This document is an Appendix P for Building 46 at the Tuscaloosa VA Medical Center, containing a comprehensive asbestos re-inspection report. The report details the findings of a 3-year asbestos re-inspection, identifying 16 homogeneous areas (HAs) within the building, with two areas confirmed as asbestos-containing material (ACM): HA 03 (12" vinyl composition floor tile and mastic in a connecting corridor) and HA 14 (downspout tar). Laboratory analysis by Safety Environmental Laboratories and Consulting, Inc. found no asbestos in the tested samples, though some areas contained non-asbestos materials like wollastonite.
The document includes detailed inspection documentation, sample location plans, photographic evidence, and estimated abatement costs. For the identified ACM areas, the report recommends managing the materials in place until they are impacted by planned renovations or repair activities. The estimated abatement costs are $2,250 for the vinyl composition floor tile and mastic (approximately 450 square feet) and $200 for the downspout tar. The inspection was conducted on July 16, 2014, by inspector E. Hyde, as part of the SELC Project #2014-1108 for the Tuscaloosa VA Medical Center.
View the file
Other files for this federal contract opportunity
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX P
BUILDING 46
CHAPEL
INCLUDED IN APPENDIX P:
P‐1 – Annual Asbestos Re‐inspection Documentation
P‐2 – Homogeneous Area / Sample Summary Table
P‐3 – Sample/ACM Location Plans
P‐4 – PLM Laboratory Reports
P‐5 – Photographic Documentation
P‐6 – Estimated Asbestos Abatement Costs
P‐7 – Additional VAMC Supplied Notes/Information
APPENDIX P‐1
Annual Asbestos Re‐inspection
Documentation
BUILDING 46 HOMOGENEOUS AREA LIST
HA 01 = 9” FLOOR TILE (BROWN) ‐ REMOVED
HA 02 = 12” FLOOR TILE (GREEN) ‐ REMOVED
HA 03 = 12” FLOOR TILE (GREEN WITH DARK GREEN)
HA 04 = CEILING TILE – 1’ X 1’ TONGUE AND GROOVE – NAD
HA 05 = CEILING TILE – 2’ X 2’ GOOVED AND PINHOLE (OLD) – NAD
HA 06 = CEILING TILE – 2’ X 2’ GOOVED AND PINHOLE (NEW) – NAD
HA 07 = CEILING TILE – 2’ X 2’ WHITE – NAD
HA 08 = ROOFING SHINGLES – NAD
HA 09 = ROOFING TAR – ROOF ‐ REMOVED
HA 10 = ROOFING FELT – NAD
HA 11 = PIPE FITTING INSULATION (HARD) ON FIBERGLASS RUNS ON DOMESTIC WATER AND STEAM
PIPING SYSTEMS = NAD
HA 12 = PIPE INSULATION, BLACK MASTIC – NAD
HA 13 = FLEXIBLE DUCT CONNECTOR ‐ REMOVED
HA 14 = DOWNSPOUT TAR
HA 15 = WHITE/OFF‐WHITE MASTIC ON RAW ENDS AND SEAMS OF INSULATED PIPING
HA 16 = GRAY‐GREEN MASTIC APPLIED TO SEAMS OF AHU DUCTWORK
HA = HOMOGENEOUS AREA
HA = ASBESTOS CONTAINING MATERIAL
NAD = NO ASBESTOS DETECTED
HA (ITALICIZED) = IDENTIFIED BY SELC DURING 2014 RE‐INSPECTION. OTHER HOMOGENEOUS AREAS
IDENTIFIED DURING PREVIOUS RE‐INSPECTIONS/INSPECTIONS BY OTHER CONSULTANTS.
Tuscaloosa VA Medical Center Annual Asbestos Re-Inspection Documentation
Physical Assessment (check all that apply) Damaged or significantly damaged TSI, ACM or ACE Damaged friable surfacing ACM or ACM Significantly damaged friable surfacing ACM or ACE Damaged or significantly damaged friable miscellaneous ACM or ACE ACM or ACE with potential for damage ACM or ACE with potential for significant damage Any remaining friable ACM or ACE X No asbestos detected
Classification of Hazard Potential (circle one)
Hazard Rank ACM Condition ACM Disturbance Potential
7 Significantly Damaged Any 6 Damaged Potential for Significant Damage 5 Damaged Potential for Damage 4 Damaged Low Potential for Damage 3 Good Significant Potential for Damage 2 Good Potential for Damage 1 Good Low Potential for Damage
Current Inspection Comments/Condition if Changed: Removed. Carpet or Centiva flooring over concrete in Rooms1, 3, 7-9, and 11. New 12” VCT over concrete in Corridor 5.
2009 Inspection Note: N/A
2002 Inspection Note: N/A
1991 Inspection Note: ACM or ACE with potential for damage. Rooms 1, 3, 5, 7-9 and 11. Rooms 7, 9, 11 under carpet
Recommendation Response Action (circle applicable actions) O&M Remove/Enclose/Encapsulate Evacuate/Restrict
Explain: N/A
Building #: 46 Homogeneous Area #: 01 Date: 7/16 & 23/14 Description: 9” x 9” Floor tile (brown) and mastic Inspector: E. Hyde
Damaged friable surfacing ACM or ACM Significantly damaged friable surfacing ACM or ACE Damaged or significantly damaged friable miscellaneous ACM or ACE ACM or ACE with potential for damage ACM or ACE with potential for significant damage
7 Significantly Damaged Any 6 Damaged Potential for Significant Damage 5 Damaged Potential for Damage 4 Damaged Low Potential for Damage 3 Good Significant Potential for Damage
Current Inspection Comments/Condition if Changed: Removed. New 12” VCT over concrete in Room 6.
2009 Inspection Note: N/A
2002 Inspection Note: N/A
1991 Inspection Note: ACM or ACE with potential for damage. Room 6 (240 SF)
Explain: N/A
Building #: 46 Homogeneous Area #: 02 Date: 7/16 & 23/14 Description: 12” x 12” Floor tile (green) and mastic Inspector: E. Hyde
Damaged friable surfacing ACM or ACM Significantly damaged friable surfacing ACM or ACE Damaged or significantly damaged friable miscellaneous ACM or ACE X ACM or ACE with potential for damage ACM or ACE with potential for significant damage
No asbestos detected
7 Significantly Damaged Any 6 Damaged Potential for Significant Damage 5 Damaged Potential for Damage 4 Damaged Low Potential for Damage 3 Good Significant Potential for Damage
Current Inspection Comments/Condition if Changed: Removed from corridor 5B portion inside sliding glass doors of chapel. However, HA 03 is present in connection corridor to Building 1.
2009 Inspection Note: N/A
1991 Inspection Note: ACM or ACE with potential for damage. Connecting corridor 5B (450 SF)
Explain: Manage in place until impacted by planned renovations or repair activities. Abate prior to or as part of planned renovation or repair activities.
Building #: 46 Homogeneous Area #: 03 Date: 7/16/14 Description: 12” x 12” Floor tile (green w/ dark green) & mastic Inspector: E. Hyde
Damaged friable surfacing ACM or ACM Significantly damaged friable surfacing ACM or ACE Damaged or significantly damaged friable miscellaneous ACM or ACE ACM or ACE with potential for damage ACM or ACE with potential for significant damage
7 Significantly Damaged Any 6 Damaged Potential for Significant Damage 5 Damaged Potential for Damage 4 Damaged Low Potential for Damage 3 Good Significant Potential for Damage
Current Inspection Comments/Condition if Changed: According to VAMC personnel, this roof was removed, and HA 09 abated in mid to late 2007s after sustained storm damage.
2009 Inspection Note: N/A
1991 Inspection Note: Any remaining friable ACM or friable suspected ACM or ACE. Roof-200 SF.
Explain: N/A
Building #: 46 Homogeneous Area #: 09 Date: 7/16/14 Description: Roofing tar Inspector: E. Hyde
Damaged friable surfacing ACM or ACM Significantly damaged friable surfacing ACM or ACE Damaged or significantly damaged friable miscellaneous ACM or ACE ACM or ACE with potential for damage ACM or ACE with potential for significant damage
7 Significantly Damaged Any 6 Damaged Potential for Significant Damage 5 Damaged Potential for Damage 4 Damaged Low Potential for Damage 3 Good Significant Potential for Damage
Current Inspection Comments/Condition if Changed: Vinyl/rubber flexible duct connectors in mechanical room.
2009 Inspection Note: N/A
2002 Inspection Note: N/A
1991 Inspection Note: Any remaining friable ACM or friable suspected ACM or ACE. Mechanical Room (1 each)
Explain: N/A
Building #: 46 Homogeneous Area #: 13 Date: 7/16/14 Description: Flexible Duct Connector Inspector: E. Hyde
Damaged friable surfacing ACM or ACM Significantly damaged friable surfacing ACM or ACE Damaged or significantly damaged friable miscellaneous ACM or ACE X ACM or ACE with potential for damage ACM or ACE with potential for significant damage
No asbestos detected
7 Significantly Damaged Any 6 Damaged Potential for Significant Damage 5 Damaged Potential for Damage 4 Damaged Low Potential for Damage 3 Good Significant Potential for Damage
Current Inspection Comments/Condition if Changed: Most removed / no tar observed. However, one downspout outside mechanical room has HA 14. Fair condition.
2009 Inspection Note: N/A
1991 Inspection Note: Any remaining friable ACM or friable suspected ACM or ACE. Downspout joints (2 each)
Explain: Manage in place until impacted by planned renovations or repair activities. Abate prior to or as part of planned renovation or repair activities.
Building #: 46 Homogeneous Area #: 14 Date: 7/16 /14 Description: Downspout tar Inspector: E. Hyde
Damaged friable surfacing ACM or ACM Significantly damaged friable surfacing ACM or ACE Damaged or significantly damaged friable miscellaneous ACM or ACE ACM or ACE with potential for damage ACM or ACE with potential for significant damage
7 Significantly Damaged Any 6 Damaged Potential for Significant Damage 5 Damaged Potential for Damage 4 Damaged Low Potential for Damage 3 Good Significant Potential for Damage
Current Inspection Comments/Condition if Changed: White/off-white mastic at raw ends and seams of kraft-faced fiberglass steam and chiller piping in mechanical room. Samples B46-1 and B46-2.
2009 Inspection Note: N/A
1991 Inspection Note: N/A
Explain: N/A
Building #: 46 Homogeneous Area #: 15 Date: 7/16 /14 Description: White/off-white mastic on piping Inspector: E. Hyde
Damaged friable surfacing ACM or ACM Significantly damaged friable surfacing ACM or ACE Damaged or significantly damaged friable miscellaneous ACM or ACE ACM or ACE with potential for damage ACM or ACE with potential for significant damage
7 Significantly Damaged Any 6 Damaged Potential for Significant Damage 5 Damaged Potential for Damage 4 Damaged Low Potential for Damage 3 Good Significant Potential for Damage
Current Inspection Comments/Condition if Changed: Gray/green mastic applied at seams of externally un-insulated metal AHU ductwork in mechanical room. On reportedly newer ductwork.
Not present on presumably older ductwork. Sample B46-3
2009 Inspection Note: N/A
1991 Inspection Note: N/A
Explain: N/A
Building #: 46 Homogeneous Area #: 16 Date: 7/16 /14 Description: Gray-green AHU Duct Mastic Inspector: E. Hyde
APPENDIX P‐2
Homogeneous Area / Sample Summary Table
HOMOGENEOUS AREA / SAMPLE SUMMARY TABLE
PROJECT: 2014-1108 – BUILDING 46
HOMG.
AREA
(HA#)
HOMOGENEOUS AREA (HA)
DESCRIPTION & LOCATION
HA TYPE (AHERA)
EPA/OSHA CATG. (IF ACM)
CONDITION (IF ACM)
SAMPLE
NO.
ASBESTOS
CONTENT
SAMPLE
LOCATION
Mastic (white/off-white) applied at seams of kraft-faced fiberglass insulation on, and raw fiberglass ends of steam and chiller piping in the mechanical room.
Miscellaneous Material on TSI Not ACM
B46-1 None Detected Mechanical
Room – Steam Pipe
B46-2 None Detected Mechanical
Room – Chiller Pipe
Mastic (gray/green) applied at seams of externally un-insulated metal AHU ductwork in mechanical room.
Ductwork appears to be relatively new. No mastic observed on what appeared to be older ductwork in the mechanical room.
Miscellaneous ACM NESHAP Category 2 Non-Friable
ACM
OSHA Class II Work
Intact
B46-3 None Detected Mechanical Room
END OF
TABLE
Notes: 1. ** = Homogeneous area # previously identified by others.
2. If not demarked with an **, this is a new homogeneous area identified by SELC during this re-inspection
APPENDIX P‐3
Sample/ACM Location Plans
APPENDIX P‐4
PLM Laboratory Reports
Safety Environmental Laboratories and Consulting, Inc.
Page 1 of 2 Analyst Kris Parker – Asbestos Analyst
Technical Review Brian Ray – Asbestos Analyst
Quality Review Carol Findlay – Microscopy Manager
Asbestos Bulk Sample Analysis Report 989 Yeager Pkwy. Phone: (205) 823-6200 Pelham, AL 35124 Fax: (205) 823-9066
Customer:
989 Yeager Parkway Pelham, AL 35124
Sample Receipt Date: 08/06/2014
Sample Analysis Date: 08/07/2014
Telephone: 205-823-6200 Fax: 205-823-9066 Sample Report Date: 08/07/2014
Project Name:
Project Location:
VAMC Tuscaloosa Building 46
Asbestos Identification in Bulk Materials by Polarized Light Microscopy
EPA/600/R-93/116 July 1993 – Method for the Determination of Asbestos in Bulk Building Materials
SELC Project #: 2014-1108 Note: See Attached Notes and Descriptions Sheet for Applicable Abbreviations and Notes
Customer Sample No.
Lab Sample
No.
Sub-sample
No.
Layer No. Sample Location / Description
Homo-geneous (yes/no)
Asbestos % and Type
% Non-Asbestos Fibers
% Non- Fibrous Material
B46-1 29 N/A 1 Steam Pipe Mastic – Mechanical Room Pipe Mastic – White, Soft
N None Detected None Detected 100%
B46-2 30 N/A 1 Chiller Pipe Mastic – Mechanical Room Pipe Mastic – Tan, Hard
N None Detected 7% Wollastonite 93%
B46-3 31 N/A 1 Duct Seam Mastic – Mechanical Room Duct Mastic – Gray, Hard
N None Detected None Detected 100%
This report is FINAL This report is PRELIMINARY – pending final QC
Page 2 of 2 Analyst Kris Parker – Asbestos Analyst
Technical Review Brian Ray – Asbestos Analyst
Quality Review Carol Findlay – Microscopy Manager
Asbestos Bulk Sample Analysis Report 989 Yeager Pkwy. Phone: (205) 823-6200 Pelham, AL 35124 Fax: (205) 823-9066
PLM Notes and Descriptions
1. Upper detection limit: 100%. Lower detection limit: <1%.
2. Bulk Samples will be stored for 3 months and will then be disposed of in an approved EPA landfill.
3. Analysis of floor tile or any other resinously bound materials by polarized light microscopy (PLM) using EPA Method 600/R-93/116 dated July 1993 may yield false-negative results because of method limitations in separating closely bound fibers from matrix material and in detecting fibers of small length and/or diameter. When analysis of such materials by the EPA PLM Method yields negative results for the presence of asbestos we recommend utilizing alternative methods of identification such as Gravimetry, XRD or AEM.
4. Samples are not homogenized by SELC prior to analysis. Distinct material layers within a sample are analyzed and reported separately by SELC. When multiple products are submitted by the customer under one sample number, SELC indicates those distinct products as sub-samples. SELC retains all samples numbers but will designate a sample number to those that are not given a sample number by the customer.
5. Percentages given are based on a visual estimated calibration.
6. Safety Environmental Laboratories and Consulting, Inc. is a NVLAP accredited laboratory, Lab Code: 200873-0 (ISO/IEC Standard 17025:2005 Compliant).
7. Results relate only to the samples tested. All tests were performed under the scope of SELC’s NVLAP accreditation, unless indicated otherwise.
8. All samples were received in a condition suitable for analysis (“Good”), unless otherwise noted.
9. This report must not be used to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government.
10. Analytical Instrument: Olympus Polarized Light Microscope Series BH-2 Model BHT-002
APPENDIX P‐5
Photographic Documentation
Photographic Documentation – 3 Year Asbestos Re-inspection – Building 46
SELC Project #2014-1108 VAMC Tuscaloosa – Building 46 Page 1
PHOTOGRAPH 2
HA 03 – ACM 12” Vinyl composition floor tile and mastic in connecting corridor to Building 1.
PHOTOGRAPH 3
View of rubber/vinyl flexible duct connector in mechanical room, and grey/green mastic on seams of AHU ductwork (HA 16 – NAD).
PHOTOGRAPH 1
HA 03 – ACM 12” Vinyl composition floor tile and mastic in connecting corridor to Building 1.
PHOTOGRAPH 4
Piping insulated with kraft-faced fiberglass insulation in mechanical room. Mastic (HA 16 – NAD) is present at raw ends and seams of this piping.
APPENDIX P‐6
Estimated Asbestos Abatement Costs
BUILDING 46
ESTIMATED ASBESTOS ABATEMENT COSTS
HA
NUMBER(S) TYPE OF ACM
FRIABLE/
NON-
FRIABLE
APPROXIMATE
QUANTITY
ESTIMATED
ABATEMENT
COST
03 Vinyl composition floor tile and mastic
Non- Friable
~ 450 square feet $2,250
14 Downspout Tar Non- Friable
Observed on one down spout by mechanical room.
$200
Notes:
1. HA = Homogeneous area
2. ACM = Asbestos containing material
3. NP = Not provided
4. Costs provided are general estimates for information purposes only. A complete and specific cost estimate should be obtained from Alabama accredited asbestos abatement contractors prior to any abatement project.
5. Quantity and cost estimates are provided only for observable ACM/homogeneous area. Cost estimates are not provided for inaccessible portions/quantities of a homogeneous group.
APPENDIX P‐7
Additional VAMC Supplied Notes/Information