2024-02-23_Bedford-VAMC-Bldg-9_FireScan.pdf

PDF 95 KB Posted

Attached to
Z2DA--518-22-111 Elevator Replacement Ph. 3 Federal contract opportunity
Solicitation number
36C24125B0003
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1

About this file

This is a fire alarm and life safety system inspection certificate and report completed by Kinetix Fire & Life Safety Experts for Building 9 at the Bedford VA Medical Center on February 23, 2024. The inspection was performed in compliance with The Joint Commission/VHA Standards and NFPA Standards for the facility located at 200 Springs Rd, Bedford, MA 01730.

The report details the testing of 59 total devices including 14 pull stations, 19 smoke detectors (18 tested, 1 untested), 1 horn/strobe, 6 releasing devices, 16 speaker/strobes, 1 control panel (EST EST3), and 2 batteries. All tested devices passed inspection. The system includes elevator recall functionality, door holders, and emergency releasing devices. Key findings note that several releasing devices need adjustment, one smoke detector had no access (Storage Room B07), and the elevator recall bypass was not working on the 2nd floor elevator lobby detector. The system was originally installed on February 25, 2020 and uses dual 12V 55Ah sealed lead acid batteries for backup power.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--518-22-111 Elevator Replacement Ph. 3, newest first.
File Type Posted
SF 1409 36C24125B0003.pdf PDF
36C24125B0003 0006.docx DOCX document
36C24125B0003 - EMR Rating Form.pdf PDF
36C24125B0003 0005.docx DOCX document
Construction Specification Institute Division Breakdown.xlsx XLSX spreadsheet
2024-02-22_Bedford-VAMC-Bldg-7_FireScan.pdf PDF
RFI Answers 1st Batch.docx DOCX document
36C24125B0003 0004.docx DOCX document
518-22-111 - Elevator Replacement Phase 3 - 100 CD - SPECIFICATIONS - updated 7-25-24.pdf PDF
2024-03-07_Bedford-VAMC-Bldg-10_FireScan.pdf PDF
2024-08-20_Bedford-VAMC-Bldg-6_FireScan.pdf PDF
RFI Answers 2nd Batch.docx DOCX document
Elevator Site Visit sign in 12-20-24.pdf PDF
36C24125B0003 0003.docx DOCX document
36C24125B0003 0002.docx DOCX document
Elevator Site Visit sign in 12-4-24.pdf PDF
36C24125B0003 0001.docx DOCX document
518-22-111 - Elevator Replacement Phase 3 - 100 CD - SPECIFICATIONS.pdf PDF
36C24125B0003.docx DOCX document
518-22-111 - Elevator Replacement Phase 3 - 100 CD - DRAWINGS.pdf PDF
SOW Elevator Replacement Ph 3.pdf PDF
SAM WD MA20240001 revised 10-11-2024.pdf PDF
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Alarm and Life Safety System Inspection Certificate

For

Bedford VAMC Bldg 9 200 Springs Rd

Bedford, MA 01730

Kinetix has performed this inspection and testing service in compliance with The Joint Commission /VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards

This Inspection was performed in accordance with applicable NFPA effective October 1, 2023.

Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Inspection Completion Date Feb 23, 2024

Building: Bedford VAMC Bldg 9 Company: Kinetix Contact: Brian Reid Contact: Jordan Caplan

Title: Project Engineer Title: Tech Fire Alarm Testing Report

Page of 2 19 Executive Summary

Kinetix Download Date: 12/30/2024

Executive Summary Generated by: BuildingReports.com

Building Information Building: Bedford VAMC Bldg 9 Contact: Brian Reid Address: 200 Springs Rd Phone: 7816872000 Address: Fax:

City/State/Zip: Bedford, MA 01730 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Kinetix Inspector: Jordan Caplan Address: 583 Abbott Dr Phone: 2028051831 Address: Fax:

City/State/Zip: Broomall, PA 19008 Mobile: 2028051831 Country: United States of America Email: jcaplan@kinetixfire.com

System Control Unit Manufacturer: EST Inspection Date: 02/23/2024 IDC Style: A Model Number: EST3 Install Date: 02/25/2020 SLC Style:

Software Version: Version Date: 02/25/2020 NAC Style: A Location: 1st in main entrance Current Protection: Breaker

Monitoring Company: Phone: Account #:

Central Station Signal Verification Type: Mfg: Model #:

Test Time/Date: Restore Time:

Page of 3 19

Kinetix Download Date: 12/30/2024

Inspection Completion Date: Feb 23, 2024 Building: Bedford VAMC Bldg 9 EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors.

NFPA 72 (2022) Table 14.4.3.2 (17)

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Pull Station 14 14 0 14 0 14 Smoke Detector 18 18 0 18 1 19

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.

NFPA 72 (2022) Table 14.4.3.2 (22)

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Horn/Strobe 1 1 0 1 0 1 Releasing Device 6 6 0 6 0 6 Speaker/Strobe 16 16 0 16 0 16

LS 02.01.34 EP 02 Protected master fire alarm control panel

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Control Panel 1 1 0 1 0 1

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Battery 2 2 0 2 0 2

Total Device Count: 59

Page of 4 19

Kinetix Download Date: 12/30/2024

Certification

Company: Kinetix Building: Bedford VAMC Bldg 9

Inspector: Jordan Caplan Contact: Brian Reid

Page of 5 19 Notes & Recommendations

Kinetix Download Date: 12/30/2024

Notes & Recommendations Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 9 Control Panel: 1 - EST EST3 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

Note Device Type Location Comment ScanID

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

1 Smoke Detector 1st By Elevator/By Rm 140 Passed 06878030 Recalls To Primary Floor

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.

NFPA 72 (2022) Table 14.4.3.2 (22)

2 Releasing Device Basement Doors by Elevator Passed 18142182 Need Adjustment

3 Releasing Device Basement Doors by Elevator Passed 18142183 Need Adjustment

4 Releasing Device Basement Tunnel Doors to Bldg 10 Passed 18142179 Need Adjustment

5 Releasing Device Basement Tunnel Doors to Bldg 10 Passed 18142180 Need Adjustment

Building: Bedford VAMC Bldg 9 Control Panel: 9 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

Note Device Type Location Comment ScanID

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

6 Smoke Detector Basement Storage Rm B07 51496268 no access, 2/23/24

7 Smoke Detector 1st Data Room by Elevator Passed 51496261 no access, 2/23/24

8 Smoke Detector 2nd Data Room by Elevator Passed 51496264 no access, 2/23/24

9 Smoke Detector 2nd Elevator Lobby Passed 06878042 Recalls To Primary Floor, elv recall bypass not working 2/23/24 javascript:editViewDevice('06878030');

javascript:editViewDevice('18142182');

javascript:editViewDevice('18142183');

javascript:editViewDevice('18142179');

javascript:editViewDevice('18142180');

javascript:editViewDevice('51496268');

javascript:editViewDevice('51496261');

javascript:editViewDevice('51496264');

javascript:editViewDevice('06878042');

Page of 6 19 Inspection & Testing

Kinetix Download Date: 12/30/2024

Inspection & Testing Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 9 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-19 Table 14.4.3.2 (17)(5)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Pull Station 14 14 0 14 14

Device Type Location ScanID Address Q1/23 Q1/24 Pull Station Basement In stair 2 06878057 9-2-102 02/14-P 02/23-P Pull Station Basement By Stair 1 06878055 9-2 105 02/14-P 02/23-P Pull Station Basement By Tunnel to Bldg 8 06878056 9-2-108 02/14-P 02/23-P Pull Station Basement By IRMB2 06878060 9-2 101 02/14-P 02/23-P Pull Station 1st Exit by Social Work Services 06878041 9-2 111 02/14-P 02/23-P Pull Station 1st Front Entrance by Rm 140 06878031 9-2-115 02/14-P 02/23-P Pull Station 1st Exit by Rm 110 06878035 9-2 120 02/14-P 02/23-P Pull Station 1st By Stair 1 06878034 9-2 117 02/14-P 02/23-P Pull Station 1st By Stair 2 06878039 9-2 112 02/14-P 02/23-P Pull Station 1st Rear Exit in Rm 122 06878032 9-2 116 02/14-P 02/23-P Pull Station 2nd Exit By Room 226 06878046 9-2-141 02/14-P 02/23-P Pull Station 2nd by stair 1 06878050 9-2 117 02/14-P 02/23-P Pull Station 2nd By room 211 06878052 9-2 150 02/14-P 02/23-P Pull Station 2nd by stair 2 06878044 9-2-144 02/14-P 02/23-P

Device Total: 14 Return to Executive Summary

Page of 7 19

Kinetix Download Date: 12/30/2024

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Smoke Detector 18 18 0 18 19

Device Type Location ScanID Address Q1/23 Q1/24 Smoke Detector Basement Tunnel to Bldg 10 71417624 9-2 2 02/14-P 02/23-P Smoke Detector Basement By Tunnel to Bldg 10 51496265 9-2-1 02/14-P 02/23-P Smoke Detector Basement Storage Rm B07 51496268 9-2-8 Smoke Detector 1st By Elevator/By Rm 140 06878030 1-3005 02/14-P 02/23-P Smoke Detector 1st Data Room by Elevator 51496261 9-2-6 02/23-P Smoke Detector 1st By Rm 105 06878036 9-2-21 02/14-P 02/23-P Smoke Detector 1st By Rm 115 06878037 9-2-22 02/14-P 02/23-P Smoke Detector 1st Outside room 139 Stair2 06878038 9-2-4 02/14-P 02/23-P Smoke Detector 1st By Rm 132 51496260 9-2-23 02/14-P 02/23-P Smoke Detector 1st By Stair 1 06878033 9-2-20 02/14-P 02/23-P Smoke Detector 2nd By Rm 219 06878043 9-3-15 02/14-P 02/23-P Smoke Detector 2nd By Rm 206 06878051 9-2 17 02/14-P 02/23-P Smoke Detector 2nd By Rm 211 06878053 9-2 18 02/14-P 02/23-P Smoke Detector 2nd Elevator Lobby 06878042 9-3 14 02/14-P 02/23-P Smoke Detector 2nd By Rm 231 06878045 9-2 13 02/14-P 02/23-P Smoke Detector 2nd By Rm 228 06878048 9-2 12 02/14-P 02/23-P Smoke Detector 2nd By Rm 225 06878047 9-2 11 02/14-P 02/23-P Smoke Detector 2nd Data Room by Elevator 51496264 9-2-7 02/13-P 02/23-P Smoke Detector 2nd By Rm 218 06878049 9-2-16 02/14-P 02/23-P

Device Total: 19 Return to Executive Summary

Page of 8 19

Kinetix Download Date: 12/30/2024

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(1)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Horn/Strobe 1 1 0 1 1

Device Type Location ScanID Address Q1/23 Q1/24 Horn/Strobe 2nd By Rm 211 18142187 1 02/13-P 02/23-P

Device Total: 1 Return to Executive Summary

Page of 9 19

Kinetix Download Date: 12/30/2024

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Releasing Device 6 6 0 6 6

Device Type Location ScanID Address Q1/23 Q1/24 Releasing Device Basement Doors by Elevator 18142182 1 02/14-P 02/23-P Releasing Device Basement Doors by Elevator 18142183 1 02/14-P 02/23-P Releasing Device Basement Tunnel Doors to Bldg 10 18142180 1 02/14-P 02/23-P Releasing Device Basement Tunnel Doors to Bldg 10 18142179 1 02/14-P 02/23-P Releasing Device 1st By Stair 1 18142197 1 02/14-P 02/23-P Releasing Device 2nd By room 201 18142191 1 02/14-P 02/23-P

Device Total: 6 Return to Executive Summary

Page of 10 19

Kinetix Download Date: 12/30/2024

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Speaker/Strobe 16 16 0 16 16

Device Type Location ScanID Address Q1/23 Q1/24 Speaker/Strobe Basement By stair 1 18142186 1 02/14-P 02/23-P Speaker/Strobe Basement By stair 2/by room IRMB2 18142181 1 02/14-P 02/23-P Speaker/Strobe 1st By room 115 18142199 1 02/13-P 02/23-P Speaker/Strobe 1st Outside Room 110 Lobby 18142201 9 02/13-P 02/23-P Speaker/Strobe 1st By Stair 1 18142198 1 02/13-P 02/23-P Speaker/Strobe 1st By room 122 18142196 1 02/13-P 02/23-P Speaker/Strobe 1st By Stair 2 18142195 1 02/13-P 02/23-P Speaker/Strobe 1st In room 136C 51496262 1 02/14-P 02/23-P Speaker/Strobe 1st In room 126 51496263 1 02/13-P 02/23-P Speaker/Strobe 2nd By Rm 211 18142200 1 02/13-P 02/23-P Speaker/Strobe 2nd By Stair 1 18142190 9 02/13-P 02/23-P Speaker/Strobe 2nd By Rm 208 18142189 1 02/13-P 02/23-P Speaker/Strobe 2nd In Rm 215 18142188 1 02/13-P 02/23-P Speaker/Strobe 2nd By Stair 2 18142192 1 02/13-P 02/23-P Speaker/Strobe 2nd By Room 229 18142193 1 02/13-P 02/23-P Speaker/Strobe 2nd By Room 224 18142194 1 02/13-P 02/23-P

Device Total: 16 Return to Executive Summary

Page of 11 19

Kinetix Download Date: 12/30/2024

LS 02.01.34 EP 02 Protected master fire alarm control panel

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Control Panel 1 1 0 1 1

Device Type Location ScanID Address Q1/23 Q1/24 Control Panel 1st in main entrance 51496257 1 02/13-P 02/23-P

Device Total: 1 Return to Executive Summary

Page of 12 19

Kinetix Download Date: 12/30/2024

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Battery 2 2 0 2 2

Device Type Location ScanID Address Q1/23 Q1/24 Battery 1st in main entrance below facp 51496258 1 02/13-P 02/23-P Battery 1st in main entrance below facp 51496259 1 02/13-P 02/23-P

Device Total: 2 Return to Executive Summary

Page of 13 19 Service Summary

Kinetix Download Date: 12/30/2024

Service Summary Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 9 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Passed Battery Tested 2 Control Panel Tested 1 Horn/Strobe Tested 1 Pull Station Tested 14 Releasing Device Tested 6 Smoke Detector Tested/Cleaned 18 Speaker/Strobe Tested 16

Total 58

Untested Smoke Detector 1

Total 1 Grand Total 59

Page of 14 19 Auxiliary Functions Testing

Kinetix Download Date: 12/30/2024

Auxiliary Functions Testing Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 9 Control Panel: 1 - EST EST3 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Releasing Device

Door Holder 1st By Stair 1 Passed 18142197 Door Holder 2nd By room 201 Passed 18142191

Smoke Detector Elevator Recall 1st By Elevator/By Rm 140 Passed 06878030

Building: Bedford VAMC Bldg 9 Control Panel: 9 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Smoke Detector

Elevator Recall 2nd Elevator Lobby Passed 06878042 Door Release Basement Tunnel to Bldg 10 Passed 71417624 javascript:editViewDevice('18142197');

javascript:editViewDevice('18142191');

javascript:editViewDevice('06878030');

javascript:editViewDevice('06878042');

javascript:editViewDevice('71417624');

Page of 15 19 Battery & Power Supply Testing

Kinetix Download Date: 12/30/2024

Battery & Power Supply Testing Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 9 Control Panel: 1 - EST EST3 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Battery

Passed Sealed Lead Acid 1st in main entrance below facp 55 12

Sealed Lead Acid 1st in main entrance below facp

55 12

Page of 16 19 Inventory & Warranty Report

Kinetix Download Date: 12/30/2024

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 9 Control Panel: 1 - EST EST3 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Battery Control 3.39% 2

Control Panel Control 1.69% 1

Horn/Strobe Indicating 1.69% 1

Pull Station Initiating 23.73% 14

Releasing Device Auxiliary 10.17% 6

Smoke Detector Initiating 32.20% 19

Speaker/Strobe Indicating 27.12% 16

Type Qty Model # Description Install Date

In Service - 3 Years to 5 Years

EST

Control Panel 1 EST3 Addressable 02/25/2020

Est Speaker/Strobe 5 A32-BL-SFXR-

TP24D-

02/25/2020

Power sonic Battery 1 SLA1165 Sealed Lead Acid 02/25/2020

Power-Sonic Battery 1 SLA1165 Sealed Lead Acid 02/25/2020

Space age Speaker/Strobe 9 A32-BL-SFXR-

TP24D-

02/25/2020

System Sensor Releasing Device 6 Door Holder 02/25/2020 Smoke Detector 1 1451 Photoelectric 02/25/2020

Wheelock Horn/Strobe 1 02/25/2020

Building: Bedford VAMC Bldg 9 Control Panel: 9 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Type Qty Model # Description Install Date

In Service - 3 Years to 5 Years

EST

Smoke Detector 1 2551-f Photoelectric 02/25/2020

Page of 17 19 Inventory & Warranty Report

Kinetix Download Date: 12/30/2024

Est Speaker/Strobe 1 1451 02/25/2020

FCI

Pull Station 1 MS-6 Dual Action 02/25/2020 Pull Station 11 MS-6 Single Action 02/25/2020 Pull Station 1 MS6 Single Action 02/25/2020

Fci Pull Station 1 ms-6 02/25/2020

Space age Speaker/Strobe 1 A32-BL-SFXR-

TP24D-

02/25/2020

System Sensor Smoke Detector 5 Photoelectric 02/25/2020 Smoke Detector 12 1451 Photoelectric 02/25/2020

Page of 18 19 Zone Address Report

Kinetix Download Date: 12/30/2024

Zone Address Report Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 9 Control Panel: 1 - EST EST3 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID 3005 Smoke Detector 1st By Elevator/By Rm 140 Photoelectric 06878030

Building: Bedford VAMC Bldg 9 Control Panel: 9 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID Zone/Circuit: 2

2 Smoke Detector Basement Tunnel to Bldg 10 Photoelectric 71417624 11 Smoke Detector 2nd By Rm 225 Photoelectric 06878047 12 Smoke Detector 2nd By Rm 228 Photoelectric 06878048 13 Smoke Detector 2nd By Rm 231 Photoelectric 06878045 17 Smoke Detector 2nd By Rm 206 Photoelectric 06878051 18 Smoke Detector 2nd By Rm 211 Photoelectric 06878053 101 Pull Station Basement By IRMB2 Single Action 06878060 105 Pull Station Basement By Stair 1 Single Action 06878055 111 Pull Station 1st Exit by Social Work Services Single Action 06878041 112 Pull Station 1st By Stair 2 06878039 116 Pull Station 1st Rear Exit in Rm 122 Single Action 06878032 117 Pull Station 1st By Stair 1 Single Action 06878034 117 Pull Station 2nd by stair 1 Single Action 06878050 120 Pull Station 1st Exit by Rm 110 Single Action 06878035 150 Pull Station 2nd By room 211 Single Action 06878052

Zone/Circuit: 3 14 Smoke Detector 2nd Elevator Lobby Photoelectric 06878042 2-1 Smoke Detector Basement By Tunnel to Bldg 10 Photoelectric 51496265 2-4 Smoke Detector 1st Outside room 139 Stair2 Photoelectric 06878038 2-6 Smoke Detector 1st Data Room by Elevator Photoelectric 51496261 2-7 Smoke Detector 2nd Data Room by Elevator Photoelectric 51496264 2-8 Smoke Detector Basement Storage Rm B07 Photoelectric 51496268 2-16 Smoke Detector 2nd By Rm 218 Photoelectric 06878049 2-20 Smoke Detector 1st By Stair 1 Photoelectric 06878033 2-21 Smoke Detector 1st By Rm 105 Photoelectric 06878036 2-22 Smoke Detector 1st By Rm 115 Photoelectric 06878037 2-23 Smoke Detector 1st By Rm 132 Photoelectric 51496260

2-102 Pull Station Basement In stair 2 Single Action 06878057 2-108 Pull Station Basement By Tunnel to Bldg 8 Single Action 06878056 2-115 Pull Station 1st Front Entrance by Rm 140 Dual Action 06878031 javascript:editViewDevice('06878030');

javascript:editViewDevice('71417624');

javascript:editViewDevice('06878047');

javascript:editViewDevice('06878048');

javascript:editViewDevice('06878045');

javascript:editViewDevice('06878051');

javascript:editViewDevice('06878053');

javascript:editViewDevice('06878060');

javascript:editViewDevice('06878055');

javascript:editViewDevice('06878041');

javascript:editViewDevice('06878039');

javascript:editViewDevice('06878032');

javascript:editViewDevice('06878034');

javascript:editViewDevice('06878050');

javascript:editViewDevice('06878035');

javascript:editViewDevice('06878052');

javascript:editViewDevice('06878042');

javascript:editViewDevice('51496265');

javascript:editViewDevice('06878038');

javascript:editViewDevice('51496261');

javascript:editViewDevice('51496264');

javascript:editViewDevice('51496268');

javascript:editViewDevice('06878049');

javascript:editViewDevice('06878033');

javascript:editViewDevice('06878036');

javascript:editViewDevice('06878037');

javascript:editViewDevice('51496260');

javascript:editViewDevice('06878057');

javascript:editViewDevice('06878056');

javascript:editViewDevice('06878031');

Page of 19 19 Zone Address Report

Kinetix Download Date: 12/30/2024

Address Device Type Location Type ScanID 2-141 Pull Station 2nd Exit By Room 226 Single Action 06878046 2-144 Pull Station 2nd by stair 2 Single Action 06878044 3-15 Smoke Detector 2nd By Rm 219 Photoelectric 06878043 javascript:editViewDevice('06878046');

javascript:editViewDevice('06878044');

javascript:editViewDevice('06878043');

Fire Alarm and Life Safety System Inspection Certificate
Notes & Recommendations
Inspection & Testing
Service Summary
Auxiliary Functions Testing
Battery & Power Supply Testing
Inventory & Warranty Report
Zone Address Report

File details come from the government source that posted it. Updated .