS PRIOR TO ESTIMATE SUBMITTALS.
CONTRACTOR TO NOTIFY ARCHITECT IF MATCHING MATERIALS ARE NOT
AVAILABLE. ANY SUBSTITUTIONS TO BE REVIEWED AND APPROVED.
39. ESTABLISH PROCEDURES AND EXECUTE OPERATIONS TO PROVIDE CONTINUOUS
SECURITY. PROVIDE TEMPORARY PROTECTION FOR OPENINGS AND AT OTHER
LOCATIONS AS MAY BE APPROPRIATE DURING CONSTRUCTION. DENY ENTRANCE
OF UNAUTHORIZED PERSONS INTO WORK AREA.
40. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO DETERMINE DEMOLITION
PROCEDURE AND SEQUENCE TO INSURE THE SAFETY OF THE BUILDING AND ITS
COMPONENT PARTS DURING DEMOLITION. THIS INCLUDES, BUT IS NOT LIMITED
TO, THE ADDITION OF WHATEVER TEMPORARY BRACING, GUYS, OR TIE-DOWNS
MAY BE NECESSARY. SUCH MATERIAL SHALL BE REMOVED AND SHALL REMAIN
THE PROPERTY OF THE CONTRACTOR AFTER COMPLETION OF THE PROJECT.
1. THE FOLLOWING CONSTRUCTION DOCUMENTS ARE INTENDED TO PROVIDE
THE CONTRACTOR WITH A GENERAL KNOWLEDGE OF THE EXISTING
CONDITIONS WITHIN THE PROJECT AREA. EXISTING EQUIPMENT, STRUCTURE,
DUCTWORK, ETC. LOCATED ON DRAWINGS WERE DERIVED FROM LIMITED
FIELD OBSERVATIONS AND THE EXISTING AS-BUILTS WHICH MAY NOT BE UP
TO DATE. THEREFORE, THIS DRAWING MAY NOT BE ALL INCLUSIVE OF
SERVICES AND CONDITIONS THAT EXIST IN THE PROJECT AREA.
2. THE DRAWINGS INDICATE THE GENERAL EXTENT OF WORK. THE DRAWINGS
ARE NOT INTENDED TO INDICATE OR DESCRIBE ALL WORK REQUIRED FOR
THE FULL PERFORMANCE AND COMPLETION OF THE REQUIREMENTS OF THE
CONTRACT DOCUMENTS.
3. THE ENUMERATION OF PARTICULAR ITEMS OF WORK IN ONE PORTION OF THE
CONTRACT DOCUMENTS SHALL NOT BE CONSTRUED TO EXCLUDE OTHER
ITEMS NECESSARY OR IMPLIED THEREFROM.
4. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF PARTS OF
THE WORK SO THAT NO WORK SHALL BE LEFT IN AN UNFINISHED OR
INCOMPLETE CONDITION.
5. WORK SHALL CONFORM TO APPLICABLE INDUSTRY AND MANUFACTURER'S
PUBLISHED STANDARDS FOR QUALITY OF MATERIALS AND WORKMANSHIP, AS
WELL AS ALL REQUIREMENTS IN THESE DRAWINGS AND SPECIFICATIONS. ANY
CONFLICTING REQUIREMENTS OF THE SOURCES LISTED ABOVE SHALL BE
BROUGHT TO THE CORS ATTENTION PRIOR TO PROCEEDING WITH THE WORK.
6. THE CONTRACTOR SHALL PROTECT EXISTING, IN-PLACE, AND NEW WORK.
7. WORK NOTED "N.I.C." IS NOT MEANT TO BE PART OF THE CONSTRUCTION
SCOPE OF WORK AGREEMENT.
8. THE CONTRACTOR SHALL PAY FOR AND COORDINATE THE REMOVAL AND
LEGAL DISPOSAL OF MATERIALS AND RUBBISH.
9. ONCE ON SITE, THE CONTRACTOR SHALL VERIFY DIMENSIONS AND SHALL
VERIFY NEW AND EXISTING CONDITIONS SHOWN ON THESE DRAWINGS. THE
CONTRACTOR SHALL NOTIFY THE COR IN WRITING OF ANY DIFFERING
CONDITIONS BEFORE COMMENCEMENT OF WORK.
10. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN, LARGE SCALE DETAILS
GOVERN OVER SMALL SCALE DETAILS. THE CONTRACTOR SHALL NOTIFY THE
COR IN WRITING OF DIFFERING CONDITIONS BEFORE COMMENCEMENT OF
WORK.
11. UNLESS NOTED OTHERWISE, GYPSUM BOARD SURFACES ARE TO RECEIVE
ONE PRIMER COAT AND TWO COATS OF PAINT.
12. NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, AND ALTERATION
OPERATIONS SHALL BE APPLIED.
13. WALL AND/OR CEILING ASSEMBLIES THAT ARE IDENTIFIED WITH A FIRE
RESISTIVE RATING SHALL BE CONSTRUCTED AS DETAILED.
14. DIMENSIONS SHOWN ARE TO FACE OF STUD OR CMU (U.N.O.).
15. INTERIOR FINISH MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF
APPLICABLE CODES, ORDINANCES AND REGULATORY AGENCIES.
16. DISSIMILAR METALS SHALL BE ISOLATED FROM EACH OTHER TO AVOID
GALVANIC CORROSION.
17. NOTES APPEAR ON VARIOUS SHEETS FOR DIFFERENT SYSTEMS AND
MATERIALS. NOTES ON INDIVIDUAL SHEETS SHALL BE APPLIED TO RELATED
DRAWINGS AND DETAILS.
18. A FINISH INDICATION ON A WALL SHALL MEAN THE ENTIRE LENGTH AND
HEIGHT OF WALL IS TO BE FINISHED OR FIRE-RATED AS INDICATED.
19. WHEN NON-DIMENSIONED PARTITIONS APPEAR IN CONJUNCTION WITH DOOR
OPENINGS, THE DOOR WIDTH AND THE DOOR FRAME DETAILS DETERMINE
THE LOCATION OF ADJACENT WALLS AND FRAMES.
20. DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER TO THOSE DETAILED.
WHERE SPECIFIC DIMENSIONS, DETAILS OR DESIGN INTENT CANNOT BE
DETERMINED, CONSULT THE COR BEFORE PROCEEDING WITH THE WORK.
21. THE CONTRACTOR SHALL COORDINATE ALL MECHANICAL AND ELECTRICAL
FLOOR AND WALL SLEEVES INCLUDING CONDUITS WITH ALL DRAWINGS.
22. PROVIDE ACCESS PANELS AS REQUIRED BY APPLICABLE CODES AND AS
REQUIRED FOR ACCESS TO MECHANICAL EQUIPMENT AND PLUMBING WORK
THAT REQUIRES PERIODIC MAINTENANCE. ALL ACCESS PANELS SHALL BE
CONCEALED AND LOCATIONS SHALL BE REVIEWED WITH THE ARCHITECT
PRIOR TO PROCEEDING.
41. ALL RFI's, PROPOSED CHANGES, OR PROPOSED VALUE ENGINEERING ITEMS MUST HAVE A COST SUBMITTED AND ITS IMPACT (i.e. NO COST, ADDITIONAL COST, CREDIT, CONSTRUCTION SCHEDULE IMPACT,ETC.) PRIOR TO ARCHITECT'S
APPROVAL. IT SHALL BE UNDERSTOOD OMISSION OF THESE ITEMS REPRESENTS
THERE IS NO COST OR SCHEDULE INCREASE ASSOCIATED.
42. ALL CUTTING AND PATCHING SHALL BE PERFORMED BY THE GENERAL
CONTRACTOR. GENERAL CONTRACTOR SHALL INCLUDE COST OF ALL REQUIRED
CUTTING AND PATCHING FOR ALL TRADES IN THEIR ESTIMATE.
43. SAFETY AND SECURITY - THE CONTRACTOR SHALL CONDUCT HIS/HER ACTIVITIES
IN A SAFE AND SECURE MANNER. CONTRACTOR TO COMPLY WITH ALL OSHA
STANDARDS AND REGULATIONS.
44. FLOAT OUT AND/OR GRIND FLOOR IRREGULARITIES WHERE OCCURRING AS
NECESSARY FOR SMOOTH, LEVEL FLOOR IN CONDITION TO RECEIVE SCHEDULED
FLOOR MATERIALS. COMPLY WITH ALL MATERIAL MANUFACTURERS'
RECOMMENDATIONS (INCLUDING SLAB MOISTURE REQUIREMENT), ALL CODES
(FEDERAL, STATE, AND LOCAL, ETC) AND SPECS AND DRAWINGS.
45. ALL WOOD BLOCKING AND CONCEALED LUMBER TO BE FIRE RETARDANT TREATED.
G.C. SHALL COORDINATE ALL REQUIRED BLOCKING WITH THE OWNER & OWNER'S
VENDOR(S) FOR ALL WALL MOUNTED ACCESSORIES & MISC WALL MOUNTED OR
RECESSED ITEMS.
46. CONTRACTOR TO FRAME FOR RIGID CONDITION AT ALL FRAMING CONDITIONS. TO
INCLUDE BUT NOT LIMITED TO DOORS, WINDOWS, WALLS, ROOF, ETC.
47. CONTRACTOR TO PROVIDE ALL ENGINEERING AND SHOP DRAWINGS OF ALL
GLAZED WINDOW SYSTEMS (INCLUDING ALL ANCHORAGE CONDITIONS - SIGNED
AND SEALED) . FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION AND
CONSTRUCTION. PROVIDE WATERPROOF CONDITION AT ALL GLAZING SYSTEMS.
48. PROVIDE OPENINGS IN NEW AND EXISTING WALLS, FLOORS, ROOF, MECHANICAL,
ELECTRICAL, PLUMBING, ETC. PROVIDE FLASHING, COUNTER-FLASHING,
SEALANTS, SMOKE BARRIERS / DAMPERS, AND FIRE-SAFING REQUIRED TO MEET
MANUFACTURER'S WARRANTIES AND SPECIFICATIONS, FEDERAL, STATE, AND
LOCAL CODES. COORDINATE WITH STRUCTURAL AND M.E.P. DRAWINGS.
COORDINATE WITH DISCIPLINE. NOTIFY ARCHITECT IN WRITING OF ALL
DISCREPANCIES.
49. UNDERGROUND UTILITY LINES AND CABLES TO REMAIN SHALL BE PROTECTED.
NOTIFY ARCHITECT IN WRITING OF ANY DAMAGE TO EXISTING ITEMS TO REMAIN.
DIMENSIONS ARE TO FACE OF EXISTING WALL/CONSTRUCTION, STRUCTURAL
COLUMN CENTERLINES, OR FACE OF STUD OR CMU UNLESS OTHERWISE NOTED.
50. PROVIDE BLOCKING AND OR SHIMS NECESSARY TO INSTALL, INCLUDING BUT NOT
LIMITED TO, DOORS, WINDOWS, FIXTURES, MILLWORK, AND EQUIPMENT, WHICH
WILL MEET MANUFACTURER'S WARRANTIES AND SPECIFICATIONS. BLOCKING TO
MEET APPLICABLE FEDERAL, STATE, AND LOCAL CODES.
51. EXPOSED INTERIOR AND EXTERIOR BUILDING FEATURES SHALL BE PAINTED
(UNLESS OTHERWISE SPECIFICALLY NOTED). IF NOT SUPPLIED AS A FINISH
PRODUCT PER OWNER OR SPECIFIED BY ARCHITECT, COORDINATE AND PROVIDE
FINISH. PAINTING EXCLUDES AND/OR PRE-FINISHED FACTORY ITEMS.
52. STRUCTURAL MEMBERS: ANY STRUCTURAL MEMBERS ACCIDENTALLY OR
INTENTIONALLY CUT WITHOUT PROPER AUTHORIZATION SHALL BE RESTORED TO
ORIGINAL INTEGRITY AND CONDITION TO THE SATISFACTION OF THE ARCHITECT,
STRUCTURAL ENGINEER, AND COR.
53. FIELD ADJUSTMENTS SHOULD COMPLY WITH THE INTENT OF THE CONTRACT
DOCUMENTS AND APPLICABLE CODES. THE CONTRACTOR IS RESPONSIBLE FOR
CORRECTNESS OF DIMENSIONS DETAILS AND QUANTITIES FOR COORDINATION OF
DISCIPLINES AND CONDITIONS (CLEARANCES, FIXTURES, EQUIPMENT, ETC) AND
ADDITIONAL COSTS INCURRED AS A RESULT OF CONTRACTOR FIELD
ADJUSTMENTS.
54. NOTHING SHALL RELIEVE THE CONTRACTOR FROM COMPLIANCE WITH
REQUIREMENTS OF THE CONTRACT DOCUMENTS AND ALL APPLICABLE CODES.
THE CONTRACTOR IS RESPONSIBLE FOR CORRECTNESS OF DIMENSIONS AND
DETAILS, QUANTITIES FOR COORDINATION OF ALL TRADES AND CONDITIONS
(CLEARANCES, FIXTURES, EQUIPMENT, ETC) AND ANY ADDITIONAL COSTS
INCURRED AS A RESULT OF CONTRACTOR REQUESTED FIELD ADJUSTMENTS.
55. ALL WORK SHALL CONFORM TO APPLICABLE INDUSTRY AND MANUFACTURERS'
PUBLISHED STANDARDS.
56. REQUIREMENTS IN THESE DRAWINGS AND SPECIFICATIONS. ANY CONFLICTING
REQUIREMENTS SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION IN WRITING
PRIOR TO COMMENCEMENT OF WORK.
57. ARCHITECT'S REVIEW OF SHOP DRAWINGS IS FOR GENERAL COMPLIANCE
WITH CONTRACT DOCUMENTS ONLY. SHOP DRAWINGS MARKED "NO
EXCEPTIONS TAKEN" OR "COMPLY WITH MARKINGS," AS WELL AS ANY
ADDITIONAL MARKINGS OR NOTES, DO NOT RELIEVE THE CONTRACTOR
FROM COMPLIANCE WITH THE REQUIREMENTS OF THE CONTRACT
DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR CORRECTNESS OF
DIMENSIONS AND DETAILS, AND FOR COORDINATION OF THE WORK OF ALL
TRADES.
58. PROVIDE FIRE AND SMOKE JOINT SYSTEMS , FIRE SAFEING, FIRE AND SMOKE
CLOSURES, ETC. TO MAINTAIN FIRE AND SMOKE RATINGS AT FIRE AND
SMOKE WALL LOCATIONS, AND WHERE SHAFTS AND WALLS INTERSECT
FLOOR AND ROOF DECKS. COMPLY WITH FBC 715.
59. THE CONTRACTOR SHOULD OBTAIN A HOT WORK PERMIT PRIOR TO
BEGINNING ANY WELDING, CUTTING, BRAZING, GRINDING, OR OTHER
ACTIVITY THAT GENERATES SPARKS CAPABLE OF CAUSING COMBUSTION.
SEE NFPA 51B AND APPENDIX A FOR ADDITIONAL INFORMATION. PROVIDE A
FIRE WATCH AND/OR A GUARD WATCH AS REQUIRED BY NFPA 601 DURING
THE PROCESS OF CUTTING, WELDING, BRAZING, GRINDING, OR OTHER
ACTIVITY THAT GENERATES SPARKS CAPABLE OF CAUSING COMBUSTION,
ETC.
60. CONTACT ARCHITECT TO CLARIFY ANY DRAWING DISCREPANCY AND/OR
CONFLICTS OF DIFFERENT BIDDING ELEMENTS/COMPONENTS. FOR THE
PURPOSES OF PRICING AND BIDDING ASSUME THE MORE COSTLY OPTION.
61. SOME EXCAVATION MAY BE REQUIRED FOR CRAWL SPACE UTILIZED IN THE
BASEMENT FOR DUCT WORK.
CODES:
INTERNATIONAL BUILDING CODES 2018 (IBC)
INTERNATIONAL EXISTING BUILDING CODES 2018 (IEBC)
NFPA 101- LIFE SAFETY CODES 2018 (LSC)
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD 2015 (ABAAS).
VA BARRIER FREE DESIGN STANDARD (SUPPLEMENT TO ABAAS) 2015
TYPE OF CONSTRUCTION:
VA (IBC); V(111) (LSC), FULLY SPRINKLERED
OCCUPANCY: BUSINESS OCCUPANCY & ACCESSORY STORAGE
FIRE RESISTANCE RATING: NFPA
- PRIMARY STRUCTURAL FRAME: 1 HR
- PRIMARY STRUCTURAL FRAME, SUPPORTING ROOF: 1 HR
- NON BEARING WALLS AND PARTITIONS - EXTERIOR: 0 HR
- NON BEARING WALLS AND PARTITION: 0 HR
- FLOOR CONSTRUCTION + SECONDARY STRUCTURAL MEMBERS: 1 HR
- ROOF CONSTRUCTION + SECONDARY STRUCTURAL MEMBERS: 1 HR
CORRIDOR WALLS: SMOKE PARTITIONS
STAIR: 1 HR FIRE RATED
SHAFTS: 2 HR FIRE BARRIER
NEW BASEMENT AREA: 567 SF TOTAL
NEW FIRST FLOOR AREA: 2,448 SF TOTAL
NEW SECOND FLOOR AREA: 2,439 SF TOTAL
TOTAL BUILDING AREA: 5,454 SF TOTAL
NUMBER OF OCCUPANTS:
CONFERENCE ROOM: 268 SF / 15 SF = 18 OCCUPANTS
CHIEF OFFICE: 181 SF / 100 SF = 2 OCCUPANT
DEPUTY CHIEF OFFICE: 154 SF / 100 SF = 2 OCCUPANT
OFFICER WORK ROOM: 375 SF / 100 SF = 4 OCCUPANTS
OFFICES: 124 SF / 100 SF = 2 OCCUPANT
RECEPTION: 110 SF / 100 SF = 2 OCCUPANT
STAFF LOUNGE: 193 SF / 50 SF = 4 OCCUPANT
LOCKER ROOMS: 129 SF / 50 SF = 3 OCCUPANTS
1ST FLOOR LOBBY: 278 SF / 100 SF = 3 OCCUPANTS
2ND FLOOR LOBBY: 207 SF / 100 SF = 3 OCCUPANTS
TOTAL: 43 OCCUPANTS
NEW BUSINESS (NFPA 101-CHAPTER 38):
MAX DEAD END: 50' (NFPA 101-38.2.5.2)
MAX. TRAVEL DISTANCE TO AN EXIT: 300' WITH SPRINKLER SYSTEM
(NFPA 101-38.2.6.3) - 128' ACTUAL
MAX. COMMON PATH OF TRAVEL: 100' WITH SPRINKLER SYSTEM (NFPA
101-38.2.5.3) - 70' ACTUAL
LIFE SAFETY CODE (NFPA 101-CHAPTER 7):
7.2.2.6.3
SEPARATION FROM OUTSIDE STAIR NOT REQUIRED.
LIFE SAFETY CODE (NFPA 101-CHAPTER 43):
43.10 REPAIR, RENOVATION, MODIFICATION OF RECONSTRUCTION OF
HISTORIC BUILDING
REPLACEMENT OF EXISTING OR MISSING FEATURES USING ORIGINAL OR
LIKE MATERIALS SHALL BE PERMITTED. PARTIAL REPLACEMENT FOR
REPAIRS THAT MATCH THE ORIGINAL IN CONFIGURATION, HEIGHT, AND SIZE
SHALL BE PERMITTED. REPLACEMENT SHALL NOT BE REQUIRED TO MEET
SPECIFIC MATERIALS, INSTALLATION, PENETRATIONS OR CONTINUITY OF
ANY COMPONENT, OR SYSTEM IN THE BUILDING.
AUTOMATIC SPRINKLER SYSTEM: NFPA 13-2019 ED.
AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT
BUILDING.
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES (IBC-P: TABLE 403.1)
- EMPLOYEES (15 OCC.)
- WATER CLOSETS: 1:18 MALE/FEMALE = 1 MALE/FEMALE REQUIRED
- LAVATORIES: 1:18 MALE/FEMALE = 1 MALE/FEMALE REQUIRED
- VISITORS: (28 OCC.)
- WATER CLOSETS: 1:75 MALE/FEMALE = 1 MALE/FEMALE REQUIRED
- LAVATORIES: 1:100 MALE/FEMALE = 1 MALE/FEMALE REQUIRED
- EMPLOYEES & VISITORS
- WATER CLOSETS: 1 MALE/FEMALE REQUIRED
- LAVATORIES: 1 MALE/FEMALE REQUIRED
- 2 ADA ACCESSIBLE RESTROOMS PROVIDED
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
G-003
BUILDING CODE SUMMARY &
DEDUCTIVE ALTERNATES
RAPJMC
DEDUCTIVE ALTERNATE #1 – DEDUCT ALL COSTS
ASSOCIATED WITH LABOR AND MATERIAL AS PART OF
THIS ALTERNATE. DEDUCT COSTS FOR MATERIAL AND
LABOR TO REPLACE THE ROOF. ALL OTHER ITEMS ON
ROOF REQUIRED TO COMPLETE OTHER SCOPE PLUS
ROOF REPAIRS AROUND THOSE PENETRATIONS MUST
STAY INCLUDED IN BASE BID.
THE EXISTING BUILDING 20 IS CURRENTLY A
VACANT OFFICE BUILDING ON THE JAMES H.
QUILLEN VA CAMPUS. THIS PROJECT WILL
RENOVATE APPROXIMATELY 5,454 SQUARE FEET,
THREE (3) FLOOR BUILDING FOR USE OF THE
POLICE SERVING THE JAMES H. QUILLEN VA
CAMPUS.
THE RECONSTRUCTED SPACE FOR THE POLICE
STAFF WILL PROVIDE OFFICES, A CONFERENCE
ROOM, AN OBSERVATION ROOM, AN INTERVIEW
ROOM, AN EVIDENCE ROOM WITH PROCESSING,
MALE AND FEMALE LOCKER ROOMS, STORAGE
SPACE, ELECTRICAL AND MECHANICAL ROOMS,
AN ARMORY WITH AMMUNITION STORAGE,
LOUNGE AREAS, WAITING AND RECEPTION AREAS,
RESTROOMS, CORRIDORS, CIRCULATION AREAS,
AND REPLACEMENT OF FINISH MATERIALS TO
INCORPORATE CURRENT VA STANDARDS.
THE SCOPE OF WORK INCLUDES TO DEMOLISH
INTERIOR, NON-STRUCTURAL ELEMENTS AND
RENOVATIONS TO INCLUDE BUT NOT LIMITED TO
NEW WALLS, COUNTERS, DOORS, HARDWARE,
FINISHES, GLASS/GLAZING, MECHANICAL,
ELECTRICAL, SPRINKLERS AND ALL ASSOCIATED
WORK. NEW SYSTEMS INSTALLED SHALL BE
DESIGNED TO VA STANDARDS AND MEET
EFFICIENCY DESIGN STANDARDS DEPLOYING THE
LATEST ENERGY SAVING TECHNOLOGY,
CONTROLS, ETC. WHERE POSSIBLE.
CODE ANALYSIS: CODE CRITERIA:
• VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND
STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE
MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL
PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN
MANUALS AND MASTER SPECIFICATIONS SPECIFY OTHER CODES AND
STANDARDS THE VA FOLLOWS ON ITS PROJECTS.
• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL
CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE
TECHNICAL INFORMATION LIBRARY (TIL) ( HYPERLINK "http://www.cfm.va.gov/til/"
HTTP://WWW.CFM.VA.GOV/TIL/).
• INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY
REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW). 2012
• NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW). 2018
• NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA 5000 AND NFPA
900. 2018
• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
• VA SEISMIC DESIGN REQUIREMENTS, H-18-8
• NATIONAL ELECTRICAL CODE (NEC) 2018
• INTERNATIONAL PLUMBING CODE (IPC) 2018
• ASME CODE FOR PRESSURE PIPING
• ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)
INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG-18-13)
• BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN
CONCRETE INSTITUTE AND COMMENTARY (ACI 3-18)
• MANUAL OF STEEL CONSTRUCTION, LOAD AND RESISTANCE FACTOR DESIGN
SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS, AMERICAN INSTITUTE
OF STEEL CONSTRUCTION (AISC)
• ENERGY POLICY ACT OF 2005 (EPACT)
• DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW
FEDERAL, COMMERCIAL, AND MULTI-FAMILY HIGH-RISE RESIDENTIAL
BUILDINGS AND NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433,
434 AND 435.
• FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS:
MEMORANDUM OF UNDERSTANDING (MOU)
• EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL,
ENERGY, AND TRANSPORTATION MANAGEMENT.
• THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE
GENERAL REQUIREMENTS SECTION 01 00 00 OF THE VA MASTER
CONSTRUCTION SPECIFICATION.
• VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD
62.1- 2016.
• SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15 –
2016.
GENERAL DEDUCTIVE ALTERNATE
NOTES:
1. A DEDUCTIVE ALTERNATE IS AN AMOUNT PROPOSED
BY GC AND STATED ON THE BID FORM FOR CERTAIN
WORK DEFINED IN THE BIDDING REQUIREMENTS
THAT MAY BE ADDED TO OR DEDUCTED FROM THE
BASE BID AMOUNT IF VA DECIDES TO ACCEPT A
CORRESPONDING CHANGE, EITHER IN THE AMOUNT
OF CONSTRUCTION TO BE COMPLETED OR IN THE
PRODUCTS, MATERIALS, EQUIPMENT, SYSTEMS, OR
INSTALLATION METHODS DESCRIBED IN THE
CONTRACT DOCUMENTS.
2. COORDINATION: MODIFY OR ADJUST AFFECTED
ADJACENT WORK AS NECESSARY TO COMPLETELY
INTEGRATE WORK OF THE BID OPTION INTO
PROJECT. INCLUDE AS PART OF EACH DEDUCTIVE
ALTERNATE MISCELLANEOUS DEVICES, ACCESSORY
OBJECTS, AND SIMILAR ITEMS INCIDENTAL TO OR
REQUIRED FOR A COMPLETE INSTALLATION
WHETHER OR NOT INDICATED AS PART OF
DEDUCTIVE ALTERNATE.
3. EXECUTE ACCEPTED DEDUCTIVE ALTERNATE
UNDER THE SAME CONDITIONS AS OTHER WORK OF
THE CONTRACT.
DEDUCTIVE ALTERNATES:
GENERAL SCOPE OF WORK:
UP
1. ALL DEVICES HAVE NOT BEEN SHOWN, BUT THE
CONTRACTOR SHALL ENSURE THE INSTALLATION OF ALL
LIFE SAFETY DEVICES INDICATED ON THE ENGINEERING
DRAWINGS.
2. CONTRACTOR SHALL FIELD VERIFY THE LOCATION OF ANY
EXISTING FIRE RATED WALLS. ANY WORK DONE AROUND
EXISTING FIRE RATED WALLS SHALL BE DONE WITH CARE
SO AS NOT TO COMPROMISE THE RATING'S INTEGRITY.
ANY DAMAGE SHALL BE REPAIRED IMMEDIATELY.
3. CONTRACTORS SHALL FOLLOW EM-385-1-1 AND NFPA 241,
ALONG WITH THE INSTALLATION’S FIRE REGULATIONS.
4. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
BARRIERS, AND SMOKE PARTITIONS OR ANY OTHER WALL
REQUIRED TO HAVE PROTECTED OPENINGS, OR
PENETRATIONS SHALL BE EFFECTIVELY AND
PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING.
SUCH IDENTIFICATION SHALL:
A. BE LOCATED WITHIN 15 FEET OF THE END OF EACH WALL
AND AT INTERVALS NOT EXCEEDING 30 FEET MEASURED
HORIZONTALLY ALONG WITH WALL OR PARTITION.
B. INCLUDE LETTERING NOT LESS THAN 3 INCHES IN HEIGHT
WITH A MINIMUM 3/8-INCH STROKE IN A CONTRASTING
COLOR INCORPORATING THE SUGGESTED WORDING,
“FIRE AND/OR SMOKE BARRIER – PROTECT ALL
OPENINGS,” OR SIMILAR WORDING.
GENERAL SHEET NOTES:
RATED WALL LEGEND
1-HR. FIRE RATED WALLS
2-HR. FIRE RATED WALLS
SMOKE PARTITION
2-HR FIRE RATED SMOKE BARRIER
FIRE RATED CURTAIN WALL
TRAVEL DISTANCE
NOTES:
1. CABINETS TO BE SIZED TO ACCOMODATE A
MINIMUM VOLUME OF 9.5L (2-1/2 GALLON).
2. EXTINGUISHER TO BE PROVIDED BY VA
FACILITY.
3. INSTALL FIRE EXTINGUISHERS ABOVE
FINISHED FLOOR PER NFPA 10. PROVIDE
STICK - ON LETTERING AND DIRECTIONAL
ARROWS TO IDENTIFY THE CABINET OR
EXTINGUISHER'S LOCATION.
EGRESS CLEAR WIDTH
45'-0"
FEC
36"
EXIT SIGN
LIFE SAFETY PLAN LEGEND
SEMI-RECESSED FIRE EXTINGUISHER CABINET
53'
FEC
52'
36"
MECHANICAL
ROOM
B01
STORAGE
B02
CORRIDOR
B00
ARMORY /
WEAPONS
B04
CORRIDOR
B03
NOTE: BULLET PROOF
MATERIAL AT CEILING
LOCATION WITH 2HR
FIRE RATING
SEE DETAIL B4/A-507
NOTE: CEILING
ASSEMBLY WITH 1HR
FIRE RATING
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
G-100
BASEMENT LIFE SAFETY PLAN
RAPJMC
NOTE: MAX DISTANCE OF TRAVEL AS SHOWN IS 53'-0"
SCALE: 3/8" = 1'-0"F1
BASEMENT LIFE SAFETY PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
DN
UP
DN
DN
1. ALL DEVICES HAVE NOT BEEN SHOWN, BUT THE
CONTRACTOR SHALL ENSURE THE INSTALLATION OF ALL
LIFE SAFETY DEVICES INDICATED ON THE ENGINEERING
DRAWINGS.
2. CONTRACTOR SHALL FIELD VERIFY THE LOCATION OF ANY
EXISTING FIRE RATED WALLS. ANY WORK DONE AROUND
EXISTING FIRE RATED WALLS SHALL BE DONE WITH CARE
SO AS NOT TO COMPROMISE THE RATING'S INTEGRITY.
ANY DAMAGE SHALL BE REPAIRED IMMEDIATELY.
3. CONTRACTORS SHALL FOLLOW EM-385-1-1 AND NFPA 241,
ALONG WITH THE INSTALLATION’S FIRE REGULATIONS.
4. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
BARRIERS, AND SMOKE PARTITIONS OR ANY OTHER WALL
REQUIRED TO HAVE PROTECTED OPENINGS, OR
PENETRATIONS SHALL BE EFFECTIVELY AND
PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING.
SUCH IDENTIFICATION SHALL:
A. BE LOCATED WITHIN 15 FEET OF THE END OF EACH WALL
AND AT INTERVALS NOT EXCEEDING 30 FEET MEASURED
HORIZONTALLY ALONG WITH WALL OR PARTITION.
B. INCLUDE LETTERING NOT LESS THAN 3 INCHES IN HEIGHT
WITH A MINIMUM 3/8-INCH STROKE IN A CONTRASTING
COLOR INCORPORATING THE SUGGESTED WORDING,
“FIRE AND/OR SMOKE BARRIER – PROTECT ALL
OPENINGS,” OR SIMILAR WORDING.
GENERAL SHEET NOTES:
TRAVEL DISTANCE
NOTES:
1. CABINETS TO BE SIZED TO ACCOMODATE A
MINIMUM VOLUME OF 9.5L (2-1/2 GALLON).
2. EXTINGUISHER TO BE PROVIDED BY VA
FACILITY.
3. INSTALL FIRE EXTINGUISHERS ABOVE
FINISHED FLOOR PER NFPA 10. PROVIDE
STICK - ON LETTERING AND DIRECTIONAL
ARROWS TO IDENTIFY THE CABINET OR
EXTINGUISHER'S LOCATION.
EGRESS CLEAR WIDTH
45'-0"
FEC
36"
EXIT SIGN
LIFE SAFETY PLAN LEGEND
SEMI-RECESSED FIRE EXTINGUISHER CABINET
RATED WALL LEGEND
1-HR. FIRE RATED WALLS
2-HR. FIRE RATED WALLS
SMOKE PARTITION
2-HR FIRE RATED SMOKE BARRIER
FIRE RATED CURTAIN WALL
36"
36"
36"
79'
78'
21'
32'
OFFICE
OFFICE
WOMEN
RESTROOM
STAFF
LOUNGE
MEN
RESTROOM
CORRIDOR
CORRIDOR
OFFICER
WORK
ROOM
INTERVIEW
ROOM
EVIDENCE
PROCESSING
EVIDENCE
ROOM
OFFICE
HOUSE
KEEPING
WAITING
ROOM
RECEPTION
ELECT.
OFFICE
OFFICE
15' - 11 1/2" DEAD-END
FEC
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
G-101
FIRST FLOOR LIFE SAFETY PLAN
RAPJMC
SCALE: 3/8" = 1'-0"F1
FIRST FLOOR LIFE SAFETY PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
NOTE: MAX DISTANCE OF TRAVEL AS SHOWN IS 79'-0"
36"
95'
96'
33'
34'
CONFERENCE
ROOM
CHIEF
OFFICE
ELECT.
LOBBY
MECHANICAL
ROOM
HOUSE
KEEPING
OFFICE
OFFICE
CORRIDOR
OFFICE
OFFICE
MEN
RESTROOM
MEN
SHOWER &
LOCKER
ROOM
WOMEN
SHOWER &
LOCKER
ROOM
206A
WOMEN
RESTROOM
OIT
DEPUTY
CHIEF
OFFICE
CORRIDOR
CORRIDOR
37' - 1 1/2" DEAD-END
1. ALL DEVICES HAVE NOT BEEN SHOWN, BUT THE
CONTRACTOR SHALL ENSURE THE INSTALLATION OF ALL
LIFE SAFETY DEVICES INDICATED ON THE ENGINEERING
DRAWINGS.
2. CONTRACTOR SHALL FIELD VERIFY THE LOCATION OF ANY
EXISTING FIRE RATED WALLS. ANY WORK DONE AROUND
EXISTING FIRE RATED WALLS SHALL BE DONE WITH CARE
SO AS NOT TO COMPROMISE THE RATING'S INTEGRITY.
ANY DAMAGE SHALL BE REPAIRED IMMEDIATELY.
3. CONTRACTORS SHALL FOLLOW EM-385-1-1 AND NFPA 241,
ALONG WITH THE INSTALLATION’S FIRE REGULATIONS.
4. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
BARRIERS, AND SMOKE PARTITIONS OR ANY OTHER WALL
REQUIRED TO HAVE PROTECTED OPENINGS, OR
PENETRATIONS SHALL BE EFFECTIVELY AND
PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING.
SUCH IDENTIFICATION SHALL:
A. BE LOCATED WITHIN 15 FEET OF THE END OF EACH WALL
AND AT INTERVALS NOT EXCEEDING 30 FEET MEASURED
HORIZONTALLY ALONG WITH WALL OR PARTITION.
B. INCLUDE LETTERING NOT LESS THAN 3 INCHES IN HEIGHT
WITH A MINIMUM 3/8-INCH STROKE IN A CONTRASTING
COLOR INCORPORATING THE SUGGESTED WORDING,
“FIRE AND/OR SMOKE BARRIER – PROTECT ALL
OPENINGS,” OR SIMILAR WORDING.
GENERAL SHEET NOTES:
TRAVEL DISTANCE
NOTES:
1. CABINETS TO BE SIZED TO ACCOMODATE A
MINIMUM VOLUME OF 9.5L (2-1/2 GALLON).
2. EXTINGUISHER TO BE PROVIDED BY VA
FACILITY.
3. INSTALL FIRE EXTINGUISHERS ABOVE
FINISHED FLOOR PER NFPA 10. PROVIDE
STICK - ON LETTERING AND DIRECTIONAL
ARROWS TO IDENTIFY THE CABINET OR
EXTINGUISHER'S LOCATION.
EGRESS CLEAR WIDTH
45'-0"
FEC
36"
EXIT SIGN
LIFE SAFETY PLAN LEGEND
SEMI-RECESSED FIRE EXTINGUISHER CABINET
RATED WALL LEGEND
1-HR. FIRE RATED WALLS
2-HR. FIRE RATED WALLS
SMOKE PARTITION
2-HR FIRE RATED SMOKE BARRIER
FIRE RATED CURTAIN WALL
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved: Chief Engineering
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
VAMC MOUNTAIN HOME, TN
CORRECT ADMIN BLDG 20
ENVIRONMENT AND
CONDITION DEFICIENCIES
MARCH 15, 2021
BID DOCUMENTS 621-15-101
G-102
SECOND FLOOR LIFE SAFETY PLAN
RAPJMC
SCALE: 3/8" = 1'-0"F1
SECOND FLOOR LIFE SAFETY PLAN
SCALE: = 1'-0"3/8"
0 2 4 62
NOTE: MAX DISTANCE OF TRAVEL AS SHOWN IS 96'-0"
| Sheets |
| G-001 - COVER SHEET & SHEET INDEX |
| G-002 - GENERAL PROJECT NOTES |
| G-003 - BUILDING CODE SUMMARY & DEDUCTIVE ALTERNATES |
| G-100 - BASEMENT LIFE SAFETY PLAN |
| G-101 - FIRST FLOOR LIFE SAFETY PLAN |
| G-102 - SECOND FLOOR LIFE SAFETY PLAN |