VA Hospital - Complete Network Architecture.pdf

PDF 159 KB Posted

Attached to
J059--Direct Digital Control Services Wilmington VAMC
Solicitation number
36C24421Q0145
Issued by

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

7 BELLECOR DRIVE

NEW CASTLE, DE

19720

TEL: 302-325-6800

FAX: 302-325-6808

REFERENCE DRAWING

SUB. REVISION ADD BCU-3; REV. MISC.1 2/16/12 BM

NO. REVISION-LOCATION ECN DATE BY

Sales Engineer Project Manager Application Engineer

BY DATE BY DATE

DRAWN APPROVED

Branch Information CONTRACT NUMBER

DRAWING NUMBER

Drawing Title

Project Title

211-1009

IW/BMIW/JAIW BM 12/30/11

R-1

VA HOSPITAL – COMPLETE

NETWORK ARCHITECTURE

VA HVAC CONTROLS UPGRADE -

WILMINGTON, DELAWARE

VA HOSPITAL – COMPLETE NETWORK ARCHITECTURE

EX. CP

THE NEW DDC SYSTEM SHALL INTEGRATE WITH ALL EXISTING TRANE SUMMIT (BCU) CONTROLLERS AND ALSO HONEYWELL WEB CONTROLLERS VIA BACNET IP AND/OR CAT-5E INTERFACE THROUGH ONE

OF THE TWO NETWORK HUBS AS SHOWN.

THE CONTRACT DOCUMENTS AND SEQUENCE OF OPERATIONS REFER TO ALL EXISTING DDC CONTROL PANELS AS ‘DCP’; AS PART OF PROJECT CLOSE OUT MODERN CONTROLS WILL PROVIDE PERMANENT, PANEL SPECIFIC LABELS FOR ALL NEW & EXISITNG CONTROL PANELS THAT WILL INDICATE THE ASSOCIATED EQUIPMENT SERVED. *ALL PANEL LABELS HAVE BEEN APPROVED BY THE VA HOSPITAL.

NOTES:

110v (EXISTING)

*BACNET TO NEW ‘DCP’s

FOR AHUS’ AND NEW

VAV CONTROLLERS

(ADD.# 5~33)

EX. CP

110v (EXISTING) e

EX. CP

110v

(EXISTING)

OWS WITH

FX FIELD SERVER

LOCATED IN MAIN

HVAC SHOP

VA

HOSPITAL

CAT-5e

*BACNET TO NEW

AHU AND VAV

CONTROLLERS IN

CLC EAST

(ADD.# 4~25)

EX. CP

110v

(EXISTING)

TRUNK #1

(4TH ~ 9TH FLOORS)

16 PORT

HUB

*LON TO

EXISTING

HONEYWELL

CONTROLLERS

CAT-5e

CAT-5e

CAT-5e (BY OTHERS)

AS-BUILT REV. FINAL PANEL / NOTES2 12/20/13 BM

FX-70-1 FX-70-2 FX-70-3 FX-60-1

BILL OF MATERIALS

Desig. Qty Part # Description

FX-70 4 LP-FX7011N-0 FX-70 SUPERVISORY CONTROLLER

FX-60 1 LP-FX6011N-0 FX-60 SUPERVISORY CONTROLLER,

FX-20 1 LP-FX2011N-0 FX-20 SUPERVISORY CONTROLLER,

FXS-1 1 LP-FXWS FX SERVER, UNRESTRICTED, W/ SOFTWARE

OWS 1 HP-VS884UT HP 505B VS884UT DESKTOP,3.1GHZ DUAL,256MB

HUB-1,2 2 SD2016T NA 16-PORT GIGABIT NETWORK SWITCH,HUB

AS-BUILT REV. ADD ALL IP’S / UPDATE CNTRLS 3 1/28/14 BM

*FX-SERVER

IP = 192.168.1.100

*VAMC-ER

IP = 192.168.1.110

*5TH FLOOR EAST

IP = 192.168.1.125

*LON TO

EXISTING

HONEYWELL

CONTROLLERS*VAMC-PHASE 2

IP = 192.168.1.104

*LON TO

EXISTING

HONEYWELL

CONTROLLERS

IDF CLOSET

(SECOND FLOOR)

CAT-5e

EX. CP

110v (EXISTING)

CAT-5e

FX-20-1

*BACNET TO NEW

AHU AND VAV

CONTROLLERS

(ADD.# 4~19)

TRUNK #1

(BACNET MS/TP)

*TRANE INTEGRATION

IP = 192.168.1.142

*BACNET TO NEW ‘DCP’s

FOR AHUS’ AND NEW

VAV CONTROLLERS

(ADD.# 4~34)

TRUNK #2

(GRND. ~ 4TH FLOORS)

*BACNET TO NEW ‘DCP’s

FOR ELEVATOR FAN COILS

(ADD.# 4~11)

TRUNK #3

(3RD ~ 9TH FLOORS)

CAT-5e CAT-5e

*BACNET TO NEW ‘DCP’s

FOR AHUS’ AND NEW

VAV CONTROLLERS

(ADD.# 5~33)

TRUNK #1

(4TH ~ 9TH FLOORS)

*BACNET TO NEW ‘DCP’s

FOR AHUS’ AND NEW

VAV CONTROLLERS

(ADD.# 4~34)

TRUNK #2

(GRND. ~ 4TH FLOORS)

*BACNET TO NEW ‘DCP’s

FOR AHUS’ AND NEW

VAV CONTROLLERS

(ADD.# 4~31)

TRUNK #1

(CLINICAL)

*BACNET TO NEW ‘DCP’s

FOR AHUS’ AND NEW

VAV CONTROLLERS

(ADD.# 4~41)

TRUNK #2

(CLINCAL)

*BACNET TO NEW ‘DCP’s

FOR ELEVATOR FAN COILS

(ADD.# 4~68)

TRUNK #3

(CLINICAL)

*BACNET TO NEW

AHU AND VAV

CONTROLLERS IN

CLC WEST

(ADD.# 4~27)

TRUNK #1

(CLC EAST)

TRUNK #2

(CLC WEST)

16 PORT

HUB

MAIN HVAC SHOP

(GROUND FLOOR)

CLINICAL ADDITION

2ND FLOOR MECH. RM 2147

*FX-70-CLINICAL

IP = 192.168.1.120

4TH FLOOR CENTRAL

MECHANICAL ROOM 40M2

*FX-70-EAST

IP = 192.168.1.141

4TH FLOOR CENTRAL

MECHANICAL ROOM 40M2

*FX-70-WEST

IP = 192.168.1.140

*FX-20-PHARMACY

IP = 192.168.1.103

CLINICAL AREA

MECHANICAL ROOM

MER 128

CAT-5e

BUILDING 17 – CLC AREA

CLC MECHANICAL ROOM

*FX-60-CLC

IP = 192.168.1.105

EXISTING TRANE

TRACER SUMMIT

WORKSTATION

VA

HOSPITAL

IP = UNKNOWN

*LON TO

EXISTING

TRANE

CONTROLLERS

*LON TO

EXISTING

TRANE

CONTROLLERSIP = 192.168.1.192 IP = 192.168.1.193

IP = 192.168.1.191

*LON TO

EXISTING

TRANE

CONTROLLERS

IP = 192.168.1.194

*LON TO

EXISTING

TRANE

CONTROLLERS

IP = 192.168.1.195

*LON TO

EXISTING

TRANE

CONTROLLERS IP = 192.168.1.196

CAT-5e