7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
REFERENCE DRAWING
SUB. REVISION ADD BCU-3; REV. MISC.1 2/16/12 BM
NO. REVISION-LOCATION ECN DATE BY
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
Drawing Title
Project Title
211-1009
IW/BMIW/JAIW BM 12/30/11
R-1
NETWORK ARCHITECTURE
VA HVAC CONTROLS UPGRADE -
WILMINGTON, DELAWARE
NETWORK ARCHITECTURE
EX. CP
THE NEW DDC SYSTEM SHALL INTEGRATE WITH THE EXISTING TRANE SUMMIT (BCU)
CONTROLLERS VIA BACNET IP.
THE NEW DDC SYSTEM SHALL INTEGRATE WITH THE EXISITNG HONEYWELL WEB
CONTROLLERS VIA TRIDIUM NIAGARA NETWORK.
A NEW CAT-5e DATA/NETWORK SHALL BE PROVIDED AND INSTALLED BY MODERN
CONTROLS UNLESS NOTED OTHERWISE.
THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING
DDC CONTROL PANELS AS ‘DCP’; FOR THIS SUBMITTAL ALL EXISTING DDC CONTROL
PANELS ARE TAGGED ‘EX.CP’
NOTES:
110v (EXISTING)
*BACNET TO NEW ‘DCP’s
FOR AHUS’ AND NEW
VAV CONTROLLERS
(5TH THRU. 9TH FLOORS)
(FX #1)
EX. CP
110v (EXISTING)
*BACNET TO NEW
AHU AND VAV
CONTROLLERS
(WEST SIDE ONLY)
*BACNET TO NEW
AHU AND VAV
CONTROLLERS
(WEST SIDE ONLY)
TRANE
BCU-1
CAT-5e
TRANE
BCU-2
*EXISTING IN
MECH. ROOM 128
BUILDING 13
MECHANICAL ROOM
(REMOTE BLDG.)
EX. CP
110v
(EXISTING)
TRUNK #1
*SEE NOTES (TYP.)
CAT-5e (BY OTHERS)
*LON TO
EXISTING TRANE
CONTROLLERS
*LON TO
EXISTING TRANE
CONTROLLERS
BUILDING 17
MECHANICAL ROOM
EX. CP
110v
(EXISTING)
TRUNK #2
TRUNK #1
*BACNET TO
NEW AHU
CONTROLLERS
(BLDG. 13)
FXS-1
FX FIELD SERVER
LOCATED IN MAIN
MECHANICAL ROOM OFFICE
WITH OTHER EXISTING TRANE
BCU CONTROLLERS
VA
HOSPITAL
*SEE NOTES
CAT-5e
(FX #2) (FX #4) (FX #5)
*BACNET TO NEW
AHU AND VAV
CONTROLLERS
(CLINICAL)
*BACNET TO NEW
AHU AND VAV
CONTROLLERS
(CLINICAL)
CAT-5e (TYP.)
*SEE NOTES
CLINICAL ADDITION
(GROUND FLOOR)
EX. CP
110v
(EXISTING)
TRUNK #2
TRUNK #1
CAT-5e
(FX #3)
*BACNET TO NEW
AHU AND VAV
CONTROLLERS
(CLINICAL)
*BACNET TO NEW
AHU AND VAV
CONTROLLERS
(CLINICAL)TRUNK #1
(CON’T. TO 5TH ~ 9TH
FLOORS)
*BACNET TO NEW ‘DCP’s
FOR AHUS’ AND NEW
VAV CONTROLLERS
(GRND. THRU. 3RD FLOORS)
TRUNK #2
(CON’T. TO GRND.
~ 3RD FLOORS)
TRUNK #1
(CON’T. TO 5TH ~ 9TH
FLOORS)
TRUNK #2
(CON’T. TO GRND.
~ 3RD FLOORS)
CISCO
8-Port Gigabit
SWITCH
HONEYWELL
WEB
*EXISTING IN E.R.
EXPANSION MECH. ROOM
*LON TO
EXISTING
HONEYWELL
CONTROLLERS
HONEYWELL
WEB
*LOCATION
T.B.D.
*EXISTING ON
3RD FLOOR
*EXISTING MER 128
FROM PHARMACY
PROJECT
*LON TO FUTURE
HONEYWELL
CONTROLLERS
IN PHASE 2
JOHNSON
CONTROLS
FX #6
CAT-5e
CISCO
8-Port Gigabit
SWITCH
CAT-5e
CAT-5e
CAT-5e
CAT-5e
CAT-5e
BUILDING 13
TELEPHONE ROOM
BUILDING 1
GROUND FLOOR
TELEPHONE ROOM
*EXISTING
FIBER
CAT-5e*EXISTING
CONVERTER
*EXISTING
CONVERTER
FOURTH FLOOR MECH.
HEAT EXCHANGER ROOM
*BACNET TO
EXISTING JOHNSON
CONTROLLERS
FOURTH FLOOR MECH.
HEAT EXCHANGER ROOM
*SEE NOTES (TYP.)
SW-2
LOCATED IN 2nd FLOOR
ELECTRIC ROOM 2005
SW-1
LOCATED IN GROUND
FLOOR MER 128 OFFICE
TRANE
BCU-3
*EXISTING IN
MECH. ROOM 245
*LON TO
EXISTING TRANE
CONTROLLERS
CAT-5e (BY OTHERS)
CAT-5e