MECHANICAL AND CONTROL SYSTEMS

Environmental Control System

Building Automation System

VA MEDICAL CENTER

HVAC CONTROLS UPGRADE - PHASE 2C

WILMINGTON, DELAWARE

PROJECT

ARCHITECT

ENGINEER

CONTRACTOR

211-1009

MODERN CONTROLS INC

7 BELLECOR DRIVE

NEW CASTLE, DE. 19720

DATE

Branch Information

CONTRACT NUMBER

IW/BM

APPLICATION ENGINEER

8/15/11IW/JA

PROJECT MANAGER

IW

SALES ENGINEER

REFERENCE DRAWING

NO. REVISION-LOCATION ECN DATE BY

Automatic Temperature Controls

Heating

Air Conditioning

Air Filters

Water Treatment

Coil Cleaning

Contract Operations

Time-Shared Automated Building Service

Refrigeration

Industrial Controls / Recording / Indication Equipment

Air and Water Systems Balancing

Instrumentation System Installation

Building Operations Management

Energy Conservation Control

Custom Programmed Maintenance

HATCH MOTT MACDONALD

27 BLEEKER ST.

MILLBURN, NJ 07041

BOB SMITH CONTRACTORS

281 EAST EVERGREEN ST.

WEST GROVE, PA 19390

DEPT. OF VETERANS AFFAIRS

1601 KIRKWOOD HIGHWAY

WILMINGTON, DE 19805

VA HVAC CONTROLS UPGRADE - PHASE 2C

(PARTIAL SUBMITTAL - INCLUDES 3RD FLOOR HVAC EQUIPMENT)

PAGE # DRAWING TITLE LAST REVISION

TP-1 TITLE PAGE 01/28/14

C-1B CONTROLLER WIRING DETAIL – AHU FOR OR (MER 3117) 12/03/13

C-1C VAV BOX CONTROLS FOR 3RD FLOOR (SERVED BY AHU FOR OR) 12/03/13

C-1D SEQUENCE OF OPERATIONS – AHU FOR OR (MER 3117) 12/03/13

C-2A AIR HANDLING UNIT CONTROL – AHU FOR LAB (3RD FLOOR ROOF) 12/03/13

C-2B CONTROLLER WIRING DETAIL – AHU FOR LAB (3RD FLOOR ROOF) 12/03/13

C-2C SEQUENCE OF OPERATIONS – AHU FOR LAB (3RD FLOOR ROOF) 12/03/13

C-3A AIR HANDLING UNIT CONTROL – AHU FOR CT SCANNER (3RD FLOOR ROOF) 12/03/13

C-3B CONTROLLER WIRING DETAIL – AHU FOR CT SCANNER (3RD FLOOR ROOF) 12/03/13

C-3C SEQUENCE OF OPERATIONS – AHU FOR CT SCANNER (3RD FLOOR ROOF) 12/03/13

C-4A AIR HANDLING UNIT CONTROL – AHU FOR ICU (3RD FLOOR ROOF) 12/03/13

C-4B CONTROLLER WIRING DETAIL – AHU FOR ICU (3RD FLOOR ROOF) 12/03/13

C-4C VAV BOX CONTROLS FOR 3RD FLOOR (SERVED BY AHU FOR ICU) 12/03/13

C-4D SEQUENCE OFOPERATIONS – AHU FOR ICU (3RD FLOOR ROOF) 12/03/13

C-5 SUPPLEMENTAL DRAWING – AHU-9 FOR LAUNDRY 01/28/14

SUB. REVISION TITLE DATES1 12/13/11 VD

AS-BUILT REV. DRAWING TITLE/DATES2 12/3/13 BM

AS-BUILT REV. DATES / REMOVE DWGS.3 12/20/13 DB

3 4

AS-BUILT REV. ADD ‘MASTER’ NOTE4 01/28/14 DB

NOTE(S): REFER TO ‘MASTER BUILDING NETWORK ARCHITECTURE DRAWING’

PROVIDED IN OUR ATC AS-BUILT / O&M MANUAL BINDER FOR ALL

SUPERVISORY CONTROLLER INFORMATION AND ASSOCIATED IP

ADDRESSES USED BY MODERN CONTROLS.

REFER TO ‘MASTER BUILDING VALVE SCHEDULE’ PROVIDED IN OUR

ATC AS-BUILT / O&M MANUAL BINDER FOR A COMPLETE LIST OF ALL

CONTROL VALVES PROVIDED FOR AIR HANDLING UNITS AND

ASSOCIATED VAV BOXES.

*DRAWING C-5 (AHU-9 FOR LAUNDRY) HAS BEEN ADDED TO PHASE-2C

AS A SUPPLEMENT TO OUR COMPLETE AS-BUILT REVISION.

IW/BMIW/JAIW

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 8/12/11

REFERENCE DRAWING

SUB. REVISION TAGS/NOTES1

BM

C-1A

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

Drawing Title

AIR HANDLING UNIT CONTROL

– AHU FOR OR (MER 3117)

Project Title

AIR HANDLING UNIT CONTROL – AHU FOR OR (MER 3117)

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

110v (EXISTING)

*EXISTING EX. CP

3RD FLOOR MECH.

EQUIPMENT RM. -

(MER 3117)

SUPPLY

AIROUTDOOR

AIR

SF

PRE-FILTER

(0-1.25"W.C.)

*BO-1

R CO-4HOA

H L

SPS

UI-6

DA

(D-1)

*BO-1

N.C.

*SEE NOTES

AND DETAIL

HUMIDIFIER

UI-1

VSMC

PH

C

STEAM

PRE-HEAT

LPS

AO-8

*SEE NOTES

V-1

COND.

UI-2

PH-T

C

C

CWS

CWR

*SEE NOTESAO-9

V-2

BI-7

DPS

HUMIDIFIER CONTROL

EXHAUST

EF

BO-2

RCO-5

VSMC

BI-8

EXHAUST

DP

UI-4

UI-3

EA-TH

E-TH

(Hum. Only)

UI-3

AFM

UI-5

N.O.

LPS

HUMID.

*SEE NOTES

COND.

CO-6BO-3

V-4V-3

FEC-26

IOM-47-1,2 (TYP. OF 2)

IOM-47-1 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

POINT NAME/DESCRIPTION

SUPPLY DUCT HIGH STATIC (SP-HL)

SUPPLY AIR HUMIDITY (S-TH)

LOW LIMIT/UNIT SHUTDOWN

FINAL FILTER DIFFERENTIAL PRESSURE (DPS)

EXHAUST AIR HUMIDITY (E-TH)

PRE-FILTER DIFFERENTIAL PRESSURE (DPS)

FEC-26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

SUPPLY AIR TEMPERATURE (S-TH)

PRE-HEAT COIL LEAVING AIR TEMP. (PH-T)

SUPPLY FAN STATUS (DPS)

EXHAUST AIR AIR-FLOW STATION (AFM)

SUPPLY AIR STATIC PRESS. (SPS)

EXHAUST FAN STATUS (DPS)

PREHEAT VALVE

COOLING COIL VALVE

EXHAUST AIR TEMPERATURE (EA-T)

SUPPLY AIR-FLOW STATION (AFM)

OUTSIDE AIR DAMPER/SUPPLY FAN S/S

HUMIDIFIER ISOLATION VALVE (V-4)

SUPPLY FAN CMD.

EXHAUST FAN CMD.

EXHAUST AIR FAN S/S

HUMIDIFIER ISOLATION VALVE (V-3)

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

AS-BUILT REV. FINAL POINT TERM.2

IOM-47-2 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

POINT NAME/DESCRIPTION

HOT WATER SUPPLY TEMPERATURE

HOT WATER RETURN TEMPERATURE

HOT WATER PUMP STATUS; HWP-1

HOT WATER PUMP STATUS; HWP-2

CHILLER SUPPLY TEMPERATURE

CHILLER RETURN TEMPERATURE

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

HOT WATER PUMP START/STOP; HWP-1

HOT WATER PUMP START/STOP; HWP-2

BI-7

CT

TE

HWS

HWR

*SEE NOTES (TYP.)

HWP-1

BO-1

R

TE

HWP-2

HWP-1 CONTROL

CTBO-2

HWP-2 CONTROL

LOCAL HOT WATER PUMP(S) CONTROL

ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-USED AND WIRED TO

NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC CONTROL DEVICES HAVE BEEN

PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON DDC CONTROLLERS AS INDICATED. *REFER TO C-1B FOR CONTROLLER WIRING DETAILS AND DRAWING C-1C FOR ASSOCIATED SEQUENCE OF

OPERATIONS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE ‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING M-1 OF THE CONTRACT DOCUMENTS.

PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS HAVE BEEN APPROVED BY THE VA HOSPITAL.

NOTE(S):

BILL OF MATERIALS

Designation Qty Part Number Description

DA 1 M9220-BGC-3 ACT.,24VAC,SPR.RTN.,189#IN,2-AUX.,W/E.S.

DP 2 PR-274-R3-MA FILTER DIFF. PRESS.,0-5”W.C.,ADJ.,4-20MA,MAMAC

X-TH 2 HE-67N3-0N00P DUCT COMBO SENSOR,T-NI & %RH

XX-T 1 TE-6315P-1 SENSOR,T-NI,0.1%,8FT AVG.,

1 TE-6311M-1 SENSOR,T-NI,0.1%,8IN DUCT

LL 1 A70GA-1C LOW LIMIT,AUTO RESET,20FT ELEM.

SP-HL 1 PR-276-R10-MA STATIC PRESS. HI LMIT,0-5”W.C.,ADJ.,4-20MA,MAMAC

FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET

IOM-1 2 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET

V-X SEE VALVE SCHEDULE FOR MORE INFORMATION

LL-1

BI-7

H

S-TH

UI-2

AFM

UI-4

TEMP.

*SF S/S SIGNAL (BO-1) IS

HARD-WIRED THROUGH

DA ‘D-1’ END SWITCH

*SF S/S SIGNAL (BO-1) IS

HARD-WIRED THROUGH

DA ‘D-1’ END SWITCH

*EXISTING CHILLED WATER

SUPPLY AND RETURN SENSORS

TO/FROM “CHILLER FOR OR”

LOCATED ON 2ND FLOOR

(SEE DWG. C-7 IN PHASE 2D)

TE

TE

*IOM-47-1 *IOM-47-1

FINAL FILTER

(2.5-5.0"W.C.)

L

H

SP-HL

HI-LIMIT

UI-1

*IOM-47-1

*IOM-47-1

*IOM-47-1

*IOM-47-2*IOM-47-2

*IOM-47-2*IOM-47-2

*IOM-47-2 *IOM-47-2

*IOM-47-2

*IOM-47-2

H

HUMID.

HIGH LIMIT

12/3/13

12/13/11 BM

HUMID.

SMK

*HARD-WIRED

*HARD-WIRED

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 8/12/11

C-1B

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

Drawing Title

CONTROLLER WIRING DETAIL

– AHU FOR OR (MER 3117)

Project Title

CONTROLLER WIRING DETAIL – AHU FOR OR (MER 3117)

AS-BUILT REV. NEW DWG. / POINT TERM.1 12/3/13 BM

SEE AS-BUILT CONTROL DRAWINGS C-1A AND C-1C FOR

ASSOCIATED UNIT CONTROL DIAGRAM AND SEQUENCE OF

OPERATIONS.

NOTE(S):

124816326412

O N

Address:

S A

PW

R

C O

M

SA BUS

FC BUS

C O

M S

H

LD+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

IN

IC

O M

IN

IC

O M

UNIVERSAL BINARY

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

FEC2611

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

124816326412

O N

Address:

SA

FC

H O

T

24V

C O

M

IOM4711-1

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

S A

P W

R

C O

M

+ - C

O M

S H

LD

SA/FC BUS

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

SU

PP

LY

A

IR

T

EM

PE

R A

TU

R

E (S

-T H

PR

EH

EA

T

C O

IL

V

A

LV

E

C O

O

LI

N G

C O

IL

V

A

LV

E

O U

TS

ID

E A

IR

D

A M

PE

R

/S U

PP

LY

F A

N S

/S

H U

M

ID

IF

IE

R

IS

O

LA

TI

O

N V

A

LV

E (V

LV

-4

SU

PP

LY

F

A N

C O

M M

A N

D

EX

H

A U

ST

F

A N

C O

M M

A N

D

EX

H

A U

ST

A

IR

F

A N

S /S

H U

M

ID

IF

IE

R

IS

O

LA

TI

O

N V

A

LV

E (V

LV

-3

PR

EH

EA

T

C O

IL

L

EA

VI

N G

A

IR

T

EM

PE

R

A

TU

R E

(P H

-T

EX

H

A U

ST

A

IR

T

EM

PE

R A

TU

R

E

SU

PP

LY

A

IR

-F

LO

W

S

TA

TI

O

N (A

FM

EX

H

A U

ST

A

IR

-F

LO

W

S

TA

TI

O

N (A

FM

SU

PP

LY

A

IR

S

TA

TI

C P

R

ES

SU

R

E

SU

PP

LY

F

A N

S

TA

TU

S

(D

PS

EX

H

A U

ST

F

A N

S

TA

TU

S

(D

PS

SU

PP

LY

D

U C

T H

IG

H

S

TA

TI

C

(S P-

H L)

SU

PP

LY

A

IR

H

U M

ID

IT

Y (S

-T H

EX

H

A U

ST

A

IR

H

U M

ID

IT

Y (E

-T H

PR

E-

FI

LT

ER

D

IF

FE

R

EN

TI

A

L

PR

ES

SU

R E

(D

PS

FI

N

A L

FI

LT

ER

D

IF

FE

R

EN

TI

A

L

PR

ES

SU

R E

(D

PS

LO

W

L

IM

IT

/U

N

IT

S H

U

TD

O W

N

124816326412

O N

Address:

SA

FC

H O

T

24V

C O

M

IOM4711-2

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

S A

P W

R

C O

M

+ - C

O M

S H

LD

SA/FC BUS

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

H O

T W

A

TE

R P

U M

P

ST

A R

T/

ST

O P;

H W

P-

H O

T W

A

TE

R S

U

PP

LY

T

EM

PE

R A

TU

R

E

H O

T W

A

TE

R R

ET

U

R N

T

EM

PE

R

A

TU

R E

C H

IL

LE

R S

U

PP

LY

T

EM

PE

R A

TU

R

E (T

E/ W

Z)

H O

T W

A

TE

R P

U M

P

ST

A

TU

S;

H

W P-

H O

T W

A

TE

R P

U M

P

ST

A

TU

S;

H

W P-

H O

T W

A

TE

R P

U M

P

ST

A R

T/

ST

O P;

H W

P-

C H

IL

LE

R R

ET

U

R N

T

EM

PE

R

A

TU

R E

(T E/

W Z)

VMA-16

(SEE NOTES)

MOUNT DIRECTLY TO

DAMPER ACTUATOR SHAFT

WITH THE DAMPER IN THE

"OPEN" POSITION.

CONNECT TO VAV BOX

VELOCITY PROBES

24V FROM NEW XFMR(S) MOUNTED IN

THE AHU FOR ICU CONTROL PANEL

*EXISTING

TRANSFORMER

211-1009

IW/BMIW/JAIW

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

C-1C

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

Drawing Title

VAV BOX CONTROLS FOR 3RD

FLOOR - SERVED BY AHU FOR OR

(TYP. OF 24)

Project Title

VAV BOX CONTROL FOR 3RD FLOOR - SERVED BY AHU FOR OR

(TYP. OF 24)

BILL OF MATERIALS

Designation Qty Part Number Description Field Devices:

STT-1 24 NS-BTP7002-0 SENSOR,TEMP.,W/C,NETWORK,WALL MNT.

TE-1 24 TE-6311M-1 SENSOR,TEMP.8IN,DUCT MNT.,

VMA-1 24 MS-VMA1620-0 VAV MODULAR ASSY.,CLG W/ REHEAT,MS/TP

VLV SEE VALVE SCHEDULE

SEQUENCE OF OPERATIONS

VAV SYSTEM CONTROL:

COOLING MODE:

On a rise in space temperature above the space temperature cooling set point, the damper will modulate from the minimum CFM set point to the maximum CFM set point. As the space temperature drops, the damper will modulate to the minimum CFM set point.

HEATING MODE:

On a drop in space temperature below the heating space temperature set point, the damper will modulate to the minimum heating CFM set point. On a further drop in space temperature below the space temperature set point, the heating coil valve will modulate to maintain the heating space temperature to it’s set point. As the temperature rises the reverse will occur.

*SEE NOTES

VELOCITY PROBES

*SEE NOTES

TEMP. / ADJ.

STT-1

SPACE TEMP.

SENSOR W/ OVERRIDE

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

TO VMA

TE-1

H

C

HWR

VLV

HWS

TO VMA

SUPPLY AIR

FROM

AHU FOR ICU

SUPPLY AIR

TO ZONES

AS-BUILT REV. FINAL POINT TERM./NOTE1 12/3/13 BM

TYPICAL CONSTRUCTION NOTES

THE NEW MODULATING ELECTRONIC CONTROL VALVES SHALL BE

PROVIDED BY MODERN CONTROLS AND INTEGRATED TO THE NEW

DDC CONTROLLERS. FIELD INSTALLATION SHALL BE PROVIDED BY

THE PROJECT GENERAL CONTRACTOR. SEE VALVE SCHEDULE FOR

MORE INFORMATION.

AIR FLOW SCHEDULE PROVIDED BY THE VA FOR REFERENCE ONLY;

SEE AS-BUILT DOCUMENTATION FOR MORE INFO.

FREEZE PROTECTION AND SUPPLY AIR TEMPERATURE MONITORING

PROVIDED BY ASSOCIATED AHU CONTROLS.

NEW PANEL MOUNTED TRANSFORMER(S) SHALL PROVIDE 24V

POWER TO NEW VAV CONTROLLERS AS REQUIRED IN THE FIELD.

ALL CONTROL POINT DESCRIPTIONS AND TERMINAL DESIGNATION

SHALL BE RECORDED IN THE FIELD FOR AS-BUILT DOCUMENTATION.

AS-BUILT NOTE

OUR O&M MANUAL PROVIDED FOR PROJECT CLOSEOUT

INCLUDEDS ALL COMMISSION AND CHECKOUT INFORMATON

FOR ALL VAV BOXES.

THE O&M MANUAL INCLUDES A TYPCIAL VAV CONTROLLER

COMMISSIONING SHEET AND ALSO A COMPLETE VAV BOX

COMMISSIONG CHECK LIST FOR ALL VAV BOXES AS SERVED

BY THEIR ASSOCIATED UNIT.

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 8/12/11

SUB. REVISION EDIT SEQUENCE1 12/13/11 VD

C-1D

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

Drawing Title

SEQUENCE OF OPERATIONS -

AHU FOR OR (MER 3117)

Project Title

SEQUENCE OF OPERATIONS - AHU FOR OR (MER 3117)

AHU FOR OF (MER #3117) SEQUENCE OF OPERATION

1. GENERAL

UNIT IS NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND

"OFF" POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. WHEN THE UNIT IS "OFF" D-1 SHALL BE CLOSED. WHEN THE UNIT IS "ON" D-1 SHALL BE FULLY

OPENED.

2. TEMPERATURE CONTROL

SUPPLY AIR TEMPERATURE SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING V-1 AND V-2 IN SEQUENCE.

3. AIRFLOW CONTROL

THE SUPPLY AIRFLOW SHALL BE CONTROLLED BY DCP MODULATING THE SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER (VSMC) TO MAINTAIN 1.5"

OF DUCT STATIC PRESSURE (FIELD ADJUSTABLE) SENSED BY SPS-1.

THE DCP USING HIGH STATIC PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING

OVER 3" OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT SPS-2 EXCEEDS 3" THE SUPPLY FAN SHALL STOP.

4. HUMIDITY CONTROL

WHEN THE DCP IS NOT CALLING FOR HUMIDIFICATION SENSED BY ROOM HUMIDISTAT H-1, TWO-WAY "ON-OFF" CONTROL VALVE V-3 SHALL REMAIN

CLOSED. WHEN THE DCP IS CALLING FOR HUMIDIFICATION, V-3 SHALL REMAIN OPEN.

SPACE AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATION CONTROL VALVE V-4 TO MAINTAIN THE DESIRED HUMIDITY. THE DCP

SHALL OVERRIDE THE CONTROL TO MAINTAIN HUMIDITY IN SUPPLY DUCT BELOW 80% AS SENSED BY H-2. DCP SHALL CLOSE VALVE V-3 WHENEVER THE

SUPPLY FAN IS OFF. VALVE V-4 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH TO KEEP THE HUMIDIFIER OFF UNTIL CONDENSATE

TEMPERATURE APPROACHES STEAM TEMPERATURE. (FIELD VERIFY).

5. FREEZE PROTECTION

IF THE AIR TEMPERATURE SENSED BY T-2 FALLS BELOW 45F AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS

BELOW 40F THE SUPPLY FAN SHALL SHUT DOWN, D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL INDICATE AT THE DCP AND BMS.

6. EMERGENCY SHUTDOWN/RESTART

WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY FAN SHALL SHUT OFF, DAMPE D-1 CLOSE AND AN ALARM SIGNAL

SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM. SUPPLY FAN RESTARTS AND DAMPER D-1 OPENS WHEN THE FIRE ALARM CIRCUIT IS MANUALLY

RESET.

7. EMERGENCY CONSTANT SPEED OPERATION

UPON FAILURE OF VSMC THE SUPPLY AND EXHAUST FANS SHALL BE STARTED/STOPPED MANUALLY AT THE DCP OR THE BMS THROUGH THE BYPASS

STARTER. FANS SHALL THEN OPERATE AT CONSTANT SPEED.

*SEE NOTES 1

AS-BUILT REV. NEW DRAWING/REV. NOTE2 12/3/13 BM

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 8/12/11

SUB. REVISION TAGS/NOTES1 12/13/11 BM

C-2A

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

Drawing Title

AIR HANDLING UNIT CONTROL –

AHU FOR LAB (3RD FLOOR ROOF)

Project Title

AIR HANDLING UNIT CONTROL – AHU FOR LAB (3RD FLOOR ROOF)

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

110v (EXISTING)

*EXISTING EX. CP

B D

F

T

F X V

HUMIDIFIER CONTROL

(TYPICAL OF 2)

SPACE TEMP &

HUM SENSOR

UI-2

H-1

(EXISTING.)

SUPPLY AIR TO

TERMINAL UNITSOUTDOOR

DIUI-3

DA-T

*SEE NOTES

H-2-1

(HUMID)

*SEE DETAIL

& NOTES

HUMIDIFIERC

C2

CWS

CWR

*SEE NOTES

AO-8

V-2B

N.C.

HUMIDIFIER

SUPPLY AIR TO

TERMINAL UNITS

3RD FLOOR MECH.

EQUIPMENT RM. -

(MECH. ROOM 128)

LPS

HUMID.

*SEE NOTES

COND.

CO-4DO-3

V-4V-3

*SEE DETAIL

& NOTES

FEC-26

IOM-47

IOM-47 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

POINT NAME/DESCRIPTION

DISCHARGE HUMIDITY 1

DISCHARGE HUMIDITY 2

FEC-26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

ZONE TEMPERATURE

ZONE HUMIDITY

SUPPLY FAN STATUS

PRE-COOL COIL TEMPERATURE (PC-T)

EXHAUST FAN STATUS

FREEZE STAT (LL)

COOLING VALVE 2

DISCHARGE AIR TEMPERATURE (DA-T)

PRE-HEAT TEMPERATURE (HC-T)

SUPPLY FAN ENABLE/DAMPER

HUMIDIFIER CONTROL VALVE COMMAND (V-4)

COOLING VALVE 1

EXHAUST FAN ENABLE

HUMIDIFIER ISOLATION VALVE COMMAND (V-3)

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

AS-BUILT REV. FINAL POINT TERM.2 12/3/13 DB

BILL OF MATERIALS

Designation Qty Part Number Description

DA 2 M9220-BGC-3 ACT.,24VAC,SPR.RTN.,189#IN,2-AUX.,W/E.S.

X-TH 3 HE-67N3-0N00P DUCT COMBO SENSOR,T-NI & %RH

1 TE-6311M-1 SENSOR,T-NI,0.1%,8IN DUCT

R 2 RIBUIC 10 AMP, SPDT, 10/30 VAC/120 VAC

CT 2 RIBXKTF CURRENT SENSING DEVICE, GO/NO

LL 1 A70GA-1C LOW LIMIT,AUTO RESET,20FT ELEM.

FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET

IOM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET

V-X SEE VALVE SCHEDULE FOR MORE INFORMATION

DA

(D-1)

N.C.

C

C1

CWS

*SEE NOTES

CO-7

N.C.

UI-5

PC-TLL

V-2A

CWR

NORMALLY

CLOSED

EN

ER

GY

RE

CO

VE

RY

WH

EE

L

BYPASS

NORMALLY

OPEN

D-1

(DA)

H

C

AO-9

V-1

HWS

HWR

UI-4

HC-T

RF

RELIEF

AIR RELIEF

AIR H-2-2

(HUMID)

BI-7

CT

UI-6

CT

UI-1 (Temp)

(Humid)

*SF S/S SIGNAL (BO-1) IS

HARD-WIRED THROUGH

DA ‘D-1’ END SWITCH

*SEE NOTES

*SF S/S SIGNAL (BO-1) IS

HARD-WIRED THROUGH

DA ‘D-1’ END SWITCH

NOTE(S): ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY

EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-

USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC

CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON

DDC CONTROLLERS AS INDICATED. *REFER TO C-2B FOR CONTROLLER WIRING DETAILS

AND DRAWING C-2C FOR ASSOCIATED SEQUENCE OF OPERATIONS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND

INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE

‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING

M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR

ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS

WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL

PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS

HAVE BEEN APPROVED BY THE VA HOSPITAL.

HEAT/ENERGY RECOVERY WHEEL WAS NOT IN WORKING CONDITION AND WAS LEFT AS

EXISTING.

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

C-2B

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

Drawing Title

CONTROLLER WIRING DETAIL –

AHU FOR LAB (3RD FLOOR ROOF)

Project Title

CONTROLLER WIRING DETAIL – AHU FOR LAB (3RD FLOOR ROOF)

AS-BUILT REV. NEW DWG. / POINT TERM.1 12/3/13 DB

SEE AS-BUILT CONTROL DRAWINGS C-2A AND C-2C FOR

ASSOCIATED UNIT CONTROL DIAGRAM AND SEQUENCE OF

OPERATIONS.

NOTE(S):

124816326412

ON

Address:

SA

PW

R

CO

M

SA BUS

FC BUS

CO

M

SH

LD+1

5V

IN

ICO

M

IN

ICO

M

+1

5V

IN

ICO

M

IN

ICO

M

+1

5V

IN

ICO

M

IN

ICO

M

IN

ICO

M

IN

ICO

M

UNIVERSAL BINARY

BINARY

OU

T4

OC

OM

OU

T5

OC

OM

OU

T6

OC

OM

OU

T7

OC

OM

OU

T8

OC

OM

OU

T9

OC

OM

CONFIGURABLE ANALOG

HOT

24V

COM

FEC2611

OU

T1

OC

OM

OU

T2

OC

OM

OU

T3

OC

OM

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

124816326412

ON

Address:

SA

FC

HOT

24V

COM

IOM4711

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

SA

PW

CO

M

+ - CO

M

SH

LD

SA/FC BUS

BINARY

OU

T4

OC

OM

OU

T5

OC

OM

OU

T6

OC

OM

OU

T7

OC

OM

OU

T8

OC

OM

OU

T9

OC

OM

CONFIGURABLE ANALOG

OU

T1

OC

OM

OU

T2

OC

OM

OU

T3

OC

OM

+1 5V

IN

ICO

M

IN

ICO

M

+1 5V

IN

ICO

M

IN

ICO

M

+1 5V

IN

ICO

M

IN

ICO

M

IN

ICO

M

IN

ICO

M

UNIVERSAL BINARY

ZO

NE

TE

MP

ER

AT

UR

E

CO

OL

ING

VA

LV

E 1

CO

OL

ING

VA

LV

E 2

SU

PP

LY

FA

N E

NA

BL

E/D

AM

PE

R

HU

MI

DIF

IER

CO

NT

RO

L V

AL

VE

CO

MM

AN

D (

V-4

RE

TU

RN

FA

N E

NA

BL

E

HU

MI

DIF

IER

IS

OL

AT

ION

VA

LV

E C

OM

MA

ND

(V -3)

ZO

NE

HU

MI

DIT

Y

DIS

CH

AR

GE

AI

R T

EM

PE

RA

TU

RE

(D

A-T

PR

E-H

EA

T T

EM

PE

RA

TU

RE

(H

C-T

PR

E-C

OO

L C

OIL

TE

MP

ER

AT

UR

E (

PC

-T)

EX

HA

US

T F

AN

ST

AT

US

SU

PP

LY

FA

N S

TA

TU

S

FR

EE

ZE

ST

AT

/ S

HU

TD

OW

N

DIS

CH

AR

GE

HU

MI

DIT

Y 1

DIS

CH

AR

GE

HU

MI

DIT

Y 2

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 8/18/11

C-2C

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Drawing Title

SEQUENCE OF OPERATIONS -

AHU FOR LAB

Project Title

SEQUENCE OF OPERATIONS - AHU FOR LAB

AHU FOR LAB SEQUENCE OF OPERATION

1. GENERAL

UNIT IS MANUALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. WHEN THE UNIT IS OFF DAMPER D-1 IS CLOSED. WHEN UNIT IS ON

DAMPER D-1 IS OPENED.

2. TEMPERATURE CONTROL

THE SUPPLY AIR TEMPERATURE, SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT BY DCP MODULATING V-1 OR V-2 IN SEQUENCE. V-1 SHALL BE

CLOSED TO COIL WHEN OUTDOOR TEMPERATURE IS ABOVE 50F.

3. AIR FLOW

THE SUPPLY FAN SHALL RUN AT CONSTANT SPEED PROVIDING CONSTANT AIR FLOW.

4. HUMIDITY CONTROL

WHEN THE SUPPLY FAN IS OFF AND THE DCP IS NOT CALLING FOR HUMIDIFICATION SENSED BY THE ROOM HUMIDITY SENSOR H-1 THE TWO-WAY VALVE

V-3 IS CLOSED. WHEN THE SUPPLY FAN IS ON AND THE DCP IS CALLING FOR HUMIDIFICATION THE V-3 SHALL BE OPEN.

THE SPACE HUMIDITY SENSED BY H-1 IS MAINTAINED AT SETPOINT BY DCP MODULATING HUMIDIFIER CONTROL VALVE V-3 TO MAINTAIN THE DESIRED

RELATIVE HUMIDITY. H-2 OVERRIDES THIS CONTROL TO MAINTAIN A MAXIMUM HUMIDITY OF 80%. VALVE V-4 SHALL BE INTERLOCKED WITH

TEMPERATURE SWITCH TO KEEP HUMIDIFIER OFF UNTIL CONDENSATE TEMPERATURE APPROACHES STEAM TEMPERATURE.

5. FREEZE PROTECTION

IF THE AIR TEMPERATURE AS SENSED BY T-2 FALLS BELOW 45F AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS

BELOW 40F THE SUPPLY FAN SHALL STOP, THE DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL BE INDICATED AT THE DCP AND BMS.

6. EMERGENCY SHUTDOWN/RESTART

WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY FAN SHALL SHUT OFF, DAMPER D-1 CLOSE AND AN ALARM SIGNAL

SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM. SUPPLY FAN RESTARTS AND DAMPER D-1 OPENS WHEN THE FIRE ALARM CIRCUIT IS MANUALLY

RESET.

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

AS-BUILT REV. NEW DWG. / REV. NOTE2 12/3/13 DB

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 8/12/11

C-3A

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

Drawing Title

AIR HANDLING UNIT CONTROL -

AHU FOR CT SCANNER

(3RD FLOOR ROOF)

Project Title

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

110v (EXISTING)

*EXISTING EX. CP

2ND FLOOR MECH.

EQUIPMENT RM. -

(MER 2109A)

SUPPLY

AIROUTDOOR

FILTER

N.C.

*SEE NOTES (TYP.) E

H

ELEC.

HEAT

UI-2

MA-T

C

C

CWS

CWR`

*SEE NOTES

CO-6

V-1

AIR HANDLING UNIT CONTROL – AHU FOR CT SCANNER (3RD FLOOR ROOF)

RETURN

AIR

D-2

CO-7

RA-H

RCO-5

ST-T

SPACE

TEMPERATURE

UI-3

*SEE NOTES

(TEMP.)

RETAIL STORE ROOM EXISTING CONTROLS

H C

CO-4

EXISTING

RE-HEAT

CONTROL

FEC-26

FEC-26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

DISCHARGE AIR TEMPERATURE (DA-TE)

MIXED AIR TEMP (MA-T)

SUPPLY FAN STATUS

RETURN HUMIDITY (RA-H)

FREEZE STAT / SHUTDOWN (LL)

RETAIL STORE ROOM TEMP

RETURN TEMP (RA-T)

SUPPLY FAN COMMAND

CHILLED WATER VALVE COMMAND

EXISTING RE-HEAT CONTROL

ELECTRIC HEAT SCR COMMAND

DAMPER COMMAND

AS-BUILT REV. FINAL POINT TERM.2 12/3/13 BM

BILL OF MATERIALS

Designation Qty Part Number Description

NS-T 1 NS-BTP7002-2 NETWORK SENSOR,RM,1K NI,NO ADJ.,NO LOGO

RA-H 1 HE-67N3-0N00P DUCT COMBO SENSOR,T-NI & %RH

XX-T 3 TE-6315P-1 SENSOR,T-NI,0.1%,8FT AVG.,

1 TE-6311M-1 SENSOR,T-NI,0.1%,8IN DUCT

LL 1 A70GA-1C LOW LIMIT,AUTO RESET,20FT ELEM.

FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET

V-X SEE VALVE SCHEDULE FOR MORE INFORMATION

UI-4

RA-T

SCR

BI-7

CT

BI-8

LL

UI-1

DA-T

NS-T

NETWORK SPACE

TEMPERATURE SENSOR

LOCATED IN

ROOM 2165 D

S/A BUS

SPACE TEMPERATURE CONTROL

1 2

NOTE(S): ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY

EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-

USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC

CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON

DDC CONTROLLERS AS INDICATED. *REFER TO C-3B FOR CONTROLLER WIRING DETAILS

AND DRAWING C-3C FOR ASSOCIATED SEQUENCE OF OPERATIONS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND

INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE

‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING

M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR

ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS

WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL

PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS

HAVE BEEN APPROVED BY THE VA HOSPITAL.

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

C-3B

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

Drawing Title

CONTROLLER WIRING DETAIL

– AHU FOR CT SCANNER

(3RD FLOOR ROOF)

Project Title

CONTROLLER WIRING DETAIL – AHU FOR CT SCANNER (3RD FLOOR ROOF)

AS-BUILT REV. NEW DWG. / POINT TERM.1 12/3/13 DB

SEE AS-BUILT CONTROL DRAWINGS C-3A AND C-3C FOR

ASSOCIATED UNIT CONTROL DIAGRAM AND SEQUENCE OF

OPERATIONS.

NOTE(S):1

124816326412

O N

Address:

S A

PW

R

C O

M

SA BUS

FC BUS

C O

M S

H

LD+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

IN

IC

O M

IN

IC

O M

UNIVERSAL BINARY

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

FEC2611

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

D

IS

C H

A R

G E

A

IR

T

EM

PE

R

A

TU

R E

SU

PP

LY

F

A N

C M

D

C H

IL

LE

D W

A

TE

R V

A

LV

E C

O M

M A

N D

EX

IS

TI

N

G R

E- H

EA

T

C O

N

TR

O L

EL

EC

TR

IC

H

EA

T

SC

R C

O M

M A

N D

D A

M

PE

R C

O M

M A

N D

M

IX

ED

A

IR

T

EM

PE

R A

TU

R

E

R

ET

A

IL

S

TO

R E

R O

O M

T

EM

PE

R

A

TU

R E

R

ET

U R

N T

EM

PE

R A

TU

R

E

R

ET

U R

N H

U M

ID

IT

Y

SU

PP

LY

F

A N

S

TA

TU

S

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 8/12/11

C-3C

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

Drawing Title

SEQUENCE OF OPERATIONS -

AHU FOR CT SCANNER

Project Title

SEQUENCE OF OPERATIONS - AHU FOR CT SCANNER (3RD FLOOR ROOF)

AHU FOR CT SCANNER - SEQUENCE OF OPERATION

1. GENERAL

UNIT IS NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. H-O-A SWITCH SHALL BE KEPT IN THE “AUTO” POSITION. “HAND” AND

“OFF” POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. WHEN THE UNIT IS “OFF” D-1 SHALL BE CLOSED. WHEN THE UNIT IS “ON” D-1 SHALL BE FULLY

OPENED.

2. TEMPERATURE CONTROL

SPACE AIR TEMPERATURE SENSED BY ROOM TEMPERATURE SENSOR T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING V-1 AND CYCLING

OF ELECTRIC HEATIN COIL IN SEQUENCE.

3. AIR FLOW CONTROL

THE SUPPLY FAN SHALL RUN AT CONSTANT SPEED PROVIDING CONSTANT AIR FLOW.

4. HUMIDITY CONTROL

WHEN THE DCP IS NOT CALLING FOR HUMIDIFICATIN SENSED BY HUMIDISTAT H-1, TWO-WAY “ON-OFF” CONTROL VALVE V-2 SHALL REMAIN CLOSED.

WHEN THE DCP IS CALLING FOR HUMIDIFICATION, V-2 SHALL REMAIN OPEN.

RETURN AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT SENSED BY H-1 VIA DCP BY MODULATING CONTROL VALVE V-3 TO MAINTAIN THE DESIRED

HUMIDITY. THE DCP SHALL OVERRIDE THE CONTROL TO MAINTAIN HUMIDITY IN SUPPLY DUCT BELOW 80% AS SENSED BY H-2. DCP SHALL CLOSE VALVE

V-2 WHENEVER THE SUPPLY FAN IS OFF. VALVE V-3 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH TO KEEP THE HUMIDIFIER OFF UNTIL

CONDENSATE TEMPERATURE APPROACHES STEAM TEMPERATURE.

5. FREEZE PROTECTION

IF THE AIR TEMPERATURE SENSED BY T-2 FALLS BELOW 45°f AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS

BELOW 40°F THE SUPPLY FAN SHALL SHUT DOWN, THE DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL INDICATE AT THE DCP AND BMS.

6. EMERGENCY SHUTDOWN/RESTART

WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY FAN SHALL STOP AND THE ALARM SIGNAL IS TRANMITTED TO THE

FIRE ALARM SYSTEM, DAMPERS D-1 AND D-2 SHALL CLOSE. SUPPLY AND RETURN FANS SHALL RESTART AND DAMPERS SHALL OPEN WHEN THE FIRE

ALARM CIRCUIT IS MANUALLY RESET.

AS-BUILT REV. NEW DWG. / ADD NOTE2 12/3/13 BM

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 8/12/11

C-4A

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

Drawing Title

AIR HANDLING UNIT CONTROL

- AHU FOR ICU

(3RD FLOOR ROOF)

Project Title

AIR HANDLING UNIT CONTROL - AHU FOR ICU (3RD FLOOR ROOF)

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

SUPPLY AIR

TO VAV’S

MIN

OUTDOOR

AIR

RELIEF

RETURN

FILTER

DI-3

*SEE NOTES (TYP)

D-3

(DA)

*AO-2

D-1

(DA)

AO-2

D-2

(DA)

AO-2

C

C

CWS

CWR

DI-3

*SEE NOTES

BILL OF MATERIALS

Designation Qty Part Number Description

DA 4 M9220-GGC-3 ACT.,0-10V,SPR.RTN.,189#IN,2-AUX.

LL 1 A70HA-1C STAT.,LOW LIMIT,MAN. RESET,20FT ELEM.

FX-16 1 LP-FX16X01-000C CNTRLR,DIG,FX,6AI,8DI,9DO,4AO

XM-07 1 LP-XM07X01-000C FX-16 CNTRLR EXPANSION

V-1~4 SEE VALVE SCHEDULE

H

RA-T

AI-1

HIGH

LIMIT

AO-4

V-1

N.C.

N.C. *SEE DETAIL

& NOTES

HUMIDIFIER

H L

SPS-1

DI

AI-2

DA-T

N.C.

110v (EXISTING)

*EXISTING EX. CP

4TH FLOOR MECH.

(STORAGE RM 4060)

DI-1

HUMIDIFIER CONTROL

DO-3

DI-

AI-3

MA-T

DO-1

RH

C

STEAM

RE-HEAT

LPS

AO-1

V-2

COND.

N.O.

*SEE NOTES

LPS

HUMID.

*SEE NOTES

COND.

AO-3

V-4

*SEE NOTES

AS-BUILT REV. FINAL POINT TERM.2 12/3/13 DB

B D F C D L F T

T S

F

CONTROLLER DETAIL AND INFORMATION

XM-07 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

AI-6

DI-1

DI-2

DI-3

DI-4

AO-1

AO-2

AO-3

DO-1

DO-2

DO-3

DO-4

DO-5

DO-6

POINT NAME/DESCRIPTION

PUMP 1 STATUS

PUMP 2 STATUS

HEAT EXCHANGER VALVE

PUMP 1 ENABLE

PUMP 2 ENABLE

FX-16 POINT IDENTIFICATION

POINT #

AI-1

AI-2

AI-3

AI-4

AI-5

AI-6

DI-1

DI-2

DI-3

DI-4

DI-5

DI-6

DI-7

DI-8

AO-1

AO-2

AO-3

AO-4

DO-1

DO-2

DO-3

DO-4

DO-5

DO-6

DO-7

DO-8

DO-9

POINT NAME/DESCRIPTION

OUTDOOR AIR TEMPERATURE (OA-T)

DISCHARGE AIR TEMPERATURE (DA-T)

SUPPLY FAN STATUS

ZONE HUMIDITY

EXHAUST FAN 1(EF-1) STATUS

SMOKE DETECTOR & LOW LIMIT (LL) SHUTDOWN

FREEZE PUMP FP-1 STATUS

MIXED AIR TEMPERATURE (MA-T)

RETURN AIR TEMPERATURE (RA-T)

ICU 5 ALARM

DAMPER COMMAND

HEATING VALVE

HUMIDIFIER VALVE

COOLING VALVE

FAN COMMAND

ICU 6 ALARM

EXHAUST FAN COMMAND

FREEZE PUMP ENABLE

FX-16

XM-07

AI-4

LL

DI-3

SH-I

NETWORK SPACE

TEMPERATURE SENSOR

LOCATED IN _________

AI-5

SPACE HUMIDITY CONTROL

CT

DI-2

EXISTING EF-1 CONTROL

*SEE NOTES DO-2

R *IOM-47-2

*IOM-47-2

ICU ALARMS

ICU-5 DI-5 ICU-6 DI-6

OUTDOOR

AIR

N.C.

D-2

(DA)

AO-2

NOTE(S): ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY

EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-

USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC

CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON

DDC CONTROLLERS AS INDICATED. *REFER TO C-4B FOR CONTROLLER WIRING DETAILS,

C-4C FOR ASSOCIATED VAV BOXES AND DRAWING C-4D FOR ASSOCIATED SEQUENCE OF

OPERATIONS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND

INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE

‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING

M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR

ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS

WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL

PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS

HAVE BEEN APPROVED BY THE VA HOSPITAL.

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

C-4B

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

Drawing Title

CONTROLLER WIRING DETAIL

– AHU FOR ICU

(3RD FLOOR ROOF)

Project Title

CONTROLLER WIRING DETAIL – AHU FOR ICU (3RD FLOOR ROOF)

AS-BUILT REV. NEW DWG. / POINT TERM.1 12/3/13 DB

SEE AS-BUILT CONTROL DRAWINGS C-4A, C-4C AND C-4D FOR

ASSOCIATED UNIT CONTROL DIAGRAM, ASSOCIATED VAV BOX

CONTROLS AND SEQUENCE OF OPERATIONS.

NOTE(S):

8(3)A Max 250V~

8(3)A Max 250V~

8(3)A Max 250V~

3(1)A Max 250V~

3(1)A Max 250V~

3(1)A Max 250V~

AO

DO

DO

1 C om DO

DO

2 C om DO

DO

3 C om DO

DO

5 C om DO

DO

DO

4 C om

DO

6 C om

Ea rth

V ~C om

V ~H ot

Power

1 2 3

AO

C om

AO

11 12 13

DI

C om

DI

DI

14 15 16

DI

DI

DI

21 22 23

AI

C om

AI

AI

C om

AI

25 26 27

AI

+5 V

AI

+1 5V

LL

+1 5V

LL

Co m

1 32

Supervisory Link

V

51 52 5341 4239 4037 3833 343231 3635

LON

Not Used

NET B

NET A

N2 1: Com

2: RT-

3: RT+

1 2 3 4 5 6 7 8 9 1110 12 13 14 15 2221 23 24 25 26 2827 29 30 32 3331 34 35

7163 72 73 74 75 7776 78 79 9180 92 9362614241 43 44 45 46 4847 51 5352 54 55 56 57

N2 LON

1: Com Not Used

2: RT- NET B

3: RT+ NET A

JP1

JP2Supervisory Link

To Modem(Optional )* (Optional )* *Connectors JP1 and JP2 are in alternative

TB3

TB4 TB5 TB6

TB7 TB8

TB1 TB2

Max 8(3)250V~

Max 8(3)250V~

Max 8(3)250V~

Max 5(3)250V~

Max 5(3)250V~

Max 8(3)250V~

Analog Inputs

J1 J2 Local LinkBus To Remote Display

Digital Inputs

Analog Outputs

Digital Outputs

AG

ND

AI

EX

T

V

AG

ND

AI

AG

ND

AI

EX

T

V

AG

ND

AI

AG

ND

AI

AV

PS

/E

XT

V

AG

ND

AI

Co m

LL

LL

Co m

LL

LL

+1

6V DI

DI

C om

DI

DI

C om

DI

DI

DI

C om

DI

DI

C om

DI

DI

DI

C om

DI

DI

V

~C om

DI

V

~H ot

DO

1 C om

DO

1 n o

DO

2 C om

DO

2 n o

DO

3 C om

DO

3 n o

DO

6 n o

DO

7 n o

DO

4/5

C om

DO

8 n o

DO

4 n o

DO

5 n o

DO

6/7

/8 Co m

FA

IL

n c

FA

IL

C om

AO

C om AO

AO

C om AO

AO

AO

AO

V

~C om

V ~C om

V ~H ot

FA

IL

n o

AO

C om

AO

C om

AO

V

~H ot

V

V

Power

V

1 2 3

FA

N

C O

M M

A N

D

EX

H

A U

ST

F

A N

C O

M M

A N

D

FR

EE

ZE

P

U M

P

EN

A B

LE

O U

TD

O

O R

A

IR

T

EM

PE

R

A

TU

R E

D

IS

C H

A R

G E

A

IR

T

EM

PE

R

A

TU

R E

M

IX

ED

A

IR

T

EM

PE

R A

TU

R

E

R

ET

U R

N A

IR

T

EM

PE

R A

TU

R

E

ZO

N

E H

U M

ID

IT

Y

SU

PP

LY

F

A N

S

TA

TU

S

EX

H

A U

ST

F

A N

S

TA

TU

S

IC

U

A

LA

R

M

FR

EE

ZE

P

U M

P

ST

A

TU

S

SM

O

K E

D

ET

EC

TO

L

L

SH

U

TD

O W

N

IC

U

A

LA

R

M

H

EA

TI

N

G V

A

LV

E

D A

M

PE

R C

O M

M A

N D

H U

M

ID

IF

IE

R V

A

LV

E

C O

O

LI

N G

V A

LV

E

PU

M

P

EN

A

B

LE

PU

M

P

EN

A

B

LE

H

EA

T

EX

C H

A N

G

ER

V A

LV

E

PU

M

P

ST

A

TU

S

PU

M

P

ST

A

TU

*CONTROLLER N2 ADDRESS = 10

VMA-16

(SEE NOTES)

MOUNT DIRECTLY TO

DAMPER ACTUATOR SHAFT

WITH THE DAMPER IN THE

"OPEN" POSITION.

CONNECT TO VAV BOX

VELOCITY PROBES

24V FROM NEW XFMR(S) MOUNTED IN

THE AHU FOR ICU CONTROL PANEL

*EXISTING

TRANSFORMER

211-1009

IW/BMIW/JAIW

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

C-4C

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

Drawing Title

VAV BOX CONTROLS FOR 3RD

FLOOR - SERVED BY AHU FOR ICU

(TYP. OF 24)

Project Title

VAV BOX CONTROL FOR 3RD FLOOR - SERVED BY AHU FOR ICU

(TYP. OF 10)

BILL OF MATERIALS

Designation Qty Part Number Description Field Devices:

STT-1 10 NS-BTP7002-0 SENSOR,TEMP.,W/C,NETWORK,WALL MNT.

TE-1 10 TE-6311M-1 SENSOR,TEMP.8IN,DUCT MNT.,

VMA-1 10 MS-VMA1620-0 VAV MODULAR ASSY.,CLG W/ REHEAT,MS/TP

VLV SEE VALVE SCHEDULE

SEQUENCE OF OPERATIONS

VAV SYSTEM CONTROL:

COOLING MODE:

On a rise in space temperature above the space temperature cooling set point, the damper will modulate from the minimum CFM set point to the maximum CFM set point. As the space temperature drops, the damper will modulate to the minimum CFM set point.

HEATING MODE:

On a drop in space temperature below the heating space temperature set point, the damper will modulate to the minimum heating CFM set point. On a further drop in space temperature below the space temperature set point, the heating coil valve will modulate to maintain the heating space temperature to it’s set point. As the temperature rises the reverse will occur.

*SEE NOTES

VELOCITY PROBES

*SEE NOTES

TEMP. / ADJ.

STT-1

SPACE TEMP.

SENSOR W/ OVERRIDE

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

TO VMA

TE-1

H

C

HWR

VLV

HWS

TO VMA

SUPPLY AIR

FROM

AHU FOR ICU

SUPPLY AIR

TO ZONES

*THERE ARE (10) EXISTING JCI BOXES SERVED BY AHU FOR ICU THAT

WILL BE ADDED TO A NEW N2 BUS.

AS-BUILT REV. FINAL POINT TERM./NOTE1 12/3/13 BM

TYPICAL CONSTRUCTION NOTES

THE NEW MODULATING ELECTRONIC CONTROL VALVES SHALL BE

PROVIDED BY MODERN CONTROLS AND INTEGRATED TO THE NEW

DDC CONTROLLERS. FIELD INSTALLATION SHALL BE PROVIDED BY

THE PROJECT GENERAL CONTRACTOR. SEE VALVE SCHEDULE FOR

MORE INFORMATION.

AIR FLOW SCHEDULE PROVIDED BY THE VA FOR REFERENCE ONLY;

SEE AS-BUILT DOCUMENTATION FOR MORE INFO.

FREEZE PROTECTION AND SUPPLY AIR TEMPERATURE MONITORING

PROVIDED BY ASSOCIATED AHU CONTROLS.

NEW PANEL MOUNTED TRANSFORMER(S) SHALL PROVIDE 24V

POWER TO NEW VAV CONTROLLERS AS REQUIRED IN THE FIELD.

ALL CONTROL POINT DESCRIPTIONS AND TERMINAL DESIGNATION

SHALL BE RECORDED IN THE FIELD FOR AS-BUILT DOCUMENTATION.

AS-BUILT NOTE

OUR O&M MANUAL PROVIDED FOR PROJECT CLOSEOUT

INCLUDEDS ALL COMMISSION AND CHECKOUT INFORMATON

FOR ALL VAV BOXES.

THE O&M MANUAL INCLUDES A TYPCIAL VAV CONTROLLER

COMMISSIONING SHEET AND ALSO A COMPLETE VAV BOX

COMMISSIONG CHECK LIST FOR ALL VAV BOXES AS SERVED

BY THEIR ASSOCIATED UNIT.

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 8/12/11

C-4D

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2C

WILMINGTON, DELAWARE

Drawing Title

SEQUENCE OF OPERATIONS -

AHU FOR ICU

Project Title

SEQUENCE OF OPERATIONS - AHU FOR ICU

AHU FOR ICU - SEQUENCE OF OPERATION

1. GENERAL

SUPPLY AND RETURN FANS ARE NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. H-O-A SWITCH SHALL BE KEPT IN THE

"AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. WHEN THE UNIT IS "OFF" D-1, D-2 AND D-3 SHALL BE CLOSED.

WHEN THE UNIT IS "ON" D-1, D-2 AND D-3 SHALL BE OPENED.

2. TEMPERATURE CONTROL

SUPPLY AIR TEMPERATURE SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING EITHER V-1 AND V-2 OR D-1, D-2 AND D-3 IN

SEQUENCE.

WHEN THE TEMPERATURE OF THE OUTSIDE AIR PROVIDED BY BMS IS BELOW 60F DCP PREVENTS MODULATION OF D-1, D-2 AND D-3 IN OPPROSITE

UNISON AND THEN V-2 MODULATES TO MAINTAIN SUPPLY AIR TEMPERATURE SENSED BY T-1.

WHEN THE TEMPERATURE OF THE OUTSIDE AIR PROVIDED BY BMS IS ABOVE 60F DAMPER D-2 OPENS, DAMPERS D-1 AND D-3 CLOSE TO MINIMUM

OUTSIDE AIR POSITION AND V-1 MODULATES TO MAINTAIN THE SCHEDULED SUPPLY AIR TEMPERATURE.

3. AIR FLOW CONTROL

THE SUPPLY FAN SHALL RUN AT CONSTANT SPEED PROVIDING CONSTANT AIR FLOW.

IF STATIC PRESSURE AT SPS-1 EXCEEDS 3" THE SUPPLY FAN STOPS.

4. HUMIDITY CONTROL

WHEN THE DCP IS NOT CALLING FOR HUMIDIFICATIN SENSED BY RETURN AIR HUMIDISTAT H-1, TWO-WAY "ON-OFF" CONTROL VALVE V-3 SHALL REMAIN

CLOSED. WHEN THE DCP IS CALLING FOR HUMIDIFICATION, V-3 SHALL OPEN.

RETURN AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING CONTROL VALVE V-4 TO MAINTAIN THE DESIRED HUMIDITY. THE

DCP SHALL OVERRIDE THE CONTROL TO MAINTAIN HUMIDITY IN SUPPLY DUCT BELOW 80% AS SENSED BY H-2.

DCP SHALL CLOSE V-3 WHENEVER THE SUPPLY FAN IS OFF.

VALVE V-4 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH TO KEEP THE HUMIDIFIER OFF UNTIL CONDENSATE TEMPERATURE APPROACHES

STEAM TEMPERATURE.

5. FREEZE PROTECTION

IF THE AIR TEMPERATURE SENSED BY T-2 FALLS BELOW 45F AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS

BELOW 40F THE SUPPLY FAN SHALL SHUT DOWN, THE DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL INDICATE AT THE DCP AND BMS.

WHEN OUTSIDE AIR TEMPERATURE PROVIDED BY BMS FALLS BELOW 40F THEN FREEZE PROTECTION PUMP P-1 OPERATES.

6. EMERGENCY SHUTDOWN/RESTART

WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY AND RETURN FANS SHALL STOP AND THE ALARM SIGNAL IS

TRANSMITTED TO THE FIRE ALARM SYSTEM, DAMPERS D-1 AND D-3 SHALL CLOSE. SUPPLY AND RETURN FANS SHALL RESTART AND THE DAMPERS OPEN

WHEN THE FIRE ALARM CIRCUIT IS MANUALLY RESET.

AS-BUILT REV. NEW DWG.2 12/3/13 BM

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 7/20/11

AS-BUILT REV. NEW DWG. / FINAL TERM.1 01/28/14 BM

C-5

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE-2C

WILMINGTON, DELAWARE

Drawing Title

AIR HANDLING UNIT CONTROL

– AHU-9 FOR LAUNDRY

Project Title

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

110v (EXISTING)

*EXISTING

EX. CPFEC-26

SUPPLY

SFRETURN

UI-1

DA-T

FEC-26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

DISCHARGE AIR TEMPERATURE (DA-T)

RETURN AIR TEMPERATURE (RA-T)

SUPPLY FAN STATUS

COMPRESSOR #2 STATUS

HEAT EXCHANGER PUMP STATUS

HEAT EXCHANGER VALVE 1

HEAT EXCHANGER VALVE 2

HEAT EXCHANGER SUPPLY TEMPERATURE

COMPRESSOR #1 STATUS

SUPPLY FAN START / STOP

DX STAGE 1 COMMAND

DX STAGE 2 COMMAND

UI-2

RA-T

AIR HANDLING UNIT CONTROL – AHU-9 FOR LAUNDRY

BILL OF MATERIALS

Designation Qty Part Number Description

DA 1 M9220-GGC-3 ACT.,PROP.,0-10V,179#IN,2-AUX.,W/ES

XX-T 2 TE-6315P-1 SENSOR,T-NI,0.1%,8FT AVG.,

LL 1 A70HA-1C STAT.,LOW LIMIT,20FT ELEM.,MAN. RESET

FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET

IOM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET

V-X SEE VALVE SCHEDULE FOR MORE INFORMATION

NOTE(S):

ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY

EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-

USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC

CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON

DDC CONTROLLERS AS INDICATED. *REFER TO C-2D FOR CONTROLLER WIRING DETAILS

AND DRAWING C-2E FOR ASSOCIATED SEQUENCE OF OPERATIONS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND

INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE

‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING

M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR

ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS

WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL

PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS

HAVE BEEN APPROVED BY THE VA HOSPITAL.

BI-7

CT

FILTER

REMOTE

CONDENSING UNIT

DX COOLING CONTROL DETAIL

BO-3

STAGE 1 CONTROL

UI-4

CT

UI-5

CT

HEAT

EXCHANGER

STEAM

CONDENSATE

BI-8

CT

TE

HWS

HWR

*SEE NOTES

P-X

*SEE NOTES

LPS

AO-8

EX. V

AO-9

EX. V

RM 141 HEAT EXCHANGER

*SEE DETAIL

BELOW

D X

STAGE 2 CONTROL

NORTH OF REHAB;

ON ROOF ABOVE

GROUND FLOOR

124816326412

O N

Address:

S A

PW

R

C O

M

SA BUS

FC BUS

C O

M S

H

LD+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

IN

IC

O M

IN

IC

O M

UNIVERSAL BINARY

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

FEC2611-0

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

D

IS

C H

A R

G E

A

IR

T

EM

PE

R

A

TU

R E

(D A

-T

H

EA

T

EX

C H

A N

G

ER

V A

LV

E

H

EA

T

EX

C H

A N

G

ER

V A

LV

E

SU

PP

LY

F

A N

S

TA

R T

/ S

TO

P

D X

ST

A

G E

C

O M

M A

N D

D X

ST

A

G E

C

O M

M A

N D

R

ET

U R

N A

IR

T

EM

PE

R A

TU

R

E (R

A -T

H

EA

T

EX

C H

A N

G

ER

S U

PP

LY

T

EM

PE

R

A

TU

R E

C O

M

PR

ES

SO

R

ST

A

TU

S

C O

M

PR

ES

SO

R

ST

A

TU

S

SU

PP

LY

F

A N

S

TA

TU

S

H

EA

T

EX

C H

A N

G

ER

P U

M P

ST

A

TU

(TRUNK-1 / FX-20 PHARMACY)

2C - .Title Page
C-1A AHU for OR
C-1B AHU for OR controller
C-1C OR VAV boxes
C-1D AHU OR sequence
C-2A AHU for LAB
C-2B AHU for LAB controller
C-2C AHU Lab sequence
C-3A AHU for CT
Visio-C-3B AHU for CT controller
Visio-C-3C AHU CT sequence
Visio-C-4A AHU for ICU
Visio-C-4B AHU for ICU controller
Visio-C-4C ICU VAV boxes
Visio-C-4D AHU ICU sequence
Visio-C-5 AHU-9 LAUNDRY