MECHANICAL AND CONTROL SYSTEMS

Environmental Control System

Building Automation System

PROJECT

ARCHITECT

ENGINEER

CONTRACTOR

MODERN CONTROLS INC

7 BELLECOR DRIVE

NEW CASTLE, DE. 19720

DATE

Branch Information

CONTRACT NUMBERAPPLICATION ENGINEERPROJECT MANAGERSALES ENGINEER

REFERENCE DRAWING

NO. REVISION-LOCATION ECN DATE BY

Automatic Temperature Controls

Heating

Air Conditioning

Air Filters

Water Treatment

Coil Cleaning

Contract Operations

Time-Shared Automated Building Service

Refrigeration

Industrial Controls / Recording / Indication Equipment

Air and Water Systems Balancing

Instrumentation System Installation

Building Operations Management

Energy Conservation Control

Custom Programmed Maintenance

211-1009IW/BM 12/17/12IW/JAIW

VA MEDICAL CENTER

HVAC CONTROLS UPGRADE - PHASE 2G

WILMINGTON, DELAWARE

HATCH MOTT MACDONALD

27 BLEEKER ST.

MILLBURN, NJ 07041

BOB SMITH CONTRACTORS

281 EAST EVERGREEN ST.

WEST GROVE, PA 19390

DEPT. OF VETERANS AFFAIRS

1601 KIRKWOOD HIGHWAY

WILMINGTON, DE 19805

VA HVAC CONTROLS UPGRADE - PHASE 2G

(PARTIAL SUBMITTAL - INCLUDES BLDG. #13 REGIONAL OFFICE HVAC EQUIPMENT)

PAGE # DRAWING TITLE LAST REVISION

TP-1 TITLE PAGE 12/10/13

C-1A AIR HANDLING UNIT CONTROL – AHU-1 12/10/13

C-1B CONTROLLER WIRING DETAIL – AHU-1 12/10/13

C-1C AIR HANDLING UNIT CONTROL – AHU-2 12/10/13

C-1D CONTROLLER WIRING DETAIL – AHU-2 12/10/13

C-1E SEQUENCE OF OPERATIONS – BLDG. 13 AHU-1 & AHU-2 12/10/13

C-2 CHILLER & ASSOCIATED HEAT EXCHANGER CONTROL 12/10/13

AS-BUILT REV. FINAL POINT TERM.1 12/10/13 DB

1 2

AS-BUILT REV. ADD ‘MASTER’ NOTE1 01/28/14 DB

NOTE(S): REFER TO ‘MASTER BUILDING NETWORK ARCHITECTURE DRAWING’

PROVIDED IN OUR ATC AS-BUILT / O&M MANUAL BINDER FOR ALL

SUPERVISORY CONTROLLER INFORMATION AND ASSOCIATED IP

ADDRESSES USED BY MODERN CONTROLS.

REFER TO ‘MASTER BUILDING VALVE SCHEDULE’ PROVIDED IN OUR

ATC AS-BUILT / O&M MANUAL BINDER FOR A COMPLETE LIST OF ALL

CONTROL VALVES PROVIDED FOR AIR HANDLING UNITS AND

ASSOCIATED VAV BOXES.

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

REFERENCE DRAWING NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Drawing Title

Project Title

BM 12/17/12

211-1009

IW/BMIW/JAIW

C-1A

AIR HANDLING UNIT CONTROL-

BLDG.#13 AHU-1

AIR HANDLING UNIT CONTROL – BLDG.#13 AHU-1

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

SUPPLY

AIR OUTDOOR

AIR

SF

FILTER

UI-3

MA-T

C

C

CWS

CWR

*SEE NOTES

AO-9

V-2

BI-7

DPS

VA HVAC CONTROLS UPGRADE -

PHASE 2G

WILMINGTON, DELAWARE

HWS

HWR

*SEE NOTES

H

C

CO-6

V-1

UI-2

DA-T

DA

(D-1)CO-7

N.C.

UI-1

*SEE NOTES

T-1

(TEMP.)

N.O.

RETURN

AIR

UI-4

UI-2

110v (EXISTING)

*EXISTING EX. CP

BLDG. 13

MECH. EQUIPMENT RM. -

(MER MAIN BLDG. 13)

BILL OF MATERIALS

Designation Qty Part Number Description

FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET

XM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET

VLV SEE VALVE SCHEDULE

RA-T/H

BO-1

R AO-8

VFD

H O

A *COMMAND

*START/STOP

NOTES:

UI-1

LH

SPS

FEC-26

IOM-47

IOM-47 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

POINT NAME/DESCRIPTION

STATIC PRESSURE

RETURN AIR HUMIDITY

FEC-26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

ZONE TEMPERATURE

DISCHARGE AIR TEMPERATURE (DA-T)

SUPPLY FAN STATUS

FREEZE STAT / SHUTDOWN

VFD COMMAND

CHILLED WATER VALVE

MIXED AIR TEMPERATURE (MA-T)

RETURN AIR TEMPERATURE (RA-T)

SUPPLY FAN START / STOP

PRE-HEAT VALVE COMMAND (V-1)

DAMPER COMMAND

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

CHILLER ENABLE

AS-BUILT REV. FINAL POINT TERM.1 12/10/13 DB

*IOM

HUM.

TEMP.

BI-8

LL

*IOM

SPACE TEMP. DETAIL

EXSISTING SPACE

TEMPERATURE SENSOR

LOCATED IN HALLWAY

BY RM 25

ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY

EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-

USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC

CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON

DDC CONTROLLERS AS INDICATED. *REFER TO C-1B FOR CONTROLLER WIRING DETAILS

AND DRAWING C-1E FOR ASSOCIATED SEQUENCE OF OPERATIONS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND

INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE

‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING

M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR

ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS

WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL

PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS

HAVE BEEN APPROVED BY THE VA HOSPITAL.

211-1009

IW/BMIW/JAIW

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 8/12/11

C-1B

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2G

WILMINGTON, DELAWARE

Drawing Title

CONTROLLER WIRING DETAIL –

AHU-1 (BLDG.13)

Project Title

CONTROLLER WIRING DETAIL – AHU-1 (BLDG. 13)

AS-BUILT REV. NEW DWG. / POINT TERM.1 12/10/13 DB

SEE AS-BUILT CONTROL DRAWINGS C-1A AND C-1E FOR

ASSOCIATED UNIT CONTROL DIAGRAM AND SEQUENCE OF

OPERATIONS.

NOTE(S):

124816326412

O N

Address:

S A

PW

R

C O

M

SA BUS

FC BUS

C O

M S

H

LD+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

IN

IC

O M

IN

IC

O M

UNIVERSAL BINARY

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

FEC2611

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

124816326412

O N

Address:

SA

FC

H O

T

24V

C O

M

IOM4711

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

S A

P W

R

C O

M

+ - C

O M

S H

LD

SA/FC BUS

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

ZO

N

E

TE

M

PE

R A

TU

R

E

VF

D

C O

M M

A N

D

C H

IL

LE

D W

A

TE

R V

A

LV

E

SU

PP

LY

F

A N

S

TA

R T/

ST

O

P

PR

E-

H

EA

T

VA

LV

E

C O

M M

A N

D (V

-1

D A

M

PE

R C

O M

M A

N D

W H

EE

L

VF

D

C O

M M

A N

D

D

IS

C H

A R

G E

A

IR

T

EM

PE

R

A

TU

R E

(D A

-T

M

IX

ED

A

IR

T

EM

PE

R A

TU

R

E (M

A -T

R

ET

U R

N A

IR

T

EM

PE

R A

TU

R

E (R

A -T

SU

PP

LY

F

A N

S

TA

TU

S

FR

EE

ZE

S

TA

T

/ S H

U

TD

O W

N

ST

A

TI

C

P R

ES

SU

R E

R

ET

U R

N A

IR

H

U M

ID

IT

Y

19720

TEL: 302-325-6800

FAX: 302-325-6808

REFERENCE DRAWING NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Drawing Title

Project Title

BM 12/17/12

211-1009

IW/BMIW/JAIW

C-1C

AIR HANDLING UNIT CONTROL-

BLDG.#13 AHU-2

AIR HANDLING UNIT CONTROL – BLDG.#13 AHU-2 (WEST)

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

SUPPLY

AIR OUTDOOR

AIR

SF

FILTER

UI-3

MA-T

C

C

CWS

CWR

*SEE NOTES

AO-9

V-2

BI-7

DPS

VA HVAC CONTROLS UPGRADE -

PHASE 2G

WILMINGTON, DELAWARE

HWS

HWR

*SEE NOTES

H

C

CO-6

V-1

UI-2

DA-T

DA

(D-1)CO-7

N.C.

UI-1

*SEE NOTES

T-1

(TEMP.)

N.O.

RETURN

AIR

UI-4

UI-2

110v (EXISTING)

*EXISTING EX. CP

BLDG. 13

MECH. EQUIPMENT RM. -

(MER MAIN BLDG. 13)

BILL OF MATERIALS

Designation Qty Part Number Description

FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET

XM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET

VLV SEE VALVE SCHEDULE

RA-T/H

R AO-8

VFD

H O

A *COMMAND

*START/STOP

NOTES:

UI-1

LH

SPS

FEC-26

IOM-47

IOM-47 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

POINT NAME/DESCRIPTION

STATIC PRESSURE

RETURN AIR HUMIDITY

HOT WATER PUMP STATUS

CHILLED WATER PUMP STATUS

HOT WATER SUPPLY TEMPERATURE

FEC-26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

ZONE TEMPERATURE

DISCHARGE AIR TEMPERATURE (DA-T)

SUPPLY FAN STATUS

OUTSIDE AIR TEMPERATURE (OA-T)

OUTSIDE AIR HUMIDITY (OA-H)

FREEZE STAT / SHUTDOWN

VFD COMMAND

CHILLED WATER VALVE

MIXED AIR TEMPERATURE (MA-T)

RETURN AIR TEMPERATURE (RA-T)

SUPPLY FAN START / STOP

PRE-HEAT VALVE COMMAND (V-1)

DAMPER COMMAND

FAN COILS OCCUPIED/UNOCCUPIED

EXHAUST FAN

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

HEAT EXCHANGER VALVE COMMAND

HOT WATER PUMP ENABLE

CHILLED WATER PUMP ENABLE

AS-BUILT REV. FINAL POINT TERM.1 12/10/13 DB

*IOM

HUM.

TEMP.

BI-8

LL

*IOM

SPACE TEMP. DETAIL

EXSISTING SPACE

TEMPERATURE SENSOR

LOCATED IN FRONT

HALLWAY

ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY

EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-

USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC

CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON

DDC CONTROLLERS AS INDICATED. *REFER TO C-1D FOR CONTROLLER WIRING DETAILS

AND DRAWING C-1E FOR ASSOCIATED SEQUENCE OF OPERATIONS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND

INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE

‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING

M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR

ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS

WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL

PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS

HAVE BEEN APPROVED BY THE VA HOSPITAL.

UI-5

OA-T

UI-6

H

OA-H

IW/BMIW/JAIW

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 8/12/11

C-1D

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2G

WILMINGTON, DELAWARE

Drawing Title

CONTROLLER WIRING DETAIL –

AHU-2 (BLDG. 13)

Project Title

CONTROLLER WIRING DETAIL – AHU-2 (BLDG.#13)

AS-BUILT REV. NEW DWG. / POINT TERM.1 12/10/13 DB

SEE AS-BUILT CONTROL DRAWINGS C-1C AND C-1E FOR

ASSOCIATED UNIT CONTROL DIAGRAM AND SEQUENCE OF

OPERATIONS.

NOTE(S):

124816326412

O N

Address:

S A

PW

R

C O

M

SA BUS

FC BUS

C O

M S

H

LD+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

IN

IC

O M

IN

IC

O M

UNIVERSAL BINARY

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

FEC2611

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

124816326412

O N

Address:

SA

FC

H O

T

24V

C O

M

IOM4711

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

S A

P W

R

C O

M

+ - C

O M

S H

LD

SA/FC BUS

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

ZO

N

E

TE

M

PE

R A

TU

R

E

VF

D

C O

M M

A N

D

C H

IL

LE

D W

A

TE

R V

A

LV

E

SU

PP

LY

F

A N

S

TA

R T/

ST

O

P

PR

E-

H

EA

T

VA

LV

E

C O

M M

A N

D (V

-1

D A

M

PE

R C

O M

M A

N D

W H

EE

L

VF

D

C O

M M

A N

D

D

IS

C H

A R

G E

A

IR

T

EM

PE

R

A

TU

R E

(D A

-T

M

IX

ED

A

IR

T

EM

PE

R A

TU

R

E (M

A -T

R

ET

U R

N A

IR

T

EM

PE

R A

TU

R

E (R

A -T

SU

PP

LY

F

A N

S

TA

TU

S

FR

EE

ZE

S

TA

T

/ S H

U

TD

O W

N

ST

A

TI

C

P R

ES

SU

R E

R

ET

U R

N A

IR

H

U M

ID

IT

Y

19720

TEL: 302-325-6800

FAX: 302-325-6808

REFERENCE DRAWING NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Drawing Title

Project Title

BM 12/17/12

211-1009

IW/BMIW/JAIW

C-1E

SEQUENCE OF OPERATIONS -

BLDG.#13 AIR HANDLING

UNITS (AHU-1 & AHU-2)

VA HVAC CONTROLS UPGRADE -

PHASE 2G

WILMINGTON, DELAWARE

SEQUENCE OF OPERATIONS - BLDG.#13 AIR HANDLING UNITS

(TYPICAL FOR AHU-1 & AHU-2)

GENERIC AHU - SEQUENCE OF OPERATION

1. GENERAL

UNIT IS MANUALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. WHEN UNIT IS OFF DAMPER D-1 IS CLOSED. WHEN UNIT IS ON DAMPER D-1 IS OPEN.

2. TEMPERATURE CONTROL

DURING HEATING MODE THE SPACE TEMPERATURE SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT BY DCP MODULATING V-1. DURING COOLING MODE THE COOLING

COIL LEAVING AIR TEMPERATURE SENSED BY T-3 SHALL BE MAINTAINED AT SETPOINT BY DCP BY MODULATING V-2, AND THE SPACE TEMPERATURE SENSED BY T-1 SHALL

BE MAINTAINED AT SETPOINT BY MODULATING V-3.

3. AIR FLOW CONTROL

THE SUPPLY FAN SHALL RUN AT CONSTANT SPEED PROVIDING CONSTANT AIR FLOW.

4. FREEZE PROTECTION

IF THE AIR TEMPERATURE AS SENSED BY T-2 FALLS BELOW 45F AN ALARM SIGNAL IS INDICATED AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS BELOW 40F THE UNIT

SUPPLY FAN SHALL STOP, THE DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL BE INDICATED AT THE DCP AND BMS.

5. EMERGENCY SHUTDOWN/RESTART

WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY FAN SHALL SHUT OFF, DAMPER D-1 CLOSE AND AN ALARM SIGNAL SHALL BE

TRANSMITTED TO THE FIRE ALARM SYSTEM. SUPPLY FAN SHALL RESTART AND DAMPER D-1 SHALL OPEN WHEN THE FIRE ALARM CIRCUIT IS MANUALLY RESET.

*SEE NOTES

NOTES: AHU-1 AND AHU-2 WERE PROGRAMMED TO MATCH THE

EXISTING CSI CONTROLLERS PROGRAM. ABOVE SEQUENCE

WAS FROM ‘AHU-1 CLINICAL’ WHICH WAS THE SAME TYPE OF

UNIT. *SEE ASSOCIATED CONTROL DIAGRAM ON DRAWING

C-1A AND C-1C.

AS-BUILT REV. NEW DWG. / POINT TERM.1 12/10/13 DB

19720

TEL: 302-325-6800

FAX: 302-325-6808

REFERENCE DRAWING NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Drawing Title

Project Title

IW/BMIW/JAIW BM 12/17/12

C-2

CHILLER & ASSOCIATED HEAT

EXCHANGER CONTROL

CHILLER & ASSOCIATED HEAT EXCHANGER CONTROL

(REGIONAL OFFICE – BUILDING 13)

VA HVAC CONTROLS UPGRADE -

PHASE 2G

WILMINGTON, DELAWARE

OAH

OAT

LOCAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SENSOR

LOCATED NEAR CHILLER

110v (EXISTING)

EX. CP

BLDG.#13

MECH. ROOM

(MAIN MER)

NOTE(S):

BILL OF MATERIALS

Designation Qty Part Number Description

VLV SEE VALVE SCHEDULE

HEAT

EXCHANGER

STEAM

CONDENSATE

BI-7

CT

TE

HWS

HWR

*SEE NOTES

HWP-X

R

*SEE NOTES

LPS

AO-8

EX. V

BO-2

RH

O A

C H L R E N B L

CH-1

CHWP-X

UI-6

CT

BO-2

R

AS-BUILT REV. NEW DWG. / POINT TERM.1 12/10/13 DB

FEC-26

IOM-47

AHU2 IOM47 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

POINT NAME/DESCRIPTION

STATIC PRESSURE

RETURN AIR HUMIDITY

HOT WATER PUMP STATUS

CHILLED WATER PUMP STATUS

HOT WATER SUPPLY TEMPERATURE

AHU1 FEC26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

ZONE TEMPERATURE

DISCHARGE AIR TEMPERATURE (DA-T)

SUPPLY FAN STATUS

OUTSIDE AIR TEMPERATURE (OA-T)

OUTSIDE AIR HUMIDITY (OA-H)

FREEZE STAT / SHUTDOWN

VFD COMMAND

CHILLED WATER VALVE

MIXED AIR TEMPERATURE (MA-T)

RETURN AIR TEMPERATURE (RA-T)

SUPPLY FAN START / STOP

PRE-HEAT VALVE COMMAND (V-1)

DAMPER COMMAND

FAN COILS OCCUPIED/UNOCCUPIED

EXHAUST FAN

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

HEAT EXCHANGER VALVE COMMAND

HOT WATER PUMP ENABLE

CHILLED WATER PUMP ENABLE

THE FEC-26 AND IOM-47

CONTROLLERS / POINT

IDENTIFICATION LAYOUTS

OF AHU-1 AND AHU-2 ARE

BEING REFERENCED

FROM DRAWINGS C-1A

AND C-1C RESPECTIVELY

*IOM

*IOM

*IOM

*IOM

*IOM

*IOM

POINT BO-2 IS

FROM AHU-1 FEC26

ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY

EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-

USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC

CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON

DDC CONTROLLERS AS INDICATED. CONTROLLERS SHALL BE PROGRAMMED TO MATCH

EXISTING SEQUENCE OF OPERATIONS FOR ANY EQUIPMENT WITHOUT A SEQUENCE OF

OPERATION PROVIDED WITHIN THE CONTRACT DOCUMENTS. *REFER TO C-1B/C-1D FOR

CONTROLLER WIRING DETAILS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND

INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE

‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING

M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR

ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS

WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL

PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS

HAVE BEEN APPROVED BY THE VA HOSPITAL.

POINT UI-5 AND UI-6

ARE FROM AHU-2

FEC26

AHU2 FEC26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

ZONE TEMPERATURE

DISCHARGE AIR TEMPERATURE (DA-T)

SUPPLY FAN STATUS

OUTSIDE AIR TEMPERATURE (OA-T)

OUTSIDE AIR HUMIDITY (OA-H)

FREEZE STAT / SHUTDOWN

VFD COMMAND

CHILLED WATER VALVE

MIXED AIR TEMPERATURE (MA-T)

RETURN AIR TEMPERATURE (RA-T)

SUPPLY FAN START / STOP

PRE-HEAT VALVE COMMAND (V-1)

DAMPER COMMAND

FAN COILS OCCUPIED/UNOCCUPIED

EXHAUST FAN

*EXISTING

Visio-2G-.TP1
Visio-2G-C1A AHU 1 unit
Visio-2G-C1B AHU 1 controller
Visio-2G-C1C AHU 2 unit
Visio-2G-C1D AHU 2 controller
Visio-2G-C1E Sequence
Visio-2G-C2 chiller and hx