36C248-21-R-0139-573-18-605 Correct Patient Privacy Deficiencies_Addendum Drawings.pdf

PDF 1018 KB Posted

Attached to
Z1DA--NRM Tier 2 (PROJ: 573-18-605) BB - Correct Patient Privacy Deficiencies
Solicitation number
36C24821R0139
Issued by

About this file

This pre-solicitation announcement is for a construction project to expand and renovate the Cardiothoracic Intensive Care Unit at the Malcolm Randall VA Medical Center in Gainesville, Florida. The project includes increasing capacity and eliminating deficiencies to improve functionality, patient access, and privacy. Bid alternates will deduct switchable privacy glass and replace it with either ceiling-mounted curtain tracks or clear tempered glass to ensure the contract is awarded within budget. The estimated construction period is 365 days. The solicitation will be issued on July 28, 2021 via beta.SAM.gov for a firm fixed-price construction contract to be awarded within 120 days. The North American Industry Classification System code is 236220 and the small business size standard is $39.5 million. Questions must be submitted in writing to the contracting officer by the specified due date.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Veterans Affairs

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

FINAL SUBMITTAL

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

SCHEDULES CORRECT PATIENT PRIVACY

DEFICIENCIES

GAINESVILLE, FL

E601

573-18-605

SBC SJB02-01-2021

TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA

TOTALS (CONN. KVA) KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP KVA KVA KVA KVA 1.00 KVA

RECEPTACLES KVA KVA KVA KVA NEC KVA

LIGHTING KVA KVA KVA KVA 1.25 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

BREAKERS IN SAME CIRCUIT LOCATION.

FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW

THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING

FED FROM PANEL BC.N.DP1

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: B: C:

29 SPACE C SPACE 30

27 EXISTING LOAD 20 B 28

25 A 26

23 EXISTING LOAD C EXISTING LOAD 24

21 EXISTING LOAD 20 B 20 EXISTING LOAD 22

19 EXISTING LOAD 20 A 20 EXISTING LOAD 20

17 EXISTING LOAD 20 C 20 EXISTING LOAD 18

15 EXISTING LOAD 20 B 20 EXISTING LOAD 16

13 EXISTING LOAD 20 A 20 EXISTING LOAD 14

11 EXISTING LOAD 20 C 20 EXISTING LOAD 12

9 EXISTING LOAD 20 B 20 EXISTING LOAD 10

7 EXISTING LOAD 20 A 20 EXISTING LOAD 8

5 EXISTING LOAD 20 C 20 EXISTING LOAD 6

3 EXISTING LOAD 20 B 20 EXISTING LOAD 4

1 EXISTING LOAD 20 A 20 EXISTING LOAD 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1

EXISTING PANEL UL-4-IC-SEC 1 SCHEDULE

TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA

TOTALS (CONN. KVA) KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP KVA KVA KVA KVA 1.00 KVA

RECEPTACLES KVA KVA KVA KVA NEC KVA

LIGHTING KVA KVA KVA KVA 1.25 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

BREAKERS IN SAME CIRCUIT LOCATION.

FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW

THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING

FED FROM PANEL BC.N.DP1

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: B: C:

29 SPACE C SPACE 30

27 EXISTING LOAD 3/4 12 20 B 20 EXISTING LOAD 28

25 EXISTING LOAD 3/4 12 20 A 20 EXISTING LOAD 26

23 EXISTING LOAD 3/4 12 20 C 20 EXISTING LOAD 24

21 EXISTING LOAD 3/4 12 20 B 20 EXISTING LOAD 22

19 EXISTING LOAD 3/4 12 20 A 20 EXISTING LOAD 20

17 EXISTING LOAD 3/4 12 20 C 20 EXISTING LOAD 18

15 EXISTING LOAD 3/4 12 20 B 20 EXISTING LOAD 16

13 A 20 EXISTING LOAD 14

11 EXISTING LOAD C 20 EXISTING LOAD 12

9 SPACE B 20 EXISTING LOAD 10

7 EXISTING LOAD 3/4 12 20 A 20 EXISTING LOAD 8

5 EXISTING LOAD 3/4 12 20 C 20 EXISTING LOAD 6

3 EXISTING LOAD 3/4 12 20 B 20 EXISTING LOAD 4

1 EXISTING LOAD 3/4 12 20 A 20 EXISTING LOAD 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1

EXISTING PANEL UL-4-IC-SEC 2 SCHEDULE

TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA

TOTALS (CONN. KVA) KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP KVA KVA KVA KVA 1.00 KVA

RECEPTACLES KVA KVA KVA KVA NEC KVA

LIGHTING KVA KVA KVA KVA 1.25 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

BREAKERS IN SAME CIRCUIT LOCATION.

FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW

THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING

FED FROM PANEL BC.N.DP1

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: B: C:

29 SPACE C 20 EXISTING LOAD 30

27 EXISTING LOAD 20 B 20 EXISTING LOAD 28

25 A 20 EXISTING LOAD 26

23 C 20 EXISTING LOAD 24

21 EXISTING LOAD 20 B 20 EXISTING LOAD 22

19 EXISTING LOAD 20 A 20 EXISTING LOAD 20

17 EXISTING LOAD 20 C 20 EXISTING LOAD 18

15 EXISTING LOAD 20 B 20 EXISTING LOAD 16

13 EXISTING LOAD 20 A 20 EXISTING LOAD 14

11 EXISTING LOAD 20 C 20 EXISTING LOAD 12

9 B 20 EXISTING LOAD 10

7 EXISTING LOAD 30 A 20 EXISTING LOAD 8

5 C 6

3 B 20 EXISTING LOAD 4

1 MAIN BREAKER 100 A 20 EXISTING LOAD 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1

EXISTING PANEL UL-4-IC-SEC 3 SCHEDULE

TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA

TOTALS (CONN. KVA) KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP KVA KVA KVA KVA 1.00 KVA

RECEPTACLES KVA KVA KVA KVA NEC KVA

LIGHTING KVA KVA KVA KVA 1.25 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

BREAKERS IN SAME CIRCUIT LOCATION.

FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW

THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING

FED FROM PANEL BC.N.DP2

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: B: C:

35 C 36

33 B 34

31 EXISTING LOAD A 20 32

29 EXISTING LOAD 20 C 20 30

27 EXISTING LOAD 20 B 20 28

25 EXISTING LOAD 20 A 20 26

23 EXISTING LOAD 20 C 20 24

21 EXISTING LOAD 20 B 20 22

19 EXISTING LOAD 20 A 20 20

17 EXISTING LOAD 20 C 20 18

15 EXISTING LOAD 20 B 20 16

13 EXISTING LOAD 20 A 20 14

11 EXISTING LOAD 20 C 20 12

9 EXISTING LOAD 20 B 20 10

7 EXISTING LOAD 20 A 20 8

5 EXISTING LOAD 20 C 20 6

3 EXISTING LOAD 20 B 20 4

1 EXISTING LOAD 20 A 20 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

175 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1

EXISTING PANEL UL.1.1B.SEC 1 SCHEDULE

TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA

TOTALS (CONN. KVA) KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP KVA KVA KVA KVA 1.00 KVA

RECEPTACLES KVA KVA KVA KVA NEC KVA

LIGHTING KVA KVA KVA KVA 1.25 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

BREAKERS IN SAME CIRCUIT LOCATION.

FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW

THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING

FED FROM PANEL BC.N.DP2

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: B: C:

35 EXISTING LOAD 3/4 12 20 C 36

33 EXISTING LOAD 3/4 12 20 B EXISTING LOAD 34

31 EXISTING LOAD 3/4 12 20 A 20 12 3/4 EXISTING LOAD 32

29 EXISTING LOAD 3/4 12 20 C 30

27 B 28

25 EXISTING LOAD A EXISTING LOAD 26

23 EXISTING LOAD 3/4 12 20 C 20 12 3/4 EXISTING LOAD 24

21 EXISTING LOAD 3/4 12 20 B 20 12 3/4 EXISTING LOAD 22

19 EXISTING LOAD 3/4 12 20 A 20 12 3/4 EXISTING LOAD 20

17 EXISTING LOAD 3/4 12 20 C 20 12 3/4 EXISTING LOAD 18

15 EXISTING LOAD 3/4 12 20 B 20 12 3/4 EXISTING LOAD 16

13 A 20 12 3/4 EXISTING LOAD 14

11 EXISTING LOAD C 20 12 3/4 EXISTING LOAD 12

9 B 20 12 3/4 EXISTING LOAD 10

7 EXISTING LOAD A 20 12 3/4 EXISTING LOAD 8

5 EXISTING LOAD 3/4 12 20 C 20 12 3/4 EXISTING LOAD 6

3 EXISTING LOAD 3/4 12 20 B 20 12 3/4 EXISTING LOAD 4

1 EXISTING LOAD 3/4 12 20 A 20 12 3/4 EXISTING LOAD 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

175 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1

EXISTING PANEL UL.1.1B.SEC 2 SCHEDULE

TOTALS (CONN. AMPS + 20%) 73.0 AMPS AMPS AMPS 73.0 AMPS 53.2 AMPS

TOTALS (CONN. AMPS) 60.8 AMPS AMPS AMPS 60.8 AMPS 44.3 AMPS

TOTALS (CONN. KVA + 20%) 26.3 KVA KVA KVA 26.3 KVA 19.2 KVA

TOTALS (CONN. KVA) 21.9 KVA KVA KVA 21.9 KVA 16.0 KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP KVA KVA KVA KVA 1.00 KVA

RECEPTACLES 21.9 KVA KVA KVA 21.9 KVA NEC 16.0 KVA

LIGHTING KVA KVA KVA KVA 1.25 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: 62.0 B: 60.7 C: 60.0

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: 62.0 B: 60.7 C: 60.0

41 RECEPTACLES 3/4 3#12 20 7.5 0.9 C 20 SPARE 42

39 RECEPTACLES 3/4 3#12 20 7.5 0.9 B 20 SPARE 40

37 RECEPTACLES 3/4 3#12 20 4.5 0.5 A 20 SPARE 38

35 RECEPTACLES 3/4 3#12 20 7.5 0.9 C 20 SPARE 36

33 RECEPTACLES 3/4 3#12 20 4.5 0.5 B 20 SPARE 34

31 RECEPTACLES 3/4 3#12 20 4.5 0.5 A 20 SPARE 32

29 RECEPTACLES 3/4 3#12 20 7.5 0.9 C 20 SPARE 30

27 RECEPTACLES 3/4 3#12 20 3.0 0.4 B 20 SPARE 28

25 RECEPTACLES 3/4 3#12 20 3.0 0.4 A 20 SPARE 26

23 RECEPTACLES 3/4 3#12 20 4.5 0.5 C 20 SPARE 24

21 RECEPTACLES 3/4 3#12 20 4.5 0.5 B 0.8 6.7 20 3#12 3/4 RECEPTACLES 22

19 RECEPTACLES 3/4 3#12 20 9.0 1.1 A 0.5 4.0 20 3#10 3/4 RECEPTACLES 20

17 RECEPTACLES 3/4 3#12 20 6.0 0.7 C 0.9 7.5 20 3#12 3/4 RECEPTACLES 18

15 RECEPTACLES 3/4 3#12 20 6.0 0.7 B 1.1 9.0 20 3#12 3/4 RECEPTACLES 16

13 RECEPTACLES 3/4 3#12 20 1.5 0.2 A 1.1 9.0 20 3#12 3/4 RECEPTACLES 14

11 RECEPTACLES 3/4 3#12 20 1.5 0.2 C 0.5 4.5 20 3#12 3/4 RECEPTACLES 12

9 RECEPTACLES 3/4 3#12 20 4.5 0.5 B 0.5 4.5 20 3#12 3/4 RECEPTACLES 10

7 RECEPTACLES 3/4 3#12 20 6.0 0.7 A 0.7 6.0 20 3#12 3/4 RECEPTACLES 8

5 RECEPTACLES 3/4 3#12 20 9.0 1.1 C 0.5 4.5 20 3#12 3/4 RECEPTACLES 6

3 RECEPTACLES 3/4 3#12 20 4.5 0.5 B 0.7 6.0 20 3#12 3/4 RECEPTACLES 4

1 RECEPTACLES 3/4 3#12 20 10.0 1.2 A 0.5 4.5 20 3#12 3/4 RECEPTACLES 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

100 AMP MCB 208Y/120 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 1

PANEL UL.2.1B SCHEDULE

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION MANUFACTURER MODEL NO.

LAMP

TYPE

VOLTAGE WATTS

MOUNTING

NOTES

COUNTTYPE HEIGHT

LED 277 V 44 W 4

A 2X4 LED TROFFER, NOMINAL 5000 LUMENS OUTPUT, 4000K CCT, MIN 90 CRI, FRAMED WHITE

ENAMEL STEEL HOUSING, FORMED WHITE STEEL OUTER REFLECTOR, EXTRUDED ALUMINUM

HEATSINK, FROSTED WHITE PLASTIC ENCLOSURE.

CREE LIGHTING CR24-50L-40K-S LED 120 V 50 W CEILING

RECESSED

N/A 57

B 6" LED DOWNLIGHT, NOMINAL 2000 LUMENS OUPUT, 4000K CCT, MIN 80 CRI, 6 IN CLEAR TRIM, SELF FLANGED, WIDE DISTRIBUTION, SEMI-SPECULAR FINISH, 0-10V ELECTRONIC DRIVER

EVO LIGHTING EVO-40/20-6AR-WD-LSS-277-EZ10 LED 120 V 23 W CEILING

RECESSED

N/A 57

C 1X4 LED TROFFER, NOMINAL 3100 LUMENS OUTPUT, 4000K CCT, MIN 90 CRI, FRAMED WHITE

ENAMEL STEEL HOUSING, FORMED WHITE STEEL OUTER REFLECTOR, EXTRUDED ALUMINUM

HEATSINK, FROSTED WHITE PLASTIC ENCLOSURE

CREE LIGHTING CR14-31L-40K LED 120 V 34 W PENDANT 7' 0" AFF UON 3

D 2X2 LED TROFFER, NOMINAL 3200 LUMENS OUTPUT, 4000K CCT, MIN 90 CRI, FRAMED WHITE

ENAMEL STEEL HOUSING, FORMED WHITE STEEL OUTER REFLECTOR, EXTRUDED ALUMINUM

HEATSINK, FROSTED WHITE PLASTIC ENCLOSURE

CREE LIGHTING CR22-32L-40K LED 120 V 32 W CEILING

RECESSED

N/A 18

E COMPACT RECESSED WHITE LED NIGHTLIGHT, ANTIMICROBIAL WHITE FACEPLATE, WITH

PHOTOCELL

COOPER INDUSTRIES MCL-UNV-AMW-PHC-TP LED 5 W WALL

RECESSED

1'-6" 8

F 2' LED CONTEMPORARY VANITY SQUARE, NOMINAL 1300 LUMENS OUTPUT, 4000K CCT, MIN 90

CRI, EXTRUDED ACRYLIC DIFFUSER, BRUSHED NICKEL FINISH

LITHONIA LIGHTING FMVCSL-24IN-MVOLT-40K-90CRI-BN LED 120 V 18 W WALL ABOVE

MIRROR

7' 0" AFF UON 1

G SKYVIEW DIGITAL CINEMA, VIRTUAL SKYLIGHT SKY FACTORY 5530 LED 120 V 800 W CEILING

RECESSED

N/A 4

H LED STRIP LIGHT LITHONIA CLX-L48-5000LM-SEF-RDL-MVOLT-GZ10-35

K-80CRI

LED 120 V 23 W SURFACE 2

X1 EXIT LIGHT LITHONIA LE-S-R LED 120 V 1 W UNIVERSAL N/A 6

1 ADDENDUM 1 8/23/21

8/24/2l

Veterans Affairs

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

FINAL SUBMITTAL

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

SCHEDULES CORRECT PATIENT PRIVACY

DEFICIENCIES

GAINESVILLE, FL

E602

573-18-605

SBC TWG02-01-2021

TOTALS (CONN. AMPS + 20%) 7.0 AMPS AMPS AMPS 7.0 AMPS 8.8 AMPS

TOTALS (CONN. AMPS) 5.9 AMPS AMPS AMPS 5.9 AMPS 7.3 AMPS

TOTALS (CONN. KVA + 20%) 5.8 KVA KVA KVA 5.8 KVA 7.3 KVA

TOTALS (CONN. KVA) 4.9 KVA KVA KVA 4.9 KVA 6.1 KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP KVA KVA KVA KVA 1.00 KVA

RECEPTACLES KVA KVA KVA KVA NEC KVA

LIGHTING 4.9 KVA KVA KVA 4.9 KVA 1.25 6.1 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

1. USE 20A SPARE BREAKER.

BREAKERS IN SAME CIRCUIT LOCATION.

FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW

THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING

FED FROM PANEL BC.LS.DLA

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: 8.2 C: 9.4

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: B: 8.2 C: 9.4

11 CORRIDOR LIGHTS (NOTE 1) 3/4 12 20 4.8 1.3 C SPACE 12

9 CORRIDOR LIGHTS 20 B SPACE 10

7 CORRIDOR LIGHTS 20 A SPACE 8

5 LIGHTS GRAPHICS LAB 20 C 1.3 4.6 20 12 3/4 INTERIOR LIGHTS (NOTE 1) 6

3 CORRIDOR LIGHTS 20 B 2.3 8.2 20 12 3/4 INTERIOR LIGHTS (NOTE 1) 4

1 CORRIDOR LIGHTS 20 A SPACE 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

30 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1

EXISTING PANEL ELH-4-1C SCHEDULE

TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA

TOTALS (CONN. KVA) KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP KVA KVA KVA KVA 1.00 KVA

RECEPTACLES KVA KVA KVA KVA NEC KVA

LIGHTING KVA KVA KVA KVA 1.25 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

BREAKERS IN SAME CIRCUIT LOCATION.

FEEDER TO SERVE NEW PANEL AND ALL BRANCH CIRCUITS SHALL BE ROUTED TO NEW

THIS PANEL SHALL BE REPLACED ONE FOR ONE IN CURRENT LOCATION. UTILIZE EXISTING

FED FROM PANEL BC.CR2.DLB

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: B: C:

19 SPACE A SPACE 20

17 EXISTING LOAD 20 C 20 12 3/4 EXISTING LOAD 18

15 EXISTING LOAD 20 B 20 12 3/4 EXISTING LOAD 16

13 EXISTING LOAD 20 A 20 12 3/4 EXISTING LOAD 14

11 EXISTING LOAD 20 C 12

9 EXISTING LOAD 20 B EXISTING LOAD 10

7 EXISTING LOAD 20 A 20 12 3/4 EXISTING LOAD 8

5 EXISTING LOAD 20 C 20 12 3/4 EXISTING LOAD 6

3 EXISTING LOAD 20 B 20 12 3/4 EXISTING LOAD 4

1 EXISTING LOAD 20 A 20 12 3/4 EXISTING LOAD 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

90 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 10 KAIC SURFACE MOUNTED NEMA 1

EXISTING PANEL CLH-4-IC SCHEDULE

TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA

TOTALS (CONN. KVA) KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP KVA KVA KVA KVA 1.00 KVA

RECEPTACLES KVA KVA KVA KVA NEC KVA

LIGHTING KVA KVA KVA KVA 1.25 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

FED FROM PANEL BC.CR3.DP1

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: B: C:

29 SPACE C SPACE 30

27 SPACE B SPACE 28

25 SPACE A SPACE 26

23 SPACE C SPACE 24

21 SPACE B SPACE 22

19 SPACE A 20 EXISTING LOAD 20

17 SPACE C 20 EXISTING LOAD 18

15 EXISTING LOAD 20 B 20 EXISTING LOAD 16

13 EXISTING LOAD 20 A SPACE 14

11 EXISTING LOAD 20 C SPACE 12

9 EXISTING LOAD 20 B 20 EXISTING LOAD 10

7 EXISTING LOAD 20 A 20 EXISTING LOAD 8

5 EXISTING LOAD 20 C 6

3 EXISTING LOAD 20 B 20 EXISTING LOAD 4

1 EXISTING LOAD 20 A 20 EXISTING LOAD 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

100 AMP MLO 208Y/120 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 1

EXISTING PANEL 1B.CR3.P2 SCHEDULE

TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA

TOTALS (CONN. KVA) KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP KVA KVA KVA KVA 1.00 KVA

RECEPTACLES KVA KVA KVA KVA NEC KVA

LIGHTING KVA KVA KVA KVA 1.25 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

FED FROM PANEL BC.CR3.DPB

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: B: C:

29 SPACE C SPACE 30

27 SPACE B SPACE 28

25 SPACE A SPACE 26

23 SPACE C SPACE 24

21 SPACE B SPACE 22

19 EXISTING LOAD 20 A 20 EXSITING LOAD 20

17 EXISTING LOAD 20 C 20 EXSITING LOAD 18

15 EXISTING LOAD 20 B 20 EXSITING LOAD 16

13 EXISTING LOAD 20 A 20 EXSITING LOAD 14

11 EXISTING LOAD 20 C 20 EXSITING LOAD 12

9 EXISTING LOAD 20 B 20 EXSITING LOAD 10

7 EXISTING LOAD 20 A 20 EXSITING LOAD 8

5 EXISTING LOAD 20 C 20 EXSITING LOAD 6

3 EXISTING LOAD 20 B 20 EXSITING LOAD 4

1 EXISTING LOAD 20 A 20 EXSITING LOAD 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

100 AMP MLO 480Y/277 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 1

EXISTING PANEL 1B.CR3.PA SCHEDULE

TOTALS (CONN. AMPS + 20%) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. AMPS) AMPS AMPS AMPS AMPS AMPS

TOTALS (CONN. KVA + 20%) KVA KVA KVA KVA KVA

TOTALS (CONN. KVA) KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP KVA KVA KVA KVA 1.00 KVA

RECEPTACLES KVA KVA KVA KVA NEC KVA

LIGHTING KVA KVA KVA KVA 1.25 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

FED FROM PANEL BC.EQ2.PA

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: B: C:

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: B: C:

47 C 48

45 B 46

43 A SPACE 44

SUBFEED BREAKERS

41 SPACE C SPACE 42

39 SPACE B SPACE 40

37 SPACE A SPACE 38

35 SPACE C SPACE 36

33 SPACE B SPACE 34

31 SPACE A SPACE 32

29 C 30

27 B 28

25 EXISTING LOAD A EXISTING LOAD 26

23 C 24

21 B 22

19 EXISTING LOAD A EXISTING LOAD 20

17 C 18

15 B 16

13 EXISTING LOAD A EXISTING LOAD 14

11 C 12

9 B 10

7 EXISTING LOAD A EXISTING LOAD 8

5 C 6

3 B 4

1 EXISTING LOAD A EXISTING LOAD 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

400 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 1

EXISTING PANEL BC.EQ2.PA SCHEDULE

TOTALS (CONN. AMPS + 20%) 65.3 AMPS AMPS AMPS 65.3 AMPS 65.3 AMPS

TOTALS (CONN. AMPS) 54.4 AMPS AMPS AMPS 54.4 AMPS 54.4 AMPS

TOTALS (CONN. KVA + 20%) 54.3 KVA KVA KVA 54.3 KVA 54.3 KVA

TOTALS (CONN. KVA) 45.3 KVA KVA KVA 45.3 KVA 45.3 KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP 45.3 KVA KVA KVA 45.3 KVA 1.00 45.3 KVA

RECEPTACLES KVA KVA KVA KVA NEC KVA

LIGHTING KVA KVA KVA KVA 1.25 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: 61.1 B: 51.1 C: 51.1

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: 61.1 B: 51.1 C: 51.1

41 C 42 39 B 40

37 A 38

35 C 36

33 B 34

31 A 32 29 7.6 2.1 C 30

27 7.6 2.1 B 28

25 HWP -1 & 2 3/4 4#12 20 7.6 2.1 A 26

23 4.0 1.1 C 24

21 4.0 1.1 B 22

19 EF-101 3/4 4#12 20 4.0 1.1 A 0.3 1.1 20

17 12.3 3.4 C 0.3 1.1 18

15 12.3 3.4 B 0.3 1.1 20 4#12 3/4 EF-31 16

13 EF-147 & 148 3/4 4#12 20 12.3 3.4 A 2.8 10.0 20 3#12 3/4 AHU-7 LTS,REC AND UV LTS/HUM-1 14

11 11.0 3.1 C 0.6 2.1 12

9 11.0 3.1 B 0.6 2.1 10

7 SF-2 - AHU-7 3/4 4#12 20 11.0 3.1 A 0.6 2.1 20 4#12 3/4 RF-2 - AHU-7 8

5 11.0 3.1 C 0.6 2.1 6

3 11.0 3.1 B 0.6 2.1 4

1 SF-1 - AHU-7 3/4 4#12 20 11.0 3.1 A 0.6 2.1 20 4#12 3/4 RF-1 - AHU-7 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

150 AMP MCB 480Y/277 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 3R

NEW PANEL R.EQ2 SCHEDULE

TOTALS (CONN. AMPS + 20%) 173.9 AMPS AMPS AMPS 173.9 AMPS 115.4 AMPS

TOTALS (CONN. AMPS) 144.9 AMPS AMPS AMPS 144.9 AMPS 96.2 AMPS

TOTALS (CONN. KVA + 20%) 62.6 KVA KVA KVA 62.6 KVA 41.6 KVA

TOTALS (CONN. KVA) 52.2 KVA KVA KVA 52.2 KVA 34.7 KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP KVA KVA KVA KVA 1.00 KVA

RECEPTACLES 47.5 KVA KVA KVA 47.5 KVA NEC 28.7 KVA

LIGHTING 4.7 KVA KVA KVA 4.7 KVA 1.25 5.9 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

FED FROM PANEL BC.CR2.DP1

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: 126.8 B: 142.7 C: 165.6

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: 126.8 B: 142.7 C: 165.6

41 RECEPTACLES 3/4 3#12 20 15.0 1.8 C 20 SPARE 42

39 RECEPTACLES 3/4 3#12 20 6.0 0.7 B 20 SPARE 40

37 RECEPTACLES 3/4 3#12 20 10.8 1.3 A 0.3 2.5 20 3/4 3#12 LIGHTING AND RECEPTACLE 38

35 RECEPTACLES 3/4 3#12 20 14.2 1.7 C 1.8 15.0 20 3/4 3#12 HEADWALL 36

33 RECEPTACLES 3/4 3#12 20 15.0 1.8 B 1.8 15.0 20 3/4 3#12 HEADWALL 34

31 RECEPTACLES 3/4 3#12 20 1.5 0.2 A 1.8 15.0 20 3/4 3#12 HEADWALL 32

29 RECEPTACLES 3/4 3#12 20 3.0 0.4 C 1.8 15.0 20 3/4 3#12 HEADWALL 30

27 RECEPTACLES 3/4 3#12 20 3.0 0.4 B 1.8 15.0 20 3/4 3#12 HEADWALL 28

25 RECEPTACLES 3/4 3#12 20 4.5 0.5 A 1.8 15.0 20 3/4 3#12 HEADWALL 26

23 RECEPTACLES 3/4 3#12 20 15.0 1.8 C 1.8 15.0 20 3/4 3#12 HEADWALL 24

21 RECEPTACLES 3/4 3#12 20 15.0 1.8 B 1.8 15.0 20 3/4 3#12 HEADWALL 22

19 RECEPTACLES 3/4 3#12 20 12.5 1.5 A 0.5 4.5 20 3/4 3#12 RECEPTACLES 20

17 RECEPTACLES 3/4 3#12 20 15.0 1.8 C 0.7 6.0 20 3/4 3#12 RECEPTACLES 18

15 RECEPTACLES 3/4 3#12 20 7.5 0.9 B 1.8 15.0 20 3/4 3#12 RECEPTACLES 16

13 RECEPTACLES 3/4 3#12 20 10.0 1.2 A 0.5 4.5 20 3/4 3#12 RECEPTACLES 14

11 RECEPTACLES 3/4 3#12 20 15.0 1.8 C 1.2 11.5 RECEPTACLES 12

9 LIGHTING 3/4 3#12 20 8.0 1.0 B 1.2 11.5 20 3/4 4#12 RECEPTACLES 10

7 LIGHTING 3/4 3#12 20 8.1 1.0 A 1.8 15.0 20 3/4 3#12 RECEPTACLES 8

5 LIGHTING 3/4 3#12 20 12.4 1.5 C 1.8 15.0 20 3/4 3#12 RECEPTACLES 6

3 LIGHTING 3/4 3#12 20 3.2 0.4 B 1.8 15.0 20 3/4 3#12 RECEPTACLES 4

1 LIGHTING 3/4 3#12 20 7.8 0.9 A 1.8 15.0 20 3/4 3#12 RECEPTACLES 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

125 AMP MLO 208Y/120 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 1

EXISTING PANEL 1B.CR2.PI SCHEDULE

TOTALS (CONN. AMPS + 20%) 102.9 AMPS AMPS AMPS 102.9 AMPS 68.1 AMPS

TOTALS (CONN. AMPS) 85.8 AMPS AMPS AMPS 85.8 AMPS 56.8 AMPS

TOTALS (CONN. KVA + 20%) 37.1 KVA KVA KVA 37.1 KVA 24.5 KVA

TOTALS (CONN. KVA) 30.9 KVA KVA KVA 30.9 KVA 20.5 KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

KVA KVA KVA KVA KVA

ELEVATOR KVA KVA KVA KVA 0.80 KVA

MISCELLANEOUS KVA KVA KVA KVA 1.00 KVA

ELECTRIC HEAT KVA KVA KVA KVA 1.25 KVA

MECH EQUIP KVA KVA KVA KVA 1.00 KVA

RECEPTACLES 30.9 KVA KVA KVA 30.9 KVA NEC 20.5 KVA

LIGHTING KVA KVA KVA KVA 1.25 KVA

LOAD DESCRIPTION CONN LOAD CONN LOAD CONN LOAD LOAD MULT. DEMAND

PANEL SUBFEED FEEDTHRU TOTAL D.F. TOTAL KVA

FED FROM PANEL BC.CR3.DP1

PANELBOARD OPTIONS: PANELBOARD NOTES:

TOTAL AMPS (CONN. LOAD + FEED-THRU) A: 99.5 B: 78.0 C: 80.0

TOTAL AMPS (FEEDTHRU) A: B: C:

TOTAL AMPS (CONN. LOAD) A: 99.5 B: 78.0 C: 80.0

41 SPARE 20 C 20 SPARE 42

39 SPARE 20 B 20 SPARE 40

37 SPARE 20 A 20 SPARE 38

35 SPARE 20 C 20 SPARE 36

33 SPARE 20 B 20 SPARE 34

31 PATIENT BED 3/4 3#12 20 10.0 1.2 A 20 SPARE 32

29 HEADWALL 3/4 3#12 20 15.0 1.8 C 20 SPARE 30

27 PATIENT BED 3/4 3#12 20 10.0 1.2 B 20 SPARE 28

25 HEADWALL 3/4 3#12 20 15.0 1.8 A 20 SPARE 26

23 PATIENT BED 3/4 3#12 20 10.0 1.2 C 20 SPARE 24

21 HEADWALL 3/4 3#12 20 15.0 1.8 B 20 SPARE 22

19 PATIENT BED 3/4 3#12 20 10.0 1.2 A 20 SPARE 20

17 HEADWALL 3/4 3#12 20 15.0 1.8 C 0.5 4.5 20 3#12 3/4 RECEPTACLES 18

15 PATIENT BED 3/4 3#12 20 10.0 1.2 B 0.5 4.5 20 3#12 3/4 RECEPTACLES 16

13 HEADWALL 3/4 3#12 20 15.0 1.8 A 0.7 6.0 20 3#12 3/4 RECEPTACLES 14

11 PATIENT BED 3/4 3#12 20 10.0 1.2 C 0.7 6.0 20 3#12 3/4 RECEPTACLES 12

9 HEADWALL 3/4 3#12 20 15.0 1.8 B 0.7 6.0 20 3#12 3/4 RECEPTACLES 10

7 PATIENT BED 3/4 3#12 20 10.0 1.2 A 0.7 6.0 20 3#12 3/4 RECEPTACLES 8

5 HEADWALL 3/4 3#12 20 15.0 1.8 C 0.5 4.5 20 3#12 3/4 RECEPTACLES 6

3 PATIENT BED 3/4 3#12 20 10.0 1.2 B 0.9 7.5 20 3#12 3/4 RECEPTACLES 4

1 HEADWALL 3/4 3#12 20 15.0 1.8 A 1.5 12.5 20 3#12 3/4 DDC PANEL 2

NO. LOAD DESCRIPTION SIZE SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE SIZE LOAD DESCRIPTION NO.

CKT. COND WIRE BKR BKR WIRE COND CKT.

125 AMP MLO 208Y/120 VOLTS 3PH, 4W, SN MIN. 22 KAIC SURFACE MOUNTED NEMA 1

EXISTING PANEL 1B.CR3.PI SCHEDULE

FIRST FLOOR

EXISTING TO REMAIN ELEC RM A261-A EXISTING TO REMAIN ELEC RM B229A-1

UL.1.1B

SEC 1

UL.1.1B

SEC 2

UL.4.1C

SEC 1

UL.4.1C

SEC 2

UL.4.1C

SEC 3

BASEMENT

ELEC B1XX-30

UL.2.1B

KITCHEN

BC.N.DLB

30KVA

480/277V- 208Y/120V

T

FIRST FLOOR

CLH.4.ICELH.4.IC

EXISTING TO REMAIN ELEC RM A261-A EXISTING TO REMAIN ELEC RM B229A-1

EXISTING TO BE RELOCATED FROM MED

ELEC RM B188C-1 TO NEW ELEC ROOM

B1XX-30

1B.CR2.P1

BC.CR2.PP1

125A 120V/208/

3PH 4W

CRITICAL

1B.CR3.P1

BC.CR3.DP1

125A 120V/208/

3PH 4W

CRITICAL

1B.CR3.PA

CRITICAL

1B.CR3.P2

CRITICAL

BC.EQ2.PA

EQUIP.LIFE

SAFETY

BC.EQ2.DPA

SECOND FLOOR

R.EQ2

BASEMENT

KITCHEN

CRITICAL

BRANCH

Veterans Affairs

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

FINAL SUBMITTAL

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

POWER RISER DIAGRAM CORRECT PATIENT PRIVACY

DEFICIENCIES

GAINESVILLE, FL

E701

573-18-605

SBC TWG02-01-2021

NO SCALE

NORMAL POWER RISER DIAGRAM

NO SCALE

EMERGENCY POWER RISER DIAGRAM

1 PROVIDE A 150/3P BREAKER IN EXISTING PANEL TO SERVE NEW PANEL

SHOWN. EXISTING PANEL IS A SQUARE D I-LINE 480V/3Ø/4W/600A PANEL.

2 PROVIDE 4#1/0,#6G;1-1/2" CONDUIT. ROUTE FEEDER UP TO ABOVE CEILING

OF FIRST FLOOR THROUGH ELECTRICAL ROOM "A-2616A" AND THEN DOWN

CORRIDOR AND UP TO ROOF JUST BELOW NEW PANEL.

3 EXISTING FEEDER (4#1, #6G, 1-1/4"C) FROM PANEL BC.CR2.DP1 IN BASEMENT

TO BE EXTENDED TO NEW PANEL LOCATION FROM ABOVE CEILING IN

BASEMENT. REFERE TO DRAWINGS ED100 AND EP100 FOR EXISTING PANEL

LOCATION AND NEW PANEL LOCATION. PROVIDE JUNCTION BOX SIZED PER

N.E.C. TO SPLICE AND EXTEND CONDUCTORS AS NECESSARY.

4 EXISTING FEEDER (4#1, #6G, 1-1/4"C) FROM PANEL BC.CR3.DP1 IN BASEMENT

TO BE EXTENDED TO NEW PANEL LOCATION FROM ABOVE CEILING IN

BASEMENT. REFERE TO DRAWINGS ED100 AND EP100 FOR EXISTING PANEL

LOCATION. PROVIDE JUNCTION BOX SIZED PER N.E.C. TO SPLICE AND

EXTEND CONDUCTORS AS NECESSARY.

5 PROVIDE A 50/3P BREAKER IN EXISTING PANEL TO SERVE NEW PANEL

SHOWN. EXISTING PANEL IS A SQUARE D I-LINE 480V/3Ø/4W/400A PANEL.

6 PROVIDE 3#6, #10G, 1"C . ROUTE FEEDER UP TO ABOVE CEILING OF FIRST

FLOOR THROUGH ELECTRICAL ROOM "A-2616A" AND THEN OVER TO NEW

TRANSFORMER LOCATION.

7 PROVIDE 4#1,#6G;1-1/2" CONDUIT.

GENERAL NOTES

KEY NOTES

A. FOR ALL NEW FEEDER AND SERVICE LOADS, CONTRACTOR SHALL VERIFY

OR DEMONSTRATE AVAILABLE CAPACITY OF EXISTING INSTALLATIONS PER

N.E.C. 220.87 PRIOR TO SUBMITTING PRICING. CONTRACTOR SHALL NOTIFY

ENGINEER 30 DAYS PRIOR TO ANY WORK BEING DONE IF THERE IS NOT

ENOUGH CAPACITY ON THE SERVING EQUIPMENT TO SERVE THE NEW

LOAD(S) SHOWN SO THAT THE ENGINEER CAN WORK WITH THE

CONTRACTOR TO FIND AND ALTERNATE SOURCE TO SERVE TO NEW

LOAD(S) FROM.

CG

CG

FE

C

CG

CG

CG

CG

CG

CG

CG

CG

CG

CG

CG

FE

C

CG

CG

CG

CG

C G

C G

C G

C G

CGCG

CG

CRC

R

C R

NNN

N

N N N

N N N N

N

N N N N

N N

N N

N N

N N

N

N

N

CR

C R

S

F

V

F

N

N

N

N

N N N N

V

C R

C R

C R

C R

F

CR

N

S

S

S

S

S

SSSS

S

S

S

S

S

N

N

N

N

F

F

N

F V V

V

V

V

V

S

S

S

D D D

N

N

N N

S

34 3E5678910 5E5W7E7W10E10W 8w 6E6W

K

L

M

N

P

R

LN

LS

J

E

E E E

R R R

R

L L LL

E

R

R

R

R

ICU 1

B1XX-25

TLT 1

B1XX-33

ICU 2

B1XX-26

TLT 2

B1XX-34

ICU 3

B1XX-27

TLT 3

B1XX-35

ICU 4

BARIATRIC

B1XX-28

BARIATRIC

TLT 4

B1XX-36

EQUIP STG

B1XX-29

ELEC

B1XX-30

CORRIDOR

B1XX-8

ICU 5

B1XX-18

TLT 5

B1XX-37

ICU 6

B1XX-17

TLT 6

B1XX-38

ICU 7

ISOLATION

B1XX-14

TLT 7

B1XX-39

ICU 8

ISOLATION

B1XX-13

TLT 8

B1XX-42

STAFF TLT

B1XX-12

DATA

B1XX-11CONSULT

B1XX-10

HAC

B1XX-7

LOCKERS

B1XX-9

SOILED

UTILITY

B1XX-2

DR

WORKROOM

B1XX-1

STAFF

LOUNGE

B1XX-3

NURSE

MGR

B1XX-22

STAFF

WORKROOM

B1XX-19

MEDICATION

B1XX-23

NOURISH

B1XX-24

NURSE

STATION

B1XX-40

WC NICHE

B1XX-41

CONFERENCE

B209-1

WAITING

ROOM

B1XX-43CONSULT

B144-1

DRESSING

B1XX-9A

CLEAN

UTILITY

B1XX-20

STORAGE

B1XX-32

E

E

E

F

F

EY101

D

E

L

L

L

L

D D

MS

LINEN

C244D-1 E E

E

E

PROJECT AREA

KEY PLAN

NTS

TRUE

NORTH

PLAN

NORTH

5 5E5W

K

AC

Veterans Affairs

VA FORM 08-6231

1 2 3 4 5 6 7 8 9

Date:

Drawing Title:

Approved Project Director

Project Title:

1 2 3 4 5 6 7 8 9

FINAL SUBMITTAL

590 MEANS ST NW

Phase Project Number

Building Number

Drawing NumberLocation

Issue Date CheckedFULLY SPRINKLERED

STAMP

STE. 200

ATLANTA, GA 30318

ARCHITECT/ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

U.S. Department of Veterans Affairs

Office of Construction and

Facilities Management

Drawn

PARTIAL FIRST FLOOR PLAN -

TELECOMMUNICATIONS

CORRECT PATIENT PRIVACY

DEFICIENCIES

GAINESVILLE, FL

EY101

573-18-605

SBC TWG02-01-2021

KEY NOTES

KEY PLAN

GRAPHIC SCALE(S)

NO SCALE

PARTIAL FIRST FLOOR PLAN - TELECOMMUNICATIONS

A. PROVIDE CAT 6 CABLE FOR ALL TELECOMMUNICATIONS CABLING. CABLE

MUST BE ROUTED TO EXISTING IT CLOSET AND TERMINATED IN PATCH

PANELS. PROVIDE JUNCTION BOX AT 18" A.F.F. UNLESS NOTED OR

DESCRIBED OTHERWISE. PROVIDE 1" CONDUIT FOR EACH DROP, FROM

JUNCTION BOX TO ABOVE CEILING WITH 90° ELBOW ROUTED TO NEAREST

CABLE TRAY.(SEE TELECOMMUNICATIONS OUTLETS DETAIL AND TYPICAL

OUTLET DETAILS ON SHEET EY501). COLOR CODE FOR COMMUNICATIONS

CABLES IS AS FOLLOWS: GREEN = DATA, WHITE = VOICE/WIFI, BLUE = CCTV.

B. FOR ALL SYSTEMS NOTED BELOW THE CONTRACTOR LISTED IS FOR BASIS

OF DESIGN, VERIFY WITH OWNER PRIOR TO BID TO VERIFY THEY ARE STILL

THE CONTRACTOR OF RECORD THAT IS SERVICING THE LISTED EQUIPMENT

FOR THE REST OF THIS CAMPUS.

GENERAL NOTES

A. PROVIDE A COMPLETE AND OPERATIONAL ACCESS CONTROL SYSTEM.

ACCESS CONTROL SYSTEM SHALL BE LENEL. PROVIDE BOXES AND CONDUIT

TO ABOVE CEILING CABLE TRAY FOR ALL DEVICES SHOWN ON THE PLANS.

THE INSTALLER SHALL PROVIDE ALL EQUIPMENT NECESSARY TO CONNECT

THIS SYSTEM TO THE NETWORK AND TIE IT INTO THE EXISTING SYSTEM

THAT IS SERVING THIS CAMPUS. SYSTEM DEVICES AND CARDS SHALL BE

COMPATIBLE WITH THE EXISTING CAMPUS SYSTEM.

B. SEE SHEET EY502 FOR ACCESS CONTROL DETAILS.

C. CONTRACTOR SHALL COORDINATE WITH DON COX AT "SECURITY 101" WHO

MAINTIANS THIS SYSTEMS . CONTACT INFORMATION FOR MR. COX IS

904-260-9101 EXT-116.

D. EXISTING ACCESS CONTROL DEVICES SERVED FROM RELOCATED PANEL

SHALL BE RE-SERVED FROM RELOCATED PANEL LOCATION SHOWN ON

DRAWING. A LIST OF DOORS SERVED FROM EXISTING CONTROLLER ARE

SHOWN IN A SCHEDULE ON THIS SHEET.

A. PROVIDE SECURITY CAMERAS AT LOCATIONS SHOWN. CAMERAS MUST BE

POE IP-BASED, FIXED, AND DOME TYPE UON. EXACT AIMING TO BE

COORDINATED WITH SITE SECURITY AND C.O.R. PRIOR TO INSTALLATION.

PROVIDE CAT-6 CABLE FROM EACH CAMERA TO RESPECTIVE 48-PORT

PATCH PANEL IN EXISTING IT ROOM. CROSS-CONNECTION TO BE

PERFORMED BY VA. EQUIPMENT MUST BE COMPATIBLE WITH EXISTING

SYSTEM. COORDINATE WITH SITE SECURITY AND PROVIDE A

COMPLETELY INTEGRATED AND OPERABLE SYSTEM. PROVIDE HARDWARE

AND SOFTWARE MODIFICATIONS AS REQUIRED.

A. PROVIDE A COMPLETE AND OPERATIONAL FIRE ALARM SYSTEM. FIRE ALARM

EQUIPMENT SHALL BE COMPATIBLE WITH EXISTING SYSTEM. PROVIDE

BOXES AND CONDUIT PAINTED RED FROM DEVICE TO DEVICE AS SHOWN ON

CONTRACTOR SHOP DRAWINGS. NEW FIRE ALARM EQUIPMENT SHALL BE

COMPATIBLE WITH THE EXISTING FIRE ALARM SYSTEM. NEW FIRE ALARM

PANELS SHALL BE PROVIDED WITH ALL NECESSARY EQUIPMENT TO

CONNECT TO THE NETWORK AND FIRE ALARM INSTALLER SHALL MAKE

CONNECTIONS TO EXISTING CAMPUS FIRE ALARM SYSTEM. UPDATE

SOFTWARE AS NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM.

A. PROVIDE A COMPLETE AND OPERATIONAL NURSE CALL SYSTEM. PROVIDE

JUNCTION BOXES, CONDUIT, AND ALL EQUIPMENT NECESSARY FOR A

COMPLETE AND OPERATIONAL SYSTEM. ALL DEVICES SHALL BE

COMPATIBLE WITH EXISTING ASCOM SYSTEM.

1/8" = 1' - 0" 0 5' 10' 15' 30'

A. PROVIDE A NEW FIBER SWITCH IN NEW SPECIAL SYSTEM RACK IN NEW DATA

B1XX-1 ROOM. PROVIDE NEW 12 STRAND FIBER TO SERVE NEW SWITCH

FROM ROOM "H303-1" APPROXIMATELY 500 FT AWAY FROM NEW RACK. ALL

NEW PATIENT MONITORING EQUIPMENT SHALL BE PROVIDED BY OWNER.

1 EXISTING IT ROOM. ALL DATA AND VOICE CABLES SHALL BE ROUTED TO

THIS SPACE.

2 EXISTING MATV SPLITTER BOX TO REMAIN AND BE USED FOR CONNECTION

OF NEW EQUIPMENT.

3 ALL LOW VOLTAGE CABLING IN THIS AREA SHALL BE ROUTED IN EXISTING

J-HOOK SYSTEM BACK TO EXISTING IT ROOM.

4 PROVIDE NEW MATV SPLITTER AND AMPLIFIER AT THIS LOCATION

CONNECT TO EXISTING SPLITTER REFERENCES IN NOTE 2 ON THIS SHEET.

ROUTE AN RG-11 CABLE FROM NEW SPLITTER TO EXISTING SPLITTER.

5 EXISTING G.E. ASCOM NURSE CALL HEAD END EQUIPMENT.

6 PROVIDE A WALL MOUNTED DATA RACK TO SUPPORT OWNER PROVIDED

SYSTEMS EQUIPMENT AND PATCH PANELS AS NECESSARY TO SUPPORT

ASK SYSTEM CABLES SERVING EQUIPMENT IN AREA OF RENOVATIONS.

7 PROVIDE A B-LINE "FLEXTRAY" FT4X12X10 SERIES CABLE TRAY OR

APPROVED EQUAL. PROVIDE TRAPEZE SUPPORT CLIPS AND 3/8" THREADED

ROD ON BOTH SIDES OF TRAY TO STRUCTURE ABOVE PER

MANUFACTURER'S RECOMMENDATIONS. PROVIDE A #6 COPPER GROUND

CONDUCTOR FROM THE DATA CLOSET GROUND PLATE TO EACH SECTION

OF TRAY AND EVERY CONDUIT ROUTED TO TRAY.

8 REFER TO EP101 FOR FLOOR BOX AT THIS LOCATION. DATA CABLES SHALL

BE ROUTED THROUGH FLOOR BOX.

9 RELOCATED ACCESS PANEL. REFER TO NOTE 6, SHEET ED100 FOR

CURRENT LOCATION OF THIS PANEL.

1/4" = 1'-0"

ENLARGED PLAN -

DATA ROOM B1XX-1

IRM GV MC 1st Flr. C263A-1

GV MC SICU Rear Entrance (staff entrance)

GV MC SICU Front Entrance

GV MC Radiology Res. Therapy Blood Lab C248-1

GV MC Radiology Viewing Room D337A

GV MC Radiology Procedure Room D338-1 Rear

GV MC Radiology Procedure Room D338-1 Front

GV MC Radiology Film Storage D337-1

GV MC Radiology CT3

GV MC Radiology CT2 East Entrance

GV MC Pathology Lab C264-1

GV MC OR Test Reader

GV MC OR Stairwell

GV MC OR SICU Hall

GV MC OR Implant Storage Rm

GV MC OR Exterior Entrance 1st Flr. OR/SICU

GV MC OR Entrance from Radiology

GV MC OR Anesthesiology Workroom Side Entrance E178-1 South

GV MC OR Anesthesiology Workroom Front Entrance E178-1 East

GV MC OR ABG 2nd East Entrance

GV MC OR 1st Flr. Main/Front Entrance

GV MC ENTRANCE -- 1st Flr. South SICU/CTICU

GV MC ENTRANCE -- 1st Flr. South Chaplian's Office

GV MC CTICU Rear Visitor Enrance

GV MC CTICU Front Employee Entrance

GV MC CTICU B183-1 Storage

GV MC Cath Lab C256-1

GV MC Cath Lab C254

GV MC Cath Lab C246-1 (2) back entrance

GV MC Cath Lab C246-1

GV MC Cath Lab B206-1

READERS TO BE RE-SERVED FROM RELOCATED ACCESS CONTROL

PANEL LOCATION

ACCESS CONTROL NOTES

CCTV NOTES

FIRE ALARM NOTES

NURSE CALL NOTES

PATIENT MONITOR NOTES

1 ADDENDUM 1 8/23/21

Sheets
E601 - SCHEDULES
E602 - SCHEDULES
E701 - POWER RISER DIAGRAM
EY101 - PARTIAL FIRST FLOOR PLAN - TELECOMMUNICATIONS

File details come from the government source that posted it. Updated .