Text version

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

REFERENCE DRAWING

SUB. REVISION ADD BCU-3; REV. MISC.1 2/16/12 BM

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Drawing Title

Project Title

211-1009

IW/BMIW/JAIW BM 12/30/11

R-1

NETWORK ARCHITECTURE

VA HVAC CONTROLS UPGRADE -

WILMINGTON, DELAWARE

NETWORK ARCHITECTURE

EX. CP

THE NEW DDC SYSTEM SHALL INTEGRATE WITH THE EXISTING TRANE SUMMIT (BCU)

CONTROLLERS VIA BACNET IP.

THE NEW DDC SYSTEM SHALL INTEGRATE WITH THE EXISITNG HONEYWELL WEB

CONTROLLERS VIA TRIDIUM NIAGARA NETWORK.

A NEW CAT-5e DATA/NETWORK SHALL BE PROVIDED AND INSTALLED BY MODERN

CONTROLS UNLESS NOTED OTHERWISE.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; FOR THIS SUBMITTAL ALL EXISTING DDC CONTROL

PANELS ARE TAGGED ‘EX.CP’

NOTES:

110v (EXISTING)

*BACNET TO NEW ‘DCP’s

FOR AHUS’ AND NEW

VAV CONTROLLERS

(5TH THRU. 9TH FLOORS)

(FX #1)

EX. CP

110v (EXISTING)

*BACNET TO NEW

AHU AND VAV

CONTROLLERS

(WEST SIDE ONLY)

*BACNET TO NEW

AHU AND VAV

CONTROLLERS

(WEST SIDE ONLY)

TRANE

BCU-1

CAT-5e

TRANE

BCU-2

*EXISTING IN

MECH. ROOM 128

BUILDING 13

MECHANICAL ROOM

(REMOTE BLDG.)

EX. CP

110v

(EXISTING)

TRUNK #1

*SEE NOTES (TYP.)

CAT-5e (BY OTHERS)

*LON TO

EXISTING TRANE

CONTROLLERS

*LON TO

EXISTING TRANE

CONTROLLERS

BUILDING 17

MECHANICAL ROOM

EX. CP

110v

(EXISTING)

TRUNK #2

TRUNK #1

*BACNET TO

NEW AHU

CONTROLLERS

(BLDG. 13)

FXS-1

FX FIELD SERVER

LOCATED IN MAIN

MECHANICAL ROOM OFFICE

WITH OTHER EXISTING TRANE

BCU CONTROLLERS

VA

HOSPITAL

*SEE NOTES

CAT-5e

(FX #2) (FX #4) (FX #5)

*BACNET TO NEW

AHU AND VAV

CONTROLLERS

(CLINICAL)

*BACNET TO NEW

AHU AND VAV

CONTROLLERS

(CLINICAL)

CAT-5e (TYP.)

*SEE NOTES

CLINICAL ADDITION

(GROUND FLOOR)

EX. CP

110v

(EXISTING)

TRUNK #2

TRUNK #1

CAT-5e

(FX #3)

*BACNET TO NEW

AHU AND VAV

CONTROLLERS

(CLINICAL)

*BACNET TO NEW

AHU AND VAV

CONTROLLERS

(CLINICAL)TRUNK #1

(CON’T. TO 5TH ~ 9TH

FLOORS)

*BACNET TO NEW ‘DCP’s

FOR AHUS’ AND NEW

VAV CONTROLLERS

(GRND. THRU. 3RD FLOORS)

TRUNK #2

(CON’T. TO GRND.

~ 3RD FLOORS)

TRUNK #1

(CON’T. TO 5TH ~ 9TH

FLOORS)

TRUNK #2

(CON’T. TO GRND.

~ 3RD FLOORS)

CISCO

8-Port Gigabit

SWITCH

HONEYWELL

WEB

*EXISTING IN E.R.

EXPANSION MECH. ROOM

*LON TO

EXISTING

HONEYWELL

CONTROLLERS

HONEYWELL

WEB

*LOCATION

T.B.D.

*EXISTING ON

3RD FLOOR

*EXISTING MER 128

FROM PHARMACY

PROJECT

*LON TO FUTURE

HONEYWELL

CONTROLLERS

IN PHASE 2

JOHNSON

CONTROLS

FX #6

CAT-5e

CISCO

8-Port Gigabit

SWITCH

CAT-5e

CAT-5e

CAT-5e

CAT-5e

CAT-5e

BUILDING 13

TELEPHONE ROOM

BUILDING 1

GROUND FLOOR

TELEPHONE ROOM

*EXISTING

FIBER

CAT-5e*EXISTING

CONVERTER

*EXISTING

CONVERTER

FOURTH FLOOR MECH.

HEAT EXCHANGER ROOM

*BACNET TO

EXISTING JOHNSON

CONTROLLERS

FOURTH FLOOR MECH.

HEAT EXCHANGER ROOM

*SEE NOTES (TYP.)

SW-2

LOCATED IN 2nd FLOOR

ELECTRIC ROOM 2005

SW-1

LOCATED IN GROUND

FLOOR MER 128 OFFICE

TRANE

BCU-3

*EXISTING IN

MECH. ROOM 245

*LON TO

EXISTING TRANE

CONTROLLERS

CAT-5e (BY OTHERS)

CAT-5e