2024-03-07_Bedford-VAMC-Bldg-10_FireScan.pdf

PDF 116 KB Posted

Attached to
Z2DA--518-22-111 Elevator Replacement Ph. 3 Federal contract opportunity
Solicitation number
36C24125B0003
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1

About this file

This is a fire alarm and life safety system inspection certificate and report for Bedford VAMC Building 10, conducted by Kinetix Fire & Life Safety Experts on March 7, 2024. The inspection was performed in compliance with Joint Commission/VHA Standards and NFPA requirements.

The inspection covered testing of 58 total devices including duct detectors, heat detectors, manual fire alarm boxes, smoke detectors, horn/strobes, speaker/strobes, strobes, and control panel components. While most devices passed testing, four batteries failed and require replacement: two 12V55A batteries in the main FACP and two 12V batteries in the power supply. The building's EST 3 fire alarm control panel was installed on April 27, 2020, and is located on the first floor by the outside elevator lobby. The system includes elevator recall functionality, which passed testing for all designated elevator recall smoke and heat detectors. All notification appliances, initiating devices, and auxiliary functions were tested according to NFPA 72 requirements, with detailed documentation provided for each device's location, model number, and test results.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--518-22-111 Elevator Replacement Ph. 3, newest first.
File Type Posted
SF 1409 36C24125B0003.pdf PDF
36C24125B0003 0006.docx DOCX document
Construction Specification Institute Division Breakdown.xlsx XLSX spreadsheet
36C24125B0003 - EMR Rating Form.pdf PDF
36C24125B0003 0005.docx DOCX document
2024-02-22_Bedford-VAMC-Bldg-7_FireScan.pdf PDF
518-22-111 - Elevator Replacement Phase 3 - 100 CD - SPECIFICATIONS - updated 7-25-24.pdf PDF
2024-08-20_Bedford-VAMC-Bldg-6_FireScan.pdf PDF
RFI Answers 2nd Batch.docx DOCX document
2024-02-23_Bedford-VAMC-Bldg-9_FireScan.pdf PDF
RFI Answers 1st Batch.docx DOCX document
36C24125B0003 0004.docx DOCX document
36C24125B0003 0003.docx DOCX document
Elevator Site Visit sign in 12-20-24.pdf PDF
36C24125B0003 0002.docx DOCX document
Elevator Site Visit sign in 12-4-24.pdf PDF
36C24125B0003 0001.docx DOCX document
518-22-111 - Elevator Replacement Phase 3 - 100 CD - SPECIFICATIONS.pdf PDF
36C24125B0003.docx DOCX document
518-22-111 - Elevator Replacement Phase 3 - 100 CD - DRAWINGS.pdf PDF
SOW Elevator Replacement Ph 3.pdf PDF
SAM WD MA20240001 revised 10-11-2024.pdf PDF
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Alarm and Life Safety System Inspection Certificate

For

Bedford VAMC Bldg 10 200 Springs Rd

Bedford, MA 01730

Kinetix has performed this inspection and testing service in compliance with The Joint Commission /VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards

This Inspection was performed in accordance with applicable NFPA effective October 1, 2023.

Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Inspection Completion Date Mar 7, 2024

Building: Bedford VAMC Bldg 10 Company: Fire Equipment, Inc.

Contact: Brian Reid Contact: Ryan Michaud

Title: Project Engineer Title: Fire Alarm Technician Fire Alarm Testing Report

Page of 2 25 Executive Summary

Fire Equipment, Inc. Download Date: 12/30/2024

Executive Summary Generated by: BuildingReports.com

Building Information Building: Bedford VAMC Bldg 10 Contact: Brian Reid Address: 200 Springs Rd Phone: 7816872000 Address: Fax:

City/State/Zip: Bedford, MA 01730 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire Equipment, Inc. Inspector: Ryan Michaud Address: 20 Hall Street Phone: 617-872-6161 Address: Fax:

City/State/Zip: Medford, MA 02155 Mobile:

Country: United States of America Email: rmichaud@feinewengland.com

System Control Unit Manufacturer: EST Inspection Date: 03/06/2024 IDC Style:

Model Number: EST 3 Install Date: 04/27/2020 SLC Style:

Software Version: Version Date: 04/27/2020 NAC Style:

Location: 1st Bldg 10 By Outside Elevator Lobby Current Protection:

Monitoring Company: Phone: Account #:

Central Station Signal Verification Type: Mfg: Model #:

Test Time/Date: Restore Time:

Page of 3 25

Fire Equipment, Inc. Download Date: 12/30/2024

Inspection Completion Date: Mar 7, 2024 Building: Bedford VAMC Bldg 10 EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors.

NFPA 72 (2022) Table 14.4.3.2 (17)

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Duct Detector 1 1 0 1 0 1 Heat Detector 1 1 0 1 0 1 Pull Station 9 9 0 9 0 9 Smoke Detector 7 7 0 7 0 7

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.

NFPA 72 (2022) Table 14.4.3.2 (22)

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Horn/Strobe 15 15 0 15 0 15 Speaker/Strobe 9 9 0 9 0 9 Strobe 9 9 0 9 0 9

EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Duct Detector 1 1 0 1 0 1

LS 02.01.34 EP 02 Protected master fire alarm control panel

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Control Panel 1 1 0 1 0 1

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Annunciator 1 1 0 1 0 1 Battery 4 0 4 4 0 4 Power Supply 1 1 0 1 0 1

Total Device Count: 58

Page of 4 25

Fire Equipment, Inc. Download Date: 12/30/2024

Certification

Company: Fire Equipment, Inc. Building: Bedford VAMC Bldg 10

Inspector: Ryan Michaud Contact: Brian Reid

Page of 5 25 Discrepancy Report

Fire Equipment, Inc. Download Date: 12/30/2024

Discrepancy Report Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 10 Control Panel: 0 - EST EST 3 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade

No items found during this inspection.

ScanID Location Problem Address Reference

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Battery

51496961 1st Bldg 10 Main FACP Failed Test 0-12V55A NFPA72 Table

14.4.3.2 (9)

51496962 1st Bldg 10 Main FACP Failed Test 0-12V55A NFPA72 Table

14.4.3.2 (9)

51496964 1st Bldg 10 Power Supply Failed Test 0-12V NFPA72 Table

14.4.3.2 (9)

51496965 1st Bldg 10 Power Supply Failed Test 0-12V NFPA72 Table

14.4.3.2 (9)

Code References NFPA72 Table 14.4.3.2 (9) Replace any battery cell/unit if the temperature is greater than 18F above ambient. Replace the battery when any cell/unit measures a voltage less than 13.26 volts. Replace the battery when any cell/unit has an internal ohmic value outside of the acceptable range.

javascript:editViewDevice('51496961');

javascript:editViewDevice('51496962');

javascript:editViewDevice('51496964');

javascript:editViewDevice('51496965');

Page of 6 25 Proposed Solutions Report

Fire Equipment, Inc. Download Date: 12/30/2024

Proposed Solutions Report Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 10 Control Panel: 0 - EST EST 3 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Battery 51496961 1st Bldg 10 Main FACP Replace Battery T/M 51496962 1st Bldg 10 Main FACP Replace Battery T/M 51496964 1st Bldg 10 Power Supply Replace Battery T/M 51496965 1st Bldg 10 Power Supply Replace Battery T/M

PO #: (none) T/M

Page of 7 25 Inspection & Testing

Fire Equipment, Inc. Download Date: 12/30/2024

Inspection & Testing Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 10 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Duct Detector 1 1 0 1 1

Device Type Location ScanID Address Q1/23 Q1/24 Duct Detector Basement By B03 06270541 10-3- 112 02/16-P 03/06-P

Device Total: 1 Return to Executive Summary

Page of 8 25

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.

(NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Heat Detector 1 1 0 1 1

Device Type Location ScanID Address Q1/23 Q1/24 Heat Detector 1st Elev Lobby by Panel 51496967 10-2-1 02/16-P 03/06-P

Page of 9 25

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-19 Table 14.4.3.2 (17)(5)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Pull Station 9 9 0 9 9

Device Type Location ScanID Address Q1/23 Q1/24 Pull Station Basement By B02A 51496937 10-3-101 02/16-P 03/06-P Pull Station Basement By Stair 2 51496938 0-10-3-106 02/16-P 03/06-P Pull Station Basement Tunnel Exit 06270545 10-3-107 02/16-P 03/06-P Pull Station Basement B 14 at exit decontamination area 51496946 1 02/16-F 03/06-P

Pull Station 1st Front Foyer 06270539 10-3-109 02/16-P 03/06-P Pull Station 1st In Rm 112 06270540 10-3-110 02/16-P 03/06-P Pull Station 1st At Stair 1 65575441 10-3-108 03/06-P The above device replaced ScanID 06270536:

Pull Station 1st At Stair 1 06270536 10-3-108 02/16-P 03/06-R Pull Station 2nd At Sprinkler Mechanical 59133978 10-3-138 02/16-P 03/06-P Pull Station Attic At Stair 1 06270537 10-3 11 03/06-P The above device replaced ScanID 51496936:

Pull Station Attic At Stair 1 51496936 10-3 11 02/16-P 03/06-R

Device Total: 9 Return to Executive Summary

Page of 10 25

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Smoke Detector 7 7 0 7 7

Device Type Location ScanID Address Q1/23 Q1/24 Smoke Detector Basement By Rm B02 32221214 10-3-001 02/16-P 03/06-P Smoke Detector Basement Front Lobby 06270542 10-3-02 02/16-P 03/06-P Smoke Detector Basement At Stair 2 06270544 10-3-3 02/16-P 03/06-P Smoke Detector Basement Tunnel Exit 06270546 10-3-4 02/16-P 03/06-P Smoke Detector 1st Main Lobby 59133577 10-3-05 02/16-P 03/06-P Smoke Detector 1st In Rm 112 51496928 10-3-7 02/16-P 03/06-P Smoke Detector 2nd At Sprinkler Mechanical 59133979 10-3-6 02/16-P 03/06-P

Device Total: 7 Return to Executive Summary

Page of 11 25

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(1)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Horn/Strobe 15 15 0 15 15

Device Type Location ScanID Address Q1/23 Q1/24 Horn/Strobe Basement By B02A 34158647 0 02/16-P 03/06-P Horn/Strobe Basement By B03 34158646 0 02/16-P 03/06-P Horn/Strobe Basement Tunnel Exit 34158642 10 02/16-P 03/06-P Horn/Strobe Basement Outside B04, men's locker rm decontamination area 51496949 10 02/16-P 03/06-P

Horn/Strobe Basement in B04, men's locker rm decontamination area

51496950 10 02/16-P 03/06-P

Horn/Strobe Basement in decontamination rm 51496951 1 02/16-P 03/06-P Horn/Strobe Basement prep rm decontamination area 51496940 10 02/16-P 03/06-P

Horn/Strobe Basement Inside Womens prep room decontamination area

51496943 1 02/16-P 03/06-P

Horn/Strobe Basement Inside Mens decontamination prep area

51496941 10 02/16-P 03/06-P

Horn/Strobe Basement Inside Room B17 decontamination area

51496947 1 02/16-P 03/06-P

Horn/Strobe Basement At Exit decontamination room B14

51496945 1 02/16-P 03/06-P

Horn/Strobe Basement B 13 decontamination area 51496948 1 02/16-P 03/06-P Horn/Strobe 1st Front Foyer 51496955 0 02/16-P 03/06-P Horn/Strobe 1st At Hallway 51496926 1 02/16-P 03/06-P Horn/Strobe 1st South Stair 1 51496935 0 02/16-P 03/06-P

Device Total: 15 Return to Executive Summary

Page of 12 25

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Speaker/Strobe 9 9 0 9 9

Device Type Location ScanID Address Q1/23 Q1/24 Speaker/Strobe Basement By Stair 2 34158645 0 02/16-P 03/06-P Speaker/Strobe 1st In Rm 100A 51496932 0 02/16-P 03/06-P Speaker/Strobe 1st In Rm 100A 51496933 0 02/16-P 03/06-P Speaker/Strobe 1st In Rm 109 59133576 10 02/16-P 03/06-P Speaker/Strobe 1st By 112 51496927 0 02/16-P 03/06-P Speaker/Strobe 1st At Main library 51496931 10 02/16-P 03/06-P Speaker/Strobe 1st In Rm 112 65575442 1 03/06-P The above device replaced ScanID 51496930:

Speaker/Strobe 1st In Rm 112 51496930 1 02/16-P 03/06-R Speaker/Strobe 2nd At Sprinkler Mechanical 71417574 10 02/16-P 03/06-P Speaker/Strobe Attic At Stair 1 31146412 10-3 02/16-P 03/06-P

Page of 13 25

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Strobe 9 9 0 9 9

Device Type Location ScanID Address Q1/23 Q1/24 Strobe Basement in men's rest rm 51496954 1 02/16-P 03/06-P Strobe Basement in womens rest rm 51496953 1 02/16-P 03/06-P Strobe Basement in womens rest rm 51496952 1 02/16-P 03/06-P Strobe Basement Inside Mens decontamination area 51496942 1 02/16-P 03/06-P

Strobe Basement Inside Womens bathroom Decontamination area

51496944 1 02/16-P 03/06-P

Strobe 1st By Rm 107 51496957 0 02/16-P 03/06-P Strobe 1st In Rm 107 51496959 0 02/16-P 03/06-P Strobe 1st In Rm 106 51496958 0 02/16-P 03/06-P Strobe 1st By FACP 51496966 0 02/16-P 03/06-P

Page of 14 25

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment.

NFPA 90A (2024) 6.4.1

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Duct Detector 1 1 0 1 1

Device Type Location ScanID Address Q1/23 Q1/24 Duct Detector Basement By B03 06270541 0-3- 112 02/16-P 03/06-P

Page of 15 25

Fire Equipment, Inc. Download Date: 12/30/2024

LS 02.01.34 EP 02 Protected master fire alarm control panel

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Control Panel 1 1 0 1 1

Device Type Location ScanID Address Q1/23 Q1/24 Control Panel 1st Bldg 10 By Outside Elevator

Lobby 51496960 0 02/16-P 03/06-P

Page of 16 25

Fire Equipment, Inc. Download Date: 12/30/2024

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Verify the correct operation and identification of annunciators. If provided, verify the correct operation of annunciator under a fault condition. (NFPA 72-22 Table 14.4.3.2 (11)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Annunciator 1 1 0 1 1

Device Type Location ScanID Address Q1/23 Q1/24 Annunciator 1st Front Foyer 51496956 0 02/16-P 03/06-P

Page of 17 25

Fire Equipment, Inc. Download Date: 12/30/2024

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Battery 4 0 4 4 4

Device Type Location ScanID Address Q1/23 Q1/24 Battery 1st Bldg 10 Power Supply 51496964 0-12V 02/16-P 03/06-F Battery 1st Bldg 10 Power Supply 51496965 0-12V 02/16-P 03/06-F Battery 1st Bldg 10 Main FACP 51496961 0-12V55A 02/16-P 03/07-F Battery 1st Bldg 10 Main FACP 51496962 0-12V55A 02/16-P 03/07-F

Device Total: 4 Return to Executive Summary

Page of 18 25

Fire Equipment, Inc. Download Date: 12/30/2024

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Power Supply 1 1 0 1 1

Device Type Location ScanID Address Q1/23 Q1/24 Power Supply 1st Bldg 10 51496963 0 02/16-P 03/06-P

Page of 19 25 Service Summary

Fire Equipment, Inc. Download Date: 12/30/2024

Service Summary Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 10 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Failed/Other Battery Tested 4

Total 4

Passed Annunciator Tested 1 Control Panel Tested 1 Duct Detector Tested 1 Heat Detector Visually Checked 1 Horn/Strobe Tested 15 Power Supply Tested 1 Pull Station Tested 9 Smoke Detector Tested/Cleaned 6 Smoke Detector Visually Checked 1 Speaker/Strobe Tested 9 Strobe Tested 9

Total 54 Grand Total 58

Page of 20 25 Auxiliary Functions Testing

Fire Equipment, Inc. Download Date: 12/30/2024

Auxiliary Functions Testing Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 10 Control Panel: 10 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Heat Detector

Elevator Recall 1st Elev Lobby by Panel Passed 51496967

Smoke Detector Elevator Recall Basement Front Lobby Passed 06270542 Elevator Recall 1st Main Lobby Passed 59133577 javascript:editViewDevice('51496967');

javascript:editViewDevice('06270542');

javascript:editViewDevice('59133577');

Page of 21 25 Battery & Power Supply Testing

Fire Equipment, Inc. Download Date: 12/30/2024

Battery & Power Supply Testing Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 10 Control Panel: 0 - EST EST 3 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Battery

Failed/Other Sealed Lead Acid 1st Bldg 10 Main FACP 55 12 Sealed Lead Acid 1st Bldg 10 Main FACP 55 12 Sealed Lead Acid 1st Bldg 10 Power Supply 8 12 Sealed Lead Acid 1st Bldg 10 Power Supply 8 12

Page of 22 25 Inventory & Warranty Report

Fire Equipment, Inc. Download Date: 12/30/2024

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 10 Control Panel: 0 - EST EST 3 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Annunciator Control 1.72% 1

Battery Control 6.90% 4

Control Panel Control 1.72% 1

Duct Detector Initiating 1.72% 1

Heat Detector Initiating 1.72% 1

Horn/Strobe Indicating 25.86% 15

Power Supply Control 1.72% 1

Pull Station Initiating 15.52% 9

Smoke Detector Initiating 12.07% 7

Speaker/Strobe Indicating 15.52% 9

Strobe Indicating 15.52% 9

Type Qty Model # Description Install Date

In Service - 3 Years to 5 Years

EST

Annunciator 1 3-RLCM/D 04/27/2020 Control Panel 1 EST 3 Addressable 04/27/2020 Power Supply 1 04/27/2020 Pull Station 1 SIGA-278 Single Action 04/27/2020

Edwards Speaker/Strobe 1 G1RF-VM 04/27/2020

Est Horn/Strobe 2 G1RF-VM 04/27/2020 Speaker/Strobe 1 G1RF-VM 04/27/2020 Speaker/Strobe 1 G4HFRF-S2VMC 04/27/2020 Strobe 4 G1RF-VM 04/27/2020

Power Sonic Battery 4 Sealed Lead Acid 04/27/2020

System Sensor Horn/Strobe 1 G1RF-VM 04/27/2020 Horn/Strobe 1 G4HFRF-S2VMC 04/27/2020 Speaker/Strobe 1 G4HFRF-S2VMC 04/27/2020

Building: Bedford VAMC Bldg 10 Control Panel: 1 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last

Page of 23 25

Fire Equipment, Inc. Download Date: 12/30/2024 year, and devices installed for two years or more are grouped together for easy reference.

Type Qty Model # Description Install Date

In Service - 3 Years to 5 Years

EST

Horn/Strobe 1 g1r- vm 04/27/2020 Horn/Strobe 1 g1r-vm 04/27/2020 Horn/Strobe 2 g1rf-vm 04/27/2020 Pull Station 1 siga 278 Single Action 04/27/2020 Strobe 1 SIGA-PD 04/27/2020 Strobe 1 g1rf-vm 04/27/2020

Est Horn/Strobe 2 G4HFRF-S2VMC 04/27/2020 Speaker/Strobe 1 G1RF-VM 04/27/2020

System Sensor Strobe 3 G4HFRF-S2VMC 04/27/2020

Building: Bedford VAMC Bldg 10 Control Panel: 10 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Type Qty Model # Description Install Date

In Service - 2 Years to 3 Years Fast

Smoke Detector 1 2551f Photoelectric 03/10/2022

Fci Pull Station 1 ms-6 Single Action 03/10/2022

Wheelock Horn/Strobe 1 03/10/2022

In Service - 3 Years to 5 Years

EST

Heat Detector 1 SIGA-PD Rate-of-Rise 04/27/2020 Horn/Strobe 1 G1RF-VM 04/27/2020 Horn/Strobe 1 SIGA-PD 04/27/2020 Pull Station 1 3-RLCM/D Single Action 04/27/2020 Pull Station 1 SIGA-278 Single Action 04/27/2020 Smoke Detector 3 2151fs Photoelectric 04/27/2020 Smoke Detector 1 SIGA-PD 04/27/2020 Speaker/Strobe 1 2151fs 04/27/2020 Speaker/Strobe 1 G4HFRF-S2VMC 04/27/2020

Est Horn/Strobe 1 g1r-vm 04/27/2020 Pull Station 2 ms-6 Single Action 04/27/2020

Page of 24 25

Fire Equipment, Inc. Download Date: 12/30/2024

Speaker/Strobe 1 G1RF-VM 04/27/2020 Speaker/Strobe 1 ms-6 04/27/2020

FAST

Smoke Detector 1 Photoelectric 04/27/2020 Smoke Detector 1 2115f Photoelectric 04/27/2020

FCI

Pull Station 2 ms-6 Single Action 04/27/2020

System Sensor Horn/Strobe 1 g1r-vm 04/27/2020 fast Duct Detector 1 Photoelectric 04/27/2020

Page of 25 25 Zone Address Report

Fire Equipment, Inc. Download Date: 12/30/2024

Zone Address Report Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 10 Control Panel: 0 - EST EST 3 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID 10-3-106 Pull Station Basement By Stair 2 Single Action 51496938

12V Battery 1st Bldg 10 Power Supply Sealed Lead Acid 51496964 12V Battery 1st Bldg 10 Power Supply Sealed Lead Acid 51496965

12V55A Battery 1st Bldg 10 Main FACP Sealed Lead Acid 51496961 12V55A Battery 1st Bldg 10 Main FACP Sealed Lead Acid 51496962

Building: Bedford VAMC Bldg 10 Control Panel: 10 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID Zone/Circuit: 3

11 Pull Station Attic At Stair 1 Single Action 06270537 Speaker/Strobe Attic At Stair 1 31146412

2-1 Heat Detector 1st Elev Lobby by Panel Rate-of-Rise 51496967 3-001 Smoke Detector Basement By Rm B02 Photoelectric 32221214 3-02 Smoke Detector Basement Front Lobby 06270542 3-3 Smoke Detector Basement At Stair 2 Photoelectric 06270544 3-4 Smoke Detector Basement Tunnel Exit Photoelectric 06270546 3-05 Smoke Detector 1st Main Lobby Photoelectric 59133577 3-6 Smoke Detector 2nd At Sprinkler Mechanical Photoelectric 59133979 3-7 Smoke Detector 1st In Rm 112 Photoelectric 51496928

3-101 Pull Station Basement By B02A Single Action 51496937 3-107 Pull Station Basement Tunnel Exit Single Action 06270545 3-108 Pull Station 1st At Stair 1 Single Action 65575441 3-109 Pull Station 1st Front Foyer Single Action 06270539 3-110 Pull Station 1st In Rm 112 Single Action 06270540 3-138 Pull Station 2nd At Sprinkler Mechanical Single Action 59133978 3- 112 Duct Detector Basement By B03 Photoelectric 06270541 javascript:editViewDevice('51496938');

javascript:editViewDevice('51496964');

javascript:editViewDevice('51496965');

javascript:editViewDevice('51496961');

javascript:editViewDevice('51496962');

javascript:editViewDevice('06270537');

javascript:editViewDevice('31146412');

javascript:editViewDevice('51496967');

javascript:editViewDevice('32221214');

javascript:editViewDevice('06270542');

javascript:editViewDevice('06270544');

javascript:editViewDevice('06270546');

javascript:editViewDevice('59133577');

javascript:editViewDevice('59133979');

javascript:editViewDevice('51496928');

javascript:editViewDevice('51496937');

javascript:editViewDevice('06270545');

javascript:editViewDevice('65575441');

javascript:editViewDevice('06270539');

javascript:editViewDevice('06270540');

javascript:editViewDevice('59133978');

javascript:editViewDevice('06270541');

Fire Alarm and Life Safety System Inspection Certificate
Discrepancy Report
Proposed Solutions Report
Inspection & Testing
Service Summary
Auxiliary Functions Testing
Battery & Power Supply Testing
Inventory & Warranty Report
Zone Address Report

File details come from the government source that posted it. Updated .