VA Hospital Phase 2B - ATC As-Built Drawings.pdf

PDF 1 MB Posted

Attached to
J059--Direct Digital Control Services Wilmington VAMC
Solicitation number
36C24421Q0145
Issued by

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MECHANICAL AND CONTROL SYSTEMS

Environmental Control System

Building Automation System

VA MEDICAL CENTER

HVAC CONTROLS UPGRADE - PHASE 2B

WILMINGTON, DELAWARE

PROJECT

OWNER

ENGINEER

CONTRACTOR

211-1009

MODERN CONTROLS INC

7 BELLECOR DRIVE

NEW CASTLE, DE. 19720

DATE

Branch Information

CONTRACT NUMBER

IW/BM

APPLICATION ENGINEER

7/19/11IW/JA

PROJECT MANAGER

IW

SALES ENGINEER

REFERENCE DRAWING

SUB. REVISION TITLE DATES1 12/13/11 VD

NO. REVISION-LOCATION ECN DATE BY

Automatic Temperature Controls

Heating

Air Conditioning

Air Filters

Water Treatment

Coil Cleaning

Contract Operations

Time-Shared Automated Building Service

Refrigeration

Industrial Controls / Recording / Indication Equipment

Air and Water Systems Balancing

Instrumentation System Installation

Building Operations Management

Energy Conservation Control

Custom Programmed Maintenance

HATCH MOTT MACDONALD

27 BLEEKER ST.

MILLBURN, NJ 07041

BOB SMITH CONTRACTORS

281 EAST EVERGREEN ST.

WEST GROVE, PA 19390

DEPT. OF VETERANS AFFAIRS

1601 KIRKWOOD HIGHWAY

WILMINGTON, DE 19805

VA HVAC CONTROLS UPGRADE - PHASE 2B

(PARTIAL SUBMITTAL - INCLUDES 7TH 8TH & 9TH FLOOR HVAC EQUIPMENT)

PAGE # DRAWING TITLE LAST REVISION

TP-1 TITLE PAGE 01/28/14

C-1A AIR HANDLING UNIT CONTROL – AHU-1 (MER 7003) 12/03/14

C-1B CONTROLLER WIRING DETAIL – AHU-1 (MER 7003) 12/03/14

C-1C SEQUENCE OF OPERATIONS – AHU-1 (MER 7003) 12/03/14

C-2A AIR HANDLING UNIT CONTROL – AHU-2 (MER 7060A) 12/03/14

C-2B CONTROLLER WIRING DETAIL – AHU-2 (MER 7060A) 12/03/14

C-2C AIR HANDLING UNIT CONTROL – AHU-3 (MER 7074) 12/03/14

C-2D CONTROLLER WIRING DETAIL – AHU-3 (MER 7074) 12/03/14

C-2E SEQUENCE OF OPERATIONS – TYPICAL FOR AHU-2 & AHU-3 (MER 7060A & 7074) 12/03/14

C-3A AIR HANDLING UNIT CONTROL – A/C-1 (MER 8TH FLOOR WEST) 12/03/14

C-3B CONTROLLER WIRING DETAIL – A/C-1 (MER 8TH FLOOR WEST) 12/03/14

C-3C SEQUENCE OF OPERATIONS – AC-1 (MER 8TH FLOOR WEST) 12/03/14

C-4A AIR HANDLING UNIT CONTROLS – AHU-7 (MER 8TH FLOOR EAST) 12/03/14

C-4B CONTROLLER WIRING DETAIL – AHU-7 (MER 8TH FLOOR EAST) 12/03/14

C-4C VAV BOX CONTROLS FOR 7TH FLOOR EAST (SERVED BY AHU-7) 12/03/14

C-4D SEQUENCE OF OPERATIONS – AHU-7 (MER 8TH FLOOR EAST) 12/03/14

C-5A AIR HANDLING UNIT CONTROL – ELEVATOR AHU 9TH FLOOR 12/03/14

C-5B CONTROLLER WIRING DETAIL – ELEVATOR AHU 9TH FLOOR 12/03/14

C-6A TYPICAL HEAT EXCHANGER CONTROL – MAIN BUILDING 01/28/14

C-6B CONTROLLER WIRING DETAIL – TYPICAL HEAT EXCHANGER (MAIN BUILDING) 01/28/14

AS-BUILT REV. NEW DWG. TITLES/DATES2 12/03/13 BM

2 3

AS-BUILT REV. ADD ‘MASTER’ NOTE3 1/28/14 DB

NOTE(S): REFER TO ‘MASTER BUILDING NETWORK ARCHITECTURE DRAWING’

PROVIDED IN OUR ATC AS-BUILT / O&M MANUAL BINDER FOR ALL

SUPERVISORY CONTROLLER INFORMATION AND ASSOCIATED IP

ADDRESSES USED BY MODERN CONTROLS.

REFER TO ‘MASTER BUILDING VALVE SCHEDULE’ PROVIDED IN OUR

ATC AS-BUILT / O&M MANUAL BINDER FOR A COMPLETE LIST OF ALL

CONTROL VALVES PROVIDED FOR AIR HANDLING UNITS AND

ASSOCIATED VAV BOXES.

IW/BMIW/JAIW

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 7/20/11

REFERENCE DRAWING

SUB. REVISION TAGS/NOTES1 12/12/11 VD

C-1A

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

AIR HANDLING UNIT CONTROL

– AHU-1 (MER 7003)

Project Title

AIR HANDLING UNIT CONTROL – AHU-1 (MER 7003)

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

110v (EXISTING)

*EXISTING EX. CP

7TH FLOOR MECH.

EQUIPMENT RM. -

(MER 7003)

SUPPLY

AIR

OUTDOOR

AIR

SF

RETURN

SMK

BO-1

R AO-8HOA

UI-3

S/S

CMD.

H L

SPS-1

UI-6

*SEE NOTES

DA

(D-1)

H

RA-H

UI-5

HUMID.

HIGH LIMIT

N.C.

HUMIDIFIER

H L

SPS-2

BI-8

UI-1

DA-T

VSMC

RH

C

STEAM

RE-HEAT

LPS

CO-5

*SEE NOTES

V-1

COND.

UI-2

MA-T

C

C

BI-7

DPS

LPS

HUMIDIFIER CONTROL

HUMID.

COND.

AO-9

V-4

BO-3

V-3

AS-BUILT REV. FINAL POINT TERM.2 12/3/13 BM

FEC-26

IOM-47

IOM-47 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

POINT NAME/DESCRIPTION

DISCHARGE AIR HUMIDITY (DA-H)

FINAL FILTER DIFFERENTIAL PRESSURE SWITCH (DP2)

PRE FILTER DIFFERENTIAL PRESSURE SWITCH (DP1)

DISCHARGE AIR DUCT HIGH STATIC (SPS-2)

FEC-26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

DISCHARGE AIR TEMPERATURE (DA-T)

MIXED AIR TEMPERATURE (MA-T)

SUPPLY FAN STATUS (DPS)

RETURN AIR HUMIDITY (RA-H)

SUPPLY AIR STATIC PRESSURE (SPS-1)

FREEZE STAT / SHUTDOWN (LL)

SUPPLY FAN VFD COMMAND

HUMIDIFIER CONTROL VALVE CMD. (V-4)

SUPPLY AIR SMOKE DETECTOR SHUTDOWN

RETURN AIR TEMPERATURE (RA-T)

SUPPLY FAN START / STOP

COOLING VALVE COMMAND (V-2)

RE-HEAT VALVE COMMAND (V-1)

*ECONOMIZER DAMPER COMMAND (D-1)

HUMIDIFIER ISOLATION VALVE (V-3)

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

BILL OF MATERIALS

Designation Qty Part Number Description

DA 1 M9220-GGC-3 ACT.,PROP.,0-10V,179#IN,2-AUX.,W/ES

RA-T 1 TE-6315P-1 SENSOR,T-NI,0.1%,8FT AVG.,

LL 1 A70HA-1C STAT.,LOW LIMIT,20FT ELEM.,MAN. RESET

FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET

IOM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET

V-X SEE VALVE SCHEDULE FOR MORE INFORMATION

*CO-7

*SEE NOTES

UI-4

RA-T

BI-8

LL

*IOM *SEE DETAIL

& NOTES

UI-1

H

DA-H

*IOM

CWS

CWR

*SEE NOTES

CO-6

V-2

N.C.

PRE

FILTER

(EXISTING DP)

FINAL

FILTER

(EXISTING DP)

UI-6

DP1 DP2

BI-7

*IOM *IOM

NOTE(S): ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY

EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-

USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC

CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON

DDC CONTROLLERS AS INDICATED. *REFER TO C-1B FOR CONTROLLER WIRING DETAILS

AND DRAWING C-1C FOR ASSOCIATED SEQUENCE OF OPERATIONS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND

INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE

‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING

M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR

ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS

WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL

PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS

HAVE BEEN APPROVED BY THE VA HOSPITAL.

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 7/20/11

C-1B

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

CONTROLLER WIRING DETAIL

– AHU-1 (MER 7003)

Project Title

AS-BUILT REV. NEW DWG./POINT TERM.1 12/3/13 BM

CONTROLLER WIRING DETAIL – AHU-1 (MER 7003)

SEE AS-BUILT CONTROL DRAWINGS C-1A AND C-1C FOR

ASSOCIATED UNIT CONTROL DIAGRAM AND SEQUENCE OF

OPERATIONS.

NOTE(S):

124816326412

O N

Address:

S A

PW

R

C O

M

SA BUS

FC BUS

C O

M S

H

LD+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

IN

IC

O M

IN

IC

O M

UNIVERSAL BINARY

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

FEC2611

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

124816326412

O N

Address:

SA

FC

H O

T

24V

C O

M

IOM4711

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

S A

P W

R

C O

M

+ - C

O M

S H

LD

SA/FC BUS

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

D

IS

C H

A R

G E

A

IR

T

EM

PE

R

A

TU

R E

(D A

-T

SU

PP

LY

F

A N

V

FD

C O

M M

A N

D

H U

M

ID

IF

IE

R C

O N

TR

O

L

VA

LV

E

C O

M M

A N

D (V

-4

SU

PP

LY

F

A N

S

TA

R T/

ST

O

P

C O

O

LI

N G

V A

LV

E

C O

M M

A N

D (V

-2

R E-

H

EA

T

VA

LV

E

C O

M M

A N

D (V

-1

*E C

O N

O M

IZ

ER

D A

M

PE

R C

O M

M A

N D

(D -1

H U

M

ID

IF

IE

R

IS

O

LA

TI

O

N V

A

VL

E (V

-3

M

IX

ED

A

IR

T

EM

PE

R A

TU

R

E (M

A -T

SU

PP

LY

A

IR

S

M O

K E

D

ET

EC

TO

R S

H U

TD

O

W N

R

ET

U R

N A

IR

T

EM

PE

R A

TU

R

E (R

A -T

R

ET

U R

N A

IR

H

U M

ID

IT

Y (R

A -H

SU

PP

LY

A

IR

S

TA

TI

C P

R

ES

SU

R

E (S

PS

-1

SU

PP

LY

F

A N

S

TA

TU

S

(D

PS

FR

EE

ZE

S

TA

T

/ S H

U

TD

O W

N (L

L)

D

IS

C H

A R

G E

A

IR

H U

M

ID

IT

Y

(D A

-H

PR

E-

FI

LT

ER

D

IF

FE

R

EN

TI

A

L

PR

ES

SU

R E

SW

IT

C H

(D P1

FI

N

A L

FI

LT

ER

D

IF

FE

R

EN

TI

A

L

PR

ES

SU

R E

SW

IT

C H

(D P2

D

IS

C H

A R

G E

A

IR

D U

C T

H

IG

H S

TA

TI

C (S

PS

-2

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 7/20/11

SUB. REVISION ADD NOTE1 12/12/11 VD

C-1C

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS

UPGRADE - PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

SEQUENCE OF OPERATIONS -

AHU-1 (MER 7003)

Project Title

SEQUENCE OF OPERATIONS - AHU-1 (MER 7003)

AHU-1 (MER #7003)

1. GENERAL

UNIT IS NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. H-O-A SWITCH SHALL BE KEPT IN THE “AUTO” POSITION. “HAND”

AND “OFF” POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. WHEN THE UNIT IS “OFF” D-1 SHALL BE CLOSED. WHEN THE UNIT IS “ON” D-1 SHALL BE

FULLY OPENED.

2. TEMPERATURE CONTROL

SUPPLY AIR TEMPERATURE SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING V-1 AND V-2 IN SEQUENCE.

3. AIF FLOW CONTROL

THE SUPPLY AIRFLOW SHALL BE CONTROLLED BY THE DCP MODULATING THE SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER (VSMC) TO

MAINTAIN 1.5” OF DUCT STATIC PRESSURE (FIELD ADJUSTABLE) SENSED BY SPS-1.

THE DCP USING HIGH STATIC PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM

DEVELOPING OVER 3” OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT SPS-2 EXCEEDS 3” THE SUPPLY FAN SHALL STOP.

4. HUMIDITY CONTROL

WHEN THE DCP IS NOT CALLING FOR HUMIDIFICATION SENSED BY SPACE AIR HUMIDISTAT H-1, TWO-WAY “ON-OFF” CONTROL VALVE V-3 SHALL REMAIN

CLOSED. WHEN THE DCP IS CALLING FOR HUMIDIFICATION, V-3 SHALL OPEN.

RETURN AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT SENSED BY H-1 VIA DCP BY MODULATING CONTROL VALVE V-4 TO MAINTAIN THE DESIRED

HUMIDITY. THE DCP SHALL OVERRIDE THE CONTROL TO MAINTAIN HUMIDITY IN SUPPLY DUCT BELOW 80% AS SENSED BY H-2. DCP SHALL CLOSE

VALVE V-3 WHENEVER THE SUPPLY FAN IS OFF. VALVE V-4 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH; (FIELD VERIFY INTERLOCK) TO

KEEP THE HUMIDIFIER OFF UNTIL CONDENSATE TEMPERATURE APPROACHES STEAM TEMPERATURE.

5. FREEZE PROTECTION

IF THE AIR TEMPERATURE SENSED BY T-2 FALLS BELOW 45°F AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS

BELOW 40°F THE SUPPLY FAN SHALL SHUT DOWN, THE DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL INDICATE AT THE DCP AND BMS.

6. EMERGENCY SHUTDOWN/RESTART

WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY FAN STOPS AND THE ALARM SIGNAL IS TRANSMITTED TO THE

FIRE ALARM SYSTEM, DAMPERS D-1 AND D-2 SHALL CLOSE. SUPPLY AND RETURN FANS SHALL RESTART AND THE DAMPERS SHALL OPEN WHEN THE

FIRE ALARM CIRCUIT IS MANUALLY RESET.

1 2

AS-BUILT REV. NEW DRAWING2 12/3/13 BM

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 7/20/11

SUB REVISION TAGS/NOTES1 12/12/11 VD

C-2A

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

AIR HANDLING UNIT CONTROL

– AHU-2 (MER 7060A)

Project Title

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

110v (EXISTING)

*EXISTING

7TH FLOOR MECH.

EQUIPMENT RM. -

(MER 7060A)

EX. CP

(AHU-2)

AS-BUILT REV. NEW DWG. / POINT TERM.2 12/3/13 BM

FEC-26

IOM-47

AIR HANDLING UNIT CONTROL – AHU-2 (MER 7060A)

(CONSTANT VOLUME UNIT)

SUPPLY

AIR

OUTDOOR

AIR

*SEE NOTES

DA

(D-1)

H

RA-H

UI-5

HUMID.

HIGH LIMIT

N.C.

HUMIDIFIER

UI-1

DA-TRH

C

STEAM

RE-HEAT

LPS

AO-9

*SEE NOTES

V-1

COND.

UI-2

MA-T

C

HUMIDIFIER CONTROL

HUMID.

COND.

AO-8

V-5

BO-3

V-4

IOM-47 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

POINT NAME/DESCRIPTION

DISCHARGE AIR HUMIDITY (DA-H)

PRE FILTER DIFFERENTIAL PRESSURE SWITCH (DP-1)

FINAL FILTER DIFFERENTIAL PRESSURE SWITCH (DP-2)

FEC-26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

DISCHARGE AIR TEMPERATURE (DA-T)

MIXED AIR TEMPERATURE (MA-T)

SUPPLY FAN STATUS (DPS)

RETURN AIR HUMIDITY (RA-H)

DISCHARGE AIR HUMIDITY (DA-H)

FREEZE STAT / SHUTDOWN (LL)

HUMIDIFIER CONTROL VALVE COMMAND (V-5)

RE-HEAT VALVE COMMAND (V-1)

PRE-HEAT DISCHARGE AIR TEMPERATURE (PH-T)

RETURN AIR TEMPERATURE (RA-T)

SUPPLY FAN START / STOP

COOLING VALVE COMMAND (V-2)

PRE-HEAT VALVE COMMAND (V-3)

*ECONOMIZER DAMPER COMMAND (D-1)

HUMIDIFIER ISOLATION VALVE (V-4)

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

*CO-7

*SEE NOTES

UI-4

RA-T

BI-8

LL

*SEE DETAIL

& NOTES

UI-6

H

DA-H

CWS

CWR

*SEE NOTES

CO-6

V-2

N.C.

PRE

FILTER

(EXISTING DP)

FINAL

FILTER

(EXISTING DP)

PH

C

HWS

HWR

*SEE NOTES

CO-5

V-3

N.C.

STEAM

PRE-HEAT

UI-3

PH-T

R

BILL OF MATERIALS

Designation Qty Part Number Description

DA 1 M9220-GGC-3 ACT.,PROP.,0-10V,179#IN,2-AUX.,W/ES

XX-T 2 TE-6315P-1 SENSOR,T-NI,0.1%,8FT AVG.,

LL 1 A70HA-1C STAT.,LOW LIMIT,20FT ELEM.,MAN. RESET

FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET

IOM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET

V-X SEE VALVE SCHEDULE FOR MORE INFORMATION

NOTE(S): ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY

EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-

USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC

CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON

DDC CONTROLLERS AS INDICATED. *REFER TO C-2B FOR CONTROLLER WIRING DETAILS

AND DRAWING C-2E FOR ASSOCIATED SEQUENCE OF OPERATIONS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND

INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE

‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING

M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR

ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS

WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL

PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS

HAVE BEEN APPROVED BY THE VA HOSPITAL.

DP-1

UI-5

*IOM

DP-2

UI-6

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

C-2B

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

CONTROLLER WIRING DETAIL;

AHU-2 (MER 7060A)

Project Title

AS-BUILT REV. NEW DWG./POINT TERM.1 12/3/13 DB

CONTROLLER WIRING DETAILS; AHU-2 (MER 7060A)

SEE AS-BUILT CONTROL DRAWINGS C-2A AND C-2E FOR

ASSOCIATED UNIT CONTROL DIAGRAM AND SEQUENCE OF

OPERATIONS.

NOTE(S):

124816326412

O N

Address:

S A

PW

R

C O

M

SA BUS

FC BUS

C O

M S

H

LD+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

IN

IC

O M

IN

IC

O M

UNIVERSAL BINARY

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

FEC2611

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

124816326412

O N

Address:

SA

FC

H O

T

24V

C O

M

IOM4711

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

S A

P W

R

C O

M

+ - C

O M

S H

LD

SA/FC BUS

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

D

IS

C H

A R

G E

A

IR

T

EM

PE

R

A

TU

R E

(D A

-T

H U

M

ID

IF

IE

R C

O N

TR

O

L

VA

LV

E

C O

M M

A N

D (V

-5

R E-

H

EA

T

VA

LV

E

C O

M M

A N

D (V

-1

SU

PP

LY

F

A N

S

TA

R T/

ST

O

P

C O

O

LI

N G

V A

LV

E

C O

M M

A N

D (V

-2

PR

E-

H

EA

T

VA

LV

E

C O

M M

A N

D (V

-3

*E C

O N

O M

IZ

ER

D A

M

PE

R C

O M

M A

N D

(D -1

H U

M

ID

IF

IE

R

IS

O

LA

TI

O

N V

A

LV

E (V

-4

M

IX

ED

A

IR

T

EM

PE

R A

TU

R

E (M

A -T

PR

E-

H

EA

T D

IS

C

H A

R G

E A

IR

T

EM

PE

R A

TU

R

E (P

H -T

R

ET

U R

N A

IR

T

EM

PE

R A

TU

R

E (R

A -T

R

ET

U R

N H

U M

ID

IT

Y (R

A -H

D

IS

C H

A R

G E

A

IR

H U

M

ID

IT

Y

(D A

-H

SU

PP

LY

F

A N

S

TA

TU

S

(D

PS

FR

EE

ZE

S

TA

T

/ S H

U

TD

O W

N (L

L)

D

IS

C H

A R

G E

A

IR

H U

M

ID

IT

Y

(D A

-H

PR

E-

FI

LT

ER

D

IF

FE

R

EN

TI

A

L

PR

ES

SU

R E

SW

IT

C H

(D P-

1)

FI

N

A L

FI

LT

ER

D

IF

FE

R

EN

TI

A

L

PR

ES

SU

R E

SW

IT

C H

(D P-

2)

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 7/20/11

SUB REVISION TAGS/NOTES1 12/12/11 VD

C-2C

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

AIR HANDLING UNIT CONTROL;

AHU-3 (MER 7074)

Project Title

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

110v (EXISTING)

*EXISTING

7TH FLOOR MECH.

EQUIPMENT RM. -

(MER 7074)

EX. CP

(AHU-3)

AS-BUILT REV. NEW DWG. / POINT TERM.2 12/3/13 BM

FEC-26

IOM-47

BI-7

*SEE NOTES

CO-7

GENERAL EXHAUST FAN CONTROL

SUPPLY

AIROUTDOOR

AIR

*SEE NOTES

DA

(D-1)

H

RA-H

UI-5

HUMID.

HIGH LIMIT

N.C.

HUMIDIFIER

UI-1

DA-TRH

C

STEAM

RE-HEAT

LPS

AO-9

*SEE NOTES

V-1

COND.

UI-2

MA-T

C

HUMIDIFIER CONTROL

HUMID.

COND.

AO-8

V-5

BO-3

V-4

IOM-47 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

POINT NAME/DESCRIPTION

EXISTING EXHAUST FAN STATUS (CT)

PRE FILTER DIFFERENTIAL PRESSURE SWITCH (DP)

FINAL FILTER DIFFERENTIAL PRESSURE SWITCH (DP)

FEC-26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

DISCHARGE AIR TEMPERATURE (DA-T)

MIXED AIR TEMPERATURE (MA-T)

SUPPLY FAN STATUS (DPS)

RETURN AIR HUMIDITY (RA-H)

DISCHARGE AIR HUMIDITY (DA-H)

FREEZE STAT / SHUTDOWN (LL)

HUMIDIFIER CONTROL VALVE COMMAND (V-5)

RE-HEAT VALVE COMMAND (V-1)

PRE-HEAT DISCHARGE AIR TEMP. (PH-T)

RETURN AIR TEMPERATURE (RA-T)

SUPPLY FAN START / STOP

COOLING VALVE COMMAND (V-2)

PRE-HEAT VALVE COMMAND (V-3)

*ECONOMIZER DAMPER COMMAND (D-1)

HUMIDIFIER ISOLATION VALVE (V-4)

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7 EXISTING EXHAUST FAN & DAMPER COMMAND (D-1/R)

*CO-7

*SEE NOTES

UI-4

RA-T

BI-8

LL

*SEE DETAIL

& NOTES

UI-6

H

DA-H

CWS

CWR

*SEE NOTES

CO-6

V-2

N.C.

PRE

FILTER

(EXISTING DP)

FINAL

FILTER

(EXISTING DP)

PH

C

HWS

HWR

*SEE NOTES

CO-5

V-3

N.C.

STEAM

PRE-HEAT

UI-3

PH-T

AIR HANDLING UNIT CONTROL – AHU-3 (MER 7070)

(CONSTANT VOLUME UNIT)

DA

(D-1)

*EXISTING DAMPER

CT

L

*IOM

BILL OF MATERIALS

Designation Qty Part Number Description

DA 1 M9220-GGC-3 ACT.,PROP.,0-10V,179#IN,2-AUX.,W/ES

XX-T 2 TE-6315P-1 SENSOR,T-NI,0.1%,8FT AVG.,

LL 1 A70HA-1C STAT.,LOW LIMIT,20FT ELEM.,MAN. RESET

FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET

IOM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET

V-X SEE VALVE SCHEDULE FOR MORE INFORMATION

NOTE(S):

ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY

EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-

USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC

CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON

DDC CONTROLLERS AS INDICATED. *REFER TO C-2D FOR CONTROLLER WIRING DETAILS

AND DRAWING C-2E FOR ASSOCIATED SEQUENCE OF OPERATIONS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND

INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE

‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING

M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR

ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS

WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL

PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

C-2D

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

CONTROLLER WIRING DETAIL;

AHU-3 (MER 7070)

Project Title

AS-BUILT REV. NEW DWG./POINT TERM.1 12/3/13 DB

CONTROLLER WIRING DETAILS; AHU-3 (MER 7070)

SEE AS-BUILT CONTROL DRAWINGS C-2C AND C-2E FOR

ASSOCIATED UNIT CONTROL DIAGRAM AND SEQUENCE OF

OPERATIONS.

NOTE(S):

124816326412

O N

Address:

S A

PW

R

C O

M

SA BUS

FC BUS

C O

M S

H

LD+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

IN

IC

O M

IN

IC

O M

UNIVERSAL BINARY

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

FEC2611

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

124816326412

O N

Address:

SA

FC

H O

T

24V

C O

M

IOM4711

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

S A

P W

R

C O

M

+ - C

O M

S H

LD

SA/FC BUS

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

D

IS

C H

A R

G E

A

IR

T

EM

PE

R

A

TU

R E

(D A

-T

H U

M

ID

IF

IE

R C

O N

TR

O

L

VA

LV

E

C O

M M

A N

D (V

-5

R E-

H

EA

T

VA

LV

E

C O

M M

A N

D (V

-1

SU

PP

LY

F

A N

S

TA

R T/

ST

O

P

C O

O

LI

N G

V A

LV

E

C O

M M

A N

D (V

-2

PR

E-

H

EA

T

VA

LV

E

C O

M M

A N

D (V

-3

*E C

O N

O M

IZ

ER

D A

M

PE

R C

O M

M A

N D

(D -1

H U

M

ID

IF

IE

R

IS

O

LA

TI

O

N V

A

LV

E (V

-4

M

IX

ED

A

IR

T

EM

PE

R A

TU

R

E (M

A -T

PR

E-

H

EA

T D

IS

C

H A

R G

E A

IR

T

EM

PE

R A

TU

R

E (P

H -T

R

ET

U R

N A

IR

T

EM

PE

R A

TU

R

E (R

A -T

R

ET

U R

N H

U M

ID

IT

Y (R

A -H

D

IS

C H

A R

G E

A

IR

H U

M

ID

IT

Y

(D A

-H

SU

PP

LY

F

A N

S

TA

TU

S

(D

PS

FR

EE

ZE

S

TA

T

/ S H

U

TD

O W

N (L

L)

PR

E-

FI

LT

ER

D

IF

FE

R

EN

TI

A

L

PR

ES

SU

R E

SW

IT

C H

(D P-

1)

FI

N

A L

FI

LT

ER

D

IF

FE

R

EN

TI

A

L

PR

ES

SU

R E

SW

IT

C H

(D P-

2)

EX

IS

TI

N

G E

XH

A

U

ST

F A

N S

TA

TU

S (C

T)

EX

IS

TI

N

G E

XH

A

U

ST

F A

N

D A

M

PE

R C

O M

M A

N D

(D -1

/R

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 7/20/11

SUB. REVISION EDIT SEQUENCE1 12/12/11 VD

C-2E

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

SEQUENCE OF OPERATIONS -

AHU-2 & AHU-3 (MER 7060A &

7074)

Project Title

SEQUENCE OF OPERATIONS – TYPICAL FOR AHU-2 & AHU-3 (MER 7060A & 7074)

AHU-2 (MER #7060A), AHU-3 (MER #7074)

1. GENERAL

UNIT IS NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. H-O-A SWITCH SHALL BE KEPT IN THE “AUTO” POSITION. “HAND”

AND “OFF” POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. WHEN THE UNIT IS “OFF” D-1 SHALL BE CLOSED. WHEN THE UNIT IS “ON” D-1 SHALL BE

FULLY OPENED.

2. TEMPERATURE CONTROL

SPACE AIR TEMPERATURE SENSED BY THE ROOM TEMPERATURE SENSOR T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING V-1 AND

V-2 IN SEQUENCE.

3. AIR FLOW CONTROL

THE SUPPLY FAN SHALL RUN AT CONSTANT SPEED PROVIDING CONSTANT AIR FLOW.

4. HUMIDITY CONTROL

WHEN THE DCP IS NOT CALLING FOR HUMIDIFICATION SENSED BY HUMIDISTAT H-1, TWO-WAY “ON-OFF” CONTROL VALVE V-3 SHALL REMAIN CLOSED.

WHEN THE DCP IS CALLING FOR HUMIDIFICATION, V-3 SHALL OPEN.

RETURN AIR HUMIDITIY SHALL BE MAINTAINED AT SETPOINT SENSED BY H-1 VIA DCP BY MODULATING CONTROL VALVE V-4 TO MAINTAIN THE DESIRED

HUMIDITY. THE DCP SHALL OVERRIDE THE CONTROL TO MAINTAIN HUMIDITY IN SUPPLY DUCT BELOW 80% AS SENSED BY H-2. DCP SHALL CLOSE

VALVE V-3 WHENEVER THE SUPPLY FAN IS OFF. VALVE V-4 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH; (FIELD VERIFY INTERLOCK) TO

KEEP THE HUMIDIFIER OFF UNTIL CONDENSATE TEMPERATURE APPROACHES STEAM TEMPERATURE.

5. FREEZE PROTECTION

IF THE AIR TEMPERATURE SENSED BY T-2 FALLS BELOW 45°F AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS

BELOW 40°F THE SUPPLY FAN SHALL SHUT DOWN, THE DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL INDICATE AT THE DCP AND BMS.

6. EMERGENCY SHUTDOWN/RESTART

WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY FAN STOPS AND THE ALARM SIGNAL IS TRANSMITTED TO THE

FIRE ALARM SYSTEM, DAMPERS D-1 AND D-2 SHALL CLOSE. SUPPLY AND RETURN FANS SHALL RESTART AND THE DAMPERS OPEN WHEN THE FIRE

ALARM CIRCUIT IS MANUALLY RESET.

AS-BUILT REV. NEW DRAWING / TYPICAL2 12/3/13 BM

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 7/19/11

SUB. REVISION TAGS/NOTES1 12/13/11 VD

C-3A

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS

UPGRADE - PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

AIR HANDLING UNIT CONTROL-

A/C-1 (MER 8TH FLOOR WEST)

Project Title

AIR HANDLING UNIT CONTROL - A/C-1 (MER 8TH FLOOR WEST)

OAH

OAT

LOCAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SENSOR

MOUNTED OUTSIDE OF

MER 8TH WEST

110v (EXISTING)

*EXISTING EX. CP

(A/C-1)

8TH FLOOR MECH.

EQUIPMENT RM. -

(MER 8TH FLOOR WEST)

SUPPLY

AIROUTDOOR

UI-1

DA-TPH

C

LPS

RH

C

AO-9

C

C

CWS

CWR

*SEE NOTES

CO-6

V-3

N.C.

*SEE NOTES

STEAM

PRE-HEAT

STEAM

RE-HEAT

V-1

COND.

LPS

CO-5

*SEE NOTES

V-2B

CO-4

V-2A

COND.

N.O. NOTE(S):

BILL OF MATERIALS

Designation Qty Part Number Description

OAT 1 TE-6313P-1 SENSOR,T-NI,0.1%,OUTSIDE,TEMP.

OAH 1 HO20K SENSOR,%RH,OUTSIDE HUMID.,KELE

DCP 1 DCP-1.5-W 1.5AMP POWER SUPPLY

DA 1 M9220-BGC-3 ACT.,24VAC,SPR.RTN.,189#IN,2-AUX.,W/E.S.

X-TH 3 HE-67N3-0N00P DUCT COMBO SENSOR,T-NI & %RH

DA-H 3 TE-6316P-1 SENSOR,T-NI,0.1%,16FT AVG.,

LL 1 A70GA-1C LOW LIMIT,AUTO RESET,20FT ELEM.

SPS 1 PXPXX02S DUCT STATIC PRESS.,0-10”W.C.,ADJ.,0-10V,SETRA

FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET

IOM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET

V-X SEE VALVE SCHEDULE FOR MORE INFORMATION

*BO-1

S/S

N.O.

N.O.

UI-4

CC-T

IOM-47 (EXP. ADD.#4)

IOM-47 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

POINT NAME/DESCRIPTION

SUPPLY HUMIDITIY HIGH LIMIT (DA-HL)

PRE FILTER STATUS (DP-1)

SUPPLY AIR DUCT STATIC PRESSURE (SPS)

FINAL FILTER STATUS (DP-2)

OUTSIDE AIR TEMPERATURE (OA-T)

OUTSIDE AIR HUMIDITY (OA-H)

FEC-26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

DISCHARGE AIR TEMPERATURE (DA-T)

REHEAT COIL LEAVING AIR TEMP. (RH-T)

SUPPLY FAN STATUS (DPS)

ZONE HUMIDITY SENSOR (SHT)

*DISCHARGE AIR HUMIDITY (DA-H)

FREEZE STAT / SHUTDOWN (LL)

HUMIDIFIER VALVE COMMAND (EV-5)

RE-HEAT VALVE COMMAND (V-1)

PRE-HEAT COIL LEAVING AIR TEMP. (PH-T)

COOLING COIL LEAVING AIR TEMP. (CC-T)

SUPPLY FAN S/S (SIGNAL THRU. ‘D-1’ END SWITCH)

COOLING VALVE COMMAND (V-3)

LOWER PRE-HEAT VALVE COMMAND (V-2B)

UPPER PRE-HEAT VALVE COMMAND (V-2A)

*SUPPLY FAN VFD COMMAND

HUMIDIFIER ISOLATION VALVE (EV-4)

H L

SPS-1

UI-6

DA-HL

*SEE NOTES

HUMIDIFIER

LPS

HUMIDIFIER CONTROL

HUMID.

*SEE NOTES

COND.

AO-8

EV-4

BO-3

EV-3

UI-3

PH-T

BI-8

LL

UI-2

RH-T

PRE

FILTER

(EXISTING DP)

FINAL

FILTER

(EXISTING DP)

SHT

SPACE

HUMIDITY

SENSOR

VFD

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

CO-7 CMD.

*UI-6

EXISTING SPACE HUMIDITY CONTROL

(LOCATED IN 7TH FLOOR CORRIDOR)

BI-7

*IOM *IOM

H

DA-H

UI-4

*IOM

UI-3

*IOM

AS-BUILT REV. FINAL REVISIONS2 12/3/13 BM

FEC-26 (ADD.#33)

*SF S/S SIGNAL (BO-1) IS

HARD-WIRED THROUGH

DA ‘D-1’ END SWITCH

DA

(D-1)*BO-1

*SF S/S SIGNAL (BO-1) IS

HARD-WIRED THROUGH

DA ‘D-1’ END SWITCH

DP-2

BI-8

H

SMR

*HARD WIRED

ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY

EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-

USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC

CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON

DDC CONTROLLERS AS INDICATED. *REFER TO C-3B FOR CONTROLLER WIRING DETAILS

AND DRAWING C-3C FOR ASSOCIATED SEQUENCE OF OPERATIONS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND

INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE

‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING

M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR

ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS

WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL

PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 7/19/11

AS-BUILT REV. TAGS/NOTES1 12/3/13 BM

C-3B

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS

UPGRADE - PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

CONTROLLER WIRING

DETAILS - A/C-1

(MER 8TH FLOOR WEST)

Project Title

CONTROLLER WIRING DETAILS - A/C-1 (MER 8TH FLOOR WEST)

SEE AS-BUILT CONTROL DRAWINGS C-3A AND C-3C FOR

ASSOCIATED UNIT CONTROL DIAGRAM AND SEQUENCE OF

OPERATIONS.

NOTE(S):

124816326412

O N

Address:

S A

PW

R

C O

M

SA BUS

FC BUS

C O

M S

H

LD+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

IN

IC

O M

IN

IC

O M

UNIVERSAL BINARY

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

FEC2611

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

124816326412

O N

Address:

SA

FC

H O

T

24V

C O

M

IOM4711

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

S A

P W

R

C O

M

+ - C

O M

S H

LD

SA/FC BUS

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

D

IS

C H

A R

G E

A

IR

T

EM

PE

R

A

TU

R E

(D A

-T

H U

M

ID

IF

IE

R V

A

LV

E C

O M

M A

N D

(E V-

5)

R

EH

EA

T

VA

LV

E C

O M

M A

N D

(V -1

SU

PP

LY

F

A N

S /S

(S

IN

G A

L

TH

R U

D

-1 ’ E

N D

S W

IT

C

H

C O

O

LI

N G

V A

LV

E

C O

M M

A N

D (V

-3

LO

W

ER

P

R

EH

EA

T

VA

LV

E C

O M

M A

N D

(V -2

B

U

PP

ER

P

R

EH

EA

T

VA

LV

E C

O M

M A

N D

(V -2

A

SU

PP

LY

F

A N

V

FD

C O

M M

A N

D

H U

M

ID

IF

IE

R

IS

O

LA

TI

O

N V

A

LV

E (E

V- 4)

R

EH

EA

T

C O

IL

L

EA

VI

N G

A

IR

T

EM

PE

R

A

TU

R E

(R H

-T

PR

EH

EA

T

C O

IL

L

EA

VI

N G

A

IR

T

EM

PE

R

A

TU

R E

(P H

-T

C O

O

LI

N G

C O

IL

L

EA

VI

N G

A

IR

T

EM

PE

R

A

TU

R E

(C C

-T

ZO

N

E H

U M

ID

IT

Y

SE

N

SO

R (S

H T)

D

IS

C H

A R

G E

A

IR

H U

M

ID

IT

Y

(D A

-H

SU

PP

LY

F

A N

S

TA

TU

S

(D

PS

FR

EE

ZE

S

TA

T

/ S H

U

TD

O W

N (L

L)

O U

TS

ID

E A

IR

T

EM

PE

R A

TU

R

E (O

A -T

O U

TS

ID

E A

IR

H

U M

ID

IT

Y (O

A -H

PR

E

FI

LT

ER

S

TA

TU

S (D

P- 1)

SU

PP

LY

D

U C

T

ST

A

TI

C P

R

ES

SU

R

E (S

PS

SU

PP

LY

H

U M

ID

IT

Y H

IG

H

L

IM

IT

(D

A -H

L)

FI

N

A L

FI

LT

ER

S

TA

TU

S (D

P- 2)

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 7/19/11

C-3C

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

SEQUENCE OF OPERATIONS -

A/C-1 (MER 8TH FLOOR WEST)

Project Title

A/C-1 (MER 8TH FLOOR WEST)

1. GENERAL

UNIT IS NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. H-O-A SWITCH SHALL BE KEPT IN THE “AUTO” POSITION. “HAND” AND “OFF” POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. WHEN THE UNIT IS “OFF” D-1 SHALL BE CLOSED. WHEN THE UNIT IS “ON” D-1 SHALL BE

FULLY OPENED.

2. TEMPERATURE CONTROL

HEATING MODE:

TEMPERATURE SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING V-4 AND V-5 IN SEQUENCE. V-1, V-2, V-3 AND V-4 SHALL

BE CLOSED.

COOLING MODE:

TEMPERATURE SENSED BY T-2 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING V-3. TEMPERATURE SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING V-1 AND V-2 IN SEQUENCE. V-4 AND V-5 SHALL BE CLOSED.

3. AIR FLOW CONTROL

THE SUPPLY FAN SHALL RUN AT CONSTANT SPEED PROVIDING CONSTANT AIR FLOW.

4. FREEZE PROTECTION

IF THE AIR TEMPERATURE SENSED BY T-2 FALLS BELOW 45°F AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS BELOW 40°F THE SUPPLY FAN SHALL SHUT DOWN, THE DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL INDICATE AT THE DCP AND BMS.

5. EMERGENCY SHUTDOWN/RESTART

WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY FAN SHALL STOP, DAMPER D-1 SHALL CLOSE AND AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM. THE SUPPLY FAN SHALL RESTART AND THE DAMPER SHALL OPEN WHEN THE FIRE

ALARM CIRCUIT IS MANUALLY RESET.

SEQUENCE OF OPERATIONS - A/C-1 (MER 8TH FLOOR WEST)

AS-BUILT REV. REVISE SEQ.1 BM12/3/13

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 7/19/11

SUB. REVISION TAGS/NOTES 1 12/13/11 VD

C-4A

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

AIR HANDLING UNIT CONTROL

– AHU-7 (MER 8TH FLOOR EAST)

Project Title

AIR HANDLING UNIT CONTROL – AHU-7 (MER 8TH FLOOR EAST)

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

H L

SPS-1

UI-6

SAFM

*SEE DETAIL

& NOTES

HUMIDIFIER

UI-1UI-1

DA-T

110v (EXISTING)

*EXISTING EX. CP

8TH FLOOR MECH.

EQUIPMENT RM. -

(MER 8TH FLOOR EAST)

CT

BI-7

EXHAUST FAN CONTROL; EF-21

*SEE NOTES BO-1

AS-BUILT REV. DWG. REVS / POINT TERM.2 12/3/13 BM

FEC-26

IOM-47-1,2 (TYP. OF 2)

IOM-47-2 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

POINT NAME/DESCRIPTION

DISCHARGE AIR FLOW STATION MONITOR (SAFM)

RETURN AIR FLOW STATION MONITOR (RAFM)

RETURN AIR FAN STATUS (DPS)

PRE FILTER DIFFERENTIAL PRESSURE (DP)

PRE HEAT COIL PUMP STATUS (CT)

FEC-26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

DISCHARGE AIR TEMPERATURE (DA-T)

MIXED AIR TEMPERATURE (MA-T)

SUPPLY FAN STATUS (DPS)

RETURN AIR HUMIDITY (RA-H)

DISCHARGE AIR DUCT STATIC PRESSURE (SPS)

LOW LIMIT SHUTDOWN (LL)

SUPPLY FAN VFD COMMAND

RETURN FAN VFD COMMAND

PRE HEAT COIL DISCHARGE TEMPERATURE (PH-T)

RETURN AIR TEMPERATURE (RA-T)

SUPPLY FAN VFD START/STOP

CHILLED WATER VALVE COMMAND (V-1)

PRE HEAT COIL PUMP START/STOP

PRE HEAT COIL VALVE COMMAND (V-2)

ECONOMIZER DAMPER COMMAND (D1~D3)

RETURN FAN VFD START/STOP

HUMIDIFIER ISOLATION VALVE (V-3)

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

HUMIDIFIER CONTROL VALVE COMMAND

IOM-47-1 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

POINT NAME/DESCRIPTION

SUPPLY AIR DUCT HIGH PRESSURE (SP-HL)

SUPPLY FAN VFD ALARM

EXHAUST FAN EF-21 STATUS (CT)

DISCHARGE AIR HUMIDITY SENSOR (DA-H)

DISCHARGE AIR SMOKE DETECTOR

RETURN AIR SMOKE DETECTOR (SMK)

RETURN FAN VFD ALARM

EXHAUST FAN EF-21 SPACE TEMPERATURE (ST)

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

EXHAUST FAN EF-21 START/STOP (R)

SUPPLY AIR

TO VAV’SOUTDOOR

UI-5BI-7

HUMIDIFIER CONTROL

RF

BO-2

RAO-9

VSMC

AIR

UI-4

RA-T

H

RA-H

UI-5

RAFM

UI-2

LPS

HUMID.

*SEE NOTES

COND.

AO-8BO-3

V-4V-3

LL

BI-8

H

DA-H

*IOM-47-2

L

H

SP-HL

HI-LIMIT

UI-1

*IOM-47-1

UI-3

*IOM-47-1

*IOM-47-2

RELIEF

D-3

D-1

D-2

DP

N.C.

N.O.CO-7

CO-7

UI-6

*IOM-47-2

RAO-8

VSMC

UI-2

*IOM-47-1

*CO-7

MA-T

UI-2

HWS

HWR

*SEE NOTES

H

C

C

C

CWS

CWR

V-2 V-1

CO-4

UI-3

PH-T

CO-6CO-5

*IOM-47-2

*IOM-47-1

*IOM-47-1*IOM-47-1

*IOM-47-1

HUMID.

HIGH LIMIT

BILL OF MATERIALS

Designation Qty Part Number Description

RA-T,MA-T 2 TE-6315P-1 SENSOR,T-NI,0.1%,8FT AVG.,

LL 1 A70HA-1C STAT.,LOW LIMIT,20FT ELEM.,MAN. RESET

FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET

IOM-1 2 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET

V-X SEE VALVE SCHEDULE FOR MORE INFORMATION

*IOM-47-1

*IOM-47-1

*IOM-47-1

NOTE(S): ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY

EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-

USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC

CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON

DDC CONTROLLERS AS INDICATED. *REFER TO C-4B FOR CONTROLLER WIRING DETAILS,

C-4C FOR ASSOCIATED VAV BOXES AND DRAWING C-4D FOR ASSOCIATED SEQUENCE OF

OPERATIONS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND

INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE

‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING

M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR

ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS

WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL

PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS

HAVE BEEN APPROVED BY THE VA HOSPITAL.

*SEE NOTES (TYP.)

ST

SPACE

TEMPERATURE

SENSOR

(EXISTING)

UI-4

*IOM-47-1

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

C-4B

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

Project Title

CONTROLLER WIRING DETAIL

– AHU-7

(MER 8TH FLOOR EAST)

CONTROLLER WIRING DETAIL – AHU-7 (MER 8TH FLOOR EAST)

SEE AS-BUILT CONTROL DRAWINGS C-4A, C-4C AND C-4D FOR

ASSOCIATED UNIT CONTROL DIAGRAM, VAV DIAGRAM AND

SEQUENCE OF OPERATIONS.

NOTE(S):

124816326412

O N

Address:

S A

PW

R

C O

M

SA BUS

FC BUS

C O

M S

H

LD+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

IN

IC

O M

IN

IC

O M

UNIVERSAL BINARY

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

FEC2611

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

124816326412

O N

Address:

SA

FC

H O

T

24V

C O

M

IOM4711-2

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

S A

P W

R

C O

M

+ - C

O M

S H

LD

SA/FC BUS

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

D

IS

C H

A R

G E

A

IR

T

EM

PE

R

A

TU

R E

(D A

-T

SU

PP

LY

F

A N

V

FD

C O

M M

A N

D

R

ET

U R

N F

A N

V

FD

C O

M M

A N

D

SU

PP

LY

F

A N

V

FD

S

TA

R T/

ST

O

P

C H

IL

LL

ED

W

A

TE

R C

O

IL

V A

LV

E

C M

D

V- 1)

PR

E

H

EA

T C

O

IL

P U

M P

ST

A

R T/

ST

O

P

PR

E

H

EA

T C

O

IL

V A

LV

E

C M

D

V- 2)

EC

O

N O

M

IZ

ER

D

A M

PE

R

C O

M M

A N

D (D

1~ D

3)

R

ET

U R

N F

A N

V

FD

S

TA

R T/

ST

O

P

H U

M

ID

IF

IE

R

IS

O

LA

TI

O

N V

A

LV

E C

M D

V-

3)

H U

M

ID

IF

IE

R C

O N

TR

O

L

VA

LV

E

C M

D

V- 4)

M

IX

ED

A

IR

T

EM

PE

R A

TU

R

E (M

A -T

PR

E

H

EA

T C

O

IL

D

IS

C H

A R

G E

TE

M

P.

(P

H -T

R

ET

U R

N A

IR

T

EM

PE

R A

TU

R

E (R

A -T

R

ET

U R

N A

IR

H

U M

ID

IT

Y (R

A -H

D

IS

C H

A R

G E

A

IR

D U

C T

ST

A

TI

C

P R

ES

SU

R E

(S

PS

SU

PP

LY

F

A N

S

TA

TU

S

(D

PS

LO

W

L

IM

IT

S

H U

TD

O

W N

(L L)

SU

PP

LY

A

IR

F

LO

W

S

TA

TI

O

N M

O N

IT

O

R (S

A

FM

R

ET

U R

N A

IR

F

LO

W

S

TA

TI

O

N M

O N

IT

O

R (R

A

FM

R

ET

U R

N A

IR

F

A N

S

TA

TU

S

(D

PS

PR

E

FI

LT

ER

D

IF

F.

P R

ES

SU

R E

(D P)

PR

E

H

EA

T C

O

IL

P U

M P

ST

A

TU

S

(C T)

AS-BUILT REV. TAGS/NOTES & POINT TERM.1 12/3/13 BM

124816326412

O N

Address:

SA

FC

H O

T

24V

C O

M

IOM4711-1

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

S A

P W

R

C O

M

+ - C

O M

S H

LD

SA/FC BUS

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

EX

H

A U

ST

F

A N

E F-

S

TA

R

T/

ST

O P

(R

SU

PP

LY

A

IR

D

U C

T H

IG

H

P R

ES

SU

R E

(S P-

H L)

SU

PP

Y

FA

N V

FD

A

LA

M

ET

U R

N F

A N

V

FD

A

LA

R M

EX

H

A U

ST

F

A N

E F-

S

PA

C

E

TE

M

PE

R A

TU

R

E (S

T)

D

IS

C H

A R

G E

A

IR

H U

M

ID

IT

Y

SE

N

SO

R

(D A

-H

D

IS

C H

A R

A G

E A

IR

S

M O

K E

D

ET

EC

TO

R

EX

H

A U

ST

F

A N

E F-

S

TA

TU

S (C

T)

R

ET

U R

N A

IR

S

M O

K E

D

ET

EC

TO

R (S

M K

VMA-16

(SEE NOTES)

MOUNT DIRECTLY TO

DAMPER ACTUATOR SHAFT

WITH THE DAMPER IN THE

"OPEN" POSITION.

CONNECT TO VAV BOX

VELOCITY PROBES

24V FROM NEW XFMR(S) MOUNTED IN

THE AHU-7 CONTROL PANEL

*EXISTING

TRANSFORMER

211-1009

IW/BMIW/JAIW

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

C-4C

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

VAV BOX CONTROLS FOR 7TH

FLOOR EAST; SERVED BY AHU-7

(TYP. OF 36)

Project Title

VAV BOX CONTROL FOR 7TH FLOOR EAST - SERVED BY AHU-7

(TYP. OF 36)

BILL OF MATERIALS

Designation Qty Part Number Description Field Devices:

STT-1 36 NS-BTP7002-0 SENSOR,TEMP.,W/C,NETWORK,WALL MNT.

TE-1 36 TE-6311M-1 SENSOR,TEMP.8IN,DUCT MNT.,

VMA-1 36 MS-VMA1620-0 VAV MODULAR ASSY.,CLG W/ REHEAT,MS/TP

HWV SEE VALVE SCHEDULE

SEQUENCE OF OPERATIONS

VAV SYSTEM CONTROL:

COOLING MODE:

On a rise in space temperature above the space temperature cooling set point, the damper will modulate from the minimum CFM set point to the maximum CFM set point. As the space temperature drops, the damper will modulate to the minimum CFM set point.

HEATING MODE:

On a drop in space temperature below the heating space temperature set point, the damper will modulate to the minimum heating CFM set point. On a further drop in space temperature below the space temperature set point, the heating coil valve will modulate to maintain the heating space temperature to it’s set point. As the temperature rises the reverse will occur.

*SEE NOTES

VELOCITY PROBES

*SEE NOTES

TEMP. / ADJ.

STT-1

SPACE TEMP.

SENSOR W/ OVERRIDE

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

TO VMA

TE-1

H

C

HWR

HWV

HWS

TO VMA

NOTE(S):

AS-BUILT REV. FINAL POINT TERM./NOTE1 12/3/13 BM

TYPICAL CONSTRUCTION NOTES

THE NEW MODULATING ELECTRONIC CONTROL VALVES SHALL BE

PROVIDED BY MODERN CONTROLS AND INTEGRATED TO THE NEW

DDC CONTROLLERS. FIELD INSTALLATION SHALL BE PROVIDED BY

THE PROJECT GENERAL CONTRACTOR. SEE VALVE SCHEDULE FOR

MORE INFORMATION.

AIR FLOW SCHEDULE PROVIDED BY THE VA FOR REFERENCE ONLY;

SEE AS-BUILT DOCUMENTATION FOR MORE INFO.

FREEZE PROTECTION AND SUPPLY AIR TEMPERATURE MONITORING

PROVIDED BY ASSOCIATED AHU CONTROLS.

NEW PANEL MOUNTED TRANSFORMER(S) SHALL PROVIDE 24V

POWER TO NEW VAV CONTROLLERS AS REQUIRED IN THE FIELD.

ALL CONTROL POINT DESCRIPTIONS AND TERMINAL DESIGNATION

SHALL BE RECORDED IN THE FIELD FOR AS-BUILT DOCUMENTATION.

AS-BUILT NOTE

OUR O&M MANUAL PROVIDED FOR PROJECT CLOSEOUT

INCLUDEDS ALL COMMISSION AND CHECKOUT INFORMATON

FOR ALL VAV BOXES.

THE O&M MANUAL INCLUDES A TYPCIAL VAV CONTROLLER

COMMISSIONING SHEET AND ALSO A COMPLETE VAV BOX

COMMISSIONG CHECK LIST FOR ALL VAV BOXES AS SERVED

BY THEIR ASSOCIATED UNIT.

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 7/19/11

SUB. REVISION EDIT SEQUENCE1 12/13/11 VD

C-4D

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

SEQUENCE OF OPERATIONS -

AHU-7 (MER 8TH FLOOR EAST)

Project Title

SEQUENCE OF OPERATIONS - AHU-7 (MER 8TH FLOOR EAST)

AHU-7 (MER 8TH FL EAST)

1. GENERAL

SUPPLY AND RETURN FANS ARE NORMALLY STARTED AND STOPPED BY THE DCP OR REMOTELY AT THE BMS. H-O-A SWITCH SHALL BE KEPT IN THE “AUTO” POSITION. “HAND” AND “OFF” POSITIONS SHALL BE USED FOR MAINTENANCE ONLY. WHEN THE UNIT IS “OFF” D-1, D-2 AND D-3 SHALL BE CLOSED. WHEN THE UNIT IS

“ON” D-1, D-2 AND D-3 SHALL BE OPENED.

2. TEMPERATURE CONTROL

SUPPLY AIR TEMPERATURE SENSED BY T-1 SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING EITHER V-1 AND V02 OR D-1, D-2 AND D-3 IN SEQUENCE.

WHEN THE TEMPERATURE OF THE OUTSIDE AIR PROVIDED BY BMS IS ABOVE 65°F DCP PREVENTS MODULATION OF D-1 AND D-2; D-1 ASSUMES MINIMUM OUTSIDE AIR POSITION AND D-2 IS OPENED. V-1 MODULATES TO MAINTAIN SUPPLY AIR TEMPERATURE SENSED BY T-1.

WHEN THE TEMPERATURE OF THE OUTSIDE AIR PROVIDED BY BMS IS BETWEEN 65°F AND THE SUPPLY AIR TEMPERATURE SENSED BY T-1, DAMPER D-2 IS CLOSED AND DAMPER D-1 IS OPENED TO MAXIMUM OUTSIDE AIR POSITION. V-1 MODULATES OPEN TO MAINTAIN THE SUPPLY AIR TEMPERATURE.

3. AIR FLOW CONTROL

THE SUPPLY AIR FLOW IS CONTROLLED BY THE DCP MODULATING SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER (VSMC) TO MAINTAIN THE DUCT STATIC

PRESSURE SETPOINT AS SENSED BY SPS-1.

THE DCP BY USING TOTAL SUPPLY AIR AND RETURN AIR FLOW SIGNALS SHALL RESET THE RETURN AIR FAN VSMC TO MAINTAIN A CONSTANT CFM DIFFERENCE

BETWEEN THE SUPPLY AIR FAN CFM AND THE RETURN AIR FAN CFM.

THE DCP USING HIGH STATIC PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3” OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT SPS-2 EXCEEDS 3” THE SUPPLY AND RETURN FANS SHALL STOP AND THE ALARM SIGNAL

SHALL INDICATE ON DCP AND BMS.

4. HUMIDITY CONTROL

WHEN THE DCP IS NOT CALLING FOR HUMIDIFICATION SENSED BY RETURN AIR HUMIDISTAT H-1, TWO-WAY “ON-OFF” CONTROL VALVE V-3 SHALL REMAIN CLOSED.

WHEN THE DCP IS CALLING FOR HUMIDIFICATION, V-3 SHALL OPEN.

RETURN AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT VIA DCP BY MODULATING CONTROL VALVE V-4 TO MAINTAIN THE DESIRED HUMMIDITY. THE DCP SHALL OVERRIDE THE CONTROL TO MAINTAIN HUMIDITY IN SUPPLY DUCT BELOW 80% AS SENSED BY H-2.

DCP SHALL CLOSE VALVE V-3 WHENEVER THE SUPPY FAN IS OFF.

VALVE V-4 SHALL BE INTERLOCKED WITH A TEMPERATURE SWITCH (FIELD VERIFY INTERLOCK) TO KEEP THE HUMIDIFIER OFF UNTIL CONDENSATE TEMPERATURE

APPROACHES STEAM TEMPERATURE.

5. FREEZE PROTECTION

IF THE AIR TEMPERATURE SENSED BY T-3 FALLS BELOW 45°F AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND BMS. IF THIS TEMPERATURE FALLS BELOW 40°F THE SUPPLY AND RETURN FANS SHALL SHUT DOWN, DAMPER D-1 SHALL CLOSE AND A CRITICAL ALARM SHALL INDICATE AT THE DCP AND BMS.

6. EMERGENCY SHUTDOWN/RESTART

WHEN SMOKE IS DETECTED BY THE DUCT MOUNTED SMOKE DETECTOR THE SUPPLY AND RETURN FANS SHALL STOP AND THE ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM. DAMPERS D-1, D-2 AND D-3 SHALL CLOSE. SUPPLY AND RETURN FANS SHALL RESTART AND THE DAMPERS SHALL

OPEN WHEN THE FIRE ALARM CIRCUIT IS MANUALLY RESET.

7. EMERGENCY CONSTANT SPEED OPERATION

UPON FAILURE OF VSMC THE SUPPLY AND RETURN FANS SHALL BE STARTED/STOPPED MANUALLY AT THE DCP OR THE BMS THROUGH THE BYPASS STARTER.

FANS SHALL THEN OPERATE AT CONSTANT SPEED.

AS-BUILT REV. NEW DWG. / ADD NOTE2 12/3/13 BM

NOTE(S): REFER TO DRAWING C-4C FOR ASSOCIATED VAV BOX

SEQUENCE OF OPERATIONS AND AIR FLOW SCHEDULE.

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

BM 7/19/11

SUB. REVISION TAGS/NOTES1 12/13/11 VD

C-5A

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

AIR HANDLING UNIT CONTROL –

AHU FOR ELEVATOR

(9TH FLOOR LOBBY)

Project Title

AIR HANDLING UNIT CONTROL – AHU for ELEVATOR (9TH FLOOR LOBBY)

OAH

OAT

LOCAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

SUPPLY

AIROUTDOOR

AIR

RELIEF

UI-4

MA-T

UI-3

*SEE NOTES (TYP)

D-3

D-1

D-2

C

DI

*SEE NOTES (TYP.)

*SEE NOTES

UI-4

RA-TH

RA-H

RF

AO-9

V-1

DP

UI-2

N.C.

N.C.

N.O. UI-2

DA-T

110v (EXISTING)

*EXISTING EX. CP

9TH FLOOR MECH.

EQUIPMENT RM. - MER

CT

*SEE NOTES

1 2

AS-BUILT REV. POINT TERM./COMM.2 12/3/13 BM

BILL OF MATERIALS

Designation Qty Part Number Description

LL 1 A70GA-1C LOW LIMIT,AUTO RESET,20FT ELEM.

FEC-1 1 MS-FEC2611-0 CNTRLR,DIG,FEC,6UI,2BI,3BO,2AO,4CO,BACNET

IOM-1 1 MS-IOM4711-0 FEC EXPANSION,6UI,2BI,3BO,2AO,4CO,BACNET

LL-1

IOM-47 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

POINT NAME/DESCRIPTION

OUTSIDE AIR HUMIDITY (OAH)

FILTER DIFFERENTIAL PRESSURE (DP)

EXHAUST FAN EF-1 STATUS (CT)

LOW LIMIT SHUTDOWN (LL)

CHILLED WATER COIL PUMP STATUS

EXHAUST FAN EF-2 STATUS (CT)

DISCHARGE AIR SMOKE DETECTOR

FEC-26 POINT IDENTIFICATION

POINT #

UI-1

UI-2

UI-3

UI-4

UI-5

UI-6

BI-7

BI-8

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

POINT NAME/DESCRIPTION

SPACE TEMPERATURE SENSOR (ST)

DISCHARGE AIR TEMPERATURE (DA-T)

SUPPLY FAN STATUS (DPS)

RETURN AIR HUMIDITY (RA-H)

OUTSIDE AIR TEMPERATURE (OAT)

RETURN FAN STATUS (DPS)

ECONOMIZER DAMPER COMMMAND (D1~D3)

CHILLED WATER COIL VALVE CONTROL (V-1)

MIXED AIR TEMPERATURE (MA-T)

RETURN AIR TEMPERATURE (RA-T)

SUPPLY FAN START/STOP

DX COOLING STAGE 2 COMMAND

CHILLED WATER COIL PUMP S/S

RETURN FAN START/STOP

DX COOLING STAGE 1 COMMAND

AO-8

AO-9

BO-1

BO-2

BO-3

CO-4

CO-5

CO-6

CO-7

FEC-26

IOM-47

CT

D

X

BI-7 BI-8

*IOM

EXISTING EXHAUST FAN CONTROL; EF-1 & EF-2

EF-1 EF-2

R CT

R CT

STAGE 1 STAGE 2

BO-3 CO-4

BI-4BI-3

CU-1

*AO-8

*AO-8

*AO-8

R BO-1

R BO-2

UI-1

*IOM

NOTE(S): ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY

EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-

USED AND WIRED TO NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC

CONTROL DEVICES HAVE BEEN PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON

DDC CONTROLLERS AS INDICATED. CONTROLLERS SHALL BE PROGRAMMED TO MATCH

EXISTING SEQUENCE OF OPERATIONS FOR ANY EQUIPMENT WITHOUT A SEQUENCE OF

OPERATION PROVIDED WITHIN THE CONTRACT DOCUMENTS. *REFER TO C-5B FOR

CONTROLLER WIRING DETAILS.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND

INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE

‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING

M-1 OF THE CONTRACT DOCUMENTS. PLEASE REFER TO VALVE SCHEDULE ‘V-1" FOR

ADDITIONAL INFORMATION.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING

DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS

WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL

PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS

HAVE BEEN APPROVED BY THE VA HOSPITAL.

ST

SPACE

TEMPERATURE

SENSOR

(EXISTING)

CO-5

*IOM*IOM

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

C-5B

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS UPGRADE -

PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

Project Title

CONTROLLER WIRING DETAIL

– AHU for ELEVATOR

(9TH FLOOR LOBBY)

CONTROLLER WIRING DETAIL – AHU for ELEVATOR (9TH FLOOR LOBBY)

SEE AS-BUILT CONTROL DRAWING C-5A FOR ASSOCIATED UNIT

CONTROL DIAGRAM AND UNIT SPECIFIC NOTES.

NOTE(S):

124816326412

O N

Address:

S A

PW

R

C O

M

SA BUS

FC BUS

C O

M S

H

LD+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

+1

5V

IN

IC

O M

IN

IC

O M

IN

IC

O M

IN

IC

O M

UNIVERSAL BINARY

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

H O

T

24V

C O

M

FEC2611

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

124816326412

O N

Address:

SA

FC

H O

T

24V

C O

M

IOM4711

FC EOL

IN

TRIAC JUMPERS

OUT1 INT

EXT

OUT2 OUT3

S A

P W

R

C O

M

+ - C

O M

S H

LD

SA/FC BUS

BINARY

O U

T4 O

C O

M

O U

T5 O

C O

M

O U

T6 O

C O

M

O U

T7 O

C O

M

O U

T8 O

C O

M

O U

T9 O

C O

M

CONFIGURABLE ANALOG

O U

T1 O

C O

M

O U

T2 O

C O

M

O U

T3 O

C O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

+1 5V

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

IN

IC

O

M

UNIVERSAL BINARY

SP

A

C E

TE

M

PE

R

A

TU

R E

SE

N

SO

R

(S T)

EC

O

N O

M

IZ

ER

D

A M

PE

R

C O

M M

A N

D (D

1~ D

3)

C H

IL

LE

D W

A

TE

R C

O

IL

V A

LV

E

C O

N

TR

O L

(V -1

SU

PP

LY

F

A N

S

TA

R T/

ST

O

P

D X

C O

O

LI

N G

S

TA

G E

C

O M

M A

N D

R

ET

U R

N F

A N

S

TA

R T/

ST

O

P

D X

C O

O

LI

N G

S

TA

G E

C

O M

M A

N D

D

IS

C H

A R

G E

A

IR

T

EM

PE

R

A

TU

R E

(D A

-T

M

IX

ED

A

IR

T

EM

PE

R A

TU

R

E (M

A -T

R

ET

U R

N A

IR

T

EM

PE

R A

TU

R

E (R

A -T

R

ET

U R

N A

IR

H

U M

ID

IT

Y

SE

N

SO

R (R

A -H

O U

TS

ID

E A

IR

T

EM

PE

R A

TU

R

E (O

A -T

SU

PP

LY

F

A N

S

TA

TU

S

(D

PS

R

ET

U R

N F

A N

S

TA

TU

S

(D

PS

O U

TS

ID

E A

IR

H

U M

ID

IT

Y (O

A -H

FI

LT

ER

D

IF

FE

R

EN

TI

A

L

PR

ES

SU

R E

(D P)

D

IS

C H

A R

G E

A

IR

S M

O K

E D

ET

EC

TO

R

LO

W

L

IM

IT

S

H U

TD

O

W N

(L L)

C H

IL

LL

ED

W

A

TE

R C

O

IL

P U

M P

ST

A

TU

S

EX

H

A U

ST

F

A N

E F-

ST

A

TU

S (C

T)

EX

H

A U

ST

F

A N

E F-

ST

A

TU

S (C

T)

AS-BUILT REV. NEW DWG. / POINT TERM.1 12/3/13 BM

C H

IL

LE

D W

A

TE

R C

O

IL

P U

M P

ST

A

R T/

ST

O

P

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

C-6A

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

VA HVAC CONTROLS

UPGRADE - PHASE 2B

WILMINGTON, DELAWARE

Drawing Title

TYPICAL HEAT EXCHANGER

CONTROL – MAIN BUILDING

Project Title

TYPICAL HEAT EXCHANGER CONTROL – MAIN BUILDING

(INCLUDES HEAT EXCHANGERS – C5, C6, C7 & C8)

OAH

OAT

GLOBAL OUTSIDE AIR

TEMPERATURE AND

HUMIDITY SIGNAL

110v (EXISTING)

*EXISTING EX. CP

EQUIPMENT RM. - MER

(MAIN HVAC SHOP)

SEQUENCE OF OPERATIONS

BOOSTER HEATER HOT WATER HEATER (PUMP P-X)

1. PUMP P-X STARTS AND STOPS BY BMS BASED ON HOT WATER DEMAND FROM HOT

WATER CONSUMING EQUIPMENT.

2. SENSOR T-1(TE) MODULATES NORMALLY CLOSED VALVES V-1 AND V-2 TO MAINTAIN 180

F SUPPLY WATER TEMPERATURE.

ALL PNEUMATIC CONTROL DEVICES HAVE BEEN REPLACED (WHERE APPLICABLE). ANY EXISTING ELECTRONIC CONTROL DEVICES IN GOOD WORKING CONDITION HAVE BEEN RE-USED AND WIRED TO

NEW JOHNSON DDC CONTROLLERS. ALL OTHER NEW ELECTRONIC CONTROL DEVICES HAVE BEEN

PROVIDED, INSTALLED AND WIRED TO THE NEW JOHNSON DDC CONTROLLERS AS INDICATED.

NEW ELECTRONIC CONTROL VALVES HAVE BEEN PROVIDED BY MODERN CONTROLS AND INSTALLED BY THE GENERAL CONTRACTOR FOR ALL EQUIPMENT AS INDICATED ON THE ‘EXISTING AHU CONTROL DAMPERS AND VALVES REPLACEMENT SCHEDULE’ ON DRAWING M-1 OF THE CONTRACT DOCUMENTS.

PLEAS…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .