Hazmat Reports ACM SurveyReport.pdf

PDF 4 MB Posted

Attached to
Z1DA--NRM Tier 2 (PROJ: 573-18-605) BB - Correct Patient Privacy Deficiencies
Solicitation number
36C24821R0139
Issued by

About this file

This pre-solicitation announcement seeks proposals for construction project number 573-18-605 to expand and renovate the Cardiothoracic Intensive Care Unit at the Malcom Randall VA Medical Center in Gainesville, Florida. The project includes increasing capacity, eliminating deficiencies, and improving functionality, patient access, and privacy. Bidders must furnish all tools, equipment, materials, permits, labor, and supervision to complete the work in accordance with contract documents, plans, and specifications. The North American Industry Classification System code for this procurement is 236220, with a size standard of $39.5 million. The government intends to award a firm fixed-price contract within 120 days of receiving bids. The solicitation will be available on or around July 28, 2021 via beta.SAM.gov and due dates will be specified therein. Questions should be directed to the issuing office.

View the file

Other files

File Type Posted
36C248-21-R-0139-573-18-605 Correct Patient Privacy Deficiencies_Addendum Drawings.pdf PDF
36C24821R0139 0003.pdf PDF
Hazmat Reports Lead Survey Report1.pdf PDF
36C24821R0139 0002.pdf PDF
Hazmat Reports PCBs Report.pdf PDF
36C24821R0139_Conformed Copy 08.26.21.pdf PDF
Correct Patient Privacy-Attendance Sheet.pdf PDF
36C24821R0139 QA RFI Combined 573-18-605 Correct Patient Privacy Deficiencies_AE RESPONSES 2021-08-25.pdf PDF
Correct Patient Privacy-Attendance Sheet.pdf PDF
36C24821R0139 QA RFI Combined 573-18-605 Correct Patient Privacy Deficiencies_AE RESPONSES 2021-08-25.xlsx XLSX spreadsheet
Attachments.zip ZIP file
36C24821R0139 0001.docx DOCX document
Attachment 8 (Exhibit B) Past and Present Performance Questionnaire.docx DOCX document
Attachment 7- (Exhibit A) Performance Relevancy Survey v2.docx DOCX document
36C24821R0139_FINALbc.docx DOCX document
Attachment 5- DB Wage Rates FL20210194 05.07.2021.pdf PDF
36C24821R0139 0001_1.docx DOCX document
Attachment 3 - LOS Certification Solicitation Version.doc DOC document
Attachment 9 - Q_A RFIs.xlsx XLSX spreadsheet
Attachment 6 -(Exhibit C) EMR.docx DOCX document
Attachment 4 - Price Matrix.xlsx XLSX spreadsheet
36C24821R0139_2.docx DOCX document
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2228 NW 40th Terrace, Suite C Gainesville, Florida 32605

352-335-6648 • Fax 352-335-6187

LIMITED RENOVATION ASBESTOS SURVEY REPORT

Correct Patient Privacy Deficiencies – CTICU Project 573-18-605

Malcom Randall VA Medical Center 1601 SW Archer Road

Gainesville, Florida

GLE Project No.: 19950-00536

Prepared for:

Mr. David Novack Toland Mizell Molnar, LLC

590 Means Street NW, Suite 200 Atlanta, Georgia 30318

September 2019

Prepared by:

GLE Associates, Inc.

2228 NW 40th Terrace, Suite C | Gainesville, Florida 32605 | 352-335-6648 | Fax: 352-335-6187

Tampa | Orlando | Ft. Lauderdale | Miami | Jacksonville | Atlanta | Nashville Architecture AA 0002369 Engineer CA 5483 Asbestos ZA 0000034 Geology GB 0000297

September 27, 2019

Mr. David Novack Toland Mizell Molnar, LLC 590 Means Street NW, Suite 200 Atlanta, Georgia 30318

RE: Limited Renovation Asbestos Survey Report

Correct Patient Privacy Deficiencies - CTICU Project 573-18-605 Malcom Randall VA Medical Center 1601 SW Archer Road Gainesville, Florida 32608-1197

GLE Project No.: 19950-00536

Dear Mr. Novack:

GLE Associates, Inc. (GLE) performed a limited renovation survey for asbestos-containing materials (ACM) on September 4, 2019, at Malcom Randall VAMC - CTICU, located in Gainesville, Florida. The survey was performed by Mr. Artiom Chacon and Mr. Michael D.

Harrell with GLE. This report outlines the sampling and testing procedures, and presents the results along with our conclusions and recommendations.

GLE appreciates the opportunity to serve as your consultant on this project. If you should have any questions, or if we can be of further service, please do not hesitate to call.

Sincerely, Artiom Chacon Robert B. Greene, PE, PG, CIH, LEED AP Senior Project Manager President

Florida LAC# EA 0000009

AC/PSZ/RBG/lr

G:\Work\Asbestos\'19\19950-VA\00536 TMM CTICU\Report\Asbestos\SurveyReport.doc

TABLE OF CONTENTS

1.0 INTRODUCTION 1

1.1 Introduction 1

1.2 Facility Description 1

2.0 RESULTS 2

2.1 Asbestos Survey Procedures 2

2.2 Identified Suspect Asbestos-Containing Materials 3

Table 2.2-1 — Summary of Homogeneous Sampling Areas

3.0 CONCLUSIONS AND RECOMMENDATIONS 8

3.1 General 8

3.2 Specific 9

4.0 LIMITATIONS AND CONDITIONS 10

APPENDICES

Appendix A – Analytical Results and Chain of Custody Appendix B – Personnel and Laboratory Certifications Appendix C – Asbestos Materials Location Plans Appendix D – Photographs

1.0 INTRODUCTION

1.1 INTRODUCTION

The purpose of this limited renovation survey was to identify accessible asbestos-containing materials (ACMs) and their general locations within the Malcom Randall VA Medical Center - CTICU, located at 1601 SW Archer Road in Gainesville, Florida. The scope of this survey is depicted in the Client-provided TMM drawings dated August 15, 2019. The survey was conducted pursuant to National Emission Standards for Hazardous Air Pollutants (NESHAP, 40 CFR 61) requirements, associated with the scheduled renovation plans. The survey was performed on September 4, 2019, by Mr. Artiom Chacon and Mr. Michael D. Harrell, Environmental Protection Agency/Asbestos Hazard Emergency Response Act (EPA/AHERA) accredited inspectors. The scope of this survey did not include demolition of any building components, evaluation of architectural plans, or the quantification of materials for abatement purposes.

1.2 FACILITY DESCRIPTION

A summary of the facility investigated is outlined in the table below.

Facility Type: Commercial, Residential Construction Date: 1967 Number of Floors: 1 in Scope

Exterior Floor Support: Concrete Slab on Grade Wall Support: Metal Framing Exterior Finish: Concrete Roof System: Not in Scope

Interior Wall Substrate: Drywall and Joint Compound, Plaster Wall Finishes: Paint, Wall Covering, Cove Base Floor Finishes: Vinyl Floor Tile, Ceramic Tile, Carpet, Sheet Vinyl Flooring Ceiling System: Suspended Ceiling System

Ceiling Finishes:

Suspended Ceiling Tiles, Radiant Heating Metal Ceiling Panels

2.0 RESULTS

2.1 ASBESTOS SURVEY PROCEDURES

The survey was performed by visually observing accessible areas within the scope of work. An EPA/AHERA accredited inspectors performed the visual observations (refer to Appendix B for personnel qualifications).

After the overall visual survey was completed, representative sampling areas were determined.

The surveyors delineated homogeneous areas of suspect materials and samples of each material were obtained, in general accordance with regulations as established by the Occupational Safety and Health Administration (OSHA) and NESHAP. The field surveyors determined sample locations based on previous experience. Both friable and non-friable materials were sampled. A friable material is one that can be crushed when dry by normal hand pressure. This survey did not include the demolition of building components to access suspect material.

After completion of the fieldwork, the samples were delivered to GLE’s National Voluntary Laboratory Accreditation Program (NVLAP) accredited laboratory for analysis. The samples were analyzed by Polarized Light Microscopy (PLM) coupled with dispersion staining, in general accordance with EPA-600/R-93/116. Utilizing this procedure, the various asbestos minerals (chrysotile, amosite, crocidolite, actinolite, tremolite, and anthophyllite) can be determined. The percentages of asbestos minerals in the samples were visually determined by the microscopist. Please note that the EPA designates all materials containing greater than one percent asbestos as an “asbestos-containing material” (ACM).

Regulated Asbestos-Containing Material (RACM) is defined as (a) Friable asbestos materials,

(b) Category I non-friable ACM that has become friable, (c) Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or (d) Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations regulated by this subpart.

Category I and Category II non-friable ACM, as defined by the EPA:

Category I non-friable ACM means asbestos-containing packings, gaskets, resilient floor covering, asphalt roofing products, and pliable sealants and mastics that are in good condition and not friable, containing more than one percent asbestos, as determined using the method specified in Appendix E, Subpart E, 40 CFR Part 763, Section 1, PLM.

Category II non-friable ACM means any material, excluding Category I non-friable ACM, containing more than one percent asbestos as determined using the methods specified in Appendix E, Subpart E, 40 CFR Part 763 Section 1, PLM that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.

2.2 IDENTIFIED SUSPECT ASBESTOS-CONTAINING MATERIALS

A total of 111 samples of suspect building materials were collected from the facility during the survey, representing 37 different identified homogeneous areas. The results of the laboratory analyses are included in Appendix A, and the approximate extent to which ACM was observed to be present are indicated on the Asbestos Location Plan(s) in Appendix C. Photographs of the various materials sampled are included in Appendix D.

A summary of the homogenous sampling areas of suspect ACM determined to be present is outlined in the following table.

ASBESTOS CONTENT

Expressed as percent

* = The facility owner has the option of point-counting by Polarized Light Microscopy (PLM) those RACM whose asbestos content is less than 10% in order to more accurately determine the asbestos content therein.

PC = Results based on Point-Count analysis TEM NOB = Transmission Electron Microscopy of Non-Friable Organically Bound Material

FRIABILITY F = Friable Material NF = Non-Friable Material

ACM CATEGORY RACM = Regulated ACM CAT I = Category I non-friable ACM CAT II = Category II non-friable ACM

ABBREVIATIONS: NA = Not Applicable ND = None Detected NIS = Not in Scope C = Chrysotile A = Amosite

HA = Homogeneous Area SF = Square Feet LF = Linear Feet CF = Cubic Feet

TABLE 2.2-1: SUMMARY OF HOMOGENEOUS SAMPLING AREAS

MALCOM RANDALL VA MEDICAL CENTER - CTICU – GAINESVILLE, FLORIDA

HA # HOMOGENEOUS MATERIAL

DESCRIPTION

HOMOGENEOUS MATERIAL

LOCATION

FRIABILITY

(F /NF)

% ASBESTOS* # OF SAMPLES

COLLECTED

APPROXIMATE

QUANTITY

ACM

CATEGORY

CT-01 2'x2' White Recessed Ceiling Tile Rooms B180-1, B185B-1, B188-1, B188A-1, B188B-1, B188C-1, B189-1, B190-1, B194-1

F ND 3 NIS NA

CT-02 2'x2' White Fissured Ceiling Tile Rooms B184-1, B184A-1, B185-1, B185C-1, Electrical Closet

F ND 3 NIS NA

CT-03 2'x2' White Smooth Ceiling Tile Rooms B191-1, B192-1, B193-1 F ND 3 NIS NA

CT-04 2'x4' White Pinhole Ceiling Tile Rooms B181-1, B181C-1, B182A-1, B235-1, B222-1, SPB222-1

F ND 3 NIS NA

DW-01 Drywall and Joint Compound Walls Throughout NF ND 3 NIS NA

FT-01

12"x12" Multicolor Floor Tile with

Black Mastic Rooms B184-1, B184A-1, B185-1, B185-1C, Electrical Room

NF

FT-ND;

Mastic-5%C

3 620 SF CAT I

FT-02

12"x12" Multicolor Floor Tile with

Tan Mastic Over FT-01 in Rooms B184-1 and

Electrical Closet

NF ND 3 NIS NA

FT-03

12"x12" Tan/Brown Floor Tile with

Yellow Mastic Over FT-01 in Room B184A-1 NF ND 3 NIS NA

FT-04

12"x12" White/Gray Floor Tile with

Yellow Mastic

Hallways and Rooms B202-1, B203-1, B204-1, B205-1, B206-1 and B181D-1

NF ND 3 NIS NA

FT-05

12"x12" Aqua Floor Tile with Yellow

Mastic Hallways Along Side FT-04 NF ND 3 NIS NA

FT-06

12"x12" White Floor Tile with

Black Mastic Rooms B181-1, B181A-1, B181C-

1, B181D-1, B182A-1

NF

FT-ND;

Mastic-5%C

3 800 SF CAT I

FT-07

12"x12" White/Brown Floor Tile with

Brown Mastic Rooms B222-1, B222A-1, SPB222-

1, SPB217A-1

NF ND 3 NIS NA

FT-08

9"x9" Brown Floor Tile with Black

Mastic

Rooms B144-1, B208-1, B209-1, B206A-1, B222A-1, SPB222-1, B196-1, B198-1, B199-1, B201-1

NF

FT-7%C;

Mastic-5%C

3 2,100 SF CAT I

* = The facility owner has the option of point-counting by Polarized Light Microscopy (PLM) those RACM whose asbestos content is less than 10% in order to more accurately determine the asbestos content therein.

PC = Results based on Point-Count analysis TEM NOB = Transmission Electron Microscopy of Non-Friable Organically Bound Material

FRIABILITY F = Friable Material NF = Non-Friable Material

ACM CATEGORY RACM = Regulated ACM CAT I = Category I non-friable ACM CAT II = Category II non-friable ACM

ABBREVIATIONS: NA = Not Applicable ND = None Detected NIS = Not in Scope C = Chrysotile A = Amosite

HA = Homogeneous Area SF = Square Feet LF = Linear Feet CF = Cubic Feet

TABLE 2.2-1: SUMMARY OF HOMOGENEOUS SAMPLING AREAS

MALCOM RANDALL VA MEDICAL CENTER - CTICU – GAINESVILLE, FLORIDA

HA # HOMOGENEOUS MATERIAL

DESCRIPTION

HOMOGENEOUS MATERIAL

LOCATION

FRIABILITY

(F /NF)

% ASBESTOS* # OF SAMPLES

COLLECTED

APPROXIMATE

QUANTITY

ACM

CATEGORY

FT-09

12"x12" Cream/Gray Floor Tile with

Yellow Mastic on Gray Float Top Layer of SPB217A-1, SPB222-

NF ND 3 NIS NA

M-01 White Ceramic Grout Room B185A-1 NF ND 3 NIS NA M-02 Tan Ceramic Grout Room B187A-1 NF ND 3 NIS NA M-03 White Door Frame Caulk Doors Throughout NF ND 3 NIS NA M-04 White Caulk on Countertops Rooms B188-1, B188C-1, B188B-1 NF ND 3 NIS NA M-05 Gray Sink Undercoat Room B235-1 NF ND 3 NIS NA

MAS-01

Black Floor Mastic with Green and

Tan Carpet Mastics Room B194-1 NF

Black Mastic- 5%C;

Green and Tan Mastic-ND

3 120 SF CAT I

MAS-02 White Duct Mastic on Fiberglass Rooms B188-1, B188E-1, B194-1, B195-1

NF ND 3 NIS NA

MAS-03 Gray HVAC Mastic Return Ductwork in CTICU Area NF ND 3 NIS NA

MAS-05 Red HVAC Mastic/Sealant

Associated with Fiberglass Covered Metal HVAC Duct

Seams In North Hallway, Center Hallway, and Rooms B144-1, B208-1, B209-1, B181A-1, B181D- 1, B196-1, B198-1, B199-1, B200-1, B201-1, B202-1, B203-1, B204-1, B205-1, B206-1

NF Mastic-5%C 3 300 LF CAT I

MSV-01

Tan Sheet Vinyl with Yellow Mastic and Gray Float

Rooms B180-1, B188-1, B188A-1, B188B-1, B188C-1, B189-1, B190-

1, B191-1, B192-1, B-193-1

NF ND 3 NIS NA

MSV-02

White/Gray Sheet Vinyl with Yellow Mastic, Gray Float and Black Mastic Room B185B-1 NF ND 3 NIS NA

* = The facility owner has the option of point-counting by Polarized Light Microscopy (PLM) those RACM whose asbestos content is less than 10% in order to more accurately determine the asbestos content therein.

PC = Results based on Point-Count analysis TEM NOB = Transmission Electron Microscopy of Non-Friable Organically Bound Material

FRIABILITY F = Friable Material NF = Non-Friable Material

ACM CATEGORY RACM = Regulated ACM CAT I = Category I non-friable ACM CAT II = Category II non-friable ACM

ABBREVIATIONS: NA = Not Applicable ND = None Detected NIS = Not in Scope C = Chrysotile A = Amosite

HA = Homogeneous Area SF = Square Feet LF = Linear Feet CF = Cubic Feet

TABLE 2.2-1: SUMMARY OF HOMOGENEOUS SAMPLING AREAS

MALCOM RANDALL VA MEDICAL CENTER - CTICU – GAINESVILLE, FLORIDA

HA # HOMOGENEOUS MATERIAL

DESCRIPTION

HOMOGENEOUS MATERIAL

LOCATION

FRIABILITY

(F /NF)

% ASBESTOS* # OF SAMPLES

COLLECTED

APPROXIMATE

QUANTITY

ACM

CATEGORY

MSV-03

Blue Pebble Sheet Vinyl with Gray Backing, Gray Float, Yellow/Black

Mastics Room B186-1 NF ND 3 NIS NA

MSV-04

Tan/Gray Pebble Sheet Vinyl with

Black Mastic Room B235-1 NF ND 3 NIS NA

PL-01 White over Tan Plaster Perimeter Walls and Columns, Various Interior Walls Throughout

NF ND 3 NIS NA

TSI-01 White Mastic on Fiberglass Heating Hot Water Throughout NF ND 3 NIS NA

TSI-02 Black Elbow Mastic

North, East and West Hallways Throughout; Rooms B144-1, B208-1, B209-1, B181A-1, B181D- 1, B196-1, B198-1, B199-1, B200-1, B201-1, B202-1, B203-1, B204-1, B205-1, B206-1

NF Mastic-10%C 3 1,440 LF CAT I

TSI-03 Black Mastic Under Paper Wrap

North, East and West Hallways Throughout; Rooms B144-1, B208-

1, B209-1, B181A-1, B181D-1, B196-1, B198-1, B199-1, B200-1, B201-1, B202-1, B203-1, B204-1, B205-1, B206-1

NF ND 3 NIS NA

VB-01 6" Tan Cove Base with Tan Mastic

Rooms B144-1, B184-1, B184A-1, B185-1, B185C-1, B202-1, B203-1, B204-1, B205-1, B206-1, SPB222-

1, SPB217A-1, Electrical Closet

NF ND 3 NIS NA

VB-02

6" Burgundy Cove Base with

Yellow/White Mastics Rooms B187-1, B194-1 NF ND 3 NIS NA

VB-03 4" Aqua Cove Base with Tan Mastic Hallways Except Center Hallway NF ND 3 NIS NA

* = The facility owner has the option of point-counting by Polarized Light Microscopy (PLM) those RACM whose asbestos content is less than 10% in order to more accurately determine the asbestos content therein.

PC = Results based on Point-Count analysis TEM NOB = Transmission Electron Microscopy of Non-Friable Organically Bound Material

FRIABILITY F = Friable Material NF = Non-Friable Material

ACM CATEGORY RACM = Regulated ACM CAT I = Category I non-friable ACM CAT II = Category II non-friable ACM

ABBREVIATIONS: NA = Not Applicable ND = None Detected NIS = Not in Scope C = Chrysotile A = Amosite

HA = Homogeneous Area SF = Square Feet LF = Linear Feet CF = Cubic Feet

TABLE 2.2-1: SUMMARY OF HOMOGENEOUS SAMPLING AREAS

MALCOM RANDALL VA MEDICAL CENTER - CTICU – GAINESVILLE, FLORIDA

HA # HOMOGENEOUS MATERIAL

DESCRIPTION

HOMOGENEOUS MATERIAL

LOCATION

FRIABILITY

(F /NF)

% ASBESTOS* # OF SAMPLES

COLLECTED

APPROXIMATE

QUANTITY

ACM

CATEGORY

VB-04 6" Gray Cove Base with Tan Mastic

Rooms B181-1, B181-A, B181B-1, B181C-1, B181D-1, B182A-1, B196-1, B198-1, B199-1, B200-1, B201-1, B208-1, B235-1 and Center

Hallway

NF ND 3 NIS NA

VB-05 6" Brown Cove Base with Tan Mastic B206A-1 NF ND 3 NIS NA

MAS-04 Tan Pneumatic Tube Mastic

Above Ceiling in B181A-1, B181D- 1, B182A-1, B181C-1, B181-1, B183-1, B184-1, B184A-1, B222-1, B235-1

NF ND 3 NIS NA

3.0 CONCLUSIONS AND RECOMMENDATIONS

3.1 GENERAL

Asbestos-containing materials (ACMs) were identified in the scope of this survey. General and specific conclusions and recommendations are provided below.

The EPA, OSHA and the State of Florida have promulgated regulations dealing with asbestos.

For commercial building owners, the EPA NESHAP (40 CFR 61) regulations require removal of RACM, prior to conducting activities which might disturb the material. They also deal with notification, handling and disposal of asbestos.

No homogenous areas of suspect RACM were determined to contain less than 10 percent asbestos by PLM analysis. According to the NESHAP, when the asbestos content of a bulk sample of suspect RACM is determined to be less than 10 percent by PLM visual estimation, you may:

1. Assume the amount to be greater than one percent and treat the material as asbestos-containing; or

2. Conduct confirmatory verification by point-counting. Note, the results obtained by point-counting are considered the definitive analytical result.

The EPA recommends that an Operations and Maintenance (O&M) Program be developed for any facilities with ACM, and this Program should address all ACM (known and/or assumed) present. The O&M Program establishes notification and training requirements along with special procedures for working around the ACM. The O&M Program would remain in effect until all asbestos is removed.

Category I and Category II non-friable materials, as defined by the EPA, may remain within a facility during demolition with no potential cessation of work, provided they remain non-friable and the appropriate engineering controls (i.e., wet methods) are utilized, with the resulting waste disposed of as asbestos-containing waste. However, there is no guarantee that these materials will remain non-friable. If the materials become friable, then they are classified as RACM.

RACM, as defined by the EPA, must be removed prior to renovation or demolition activities that may disturb the materials.

The OSHA regulations deal with employee exposure to airborne asbestos fibers. The regulations restrict employee exposure, and require special monitoring, training and handling procedures when dealing with asbestos. Additionally, OSHA has regulations that may supersede the EPA regulations. In order to protect the worker, OSHA has established a permissible exposure limit (PEL), which limits employee exposure to airborne fiber concentrations. OSHA requires objective evidence that the PEL will not be exceeded, as justification that personal air monitoring and engineering controls will not be required. OSHA has also established rules requiring the containerization and labeling of asbestos waste.

The State regulations require that anyone involved in asbestos consulting activities be a licensed asbestos consultant and that anyone involved in asbestos abatement, with the exception of roofing materials, be a licensed asbestos abatement contractor.

3.2 SPECIFIC

Black Mastic Associated with 12"x12" Multicolor Floor Tile Black Mastic Associated with 12"x12" White Floor Tile 9"x9" Brown Floor Tile with Black Mastic Black Floor Mastic with Green and Tan Carpet Mastics Red HVAC Mastic/Sealant Black Elbow Mastic

These materials are defined by the EPA as a Category I non-friable materials. These materials do not appear to present a significant issue, as observed, at the time of the survey. We recommend that the identified ACM be maintained as part of an O&M Program and periodically monitored for any changes in condition. Additionally, we recommend that a licensed asbestos abatement contractor properly remove and dispose of the ACM prior to conducting renovation activities that might disturb the ACM.

4.0 LIMITATIONS AND CONDITIONS

As a result of previous renovations, there may be hidden materials, such as floor tile, sheet vinyl flooring, insulation, etc. These materials may be found in various areas hidden under existing flooring materials or in wall cavities. Any materials found during construction activities, either not addressed in this survey report, or similar to the ACM identified in this survey report should be assumed to be ACM until sampling and analysis documents otherwise.

Because of the hidden nature of many building components (i.e. within mechanical chases, underneath cabinetry and built-in lockers, underneath partition walls placed during previous renovations, etc.), it may be impossible to determine if all of the suspect building materials have been located and subsequently tested. Destructive testing in some instances is not a viable option.

We cannot, therefore, guarantee that all potential ACM has been located. For the same reasons, estimates of quantities and/or conditions are subject to readily apparent situations, and our findings reflect this condition. We do warrant, however, that the investigations and methodology reflect our best efforts based upon the prevailing standard of care in the environmental industry.

The information contained in this report was prepared based upon specific parameters and regulations in force at the time of this report. The information herein is only for the specific use of the client and GLE. GLE accepts no responsibility for the use, interpretation, or reliance by other parties on the information contained herein, unless prior written authorization has been obtained from GLE.

APPENDIX A

Analytical Results and Chain of Custody

SUMMARY OF BULK SAMPLE ANALYSIS

Toland Mizell Molnar; MRV AMC CTICU 19950-00536

Sample Sample Type Fiber Type

CT-01A 2' X 2' White Recessed

Ceiling Tile 100% Mineral Wool

CT-01B 2' X 2' White Recessed

Ceiling Tile 100% Mineral Wool

CT-01C-QC 2' X 2' White Recessed

Ceiling Tile 100% Mineral Wool

CT-02A 2' X 2' White Fissured

Ceiling Tile 100% Mineral Wool

CT-02B 2' X 2' White Fissured

Ceiling Tile 100% Mineral Wool

CT-02C 2' X 2' White Fissured

Ceiling Tile 100% Mineral Wool

CT-03A 2' X 2' White Smooth

Ceiling Tile 100% Mineral Wool

CT-03B 2' X 2' White Smooth

Ceiling Tile 100% Mineral Wool

CT-03C 2' X 2' White Smooth

Ceiling Tile 100% Mineral Wool

CT-04A 2' X 4' White Pinhole

Ceiling Tile 100% Mineral Wool

CT-04B 2' X 4' White Pinhole

Ceiling Tile 100% Mineral Wool

CT-04C 2' X 4' White Pinhole

Ceiling Tile 100% Mineral Wool

Darryl Neldner

* Polarized Light Microscopy coupled with dispersion is the technique used for identification in accordance with EPA 600/M4-82-020, EPA 600/R-93/116, and NIOSH Method 9002.

** The percentage of each component is visually estimated. The result of this analysis relate only to the material tested.

The report shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.

(>1% greater than one percent, <1% less than one percent) QC - Sample reanalyzed for QA/QC.

Analysis performed by GLE Associates, Inc. NVLAP Code 102003-0, CO AL-17485, TX 30-0337

*** This report shall not be reproduced except in full, without the written approval of the laboratory. GLE Report # 24471

Analyst / Approved

Signatory:

Feedback regarding laboratory performance should be addressed to lab@gleassociates.com.

Report Date: 9/6/2019

19950-00536

Sample Sample Type Fiber Type

DW-01A-QC Drywall & Joint

Compound 100% Gypsum, Quartz, Calcite, Clay

DW-01B Drywall & Joint

Compound 100% Gypsum, Quartz, Calcite, Clay

DW-01C Drywall & Joint

Compound 100% Gypsum, Quartz, Calcite, Clay

FT-01A 12" X 12" Multicolor

Floor Tile & Yellow

Mastic

100% Polymer, Quartz, Calcite, Clay, Mica

Black Mastic 5% Chrysotile Asbestos

95% Bitumen

FT-01B 12" X 12" Multicolor

Floor Tile & Yellow

Mastic

100% Polymer, Quartz, Calcite, Clay, Mica

Black Mastic Positive Stop/Sample not analyzed

FT-01C 12" X 12" Multicolor

Floor Tile & Yellow

Mastic

100% Polymer, Quartz, Calcite, Clay, Mica

Black Mastic Positive Stop/Sample not analyzed

FT-02A 12" X 12" Multicolor

Floor Tile & Tan Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

FT-02B 12" X 12" Multicolor

Floor Tile & Tan Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

Darryl Neldner

* Polarized Light Microscopy coupled with dispersion is the technique used for identification in accordance with EPA 600/M4-82-020, EPA 600/R-93/116, and NIOSH Method 9002.

** The percentage of each component is visually estimated. The result of this analysis relate only to the material tested.

The report shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.

(>1% greater than one percent, <1% less than one percent) QC - Sample reanalyzed for QA/QC.

Analysis performed by GLE Associates, Inc. NVLAP Code 102003-0, CO AL-17485, TX 30-0337

*** This report shall not be reproduced except in full, without the written approval of the laboratory. GLE Report # 24471

Analyst / Approved

Signatory:

19950-00536

Sample Sample Type Fiber Type

FT-02C 12" X 12" Multicolor

Floor Tile & Tan Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

FT-03A 12" X 12" Tan & Brown

Floor Tile & Yellow

Mastic

100% Polymer, Quartz, Calcite, Clay, Mica

FT-03B-QC 12" X 12" Tan & Brown

Floor Tile & Yellow

Mastic

100% Polymer, Quartz, Calcite, Clay, Mica

FT-03C 12" X 12" Tan & Brown

Floor Tile & Yellow

Mastic

100% Polymer, Quartz, Calcite, Clay, Mica

FT-04A 12" X 12" White & Gray

Floor Tile & Yellow

Mastic

100% Polymer, Quartz, Calcite, Clay, Mica

FT-04B 12" X 12" White & Gray

Floor Tile & Yellow

Mastic

100% Polymer, Quartz, Calcite, Clay, Mica

FT-04C 12" X 12" White & Gray

Floor Tile & Yellow

Mastic

100% Polymer, Quartz, Calcite, Clay, Mica

FT-05A 12" X 12" Aqua Floor Tile

& Yellow Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

FT-05B 12" X 12" Aqua Floor Tile

& Yellow Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

Darryl Neldner

* Polarized Light Microscopy coupled with dispersion is the technique used for identification in accordance with EPA 600/M4-82-020, EPA 600/R-93/116, and NIOSH Method 9002.

** The percentage of each component is visually estimated. The result of this analysis relate only to the material tested.

The report shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.

(>1% greater than one percent, <1% less than one percent) QC - Sample reanalyzed for QA/QC.

Analysis performed by GLE Associates, Inc. NVLAP Code 102003-0, CO AL-17485, TX 30-0337

*** This report shall not be reproduced except in full, without the written approval of the laboratory. GLE Report # 24471

Analyst / Approved

Signatory:

19950-00536

Sample Sample Type Fiber Type

FT-05C 12" X 12" Aqua Floor Tile

& Yellow Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

FT-06A 12" X 12" White Floor

Tile & Yellow Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

Black Mastic 5% Chrysotile Asbestos

95% Bitumen

FT-06B 12" X 12" White Floor

Tile & Yellow Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

Black Mastic Positive Stop/Sample not analyzed

FT-06C-QC 12" X 12" White Floor

Tile & Yellow Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

Black Mastic Positive Stop/Sample not analyzed

FT-07A 12" X 12" White & Brown

Floor Tile & Brown Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

FT-07B 12" X 12" White & Brown

Floor Tile & Brown Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

FT-07C 12" X 12" White & Brown

Floor Tile & Brown Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

FT-08A 9" X 9" Brown Floor Tile 7% Chrysotile Asbestos

93% Polymer, Quartz, Calcite, Clay, Mica

Black Mastic 5% Chrysotile Asbestos

95% Bitumen

Yellow Mastic 100% Polymer

Darryl Neldner

* Polarized Light Microscopy coupled with dispersion is the technique used for identification in accordance with EPA 600/M4-82-020, EPA 600/R-93/116, and NIOSH Method 9002.

** The percentage of each component is visually estimated. The result of this analysis relate only to the material tested.

The report shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.

(>1% greater than one percent, <1% less than one percent) QC - Sample reanalyzed for QA/QC.

Analysis performed by GLE Associates, Inc. NVLAP Code 102003-0, CO AL-17485, TX 30-0337

*** This report shall not be reproduced except in full, without the written approval of the laboratory. GLE Report # 24471

Analyst / Approved

Signatory:

19950-00536

Sample Sample Type Fiber Type

FT-08B 9" X 9" Brown Floor Tile

& Black Mastic Positive Stop/Sample not analyzed

Yellow Mastic 100% Polymer

FT-08C 9" X 9" Brown Floor Tile

& Black Mastic Positive Stop/Sample not analyzed

Yellow Mastic 100% Polymer

FT-09A 12" X 12" Cream & Gray

Floor Tile & Yellow

Mastic

100% Polymer, Quartz, Calcite, Clay, Mica

FT-09B 12" X 12" Cream & Gray

Floor Tile & Yellow

Mastic

100% Polymer, Quartz, Calcite, Clay, Mica

FT-09C 12" X 12" Cream & Gray

Floor Tile & Yellow

Mastic

100% Polymer, Quartz, Calcite, Clay, Mica

M-01A-QC White Ceramic Grout 100% Quartz, Calcite, Clay, Mica

M-01B White Ceramic Grout 100% Quartz, Calcite, Clay, Mica

M-01C White Ceramic Grout 100% Quartz, Calcite, Clay, Mica

M-02A Tan Ceramic Grout 100% Quartz, Calcite, Clay, Mica

M-02B Tan Ceramic Grout 100% Quartz, Calcite, Clay, Mica

M-02C Tan Ceramic Grout 100% Quartz, Calcite, Clay, Mica

Darryl Neldner

* Polarized Light Microscopy coupled with dispersion is the technique used for identification in accordance with EPA 600/M4-82-020, EPA 600/R-93/116, and NIOSH Method 9002.

** The percentage of each component is visually estimated. The result of this analysis relate only to the material tested.

The report shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.

(>1% greater than one percent, <1% less than one percent) QC - Sample reanalyzed for QA/QC.

Analysis performed by GLE Associates, Inc. NVLAP Code 102003-0, CO AL-17485, TX 30-0337

*** This report shall not be reproduced except in full, without the written approval of the laboratory. GLE Report # 24471

Analyst / Approved

Signatory:

19950-00536

Sample Sample Type Fiber Type

M-03A White Door Frame Caulk 100% Polymer, Quartz, Calcite, Clay, Mica

M-03B White Door Frame Caulk 100% Polymer, Quartz, Calcite, Clay, Mica

M-03C White Door Frame Caulk 100% Polymer, Quartz, Calcite, Clay, Mica

M-04A White Caulk on

Countertops 100% Polymer, Quartz, Calcite, Clay, Mica

M-04B-QC White Caulk on

Countertops 100% Polymer, Quartz, Calcite, Clay, Mica

M-04C White Caulk on

Countertops 100% Polymer, Quartz, Calcite, Clay, Mica

M-05A Gray Sink Undercoat 100% Polymer, Quartz, Calcite, Clay, Mica

M-05B Gray Sink Undercoat 100% Polymer, Quartz, Calcite, Clay, Mica

M-05C Gray Sink Undercoat 100% Polymer, Quartz, Calcite, Clay, Mica

MAS-01A Black Floor Mastic 5% Chrysotile Asbestos

95% Bitumen

Green & Tan Carpet

Mastics 100% Polymer

MAS-01B Black Floor Mastic Positive Stop/Sample not analyzed

Green & Tan Carpet

Mastics 100% Polymer

Darryl Neldner

* Polarized Light Microscopy coupled with dispersion is the technique used for identification in accordance with EPA 600/M4-82-020, EPA 600/R-93/116, and NIOSH Method 9002.

** The percentage of each component is visually estimated. The result of this analysis relate only to the material tested.

The report shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.

(>1% greater than one percent, <1% less than one percent) QC - Sample reanalyzed for QA/QC.

Analysis performed by GLE Associates, Inc. NVLAP Code 102003-0, CO AL-17485, TX 30-0337

*** This report shall not be reproduced except in full, without the written approval of the laboratory. GLE Report # 24471

Analyst / Approved

Signatory:

19950-00536

Sample Sample Type Fiber Type

MAS-01C Black Floor Mastic Positive Stop/Sample not analyzed

Green & Tan Carpet

Mastics 100% Polymer

MAS-02A White Duct Mastic on

Fiberglass 100% Polymer, Quartz, Calcite, Clay, Mica

MAS-02B White Duct Mastic on

Fiberglass 100% Polymer, Quartz, Calcite, Clay, Mica

MAS-02C-QC White Duct Mastic on

Fiberglass 100% Polymer, Quartz, Calcite, Clay, Mica

MAS-03A Gray HVAC Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

MAS-03B Gray HVAC Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

MAS-03C Gray HVAC Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

MAS-05A Red HVAC Mastic &

Sealant

5% Chrysotile Asbestos

95% Polymer

Brown HVAC Insulation 100% Cellulose/paper

MAS-05B Red HVAC Mastic &

Sealant Positive Stop/Sample not analyzed

Brown HVAC Insulation 100% Cellulose/paper

MAS-05C Red HVAC Mastic &

Sealant Positive Stop/Sample not analyzed

Brown HVAC Insulation 100% Cellulose/paper

Darryl Neldner

* Polarized Light Microscopy coupled with dispersion is the technique used for identification in accordance with EPA 600/M4-82-020, EPA 600/R-93/116, and NIOSH Method 9002.

** The percentage of each component is visually estimated. The result of this analysis relate only to the material tested.

The report shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.

(>1% greater than one percent, <1% less than one percent) QC - Sample reanalyzed for QA/QC.

Analysis performed by GLE Associates, Inc. NVLAP Code 102003-0, CO AL-17485, TX 30-0337

*** This report shall not be reproduced except in full, without the written approval of the laboratory. GLE Report # 24471

Analyst / Approved

Signatory:

19950-00536

Sample Sample Type Fiber Type

MSV-01A Tan Sheet Vinyl & Yellow

Mastic & Gray Float 100% Polymer, Quartz, Calcite, Clay, Mica

MSV-01B Tan Sheet Vinyl & Yellow

Mastic & Gray Float 100% Polymer, Quartz, Calcite, Clay, Mica

MSV-01C Tan Sheet Vinyl & Yellow

Mastic & Gray Float 100% Polymer, Quartz, Calcite, Clay, Mica

MSV-02A-QC White & Gray Sheet Vinyl 100% Polymer, Quartz, Calcite, Clay, Mica

Black Mastic Insufficient Material

MSV-02B White & Gray Sheet Vinyl 100% Polymer, Quartz, Calcite, Clay, Mica

Black Mastic Insufficient Material

MSV-02C White & Gray Sheet Vinyl 100% Polymer, Quartz, Calcite, Clay, Mica

Black Mastic Insufficient Material

MSV-03A Blue Pebble Sheet Vinyl

& Yellow & Black Mastics 100% Polymer, Quartz, Calcite, Clay, Mica, Bitumen

MSV-03B Blue Pebble Sheet Vinyl

& Yellow & Black Mastics 100% Polymer, Quartz, Calcite, Clay, Mica, Bitumen

MSV-03C Blue Pebble Sheet Vinyl

& Yellow & Black Mastics 100% Polymer, Quartz, Calcite, Clay, Mica, Bitumen

MSV-04A Tan & Gray Pebble Sheet

Vinyl & Black Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

Darryl Neldner

* Polarized Light Microscopy coupled with dispersion is the technique used for identification in accordance with EPA 600/M4-82-020, EPA 600/R-93/116, and NIOSH Method 9002.

** The percentage of each component is visually estimated. The result of this analysis relate only to the material tested.

The report shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.

(>1% greater than one percent, <1% less than one percent) QC - Sample reanalyzed for QA/QC.

Analysis performed by GLE Associates, Inc. NVLAP Code 102003-0, CO AL-17485, TX 30-0337

*** This report shall not be reproduced except in full, without the written approval of the laboratory. GLE Report # 24471

Analyst / Approved

Signatory:

19950-00536

Sample Sample Type Fiber Type

MSV-04B Tan & Gray Pebble Sheet

Vinyl & Black Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

MSV-04C Tan & Gray Pebble Sheet

Vinyl & Black Mastic 100% Polymer, Quartz, Calcite, Clay, Mica

PL-01A White over Tan Plaster 100% Quartz, Calcite, Clay, Mica

PL-01B-QC White over Tan Plaster 100% Quartz, Calcite, Clay, Mica

PL-01C White over Tan Plaster 100% Quartz, Calcite, Clay, Mica

TSI-01A White Mastic on Fiberglass 100% Polymer, Quartz, Calcite, Clay, Mica

TSI-01B White Mastic on Fiberglass 100% Polymer, Quartz, Calcite, Clay, Mica

TSI-01C White Mastic on Fiberglass 100% Polymer, Quartz, Calcite, Clay, Mica

TSI-02A Black Elbow Mastic 10% Chrysotile Asbestos

90% Bitumen

Yellow Insulation 100% Mineral Wool

TSI-02B Black Elbow Mastic Positive Stop/Sample not analyzed

Yellow Insulation 100% Mineral Wool

TSI-02C Black Elbow Mastic Positive Stop/Sample not analyzed

Yellow Insulation 100% Mineral Wool

TSI-03A Black Mastic under Paper

Wrap 100% Bitumen

Darryl Neldner

* Polarized Light Microscopy coupled with dispersion is the technique used for identification in accordance with EPA 600/M4-82-020, EPA 600/R-93/116, and NIOSH Method 9002.

** The percentage of each component is visually estimated. The result of this analysis relate only to the material tested.

The report shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.

(>1% greater than one percent, <1% less than one percent) QC - Sample reanalyzed for QA/QC.

Analysis performed by GLE Associates, Inc. NVLAP Code 102003-0, CO AL-17485, TX 30-0337

*** This report shall not be reproduced except in full, without the written approval of the laboratory. GLE Report # 24471

Analyst / Approved

Signatory:

19950-00536

Sample Sample Type Fiber Type

TSI-03B Black Mastic under Paper

Wrap 100% Bitumen

TSI-03C-QC Black Mastic under Paper

Wrap 100% Bitumen

VB-01A 6" Tan Cove Base & Tan

Mastic 100% Polymer

VB-01B 6" Tan Cove Base & Tan

Mastic 100% Polymer

VB-01C 6" Tan Cove Base & Tan

Mastic 100% Polymer

VB-02A 6" Burgundy Cove Base &

Yellow & White Mastic 100% Polymer

VB-02B 6" Burgundy Cove Base &

Yellow & White Mastic 100% Polymer

VB-02C 6" Burgundy Cove Base &

Yellow & White Mastic 100% Polymer

VB-03A 4" Aqua Cove Base & Tan

Mastic 100% Polymer

VB-03B 4" Aqua Cove Base & Tan

Mastic 100% Polymer

VB-03C 4" Aqua Cove Base & Tan

Mastic 100% Polymer

VB-04A-QC 6" Gray Cove Base & Tan

Mastic 100% Polymer

Darryl Neldner

* Polarized Light Microscopy coupled with dispersion is the technique used for identification in accordance with EPA 600/M4-82-020, EPA 600/R-93/116, and NIOSH Method 9002.

** The percentage of each component is visually estimated. The result of this analysis relate only to the material tested.

The report shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.

(>1% greater than one percent, <1% less than one percent) QC - Sample reanalyzed for QA/QC.

Analysis performed by GLE Associates, Inc. NVLAP Code 102003-0, CO AL-17485, TX 30-0337

*** This report shall not be reproduced except in full, without the written approval of the laboratory. GLE Report # 24471

Analyst / Approved

Signatory:

19950-00536

Sample Sample Type Fiber Type

VB-04B 6" Gray Cove Base & Tan

Mastic 100% Polymer

VB-04C 6" Gray Cove Base & Tan

Mastic 100% Polymer

VB-05A 6" Brown Cove Base &

Tan Mastic 100% Polymer

VB-05B 6" Brown Cove Base &

Tan Mastic 100% Polymer

VB-05C 6" Brown Cove Base &

Tan Mastic 100% Polymer

Darryl Neldner

* Polarized Light Microscopy coupled with dispersion is the technique used for identification in accordance with EPA 600/M4-82-020, EPA 600/R-93/116, and NIOSH Method 9002.

** The percentage of each component is visually estimated. The result of this analysis relate only to the material tested.

The report shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.

(>1% greater than one percent, <1% less than one percent) QC - Sample reanalyzed for QA/QC.

Analysis performed by GLE Associates, Inc. NVLAP Code 102003-0, CO AL-17485, TX 30-0337

*** This report shall not be reproduced except in full, without the written approval of the laboratory. GLE Report # 24471

Analyst / Approved

Signatory:

APPENDIX B

Personnel and Laboratory Certifications

JONATHAN ZACHEM, SECRETARYRICK SCOTT, GOVERNOR

STATE OF FLORIDA

DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION

ASBESTOS LICENSING UNIT

THE ASBESTOS CONSULTANT - ENGINEER HEREIN IS LICENSED UNDER THE

PROVISIONS OF CHAPTER 469, FLORIDA STATUTES

GREENE, ROBERT BLAIR

Do not alter this document in any form.

GLE ASSOCIATES INC

LICENSE NUMBER: EA0000009

EXPIRATION DATE: NOVEMBER 30, 2020

This is your license. It is unlawful for anyone other than the licensee to use this document.

5405 CYPRESS CENTER DR

SUITE 110

TAMPA FL 33609

Always verify licenses online at MyFloridaLicense.com https://www.myfloridalicense.com/LicenseDetail.asp?SID=&id=10324f95ba50b55978623c96241000ac

APPENDIX C

Asbestos Materials Location Plans

APPENDIX D

Photographs

Photograph Date:

September 4, 2019

Prepared By:

Upper Photo: CT-01-2’ x 2’ White Recessed Ceiling Tile

Lower Photo: CT-02-2’ x 2’ White Fissured Ceiling Tile 1

Figure

Job No.

19950-00536

Correct Patient Privacy Deficiencies-CTICU

Upper Photo: CT-03-2’ x 2’ White Smooth Ceiling Tile

Lower Photo: CT-04-2’ x 2’ White Pinhole Ceiling Tile 2

Figure

Job No.

19950-00536

Upper Photo: DW-01-Drywall and Joint Compound

Lower Photo: FT-01-12” x 12” Multicolor Floor Tile with Black Mastic 3

Figure

Job No.

19950-00536

Upper Photo: FT-02-12” x 12” Multicolor Floor Tile with Tan Mastic

Lower Photo: FT-03-12” x 12” Tan/Brown Floor Tile with Yellow Mastic 4

Figure

Job No.

19950-00536

Upper Photo: FT-04-12” x 12” White/Gray Floor Tile with Yellow Mastic

Lower Photo: FT-05-12” x 12” Aqua Floor Tile with Yellow Mastic 5

Figure

Job No.

19950-00536

Upper Photo: FT-06-12” x 12” White Floor Tile with Black Mastic

Lower Photo: FT-07-12” x 12” White/Brown Floor Tile with Brown Mastic

Figure

Job No.

19950-00536

Upper Photo: FT-08-9” x 9” Brown Floor Tile with Black Mastic

Lower Photo: FT-09-12” x 12” Cream/Gray Floor Tile with Yellow Mastic on Gray Float

Figure

Job No.

19950-00536

Upper Photo: M-01-White Ceramic Grout

Lower Photo: M-02-Tan Ceramic Grout

Figure

Job No.

19950-00536

Upper Photo: M-03-White Door Frame Caulk

Lower Photo: M-04-White Caulk on Countertops 9

Figure

Job No.

19950-00536

Upper Photo: M-05-Gray Sink Undercoat

Lower Photo: MAS-01-Black Floor Mastic with Green and Tan Carpet Mastics

Figure

Job No.

19950-00536

Upper Photo: MAS-02-White Duct Mastic on Fiberglass

Lower Photo: MAS-03-Gray HVAC Mastic 11

Figure

Job No.

19950-00536

Upper Photo: MAS-05-Red HVAC Mastic/Sealant

Lower Photo: MSV-01-Tan Sheet Vinyl with Yellow Mastic and Gray Float 12

Figure

Job No.

19950-00536

Upper Photo: MSV-02-White/Gray Sheet Vinyl with Yellow Mastic, Gray Float and Black Mastic

Lower Photo: MSV-03-Blue Pebble Sheet Vinyl with Gray Backing, Gray Float, Yellow/Black Mastics

Figure

Job No.

19950-00536

Upper Photo: MSV-04-Tan/Gray Pebble Sheet Vinyl with Black Mastic

Lower Photo: PL-01-White over Tan Plaster 14

Figure

Job No.

19950-00536

Upper Photo: TSI-01-White Mastic on Fiberglass

Lower Photo: TSI-02-Black Elbow Mastic 15

Figure

Job No.

19950-00536

Upper Photo: TSI-03-Black Mastic under Paper Wrap

Lower Photo: VB-01-6” Tan Cove Base with Tan Mastic 16

Figure

Job No.

19950-00536

Upper Photo: VB-02-6” Burgundy Cove Base with Yellow/White Mastics

Lower Photo: VB-03-4” Aqua Cove Base with Tan Mastic 17

Figure

Job No.

19950-00536

Upper Photo: VB-04-6” Gray Cove Base with Tan Mastic

Lower Photo: VB-05-6” Brown Cove Base with Tan Mastic 18

Figure

Job No.

19950-00536

Upper Photo: MAS-04-Tan Pneumatic Tube Mastic

Figure

Job No.

19950-00536