36C248-21-R-0139-573-18-605 Correct Patient Privacy Deficiencies_Addendum Drawings.pdf
PDF 1018 KB Posted
- Solicitation number
- 36C24821R0139
About this file
This pre-solicitation announcement is for a construction project to expand and renovate the Cardiothoracic Intensive Care Unit at the Malcolm Randall VA Medical Center in Gainesville, Florida. The project includes increasing capacity and eliminating deficiencies to improve functionality, patient access, and privacy. Bid alternates will deduct switchable privacy glass and replace it with either ceiling-mounted curtain tracks or clear tempered glass to ensure the contract is awarded within budget. The estimated construction period is 365 days. The solicitation will be issued on July 28, 2021 via beta.SAM.gov for a firm fixed-price construction contract to be awarded within 120 days. The North American Industry Classification System code is 236220 and the small business size standard is $39.5 million. Questions must be submitted in writing to the contracting officer by the specified due date.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
FINAL SUBMITTAL
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
SCHEDULES CORRECT PATIENT PRIVACY
DEFICIENCIES
GAINESVILLE, FL
E601
573-18-605
SBC SJB02-01-2021
TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA
TOTALS (CONN. KVA) KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP KVA KVA KVA KVA 1.00 KVA
RECEPTACLES KVA KVA KVA KVA NEC KVA
LIGHTING KVA KVA KVA KVA 1.25 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
BREAKERS IN SAME CIRCUIT LOCATION.
FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW
THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING
FED FROM PANEL BC.N.DP1
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: B: C:
29 SPACE C SPACE 30
27 EXISTING LOAD 20 B 28
25 A 26
23 EXISTING LOAD C EXISTING LOAD 24
21 EXISTING LOAD 20 B 20 EXISTING LOAD 22
19 EXISTING LOAD 20 A 20 EXISTING LOAD 20
17 EXISTING LOAD 20 C 20 EXISTING LOAD 18
15 EXISTING LOAD 20 B 20 EXISTING LOAD 16
13 EXISTING LOAD 20 A 20 EXISTING LOAD 14
11 EXISTING LOAD 20 C 20 EXISTING LOAD 12
9 EXISTING LOAD 20 B 20 EXISTING LOAD 10
7 EXISTING LOAD 20 A 20 EXISTING LOAD 8
5 EXISTING LOAD 20 C 20 EXISTING LOAD 6
3 EXISTING LOAD 20 B 20 EXISTING LOAD 4
1 EXISTING LOAD 20 A 20 EXISTING LOAD 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1
EXISTING PANEL UL-4-IC-SEC 1 SCHEDULE
TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA
TOTALS (CONN. KVA) KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP KVA KVA KVA KVA 1.00 KVA
RECEPTACLES KVA KVA KVA KVA NEC KVA
LIGHTING KVA KVA KVA KVA 1.25 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
BREAKERS IN SAME CIRCUIT LOCATION.
FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW
THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING
FED FROM PANEL BC.N.DP1
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: B: C:
29 SPACE C SPACE 30
27 EXISTING LOAD 3/4 12 20 B 20 EXISTING LOAD 28
25 EXISTING LOAD 3/4 12 20 A 20 EXISTING LOAD 26
23 EXISTING LOAD 3/4 12 20 C 20 EXISTING LOAD 24
21 EXISTING LOAD 3/4 12 20 B 20 EXISTING LOAD 22
19 EXISTING LOAD 3/4 12 20 A 20 EXISTING LOAD 20
17 EXISTING LOAD 3/4 12 20 C 20 EXISTING LOAD 18
15 EXISTING LOAD 3/4 12 20 B 20 EXISTING LOAD 16
13 A 20 EXISTING LOAD 14
11 EXISTING LOAD C 20 EXISTING LOAD 12
9 SPACE B 20 EXISTING LOAD 10
7 EXISTING LOAD 3/4 12 20 A 20 EXISTING LOAD 8
5 EXISTING LOAD 3/4 12 20 C 20 EXISTING LOAD 6
3 EXISTING LOAD 3/4 12 20 B 20 EXISTING LOAD 4
1 EXISTING LOAD 3/4 12 20 A 20 EXISTING LOAD 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1
EXISTING PANEL UL-4-IC-SEC 2 SCHEDULE
TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA
TOTALS (CONN. KVA) KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP KVA KVA KVA KVA 1.00 KVA
RECEPTACLES KVA KVA KVA KVA NEC KVA
LIGHTING KVA KVA KVA KVA 1.25 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
BREAKERS IN SAME CIRCUIT LOCATION.
FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW
THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING
FED FROM PANEL BC.N.DP1
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: B: C:
29 SPACE C 20 EXISTING LOAD 30
27 EXISTING LOAD 20 B 20 EXISTING LOAD 28
25 A 20 EXISTING LOAD 26
23 C 20 EXISTING LOAD 24
21 EXISTING LOAD 20 B 20 EXISTING LOAD 22
19 EXISTING LOAD 20 A 20 EXISTING LOAD 20
17 EXISTING LOAD 20 C 20 EXISTING LOAD 18
15 EXISTING LOAD 20 B 20 EXISTING LOAD 16
13 EXISTING LOAD 20 A 20 EXISTING LOAD 14
11 EXISTING LOAD 20 C 20 EXISTING LOAD 12
9 B 20 EXISTING LOAD 10
7 EXISTING LOAD 30 A 20 EXISTING LOAD 8
5 C 6
3 B 20 EXISTING LOAD 4
1 MAIN BREAKER 100 A 20 EXISTING LOAD 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1
EXISTING PANEL UL-4-IC-SEC 3 SCHEDULE
TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA
TOTALS (CONN. KVA) KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP KVA KVA KVA KVA 1.00 KVA
RECEPTACLES KVA KVA KVA KVA NEC KVA
LIGHTING KVA KVA KVA KVA 1.25 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
BREAKERS IN SAME CIRCUIT LOCATION.
FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW
THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING
FED FROM PANEL BC.N.DP2
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: B: C:
35 C 36
33 B 34
31 EXISTING LOAD A 20 32
29 EXISTING LOAD 20 C 20 30
27 EXISTING LOAD 20 B 20 28
25 EXISTING LOAD 20 A 20 26
23 EXISTING LOAD 20 C 20 24
21 EXISTING LOAD 20 B 20 22
19 EXISTING LOAD 20 A 20 20
17 EXISTING LOAD 20 C 20 18
15 EXISTING LOAD 20 B 20 16
13 EXISTING LOAD 20 A 20 14
11 EXISTING LOAD 20 C 20 12
9 EXISTING LOAD 20 B 20 10
7 EXISTING LOAD 20 A 20 8
5 EXISTING LOAD 20 C 20 6
3 EXISTING LOAD 20 B 20 4
1 EXISTING LOAD 20 A 20 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
175 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1
EXISTING PANEL UL.1.1B.SEC 1 SCHEDULE
TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA
TOTALS (CONN. KVA) KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP KVA KVA KVA KVA 1.00 KVA
RECEPTACLES KVA KVA KVA KVA NEC KVA
LIGHTING KVA KVA KVA KVA 1.25 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
BREAKERS IN SAME CIRCUIT LOCATION.
FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW
THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING
FED FROM PANEL BC.N.DP2
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: B: C:
35 EXISTING LOAD 3/4 12 20 C 36
33 EXISTING LOAD 3/4 12 20 B EXISTING LOAD 34
31 EXISTING LOAD 3/4 12 20 A 20 12 3/4 EXISTING LOAD 32
29 EXISTING LOAD 3/4 12 20 C 30
27 B 28
25 EXISTING LOAD A EXISTING LOAD 26
23 EXISTING LOAD 3/4 12 20 C 20 12 3/4 EXISTING LOAD 24
21 EXISTING LOAD 3/4 12 20 B 20 12 3/4 EXISTING LOAD 22
19 EXISTING LOAD 3/4 12 20 A 20 12 3/4 EXISTING LOAD 20
17 EXISTING LOAD 3/4 12 20 C 20 12 3/4 EXISTING LOAD 18
15 EXISTING LOAD 3/4 12 20 B 20 12 3/4 EXISTING LOAD 16
13 A 20 12 3/4 EXISTING LOAD 14
11 EXISTING LOAD C 20 12 3/4 EXISTING LOAD 12
9 B 20 12 3/4 EXISTING LOAD 10
7 EXISTING LOAD A 20 12 3/4 EXISTING LOAD 8
5 EXISTING LOAD 3/4 12 20 C 20 12 3/4 EXISTING LOAD 6
3 EXISTING LOAD 3/4 12 20 B 20 12 3/4 EXISTING LOAD 4
1 EXISTING LOAD 3/4 12 20 A 20 12 3/4 EXISTING LOAD 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
175 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1
EXISTING PANEL UL.1.1B.SEC 2 SCHEDULE
TOTALS (CONN. AMPS + 20%) 73.0 AMPS AMPS AMPS 73.0 AMPS 53.2 AMPS
TOTALS (CONN. AMPS) 60.8 AMPS AMPS AMPS 60.8 AMPS 44.3 AMPS
TOTALS (CONN. KVA + 20%) 26.3 KVA KVA KVA 26.3 KVA 19.2 KVA
TOTALS (CONN. KVA) 21.9 KVA KVA KVA 21.9 KVA 16.0 KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP KVA KVA KVA KVA 1.00 KVA
RECEPTACLES 21.9 KVA KVA KVA 21.9 KVA NEC 16.0 KVA
LIGHTING KVA KVA KVA KVA 1.25 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: 62.0 B: 60.7 C: 60.0
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: 62.0 B: 60.7 C: 60.0
41 RECEPTACLES 3/4 3#12 20 7.5 0.9 C 20 SPARE 42
39 RECEPTACLES 3/4 3#12 20 7.5 0.9 B 20 SPARE 40
37 RECEPTACLES 3/4 3#12 20 4.5 0.5 A 20 SPARE 38
35 RECEPTACLES 3/4 3#12 20 7.5 0.9 C 20 SPARE 36
33 RECEPTACLES 3/4 3#12 20 4.5 0.5 B 20 SPARE 34
31 RECEPTACLES 3/4 3#12 20 4.5 0.5 A 20 SPARE 32
29 RECEPTACLES 3/4 3#12 20 7.5 0.9 C 20 SPARE 30
27 RECEPTACLES 3/4 3#12 20 3.0 0.4 B 20 SPARE 28
25 RECEPTACLES 3/4 3#12 20 3.0 0.4 A 20 SPARE 26
23 RECEPTACLES 3/4 3#12 20 4.5 0.5 C 20 SPARE 24
21 RECEPTACLES 3/4 3#12 20 4.5 0.5 B 0.8 6.7 20 3#12 3/4 RECEPTACLES 22
19 RECEPTACLES 3/4 3#12 20 9.0 1.1 A 0.5 4.0 20 3#10 3/4 RECEPTACLES 20
17 RECEPTACLES 3/4 3#12 20 6.0 0.7 C 0.9 7.5 20 3#12 3/4 RECEPTACLES 18
15 RECEPTACLES 3/4 3#12 20 6.0 0.7 B 1.1 9.0 20 3#12 3/4 RECEPTACLES 16
13 RECEPTACLES 3/4 3#12 20 1.5 0.2 A 1.1 9.0 20 3#12 3/4 RECEPTACLES 14
11 RECEPTACLES 3/4 3#12 20 1.5 0.2 C 0.5 4.5 20 3#12 3/4 RECEPTACLES 12
9 RECEPTACLES 3/4 3#12 20 4.5 0.5 B 0.5 4.5 20 3#12 3/4 RECEPTACLES 10
7 RECEPTACLES 3/4 3#12 20 6.0 0.7 A 0.7 6.0 20 3#12 3/4 RECEPTACLES 8
5 RECEPTACLES 3/4 3#12 20 9.0 1.1 C 0.5 4.5 20 3#12 3/4 RECEPTACLES 6
3 RECEPTACLES 3/4 3#12 20 4.5 0.5 B 0.7 6.0 20 3#12 3/4 RECEPTACLES 4
1 RECEPTACLES 3/4 3#12 20 10.0 1.2 A 0.5 4.5 20 3#12 3/4 RECEPTACLES 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 1
PANEL UL.2.1B SCHEDULE
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL NO.
LAMP
TYPE
VOLTAGE WATTS
MOUNTING
NOTES
COUNTTYPE HEIGHT
LED 277 V 44 W 4
A 2X4 LED TROFFER, NOMINAL 5000 LUMENS OUTPUT, 4000K CCT, MIN 90 CRI, FRAMED WHITE
ENAMEL STEEL HOUSING, FORMED WHITE STEEL OUTER REFLECTOR, EXTRUDED ALUMINUM
HEATSINK, FROSTED WHITE PLASTIC ENCLOSURE.
CREE LIGHTING CR24-50L-40K-S LED 120 V 50 W CEILING
RECESSED
N/A 57
B 6" LED DOWNLIGHT, NOMINAL 2000 LUMENS OUPUT, 4000K CCT, MIN 80 CRI, 6 IN CLEAR TRIM, SELF FLANGED, WIDE DISTRIBUTION, SEMI-SPECULAR FINISH, 0-10V ELECTRONIC DRIVER
EVO LIGHTING EVO-40/20-6AR-WD-LSS-277-EZ10 LED 120 V 23 W CEILING
RECESSED
N/A 57
C 1X4 LED TROFFER, NOMINAL 3100 LUMENS OUTPUT, 4000K CCT, MIN 90 CRI, FRAMED WHITE
ENAMEL STEEL HOUSING, FORMED WHITE STEEL OUTER REFLECTOR, EXTRUDED ALUMINUM
HEATSINK, FROSTED WHITE PLASTIC ENCLOSURE
CREE LIGHTING CR14-31L-40K LED 120 V 34 W PENDANT 7' 0" AFF UON 3
D 2X2 LED TROFFER, NOMINAL 3200 LUMENS OUTPUT, 4000K CCT, MIN 90 CRI, FRAMED WHITE
ENAMEL STEEL HOUSING, FORMED WHITE STEEL OUTER REFLECTOR, EXTRUDED ALUMINUM
HEATSINK, FROSTED WHITE PLASTIC ENCLOSURE
CREE LIGHTING CR22-32L-40K LED 120 V 32 W CEILING
RECESSED
N/A 18
E COMPACT RECESSED WHITE LED NIGHTLIGHT, ANTIMICROBIAL WHITE FACEPLATE, WITH
PHOTOCELL
COOPER INDUSTRIES MCL-UNV-AMW-PHC-TP LED 5 W WALL
RECESSED
1'-6" 8
F 2' LED CONTEMPORARY VANITY SQUARE, NOMINAL 1300 LUMENS OUTPUT, 4000K CCT, MIN 90
CRI, EXTRUDED ACRYLIC DIFFUSER, BRUSHED NICKEL FINISH
LITHONIA LIGHTING FMVCSL-24IN-MVOLT-40K-90CRI-BN LED 120 V 18 W WALL ABOVE
MIRROR
7' 0" AFF UON 1
G SKYVIEW DIGITAL CINEMA, VIRTUAL SKYLIGHT SKY FACTORY 5530 LED 120 V 800 W CEILING
RECESSED
N/A 4
H LED STRIP LIGHT LITHONIA CLX-L48-5000LM-SEF-RDL-MVOLT-GZ10-35
K-80CRI
LED 120 V 23 W SURFACE 2
X1 EXIT LIGHT LITHONIA LE-S-R LED 120 V 1 W UNIVERSAL N/A 6
1 ADDENDUM 1 8/23/21
8/24/2l
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
FINAL SUBMITTAL
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
SCHEDULES CORRECT PATIENT PRIVACY
DEFICIENCIES
GAINESVILLE, FL
E602
573-18-605
SBC TWG02-01-2021
TOTALS (CONN. AMPS + 20%) 7.0 AMPS AMPS AMPS 7.0 AMPS 8.8 AMPS
TOTALS (CONN. AMPS) 5.9 AMPS AMPS AMPS 5.9 AMPS 7.3 AMPS
TOTALS (CONN. KVA + 20%) 5.8 KVA KVA KVA 5.8 KVA 7.3 KVA
TOTALS (CONN. KVA) 4.9 KVA KVA KVA 4.9 KVA 6.1 KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP KVA KVA KVA KVA 1.00 KVA
RECEPTACLES KVA KVA KVA KVA NEC KVA
LIGHTING 4.9 KVA KVA KVA 4.9 KVA 1.25 6.1 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
1. USE 20A SPARE BREAKER.
BREAKERS IN SAME CIRCUIT LOCATION.
FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW
THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING
FED FROM PANEL BC.LS.DLA
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: 8.2 C: 9.4
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: B: 8.2 C: 9.4
11 CORRIDOR LIGHTS (NOTE 1) 3/4 12 20 4.8 1.3 C SPACE 12
9 CORRIDOR LIGHTS 20 B SPACE 10
7 CORRIDOR LIGHTS 20 A SPACE 8
5 LIGHTS GRAPHICS LAB 20 C 1.3 4.6 20 12 3/4 INTERIOR LIGHTS (NOTE 1) 6
3 CORRIDOR LIGHTS 20 B 2.3 8.2 20 12 3/4 INTERIOR LIGHTS (NOTE 1) 4
1 CORRIDOR LIGHTS 20 A SPACE 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
30 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1
EXISTING PANEL ELH-4-1C SCHEDULE
TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA
TOTALS (CONN. KVA) KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP KVA KVA KVA KVA 1.00 KVA
RECEPTACLES KVA KVA KVA KVA NEC KVA
LIGHTING KVA KVA KVA KVA 1.25 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
BREAKERS IN SAME CIRCUIT LOCATION.
FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW
THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING
FED FROM PANEL BC.CR2.DLB
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: B: C:
19 SPACE A SPACE 20
17 EXISTING LOAD 20 C 20 12 3/4 EXISTING LOAD 18
15 EXISTING LOAD 20 B 20 12 3/4 EXISTING LOAD 16
13 EXISTING LOAD 20 A 20 12 3/4 EXISTING LOAD 14
11 EXISTING LOAD 20 C 12
9 EXISTING LOAD 20 B EXISTING LOAD 10
7 EXISTING LOAD 20 A 20 12 3/4 EXISTING LOAD 8
5 EXISTING LOAD 20 C 20 12 3/4 EXISTING LOAD 6
3 EXISTING LOAD 20 B 20 12 3/4 EXISTING LOAD 4
1 EXISTING LOAD 20 A 20 12 3/4 EXISTING LOAD 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
90 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1
EXISTING PANEL CLH-4-IC SCHEDULE
TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA
TOTALS (CONN. KVA) KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP KVA KVA KVA KVA 1.00 KVA
RECEPTACLES KVA KVA KVA KVA NEC KVA
LIGHTING KVA KVA KVA KVA 1.25 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
FED FROM PANEL BC.CR3.DP1
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: B: C:
29 SPACE C SPACE 30
27 SPACE B SPACE 28
25 SPACE A SPACE 26
23 SPACE C SPACE 24
21 SPACE B SPACE 22
19 SPACE A 20 EXISTING LOAD 20
17 SPACE C 20 EXISTING LOAD 18
15 EXISTING LOAD 20 B 20 EXISTING LOAD 16
13 EXISTING LOAD 20 A SPACE 14
11 EXISTING LOAD 20 C SPACE 12
9 EXISTING LOAD 20 B 20 EXISTING LOAD 10
7 EXISTING LOAD 20 A 20 EXISTING LOAD 8
5 EXISTING LOAD 20 C 6
3 EXISTING LOAD 20 B 20 EXISTING LOAD 4
1 EXISTING LOAD 20 A 20 EXISTING LOAD 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
100 AMP MLO 208Y/120 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 1
EXISTING PANEL 1B.CR3.P2 SCHEDULE
TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA
TOTALS (CONN. KVA) KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP KVA KVA KVA KVA 1.00 KVA
RECEPTACLES KVA KVA KVA KVA NEC KVA
LIGHTING KVA KVA KVA KVA 1.25 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
FED FROM PANEL BC.CR3.DPB
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: B: C:
29 SPACE C SPACE 30
27 SPACE B SPACE 28
25 SPACE A SPACE 26
23 SPACE C SPACE 24
21 SPACE B SPACE 22
19 EXISTING LOAD 20 A 20 EXSITING LOAD 20
17 EXISTING LOAD 20 C 20 EXSITING LOAD 18
15 EXISTING LOAD 20 B 20 EXSITING LOAD 16
13 EXISTING LOAD 20 A 20 EXSITING LOAD 14
11 EXISTING LOAD 20 C 20 EXSITING LOAD 12
9 EXISTING LOAD 20 B 20 EXSITING LOAD 10
7 EXISTING LOAD 20 A 20 EXSITING LOAD 8
5 EXISTING LOAD 20 C 20 EXSITING LOAD 6
3 EXISTING LOAD 20 B 20 EXSITING LOAD 4
1 EXISTING LOAD 20 A 20 EXSITING LOAD 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
100 AMP MLO 480Y/277 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 1
EXISTING PANEL 1B.CR3.PA SCHEDULE
TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS
TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA
TOTALS (CONN. KVA) KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP KVA KVA KVA KVA 1.00 KVA
RECEPTACLES KVA KVA KVA KVA NEC KVA
LIGHTING KVA KVA KVA KVA 1.25 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
FED FROM PANEL BC.EQ2.PA
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: B: C:
47 C 48
45 B 46
43 A SPACE 44
SUBFEED BREAKERS
41 SPACE C SPACE 42
39 SPACE B SPACE 40
37 SPACE A SPACE 38
35 SPACE C SPACE 36
33 SPACE B SPACE 34
31 SPACE A SPACE 32
29 C 30
27 B 28
25 EXISTING LOAD A EXISTING LOAD 26
23 C 24
21 B 22
19 EXISTING LOAD A EXISTING LOAD 20
17 C 18
15 B 16
13 EXISTING LOAD A EXISTING LOAD 14
11 C 12
9 B 10
7 EXISTING LOAD A EXISTING LOAD 8
5 C 6
3 B 4
1 EXISTING LOAD A EXISTING LOAD 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
400 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 1
EXISTING PANEL BC.EQ2.PA SCHEDULE
TOTALS (CONN. AMPS + 20%) 65.3 AMPS AMPS AMPS 65.3 AMPS 65.3 AMPS
TOTALS (CONN. AMPS) 54.4 AMPS AMPS AMPS 54.4 AMPS 54.4 AMPS
TOTALS (CONN. KVA + 20%) 54.3 KVA KVA KVA 54.3 KVA 54.3 KVA
TOTALS (CONN. KVA) 45.3 KVA KVA KVA 45.3 KVA 45.3 KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP 45.3 KVA KVA KVA 45.3 KVA 1.00 45.3 KVA
RECEPTACLES KVA KVA KVA KVA NEC KVA
LIGHTING KVA KVA KVA KVA 1.25 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: 61.1 B: 51.1 C: 51.1
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: 61.1 B: 51.1 C: 51.1
41 C 42 39 B 40
37 A 38
35 C 36
33 B 34
31 A 32 29 7.6 2.1 C 30
27 7.6 2.1 B 28
25 HWP -1 & 2 3/4 4#12 20 7.6 2.1 A 26
23 4.0 1.1 C 24
21 4.0 1.1 B 22
19 EF-101 3/4 4#12 20 4.0 1.1 A 0.3 1.1 20
17 12.3 3.4 C 0.3 1.1 18
15 12.3 3.4 B 0.3 1.1 20 4#12 3/4 EF-31 16
13 EF-147 & 148 3/4 4#12 20 12.3 3.4 A 2.8 10.0 20 3#12 3/4 AHU-7 LTS,REC AND UV LTS/HUM-1 14
11 11.0 3.1 C 0.6 2.1 12
9 11.0 3.1 B 0.6 2.1 10
7 SF-2 - AHU-7 3/4 4#12 20 11.0 3.1 A 0.6 2.1 20 4#12 3/4 RF-2 - AHU-7 8
5 11.0 3.1 C 0.6 2.1 6
3 11.0 3.1 B 0.6 2.1 4
1 SF-1 - AHU-7 3/4 4#12 20 11.0 3.1 A 0.6 2.1 20 4#12 3/4 RF-1 - AHU-7 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
150 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 3R
NEW PANEL R.EQ2 SCHEDULE
TOTALS (CONN. AMPS + 20%) 173.9 AMPS AMPS AMPS 173.9 AMPS 115.4 AMPS
TOTALS (CONN. AMPS) 144.9 AMPS AMPS AMPS 144.9 AMPS 96.2 AMPS
TOTALS (CONN. KVA + 20%) 62.6 KVA KVA KVA 62.6 KVA 41.6 KVA
TOTALS (CONN. KVA) 52.2 KVA KVA KVA 52.2 KVA 34.7 KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP KVA KVA KVA KVA 1.00 KVA
RECEPTACLES 47.5 KVA KVA KVA 47.5 KVA NEC 28.7 KVA
LIGHTING 4.7 KVA KVA KVA 4.7 KVA 1.25 5.9 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
FED FROM PANEL BC.CR2.DP1
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: 126.8 B: 142.7 C: 165.6
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: 126.8 B: 142.7 C: 165.6
41 RECEPTACLES 3/4 3#12 20 15.0 1.8 C 20 SPARE 42
39 RECEPTACLES 3/4 3#12 20 6.0 0.7 B 20 SPARE 40
37 RECEPTACLES 3/4 3#12 20 10.8 1.3 A 0.3 2.5 20 3/4 3#12 LIGHTING AND RECEPTACLE 38
35 RECEPTACLES 3/4 3#12 20 14.2 1.7 C 1.8 15.0 20 3/4 3#12 HEADWALL 36
33 RECEPTACLES 3/4 3#12 20 15.0 1.8 B 1.8 15.0 20 3/4 3#12 HEADWALL 34
31 RECEPTACLES 3/4 3#12 20 1.5 0.2 A 1.8 15.0 20 3/4 3#12 HEADWALL 32
29 RECEPTACLES 3/4 3#12 20 3.0 0.4 C 1.8 15.0 20 3/4 3#12 HEADWALL 30
27 RECEPTACLES 3/4 3#12 20 3.0 0.4 B 1.8 15.0 20 3/4 3#12 HEADWALL 28
25 RECEPTACLES 3/4 3#12 20 4.5 0.5 A 1.8 15.0 20 3/4 3#12 HEADWALL 26
23 RECEPTACLES 3/4 3#12 20 15.0 1.8 C 1.8 15.0 20 3/4 3#12 HEADWALL 24
21 RECEPTACLES 3/4 3#12 20 15.0 1.8 B 1.8 15.0 20 3/4 3#12 HEADWALL 22
19 RECEPTACLES 3/4 3#12 20 12.5 1.5 A 0.5 4.5 20 3/4 3#12 RECEPTACLES 20
17 RECEPTACLES 3/4 3#12 20 15.0 1.8 C 0.7 6.0 20 3/4 3#12 RECEPTACLES 18
15 RECEPTACLES 3/4 3#12 20 7.5 0.9 B 1.8 15.0 20 3/4 3#12 RECEPTACLES 16
13 RECEPTACLES 3/4 3#12 20 10.0 1.2 A 0.5 4.5 20 3/4 3#12 RECEPTACLES 14
11 RECEPTACLES 3/4 3#12 20 15.0 1.8 C 1.2 11.5 RECEPTACLES 12
9 LIGHTING 3/4 3#12 20 8.0 1.0 B 1.2 11.5 20 3/4 4#12 RECEPTACLES 10
7 LIGHTING 3/4 3#12 20 8.1 1.0 A 1.8 15.0 20 3/4 3#12 RECEPTACLES 8
5 LIGHTING 3/4 3#12 20 12.4 1.5 C 1.8 15.0 20 3/4 3#12 RECEPTACLES 6
3 LIGHTING 3/4 3#12 20 3.2 0.4 B 1.8 15.0 20 3/4 3#12 RECEPTACLES 4
1 LIGHTING 3/4 3#12 20 7.8 0.9 A 1.8 15.0 20 3/4 3#12 RECEPTACLES 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
125 AMP MLO 208Y/120 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 1
EXISTING PANEL 1B.CR2.PI SCHEDULE
TOTALS (CONN. AMPS + 20%) 102.9 AMPS AMPS AMPS 102.9 AMPS 68.1 AMPS
TOTALS (CONN. AMPS) 85.8 AMPS AMPS AMPS 85.8 AMPS 56.8 AMPS
TOTALS (CONN. KVA + 20%) 37.1 KVA KVA KVA 37.1 KVA 24.5 KVA
TOTALS (CONN. KVA) 30.9 KVA KVA KVA 30.9 KVA 20.5 KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
KVA KVA KVA KVA KVA
ELEVATOR KVA KVA KVA KVA 0.80 KVA
MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA
ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA
MECH EQUIP KVA KVA KVA KVA 1.00 KVA
RECEPTACLES 30.9 KVA KVA KVA 30.9 KVA NEC 20.5 KVA
LIGHTING KVA KVA KVA KVA 1.25 KVA
LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND
PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA
FED FROM PANEL BC.CR3.DP1
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: 99.5 B: 78.0 C: 80.0
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: 99.5 B: 78.0 C: 80.0
41 SPARE 20 C 20 SPARE 42
39 SPARE 20 B 20 SPARE 40
37 SPARE 20 A 20 SPARE 38
35 SPARE 20 C 20 SPARE 36
33 SPARE 20 B 20 SPARE 34
31 PATIENT BED 3/4 3#12 20 10.0 1.2 A 20 SPARE 32
29 HEADWALL 3/4 3#12 20 15.0 1.8 C 20 SPARE 30
27 PATIENT BED 3/4 3#12 20 10.0 1.2 B 20 SPARE 28
25 HEADWALL 3/4 3#12 20 15.0 1.8 A 20 SPARE 26
23 PATIENT BED 3/4 3#12 20 10.0 1.2 C 20 SPARE 24
21 HEADWALL 3/4 3#12 20 15.0 1.8 B 20 SPARE 22
19 PATIENT BED 3/4 3#12 20 10.0 1.2 A 20 SPARE 20
17 HEADWALL 3/4 3#12 20 15.0 1.8 C 0.5 4.5 20 3#12 3/4 RECEPTACLES 18
15 PATIENT BED 3/4 3#12 20 10.0 1.2 B 0.5 4.5 20 3#12 3/4 RECEPTACLES 16
13 HEADWALL 3/4 3#12 20 15.0 1.8 A 0.7 6.0 20 3#12 3/4 RECEPTACLES 14
11 PATIENT BED 3/4 3#12 20 10.0 1.2 C 0.7 6.0 20 3#12 3/4 RECEPTACLES 12
9 HEADWALL 3/4 3#12 20 15.0 1.8 B 0.7 6.0 20 3#12 3/4 RECEPTACLES 10
7 PATIENT BED 3/4 3#12 20 10.0 1.2 A 0.7 6.0 20 3#12 3/4 RECEPTACLES 8
5 HEADWALL 3/4 3#12 20 15.0 1.8 C 0.5 4.5 20 3#12 3/4 RECEPTACLES 6
3 PATIENT BED 3/4 3#12 20 10.0 1.2 B 0.9 7.5 20 3#12 3/4 RECEPTACLES 4
1 HEADWALL 3/4 3#12 20 15.0 1.8 A 1.5 12.5 20 3#12 3/4 DDC PANEL 2
NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.
CKT. COND WIRE BKR BKR WIRE COND CKT.
125 AMP MLO 208Y/120 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 1
EXISTING PANEL 1B.CR3.PI SCHEDULE
FIRST FLOOR
EXISTING TO REMAIN ELEC RM A261-A EXISTING TO REMAIN ELEC RM B229A-1
UL.1.1B
SEC 1
UL.1.1B
SEC 2
UL.4.1C
SEC 1
UL.4.1C
SEC 2
UL.4.1C
SEC 3
BASEMENT
ELEC B1XX-30
UL.2.1B
KITCHEN
BC.N.DLB
30KVA
480/277V- 208Y/120V
T
FIRST FLOOR
CLH.4.ICELH.4.IC
EXISTING TO REMAIN ELEC RM A261-A EXISTING TO REMAIN ELEC RM B229A-1
EXISTING TO BE RELOCATED FROM MED
ELEC RM B188C-1 TO NEW ELEC ROOM
B1XX-30
1B.CR2.P1
BC.CR2.PP1
125A 120V/208/
3PH 4W
CRITICAL
1B.CR3.P1
BC.CR3.DP1
125A 120V/208/
3PH 4W
CRITICAL
1B.CR3.PA
CRITICAL
1B.CR3.P2
CRITICAL
BC.EQ2.PA
EQUIP.LIFE
SAFETY
BC.EQ2.DPA
SECOND FLOOR
R.EQ2
BASEMENT
KITCHEN
CRITICAL
BRANCH
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
FINAL SUBMITTAL
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
POWER RISER DIAGRAM CORRECT PATIENT PRIVACY
DEFICIENCIES
GAINESVILLE, FL
E701
573-18-605
SBC TWG02-01-2021
NO SCALE
NORMAL POWER RISER DIAGRAM
NO SCALE
EMERGENCY POWER RISER DIAGRAM
1 PROVIDE A 150/3P BREAKER IN EXISTING PANEL TO SERVE NEW PANEL
SHOWN. EXISTING PANEL IS A SQUARE D I-LINE 480V/3Ø/4W/600A PANEL.
2 PROVIDE 4#1/0,#6G;1-1/2" CONDUIT. ROUTE FEEDER UP TO ABOVE CEILING
OF FIRST FLOOR THROUGH ELECTRICAL ROOM "A-2616A" AND THEN DOWN
CORRIDOR AND UP TO ROOF JUST BELOW NEW PANEL.
3 EXISTING FEEDER (4#1, #6G, 1-1/4"C) FROM PANEL BC.CR2.DP1 IN BASEMENT
TO BE EXTENDED TO NEW PANEL LOCATION FROM ABOVE CEILING IN
BASEMENT. REFERE TO DRAWINGS ED100 AND EP100 FOR EXISTING PANEL
LOCATION AND NEW PANEL LOCATION. PROVIDE JUNCTION BOX SIZED PER
N.E.C. TO SPLICE AND EXTEND CONDUCTORS AS NECESSARY.
4 EXISTING FEEDER (4#1, #6G, 1-1/4"C) FROM PANEL BC.CR3.DP1 IN BASEMENT
TO BE EXTENDED TO NEW PANEL LOCATION FROM ABOVE CEILING IN
BASEMENT. REFERE TO DRAWINGS ED100 AND EP100 FOR EXISTING PANEL
LOCATION. PROVIDE JUNCTION BOX SIZED PER N.E.C. TO SPLICE AND
EXTEND CONDUCTORS AS NECESSARY.
5 PROVIDE A 50/3P BREAKER IN EXISTING PANEL TO SERVE NEW PANEL
SHOWN. EXISTING PANEL IS A SQUARE D I-LINE 480V/3Ø/4W/400A PANEL.
6 PROVIDE 3#6, #10G, 1"C . ROUTE FEEDER UP TO ABOVE CEILING OF FIRST
FLOOR THROUGH ELECTRICAL ROOM "A-2616A" AND THEN OVER TO NEW
TRANSFORMER LOCATION.
7 PROVIDE 4#1,#6G;1-1/2" CONDUIT.
GENERAL NOTES
KEY NOTES
A. FOR ALL NEW FEEDER AND SERVICE LOADS, CONTRACTOR SHALL VERIFY
OR DEMONSTRATE AVAILABLE CAPACITY OF EXISTING INSTALLATIONS PER
N.E.C. 220.87 PRIOR TO SUBMITTING PRICING. CONTRACTOR SHALL NOTIFY
ENGINEER 30 DAYS PRIOR TO ANY WORK BEING DONE IF THERE IS NOT
ENOUGH CAPACITY ON THE SERVING EQUIPMENT TO SERVE THE NEW
LOAD(S) SHOWN SO THAT THE ENGINEER CAN WORK WITH THE
CONTRACTOR TO FIND AND ALTERNATE SOURCE TO SERVE TO NEW
LOAD(S) FROM.
CG
CG
FE
C
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
CG
FE
C
CG
CG
CG
CG
C G
C G
C G
C G
CGCG
CG
CRC
R
C R
NNN
N
N N N
N N N N
N
N N N N
N N
N N
N N
N N
N
N
N
CR
C R
S
F
V
F
N
N
N
N
N N N N
V
C R
C R
C R
C R
F
CR
N
S
S
S
S
S
SSSS
S
S
S
S
S
N
N
N
N
F
F
N
F V V
V
V
V
V
S
S
S
D D D
N
N
N N
S
34 3E5678910 5E5W7E7W10E10W 8w 6E6W
K
L
M
N
P
R
LN
LS
J
E
E E E
R R R
R
L L LL
E
R
R
R
R
ICU 1
B1XX-25
TLT 1
B1XX-33
ICU 2
B1XX-26
TLT 2
B1XX-34
ICU 3
B1XX-27
TLT 3
B1XX-35
ICU 4
BARIATRIC
B1XX-28
BARIATRIC
TLT 4
B1XX-36
EQUIP STG
B1XX-29
ELEC
B1XX-30
CORRIDOR
B1XX-8
ICU 5
B1XX-18
TLT 5
B1XX-37
ICU 6
B1XX-17
TLT 6
B1XX-38
ICU 7
ISOLATION
B1XX-14
TLT 7
B1XX-39
ICU 8
ISOLATION
B1XX-13
TLT 8
B1XX-42
STAFF TLT
B1XX-12
DATA
B1XX-11CONSULT
B1XX-10
HAC
B1XX-7
LOCKERS
B1XX-9
SOILED
UTILITY
B1XX-2
DR
WORKROOM
B1XX-1
STAFF
LOUNGE
B1XX-3
NURSE
MGR
B1XX-22
STAFF
WORKROOM
B1XX-19
MEDICATION
B1XX-23
NOURISH
B1XX-24
NURSE
STATION
B1XX-40
WC NICHE
B1XX-41
CONFERENCE
B209-1
WAITING
ROOM
B1XX-43CONSULT
B144-1
DRESSING
B1XX-9A
CLEAN
UTILITY
B1XX-20
STORAGE
B1XX-32
E
E
E
F
F
EY101
D
E
L
L
L
L
D D
MS
LINEN
C244D-1 E E
E
E
PROJECT AREA
KEY PLAN
NTS
TRUE
NORTH
PLAN
NORTH
5 5E5W
K
AC
Veterans Affairs
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
FINAL SUBMITTAL
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
PARTIAL FIRST FLOOR PLAN -
TELECOMMUNICATIONS
CORRECT PATIENT PRIVACY
DEFICIENCIES
GAINESVILLE, FL
EY101
573-18-605
SBC TWG02-01-2021
KEY NOTES
KEY PLAN
GRAPHIC SCALE(S)
NO SCALE
PARTIAL FIRST FLOOR PLAN - TELECOMMUNICATIONS
A. PROVIDE CAT 6 CABLE FOR ALL TELECOMMUNICATIONS CABLING. CABLE
MUST BE ROUTED TO EXISTING IT CLOSET AND TERMINATED IN PATCH
PANELS. PROVIDE JUNCTION BOX AT 18" A.F.F. UNLESS NOTED OR
DESCRIBED OTHERWISE. PROVIDE 1" CONDUIT FOR EACH DROP, FROM
JUNCTION BOX TO ABOVE CEILING WITH 90° ELBOW ROUTED TO NEAREST
CABLE TRAY.(SEE TELECOMMUNICATIONS OUTLETS DETAIL AND TYPICAL
OUTLET DETAILS ON SHEET EY501). COLOR CODE FOR COMMUNICATIONS
CABLES IS AS FOLLOWS: GREEN = DATA, WHITE = VOICE/WIFI, BLUE = CCTV.
B. FOR ALL SYSTEMS NOTED BELOW THE CONTRACTOR LISTED IS FOR BASIS
OF DESIGN, VERIFY WITH OWNER PRIOR TO BID TO VERIFY THEY ARE STILL
THE CONTRACTOR OF RECORD THAT IS SERVICING THE LISTED EQUIPMENT
FOR THE REST OF THIS CAMPUS.
GENERAL NOTES
A. PROVIDE A COMPLETE AND OPERATIONAL ACCESS CONTROL SYSTEM.
ACCESS CONTROL SYSTEM SHALL BE LENEL. PROVIDE BOXES AND CONDUIT
TO ABOVE CEILING CABLE TRAY FOR ALL DEVICES SHOWN ON THE PLANS.
THE INSTALLER SHALL PROVIDE ALL EQUIPMENT NECESSARY TO CONNECT
THIS SYSTEM TO THE NETWORK AND TIE IT INTO THE EXISTING SYSTEM
THAT IS SERVING THIS CAMPUS. SYSTEM DEVICES AND CARDS SHALL BE
COMPATIBLE WITH THE EXISTING CAMPUS SYSTEM.
B. SEE SHEET EY502 FOR ACCESS CONTROL DETAILS.
C. CONTRACTOR SHALL COORDINATE WITH DON COX AT "SECURITY 101" WHO
MAINTIANS THIS SYSTEMS . CONTACT INFORMATION FOR MR. COX IS
904-260-9101 EXT-116.
D. EXISTING ACCESS CONTROL DEVICES SERVED FROM RELOCATED PANEL
SHALL BE RE-SERVED FROM RELOCATED PANEL LOCATION SHOWN ON
DRAWING. A LIST OF DOORS SERVED FROM EXISTING CONTROLLER ARE
SHOWN IN A SCHEDULE ON THIS SHEET.
A. PROVIDE SECURITY CAMERAS AT LOCATIONS SHOWN. CAMERAS MUST BE
POE IP-BASED, FIXED, AND DOME TYPE UON. EXACT AIMING TO BE
COORDINATED WITH SITE SECURITY AND C.O.R. PRIOR TO INSTALLATION.
PROVIDE CAT-6 CABLE FROM EACH CAMERA TO RESPECTIVE 48-PORT
PATCH PANEL IN EXISTING IT ROOM. CROSS-CONNECTION TO BE
PERFORMED BY VA. EQUIPMENT MUST BE COMPATIBLE WITH EXISTING
SYSTEM. COORDINATE WITH SITE SECURITY AND PROVIDE A
COMPLETELY INTEGRATED AND OPERABLE SYSTEM. PROVIDE HARDWARE
AND SOFTWARE MODIFICATIONS AS REQUIRED.
A. PROVIDE A COMPLETE AND OPERATIONAL FIRE ALARM SYSTEM. FIRE ALARM
EQUIPMENT SHALL BE COMPATIBLE WITH EXISTING SYSTEM. PROVIDE
BOXES AND CONDUIT PAINTED RED FROM DEVICE TO DEVICE AS SHOWN ON
CONTRACTOR SHOP DRAWINGS. NEW FIRE ALARM EQUIPMENT SHALL BE
COMPATIBLE WITH THE EXISTING FIRE ALARM SYSTEM. NEW FIRE ALARM
PANELS SHALL BE PROVIDED WITH ALL NECESSARY EQUIPMENT TO
CONNECT TO THE NETWORK AND FIRE ALARM INSTALLER SHALL MAKE
CONNECTIONS TO EXISTING CAMPUS FIRE ALARM SYSTEM. UPDATE
SOFTWARE AS NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM.
A. PROVIDE A COMPLETE AND OPERATIONAL NURSE CALL SYSTEM. PROVIDE
JUNCTION BOXES, CONDUIT, AND ALL EQUIPMENT NECESSARY FOR A
COMPLETE AND OPERATIONAL SYSTEM. ALL DEVICES SHALL BE
COMPATIBLE WITH EXISTING ASCOM SYSTEM.
1/8" = 1' - 0" 0 5' 10' 15' 30'
A. PROVIDE A NEW FIBER SWITCH IN NEW SPECIAL SYSTEM RACK IN NEW DATA
B1XX-1 ROOM. PROVIDE NEW 12 STRAND FIBER TO SERVE NEW SWITCH
FROM ROOM "H303-1" APPROXIMATELY 500 FT AWAY FROM NEW RACK. ALL
NEW PATIENT MONITORING EQUIPMENT SHALL BE PROVIDED BY OWNER.
1 EXISTING IT ROOM. ALL DATA AND VOICE CABLES SHALL BE ROUTED TO
THIS SPACE.
2 EXISTING MATV SPLITTER BOX TO REMAIN AND BE USED FOR CONNECTION
OF NEW EQUIPMENT.
3 ALL LOW VOLTAGE CABLING IN THIS AREA SHALL BE ROUTED IN EXISTING
J-HOOK SYSTEM BACK TO EXISTING IT ROOM.
4 PROVIDE NEW MATV SPLITTER AND AMPLIFIER AT THIS LOCATION
CONNECT TO EXISTING SPLITTER REFERENCES IN NOTE 2 ON THIS SHEET.
ROUTE AN RG-11 CABLE FROM NEW SPLITTER TO EXISTING SPLITTER.
5 EXISTING G.E. ASCOM NURSE CALL HEAD END EQUIPMENT.
6 PROVIDE A WALL MOUNTED DATA RACK TO SUPPORT OWNER PROVIDED
SYSTEMS EQUIPMENT AND PATCH PANELS AS NECESSARY TO SUPPORT
ASK SYSTEM CABLES SERVING EQUIPMENT IN AREA OF RENOVATIONS.
7 PROVIDE A B-LINE "FLEXTRAY" FT4X12X10 SERIES CABLE TRAY OR
APPROVED EQUAL. PROVIDE TRAPEZE SUPPORT CLIPS AND 3/8" THREADED
ROD ON BOTH SIDES OF TRAY TO STRUCTURE ABOVE PER
MANUFACTURER'S RECOMMENDATIONS. PROVIDE A #6 COPPER GROUND
CONDUCTOR FROM THE DATA CLOSET GROUND PLATE TO EACH SECTION
OF TRAY AND EVERY CONDUIT ROUTED TO TRAY.
8 REFER TO EP101 FOR FLOOR BOX AT THIS LOCATION. DATA CABLES SHALL
BE ROUTED THROUGH FLOOR BOX.
9 RELOCATED ACCESS PANEL. REFER TO NOTE 6, SHEET ED100 FOR
CURRENT LOCATION OF THIS PANEL.
1/4" = 1'-0"
ENLARGED PLAN -
DATA ROOM B1XX-1
IRM GV MC 1st Flr. C263A-1
GV MC SICU Rear Entrance (staff entrance)
GV MC SICU Front Entrance
GV MC Radiology Res. Therapy Blood Lab C248-1
GV MC Radiology Viewing Room D337A
GV MC Radiology Procedure Room D338-1 Rear
GV MC Radiology Procedure Room D338-1 Front
GV MC Radiology Film Storage D337-1
GV MC Radiology CT3
GV MC Radiology CT2 East Entrance
GV MC Pathology Lab C264-1
GV MC OR Test Reader
GV MC OR Stairwell
GV MC OR SICU Hall
GV MC OR Implant Storage Rm
GV MC OR Exterior Entrance 1st Flr. OR/SICU
GV MC OR Entrance from Radiology
GV MC OR Anesthesiology Workroom Side Entrance E178-1 South
GV MC OR Anesthesiology Workroom Front Entrance E178-1 East
GV MC OR ABG 2nd East Entrance
GV MC OR 1st Flr. Main/Front Entrance
GV MC ENTRANCE -- 1st Flr. South SICU/CTICU
GV MC ENTRANCE -- 1st Flr. South Chaplian's Office
GV MC CTICU Rear Visitor Enrance
GV MC CTICU Front Employee Entrance
GV MC CTICU B183-1 Storage
GV MC Cath Lab C256-1
GV MC Cath Lab C254
GV MC Cath Lab C246-1 (2) back entrance
GV MC Cath Lab C246-1
GV MC Cath Lab B206-1
READERS TO BE RE-SERVED FROM RELOCATED ACCESS CONTROL
PANEL LOCATION
ACCESS CONTROL NOTES
CCTV NOTES
FIRE ALARM NOTES
NURSE CALL NOTES
PATIENT MONITOR NOTES
1 ADDENDUM 1 8/23/21
| Sheets |
| E601 - SCHEDULES |
| E602 - SCHEDULES |
| E701 - POWER RISER DIAGRAM |
| EY101 - PARTIAL FIRST FLOOR PLAN - TELECOMMUNICATIONS |
File details come from the government source that posted it. Updated .