22 139 Drawings Vol1 100 SS 20260717.pdf
PDF 36 MB Posted
- Attached to
- Project 619A4-23-105 - Renovate Building 10
- Solicitation number
- 36C24726R0095
About this file
This is a 100% Bid Document drawing set for the renovation of Building 10 at Central Alabama Veterans Health Care System (CAVHCS) in Tuskegee, Alabama. The project, identified as 619A4-23-105, involves comprehensive renovation of an existing facility to accommodate Community Care and Call Center operations serving approximately 12,100 gross square feet across basement, first floor, and second floor levels. The project is fully sprinklered and classified as Construction Type II per NFPA 101 standards, with mixed occupancy including business office space and assembly areas. Key project components include demolition of existing structures and utilities, site work including new concrete sidewalks and asphalt patching, structural modifications with new floor framing and foundation work, hazardous material abatement, architectural renovation with interior finishes and equipment installations, and comprehensive mechanical, electrical, plumbing, fire protection, and low-voltage systems.
The scope encompasses infection control and risk assessment (ICRA) measures for work within an active medical facility, with designated temporary barriers, negative pressure ventilation systems, and dust control protocols detailed throughout. Civil work includes new sanitary sewer, domestic water, and fire water service connections, gas service installation, chilled water lines, and storm drainage improvements. Architectural elements include new entry porch with ramps, interior renovation with finalized floor plans showing departmental layouts, accessible toilet facilities, and equipment specifications. The document set reflects 100% bid document phase with a completion date reference of May 9, 2025, and includes detailed life safety plans showing egress paths, occupant loads for business and assembly uses, and fire-rated wall separations. Professional design consultants include Apogee Consulting Group, P.A. (architectural/structural/MEP) and Foresite Group, LLC (civil/landscape), with VA project management oversight.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24726R0095 0003.pdf | ||
| 36C24726R0095 0002.docx | DOCX document | |
| Site Visit Sign In Sheet.pdf | ||
| 22 139 Drawings Vol2 100 SS 20260717.pdf | ||
| 22-139 Specs 100 BC 20250417.pdf | ||
| 36C24726R0095 0001.pdf | ||
| Attachment 5 - DBA Wage Rates_Macon County AL.pdf | ||
| 36C24726R0095_1.docx | DOCX document | |
| Attachment 3 - Past Performance Questionnaire -PPQ.docx | DOCX document | |
| Attachment 1 - EMR.pdf | ||
| 22-139 100 BC SPC 20250414.pdf | ||
| Attachment 4_Itemized Cost Breakdown example.xlsx | XLSX spreadsheet | |
| Attachment 7 - Combined Drawings 22-139 20250417.pdf | ||
| Attachment 2 -VA Notice of Limitations in Subcontracting.pdf | ||
| Attachment 6 - Invoicing.pdf |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4A
3 83
3A
BUILDING 10
WEST ENTRANCE
CONSTRUCTION TRAILER
ALTERNATE FENCED LAY
DOWN AREA
G-002
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
PROJECT SITE MAP PROJECT LOCATION MAP
EXISTING BUILDING 10 - VIEW FROM WEST EXISTING BUILDING 10 - VIEW FROM SOUTH EXISTING BUILDING 10 - VIEW FROM EAST
/1
/2
:0
:4
A
M C
U s e rs
\c th o m p s o n
\D o c u m e n ts \A
-1
-T u s k e g e e
B ld g
R e n o c th o m p s o n
B V
E
.r v t
G-000
COVER - VOLUME 1
1 9CET
RENOVATE BUILDING 10
CENTRAL ALABAMA VETERANS
HEALTH CARE SYSTEM, EAST CAMPUS
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083
MAY 9, 2025
100% BID DOCUMENTS
619A4-23-10522-139
RENOVATE BUILDING 10
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM, EAST CAMPUS
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083
VA PROJECT #: 619A4-23-105
DJR
DRAWING LIST - VOLUME 1
GENERAL
G-000 COVER - VOLUME 1 1 9
G-002 ENLARGED PROJECT SITE PLAN 2 9
G-003 GENERAL INFORMATION 3 9
G-004 CODE SUMMARY - NFPA 101 4 9
G-201 BLDG 10 FIRST FLOOR ICRA PLAN 5 9
G-202 BLDG 4A AND 4 BASEMENT ICRA PLAN 6 9
G-203 BLDG 2 BASEMENT, BLDG 3A BASEMENT, FIRST FLOOR AND PENTHOUSE ICRA
PLANS
7 9
LS101 BASEMENT AND FIRST FLOOR LIFE SAFETY PLANS 8 9
LS102 SECOND FLOOR LIFE SAFETY PLAN 9 9
CIVIL
CD101 CIVIL DEMOLITION PLAN 1 6
CS101 CIVIL SITE, GRADING & UTILITY PLAN 2 6
CS102 CIVIL UTILITY PROFILES 3 6
CS103 CONSTRUCTION SITE AND EROSION CONTROL PLAN 4 6
CS501 CIVIL DETAILS 5 6
CS502 CIVIL DETAILS 6 6
LANDSCAPE
LP101 LANDSCAPE PLAN 1 6
LP102 LANDSCAPE PLAN ENLARGEMENT 2 6
LP501 LANDSCAPE DETAILS AND SCHEDULES 3 6
IP101 IRRIGATION PLAN 4 6
IP102 IRRIGATION DETAILS 5 6
IP103 IRRIGATION DETAILS 6 6
STRUCTURAL
S-001 GENERAL NOTES 1 13
S-002 LATERAL LOADING DIAGRAMS 2 13
S-101 BASEMENT LEVEL FOUNDATION PLAN 3 13
S-102 FIRST FLOOR FRAMING PLAN 4 13
S-103 SECOND FLOOR FRAMING PLAN 5 13
S-104 ATTIC LEVEL FRAMING PLAN 6 13
S-105 ROOF FRAMING PLAN 7 13
S-301 CONCRETE DETAILS 8 13
S-302 CONCRETE DETAILS 9 13
S-401 MASONRY DETAILS 10 13
S-501 STEEL FRAMING DETAILS 11 13
S-502 STEEL FRAMING DETAILS 12 13
S-901 CONCEPTUAL CONSTRUCTION SEQUENCING DIAGRAMS 13 13
HAZARDOUS ABATEMENT
HA101 BASEMENT AND FIRST FLOORS HAZARDOUS REMEDIATION PLANS 1 2
HA102 SECOND AND ATTIC FLOORS HAZARDOUS REMEDIATION PLANS 2 2
ARCHITECTURAL
A-001 ARCHITECTURAL SYMBOLS, ABBREVIATIONS AND NOTES 1 31
AD101 BASEMENT DEMOLITION AND EXCAVATION PLANS 2 31
AD102 FIRST AND SECOND FLOOR DEMOLITION PLANS 3 31
AD103 ATTIC AND ROOF DEMOLITION PLAN 4 31
AD104 EXISTING BUILDING DEMOLITION SECTIONS 5 31
AD110 FIRST & SECOND FLOOR DEMOLITION PHOTOS 6 31
A-101 BASEMENT FLOOR PLAN AND DIMENSION PLAN 7 31
A-102 FIRST FLOOR PLAN AND DIMENSION PLAN 8 31
A-103 SECOND FLOOR PLAN AND DIMENSION PLAN 9 31
A-104 ATTIC AND ROOF PLANS 10 31
A-110 BASEMENT AND FIRST FLOOR REFLECTED CEILING PLANS 11 31
A-111 SECOND FLOOR REFLECTED CEILING PLAN 12 31
A-201 BUILDING ELEVATIONS 13 31
A-301 BUILDING SECTIONS 14 31
A-302 WALL SECTIONS 15 31
A-401 MAIN ENTRY - ENLARGED PLAN, ELEVATIONS AND SECTIONS 16 31
A-402 MAIN ENTRY - SECTION AND DETAILS 17 31
A-501 PARTITION TYPES AND MISC WALL DETAILS 18 31
A-502 MISC DETAILS 19 31
A-503 MISC DETAILS 20 31
A-601 DOOR AND WINDOW SCHEDULE, ELEVATIONS AND DETAILS 21 31
A-701 VERTICAL CIRCULATION PLANS, SECTIONS AND DETAILS - STAIR 1 22 31
A-702 VERTICAL CIRCULATION PLANS, SECTIONS AND DETAILS - STAIR 2 23 31
A-703 VERTICAL CIRCULATION SECTIONS AND DETAILS 24 31
A-704 VERTICAL CIRCULATION SECTIONS AND DETAILS 25 31
A-705 CRAWL SPACE ACCESS STAIR DETAILS 26 31
A-706 ELEVATOR PLANS AND SECTIONS 27 31
A-801 INTERIOR ELEVATOR TYPICAL PLAN, ELEVATIONS, AND DETAILS 28 31
A-901 POTENTIAL SEQUENCING FOR REFERENCE ONLY 29 31
A-902 POTENTIAL SEQUENCING FOR REFERENCE ONLY 30 31
A-903 POTENTIAL SEQUENCING FOR REFERENCE ONLY 31 31
PROJECT LOCATION
V O
L U
M E
DRAWING LIST - VOLUME 1
INTERIORS
I-001 GENERAL NOTES, ABBREVIATIONS AND ROOM FINISH SCHEDULE 1 24
I-101 FIRST AND SECOND FLOOR FINISH PLANS AND WALL PROTECTION PLANS 2 24
I-121 FIRST AND SECOND FLOOR PATTERN PLANS 3 24
I-122 ENLARGED FIRST AND SECOND FLOOR PATTERN PLAN 4 24
I-141 BASEMENT AND FIRST FLOOR SIGNAGE PLANS 5 24
I-142 SECOND FLOOR SIGNAGE PLANS 6 24
I-201 CASEWORK AND MILLWORK ELEVATIONS 7 24
I-202 CASEWORK DETAILS 8 24
I-401 INTERIOR ELEVATIONS - WALL PROTECTION 9 24
I-402 INTERIOR ELEVATIONS - WALL PROTECTION 10 24
I-403 INTERIOR ELEVATIONS - EQUIPMENT 11 24
I-411 FIRST AND SECOND FLOOR OVERALL EQUIPMENT PLANS 12 24
I-421 FIRST FLOOR EQUIPMENT PLAN-'AREA - A' 13 24
I-422 FIRST FLOOR EQUIPMENT PLAN-'AREA - B' 14 24
I-423 SECOND FLOOR EQUIPMENT PLAN-'AREA - A' 15 24
I-424 SECOND FLOOR EQUIPMENT PLAN-'AREA - B' 16 24
I-425 ENLARGED EQUIPMENT PLANS 17 24
I-426 ENLARGED EQUIPMENT PLANS 18 24
I-431 ENLARGED TOILET PLANS AND ELEVATIONS 19 24
I-501 INTERIOR DETAILS 20 24
I-601 EQUIPMENT SCHEDULES 21 24
I-901 INTERIOR AXONOMETRIC VIEWS 22 24
I-902 INTERIOR AXONOMETRIC VIEWS 23 24
I-903 INTERIOR AXONOMETRIC VIEWS 24 24
5070L
IC
E N
S E D A RC H I T ECT
DA
V ID J . REICHARD
NOR T H CA RO L I NA
Docusign Envelope ID: 0676F436-47F1-46F1-B361-38300EBB1F9D
5/6/2025
CONC. SIDEWALK
CONC. SIDEW
ALK
CONC. SIDEWALK
PROPOSED LAYDOWN AREA
APPROX 2,140 SQ FT
PROPOSED
DUMPSTER
BUILDING 4A
EXISTING
BUILDING 10
6' HIGH
CONSTRUCTION
CHAIN LINK FENCE
APPROX 674 SQ FT
3' - 0" HIGH 8' - 0" WIDE
CONSTRUCTION CHAIN
LINK FENCE GATE
EXISTING TREE
TO REMAIN
EXISTING
STORM DRAIN
EXISTING SIDEWALK TO REMAIN
EXISTING SIDEWALK TO REMAIN
E X
IS
T
IN
G
S
ID
E W
A L K
T O
R E
M A
IN
EXISTING
BOLLARD
EXISTING SIDEWALK TO REMAIN
EXISTING AC
PAD TO BE
REMOVED
EXISTING AC
PAD TO BE
REMOVED
EXISTING SIDEWALK TO REMAIN
EXISTING SIDEWALK TO REMAIN
E X
IS
T
IN
G
S
ID
E W
A L K
T O
R E
M
E X
IS
T
IN
G
S
ID
E W
A L K
T O
R E
M
E X
IS
TI
N
G S
ID
E W
A
LK
T O
R E M
IS
T
IN
G
S
ID
E W
A L K
T O
R E
M
EXISTING SIDEWALK TO REMAIN
X
IS
T
IN
G
S
ID
E W
A L K
T O
R E
M
IS
T
IN
G
S
ID
E W
A L K
T O
R E
M
NOTE:
SEE CIVIL DRAWINGS FOR
SITE WORK
4'-0"
6' - 0" HIGH 8' - 0" WIDE
CONSTRUCTION CHAIN
LINK FENCE GATE
3' - 0" HIGH 8' - 0" WIDE
CONSTRUCTION CHAIN
LINK FENCE GATE
6' - 0" HIGH 8' - 0" WIDE
CONSTRUCTION CHAIN
LINK FENCE GATE
LEGEND
6' HIGH CHAIN LINK FENCE
6' HIGH CHAIN LINK FENCE GATE
LAY DOWN AREA
BUILDING UNDER
CONSTRUCTION
EXISTING BUILDING
TREE PROTECTION FENCE
NEW MANHOLE
NEW ASPHALT PAVING
EXISTING SIDEWALK TO BE
REMOVED
1. SEE CIVIL DRAWINGS FOR MORE SITE WORK
INFORMATION.
2. ALL LAYDOWN, TRAILERS, PORTABLE TOILETS,
AND TRASH COLLECTION SHALL BE WITHIN
PROJECT SITE AND LAYDOWN AREA.
3. CONTRACTOR IS TO PARK IN DESIGNATED
AREA - COORDINATE WITH COR PRIOR TO
PROJECT START.
4. CONTRACTOR IS TO STORE ANY MATERIALS OR
EQUIPMENT IN THE DESIGNATED LAY DOWN
AREA SHOWN ON THE SITE PLAN. COORDINATE
EXACT ASSIGNED AREA WITHIN LAY DOWN
AREA WITH COR. PRIOR TO PROJECT START.
5. CONTRACTOR SHALL PROVIDE DUMPSTER FOR
ALL DEBRIS GENERATED BY THE PROJECT.
CONTRACTOR SHALL NOT BE PERMITTED TO
USE THE VA FACILITY DUMPSTER.
6. COORDINATE ALL CONSTRUCTION ACTIVITIES
AND SITE WORK WITH COR.
7. ALL TREES SHOWN ARE EXISTING TO REMAIN.
8. ADD TREE PROTECTION FOR TREES WITHIN
THE LAY DONW AREA
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:0
:4
A
M C
U s e rs
\c th o m p s o n
\D o c u m e n ts \A
-1
-T u s k e g e e
B ld g
R e n o c th o m p s o n
B V
E
.r v t
G-002
ENLARGED PROJECT SITE PLAN
2 9CET
RENOVATE BUILDING 10
CENTRAL ALABAMA VETERANS
HEALTH CARE SYSTEM, EAST CAMPUS
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083
MAY 9, 2025
100% BID DOCUMENTS
619A4-23-10522-139
DJR
Scale: 1" = 10'-0"
ENLARGED PROJECT SITE PLAN N
O R
TH
0 2010 40
CONTRACTOR TO REVIEW WITH COR
1. CONSTRUCTION ACCESS ROUTE
2. CONSTRUCTION PARKING
3. CONSTRUCTION SIGNAGE
1 NEW CONCRETE SIDEWALK AND CONTROL
JOINT. REFER CIVIL.
2 PROVIDE TREE PROTECTION FENCE REFER
CIVIL.
3 EXISTING TREE TO REMAIN
4 EXISTING LAMP POST TO REMAIN
5 EXISTING CONCRETE STEPS TO REMAIN.
6 NEW COVERED PORCH AND STAIRS.
7 NEW SANITARY SEWER MANHOLE REFER
CIVIL.
8 NEW ASPHALT PAVING PATCH REFER CIVIL.
9 CE-916 6" SQUARE PUSH PLATE BOLLARD,
CURRAND ENG. COMPANY.
11 DOME GRATE INLET. REFER TO CIVIL.
12 EXISTING TRANSFORMER. SEE ELECTRICAL
FOR DETAILS.
5070L
IC
E N
S E D A RC H I T ECT
DA
V ID J . REICHARD
NOR T H CA RO L I NA
S SS
WALL SECTION
SYMBOL
INTERIOR ELEVATION
SYMBOL
COLUMN GRID
ELEVATION SYMBOL
REVISION NOTE
ENLARGED DETAIL CALLOUT
ROOM DESIGNATION
SYMBOL
BREAK LINE
ROOF SLOPE
DIRECTION SYMBOL
TYPICAL GRAPHIC SCALE
DETAIL #
PAGE #
DETAIL #
PAGE #
VIEW NORTH ARROW
A8.1
EXTERIOR ELEVATION
SYMBOL
DETAIL #
PAGE #
A8.1
A8.1
A8.1
BUILDING SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
A8.1
DETAIL SECTION
SYMBOL
DETAIL #
PAGE #
A8.1
XX.X
ELEVATION
0'-0"
ROOM
NAME
101A
NORTHNORTH
0 4 8 16
1-1/2"
DIAMETER
GRAB BAR
TOILET
TISSUE
DISPENSER
SANITARY
NAPKIN
DISPOSAL
TOILET
FIXTURE
TOILET
FIXTURE
TOILET
TISSUE
DISPENSER
1-1/2"
DIAMETER
GRAB BAR
EXPOSED
PLUMBING AT
BARRIER
FREE
LAVATORIES
SHALL BE
INSULATED.
LEVER OPERATING
CONTROLLED
SOAP DISPENSER
NOTE: SINKS IN COUNTERS TO BE
MOUNTED WITH RIM NO MORE
THAN 2'-10" HIGH AND WITH AT
LEAST 2'-3" KNEE CLEARANCE.
CLEAR
ACCESSIBLE TOILET TYPICAL ACCESSIBLE
CLEARANCE AT LAVATORY
TYPICAL ACCESSIBLE
LAVATORY AND MIRROR
1'-3" 1'-3"
M
IN
M A
X
M
A X
M
A X6
A
.F .F
1'-6"
5'-0" CLEAR
3'-0" 6"
3'-0"
" 3
1'-0" 3'-6"
2'-4"
5'-0" CLEAR
MIN
8"
MAX
6"
M
IN9
M
IN
M
IN
M A
X
17" MIN
FIRE ALARM
CHIME WITH
VISUAL
ALARM LIGHT
FIRE ALARM
PULL STATION
FIRE ALARM
ANNUNCIATOR
FIRE ALARM
DRINKING FOUNTAIN
WHEELCHAIR ACCESSIBLE
(CANTILEVERED STYLE)
17" - 19"
8" MIN
9" MIN
6" MAX
M
IN
T O
P O
F S
P O
U T
' M
A X
/4
T O
B O
T T
O M
O F
R
F
L E
C T
IV
S
U R
F A
C E
F
M
IR
R
O R
ELECTRICAL CABINET
DUPLEX
OUTLET
SWITCH
THERMOSTAT
TELEPHONE
OR DATA
OUTLET
FIRE ALARM
PULL
INTERCOM
STATION
DUPLEX
OUTLET
COMPUTER
TERMINAL
MISC. WALL DEVICES WALL MOUNTED WHITEBOARD
MOP BASIN
MOP SHELF
TYPICAL JANITORS CLOSET
ACCESSIBLE
ROBE/COAT HOOK
ROBE/COAT
HOOK
TOILET ACCESSORIES
6"
4'-0" MAX TO
HIGHEST OPERABLE
POINT - IF FIRE
EXTINGUISHER
OVER 40 LBS
3'-6" MAX HT.
FIRE EXTINGUISHER
CABINET
FEMININE HYGIENE
DISPENSER
PAPER TOWEL
DISPENSER
2'-0" AT SIDEWALLS
AT COUNTER SINKS
1'-6" AT SIDEWALLS
AT LAVATORY
CLOCK
NURSE
CALL
DOME
LIGHT
CLOCK & NURSE CALL DEVICES
NURSE CALL
/4
M A
X
T O
T O
P O
F H
IG
H
E S
T
P
E R
A B
L E
P A
R T
LIFE SAFETY GENERAL NOTES
GENERAL
1. REFER TO CIVIL DRAWINGS FOR INFORMATION INCLUDING CONCRETE SIDEWALKS, CONCRETE PADS, AND
PARKING CONFIGURATIONS. CIVIL BACKGROUND IS SHOWN FOR REFERENCE ONLY.
2. REFER TO MECHANICAL DRAWINGS FOR INFORMATION CONCERNING DAMPERS.
3. REFER TO ELECTRICAL DRAWINGS FOR FIRE ALARM NOTIFICATION AND EMERGENCY EGRESS LIGHTING
LOCATIONS.
ALL WORK
1. ALL FIRE-RATED ASSEMBLIES SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND/OR TESTED ASSEMBLIES INDICATED. DEVIATIONS FROM THESE SHALL BE CORRECTED
AT NO ADDITIONAL COST.
2. WHERE FIRE-RATED CONSTRUCTION IS SHOWN OR NOTED, CONTRACTOR SHALL SUBMIT CERTIFIED ASSEMBLIES. THIS INCLUDES PARITIONS / BARRIERS, ROOF / FLOOR ASSEMBLIES, TOP AND BOTTOM OF WALL
ASSEMBLIES, PENETRATIONS AND RECESSED ITEMS.
3. EXTEND ALL FIRE AND/OR SMOKE PARTITIONS / BARRIERS TO BOTTOM OF ROOF / FLOOR DECK ABOVE (OR AS DIRECTED BY UL ASSEMBLY) AND TO EXTERIOR WALL SHEATHING. SEAL JOINT BETWEEN EDGES OF PARTITION
WITH FIRE RATED SEALANT AND/OR INTUMESCENT ASSEMBLY.
4. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES SHALL BE FIRE-SEALED IN ACCORDANCE WITH APPROVED MANUFACTURER'S DETAILS FOR LOCATION, TYPE OF CONSTRUCTION, PENETRATING ITEM AND RATING
REQUIRED.
5. ALL DUCTWORK, DIFFUSERS AND GRILLES PENETRATING FIRE-RATED WALLS, CEILINGS AND FLOORS SHALL HAVE THE APPROPRIATE TYPE OF FIRE/SMOKE DAMPER IN ACCORDANCE WITH THE TYPE OF CONSTRUCTION
BEING PENETRATED AND THE FIRE/SMOKE RATING REQUIRED.
6. ALL LIGHT FIXTURES AND ELECTRICAL DEVICES PENETRATING FIRE-RATED ASSEMBLIES SHALL BE UL-LISTED FOR INSTALLATION IN THE ASSEMBLY OR SHALL BE INSTALLED SUCH THAT THE FIRE-RATING IS NOT
COMPROMISED.
7. ALL DOORS, WINDOW ASSEMBLIES, AND OTHER OPENINGS PENETRATING FIRE-RATED WALLS SHALL HAVE AN FIRE-RATING BASED ON THE TYPE OF CONSTRUCTION BEING PENETRATED. DOORS SHALL BE POSITIVE
LATCHING AT ALL FIRE-RATED ASSEMBLIES. WIRE GLASS IS NOT PERMITTED.
8. DOORS SHALL NOT HAVE AIR TRANSFER OPENINGS AND SHALL NOT BE UNDERCUT IN EXCESS OF CLEARANCE
PERMITTED WITH ACCORDANCE TO NFPA 80.
9. PROVIDE ENCLOSURE AND ACCESS PANEL AT EACH FIRE PROTECTION INSPECTION TEST VALVE. DO NOT LOCATE VALVES AND PIPES IN EXTERIOR WALLS. ALL ACCESS PANELS SHALL HAVE AN EQUAL FIRE-RATING AS
WALLS AND/OR CEILINGS BEING PENETRATED.
10. UNLESS SCHEDULED TO RECIEVE SELF-SEALING FIRE-RATED PATHWAYS, METALLIC SLEEVES SHOULD BE INSTALLED AROUND LOW VOLTAGE CABLES THAT PENETRATE THE WALL, AND SEALANT SHOULD BE USED TO
SEAL AROUND THE SLEEVE AND INSIDE THE SLEEVE.
11. WHERE DEVICES ARE INDICATED IN RATED CONSTRUCTION, PROVIDE INTUMESCENT INSERTS FOR THE
ELECTRICAL BOXES WHERE ANY OF THE FOLLOWING CONDITIONS OCCUR:
- BOX EXCEEDS THE ALLOWABLE SIZE OF 16 SQ. IN.
- AGGREGATE AREA OF BOXES EXCEEDS 100 SQ. IN. PER 100 SF OF PARTITION.
- BOXES ON OPPOSITE SIDES OF PARTITION ARE LESS THAN 24" APART.
- BOXES OCCUR WITHIN THE SAME STUD CAVITY.
12. WHERE FIRE-RATED WALL ASSEMBLIES OCCUR IN PROXIMITY TO STEEL BEAMS / JOIST WITH INADEQUATE DIMENSION TO INSTALL GYP. BD. ON BOTH SIDES OF STUD FULLY TO THE BOTTOM OF THE ROOF/ FLOOR DECK, PROVIDE STUD FRAMING AROUND THE STRUCTURE WITH LAYERS OF GYP. BD. REFLECTING THE RATING OF THE
WALL ASSEMBLY.
1 HOUR FIRE SEPARATION
2 HOUR FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:0
:4
A
M C
U s e rs
\c th o m p s o n
\D o c u m e n ts \A
-1
-T u s k e g e e
B ld g
R e n o c th o m p s o n
B V
E
.r v t
G-003
GENERAL INFORMATION
3 9CET
RENOVATE BUILDING 10
CENTRAL ALABAMA VETERANS
HEALTH CARE SYSTEM, EAST CAMPUS
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083
MAY 9, 2025
100% BID DOCUMENTS
619A4-23-10522-139
DJR
GENERAL SYMBOL LEGEND
Scale: 3/8" = 1'-0"
STANDARD MOUNTING HEIGHTS
WALL RATING LEGEND
5070L
IC
E N
S E D A RC H I T ECT
DA
V ID J . REICHARD
NOR T H CA RO L I NA
CODE SUMMARY - NFPA
DESIGNER FIRM NAME LIC.# PHONE# EXTERIOR WALLS -(EACH ASSEMBLY):
ROOF/CEILING ASSEMBLY - (EACH ASSEMBLY):
ENERGY SUMMARY
THERMAL ENVELOPE
GROSS BUILDING AREA:
HIGH RISE:
METHOD OF COMPLIANCE
FLOOR OVER UNCONDITIONED SPACEBUILDING DATA (NFPA 220):
FIRE DISTRICT:
SPRINKLERS:
MEZZANINE:
ALLOWABLE BUILDING HEIGHT:
CONSTRUCTION TYPE:
LEAD DESIGN PROFESSIONAL:
FLOOR SLAB ON GRADE (EACH ASSEMBLY)
WALLS BELOW GRADE (EACH ASSEMBLY)
STANDPIPES:
OCCUPANCY
PRIMARY OCCUPANCY:
MIXED OCCUPANCY:
FIRE PROTECTION REQUIREMENTS *
STRUCTURAL DESIGN
IMPORTANCE FACTORS:
DESIGN LOADS:
LIVE LOADS:
SNOW LOAD:
WIND LOAD:
SEISMIC DESIGN CATEGORY A
SEISMIC DESIGN CATEGORY B, C, & D
SEISMIC RISK CATEGORY
SPECTRAL RESPONSE ACCELERATION S %g S %g
SITE CLASSIFICATION
BASIC STRUCTURAL SYSTEM (CHECK ONE)
SEISMIC BASE SHEAR Vx= Vy=
ANALYSIS PROCEDURE
ARCHITECTURAL, MECHANICAL, COMPONENTS ANCHORED?
LATERAL DESIGN CONTROL:
SOIL BEARING CAPACITIES:
CONSTRUCTED:
RENOVATED:
ORIGINAL USE(S) (CH.3):
CURRENT USE(S) (CH.3):
PROPOSED USE(S) (CH.3):
LIFE SAFETY PLAN REQUIREMENTS
CLIMATE ZONE
LOW E REQUIRED, IF APPLICABLE
OPENINGS (WINDOWS OR DOORS WITH GLAZING)
R-VALUE OF INSULATION:
PROJECTION FACTOR
U-VALUE OF ASSEMBLY
SHADING COEFFICIENT
U-VALUE OF TOTAL ASSEMBLY:
DOOR R-VALUES
TOTAL SQUARE FOOTAGE OF SKYLIGHTS IN EACH ASS'Y
SKYLIGHTS IN EACH ASSEMBLY:
R-VALUE OF INSULATION:
U-VALUE OF TOTAL ASSEMBLY:
U-VALUE OF SKYLIGHT
DESCRIPTION OF ASSEMBLY:
PRESCRIPTIVE (BUILDING CODE) PERFORMANCE (COMCheck)
PRESCRIPTIVE (ASHRAE 90.1)
IV (2HH)
I (442)
III (211)
II (222)I (332)
III (200)
II (111)
V (111)
FIRE
PROTECTION:
RETAINING
WALLS >5' HIGH:
STRUCTURAL:
MECHANICAL:
ELECTRICAL:
FIRE ALARM:
PLUMBING:
CODE ENFORCEMENT JURISDICTION:
ARCHITECTURAL:
CIVIL:
OWNER OR
OWNED BY: FEDERAL CITY/COUNTY PRIVATE STATE
NAME OF PROJECT:
PROPOSED USE:
ADDRESS:
DESCRIPTION OF ASSEMBLY:
HORIZONTAL/VERTICAL REQUIREMENT
DESCRIPTION OF ASSEMBLY:
U-VALUE OF TOTAL ASSEMBLY:
R-VALUE OF INSULATION:
R-VALUE OF INSULATION:
U-VALUE OF TOTAL ASSEMBLY:
SLAB HEATED
DESCRIPTION OF ASSEMBLY:
U-VALUE OF TOTAL ASSEMBLY:
R-VALUE OF INSULATION:
OTHER:
NO NFPA 13YES NFPA 13R NFPA 13D
NO CLASSYES
NO YES
FEET # STORIES
NO YES
NO YES CENTRAL REFERENCE SHEET #
ASSEMBLY
BUSINESS EDUCATIONAL
INDUSTRIALHEALTHCARE MERCANTILE
RESIDENTIAL BOARD AND CARESTORAGE
DETENTION AND CORRECTIONAL
NO YES SEPARATION: HR. EXCEPTION:
LIFE SAFETY PLAN SHEET #, IF PROVIDED: LS101 & LS102
STATE
COUNTY
AUTHORIZED AGENT
NFPA 14
WIND (I W)
SNOW (I S)
SEISMIC (I E)
ROOF
MECHANICAL
FLOOR
PSF
PSF
PSF
PSF
BASIC WIND SPEED EXPOSURE
CATEGORY WIND BASE SHEARS
(FOR MWFRS) Vx=
MPH (ASCE 7-16)
COMPLIANCE WITH SECTION 1616.4 ONLY? NOYES
PROVIDE THE FOLLOWING SEISMIC DESIGN PARAMETERS:
BEARING WALL
BUILDING FRAME
MOMENT FRAME
DUAL W/SPECIAL MOMENT FRAME
DUAL W/INTERMEDIATE R/C OR SPECIAL STEEL
INVERTED PENDULUM
S 1
EARTHQUAKE
FIELD TEST (PROVIDE COPY OF TEST REPORT)
PRESUMPTIVE BEARING CAPACITY
PILE SIZE, TYPE, AND CAPACITY
PSF
PSF
MECHANICAL SUMMARY - SEE MECHANICAL DRAWINGS
ELECTRICAL SUMMARY - SEE ELECTRICAL DRAWINGS
DESCRIPTION OF ASSEMBLY:
R-VALUE OF INSULATION:
U-VALUE OF TOTAL ASSEMBLY:
DESCRIPTION OF ASSEMBLY:
BUILDING 10 RENOVATION
2400 HOSPITAL ROAD, TUSKEGEE, AL ZIP CODE: 36083
BUSINESS
EMAIL:
RODNEY HARDY
CITY
APOGEE CONSULTING DAVID REICHARD NC 5070 (919) 858-7420
APOGEE CONSULTING KEVIN KUBLANK
NEW CONSTRUCTION ADDITION UPFIT
RECONSTRUCTION ALTERATION REPAIR RENOVATION
N/A
FIRE AND/OR SMOKE RATED WALL LOCATIONS
ASSUMED AND REAL PROPERTY LINE LOCATIONS
EXTERIOR WALL OPNEING AREA WITH RESPECT TO DISTANCE TO ASSUMED
PROPERTY LINES
EXISTING STRUCTURES WITHIN 30' OF THE PROPOSED BUILDING
OCCUPANCY TYPES FOR EACH AREA
OCCUPANT LOADS FOR EACH AREA
EXIT ACCESS TRAVEL DISTANCES
COMMON PATH OF TRAVEL DISTANCE
DEAD END LENGTHS
CLEAR EXIT WIDTHS FOR EACH EXIT DOOR
MAXIMUM CALCULATED OCCUPANT LOAD CAPACITY EACH EXIT DOOR CAN
ACCOMMODATE BASED ON EGRESS WIDTH
ACTUAL OCCUPANT LOAD FOR EACH EXIT DOOR
A SEPARATE SCHEMATIC PLAN INDICATING WHERE FIRE RATED FLOOR/
CEILING AND/OR ROOF STRUCTURE IS PROVIDED FOR PURPOSES OF
OCCUPANCY SEPARATION
LOCATION OF DOORS WITH PANIC HARDWARE
LOCATION OF DOORS WITH DELAYED EGRESS LOCKS AND THE AMOUNT OF
DELAY
LOCATION OF DOORS WITH ELECTROMAGNETIC EGRESS LOCKS
LOCATION OF DOORS EQUIPPED WITH HOLD-OPEN DEVICES
LOCATION OF EMERGENCY ESCAPE WINDOWS
THE SQUARE FOOTAGE OF EACH FIRE AREA
THE SQUARE FOOTAGE OF EACH SMOKE COMPARTMENT
NOTE ANY CODE EXCEPTIONS OR TABLE NOTES THAT MAY HAVE BEEN
UTILIZED REGARDING THE ITEMS ABOVE
PERFORMANCE (ASHRAE 90.1)
3 4 5
STRUCTURAL DESIGN - SEE STRUCTURAL DRAWINGS
75' 4
II
II
0.18 0.083
D
YES
2,000
FLOOR EXISTING (SQ FT) NEW (SQ FT) SUB-TOTAL
BASEMENT
TOTAL
PHONE:
FORESITE
Vy=
WIND
EMERGENCY LIGHTING:
EXIT SIGNS:
FIRE ALARM:
SMOKE DETECTION SYSTEMS:
PANIC HARDWARE:
BUILDING
ELEMENT
FIRE
SEPARATION
DISTANCE
(FEET)
PER T602
NONBEARING
WALLS &
PARTITIONS
STRUCTURAL
FRAME,
INCLUDING
COLUMNS,
GIRDERS,
TRUSSES
DETAIL #
AND
SHEET #
DESIGN
# FOR
RATED
ASS'Y
DESIGN
# FOR
RATED
PENETRATION
DESIGN
# FOR
RATED
JOINTS
RATING
PROVIDED
REQ'D
(HRS)
BEARING WALLS
EXTERIOR
NORTH
EAST
WEST
SOUTH
INTERIOR
EXTERIOR
NORTH
EAST
WEST
SOUTH
INTERIOR
FLOOR
CONSTRUCTION,
INCLUDING
SUPPORTING
BEAMS & JOISTS
ROOF
CONSTRUCTION,
INCLUDING
SUPPORTING
BEAMS & JOISTS
SHAFTS-ELEV.
SHAFTS-OTHER
CORR. SEP.
OCC'Y SEP. (C)
PARTY/FIRE
WALL SEP.
SMOKE BARRIER
SEPARATION
TENANT SEP.
LIFE SAFETY SYSTEM REQUIREMENTS
INCID. USE SEP.
* INDICATE SECTION NUMBER PERMITTING REDUCTION
NO YES
NO YES
NO YES
NO YES
NO YES
PARTIAL
N/A
0 -- -- -- ----
0 -- -- -- ----
N/A -- -- -- ----
N/A -- -- -- ----
N/A -- -- -- ----
N/A -- -- -- ----
N/A -- -- -- ----
0 N/A -- -- ----
>30'
0 -- -- -- ---->30'
0 0 -- -- -->30'
0 -- -- -->30'
0 -- -- -->30'
0 -- -- -->30'
N/A
N/A
N/A -- -- -- ----
N/A
N/A
EQUIVALENET LATERAL FORCE
VETERANS ADMINISTRATION
334-312-9382
RODNEY.HARDY2@VA.GOV
(919) 858-7420
FEDERAL DEPT OF VETERAN AFFAIRS
CLAY MASSEY AL 38677 (770) 368-1399
NC 33282
APOGEE CONSULTING KEVIN KUBLANK (919) 858-7420NC33282
APOGEE CONSULTING SILAS GEORGE (919) 858-7420PE 50996
APOGEE CONSULTING SILAS GEORGE (919) 858-7420PE 50996
APOGEE CONSULTING SILAS GEORGE (919) 858-7420PE 50996
FORESITE JANICE WEAVER GA 038853 (770) 368-1399
NONE [name] [license] [phone]
NONE [name] [license] [phone]
SCOPE TYPE:
ACTUAL BUILDING HEIGHT: FEET # STORIES
UNLIMITED PER:
32'-0" 2
1ST FLOOR
2ND FLOOR 5,100
6,000
11,300
1,450
5,100
6,000
1,650
12,100
1.20 1.00
II (000)
V (000)
AMBULATORY HEALTH CARE
DAY CARE
ONE- AND TWO-FAMILY DWELLING
APARTMENT
LODGING OR ROOMING HOUSE
HOTELS AND DORMITORY
MISSION CRITICAL
LIFE SAFETY
PHYSICAL SECURITY
CENTRAL ALABAMA VETERANS HEALTH CARE SYSTEM, EAST CAMPUS
EXISTING TO REMAIN
EXISTING TO REMAIN
SUPPORTED SLAB OVER CRAWL SPACE
N/A
N/A
1/16.29 = 0.061
9.0
16.29
LOW E
SLAB ON GRADE AT BASEMENT
NO
ALL
EXTERIOR GLAZING TO BE LAMINATED GLASS
BUSINESS (OUTPATIENT)
BUSINESS (OUTPATIENT)
DERELICT
NFPA TABLE 8.3.3.2.2 (WITH FIRE SPRINKLERS)
N/A
N/A
N/A
N/A
N/A
* SEE SOIL BORING LOGS
CFMF ROOF RAFTERS
METAL DECK
RIGID INSULATION (5" R.I.; R=31.0)
N/A
N/A
0.06
TRAVEL DISTANCE:
BUSINESS OCCUPANCY ALLOWABLE TRAVEL DISTANCE: 300'-0" MAXIMUM
PROVIDED: SEE SHEET LS101 AND LS102
DEADEND LIMIT 50'-0" MAXIMUM
COMMON PATH OF TRAVEL LIMIT 100'-0" MAXIMUM
U905
DAVID REICHARD
SEE WUFI REPORT
UNI-SEX STD.
PLUMBING FIXTURE REQUIREMENTS
WATER CLOSETS DRINKING FOUNTAINS
USE
LAVATORIES
URINALS
SHOWERS/
TUBS
ACCESS.
SPACE EXISTING
NEW
REQUIRED
1*
UNI-SEX
IBC 2021 CHAPTER 29 TABLE 2902.1
* WATER FILLER STATIONS BY OWNER
6 0 6 0 0 1*
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:2
:1
P
M C
U s e rs
\s m is e v ic h \D o c u m e n ts
\A
-1
-T u s k e g e e B ld g
R e n o s m is e v ic h .r v t
G-004
CODE SUMMARY - NFPA 101
4 9CET
RENOVATE BUILDING 10
CENTRAL ALABAMA VETERANS
HEALTH CARE SYSTEM, EAST CAMPUS
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083
MAY 9, 2025
100% BID DOCUMENTS
619A4-23-10522-139
DJR
Docusign Envelope ID: 2553BC93-08C6-82AB-81C4-F301DAA0D0A7
7/17/2026
UP UP
DN
UP
MAIN ENTRY
DN
VACANT SPACE
VACANT SPACE
C-3
VACANT SPACE
VACANT SPACE
102A
VACANT
VACANT SPACE
VACANT
SPACE
101A
C-2
CORR.
VACANT SPACEVACANT
SPACE
VACANT SPACE
VACANT
SPACE
VACANT
SPACE
VACANT SPACE
113A
VACANT SPACE
113B
VACANT SPACE
CORRIDOR
VACANT
SPACE
113H
VACANT
SPACE
113F
113E
VACANT SPACE
113C
VACANT SPACE
113D
VACANT SPACE
113G
VACANT SPACE
VACANT
SPACE
4'-0"4
A.1 A.9
0.9
E.1 E.9E.5
A. REMOVE ALL TRASH DAILY FROM THE WORK AREA.
B. THESE DRAWINGS ARE BASED ON FIELD SURVEY AND
EXISTING PLANS. VERIFY ALL FIELD CONDITIONS.
C. COORDINATE WITH VA COR FOR OFF-HOURS
SCHEDULE AND TEMPORARY REROUTING ACCESS
FOR HOSPITAL STAFF AND VISITORS, PRIOR TO
ERECTING TEMPORARY BARRIERS.
D. EXISTING WINDOWS THAT NEED TO BE TEMPORARILY
REMOVED TO ACCOMMODATE DISCHARGED AIR
EXHAUST DUCT, SHALL BE REINSTALLED AFTER
CONSTRUCTION.
E. CONTRACTOR TO VERIFY AND COORDINATE FINAL
AND APPROVED ICRA MEASURES WITH THE VA ICRA
PERSONNEL, PRIOR TO THE COMMENCEMENT OF
CONSTRUCTION ACTIVITY.
F. CONTRACTOR SHALL VISIT ALL AREAS OF WORK,
INCLUDING WALKING THE SITE, MEASURING EXISTING
DIMENSIONS AND OBSERVING EXISTING CONDITIONS
BEFORE BEGINNING WORK ORDERING MATERIALS,
OR STARTING ANY CONSTRUCTION. CONTRACTOR TO
FIELD VERIFY ALL DIMENSIONS OF EXISTING SITE
CONDITION PRIOR TO START OF WORK AND
ORDERING OF MATERIALS.
G. CONTRACTOR SHALL RECYCLE REMOVED MATERIALS
WHENEVER POSSIBLE. SEE DIVISION 1
SPECIFICATIONS.
H. CONTRACTOR TO PROTECT AREA ADJACENT TO THE
DEMOLITION AND NEW CONSTRUCTION WORK TO
PREVENT DAMAGES. IF DAMAGED, REPAIR, PATCH,
REPLACE, OR SAND SMOOTH AND TO MATCH
EXISTING ADJACENT MATERIALS. REPORT ANY AND
ALL DAMAGES TO COR.
I. CONTRACTOR SHALL REPORT TO COR IMMEDIATELY
WHEN DISCREPANCIES TO THE DRAWINGS ARE
FOUND IN THE FIELD.
J. CONTRACTOR TO INSTALL TEMPORARY DIGITAL
MANOMETER TO MONITOR AND ENSURE PRESSURE
LEVEL TO MEET VA GUIDELINE WITHIN
CONSTRUCTION AREA. WITH VA COR PRIOR TO
INSTALLATION.
K. TEMPORARY BARRIERS SHALL BE INSPECTED BY VA
LIFE SAFETY AND ICRA STAFF PRIOR TO START OF
CONSTRUCTION IN SPACE. MAINTAIN NEGATIVE
PRESSURE VENTILATION IN CONSTRUCTION SPACE.
L. DOORS TO CORRIDORS FROM OCCUPIED ROOMS
SHALL NOT BE BLOCKED DURING SHIFTS.
M. USE OF MOBILE CONTAINMENT (ICRA) CART IS
ACCEPTABLE FOR ABOVE CEILING WORK THAT CAN
BE LIMITED TO THE CONTAINMENT OF THE CART.
N. TEMPORARY BARRIER SHALL BE INSTALLED FOR
EACH OF THE ROOMS OR CONSTRUCTION AREAS AS
IDENTIFIED WITHIN THE SCOPE OF WORK OF THE
CONTRACT DOCUMENTS.
O. PLASTIC SHEET BARRIERS MAY NOT BE REUSED.
CONTRACTOR SHALL TAKE CARE TO CONTAIN ANY
DUST ON PLASTIC SHEET BARRIERS DURING
REMOVAL AND DISPOSAL.
P. CONSTRUCTED AND/OR MODULAR ICRA BARRIERS
SHALL BE WIPED CLEAN BEFORE REMOVAL TO AVOID
SPREADING DUST.
Q. NO MORE THAN 1 CEILING TILE PER 50 SQ.FT. SHALL
BE REMOVED WITHOUT PROPER ICRA AND LIFE
SAFETY MEASURES IN PLACE.
F L E
X D
U C
T
FIRE EXTINGUISHER ON
PORTABLE FLOOR BRACKET
(ILSM MAY REQUIRE MORE
THAN ONE).
PROVIDE STICKY
MATS (CHANGED END
OF SHIFT OR MORE IF
NECESSARY TO
MAINTAIN
CLEANLINESS).
HEPA NEGATIVE
AIR UNIT
SUPPLY DUCTS EITHER
KEEP RUNNING OR
COVER WHEN RUNNING
TO KEEP DUST OUT
COVER ALL RETURNS
AT THE
GRATE/DIFFUSERS
SUSPENDED PLASTIC
ZIPPER WALL
CURTAIN BARRIER
POST ICRA, ILSM, FIRE
INPECTION SHEETS
VISIBLE TO PUBLIC
FIRE PULL
STATION WITH
AUDIO / VISUAL
EXISTING WALL
BARRIER
NOTE:
A. TURN UP EXHAUST ON EXTERIOR
ON SIDE. CONTRACTOR SHALL
VERIFY LOCATION OF AIR INTAKES
ARE AT THE PROPER DISTANCE
FROM EXHAUST. VERIFY LOCAL
JURISDICATION CODE AND VA
REQUIREMENTS FOR DISTANCE
PRIOR TO STARTING WORK.
EXHAUST LOCATION
- SEE NOTE A
PLASTIC WINDOW
SWIVEL CASTERS
WITH TWO
LOCKING BRAKES
MOBILE CART
A D
J U
S T
A B
L E
H E
IG
H
T
HEPA NEGATIVE
AIR UNIT
EXISTING WALL
EXISTING CEILINGFLEX DUCT
ILSM SIGNAGE
INTERIM LIFE SAFETY MEASURES IN EFFECT
FOR RENOVATE BUILDING 10
THIS EXIT IS CLOSED AND LEADS TO A
CONSTRUCTION AREA.
PLEASE USE ALL ALTERNATE EXITS AS MARKED.
1' - 5"
1/2"1/2"
/2
/2
/2
/2
/2
/2
EQ.EQ.
3 5/8" INSULATED WALL WITH
16 GAUGE METAL STUDS @
16" O.C. WALL TO EXTEND TO
UNDERSIDE OF DECK
5/8" FIRE RESISTANT GYPSUM
BOARD - BOTH SIDES
CONCRETE SLAB
UNDERSIDE OF EXISTING
DECK
W A
L L
H E
IG
H
T V
A R
IE
S
F
IE
L D
V E
R
IF
Y
4 7/8"
A
FIRE RESISTANT SEALANT,
BOTH SIDES
1-HR RATED
U.L. DESIGN NO. U419
PLASTIC SHEET BARRIER
NON RATED
PLASTIC SHEET
BARRIER
EXISTING WALL
ASSEMBLY
BOTTOM SEALING
RUNNER
TOP SEALING
RUNNER
SUPPORT POLES,
QUANTITY PER
MANUF.
RECOMMENDATIONS
B
UNDERSIDE OF EXISTING
DECK
ILSM TEMPORARY BARRIER TAG
PROJECT:
PRIME CONTRACTOR:
SUB CONTRACTOR:
EMERGENCY CONTACT NO.:
BARRIER INSTALLATION DATE:
BARRIER EXPIRATION DATE:
DUST CONTROL PLAN NOTES
1. THE VAMC INFECTION CONTROL GROUP HAS CONFIRMED THE DESIGNATION
FOR THIS PROJECT IS LEVEL I FOR THE CLASS OF PRECAUTIONS OR LEVEL OF
INFECTION CONTROL ACTIVITIES. HARD SURFACE BARRIERS SHALL BE USED
EXCEPT IN THE AREA INDICATED ON THE PHASING PLAN WITH PLASTIC BARRIERS
(MINIMUM 4MIL) TO SEAL AREA FROM NON-WORK AREA AS LONG AS THE SPRINKLER
SYSTEM IS INTACT AND ACTIVE.
1A. THIS PROJECT NEEDS AN ENTRY VESTIBULE FOR CLOTHING CHANGES
(PROVIDE AND LOCATE A STAGING AREA FOR HAZMAT SUITS NEAR THE PLASTIC
BARRIER ENTRANCE SPACES - CONSTRUCTION ANTEROOM. THEY SHALL BE USED
WHEN GOING INTO CONSTRUCTION AREA AND LEAVING THE CONSTRUCTION AREA)
AND TOOL STORAGE AND TIGHT SEALS SHALL BE MAINTAINED AT THE FULL
PERIMETER OF WALLS AND WALL PENETRATIONS. ANY DUST SHALL BE
IMMEDIATELY CLEANED IF TRACKED OUTSIDE OF THE CONSTRUCTION BARRIER.
UPON COMPLETION OF THE CONSTRUCTION PHASE, DUST BARRIERS SHALL BE
REMOVED CAREFULLY TO MINIMIZE SPREADING OF DUST AND THE CONTRACTOR
SHALL HAVE TEMPORARY DUST PROTECTION IN PLACE BEFORE REMOVAL OF A
PERMANENT BARRIER.
2. PROVIDE STICKY MATS AND BLANKET AT THE PLASTIC BARRIER ENTRANCE
SPACES (CONSTRUCTION ANTEROOM) AND CHANGE DAILY OR MORE OFTEN AS
NEEDED TO PREVENT THE SPREAD OF DUST AND DEBRIS INTO ADJACENT CLEAN
SPACE.
INTERNAL DEMOLITION AND CONSTRUCTION ACTIVITIES DUST AND DEBRIS
CONTROL
3. USE CORRIDORS AS PRIMARY CONSTRUCTION ACCESS.
3A. TRAFFIC CONTROL: DESIGNATED ENTRY AND EXIT PROCEDURES SHALL BE
DEFINED. EGRESS PATHS SHALL BE FREE OF DEBRIS; DESIGNATED ELEVATORS
SHALL BE USED DURING SCHEDULED TIMES; AND ONLY AUTHORIZED
PERSONNEL SHALL BE ALLOWED TO ENTER THE CONSTRUCTION ZONE. SIGNAGE
SHALL DIRECT PEDESTRIAN TRAFFIC AWAY FROM THE CONSTRUCTION AREA AND
MATERIALS.
4. CONTRACTOR SHALL USE TWO CARTS TO TRANSFER CONSTRUCTION
MATERIAL IN AND OUT OF THE PROJECT - A CLEAN CART SHALL BE USED; THE NOT-
SO-CLEAN CART SHALL BE USED BETWEEN THE MAIN ENTRY AND THE
CONSTRUCTION STAGING/PREP AREA.
4A. DEMOLITION DEBRIS: DEBRIS SHALL BE REMOVED IN CARTS WITH TIGHTLY
FITTED COVERS, USING DESIGNATED TRAFFIC ROUTES. EFFORTS SHALL BE MADE
TO MINIMIZE USE OF ELEVATORS WITH AN EMPHASIS ON TRANSPORT DURING THE
LOWEST PERIOD OF ACTIVITY. DEBRIS SHALL BE REMOVED DAILY AND AT TIMES
SPECIFIED BY THE VAMC. IF CHUTES ARE USED TO DIRECT DEBRIS OUTSIDE, HIGH
EFFICIENCY PARTICULATE AIR (HEPA) FILTERED NEGATIVE AIR MACHINES SHALL BE
USED, AND THE CHUTE OPENING SHALL BE SEALED WHEN NOT IN USE. FILTERS
SHALL BE BAGGED AND SEALED BEFORE BEING TRANSPORTED OUT OF THE
CONSTRUCTION AREA. THE CONTRACTOR SHALL NOT HAUL DEBRIS THROUGH
PATIENT-CARE AREAS WITHOUT PRIOR APPROVAL OF THE COR.
4B. EXTERIOR WINDOWS: WINDOWS SHALL BE SEALED TO MINIMIZE
INFILTRATION FROM ANY ADJACENT EXCAVATION DEBRIS.
ICRA NOTES
VENTILATION AND ENVIRONMENTAL CONTROLS
5. AIR SYSTEM FLOW: THE COR VERIFY AND ACKNOWLEDGE
CONTRACTOR WHETHER THE CONSTRUCTION AREA USES
FRESH/OUTSIDE OR RE-CIRCULATED AIR; FILTERS SHALL BE
ADDED OR RETURN VENTS COVERED AS NEEDED WITH FILTER
MATERIAL OR PLASTIC. AIR MUST FLOW FROM CLEAN TO DIRTY
AREAS.
5A. NEGATIVE AIR PRESSURE: THE AIR WITHIN THE
CONSTRUCTION AREA SHALL BE NEGATIVE WITH RESPECT TO
SURROUNDING AREAS AND WITH NO DISRUPTION OF AIR
SYSTEMS OF ADJACENT AREAS. USE OF THE NEGATIVE AIR
PRESSURE SYSTEM WITHIN THE ENCLOSURE TO REMOVE DUST
SHALL PASS AIR THROUGH AN INDUSTRIAL GRADE, PORTABLE
HEPA FILTER CAPABLE OF FILTRATION RATES OF 300-800 CUBIC
FEET PER MINUTE (FT3/MIN), OR EXHAUST AIR DIRECTLY TO THE
OUTSIDE IF APPROVED BY VAMC. IF EXHAUST SHALL BE TIED
INTO A RE-CIRCULATED AIR SYSTEM, A PRE-FILTER AND HEPA
FILTER SHALL BE USED BEFORE EXHAUST TO PREVENT
CONTAMINATION OF THE DUCTS.
5B. ADJACENT AREAS: THE STATUS OF SEALED
PENETRATIONS AND INTACT CEILING SHALL BE VERIFIED DAILY.
5C. AIR EXCHANGE RATES AND PRESSURE RELATIONSHIPS:
VAMC AND CONTRACTOR SHALL VERIFY AND MAINTAIN PROPER
RATES IN CRITICAL AREAS NEAR CONSTRUCTION ACTIVITY AND
ENSURE AIR IS NOT BEING RE-CIRCULATED WITHOUT
FILTRATION FROM THE CONSTRUCTION AREA ELSEWHERE.
PROVIDE AIR PRESSURE TESTING THROUGHOUT THE PROJECT
IN THE FREQUENCY AS IDENTIFIED BY THE COR.
EXISTING WALL TO REMAIN
EXISTING DOOR TO REMAIN
EXISTING WINDOW TO REMAIN
ICRA LEGEND
TEMPORARY DOOR
TEMPORARY PLASTIC BARRIER
WITH ZIPPER ENTRY
STICKY MAT
Scale: 1/2" = 1'-0"
TYPICAL CONSTRUCTION PLAN LAYOUT
Scale: 1/2" = 1'-0"
ICRA MOBILE CONTAINMENT CART
Scale: 3" = 1'-0"
ILSM CONSTRUCTION EGRESS SIGNAGE
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:0
:5
A
M C
U s e rs
\c th o m p s o n
\D o c u m e n ts \A
-1
-T u s k e g e e
B ld g
R e n o c th o m p s o n
B V
E
.r v t
G-201
BLDG 10 FIRST FLOOR ICRA PLAN
5 9CET
RENOVATE BUILDING 10
CENTRAL ALABAMA VETERANS
HEALTH CARE SYSTEM, EAST CAMPUS
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083
MAY 9, 2025
100% BID DOCUMENTS
619A4-23-10522-139
DJR
Scale: 1/8" = 1'-0"
FIRST FLOOR ICRA PLAN
Scale: 3/4" = 1'-0"
ICRA BARRIER WALL TYPE
1 CONSTRUCTION ENTRANCE.
2 ICRA VESTIBULE FOR PPE CHANGE OF
CLOTHING.
3 NON-RATED TEMPORARY BARRIER, TYPE B.
4 NON-RATED TEMPORARY DOOR.
5 STICKY MATS.
NORTH
0 4 8 16
5070L
IC
E N
S E D A RC H I T ECT
DA
V ID J . REICHARD
NOR T H CA RO L I NA
1234678 5910
567891011
DN
BLDG 4A BASEMENT
BLDG 4 BASEMENT FLOOR
1 2
AREA OF WORK
M A
T C
H L
IN
E
EXISTING UNDERGROUND
CONDUIT, REFER TO LOW
VOLTAGE
G-201
ABOVE CEILING WORK,
REFER TO LOW VOLTAGE
EXISTING WALL TO REMAIN
EXISTING DOOR TO REMAIN
EXISTING WINDOW TO REMAIN
ICRA LEGEND
TEMPORARY DOOR
TEMPORARY PLASTIC BARRIER
WITH ZIPPER ENTRY
STICKY MAT
LEGEND
EXISTING BUILDING
NEW FLOOR SLAB
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:0
:5
A
M C
U s e rs
\c th o m p s o n
\D o c u m e n ts \A
-1
-T u s k e g e e
B ld g
R e n o c th o m p s o n
B V
E
.r v t
G-202
BLDG 4A AND 4 BASEMENT ICRA PLAN
6 9CET
RENOVATE BUILDING 10
CENTRAL ALABAMA VETERANS
HEALTH CARE SYSTEM, EAST CAMPUS
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083
MAY 9, 2025
100% BID DOCUMENTS
619A4-23-10522-139
DJR
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
4A
4 2 3 3A
Scale: 1/16" = 1'-0"
BLDG 4A AND BLDG 4 BASEMENT ICRA PLAN
NORTH
0 4 8 16
1 TEMPORARY PLASTIC BARRIER WITH ZIPPER
ENTRY, TYP.
2 STICKY MAT, TYP.
A. COORDINATE WITH COR/VA FOR ABOVE CEILING
WORK IN CORRIDORS.
B. REFER TO LOW VOLTAGE DRAWINGS FOR
SCOPE OF WORK
5070L
IC
E N
S E D A RC H I T ECT
DA
V ID J . REICHARD
NOR T H CA RO L I NA
BLDG 3A PENTHOUSE
AREA OF
WORK
EXISTING WALL TO REMAIN
EXISTING DOOR TO REMAIN
EXISTING WINDOW TO REMAIN
ICRA LEGEND
TEMPORARY DOOR
TEMPORARY PLASTIC BARRIER
WITH ZIPPER ENTRY
STICKY MAT
AREA OF WORK
BLDG 3A FIRST FLOOR
AREA OF WORK
BLDG 3A BASEMENT FLOOR
BLDG 2 BASEMENT FLOOR
M A
T C
H L
IN
E
ABOVE CEILING WORK,
REFER TO LOW VOLTAGE
BLDG 3 BASEMENT FLOOR
LEGEND
EXISTING BUILDING
NEW FLOOR SLAB
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:0
:5
A
M C
U s e rs
\c th o m p s o n
\D o c u m e n ts \A
-1
-T u s k e g e e
B ld g
R e n o c th o m p s o n
B V
E
.r v t
G-203
BLDG 2 BASEMENT, BLDG 3A
BASEMENT, FIRST FLOOR AND
PENTHOUSE ICRA PLANS
7 9CET
RENOVATE BUILDING 10
CENTRAL ALABAMA VETERANS
HEALTH CARE SYSTEM, EAST CAMPUS
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083
MAY 9, 2025
100% BID DOCUMENTS
619A4-23-10522-139
DJR
N
AREA OF WORK
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
4A
4 2 3 3A
Scale: 1/16" = 1'-0"
EXISTING BUILDING ICRA PLAN
NORTH
0 4 8 16
1 TEMPORARY PLASTIC BARRIER WITH ZIPPER
ENTRY, TYP.
2 STICKY MAT, TYP.
Scale: 1/16" = 1'-0"
EXISTING BUILDING ICRA PLAN
Scale: 1/16" = 1'-0"
EXISTING BUILDING ICRA PLAN
NORTH
0 4 8 16
NORTH
0 4 8 16
A. COORDINATE WITH COR/VA FOR ABOVE CEILING
WORK IN CORRIDORS.
B. REFER TO LOW VOLTAGE DRAWINGS FOR
SCOPE OF WORK
5070L
IC
E N
S E D A RC H I T ECT
DA
V ID J . REICHARD
NOR T H CA RO L I NA
DN
136 SF
OIT
62 SF
TLT
50 SF
STF TLT
46 SF
TLT
387 SF
STAFF LOUNGE
671 SF
SHARED
CONFERENCE/
CLASSROOM
46 SF
HAC
81 SF
QUIET ROOM
83 SF
VESTIBULE
130 SF
102D
TELERETINAL
113 SF
EDUCATOR
OFFICE
91 SF
102C
TELEHEALTH
SUPERVISOR
OFFICE
75 SF
102A
CHECK-IN
108 SF
102F
TELEHEALTH
EXAM ROOM
128 SF
102H
TELEHEALTH
EXAM ROOM
99 SF
102G
TELEHEALTH
TCT ROOM
115 SF
102I
TELEHEALTH
TCT ROOM
64 SF
ELEC
120 SF
WHOLE HEALTH
SUPERVISOR
OFFICE
93 SF
VESTIBULE
78 SF
TELEHEALTH
WAITING
FEC FEC
FEC
FEC
FEB
66 SF
E01
ELEV.
145 SF
SHARED OFFICE
144 SF
C-04
CORRIDOR
106 SF
101A
ELEV. LOBBY
610 SF
LOBBY
10 SF
102B
COPY AREA
S
F
C -0
S U
IT
E
C O
R R
356 SF
C-03
CORRIDOR
188 SF
S01
STAIR 1
OPENING ABOVE
K
E L E
C
102J
STORAGE
56 SF
102E
TLTC
-0
C O
R R
ID
O
R
C-01
CORRIDOR
B C C.1 C.3 C.6 D ED.1 F
4.8
CAPACITYCLR
EXTERIOR
EXIT
33" 275N E
W S
ID
E
W A
L K
NEW SIDEWALK
NEW RAMPEXISTING
SIDEWALK
DN
X Y
N E
W S
ID
E
W A
L
K FEC
A
B
B
CAPACITYCLR
EXTERIOR
EXIT
33" 124
CAPACITYCLR
EXTERIOR
EXIT
37" 180
1 2
55"
UPUP
DN
S02
STAIR 2
32"
A.1 A.9
0.9
E.1 E.9
ASSEMBLY
ASSEMBLY
CAPACITYCLR
EXIT
36" 160
D E
A D
E N
D C
O R
R . L
E N
G
TH
: 5 0'
-0
E.5
32''
36''
EXIT LIGHT
EGRESS PATH
EGRESS PATH TAG
EGRESS IDENTIFICATION
FIRE EXTINGUISHER BRACKET
FIRE EXTINGUISHER CABINET
XXX
FEB
FEC
CAPACITYCLR
EXTERIOR
EXIT
XX" ###
EXIT
IDENTIFICATION
EGRESS CLEAR
WIDTH
EGRESS
CAPACITY
A
CRAWL SPACE
CLEAN CRAWL
SPACE TYP.
FEB
PIT LADDER
SUMP PUMP; SEE
PLUMBING DWGS.
MECH
SHAFT
ABOVE1085 SF
B03
MECHANICAL
ROOM B
68 SF
B01
ELEV EQUIP
198 SF
B02
MECHANICAL
ROOM A
FEB
B C C.1 C.3 C.6 D ED.1 F
FEB
4.8
MECH
SHAFT
ABOVE
X Y
ENTRY
PORCH
ABOVE
A
EXISTING
STAIR ABOVE
5'-2"
CLEAN CRAWL
SPACE TYP.
CLEAN CRAWL
SPACE TYP.
CLEAN CRAWL
SPACE TYP.
UP
UP
UP
S02
STAIR 2
E01
ELEV.
A.1 A.9
0.9
E.1 E.9
DEAD END CORR.
20'-4 1/2"
E.5
LEGEND
EXISTING BUILDING
NEW FLOOR SLAB
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:2
:1
P
M C
U s e rs
\s m is e v ic h \D o c u m e n ts
\A
-1
-T u s k e g e e B ld g
R e n o s m is e v ic h .r v t
LS101
BASEMENT AND FIRST FLOOR LIFE
SAFETY PLANS
8 9CET
RENOVATE BUILDING 10
CENTRAL ALABAMA VETERANS
HEALTH CARE SYSTEM, EAST CAMPUS
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083
MAY 9, 2025
100% BID DOCUMENTS
619A4-23-10522-139
DJR
NORTH
0 4 8 16
Scale: 1/8" = 1'-0"
FIRST FLOOR LIFE SAFETY PLAN
LIFE SAFETY LEGEND
Scale: 1/8" = 1'-0"
BASEMENT FLOOR LIFE SAFETY PLAN
NORTH
0 4 8 16
EGRESS PATH "A"
PATH ID LENGTH
A 69' - 8"
TOTAL PATH LENGTH 69' - 8"
EGRESS PATH "A"
PATH ID LENGTH
A 61' - 6"
TOTAL PATH LENGTH 61' - 6"
EGRESS PATH "B"
PATH ID LENGTH
B 94' - 8"
TOTAL PATH LENGTH 94' - 8"
1 MECHANICAL SHAFT.
2 NEW WATER COOLER / DISPENSER.
A. SEE SHEET A-001 FOR SYMBOLS AND
ABBREVIATIONS.
B. SEE CIVIL DRAWINGS FOR INFORMATION INCLUDING
CONCRETE SIDEWALKS, CONCRETE PADS, AND
PARKING CONFIGURATIONS.
C. SEE STRUCTURAL DRAWINGS FOR FRAMING
INFORMATION & FRAMING DIMENSIONS. ALL
DIMENSIONS ARE FOR REFERENCE ONLY - VERIFY
ALL FRAMING WITH STRUCTURAL DRAWINGS.
D. REFER TO PLUMBING DRAWINGS FOR INFORMATION
CONCERNING PLUMBING FIXTURES AND PIPING
SYSTEM(S).
E. REFER TO MECHANICAL DRAWINGS FOR
INFORMATION CONCERNING HVAC SYSTEM(S).
F. REFER TO TECHNOLOGY DRAWINGS FOR
INFORMATION CONCERNING COMMUNICATION
SYSTEM(S).
G. REFER TO FIRE PROTECTION DRAWINGS FOR FIRE
ALARM NOTIFICATION AND EMERGENCY EGRESS
LIGHTING LOCATIONS.
H. REFER TO PARTITION TYPES FOR FURTHER FIRE
SEPARATION REQUIREMENTS.
I. CONTRACTOR TO PROVDE ALL ADDITIONAL FRAMING
NECESSARY FOR ALL OPENINGS AND
SUPPLEMENTAL FRAMING ABOVE PARTITIONS.
J. ALL FIRE RATED ASSEMBLIES SHALL BE INSTALLED IN
STRICT ACCORDANCE WITH TESTED ASSEMBLIES
INDICATED.
K. EXTEND FIRE RATED PARTITIONS, BARRIERS, AND
OTHER SEPARATIONS TO BOTTOM OF ROOF/FLOOR
DECK ABOVE (OR AS DIRECTED BY UL ASSEMBLY).
SEAL JOINT BETWEEN EDGES OF PARTITION WITH
FIRE RATED SEALANT AND/OR INTUMESCENT
ASSEMBLY.
L. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES
SHALL BE FIRESTOPPED IN ACCORDANCE WITH
APPROVED MANUFACTURER'S DETAIL FOR
LOCATION, TYPE OF CONSTRUCTION, PENETRATING
ITEM AND RATING REQUIRED.
M. ALL DUCTWORK, DIFFUSERS AND GRILLES
PENETRATING FIRE-RATED WALLS, CEILINGS AND
FLOORS SHALL HAVE THE APPROPRIATE TYPE OF
FIRE/SMOKE DAMPER IN ACCORDANCE WITH THE
TYPE OF CONSTRUCTION BEING PENETRATED AND
THE FIRE/SMOKE RATING REQUIRED.
N. ALL LIGHT FIXTURES AND ELECTRICAL DEVICES
PENETRATING FIRE-RATED ASSEMBLIES SHALL BE
UL-LISTED FOR INSTALLATION IN THE ASSEMBLY OR
SHALL BE INSTALLED SUCH THAT THE FIRE-RATING IS
NOT COMPROMISED.
O. SMOKE RESISTANT CONSTRUCTION SHALL MEET THE
REQUIREMENTS OF ALL APPLICABLE CODES. AREA
SHALL BE SEPARATED FROM THE REMAINDER OF
THE BUILDING BY CONSTRUCTION CAPABLE OF
RESISTING THE PASSAGE OF SMOKE. THE
PARTITIONS SHALL EXTEND FROM THE FLOOR TO
THE UNDERSIDE OF THE FLOOR OR ROOF ASSEMBLY
ABOVE. DOORS SHALL BE SELF OR AUTOMATIC
CLOSING. DOORS SHALL NOT HAVE AIR TRANSFER
OPENINGS AND SHALL NOT BE UNDERCUT IN EXCESS
OF CLEARANCE PERMITTED WITH ACCORDANCE TO
NFPA 80.
P. SEE SHEET G-004 FOR CODE SUMMARY
INFORMATION.
OCCUPANT LOAD
BUSINESS OCCUPANCY:
BASEMENT - 1,650 GSF/150 = 11 OCC.
FIRST FLOOR - 5,329 GSF/150 = 36 OCC.
SECOND FLOOR - 2,087 GSF/150 = 14 OCC.
ASSEMBLY OCCUPANCY:
FIRST FLOOR - 671 GSF/15 = 45 OCC.
SECOND FLOOR - 3,013 GSF/15 = 201 OCC.
BUSINESS OCCUPANCY ALLOWABLE TRAVEL DISTANCE:
300'-0" MAXIMUM
DEADEND LIMIT: 50'-0" MAXIMUM
COMMON PATH OF TRAVEL LIMIT: 100'-0" MAXIMUM
509 SF
GROUP ROOM 1
714 SF
GROUP ROOM 2
716 SF
GROUP ROOM 3
522 SF
GROUP ROOM 4
88 SF
COACHING
97 SF
COACHING
122 SF
MASSAGE
50 SF
TOILET
118 SF
OIT
552 SF
CLASSROOM
44 SF
TOILET
90 SF
COACHING
21551 SF
STORAGE
UP UP
OPEN TO BELOW
39 SF
STOR
638 SF
CORRIDOR
S
F
C O
R R
ID
O
R
S
F
C O
R R
ID
O
R 66 SF
E01
ELEV.
FEC
FEC
FEC
E L E
C
E L E
C 220
HAC
188 SF
S01
STAIR 1
B C C.1 C.3 C.6 D ED.1 F
4.8
36" 180 36" 180
X Y
A B
LOW ROOF BELOW
LOW ROOF BELOW
MAIN ENTRY
ROOF BELOW
CAPACITYCLR
EXIT
FEC
S02
STAIR 2 CAPACITYCLR
EXIT
A.1 A.9
0.9
E.1 E.9
ASSEMBLY
ASSEMBLY
ASSEMBLY
ASSEMBLY
ASSEMBLY
E.5
EXIT LIGHT
EGRESS PATH
EGRESS PATH TAG
EGRESS IDENTIFICATION
FIRE EXTINGUISHER BRACKET
FIRE EXTINGUISHER CABINET
XXX
FEB
FEC
CAPACITYCLR
EXTERIOR
EXIT
XX" ###
EXIT
IDENTIFICATION
EGRESS CLEAR
WIDTH
EGRESS
CAPACITY
LEGEND
EXISTING BUILDING
NEW FLOOR SLAB
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:2
:1
P
M C
U s e rs
\s m is e v ic h \D o c u m e n ts
\A
-1
-T u s k e g e e B ld g
R e n o s m is e v ic h .r v t
LS102
SECOND FLOOR LIFE SAFETY PLAN
9 9CET
RENOVATE BUILDING 10
CENTRAL ALABAMA VETERANS
HEALTH CARE SYSTEM, EAST CAMPUS
2400 HOSPITAL ROAD
TUSKEGEE, AL 36083
MAY 9, 2025
100% BID DOCUMENTS
619A4-23-10522-139
DJR
NORTH
0 4 8 16
Scale: 1/8" = 1'-0"
SECOND FLOOR LIFE SAFETY PLAN
LIFE SAFETY LEGEND
1 MECHANICAL SHAFT.
EGRESS PATH "A"
PATH ID LENGTH
A 61' - 8"
TOTAL PATH LENGTH 61' - 8"
EGRESS PATH "B"
PATH ID LENGTH
B 72' - 9"
TOTAL PATH LENGTH 72' - 9"
A. SEE SHEET A-001 FOR SYMBOLS AND
ABBREVIATIONS.
B. SEE CIVIL DRAWINGS FOR INFORMATION INCLUDING
CONCRETE SIDEWALKS, CONCRETE PADS, AND
PARKING CONFIGURATIONS. CIVIL BACKGROUND
DRAWING INFORMATION IS FOR REFERENCE ONLY.
C. SEE STRUCTURAL DRAWINGS FOR FRAMING
INFORMATION & FRAMING DIMENSIONS. ALL
DIMENSIONS ARE FOR REFERENCE ONLY - VERIFY
ALL FRAMING WITH STRUCTURAL DRAWINGS.
D. REFER TO PLUMBING DRAWINGS FOR INFORMATION
CONCERNING PLUMBING FIXTURES AND PIPING
SYSTEM(S).
E. REFER TO MECHANICAL DRAWINGS FOR
INFORMATION CONCERNING HVAC SYSTEM(S).
F. REFER TO TECHNOLOGY DRAWINGS FOR
INFORMATION CONCERNING COMMUNICATION
SYSTEM(S).
G. REFER TO FIRE PROTECTION DRAWINGS FOR FIRE
ALARM NOTIFICATION AND EMERGENCY EGRESS
LIGHTING LOCATIONS.
H. REFER TO PARTITION TYPES FOR FURTHER FIRE
SEPARATION REQUIREMENTS.
I. CONTRACTOR TO PROVDE ALL ADDITIONAL FRAMING
NECESSARY FOR ALL OPENINGS AND
SUPPLEMENTAL FRAMING ABOVE PARTITIONS.
J. ALL FIRE RATED ASSEMBLIES SHALL BE INSTALLED IN
STRICT ACCORDANCE WITH TESTED ASSEMBLIES
INDICATED.
K. EXTEND FIRE RATED PARTITIONS, BARRIERS, AND
OTHER SEPARATIONS TO BOTTOM OF ROOF/FLOOR
DECK ABOVE (OR AS DIRECTED BY UL ASSEMBLY)
AND TO EXTERIOR WALL. SEAL JOINT BETWEEN
EDGES OF PARTITION WITH FIRE RATED SEALANT
AND/OR INTUMESCENT ASSEMBLY.
L. ALL PENETRATIONS OF FIRE-RATED ASSEMBLIES
SHALL BE FIRE-SEALED IN ACCORDANCE WITH
APPROVED MANUFACTURER'S DETAIL FOR
LOCATION, TYPE OF CONSTRUCTION, PENETRATING
ITEM AND RATING REQUIRED.
M. ALL DUCTWORK, DIFFUSERS AND GRILLES
PENETRATING FIRE-RATED WALLS, CEILINGS AND
FLOORS SHALL HAVE THE APPROPRIATE TYPE OF
FIRE/SMOKE DAMPER IN ACCORDANCE WITH THE
TYPE OF CONSTRUCTION BEING PENETRATED AND
THE FIRE/SMOKE RATING REQUIRED.
N. ALL LIGHT FIXTURES AND ELECTRICAL DEVICES
PENETRATING FIRE-RATED ASSEMBLIES SHALL BE
UL-LISTED FOR INSTALLATION IN THE ASSEMBLY OR
SHALL BE INSTALLED SUCH THAT THE FIRE-RATING IS
NOT COMPROMISED.
O. SMOKE RESISTANT CONSTRUCTION SHALL MEET THE
REQUIREMENTS OF ALL APPLICABLE CODES. AREA
SHALL BE SEPARATED FROM THE REMAINDER OF
THE BUILDING BY CONSTRUCTION CAPABLE OF
RESISTING THE PASSAGE OF SMOKE. THE
PARTITIONS SHALL EXTEND FROM THE FLOOR TO
THE UNDERSIDE OF THE FLOOR OR ROOF ASSEMBLY
ABOVE. DOORS SHALL BE SELF OR AUTOMATIC
CLOSING. DOORS SHALL NOT HAVE AIR TRANSFER
OPENINGS AND SHALL NOT BE UNDERCUT IN EXCESS
OF CLEARANCE PERMITTED WITH ACCORDANCE TO
NFPA 80.
P. SEE SHEET G-004 FOR CODE SUMMARY
INFORMATION.
OCCUPANT LOAD
BUSINESS OCCUPANCY:
BASEMENT - 1,650 GSF/150 = 11 OCC.
FIRST FLOOR - 5,329 GSF/150 = 36 OCC.
SECOND FLOOR - 2,087 GSF/150 = 14 OCC.
ASSEMBLY OCCUPANCY:
FIRST FLOOR - 671 GSF/15 = 45 OCC.
SECOND FLOOR - 3,013 GSF/15 = 201 OCC.
BUSINESS OCCUPANCY ALLOWABLE TRAVEL DISTANCE:
300'-0" MAXIMUM
DEADEND LIMIT: 50'-0" MAXIMUM
COMMON PATH OF TRAVEL LIMIT: 100'-0" MAXIMUM
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
20" OAK
22" OAK
26" OAK
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
UG/E UG/E UG/E UG/E UG/E UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
15" OAK
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG
/E
UG
/E
UG
/E
UG
/E
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LODLO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LOD
LOD
LOD
LODLODLOD
LO
D
LO
D
LO
D
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LODLOD
LO
D
LO
D
LOD
W
W
W
W
W
BUILDING 10
BUILDING 4-A
APPROX. FFE
428.84
APPROX. FFE
428.96
APPROX. FFE
429.01
APPROX. 2ND
FLOOR FFE
439.45
APPROX. FFE
428.95
14" MAPLE
38" OAK
36" OAK
34" OAK
34" OAK
36" OAK
CONC. WALL
W/ GRATE
29.2'
36.0'
23.7'
47.2'
32.1'
23.6'
29.2'
4.9'
4.9'8.8'
23.7'
29.1'
23.6' 4.9'
9.2'
28.5' 4.8'
9.4'
23.7'
8.8'
29.2'
23.6'
35.9'32.2'
22.7'
11.2'
5.0' 20.9'
8.5'
32.3'
8.5'
42.7'
59.9'
32.1'
32.0'
17.4'
49.9'
0.7'
54.9' 36.4'
5.8'
59.9'
SS-T6
FIBER
MARKER
POST
FIBER
MARKER
POST
SD-T1
SD-T3
SS-TB
SS-TA
UG/E
UG/E
UG/E
UG/E
UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E
UG/E
UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E
UG
/E
UG
/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E UG/E
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
STSTSTSTSTSTST
ST
ST
ST
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG/C
UG/C
UG/C
UG/CUG/CUG/CUG/CUG/CUG/CUG/CUG/CUG/CUG/CUG/CUG/CUG/CUG/CUG/CUG/CUG/CUG/CUG/CUG/C
ST
ST
ST
UG/E
UG/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG
/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG
/E
UG
/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
W W
W W
W W
W W
W W
W W
W W
W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W W
W
W W
W W
W W
W W
W W
W W
W W
W
W W
W W
W W
W W
W W
W W
W
W W
W W
W W
W W
W W
W W
W
20" OAK
16" RED MAPLE
8" DOGWOOD
42" OAK
9-4" PIPES WITH
COMMUNICATION
LINES
OLD ROOF
DRAIN
0.4'
TRENCH DRAIN
AND GRATE
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
UG
/C
433432
423423
UG/E
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SD-T4
UG/C UG/C UG/C UG/C UG/C
UG/C
UG/C
UG/C
UG/C
UG/C
UG/C
UG/C
UG/C
UG/C
UG/C
UG/C
UG/C UG/C UG/C UG/C UG/C UG/C UG/C UG/C UG/C UG/C UG/C
22" OAK
26" OAK
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
UG/E
UG/E
UG/E
UG/E
UG/E UG/E UG/E UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
15" OAK
15" OAK
18" OAK
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG/E
UG
/E
UG
/E
UG
/E
UG
/E
HOSPITAL ROAD
SIGN-BUILDING 9 &
10 PROJECT
29.2'
36.0'
23.7'
47.2'
32.1'
23.6'
29.2'
4.9'
4.9'8.8'
23.7'
29.1'
23.6' 4.9'
9.2'
28.5' 4.8'
9.4'
23.7'
8.8'
29.2'
23.6'
35.9'32.2'
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LO
D
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD
LOD
LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LO
D LOD
LO
D
LOD
LO
D
LOD LOD LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD
LOD
LOD
LODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLODLOD
LOD
LOD
LOD
LOD
LOD
LODLODLOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LO
D
LODLODLODLODLODLOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LOD
LOD
LOD
LODLODLOD
LO
D
LO
D
LO
D
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LOD
LODLOD
EXISTING FDC
SS
SS
SS
SS
SS
SS
SS
101010
2 1
STORM DRAIN GRATE, SD-1
TOP EL.: 425.48
6" VCP INV-IN (NW) EL.: 423.34
6" VCP INV-IN (NE) EL.: 423.33
6" VCP INV-IN (SW) EL.: 423.31
6" VCP INV-OUT (SE) EL.: 422.87
STORM DRAIN GRATE, SD-T1
TOP EL.: 422.55
8" VCP INV-IN (NW) EL.: 418.93
8" VCP INV-IN (NE) EL.: 418.89
12" VCP INV-OUT (SE) EL.: 418.72
STORM DRAIN GRATE, SD-T2
TOP EL.: 423.09
12" VCP INV-IN (NW) EL.: 418.55
12" VCP INV-OUT (SE) EL.: 418.44
STORM DRAIN GRATE, SD-T3
TOP EL.: 423.20
6" VCP INV-IN…