2024-08-20_Bedford-VAMC-Bldg-6_FireScan.pdf

PDF 101 KB Posted

Attached to
Z2DA--518-22-111 Elevator Replacement Ph. 3 Federal contract opportunity
Solicitation number
36C24125B0003
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1

About this file

This is a fire alarm and life safety system inspection certificate and report for Building 6 of the Bedford VA Medical Center, conducted by Kinetix Fire & Life Safety Experts. The inspection was completed on August 20, 2024, in compliance with The Joint Commission/VHA Standards and NFPA Standards.

The inspection tested 90 total devices, all of which passed testing requirements. The devices included 1 duct detector, 6 heat detectors, 19 pull stations, 11 smoke detectors, 37 speaker/strobes, 6 strobes, 4 door releasing devices, 4 batteries, 1 power supply, and 1 EST EST3 control panel. The system was installed on April 23, 2020, and includes auxiliary functions testing of door holders and AHU shutdown capabilities. The inspection verified proper operation of all initiating devices, notification appliances, supervisory functions, and power supplies including battery load testing. All components were found to be functioning properly with no failures noted.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--518-22-111 Elevator Replacement Ph. 3, newest first.
File Type Posted
SF 1409 36C24125B0003.pdf PDF
36C24125B0003 0006.docx DOCX document
Construction Specification Institute Division Breakdown.xlsx XLSX spreadsheet
36C24125B0003 - EMR Rating Form.pdf PDF
36C24125B0003 0005.docx DOCX document
518-22-111 - Elevator Replacement Phase 3 - 100 CD - SPECIFICATIONS - updated 7-25-24.pdf PDF
2024-03-07_Bedford-VAMC-Bldg-10_FireScan.pdf PDF
RFI Answers 2nd Batch.docx DOCX document
2024-02-23_Bedford-VAMC-Bldg-9_FireScan.pdf PDF
2024-02-22_Bedford-VAMC-Bldg-7_FireScan.pdf PDF
RFI Answers 1st Batch.docx DOCX document
36C24125B0003 0004.docx DOCX document
36C24125B0003 0003.docx DOCX document
Elevator Site Visit sign in 12-20-24.pdf PDF
36C24125B0003 0002.docx DOCX document
Elevator Site Visit sign in 12-4-24.pdf PDF
36C24125B0003 0001.docx DOCX document
518-22-111 - Elevator Replacement Phase 3 - 100 CD - SPECIFICATIONS.pdf PDF
36C24125B0003.docx DOCX document
518-22-111 - Elevator Replacement Phase 3 - 100 CD - DRAWINGS.pdf PDF
SOW Elevator Replacement Ph 3.pdf PDF
SAM WD MA20240001 revised 10-11-2024.pdf PDF
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Alarm and Life Safety System Inspection Certificate

For

Bedford VAMC Bldg 6 200 Springs Rd

Bedford, MA 01730

Kinetix has performed this inspection and testing service in compliance with The Joint Commission /VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards

This Inspection was performed in accordance with applicable NFPA effective October 1, 2023.

Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Inspection Completion Date Aug 20, 2024

Building: Bedford VAMC Bldg 6 Company: Fire Equipment, Inc.

Contact: Brian Reid Contact: Ryan Michaud

Title: Project Engineer Title: Fire Alarm Technician Fire Alarm Testing Report

Page of 2 21 Executive Summary

Fire Equipment, Inc. Download Date: 12/30/2024

Executive Summary Generated by: BuildingReports.com

Building Information Building: Bedford VAMC Bldg 6 Contact: Brian Reid Address: 200 Springs Rd Phone: 781-687-2779 Address: Fax:

City/State/Zip: Bedford, MA 01730 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire Equipment, Inc. Inspector: Ryan Michaud Address: 20 Hall Street Phone: 617-872-6161 Address: Fax:

City/State/Zip: Medford, MA 02155 Mobile:

Country: United States of America Email: rmichaud@feinewengland.com

System Control Unit Manufacturer: EST Inspection Date: 08/19/2024 IDC Style:

Model Number: EST3 Install Date: 04/23/2020 SLC Style:

Software Version: Version Date: 04/23/2020 NAC Style:

Location: Basement At FACP Current Protection:

Monitoring Company: Phone: Account #:

Central Station Signal Verification Type: Mfg: Model #:

Test Time/Date: Restore Time:

Page of 3 21

Fire Equipment, Inc. Download Date: 12/30/2024

Inspection Completion Date: Aug 20, 2024 Building: Bedford VAMC Bldg 6 EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors.

NFPA 72 (2022) Table 14.4.3.2 (17)

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Duct Detector 1 1 0 1 0 1 Heat Detector 6 6 0 6 0 6 Pull Station 19 19 0 19 0 19 Smoke Detector 11 11 0 11 0 11

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.

NFPA 72 (2022) Table 14.4.3.2 (22)

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Releasing Device 4 4 0 4 0 4 Speaker/Strobe 37 37 0 37 0 37 Strobe 6 6 0 6 0 6

EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Duct Detector 1 1 0 1 0 1

LS 02.01.34 EP 02 Protected master fire alarm control panel

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Control Panel 1 1 0 1 0 1

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Battery 4 4 0 4 0 4 Power Supply 1 1 0 1 0 1

Total Device Count: 90

Page of 4 21

Fire Equipment, Inc. Download Date: 12/30/2024

Certification

Company: Fire Equipment, Inc. Building: Bedford VAMC Bldg 6

Inspector: Ryan Michaud Contact: Brian Reid

Page of 5 21 Inspection & Testing

Fire Equipment, Inc. Download Date: 12/30/2024

Inspection & Testing Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 6 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q3/24 Pass Q3/24 Fail Q3/24 Tested YTD (2024) Total Quantity Duct Detector 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Duct Detector 2nd In Rm B12 6871715 0-6-4-104 08/20-P

Device Total: 1 Return to Executive Summary

Page of 6 21

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.

(NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q3/24 Pass Q3/24 Fail Q3/24 Tested YTD (2024) Total Quantity Heat Detector 6 6 0 6 6

Device Type Location ScanID Address Q3/24 Heat Detector 3rd Elev Eq Rm 51496908 0 08/19-P Heat Detector 3rd Elev Eq Rm 51496907 0 08/19-P Heat Detector 3rd Elev Eq Rm 51496906 0 08/19-P Heat Detector 3rd Elev Eq Rm 51496905 0 08/19-P Heat Detector 3rd Elev Eq Rm 51496904 0 08/19-P Heat Detector 3rd Elev Eq Rm 51496903 0 08/19-P

Device Total: 6 Return to Executive Summary

Page of 7 21

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-19 Table 14.4.3.2 (17)(5)) Devices Tested Q3/24 Pass Q3/24 Fail Q3/24 Tested YTD (2024) Total Quantity Pull Station 19 19 0 19 19

Device Type Location ScanID Address Q3/24 Pull Station Basement Main Entrance 65575550 0-6-4-110 08/19-P Pull Station Basement At South Stair 2 65575546 0-6-4-111 08/19-P Pull Station Basement South Stair 2 65575545 0-6-4-111 08/19-P Pull Station Basement At tunnel to bldg 5 65575541 0-6-4-004 08/19-P Pull Station Basement North at Stair 1 65575537 0-6-4-106 08/19-P Pull Station Basement Tunnel to Bldg 7 65575536 0-6-4-102 08/19-P Pull Station 1st Front Entrance 65575509 0-6-4-122 08/19-P Pull Station 1st Center Corridor 65575510 0-6-4-122 08/19-P Pull Station 1st By Stair 1 65575511 0-6-4-122 08/19-P Pull Station 1st By Stair 3 65575518 0-6-5-024 08/19-P Pull Station 1st By Stair 2 65575527 0-6-5-024 08/19-P Pull Station 1st Inside Carpentry Shop 51496039 0-6-4-101 08/19-P Pull Station 2nd at Stair A 65575499 0-6-5-123 08/19-P Pull Station 2nd At Stair B 65575503 0-6-5-120 08/19-P Pull Station 2nd Nurse Station 51496018 0-6-5-124 08/19-P Pull Station 2nd At Stair 2 65575505 0-6-5-119 08/19-P Pull Station 2nd At Stair C 65575508 0-6-5-024 08/19-P Pull Station 2nd By Rm 114 65575514 0-6-5-121 08/19-P Pull Station 3rd Attic Entrance 31149494 0-6-4-110 08/19-P

Device Total: 19 Return to Executive Summary

Page of 8 21

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q3/24 Pass Q3/24 Fail Q3/24 Tested YTD (2024) Total Quantity Smoke Detector 11 11 0 11 11

Device Type Location ScanID Address Q3/24 Smoke Detector Basement At FACP 65575551 0-6-4-021 08/19-P Smoke Detector Basement Elevator Lobby 65575549 0-6-4-002 08/19-P Smoke Detector Basement Outside Rm B10 65575548 0-6-4-002 08/19-P Smoke Detector Basement Outside B01A 65575559 0-6-4-001 08/19-P Smoke Detector Basement Tunnel to Bldg 7 65575534 0-6-4-001 08/19-P Smoke Detector Basement IT Closet 51495982 0-6-4-050 08/20-P Smoke Detector 1st By Front Entry 65575531 0-6-5-028 08/19-P Smoke Detector 1st Elevator Lobby 65575532 0-6-5-028 08/19-P Smoke Detector 2nd South Corr at Rm 234 65575501 0-6-5-037 08/19-P Smoke Detector 2nd Elev Lobby 51495986 0-6-5-033 08/19-P Smoke Detector 3rd Elev Eq Rm 51496902 0 08/19-P

Device Total: 11 Return to Executive Summary

Page of 9 21

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/24 Pass Q3/24 Fail Q3/24 Tested YTD (2024) Total Quantity Releasing Device 4 4 0 4 4

Device Type Location ScanID Address Q3/24 Releasing Device Basement Doors to Bldg 5 18142369 0 08/19-P Releasing Device Basement Doors to Bldg 5 18142370 0 08/19-P Releasing Device Basement Doors to Bldg 7 18142360 0 08/19-P Releasing Device Basement Doors to Bldg 7 18142361 0 08/19-P

Device Total: 4 Return to Executive Summary

Page of 10 21

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/24 Pass Q3/24 Fail Q3/24 Tested YTD (2024) Total Quantity Speaker/Strobe 37 37 0 37 37

Device Type Location ScanID Address Q3/24 Speaker/Strobe Basement By B02 65575547 0 08/19-P Speaker/Strobe Basement By B029 51496026 0 08/19-P Speaker/Strobe Basement By B20A 65575543 0 08/19-P Speaker/Strobe Basement By Tunnel To Bldg 5 65575542 0 08/19-P Speaker/Strobe Basement Elev Lobby 65575540 0 08/19-P Speaker/Strobe Basement Outside B14A 65575538 0 08/19-P Speaker/Strobe Basement By B13 65575533 0 08/19-P Speaker/Strobe Basement Tunnel to Bldg 7 65575535 0 08/19-P Speaker/Strobe Basement South In Elec Shop 51495984 0 08/19-P Speaker/Strobe Basement By B06A 51495983 0 08/20-P Speaker/Strobe Basement By B13 18142363 0 08/20-P Speaker/Strobe 1st By Stair 1 65575512 0 08/19-P Speaker/Strobe 1st By Rm 115 65575513 0 08/19-P Speaker/Strobe 1st By Rm 116 65575515 0 08/19-P Speaker/Strobe 1st By Rm 125 65575516 0 08/19-P Speaker/Strobe 1st In Rm 123 65575517 0 08/19-P Speaker/Strobe 1st In Rm 130 65575519 0 08/19-P Speaker/Strobe 1st In Rm 130 65575520 0 08/19-P Speaker/Strobe 1st By Rm 133 65575521 0 08/19-P Speaker/Strobe 1st Center Corridor 65575525 0 08/19-P Speaker/Strobe 1st Center Corridor By 149 65575526 0 08/19-P Speaker/Strobe 1st By Rm 161 65575528 0 08/19-P Speaker/Strobe 1st By Rm 157 65575529 0 08/19-P Speaker/Strobe 1st By Rm 166 65575530 0 08/19-P Speaker/Strobe 2nd In Rm 235 65575500 0 08/19-P Speaker/Strobe 2nd Across from Rm 243 51496031 0 08/19-P Speaker/Strobe 2nd In Rm 244 65575504 0 08/19-P Speaker/Strobe 2nd By rm 251 51496020 0 08/19-P Speaker/Strobe 2nd Across from Rm 224 51495994 0 08/19-P Speaker/Strobe 2nd North Corr 200B 51496007 0 08/19-P Speaker/Strobe 2nd By Rm 218 65575506 0 08/19-P Speaker/Strobe 2nd by Rm 212 51495998 0 08/19-P Speaker/Strobe 2nd by Rm 208 65575507 0 08/19-P Speaker/Strobe 2nd by Rm 202 51496016 0 08/19-P Speaker/Strobe 2nd Elev Lobby 51495985 0 08/19-P Speaker/Strobe 2nd By Rm 241 51496029 0 08/19-P Speaker/Strobe 3rd Attic Rear 51496505 0 08/19-P

Page of 11 21

Fire Equipment, Inc. Download Date: 12/30/2024

Device Type Location ScanID Address Q3/24

Device Total: 37 Return to Executive Summary

Page of 12 21

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q3/24 Pass Q3/24 Fail Q3/24 Tested YTD (2024) Total Quantity Strobe 6 6 0 6 6

Device Type Location ScanID Address Q3/24 Strobe 1st In Rm 116 65575522 0 08/19-P Strobe 1st In Rm 118 65575523 0 08/19-P Strobe 1st In Rm 112 65575524 0 08/19-P Strobe 2nd In Rm 230 51496035 0 08/19-P Strobe 2nd In Rm 201 51496017 0 08/19-P Strobe 2nd Bathroom 51495988 0 08/20-P

Device Total: 6 Return to Executive Summary

Page of 13 21

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment.

NFPA 90A (2024) 6.4.1

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q3/24 Pass Q3/24 Fail Q3/24 Tested YTD (2024) Total Quantity Duct Detector 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Duct Detector 2nd In Rm B12 6871715 0-6-4-104 08/20-P

Page of 14 21

Fire Equipment, Inc. Download Date: 12/30/2024

LS 02.01.34 EP 02 Protected master fire alarm control panel

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q3/24 Pass Q3/24 Fail Q3/24 Tested YTD (2024) Total Quantity Control Panel 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Control Panel Basement At FACP 51495981 0 08/19-P

Page of 15 21

Fire Equipment, Inc. Download Date: 12/30/2024

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q3/24 Pass Q3/24 Fail Q3/24 Tested YTD (2024) Total Quantity Battery 4 4 0 4 4

Device Type Location ScanID Address Q3/24 Battery Basement At FACP Main FACP 51495977 0-12V68A 08/19-P Battery Basement At FACP Main FACP 51495978 0-12V68A 08/19-P Battery Basement At FACP Nac 51495979 0-12V68A 08/19-P Battery Basement At FACP Nac 51495980 0-12V68A 08/19-P

Device Total: 4 Return to Executive Summary

Page of 16 21

Fire Equipment, Inc. Download Date: 12/30/2024

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q3/24 Pass Q3/24 Fail Q3/24 Tested YTD (2024) Total Quantity Power Supply 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Power Supply Basement At FACP 51495976 0 08/19-P

Page of 17 21 Service Summary

Fire Equipment, Inc. Download Date: 12/30/2024

Service Summary Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 6 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Passed Battery Tested 4 Control Panel Tested 1 Duct Detector Tested 1 Heat Detector Tested 6 Power Supply Tested 1 Pull Station Tested 19 Releasing Device Tested 4 Smoke Detector Tested 11 Speaker/Strobe Tested 37 Strobe Tested 6

Total 90 Grand Total 90

Page of 18 21 Auxiliary Functions Testing

Fire Equipment, Inc. Download Date: 12/30/2024

Auxiliary Functions Testing Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 6 Control Panel: 0 - EST EST3 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Releasing Device

Door Holder Basement Doors to Bldg 5 Passed 18142369 Door Holder Basement Doors to Bldg 5 Passed 18142370 Door Holder Basement Doors to Bldg 7 Passed 18142360 Door Holder Basement Doors to Bldg 7 Passed 18142361

Duct Detector AHU Shutdown 2nd In Rm B12 Passed 6871715 javascript:editViewDevice('18142369');

javascript:editViewDevice('18142370');

javascript:editViewDevice('18142360');

javascript:editViewDevice('18142361');

javascript:editViewDevice('6871715');

Page of 19 21 Battery & Power Supply Testing

Fire Equipment, Inc. Download Date: 12/30/2024

Battery & Power Supply Testing Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 6 Control Panel: 0 - EST EST3 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Battery

Passed Sealed Lead Acid Basement At FACP Main

FACP

55 12

Sealed Lead Acid Basement At FACP Main

FACP

55 12

Page of 20 21 Inventory & Warranty Report

Fire Equipment, Inc. Download Date: 12/30/2024

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 6 Control Panel: 0 - EST EST3 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Battery Control 4.44% 4

Control Panel Control 1.11% 1

Duct Detector Initiating 1.11% 1

Heat Detector Initiating 6.67% 6

Power Supply Control 1.11% 1

Pull Station Initiating 21.11% 19

Releasing Device Auxiliary 4.44% 4

Smoke Detector Initiating 12.22% 11

Speaker/Strobe Indicating 41.11% 37

Strobe Indicating 6.67% 6

Type Qty Model # Description Install Date

In Service - 3 Years to 5 Years Power Supply 1 04/23/2020

EST

Control Panel 1 EST3 04/23/2020 Duct Detector 1 SIGA-SD 04/23/2020 Heat Detector 6 SIGA-HRS 04/23/2020 Pull Station 19 SIGA-278 04/23/2020 Smoke Detector 11 SIGA-PD 04/23/2020

Power Sonic Battery 2 04/23/2020 Battery 2 Sealed Lead Acid 04/23/2020

System Sensor Releasing Device 4 Door Holder 04/23/2020 Speaker/Strobe 37 G4HFRF-S2VMC 04/23/2020 Strobe 6 G1RF-VM 04/23/2020

Page of 21 21 Zone Address Report

Fire Equipment, Inc. Download Date: 12/30/2024

Zone Address Report Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 6 Control Panel: 0 - EST EST3 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID 6-4-001 Smoke Detector Basement Outside B01A 65575559 6-4-001 Smoke Detector Basement Tunnel to Bldg 7 65575534 6-4-002 Smoke Detector Basement Elevator Lobby 65575549 6-4-002 Smoke Detector Basement Outside Rm B10 65575548 6-4-004 Pull Station Basement At tunnel to bldg 5 65575541 6-4-021 Smoke Detector Basement At FACP 65575551 6-4-050 Smoke Detector Basement IT Closet 51495982 6-4-101 Pull Station 1st Inside Carpentry Shop 51496039 6-4-102 Pull Station Basement Tunnel to Bldg 7 65575536 6-4-104 Duct Detector 2nd In Rm B12 6871715 6-4-106 Pull Station Basement North at Stair 1 65575537 6-4-110 Pull Station Basement Main Entrance 65575550 6-4-110 Pull Station 3rd Attic Entrance 31149494 6-4-111 Pull Station Basement At South Stair 2 65575546 6-4-111 Pull Station Basement South Stair 2 65575545 6-4-122 Pull Station 1st By Stair 1 65575511 6-4-122 Pull Station 1st Center Corridor 65575510 6-4-122 Pull Station 1st Front Entrance 65575509 6-5-024 Pull Station 1st By Stair 2 65575527 6-5-024 Pull Station 1st By Stair 3 65575518 6-5-024 Pull Station 2nd At Stair C 65575508 6-5-028 Smoke Detector 1st By Front Entry 65575531 6-5-028 Smoke Detector 1st Elevator Lobby 65575532 6-5-033 Smoke Detector 2nd Elev Lobby 51495986 6-5-037 Smoke Detector 2nd South Corr at Rm 234 65575501 6-5-119 Pull Station 2nd At Stair 2 65575505 6-5-120 Pull Station 2nd At Stair B 65575503 6-5-121 Pull Station 2nd By Rm 114 65575514 6-5-123 Pull Station 2nd at Stair A 65575499 6-5-124 Pull Station 2nd Nurse Station 51496018 12V68A Battery Basement At FACP Main FACP Sealed Lead Acid 51495977 12V68A Battery Basement At FACP Main FACP Sealed Lead Acid 51495978 12V68A Battery Basement At FACP Nac 51495979 12V68A Battery Basement At FACP Nac 51495980 javascript:editViewDevice('65575559');

javascript:editViewDevice('65575534');

javascript:editViewDevice('65575549');

javascript:editViewDevice('65575548');

javascript:editViewDevice('65575541');

javascript:editViewDevice('65575551');

javascript:editViewDevice('51495982');

javascript:editViewDevice('51496039');

javascript:editViewDevice('65575536');

javascript:editViewDevice('6871715');

javascript:editViewDevice('65575537');

javascript:editViewDevice('65575550');

javascript:editViewDevice('31149494');

javascript:editViewDevice('65575546');

javascript:editViewDevice('65575545');

javascript:editViewDevice('65575511');

javascript:editViewDevice('65575510');

javascript:editViewDevice('65575509');

javascript:editViewDevice('65575527');

javascript:editViewDevice('65575518');

javascript:editViewDevice('65575508');

javascript:editViewDevice('65575531');

javascript:editViewDevice('65575532');

javascript:editViewDevice('51495986');

javascript:editViewDevice('65575501');

javascript:editViewDevice('65575505');

javascript:editViewDevice('65575503');

javascript:editViewDevice('65575514');

javascript:editViewDevice('65575499');

javascript:editViewDevice('51496018');

javascript:editViewDevice('51495977');

javascript:editViewDevice('51495978');

javascript:editViewDevice('51495979');

javascript:editViewDevice('51495980');

Fire Alarm and Life Safety System Inspection Certificate
Inspection & Testing
Service Summary
Auxiliary Functions Testing
Battery & Power Supply Testing
Inventory & Warranty Report
Zone Address Report

File details come from the government source that posted it. Updated .