MECHANICAL AND CONTROL SYSTEMS
Environmental Control System
Building Automation System
VA MEDICAL CENTER
HVAC CONTROLS UPGRADE - PHASE 2B
WILMINGTON, DELAWARE
PROJECT
OWNER
ENGINEER
CONTRACTOR
211-1009
MODERN CONTROLS INC
7 BELLECOR DRIVE
NEW CASTLE, DE. 19720
DATE
Branch Information
CONTRACT NUMBER
IW/BM
APPLICATION ENGINEER
7/19/11IW/JA
PROJECT MANAGER
IW
SALES ENGINEER
REFERENCE DRAWING
SUB. REVISION TITLE DATES1 12/13/11 VD
NO. REVISION-LOCATION ECN DATE BY
Automatic Temperature Controls
Heating
Air Conditioning
Air Filters
Water Treatment
Coil Cleaning
Contract Operations
Time-Shared Automated Building Service
Refrigeration
Industrial Controls / Recording / Indication Equipment
Air and Water Systems Balancing
Instrumentation System Installation
Building Operations Management
Energy Conservation Control
Custom Programmed Maintenance
HATCH MOTT MACDONALD
27 BLEEKER ST.
MILLBURN, NJ 07041
BOB SMITH CONTRACTORS
281 EAST EVERGREEN ST.
WEST GROVE, PA 19390
DEPT. OF VETERANS AFFAIRS
1601 KIRKWOOD HIGHWAY
WILMINGTON, DE 19805
VA HVAC CONTROLS UPGRADE - PHASE 2B
(PARTIAL SUBMITTAL - INCLUDES 7TH 8TH & 9TH FLOOR HVAC EQUIPMENT)
PAGE # DRAWING TITLE LAST REVISION
TP-1 TITLE PAGE 01/28/14
C-1A AIR HANDLING UNIT CONTROL – AHU-1 (MER 7003) 12/03/14
C-1B CONTROLLER WIRING DETAIL – AHU-1 (MER 7003) 12/03/14
C-1C SEQUENCE OF OPERATIONS – AHU-1 (MER 7003) 12/03/14
C-2A AIR HANDLING UNIT CONTROL – AHU-2 (MER 7060A) 12/03/14
C-2B CONTROLLER WIRING DETAIL – AHU-2 (MER 7060A) 12/03/14
C-2C AIR HANDLING UNIT CONTROL – AHU-3 (MER 7074) 12/03/14
C-2D CONTROLLER WIRING DETAIL – AHU-3 (MER 7074) 12/03/14
C-2E SEQUENCE OF OPERATIONS – TYPICAL FOR AHU-2 & AHU-3 (MER 7060A & 7074) 12/03/14
C-3A AIR HANDLING UNIT CONTROL – A/C-1 (MER 8TH FLOOR WEST) 12/03/14
C-3B CONTROLLER WIRING DETAIL – A/C-1 (MER 8TH FLOOR WEST) 12/03/14
C-3C SEQUENCE OF OPERATIONS – AC-1 (MER 8TH FLOOR WEST) 12/03/14
C-4A AIR HANDLING UNIT CONTROLS – AHU-7 (MER 8TH FLOOR EAST) 12/03/14
C-4B CONTROLLER WIRING DETAIL – AHU-7 (MER 8TH FLOOR EAST) 12/03/14
C-4C VAV BOX CONTROLS FOR 7TH FLOOR EAST (SERVED BY AHU-7) 12/03/14
C-4D SEQUENCE OF OPERATIONS – AHU-7 (MER 8TH FLOOR EAST) 12/03/14
C-5A AIR HANDLING UNIT CONTROL – ELEVATOR AHU 9TH FLOOR 12/03/14
C-5B CONTROLLER WIRING DETAIL – ELEVATOR AHU 9TH FLOOR 12/03/14
C-6A TYPICAL HEAT EXCHANGER CONTROL – MAIN BUILDING 01/28/14
C-6B CONTROLLER WIRING DETAIL – TYPICAL HEAT EXCHANGER (MAIN BUILDING) 01/28/14
AS-BUILT REV. NEW DWG. TITLES/DATES2 12/03/13 BM
2 3
AS-BUILT REV. ADD ‘MASTER’ NOTE3 1/28/14 DB
NOTE(S): REFER TO ‘MASTER BUILDING NETWORK ARCHITECTURE DRAWING’
PROVIDED IN OUR ATC AS-BUILT / O&M MANUAL BINDER FOR ALL
SUPERVISORY CONTROLLER INFORMATION AND ASSOCIATED IP
ADDRESSES USED BY MODERN CONTROLS.
REFER TO ‘MASTER BUILDING VALVE SCHEDULE’ PROVIDED IN OUR
ATC AS-BUILT / O&M MANUAL BINDER FOR A COMPLETE LIST OF ALL
CONTROL VALVES PROVIDED FOR AIR HANDLING UNITS AND
ASSOCIATED VAV BOXES.
IW/BMIW/JAIW
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
BM 7/20/11
REFERENCE DRAWING
SUB. REVISION TAGS/NOTES1 12/12/11 VD
C-1A
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
AIR HANDLING UNIT CONTROL
– AHU-1 (MER 7003)
Project Title
AIR HANDLING UNIT CONTROL – AHU-1 (MER 7003)
OAH
OAT
GLOBAL OUTSIDE AIR
TEMPERATURE AND
HUMIDITY SIGNAL
110v (EXISTING)
*EXISTING EX. CP
7TH FLOOR MECH.
EQUIPMENT RM. -
(MER 7003)
SUPPLY
AIR
OUTDOOR
AIR
SF
RETURN
SMK
BO-1
R AO-8HOA
UI-3
S/S
CMD.
H L
SPS-1
UI-6
*SEE NOTES
DA
(D-1)
H
RA-H
UI-5
HUMID.
HIGH LIMIT
N.C.
HUMIDIFIER
H L
SPS-2
BI-8
UI-1
DA-T
VSMC
RH
C
STEAM
RE-HEAT
LPS
CO-5
*SEE NOTES
V-1
COND.
UI-2
MA-T
C
C
BI-7
DPS
LPS
HUMIDIFIER CONTROL
HUMID.
COND.
AO-9
V-4
BO-3
V-3
AS-BUILT REV. FINAL POINT TERM.2 12/3/13 BM
FEC-26
IOM-47
IOM-47 POINT IDENTIFICATION
POINT #
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
BI-7
BI-8
POINT NAME/DESCRIPTION
DISCHARGE AIR HUMIDITY (DA-H)
FINAL FILTER DIFFERENTIAL PRESSURE SWITCH (DP2)
PRE FILTER DIFFERENTIAL PRESSURE SWITCH (DP1)
DISCHARGE AIR DUCT HIGH STATIC (SPS-2)
FEC-26 POINT IDENTIFICATION
POINT #
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
BI-7
BI-8
AO-8
AO-9
BO-1
BO-2
BO-3
CO-4
CO-5
CO-6
CO-7
POINT NAME/DESCRIPTION
DISCHARGE AIR TEMPERATURE (DA-T)
MIXED AIR TEMPERATURE (MA-T)
SUPPLY FAN STATUS (DPS)
RETURN AIR HUMIDITY (RA-H)
SUPPLY AIR STATIC PRESSURE (SPS-1)
FREEZE STAT / SHUTDOWN (LL)
SUPPLY FAN VFD COMMAND
HUMIDIFIER CONTROL VALVE CMD. (V-4)
SUPPLY AIR SMOKE DETECTOR SHUTDOWN
RETURN AIR TEMPERATURE (RA-T)
SUPPLY FAN START / STOP
COOLING VALVE COMMAND (V-2)
RE-HEAT VALVE COMMAND (V-1)
*ECONOMIZER DAMPER COMMAND (D-1)
HUMIDIFIER ISOLATION VALVE (V-3)
AO-8
AO-9
BO-1
BO-2
BO-3
CO-4
CO-5
CO-6
CO-7
BILL OF MATERIALS
Designation Qty Part Number Description
DA 1 M9220-GGC-3 ACT.,PROP.,0-10V,179#IN,2-AUX.,W/ES
RA-T 1 TE-6315P-1 SENSOR,T-NI,0.1%,8FT AVG.,
LL 1 A70HA-1C STAT.,LOW LIMIT,20FT ELEM.,MAN. RESET
FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET
IOM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET
V-X SEE VALVE SCHEDULE FOR MORE INFORMATION
*CO-7
*SEE NOTES
UI-4
RA-T
BI-8
LL
*IOM *SEE DETAIL
& NOTES
UI-1
H
DA-H
*IOM
CWS
CWR
*SEE NOTES
CO-6
V-2
N.C.
PRE
FILTER
(EXISTING DP)
FINAL
FILTER
(EXISTING DP)
UI-6
DP1 DP2
BI-7
*IOM *IOM
NOTE(S): ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY
EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-
USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC
CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON
DDC CONTROLLERS AS INDICATED. *REFER TO C-1B FOR CONTROLLER WIRING DETAILS
AND DRAWING C-1C FOR ASSOCIATED SEQUENCE OF OPERATIONS.
NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND
INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE
‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING
M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR
ADDITIONAL INFORMATION.
THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING
DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS
WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL
PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS
HAVE BEEN APPROVED BY THE VA HOSPITAL.
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
BM 7/20/11
C-1B
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
CONTROLLER WIRING DETAIL
– AHU-1 (MER 7003)
Project Title
AS-BUILT REV. NEW DWG./POINT TERM.1 12/3/13 BM
CONTROLLER WIRING DETAIL – AHU-1 (MER 7003)
SEE AS-BUILT CONTROL DRAWINGS C-1A AND C-1C FOR
ASSOCIATED UNIT CONTROL DIAGRAM AND SEQUENCE OF
OPERATIONS.
NOTE(S):
124816326412
O N
Address:
S A
PW
R
C O
M
SA BUS
FC BUS
C O
M S
H
LD+1
5V
IN
IC
O M
IN
IC
O M
+1
5V
IN
IC
O M
IN
IC
O M
+1
5V
IN
IC
O M
IN
IC
O M
IN
IC
O M
IN
IC
O M
UNIVERSAL BINARY
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
H O
T
24V
C O
M
FEC2611
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
124816326412
O N
Address:
SA
FC
H O
T
24V
C O
M
IOM4711
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
S A
P W
R
C O
M
+ - C
O M
S H
LD
SA/FC BUS
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
UNIVERSAL BINARY
D
IS
C H
A R
G E
A
IR
T
EM
PE
R
A
TU
R E
(D A
-T
SU
PP
LY
F
A N
V
FD
C O
M M
A N
D
H U
M
ID
IF
IE
R C
O N
TR
O
L
VA
LV
E
C O
M M
A N
D (V
-4
SU
PP
LY
F
A N
S
TA
R T/
ST
O
P
C O
O
LI
N G
V A
LV
E
C O
M M
A N
D (V
-2
R E-
H
EA
T
VA
LV
E
C O
M M
A N
D (V
-1
*E C
O N
O M
IZ
ER
D A
M
PE
R C
O M
M A
N D
(D -1
H U
M
ID
IF
IE
R
IS
O
LA
TI
O
N V
A
VL
E (V
-3
M
IX
ED
A
IR
T
EM
PE
R A
TU
R
E (M
A -T
SU
PP
LY
A
IR
S
M O
K E
D
ET
EC
TO
R S
H U
TD
O
W N
R
ET
U R
N A
IR
T
EM
PE
R A
TU
R
E (R
A -T
R
ET
U R
N A
IR
H
U M
ID
IT
Y (R
A -H
SU
PP
LY
A
IR
S
TA
TI
C P
R
ES
SU
R
E (S
PS
-1
SU
PP
LY
F
A N
S
TA
TU
S
(D
PS
FR
EE
ZE
S
TA
T
/ S H
U
TD
O W
N (L
L)
D
IS
C H
A R
G E
A
IR
H U
M
ID
IT
Y
(D A
-H
PR
E-
FI
LT
ER
D
IF
FE
R
EN
TI
A
L
PR
ES
SU
R E
SW
IT
C H
(D P1
FI
N
A L
FI
LT
ER
D
IF
FE
R
EN
TI
A
L
PR
ES
SU
R E
SW
IT
C H
(D P2
D
IS
C H
A R
G E
A
IR
D U
C T
H
IG
H S
TA
TI
C (S
PS
-2
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
BM 7/20/11
SUB. REVISION ADD NOTE1 12/12/11 VD
C-1C
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS
UPGRADE - PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
SEQUENCE OF OPERATIONS -
AHU-1 (MER 7003)
Project Title
SEQUENCE OF OPERATIONS - AHU-1 (MER 7003)
AHU-1 (MER #7003)
1. GENERAL
UNIT IS NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. H-O-A SWITCH SHALL BE KEPT IN THE “AUTO” POSITION. “HAND”
AND “OFF” POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. WHEN THE UNIT IS “OFF” D-1 SHALL BE CLOSED. WHEN THE UNIT IS “ON” D-1 SHALL BE
FULLY OPENED.
2. TEMPERATURE CONTROL
SUPPLY AIR TEMPERATURE SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING V-1 AND V-2 IN SEQUENCE.
3. AIF FLOW CONTROL
THE SUPPLY AIRFLOW SHALL BE CONTROLLED BY THE DCP MODULATING THE SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER (VSMC) TO
MAINTAIN 1.5” OF DUCT STATIC PRESSURE (FIELD ADJUSTABLE) SENSED BY SPS-1.
THE DCP USING HIGH STATIC PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM
DEVELOPING OVER 3” OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT SPS-2 EXCEEDS 3” THE SUPPLY FAN SHALL STOP.
4. HUMIDITY CONTROL
WHEN THE DCP IS NOT CALLING FOR HUMIDIFICATION SENSED BY SPACE AIR HUMIDISTAT H-1, TWO-WAY “ON-OFF” CONTROL VALVE V-3 SHALL REMAIN
CLOSED. WHEN THE DCP IS CALLING FOR HUMIDIFICATION, V-3 SHALL OPEN.
RETURN AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT SENSED BY H-1 VIA DCP BY MODULATING CONTROL VALVE V-4 TO MAINTAIN THE DESIRED
HUMIDITY. THE DCP SHALL OVERRIDE THE CONTROL TO MAINTAIN HUMIDITY IN SUPPLY DUCT BELOW 80% AS SENSED BY H-2. DCP SHALL CLOSE
VALVE V-3 WHENEVER THE SUPPLY FAN IS OFF. VALVE V-4 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH; (FIELD VERIFY INTERLOCK) TO
KEEP THE HUMIDIFIER OFF UNTIL CONDENSATE TEMPERATURE APPROACHES STEAM TEMPERATURE.
5. FREEZE PROTECTION
IF THE AIR TEMPERATURE SENSED BY T-2 FALLS BELOW 45°F AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS
BELOW 40°F THE SUPPLY FAN SHALL SHUT DOWN, THE DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL INDICATE AT THE DCP AND BMS.
6. EMERGENCY SHUTDOWN/RESTART
WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY FAN STOPS AND THE ALARM SIGNAL IS TRANSMITTED TO THE
FIRE ALARM SYSTEM, DAMPERS D-1 AND D-2 SHALL CLOSE. SUPPLY AND RETURN FANS SHALL RESTART AND THE DAMPERS SHALL OPEN WHEN THE
FIRE ALARM CIRCUIT IS MANUALLY RESET.
1 2
AS-BUILT REV. NEW DRAWING2 12/3/13 BM
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
BM 7/20/11
SUB REVISION TAGS/NOTES1 12/12/11 VD
C-2A
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
AIR HANDLING UNIT CONTROL
– AHU-2 (MER 7060A)
Project Title
OAH
OAT
GLOBAL OUTSIDE AIR
TEMPERATURE AND
HUMIDITY SIGNAL
110v (EXISTING)
*EXISTING
7TH FLOOR MECH.
EQUIPMENT RM. -
(MER 7060A)
EX. CP
(AHU-2)
AS-BUILT REV. NEW DWG. / POINT TERM.2 12/3/13 BM
FEC-26
IOM-47
AIR HANDLING UNIT CONTROL – AHU-2 (MER 7060A)
(CONSTANT VOLUME UNIT)
SUPPLY
AIR
OUTDOOR
AIR
*SEE NOTES
DA
(D-1)
H
RA-H
UI-5
HUMID.
HIGH LIMIT
N.C.
HUMIDIFIER
UI-1
DA-TRH
C
STEAM
RE-HEAT
LPS
AO-9
*SEE NOTES
V-1
COND.
UI-2
MA-T
C
HUMIDIFIER CONTROL
HUMID.
COND.
AO-8
V-5
BO-3
V-4
IOM-47 POINT IDENTIFICATION
POINT #
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
BI-7
BI-8
POINT NAME/DESCRIPTION
DISCHARGE AIR HUMIDITY (DA-H)
PRE FILTER DIFFERENTIAL PRESSURE SWITCH (DP-1)
FINAL FILTER DIFFERENTIAL PRESSURE SWITCH (DP-2)
FEC-26 POINT IDENTIFICATION
POINT #
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
BI-7
BI-8
AO-8
AO-9
BO-1
BO-2
BO-3
CO-4
CO-5
CO-6
CO-7
POINT NAME/DESCRIPTION
DISCHARGE AIR TEMPERATURE (DA-T)
MIXED AIR TEMPERATURE (MA-T)
SUPPLY FAN STATUS (DPS)
RETURN AIR HUMIDITY (RA-H)
DISCHARGE AIR HUMIDITY (DA-H)
FREEZE STAT / SHUTDOWN (LL)
HUMIDIFIER CONTROL VALVE COMMAND (V-5)
RE-HEAT VALVE COMMAND (V-1)
PRE-HEAT DISCHARGE AIR TEMPERATURE (PH-T)
RETURN AIR TEMPERATURE (RA-T)
SUPPLY FAN START / STOP
COOLING VALVE COMMAND (V-2)
PRE-HEAT VALVE COMMAND (V-3)
*ECONOMIZER DAMPER COMMAND (D-1)
HUMIDIFIER ISOLATION VALVE (V-4)
AO-8
AO-9
BO-1
BO-2
BO-3
CO-4
CO-5
CO-6
CO-7
*CO-7
*SEE NOTES
UI-4
RA-T
BI-8
LL
*SEE DETAIL
& NOTES
UI-6
H
DA-H
CWS
CWR
*SEE NOTES
CO-6
V-2
N.C.
PRE
FILTER
(EXISTING DP)
FINAL
FILTER
(EXISTING DP)
PH
C
HWS
HWR
*SEE NOTES
CO-5
V-3
N.C.
STEAM
PRE-HEAT
UI-3
PH-T
R
BILL OF MATERIALS
Designation Qty Part Number Description
DA 1 M9220-GGC-3 ACT.,PROP.,0-10V,179#IN,2-AUX.,W/ES
XX-T 2 TE-6315P-1 SENSOR,T-NI,0.1%,8FT AVG.,
LL 1 A70HA-1C STAT.,LOW LIMIT,20FT ELEM.,MAN. RESET
FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET
IOM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET
V-X SEE VALVE SCHEDULE FOR MORE INFORMATION
NOTE(S): ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY
EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-
USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC
CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON
DDC CONTROLLERS AS INDICATED. *REFER TO C-2B FOR CONTROLLER WIRING DETAILS
AND DRAWING C-2E FOR ASSOCIATED SEQUENCE OF OPERATIONS.
NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND
INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE
‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING
M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR
ADDITIONAL INFORMATION.
THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING
DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS
WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL
PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS
HAVE BEEN APPROVED BY THE VA HOSPITAL.
DP-1
UI-5
*IOM
DP-2
UI-6
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
C-2B
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
CONTROLLER WIRING DETAIL;
AHU-2 (MER 7060A)
Project Title
AS-BUILT REV. NEW DWG./POINT TERM.1 12/3/13 DB
CONTROLLER WIRING DETAILS; AHU-2 (MER 7060A)
SEE AS-BUILT CONTROL DRAWINGS C-2A AND C-2E FOR
ASSOCIATED UNIT CONTROL DIAGRAM AND SEQUENCE OF
OPERATIONS.
NOTE(S):
124816326412
O N
Address:
S A
PW
R
C O
M
SA BUS
FC BUS
C O
M S
H
LD+1
5V
IN
IC
O M
IN
IC
O M
+1
5V
IN
IC
O M
IN
IC
O M
+1
5V
IN
IC
O M
IN
IC
O M
IN
IC
O M
IN
IC
O M
UNIVERSAL BINARY
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
H O
T
24V
C O
M
FEC2611
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
124816326412
O N
Address:
SA
FC
H O
T
24V
C O
M
IOM4711
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
S A
P W
R
C O
M
+ - C
O M
S H
LD
SA/FC BUS
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
UNIVERSAL BINARY
D
IS
C H
A R
G E
A
IR
T
EM
PE
R
A
TU
R E
(D A
-T
H U
M
ID
IF
IE
R C
O N
TR
O
L
VA
LV
E
C O
M M
A N
D (V
-5
R E-
H
EA
T
VA
LV
E
C O
M M
A N
D (V
-1
SU
PP
LY
F
A N
S
TA
R T/
ST
O
P
C O
O
LI
N G
V A
LV
E
C O
M M
A N
D (V
-2
PR
E-
H
EA
T
VA
LV
E
C O
M M
A N
D (V
-3
*E C
O N
O M
IZ
ER
D A
M
PE
R C
O M
M A
N D
(D -1
H U
M
ID
IF
IE
R
IS
O
LA
TI
O
N V
A
LV
E (V
-4
M
IX
ED
A
IR
T
EM
PE
R A
TU
R
E (M
A -T
PR
E-
H
EA
T D
IS
C
H A
R G
E A
IR
T
EM
PE
R A
TU
R
E (P
H -T
R
ET
U R
N A
IR
T
EM
PE
R A
TU
R
E (R
A -T
R
ET
U R
N H
U M
ID
IT
Y (R
A -H
D
IS
C H
A R
G E
A
IR
H U
M
ID
IT
Y
(D A
-H
SU
PP
LY
F
A N
S
TA
TU
S
(D
PS
FR
EE
ZE
S
TA
T
/ S H
U
TD
O W
N (L
L)
D
IS
C H
A R
G E
A
IR
H U
M
ID
IT
Y
(D A
-H
PR
E-
FI
LT
ER
D
IF
FE
R
EN
TI
A
L
PR
ES
SU
R E
SW
IT
C H
(D P-
1)
FI
N
A L
FI
LT
ER
D
IF
FE
R
EN
TI
A
L
PR
ES
SU
R E
SW
IT
C H
(D P-
2)
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
BM 7/20/11
SUB REVISION TAGS/NOTES1 12/12/11 VD
C-2C
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
AIR HANDLING UNIT CONTROL;
AHU-3 (MER 7074)
Project Title
OAH
OAT
GLOBAL OUTSIDE AIR
TEMPERATURE AND
HUMIDITY SIGNAL
110v (EXISTING)
*EXISTING
7TH FLOOR MECH.
EQUIPMENT RM. -
(MER 7074)
EX. CP
(AHU-3)
AS-BUILT REV. NEW DWG. / POINT TERM.2 12/3/13 BM
FEC-26
IOM-47
BI-7
*SEE NOTES
CO-7
GENERAL EXHAUST FAN CONTROL
SUPPLY
AIROUTDOOR
AIR
*SEE NOTES
DA
(D-1)
H
RA-H
UI-5
HUMID.
HIGH LIMIT
N.C.
HUMIDIFIER
UI-1
DA-TRH
C
STEAM
RE-HEAT
LPS
AO-9
*SEE NOTES
V-1
COND.
UI-2
MA-T
C
HUMIDIFIER CONTROL
HUMID.
COND.
AO-8
V-5
BO-3
V-4
IOM-47 POINT IDENTIFICATION
POINT #
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
BI-7
BI-8
POINT NAME/DESCRIPTION
EXISTING EXHAUST FAN STATUS (CT)
PRE FILTER DIFFERENTIAL PRESSURE SWITCH (DP)
FINAL FILTER DIFFERENTIAL PRESSURE SWITCH (DP)
FEC-26 POINT IDENTIFICATION
POINT #
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
BI-7
BI-8
AO-8
AO-9
BO-1
BO-2
BO-3
CO-4
CO-5
CO-6
CO-7
POINT NAME/DESCRIPTION
DISCHARGE AIR TEMPERATURE (DA-T)
MIXED AIR TEMPERATURE (MA-T)
SUPPLY FAN STATUS (DPS)
RETURN AIR HUMIDITY (RA-H)
DISCHARGE AIR HUMIDITY (DA-H)
FREEZE STAT / SHUTDOWN (LL)
HUMIDIFIER CONTROL VALVE COMMAND (V-5)
RE-HEAT VALVE COMMAND (V-1)
PRE-HEAT DISCHARGE AIR TEMP. (PH-T)
RETURN AIR TEMPERATURE (RA-T)
SUPPLY FAN START / STOP
COOLING VALVE COMMAND (V-2)
PRE-HEAT VALVE COMMAND (V-3)
*ECONOMIZER DAMPER COMMAND (D-1)
HUMIDIFIER ISOLATION VALVE (V-4)
AO-8
AO-9
BO-1
BO-2
BO-3
CO-4
CO-5
CO-6
CO-7 EXISTING EXHAUST FAN & DAMPER COMMAND (D-1/R)
*CO-7
*SEE NOTES
UI-4
RA-T
BI-8
LL
*SEE DETAIL
& NOTES
UI-6
H
DA-H
CWS
CWR
*SEE NOTES
CO-6
V-2
N.C.
PRE
FILTER
(EXISTING DP)
FINAL
FILTER
(EXISTING DP)
PH
C
HWS
HWR
*SEE NOTES
CO-5
V-3
N.C.
STEAM
PRE-HEAT
UI-3
PH-T
AIR HANDLING UNIT CONTROL – AHU-3 (MER 7070)
(CONSTANT VOLUME UNIT)
DA
(D-1)
*EXISTING DAMPER
CT
L
*IOM
BILL OF MATERIALS
Designation Qty Part Number Description
DA 1 M9220-GGC-3 ACT.,PROP.,0-10V,179#IN,2-AUX.,W/ES
XX-T 2 TE-6315P-1 SENSOR,T-NI,0.1%,8FT AVG.,
LL 1 A70HA-1C STAT.,LOW LIMIT,20FT ELEM.,MAN. RESET
FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET
IOM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET
V-X SEE VALVE SCHEDULE FOR MORE INFORMATION
NOTE(S):
ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY
EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-
USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC
CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON
DDC CONTROLLERS AS INDICATED. *REFER TO C-2D FOR CONTROLLER WIRING DETAILS
AND DRAWING C-2E FOR ASSOCIATED SEQUENCE OF OPERATIONS.
NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND
INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE
‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING
M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR
ADDITIONAL INFORMATION.
THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING
DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS
WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL
PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
C-2D
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
CONTROLLER WIRING DETAIL;
AHU-3 (MER 7070)
Project Title
AS-BUILT REV. NEW DWG./POINT TERM.1 12/3/13 DB
CONTROLLER WIRING DETAILS; AHU-3 (MER 7070)
SEE AS-BUILT CONTROL DRAWINGS C-2C AND C-2E FOR
ASSOCIATED UNIT CONTROL DIAGRAM AND SEQUENCE OF
OPERATIONS.
NOTE(S):
124816326412
O N
Address:
S A
PW
R
C O
M
SA BUS
FC BUS
C O
M S
H
LD+1
5V
IN
IC
O M
IN
IC
O M
+1
5V
IN
IC
O M
IN
IC
O M
+1
5V
IN
IC
O M
IN
IC
O M
IN
IC
O M
IN
IC
O M
UNIVERSAL BINARY
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
H O
T
24V
C O
M
FEC2611
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
124816326412
O N
Address:
SA
FC
H O
T
24V
C O
M
IOM4711
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
S A
P W
R
C O
M
+ - C
O M
S H
LD
SA/FC BUS
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
UNIVERSAL BINARY
D
IS
C H
A R
G E
A
IR
T
EM
PE
R
A
TU
R E
(D A
-T
H U
M
ID
IF
IE
R C
O N
TR
O
L
VA
LV
E
C O
M M
A N
D (V
-5
R E-
H
EA
T
VA
LV
E
C O
M M
A N
D (V
-1
SU
PP
LY
F
A N
S
TA
R T/
ST
O
P
C O
O
LI
N G
V A
LV
E
C O
M M
A N
D (V
-2
PR
E-
H
EA
T
VA
LV
E
C O
M M
A N
D (V
-3
*E C
O N
O M
IZ
ER
D A
M
PE
R C
O M
M A
N D
(D -1
H U
M
ID
IF
IE
R
IS
O
LA
TI
O
N V
A
LV
E (V
-4
M
IX
ED
A
IR
T
EM
PE
R A
TU
R
E (M
A -T
PR
E-
H
EA
T D
IS
C
H A
R G
E A
IR
T
EM
PE
R A
TU
R
E (P
H -T
R
ET
U R
N A
IR
T
EM
PE
R A
TU
R
E (R
A -T
R
ET
U R
N H
U M
ID
IT
Y (R
A -H
D
IS
C H
A R
G E
A
IR
H U
M
ID
IT
Y
(D A
-H
SU
PP
LY
F
A N
S
TA
TU
S
(D
PS
FR
EE
ZE
S
TA
T
/ S H
U
TD
O W
N (L
L)
PR
E-
FI
LT
ER
D
IF
FE
R
EN
TI
A
L
PR
ES
SU
R E
SW
IT
C H
(D P-
1)
FI
N
A L
FI
LT
ER
D
IF
FE
R
EN
TI
A
L
PR
ES
SU
R E
SW
IT
C H
(D P-
2)
EX
IS
TI
N
G E
XH
A
U
ST
F A
N S
TA
TU
S (C
T)
EX
IS
TI
N
G E
XH
A
U
ST
F A
N
D A
M
PE
R C
O M
M A
N D
(D -1
/R
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
BM 7/20/11
SUB. REVISION EDIT SEQUENCE1 12/12/11 VD
C-2E
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
SEQUENCE OF OPERATIONS -
AHU-2 & AHU-3 (MER 7060A &
7074)
Project Title
SEQUENCE OF OPERATIONS – TYPICAL FOR AHU-2 & AHU-3 (MER 7060A & 7074)
AHU-2 (MER #7060A), AHU-3 (MER #7074)
1. GENERAL
UNIT IS NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. H-O-A SWITCH SHALL BE KEPT IN THE “AUTO” POSITION. “HAND”
AND “OFF” POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. WHEN THE UNIT IS “OFF” D-1 SHALL BE CLOSED. WHEN THE UNIT IS “ON” D-1 SHALL BE
FULLY OPENED.
2. TEMPERATURE CONTROL
SPACE AIR TEMPERATURE SENSED BY THE ROOM TEMPERATURE SENSOR T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING V-1 AND
V-2 IN SEQUENCE.
3. AIR FLOW CONTROL
THE SUPPLY FAN SHALL RUN AT CONSTANT SPEED PROVIDING CONSTANT AIR FLOW.
4. HUMIDITY CONTROL
WHEN THE DCP IS NOT CALLING FOR HUMIDIFICATION SENSED BY HUMIDISTAT H-1, TWO-WAY “ON-OFF” CONTROL VALVE V-3 SHALL REMAIN CLOSED.
WHEN THE DCP IS CALLING FOR HUMIDIFICATION, V-3 SHALL OPEN.
RETURN AIR HUMIDITIY SHALL BE MAINTAINED AT SETPOINT SENSED BY H-1 VIA DCP BY MODULATING CONTROL VALVE V-4 TO MAINTAIN THE DESIRED
HUMIDITY. THE DCP SHALL OVERRIDE THE CONTROL TO MAINTAIN HUMIDITY IN SUPPLY DUCT BELOW 80% AS SENSED BY H-2. DCP SHALL CLOSE
VALVE V-3 WHENEVER THE SUPPLY FAN IS OFF. VALVE V-4 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH; (FIELD VERIFY INTERLOCK) TO
KEEP THE HUMIDIFIER OFF UNTIL CONDENSATE TEMPERATURE APPROACHES STEAM TEMPERATURE.
5. FREEZE PROTECTION
IF THE AIR TEMPERATURE SENSED BY T-2 FALLS BELOW 45°F AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS
BELOW 40°F THE SUPPLY FAN SHALL SHUT DOWN, THE DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL INDICATE AT THE DCP AND BMS.
6. EMERGENCY SHUTDOWN/RESTART
WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY FAN STOPS AND THE ALARM SIGNAL IS TRANSMITTED TO THE
FIRE ALARM SYSTEM, DAMPERS D-1 AND D-2 SHALL CLOSE. SUPPLY AND RETURN FANS SHALL RESTART AND THE DAMPERS OPEN WHEN THE FIRE
ALARM CIRCUIT IS MANUALLY RESET.
AS-BUILT REV. NEW DRAWING / TYPICAL2 12/3/13 BM
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
BM 7/19/11
SUB. REVISION TAGS/NOTES1 12/13/11 VD
C-3A
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS
UPGRADE - PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
AIR HANDLING UNIT CONTROL-
A/C-1 (MER 8TH FLOOR WEST)
Project Title
AIR HANDLING UNIT CONTROL - A/C-1 (MER 8TH FLOOR WEST)
OAH
OAT
LOCAL OUTSIDE AIR
TEMPERATURE AND
HUMIDITY SENSOR
MOUNTED OUTSIDE OF
MER 8TH WEST
110v (EXISTING)
*EXISTING EX. CP
(A/C-1)
8TH FLOOR MECH.
EQUIPMENT RM. -
(MER 8TH FLOOR WEST)
SUPPLY
AIROUTDOOR
UI-1
DA-TPH
C
LPS
RH
C
AO-9
C
C
CWS
CWR
*SEE NOTES
CO-6
V-3
N.C.
*SEE NOTES
STEAM
PRE-HEAT
STEAM
RE-HEAT
V-1
COND.
LPS
CO-5
*SEE NOTES
V-2B
CO-4
V-2A
COND.
N.O. NOTE(S):
BILL OF MATERIALS
Designation Qty Part Number Description
OAT 1 TE-6313P-1 SENSOR,T-NI,0.1%,OUTSIDE,TEMP.
OAH 1 HO20K SENSOR,%RH,OUTSIDE HUMID.,KELE
DCP 1 DCP-1.5-W 1.5AMP POWER SUPPLY
DA 1 M9220-BGC-3 ACT.,24VAC,SPR.RTN.,189#IN,2-AUX.,W/E.S.
X-TH 3 HE-67N3-0N00P DUCT COMBO SENSOR,T-NI & %RH
DA-H 3 TE-6316P-1 SENSOR,T-NI,0.1%,16FT AVG.,
LL 1 A70GA-1C LOW LIMIT,AUTO RESET,20FT ELEM.
SPS 1 PXPXX02S DUCT STATIC PRESS.,0-10”W.C.,ADJ.,0-10V,SETRA
FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET
IOM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET
V-X SEE VALVE SCHEDULE FOR MORE INFORMATION
*BO-1
S/S
N.O.
N.O.
UI-4
CC-T
IOM-47 (EXP. ADD.#4)
IOM-47 POINT IDENTIFICATION
POINT #
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
BI-7
BI-8
POINT NAME/DESCRIPTION
SUPPLY HUMIDITIY HIGH LIMIT (DA-HL)
PRE FILTER STATUS (DP-1)
SUPPLY AIR DUCT STATIC PRESSURE (SPS)
FINAL FILTER STATUS (DP-2)
OUTSIDE AIR TEMPERATURE (OA-T)
OUTSIDE AIR HUMIDITY (OA-H)
FEC-26 POINT IDENTIFICATION
POINT #
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
BI-7
BI-8
AO-8
AO-9
BO-1
BO-2
BO-3
CO-4
CO-5
CO-6
CO-7
POINT NAME/DESCRIPTION
DISCHARGE AIR TEMPERATURE (DA-T)
REHEAT COIL LEAVING AIR TEMP. (RH-T)
SUPPLY FAN STATUS (DPS)
ZONE HUMIDITY SENSOR (SHT)
*DISCHARGE AIR HUMIDITY (DA-H)
FREEZE STAT / SHUTDOWN (LL)
HUMIDIFIER VALVE COMMAND (EV-5)
RE-HEAT VALVE COMMAND (V-1)
PRE-HEAT COIL LEAVING AIR TEMP. (PH-T)
COOLING COIL LEAVING AIR TEMP. (CC-T)
SUPPLY FAN S/S (SIGNAL THRU. ‘D-1’ END SWITCH)
COOLING VALVE COMMAND (V-3)
LOWER PRE-HEAT VALVE COMMAND (V-2B)
UPPER PRE-HEAT VALVE COMMAND (V-2A)
*SUPPLY FAN VFD COMMAND
HUMIDIFIER ISOLATION VALVE (EV-4)
H L
SPS-1
UI-6
DA-HL
*SEE NOTES
HUMIDIFIER
LPS
HUMIDIFIER CONTROL
HUMID.
*SEE NOTES
COND.
AO-8
EV-4
BO-3
EV-3
UI-3
PH-T
BI-8
LL
UI-2
RH-T
PRE
FILTER
(EXISTING DP)
FINAL
FILTER
(EXISTING DP)
SHT
SPACE
HUMIDITY
SENSOR
VFD
AO-8
AO-9
BO-1
BO-2
BO-3
CO-4
CO-5
CO-6
CO-7
CO-7 CMD.
*UI-6
EXISTING SPACE HUMIDITY CONTROL
(LOCATED IN 7TH FLOOR CORRIDOR)
BI-7
*IOM *IOM
H
DA-H
UI-4
*IOM
UI-3
*IOM
AS-BUILT REV. FINAL REVISIONS2 12/3/13 BM
FEC-26 (ADD.#33)
*SF S/S SIGNAL (BO-1) IS
HARD-WIRED THROUGH
DA ‘D-1’ END SWITCH
DA
(D-1)*BO-1
*SF S/S SIGNAL (BO-1) IS
HARD-WIRED THROUGH
DA ‘D-1’ END SWITCH
DP-2
BI-8
H
SMR
*HARD WIRED
ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY
EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-
USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC
CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON
DDC CONTROLLERS AS INDICATED. *REFER TO C-3B FOR CONTROLLER WIRING DETAILS
AND DRAWING C-3C FOR ASSOCIATED SEQUENCE OF OPERATIONS.
NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND
INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE
‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING
M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR
ADDITIONAL INFORMATION.
THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING
DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS
WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL
PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
BM 7/19/11
AS-BUILT REV. TAGS/NOTES1 12/3/13 BM
C-3B
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS
UPGRADE - PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
CONTROLLER WIRING
DETAILS - A/C-1
(MER 8TH FLOOR WEST)
Project Title
CONTROLLER WIRING DETAILS - A/C-1 (MER 8TH FLOOR WEST)
SEE AS-BUILT CONTROL DRAWINGS C-3A AND C-3C FOR
ASSOCIATED UNIT CONTROL DIAGRAM AND SEQUENCE OF
OPERATIONS.
NOTE(S):
124816326412
O N
Address:
S A
PW
R
C O
M
SA BUS
FC BUS
C O
M S
H
LD+1
5V
IN
IC
O M
IN
IC
O M
+1
5V
IN
IC
O M
IN
IC
O M
+1
5V
IN
IC
O M
IN
IC
O M
IN
IC
O M
IN
IC
O M
UNIVERSAL BINARY
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
H O
T
24V
C O
M
FEC2611
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
124816326412
O N
Address:
SA
FC
H O
T
24V
C O
M
IOM4711
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
S A
P W
R
C O
M
+ - C
O M
S H
LD
SA/FC BUS
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
UNIVERSAL BINARY
D
IS
C H
A R
G E
A
IR
T
EM
PE
R
A
TU
R E
(D A
-T
H U
M
ID
IF
IE
R V
A
LV
E C
O M
M A
N D
(E V-
5)
R
EH
EA
T
VA
LV
E C
O M
M A
N D
(V -1
SU
PP
LY
F
A N
S /S
(S
IN
G A
L
TH
R U
D
-1 ’ E
N D
S W
IT
C
H
C O
O
LI
N G
V A
LV
E
C O
M M
A N
D (V
-3
LO
W
ER
P
R
EH
EA
T
VA
LV
E C
O M
M A
N D
(V -2
B
U
PP
ER
P
R
EH
EA
T
VA
LV
E C
O M
M A
N D
(V -2
A
SU
PP
LY
F
A N
V
FD
C O
M M
A N
D
H U
M
ID
IF
IE
R
IS
O
LA
TI
O
N V
A
LV
E (E
V- 4)
R
EH
EA
T
C O
IL
L
EA
VI
N G
A
IR
T
EM
PE
R
A
TU
R E
(R H
-T
PR
EH
EA
T
C O
IL
L
EA
VI
N G
A
IR
T
EM
PE
R
A
TU
R E
(P H
-T
C O
O
LI
N G
C O
IL
L
EA
VI
N G
A
IR
T
EM
PE
R
A
TU
R E
(C C
-T
ZO
N
E H
U M
ID
IT
Y
SE
N
SO
R (S
H T)
D
IS
C H
A R
G E
A
IR
H U
M
ID
IT
Y
(D A
-H
SU
PP
LY
F
A N
S
TA
TU
S
(D
PS
FR
EE
ZE
S
TA
T
/ S H
U
TD
O W
N (L
L)
O U
TS
ID
E A
IR
T
EM
PE
R A
TU
R
E (O
A -T
O U
TS
ID
E A
IR
H
U M
ID
IT
Y (O
A -H
PR
E
FI
LT
ER
S
TA
TU
S (D
P- 1)
SU
PP
LY
D
U C
T
ST
A
TI
C P
R
ES
SU
R
E (S
PS
SU
PP
LY
H
U M
ID
IT
Y H
IG
H
L
IM
IT
(D
A -H
L)
FI
N
A L
FI
LT
ER
S
TA
TU
S (D
P- 2)
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
BM 7/19/11
C-3C
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
SEQUENCE OF OPERATIONS -
A/C-1 (MER 8TH FLOOR WEST)
Project Title
A/C-1 (MER 8TH FLOOR WEST)
1. GENERAL
UNIT IS NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. H-O-A SWITCH SHALL BE KEPT IN THE “AUTO” POSITION. “HAND” AND “OFF” POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. WHEN THE UNIT IS “OFF” D-1 SHALL BE CLOSED. WHEN THE UNIT IS “ON” D-1 SHALL BE
FULLY OPENED.
2. TEMPERATURE CONTROL
HEATING MODE:
TEMPERATURE SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING V-4 AND V-5 IN SEQUENCE. V-1, V-2, V-3 AND V-4 SHALL
BE CLOSED.
COOLING MODE:
TEMPERATURE SENSED BY T-2 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING V-3. TEMPERATURE SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING V-1 AND V-2 IN SEQUENCE. V-4 AND V-5 SHALL BE CLOSED.
3. AIR FLOW CONTROL
THE SUPPLY FAN SHALL RUN AT CONSTANT SPEED PROVIDING CONSTANT AIR FLOW.
4. FREEZE PROTECTION
IF THE AIR TEMPERATURE SENSED BY T-2 FALLS BELOW 45°F AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS BELOW 40°F THE SUPPLY FAN SHALL SHUT DOWN, THE DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL INDICATE AT THE DCP AND BMS.
5. EMERGENCY SHUTDOWN/RESTART
WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY FAN SHALL STOP, DAMPER D-1 SHALL CLOSE AND AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM. THE SUPPLY FAN SHALL RESTART AND THE DAMPER SHALL OPEN WHEN THE FIRE
ALARM CIRCUIT IS MANUALLY RESET.
SEQUENCE OF OPERATIONS - A/C-1 (MER 8TH FLOOR WEST)
AS-BUILT REV. REVISE SEQ.1 BM12/3/13
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
BM 7/19/11
SUB. REVISION TAGS/NOTES 1 12/13/11 VD
C-4A
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
AIR HANDLING UNIT CONTROL
– AHU-7 (MER 8TH FLOOR EAST)
Project Title
AIR HANDLING UNIT CONTROL – AHU-7 (MER 8TH FLOOR EAST)
OAH
OAT
GLOBAL OUTSIDE AIR
TEMPERATURE AND
HUMIDITY SIGNAL
H L
SPS-1
UI-6
SAFM
*SEE DETAIL
& NOTES
HUMIDIFIER
UI-1UI-1
DA-T
110v (EXISTING)
*EXISTING EX. CP
8TH FLOOR MECH.
EQUIPMENT RM. -
(MER 8TH FLOOR EAST)
CT
BI-7
EXHAUST FAN CONTROL; EF-21
*SEE NOTES BO-1
AS-BUILT REV. DWG. REVS / POINT TERM.2 12/3/13 BM
FEC-26
IOM-47-1,2 (TYP. OF 2)
IOM-47-2 POINT IDENTIFICATION
POINT #
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
BI-7
BI-8
POINT NAME/DESCRIPTION
DISCHARGE AIR FLOW STATION MONITOR (SAFM)
RETURN AIR FLOW STATION MONITOR (RAFM)
RETURN AIR FAN STATUS (DPS)
PRE FILTER DIFFERENTIAL PRESSURE (DP)
PRE HEAT COIL PUMP STATUS (CT)
FEC-26 POINT IDENTIFICATION
POINT #
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
BI-7
BI-8
AO-8
AO-9
BO-1
BO-2
BO-3
CO-4
CO-5
CO-6
CO-7
POINT NAME/DESCRIPTION
DISCHARGE AIR TEMPERATURE (DA-T)
MIXED AIR TEMPERATURE (MA-T)
SUPPLY FAN STATUS (DPS)
RETURN AIR HUMIDITY (RA-H)
DISCHARGE AIR DUCT STATIC PRESSURE (SPS)
LOW LIMIT SHUTDOWN (LL)
SUPPLY FAN VFD COMMAND
RETURN FAN VFD COMMAND
PRE HEAT COIL DISCHARGE TEMPERATURE (PH-T)
RETURN AIR TEMPERATURE (RA-T)
SUPPLY FAN VFD START/STOP
CHILLED WATER VALVE COMMAND (V-1)
PRE HEAT COIL PUMP START/STOP
PRE HEAT COIL VALVE COMMAND (V-2)
ECONOMIZER DAMPER COMMAND (D1~D3)
RETURN FAN VFD START/STOP
HUMIDIFIER ISOLATION VALVE (V-3)
AO-8
AO-9
BO-1
BO-2
BO-3
CO-4
CO-5
CO-6
CO-7
HUMIDIFIER CONTROL VALVE COMMAND
IOM-47-1 POINT IDENTIFICATION
POINT #
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
BI-7
BI-8
POINT NAME/DESCRIPTION
SUPPLY AIR DUCT HIGH PRESSURE (SP-HL)
SUPPLY FAN VFD ALARM
EXHAUST FAN EF-21 STATUS (CT)
DISCHARGE AIR HUMIDITY SENSOR (DA-H)
DISCHARGE AIR SMOKE DETECTOR
RETURN AIR SMOKE DETECTOR (SMK)
RETURN FAN VFD ALARM
EXHAUST FAN EF-21 SPACE TEMPERATURE (ST)
AO-8
AO-9
BO-1
BO-2
BO-3
CO-4
CO-5
CO-6
CO-7
EXHAUST FAN EF-21 START/STOP (R)
SUPPLY AIR
TO VAV’SOUTDOOR
UI-5BI-7
HUMIDIFIER CONTROL
RF
BO-2
RAO-9
VSMC
AIR
UI-4
RA-T
H
RA-H
UI-5
RAFM
UI-2
LPS
HUMID.
*SEE NOTES
COND.
AO-8BO-3
V-4V-3
LL
BI-8
H
DA-H
*IOM-47-2
L
H
SP-HL
HI-LIMIT
UI-1
*IOM-47-1
UI-3
*IOM-47-1
*IOM-47-2
RELIEF
D-3
D-1
D-2
DP
N.C.
N.O.CO-7
CO-7
UI-6
*IOM-47-2
RAO-8
VSMC
UI-2
*IOM-47-1
*CO-7
MA-T
UI-2
HWS
HWR
*SEE NOTES
H
C
C
C
CWS
CWR
V-2 V-1
CO-4
UI-3
PH-T
CO-6CO-5
*IOM-47-2
*IOM-47-1
*IOM-47-1*IOM-47-1
*IOM-47-1
HUMID.
HIGH LIMIT
BILL OF MATERIALS
Designation Qty Part Number Description
RA-T,MA-T 2 TE-6315P-1 SENSOR,T-NI,0.1%,8FT AVG.,
LL 1 A70HA-1C STAT.,LOW LIMIT,20FT ELEM.,MAN. RESET
FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET
IOM-1 2 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET
V-X SEE VALVE SCHEDULE FOR MORE INFORMATION
*IOM-47-1
*IOM-47-1
*IOM-47-1
NOTE(S): ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY
EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-
USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC
CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON
DDC CONTROLLERS AS INDICATED. *REFER TO C-4B FOR CONTROLLER WIRING DETAILS,
C-4C FOR ASSOCIATED VAV BOXES AND DRAWING C-4D FOR ASSOCIATED SEQUENCE OF
OPERATIONS.
NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND
INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE
‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING
M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR
ADDITIONAL INFORMATION.
THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING
DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS
WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL
PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS
HAVE BEEN APPROVED BY THE VA HOSPITAL.
*SEE NOTES (TYP.)
ST
SPACE
TEMPERATURE
SENSOR
(EXISTING)
UI-4
*IOM-47-1
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
C-4B
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
Project Title
CONTROLLER WIRING DETAIL
– AHU-7
(MER 8TH FLOOR EAST)
CONTROLLER WIRING DETAIL – AHU-7 (MER 8TH FLOOR EAST)
SEE AS-BUILT CONTROL DRAWINGS C-4A, C-4C AND C-4D FOR
ASSOCIATED UNIT CONTROL DIAGRAM, VAV DIAGRAM AND
SEQUENCE OF OPERATIONS.
NOTE(S):
124816326412
O N
Address:
S A
PW
R
C O
M
SA BUS
FC BUS
C O
M S
H
LD+1
5V
IN
IC
O M
IN
IC
O M
+1
5V
IN
IC
O M
IN
IC
O M
+1
5V
IN
IC
O M
IN
IC
O M
IN
IC
O M
IN
IC
O M
UNIVERSAL BINARY
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
H O
T
24V
C O
M
FEC2611
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
124816326412
O N
Address:
SA
FC
H O
T
24V
C O
M
IOM4711-2
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
S A
P W
R
C O
M
+ - C
O M
S H
LD
SA/FC BUS
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
UNIVERSAL BINARY
D
IS
C H
A R
G E
A
IR
T
EM
PE
R
A
TU
R E
(D A
-T
SU
PP
LY
F
A N
V
FD
C O
M M
A N
D
R
ET
U R
N F
A N
V
FD
C O
M M
A N
D
SU
PP
LY
F
A N
V
FD
S
TA
R T/
ST
O
P
C H
IL
LL
ED
W
A
TE
R C
O
IL
V A
LV
E
C M
D
V- 1)
PR
E
H
EA
T C
O
IL
P U
M P
ST
A
R T/
ST
O
P
PR
E
H
EA
T C
O
IL
V A
LV
E
C M
D
V- 2)
EC
O
N O
M
IZ
ER
D
A M
PE
R
C O
M M
A N
D (D
1~ D
3)
R
ET
U R
N F
A N
V
FD
S
TA
R T/
ST
O
P
H U
M
ID
IF
IE
R
IS
O
LA
TI
O
N V
A
LV
E C
M D
V-
3)
H U
M
ID
IF
IE
R C
O N
TR
O
L
VA
LV
E
C M
D
V- 4)
M
IX
ED
A
IR
T
EM
PE
R A
TU
R
E (M
A -T
PR
E
H
EA
T C
O
IL
D
IS
C H
A R
G E
TE
M
P.
(P
H -T
R
ET
U R
N A
IR
T
EM
PE
R A
TU
R
E (R
A -T
R
ET
U R
N A
IR
H
U M
ID
IT
Y (R
A -H
D
IS
C H
A R
G E
A
IR
D U
C T
ST
A
TI
C
P R
ES
SU
R E
(S
PS
SU
PP
LY
F
A N
S
TA
TU
S
(D
PS
LO
W
L
IM
IT
S
H U
TD
O
W N
(L L)
SU
PP
LY
A
IR
F
LO
W
S
TA
TI
O
N M
O N
IT
O
R (S
A
FM
R
ET
U R
N A
IR
F
LO
W
S
TA
TI
O
N M
O N
IT
O
R (R
A
FM
R
ET
U R
N A
IR
F
A N
S
TA
TU
S
(D
PS
PR
E
FI
LT
ER
D
IF
F.
P R
ES
SU
R E
(D P)
PR
E
H
EA
T C
O
IL
P U
M P
ST
A
TU
S
(C T)
AS-BUILT REV. TAGS/NOTES & POINT TERM.1 12/3/13 BM
124816326412
O N
Address:
SA
FC
H O
T
24V
C O
M
IOM4711-1
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
S A
P W
R
C O
M
+ - C
O M
S H
LD
SA/FC BUS
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
UNIVERSAL BINARY
EX
H
A U
ST
F
A N
E F-
S
TA
R
T/
ST
O P
(R
SU
PP
LY
A
IR
D
U C
T H
IG
H
P R
ES
SU
R E
(S P-
H L)
SU
PP
Y
FA
N V
FD
A
LA
M
ET
U R
N F
A N
V
FD
A
LA
R M
EX
H
A U
ST
F
A N
E F-
S
PA
C
E
TE
M
PE
R A
TU
R
E (S
T)
D
IS
C H
A R
G E
A
IR
H U
M
ID
IT
Y
SE
N
SO
R
(D A
-H
D
IS
C H
A R
A G
E A
IR
S
M O
K E
D
ET
EC
TO
R
EX
H
A U
ST
F
A N
E F-
S
TA
TU
S (C
T)
R
ET
U R
N A
IR
S
M O
K E
D
ET
EC
TO
R (S
M K
VMA-16
(SEE NOTES)
MOUNT DIRECTLY TO
DAMPER ACTUATOR SHAFT
WITH THE DAMPER IN THE
"OPEN" POSITION.
CONNECT TO VAV BOX
VELOCITY PROBES
24V FROM NEW XFMR(S) MOUNTED IN
THE AHU-7 CONTROL PANEL
*EXISTING
TRANSFORMER
211-1009
IW/BMIW/JAIW
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
C-4C
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
VAV BOX CONTROLS FOR 7TH
FLOOR EAST; SERVED BY AHU-7
(TYP. OF 36)
Project Title
VAV BOX CONTROL FOR 7TH FLOOR EAST - SERVED BY AHU-7
(TYP. OF 36)
BILL OF MATERIALS
Designation Qty Part Number Description Field Devices:
STT-1 36 NS-BTP7002-0 SENSOR,TEMP.,W/C,NETWORK,WALL MNT.
TE-1 36 TE-6311M-1 SENSOR,TEMP.8IN,DUCT MNT.,
VMA-1 36 MS-VMA1620-0 VAV MODULAR ASSY.,CLG W/ REHEAT,MS/TP
HWV SEE VALVE SCHEDULE
SEQUENCE OF OPERATIONS
VAV SYSTEM CONTROL:
COOLING MODE:
On a rise in space temperature above the space temperature cooling set point, the damper will modulate from the minimum CFM set point to the maximum CFM set point. As the space temperature drops, the damper will modulate to the minimum CFM set point.
HEATING MODE:
On a drop in space temperature below the heating space temperature set point, the damper will modulate to the minimum heating CFM set point. On a further drop in space temperature below the space temperature set point, the heating coil valve will modulate to maintain the heating space temperature to it’s set point. As the temperature rises the reverse will occur.
*SEE NOTES
VELOCITY PROBES
*SEE NOTES
TEMP. / ADJ.
STT-1
SPACE TEMP.
SENSOR W/ OVERRIDE
OAH
OAT
GLOBAL OUTSIDE AIR
TEMPERATURE AND
HUMIDITY SIGNAL
TO VMA
TE-1
H
C
HWR
HWV
HWS
TO VMA
NOTE(S):
AS-BUILT REV. FINAL POINT TERM./NOTE1 12/3/13 BM
TYPICAL CONSTRUCTION NOTES
THE NEW MODULATING ELECTRONIC CONTROL VALVES SHALL BE
PROVIDED BY MODERN CONTROLS AND INTEGRATED TO THE NEW
DDC CONTROLLERS. FIELD INSTALLATION SHALL BE PROVIDED BY
THE PROJECT GENERAL CONTRACTOR. SEE VALVE SCHEDULE FOR
MORE INFORMATION.
AIR FLOW SCHEDULE PROVIDED BY THE VA FOR REFERENCE ONLY;
SEE AS-BUILT DOCUMENTATION FOR MORE INFO.
FREEZE PROTECTION AND SUPPLY AIR TEMPERATURE MONITORING
PROVIDED BY ASSOCIATED AHU CONTROLS.
NEW PANEL MOUNTED TRANSFORMER(S) SHALL PROVIDE 24V
POWER TO NEW VAV CONTROLLERS AS REQUIRED IN THE FIELD.
ALL CONTROL POINT DESCRIPTIONS AND TERMINAL DESIGNATION
SHALL BE RECORDED IN THE FIELD FOR AS-BUILT DOCUMENTATION.
AS-BUILT NOTE
OUR O&M MANUAL PROVIDED FOR PROJECT CLOSEOUT
INCLUDEDS ALL COMMISSION AND CHECKOUT INFORMATON
FOR ALL VAV BOXES.
THE O&M MANUAL INCLUDES A TYPCIAL VAV CONTROLLER
COMMISSIONING SHEET AND ALSO A COMPLETE VAV BOX
COMMISSIONG CHECK LIST FOR ALL VAV BOXES AS SERVED
BY THEIR ASSOCIATED UNIT.
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
BM 7/19/11
SUB. REVISION EDIT SEQUENCE1 12/13/11 VD
C-4D
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
SEQUENCE OF OPERATIONS -
AHU-7 (MER 8TH FLOOR EAST)
Project Title
SEQUENCE OF OPERATIONS - AHU-7 (MER 8TH FLOOR EAST)
AHU-7 (MER 8TH FL EAST)
1. GENERAL
SUPPLY AND RETURN FANS ARE NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. H-O-A SWITCH SHALL BE KEPT IN THE “AUTO” POSITION. “HAND” AND “OFF” POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. WHEN THE UNIT IS “OFF” D-1, D-2 AND D-3 SHALL BE CLOSED. WHEN THE UNIT IS
“ON” D-1, D-2 AND D-3 SHALL BE OPENED.
2. TEMPERATURE CONTROL
SUPPLY AIR TEMPERATURE SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING EITHER V-1 AND V02 OR D-1, D-2 AND D-3 IN SEQUENCE.
WHEN THE TEMPERATURE OF THE OUTSIDE AIR PROVIDED BY BMS IS ABOVE 65°F DCP PREVENTS MODULATION OF D-1 AND D-2; D-1 ASSUMES MINIMUM OUTSIDE AIR POSITION AND D-2 IS OPENED. V-1 MODULATES TO MAINTAIN SUPPLY AIR TEMPERATURE SENSED BY T-1.
WHEN THE TEMPERATURE OF THE OUTSIDE AIR PROVIDED BY BMS IS BETWEEN 65°F AND THE SUPPLY AIR TEMPERATURE SENSED BY T-1, DAMPER D-2 IS CLOSED AND DAMPER D-1 IS OPENED TO MAXIMUM OUTSIDE AIR POSITION. V-1 MODULATES OPEN TO MAINTAIN THE SUPPLY AIR TEMPERATURE.
3. AIR FLOW CONTROL
THE SUPPLY AIR FLOW IS CONTROLLED BY THE DCP MODULATING SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER (VSMC) TO MAINTAIN THE DUCT STATIC
PRESSURE SETPOINT AS SENSED BY SPS-1.
THE DCP BY USING TOTAL SUPPLY AIR AND RETURN AIR FLOW SIGNALS SHALL RESET THE RETURN AIR FAN VSMC TO MAINTAIN A CONSTANT CFM DIFFERENCE
BETWEEN THE SUPPLY AIR FAN CFM AND THE RETURN AIR FAN CFM.
THE DCP USING HIGH STATIC PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3” OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT SPS-2 EXCEEDS 3” THE SUPPLY AND RETURN FANS SHALL STOP AND THE ALARM SIGNAL
SHALL INDICATE ON DCP AND BMS.
4. HUMIDITY CONTROL
WHEN THE DCP IS NOT CALLING FOR HUMIDIFICATION SENSED BY RETURN AIR HUMIDISTAT H-1, TWO-WAY “ON-OFF” CONTROL VALVE V-3 SHALL REMAIN CLOSED.
WHEN THE DCP IS CALLING FOR HUMIDIFICATION, V-3 SHALL OPEN.
RETURN AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING CONTROL VALVE V-4 TO MAINTAIN THE DESIRED HUMMIDITY. THE DCP SHALL OVERRIDE THE CONTROL TO MAINTAIN HUMIDITY IN SUPPLY DUCT BELOW 80% AS SENSED BY H-2.
DCP SHALL CLOSE VALVE V-3 WHENEVER THE SUPPY FAN IS OFF.
VALVE V-4 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH (FIELD VERIFY INTERLOCK) TO KEEP THE HUMIDIFIER OFF UNTIL CONDENSATE TEMPERATURE
APPROACHES STEAM TEMPERATURE.
5. FREEZE PROTECTION
IF THE AIR TEMPERATURE SENSED BY T-3 FALLS BELOW 45°F AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS BELOW 40°F THE SUPPLY AND RETURN FANS SHALL SHUT DOWN, DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL INDICATE AT THE DCP AND BMS.
6. EMERGENCY SHUTDOWN/RESTART
WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY AND RETURN FANS SHALL STOP AND THE ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM. DAMPERS D-1, D-2 AND D-3 SHALL CLOSE. SUPPLY AND RETURN FANS SHALL RESTART AND THE DAMPERS SHALL
OPEN WHEN THE FIRE ALARM CIRCUIT IS MANUALLY RESET.
7. EMERGENCY CONSTANT SPEED OPERATION
UPON FAILURE OF VSMC THE SUPPLY AND RETURN FANS SHALL BE STARTED/STOPPED MANUALLY AT THE DCP OR THE BMS THROUGH THE BYPASS STARTER.
FANS SHALL THEN OPERATE AT CONSTANT SPEED.
AS-BUILT REV. NEW DWG. / ADD NOTE2 12/3/13 BM
NOTE(S): REFER TO DRAWING C-4C FOR ASSOCIATED VAV BOX
SEQUENCE OF OPERATIONS AND AIR FLOW SCHEDULE.
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
BM 7/19/11
SUB. REVISION TAGS/NOTES1 12/13/11 VD
C-5A
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
AIR HANDLING UNIT CONTROL –
AHU FOR ELEVATOR
(9TH FLOOR LOBBY)
Project Title
AIR HANDLING UNIT CONTROL – AHU for ELEVATOR (9TH FLOOR LOBBY)
OAH
OAT
LOCAL OUTSIDE AIR
TEMPERATURE AND
HUMIDITY SIGNAL
SUPPLY
AIROUTDOOR
AIR
RELIEF
UI-4
MA-T
UI-3
*SEE NOTES (TYP)
D-3
D-1
D-2
C
DI
*SEE NOTES (TYP.)
*SEE NOTES
UI-4
RA-TH
RA-H
RF
AO-9
V-1
DP
UI-2
N.C.
N.C.
N.O. UI-2
DA-T
110v (EXISTING)
*EXISTING EX. CP
9TH FLOOR MECH.
EQUIPMENT RM. - MER
CT
*SEE NOTES
1 2
AS-BUILT REV. POINT TERM./COMM.2 12/3/13 BM
BILL OF MATERIALS
Designation Qty Part Number Description
LL 1 A70GA-1C LOW LIMIT,AUTO RESET,20FT ELEM.
FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET
IOM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET
LL-1
IOM-47 POINT IDENTIFICATION
POINT #
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
BI-7
BI-8
POINT NAME/DESCRIPTION
OUTSIDE AIR HUMIDITY (OAH)
FILTER DIFFERENTIAL PRESSURE (DP)
EXHAUST FAN EF-1 STATUS (CT)
LOW LIMIT SHUTDOWN (LL)
CHILLED WATER COIL PUMP STATUS
EXHAUST FAN EF-2 STATUS (CT)
DISCHARGE AIR SMOKE DETECTOR
FEC-26 POINT IDENTIFICATION
POINT #
UI-1
UI-2
UI-3
UI-4
UI-5
UI-6
BI-7
BI-8
AO-8
AO-9
BO-1
BO-2
BO-3
CO-4
CO-5
CO-6
CO-7
POINT NAME/DESCRIPTION
SPACE TEMPERATURE SENSOR (ST)
DISCHARGE AIR TEMPERATURE (DA-T)
SUPPLY FAN STATUS (DPS)
RETURN AIR HUMIDITY (RA-H)
OUTSIDE AIR TEMPERATURE (OAT)
RETURN FAN STATUS (DPS)
ECONOMIZER DAMPER COMMMAND (D1~D3)
CHILLED WATER COIL VALVE CONTROL (V-1)
MIXED AIR TEMPERATURE (MA-T)
RETURN AIR TEMPERATURE (RA-T)
SUPPLY FAN START/STOP
DX COOLING STAGE 2 COMMAND
CHILLED WATER COIL PUMP S/S
RETURN FAN START/STOP
DX COOLING STAGE 1 COMMAND
AO-8
AO-9
BO-1
BO-2
BO-3
CO-4
CO-5
CO-6
CO-7
FEC-26
IOM-47
CT
D
X
BI-7 BI-8
*IOM
EXISTING EXHAUST FAN CONTROL; EF-1 & EF-2
EF-1 EF-2
R CT
R CT
STAGE 1 STAGE 2
BO-3 CO-4
BI-4BI-3
CU-1
*AO-8
*AO-8
*AO-8
R BO-1
R BO-2
UI-1
*IOM
NOTE(S): ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY
EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-
USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC
CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON
DDC CONTROLLERS AS INDICATED. CONTROLLERS SHALL BE PROGRAMMED TO MATCH
EXISTING SEQUENCE OF OPERATIONS FOR ANY EQUIPMENT WITHOUT A SEQUENCE OF
OPERATION PROVIDED WITHIN THE CONTRACT DOCUMENTS. *REFER TO C-5B FOR
CONTROLLER WIRING DETAILS.
NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND
INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE
‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING
M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR
ADDITIONAL INFORMATION.
THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING
DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS
WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL
PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS
HAVE BEEN APPROVED BY THE VA HOSPITAL.
ST
SPACE
TEMPERATURE
SENSOR
(EXISTING)
CO-5
*IOM*IOM
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
C-5B
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS UPGRADE -
PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
Project Title
CONTROLLER WIRING DETAIL
– AHU for ELEVATOR
(9TH FLOOR LOBBY)
CONTROLLER WIRING DETAIL – AHU for ELEVATOR (9TH FLOOR LOBBY)
SEE AS-BUILT CONTROL DRAWING C-5A FOR ASSOCIATED UNIT
CONTROL DIAGRAM AND UNIT SPECIFIC NOTES.
NOTE(S):
124816326412
O N
Address:
S A
PW
R
C O
M
SA BUS
FC BUS
C O
M S
H
LD+1
5V
IN
IC
O M
IN
IC
O M
+1
5V
IN
IC
O M
IN
IC
O M
+1
5V
IN
IC
O M
IN
IC
O M
IN
IC
O M
IN
IC
O M
UNIVERSAL BINARY
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
H O
T
24V
C O
M
FEC2611
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
124816326412
O N
Address:
SA
FC
H O
T
24V
C O
M
IOM4711
FC EOL
IN
TRIAC JUMPERS
OUT1 INT
EXT
OUT2 OUT3
S A
P W
R
C O
M
+ - C
O M
S H
LD
SA/FC BUS
BINARY
O U
T4 O
C O
M
O U
T5 O
C O
M
O U
T6 O
C O
M
O U
T7 O
C O
M
O U
T8 O
C O
M
O U
T9 O
C O
M
CONFIGURABLE ANALOG
O U
T1 O
C O
M
O U
T2 O
C O
M
O U
T3 O
C O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
+1 5V
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
IN
IC
O
M
UNIVERSAL BINARY
SP
A
C E
TE
M
PE
R
A
TU
R E
SE
N
SO
R
(S T)
EC
O
N O
M
IZ
ER
D
A M
PE
R
C O
M M
A N
D (D
1~ D
3)
C H
IL
LE
D W
A
TE
R C
O
IL
V A
LV
E
C O
N
TR
O L
(V -1
SU
PP
LY
F
A N
S
TA
R T/
ST
O
P
D X
C O
O
LI
N G
S
TA
G E
C
O M
M A
N D
R
ET
U R
N F
A N
S
TA
R T/
ST
O
P
D X
C O
O
LI
N G
S
TA
G E
C
O M
M A
N D
D
IS
C H
A R
G E
A
IR
T
EM
PE
R
A
TU
R E
(D A
-T
M
IX
ED
A
IR
T
EM
PE
R A
TU
R
E (M
A -T
R
ET
U R
N A
IR
T
EM
PE
R A
TU
R
E (R
A -T
R
ET
U R
N A
IR
H
U M
ID
IT
Y
SE
N
SO
R (R
A -H
O U
TS
ID
E A
IR
T
EM
PE
R A
TU
R
E (O
A -T
SU
PP
LY
F
A N
S
TA
TU
S
(D
PS
R
ET
U R
N F
A N
S
TA
TU
S
(D
PS
O U
TS
ID
E A
IR
H
U M
ID
IT
Y (O
A -H
FI
LT
ER
D
IF
FE
R
EN
TI
A
L
PR
ES
SU
R E
(D P)
D
IS
C H
A R
G E
A
IR
S M
O K
E D
ET
EC
TO
R
LO
W
L
IM
IT
S
H U
TD
O
W N
(L L)
C H
IL
LL
ED
W
A
TE
R C
O
IL
P U
M P
ST
A
TU
S
EX
H
A U
ST
F
A N
E F-
ST
A
TU
S (C
T)
EX
H
A U
ST
F
A N
E F-
ST
A
TU
S (C
T)
AS-BUILT REV. NEW DWG. / POINT TERM.1 12/3/13 BM
C H
IL
LE
D W
A
TE
R C
O
IL
P U
M P
ST
A
R T/
ST
O
P
7 BELLECOR DRIVE
NEW CASTLE, DE
19720
TEL: 302-325-6800
FAX: 302-325-6808
C-6A
Sales Engineer Project Manager Application Engineer
BY DATE BY DATE
DRAWN APPROVED
Branch Information CONTRACT NUMBER
DRAWING NUMBER
VA HVAC CONTROLS
UPGRADE - PHASE 2B
WILMINGTON, DELAWARE
Drawing Title
TYPICAL HEAT EXCHANGER
CONTROL – MAIN BUILDING
Project Title
TYPICAL HEAT EXCHANGER CONTROL – MAIN BUILDING
(INCLUDES HEAT EXCHANGERS – C5, C6, C7 & C8)
OAH
OAT
GLOBAL OUTSIDE AIR
TEMPERATURE AND
HUMIDITY SIGNAL
110v (EXISTING)
*EXISTING EX. CP
EQUIPMENT RM. - MER
(MAIN HVAC SHOP)
SEQUENCE OF OPERATIONS
BOOSTER HEATER HOT WATER HEATER (PUMP P-X)
1. PUMP P-X STARTS AND STOPS BY BMS BASED ON HOT WATER DEMAND FROM HOT
WATER CONSUMING EQUIPMENT.
2. SENSOR T-1(TE) MODULATES NORMALLY CLOSED VALVES V-1 AND V-2 TO MAINTAIN 180
F SUPPLY WATER TEMPERATURE.
ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-USED AND WIRED TO
NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC CONTROL DEVICES HAVE BEEN
PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON DDC CONTROLLERS AS INDICATED.
NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE ‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING M-1 OF THE CONTRACT DOCUMENTS.
PLEAS…