2024-02-22_Bedford-VAMC-Bldg-7_FireScan.pdf

PDF 171 KB Posted

Attached to
Z2DA--518-22-111 Elevator Replacement Ph. 3 Federal contract opportunity
Solicitation number
36C24125B0003
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1

About this file

This is a Fire Alarm and Life Safety System Inspection Certificate report completed by Fire Equipment, Inc. for Building 7 at the Bedford VA Medical Center in Massachusetts. The inspection was conducted on February 22, 2024, using an EST 3 fire alarm control panel system installed in April 2020.

The inspection revealed several system deficiencies requiring attention, including: one failed pull station (damaged/worn), three failed speaker/strobes (one inaccessible, two with failed operation), one failed strobe, a ground fault in the control panel, and two failed batteries. The building contains a total of 185 devices including 58 smoke detectors, 60 speaker/strobes, 24 pull stations, 14 releasing devices, 10 strobes, 5 heat detectors, and 4 duct detectors. All auxiliary functions including elevator recall, AHU shutdown, and door holder operations were tested with most passing inspection. The report provides detailed documentation of each device's location, test results, and proposed solutions for failed components, with repairs available on a Time and Materials basis.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--518-22-111 Elevator Replacement Ph. 3, newest first.
File Type Posted
SF 1409 36C24125B0003.pdf PDF
36C24125B0003 0006.docx DOCX document
Construction Specification Institute Division Breakdown.xlsx XLSX spreadsheet
36C24125B0003 - EMR Rating Form.pdf PDF
36C24125B0003 0005.docx DOCX document
518-22-111 - Elevator Replacement Phase 3 - 100 CD - SPECIFICATIONS - updated 7-25-24.pdf PDF
2024-03-07_Bedford-VAMC-Bldg-10_FireScan.pdf PDF
2024-08-20_Bedford-VAMC-Bldg-6_FireScan.pdf PDF
RFI Answers 2nd Batch.docx DOCX document
RFI Answers 1st Batch.docx DOCX document
36C24125B0003 0004.docx DOCX document
2024-02-23_Bedford-VAMC-Bldg-9_FireScan.pdf PDF
36C24125B0003 0003.docx DOCX document
Elevator Site Visit sign in 12-20-24.pdf PDF
36C24125B0003 0002.docx DOCX document
Elevator Site Visit sign in 12-4-24.pdf PDF
36C24125B0003 0001.docx DOCX document
518-22-111 - Elevator Replacement Phase 3 - 100 CD - SPECIFICATIONS.pdf PDF
36C24125B0003.docx DOCX document
518-22-111 - Elevator Replacement Phase 3 - 100 CD - DRAWINGS.pdf PDF
SOW Elevator Replacement Ph 3.pdf PDF
SAM WD MA20240001 revised 10-11-2024.pdf PDF
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Alarm and Life Safety System Inspection Certificate

For

Bedford VAMC Bldg 7 200 Springs Rd

Bedford, MA 01730

Kinetix has performed this inspection and testing service in compliance with The Joint Commission /VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards

This Inspection was performed in accordance with applicable NFPA effective October 1, 2023.

Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Inspection Completion Date Feb 22, 2024

Building: Bedford VAMC Bldg 7 Company: Fire Equipment, Inc.

Contact: Brian Reid Contact: Ryan Michaud

Title: Project Engineer Title: Fire Alarm Technician Fire Alarm Testing Report

Page of 2 31 Executive Summary

Fire Equipment, Inc. Download Date: 12/30/2024

Executive Summary Generated by: BuildingReports.com

Building Information Building: Bedford VAMC Bldg 7 Contact: Brian Reid Address: 200 Springs Rd Phone: 7816872000 Address: Fax:

City/State/Zip: Bedford, MA 01730 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire Equipment, Inc. Inspector: Ryan Michaud Address: 20 Hall Street Phone: 617-872-6161 Address: Fax:

City/State/Zip: Medford, MA 02155 Mobile:

Country: United States of America Email: rmichaud@feinewengland.com

System Control Unit Manufacturer: EST Inspection Date: 02/16/2024 IDC Style:

Model Number: EST 3 Install Date: 04/23/2020 SLC Style:

Software Version: Version Date: 04/23/2020 NAC Style:

Location: Basement Bldg 7 Current Protection:

Monitoring Company: Phone: Account #:

Central Station Signal Verification Type: Mfg: Model #:

Test Time/Date: Restore Time:

Page of 3 31

Fire Equipment, Inc. Download Date: 12/30/2024

Inspection Completion Date: Feb 22, 2024 Building: Bedford VAMC Bldg 7 EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors.

NFPA 72 (2022) Table 14.4.3.2 (17)

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Duct Detector 4 4 0 4 0 4 Heat Detector 5 5 0 5 0 5 Pull Station 24 23 1 24 0 24 Smoke Detector 58 58 0 58 0 58

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.

NFPA 72 (2022) Table 14.4.3.2 (22)

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Horn/Strobe 4 4 0 4 0 4 Releasing Device 14 14 0 14 0 14 Speaker/Strobe 60 57 3 60 0 60 Strobe 10 9 1 10 0 10

EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Duct Detector 4 4 0 4 0 4

LS 02.01.34 EP 02 Protected master fire alarm control panel

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Control Panel 1 0 1 1 0 1

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Devices Tested This

Quarter Pass Fail Tested YTD

(2024) Untested YTD

(2024) Total

Quantity Battery 4 2 2 4 0 4 Power Supply 1 1 0 1 0 1

Total Device Count: 185

Page of 4 31

Fire Equipment, Inc. Download Date: 12/30/2024

Certification

Company: Fire Equipment, Inc. Building: Bedford VAMC Bldg 7

Inspector: Ryan Michaud Contact: Brian Reid

Page of 5 31 Discrepancy Report

Fire Equipment, Inc. Download Date: 12/30/2024

Discrepancy Report Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 7 Control Panel: 0 - EST EST 3 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade

No items found during this inspection.

ScanID Location Problem Address Reference

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22) Speaker/Strobe

51496059 Basement Restroom B06 Inaccessible 0 NFPA72 14.2.2.2.2

51496198 Attic Northwest Failed Annunciation

0 NFPA72 14.2.2.2.2

59133958 Attic Southeast End Failed Operation 0 NFPA72 14.2.2.2.2

Strobe

51496199 Attic Northwest Failed Annunciation

0 NFPA72 14.2.2.2.2

LS 02.01.34 EP 02 Protected master fire alarm control panel Control Panel

51496044 Basement Bldg 7 Ground Fault 0 NFPA72 12.2.4.1

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Battery

51496041 Basement Bldg 7 Failed Test 0-12V8A NFPA72 Table

14.4.3.2 (9)

51496042 Basement Bldg 7 Failed Test 0-12V8A NFPA72 Table

14.4.3.2 (9)

Code References NFPA72 14.2.2.2.2 System deficiencies shall be corrected.

NFPA72 12.2.4.1 All fire alarm systems shall test free of grounds.

NFPA72 Table 14.4.3.2 (9) Replace any battery cell/unit if the temperature is greater than 18F above ambient. Replace the battery when any cell/unit measures a voltage less than 13.26 volts. Replace the battery when any cell/unit has an internal ohmic value outside of the acceptable range.

Building: Bedford VAMC Bldg 7 Control Panel: 7 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

javascript:editViewDevice('51496059');

javascript:editViewDevice('51496198');

javascript:editViewDevice('59133958');

javascript:editViewDevice('51496199');

javascript:editViewDevice('51496044');

javascript:editViewDevice('51496041');

javascript:editViewDevice('51496042');

Page of 6 31 Discrepancy Report

Fire Equipment, Inc. Download Date: 12/30/2024

Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade

No items found during this inspection.

ScanID Location Problem Address Reference

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Pull Station

51496106 1st At Stair 1 Damaged/Worn 7-5-156 NFPA72 14.2.2.2.2

Code References NFPA72 14.2.2.2.2 System deficiencies shall be corrected.

javascript:editViewDevice('51496106');

Page of 7 31 Proposed Solutions Report

Fire Equipment, Inc. Download Date: 12/30/2024

Proposed Solutions Report Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 7 Control Panel: 0 - EST EST 3 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.

NFPA 72 (2022) Table 14.4.3.2 (22)

Speaker/Strobe 51496059 Basement Restroom B06 G4HFRF-

S2VMC

T/M

51496198 Attic Northwest Service G4HFRF-

S2VMC

T/M

59133958 Attic Southeast End Service G4HFRF-

S2VMC

T/M

Strobe 51496199 Attic Northwest Service G1RF-VM T/M

LS 02.01.34 EP 02 Protected master fire alarm control panel

Control Panel 51496044 Basement Bldg 7 Service EST 3 T/M

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Battery 51496041 Basement Bldg 7 Replace Battery sla 1075 T/M 51496042 Basement Bldg 7 Replace Battery sla-1075 T/M

Building: Bedford VAMC Bldg 7 Control Panel: 7 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Pull Station 51496106 1st At Stair 1 Replace SIGA-278 T/M

PO #: (none) T/M

Page of 8 31 Notes & Recommendations

Fire Equipment, Inc. Download Date: 12/30/2024

Notes & Recommendations Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 7 Control Panel: 0 - EST EST 3 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

Note Device Type Location Comment ScanID

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.

NFPA 72 (2022) Table 14.4.3.2 (22)

1 Speaker/Strobe Attic Northwest Failed Annunciation

51496198

Strobe portion works, speaker portion does not.

2 Speaker/Strobe Attic Southeast End Failed Operation 59133958

Strobe portion works, speakers portion does not javascript:editViewDevice('51496198');

javascript:editViewDevice('59133958');

Page of 9 31 Inspection & Testing

Fire Equipment, Inc. Download Date: 12/30/2024

Inspection & Testing Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 7 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Duct Detector 4 4 0 4 4

Device Type Location ScanID Address Q3/23 Q1/24 Duct Detector Basement Inside Rm B02A 51496080 0-7-5-002 07/21-P 02/16-P Duct Detector Attic Inside Elev Equip Rm 51496195 1-12-004 07/21-P 02/16-P Duct Detector Attic Attic North 51496197 7-12-002 07/21-P 02/16-P Duct Detector Attic South Stair 1 51496200 7-12-003 07/21-P 02/16-P

Device Total: 4 Return to Executive Summary

Page of 10 31

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.

(NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Heat Detector 5 5 0 5 5

Device Type Location ScanID Address Q3/23 Q1/24 Heat Detector Basement Elev Eq Room 51496910 7-12-132 07/21-P 02/16-P Heat Detector Basement Elev Eq Room 58984202 0 07/21-P 02/16-P Heat Detector Basement Elev Eq Room 58984201 0 07/21-P 02/16-P Heat Detector Basement Elev Eq Room 58984200 0 07/21-P 02/16-P Heat Detector Basement Elev Eq Room 58984199 0 07/21-P 02/16-P

Device Total: 5 Return to Executive Summary

Page of 11 31

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-19 Table 14.4.3.2 (17)(5)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Pull Station 24 23 1 24 24

Device Type Location ScanID Address Q3/23 Q1/24 Pull Station Basement North Hall trailer 51496060 0-7-12-149 02/16-P Pull Station Basement Rear Hall 51496062 0-7-12-150 07/21-P 02/16-P Pull Station Basement Left Entrance trailer 51496066 0-7-12-151 07/21-P 02/16-P Pull Station Basement South Hall trailer 51496064 1-7-12-148 07/21-P 02/16-P Pull Station Basement Tunnel to Bldg 8 51496048 7-5-128 07/21-P 02/16-P Pull Station Basement Tunnel to Bldg 61 51496074 7-5-126 07/21-P 02/16-P Pull Station Basement At Stair 3 51496051 7-5-127 07/21-P 02/16-P Pull Station Basement At Stair 1 51496057 7-5-138 07/21-P 02/16-P Pull Station Basement Tunnel to Bldg 6 51496086 7-5-134 07/21-P 02/16-P Pull Station Basement South In Rm B02 51496081 7-5-143 07/21-P 02/16-P Pull Station Basement North In Rm B08E 51496076 7-5-163 07/21-P 02/16-P Pull Station 1st South in Rm 123 51496185 7-5-161 07/21-P 02/16-P Pull Station 1st South Dining 123 51496099 7-5-160 07/21-P 02/16-P Pull Station 1st At Stair 3 51496087 7-5-159 07/21-P 02/16-P Pull Station 1st In Rm 117A @ Stair 4 51496093 0-7-5-158 07/21-P 02/16-P Pull Station 1st North in Rm 128 51496156 7-5-162 07/21-P 02/16-P Pull Station 1st South in rm 134A 51496114 7-5-157 07/21-P 02/16-P Pull Station 1st At Stair 1 51496106 7-5-156 07/21-P 02/16-F Pull Station 2nd North 51496204 7-12-131 07/21-P 02/16-P Pull Station 2nd South Stair 1 51496147 7-12-128 07/21-P 02/16-P Pull Station 2nd South Stair 5 51496153 7-12-129 07/21-P 02/16-P Pull Station 2nd South 51496140 0-7-12-141 07/21-P 02/22-P Pull Station 2nd North Stair 4 51496211 0-7-12-130 07/21-P 02/22-P Pull Station Attic Attic by Door 51496189 0-7-12-126 07/21-P 02/16-P

Device Total: 24 Return to Executive Summary

Page of 12 31

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Smoke Detector 58 58 0 58 58

Device Type Location ScanID Address Q3/23 Q1/24 Smoke Detector Basement Elev Eq Room 58984198 0 07/21-P 02/16-P Smoke Detector Basement Tunnel to Bldg 61 51496046 0-7-5-006 07/21-P 02/16-P Smoke Detector Basement Corr Outside Rm B06 51496053 7-5-005 07/21-P 02/16-P Smoke Detector Basement Elev Lobby 51496055 7-5-001 07/21-P 02/16-P Smoke Detector Basement Tunnel to Bldg 8 51496050 7-5-004 07/21-P 02/16-P Smoke Detector 1st Elev Lobby 51496187 7-5-011 07/21-P 02/16-P Smoke Detector 1st Corr by Rm 126 51496103 0-7-5-017 07/21-P 02/16-P Smoke Detector 1st South Corr by Kitchen 51496096 7-5-029 07/21-P 02/16-P Smoke Detector 1st South Corr Rm 123 51496102 7-5-018 07/21-P 02/16-P Smoke Detector 1st West Dining 123 51496101 7-5-019 07/21-P 02/16-P Smoke Detector 1st West Dining 123 51496097 7-5-020 07/21-P 02/16-P Smoke Detector 1st Corr Fire Doors by Rm 105 51496095 7-5-021 07/21-P 02/16-P Smoke Detector 1st North Corr by rm 104 51496094 7-5-030 07/21-P 02/16-P Smoke Detector 1st North Hall Outside Rm 111 51496088 7-5-022 07/21-P 02/16-P Smoke Detector 1st Corr by 112 51496089 7-5-023 07/21-P 02/16-P Smoke Detector 1st Corr 115 51496090 7-5-026 07/21-P 02/16-P Smoke Detector 1st Northeast Rm 117 CTR 1 51496091 7-5-027 07/21-P 02/16-P Smoke Detector 1st Northeast Rm 117 CTR 2 51496092 0-7-5-028 07/21-P 02/16-P Smoke Detector 1st North Corr by Rm 110B 51496182 7-5-025 07/21-P 02/16-P Smoke Detector 1st In Rm 110J 51496179 0-7-5-049 07/21-P 02/16-P Smoke Detector 1st In Rm 110c 59133956 7-5-052 07/21-P 02/16-P Smoke Detector 1st In Rm 110K 51496180 0-7-5-051 07/21-P 02/16-P Smoke Detector 1st In Rm 110B 51496175 0-7-5-050 07/21-P 02/16-P Smoke Detector 1st South Hall Outside Rm 125 51496104 7-5-012 07/21-P 02/16-P Smoke Detector 1st Outside Rm 129 51496105 7-5-009 07/21-P 02/16-P Smoke Detector 1st Corr 132A Closet 51496107 7-5-013 07/21-P 02/16-P Smoke Detector 1st South By Rm 133 51496108 7-5-040 07/21-P 02/16-P Smoke Detector 1st East in Rm 134B 51496171 0-7-5-042 07/21-P 02/16-P Smoke Detector 1st East in Cubicle 7-8 51496168 0-7-5-047 07/21-P 02/16-P Smoke Detector 1st East in Cubicle 9-10 51496169 0-7-5-048 07/21-P 02/16-P Smoke Detector 1st East in Rm 134F 51496167 0-7-5-045 07/21-P 02/16-P Smoke Detector 1st East in Rm 134H 51496166 0-7-5-046 07/21-P 02/16-P Smoke Detector 1st East in Rm 134J 51496165 0-7-5-044 07/21-P 02/16-P Smoke Detector 1st East in Rm 134C 51496170 0-7-5-043 07/21-P 02/16-P Smoke Detector 1st East in Cube 15-16 51496164 0-7-5-041 07/21-P 02/16-P Smoke Detector 1st South Corr by Rm 135B 51496113 7-5-016 07/21-P 02/16-P

Page of 13 31

Fire Equipment, Inc. Download Date: 12/30/2024

Device Type Location ScanID Address Q3/23 Q1/24 Smoke Detector 1st Rm 131K 51496158 0-7-5-038 07/21-P 02/16-P Smoke Detector 1st Rm 131E 51496161 0-7-5-033 07/21-P 02/16-P Smoke Detector 1st Rm 131H 51496160 0-7-5-032 07/21-P 02/16-P Smoke Detector 1st Rm 131C 51496162 0-7-5-034 07/21-P 02/16-P Smoke Detector 1st South Corr by Rm 131B 51496109 7-5-037 07/21-P 02/16-P Smoke Detector 1st South Corr by Rm 131F 51496110 7-5-036 07/21-P 02/16-P Smoke Detector 1st 132 Closet 51496111 7-5-014 07/21-P 02/16-P Smoke Detector 1st South Corr by Rm 134A 51496112 7-5-015 07/21-P 02/16-P Smoke Detector 1st In Rm 127 59133957 1 07/21-P 02/16-P Smoke Detector 1st South in Rm 125 51496172 7-5-055 07/21-P 02/16-P Smoke Detector 1st Rm 131J 51496159 0-7-5-035 07/21-P 02/16-P Smoke Detector 1st Rm 131A 51496163 0-7-5-039 07/21-P 02/16-P Smoke Detector 1st In Rm 110A 51496177 0-7-5-054 07/21-P 02/16-P Smoke Detector 1st North Corr by Rm 110E 51496183 7-5-024 07/21-P 02/16-P Smoke Detector 1st In Rm 110H 51496178 0-7-5-053 07/21-P 02/16-P Smoke Detector 1st IRM Closet 51496188 7-5-010 07/21-P 02/16-P Smoke Detector 2nd Elev Lobby 51496136 7-12-5 07/21-P 02/16-P Smoke Detector 2nd Corr inside Rm 223 51496143 7-12-006 07/21-P 02/16-P Smoke Detector 2nd North Corr by Rm 204 51496201 0-7-12-007 07/21-P 02/16-P Smoke Detector 2nd North Corr Outside Rm 208 51496205 0-7-12-001 07/21-P 02/16-P Smoke Detector 2nd IRM Closet 51496137 7-12-9 07/21-P 02/16-P Smoke Detector Attic At Elevator Machine room 51496909 7-12-8 07/21-P 02/16-P Smoke Detector Penthouse Elevator machine room 59133315 7-12-8 07/21-P 02/22

Removed

Device Total: 58 Return to Executive Summary

Page of 14 31

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(1)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Horn/Strobe 4 4 0 4 4

Device Type Location ScanID Address Q3/23 Q1/24 Horn/Strobe Basement Rear Hall trailer 51496063 0 07/21-P 02/16-P Horn/Strobe Basement South Hall trailer 51496065 0 07/21-P 02/16-P Horn/Strobe Basement North Hall trailer 51496061 0 07/21-P 02/16-P The above device replaced ScanID 51496861:

Horn/Strobe Basement North Hall trailer 51496861 0 07/21-P 02/16-R Horn/Strobe 1st Inside Bathroom 136 71417608 7-7-5-035 07/21-P 02/16-P

Page of 15 31

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Releasing Device 14 14 0 14 14

Device Type Location ScanID Address Q3/23 Q1/24 Releasing Device Basement Doors by B06 18142243 0 07/21-P 02/16-P Releasing Device Basement Doors by B06 18142242 0 07/21-P 02/16-P Releasing Device Basement To Bldg 61 18142239 0 07/21-P 02/16-P Releasing Device Basement To Bldg 61 18142238 0 07/21-P 02/16-P Releasing Device Basement Door to Bldg 8 18142234 0 07/21-P 02/16-P Releasing Device Basement Door to Bldg 8 18142235 0 07/21-P 02/16-P Releasing Device 1st Doors to Dining Rm 123 18142261 0 07/21-P 02/16-P Releasing Device 1st Doors to Dining Rm 123 18142260 0 07/21-P 02/16-P Releasing Device 1st Door to 102A 18142262 0 07/21-P 02/16-P Releasing Device 1st Door to 102A 18142265 0 07/21-P 02/16-P Releasing Device 2nd Door to Rm 223 51496138 0 07/21-P 02/16-P Releasing Device 2nd By Rm 204 18142253 0 07/21-P 02/16-P Releasing Device 2nd By Rm 204 18142252 0 07/21-P 02/16-P Releasing Device 2nd Elev Lobby Door 18142254 0 07/21-P 02/16-P

Device Total: 14 Return to Executive Summary

Page of 16 31

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Speaker/Strobe 60 57 3 60 60

Device Type Location ScanID Address Q3/23 Q1/24 Speaker/Strobe Basement By B15 51496047 0 07/21-P 02/16-P Speaker/Strobe Basement By Stair 4 51496049 0 07/21-P 02/16-P Speaker/Strobe Basement Outside Bathroom B06 51496052 7 07/21-P 02/16-P Speaker/Strobe Basement In Rm B18A 51496056 0 07/21-P 02/16-P Speaker/Strobe Basement By Rm B22 51496058 0 07/21-P 02/16-P Speaker/Strobe Basement By Rm B21 51496085 0 07/21-P 02/16-P Speaker/Strobe Basement By 202A 51496078 0 07/21-P 02/16-P Speaker/Strobe Basement South In Rm B02 51496082 0 07/21-P 02/16-P Speaker/Strobe Basement In Rm B08 51496075 0 07/21-P 02/16-P Speaker/Strobe Basement North In Rm B08E 51496077 0 07/21-P 02/16-P Speaker/Strobe Basement By B02 51496079 0 07/21-P 02/16-P Speaker/Strobe Basement Restroom B06 51496059 0 07/21-P 02/16-F Speaker/Strobe 1st By 102A 51496121 0 07/21-P 02/16-P Speaker/Strobe 1st In 102A 51496122 0 07/21-P 02/16-P Speaker/Strobe 1st By Rm 123A 51496124 0 07/21-P 02/16-P Speaker/Strobe 1st By Rm 105 51496120 0 07/21-P 02/16-P Speaker/Strobe 1st By Rm 106 51496119 0 07/21-P 02/16-P Speaker/Strobe 1st By Rm 114 51496115 0 07/21-P 02/16-P Speaker/Strobe 1st By Rm 119 51496118 0 07/21-P 02/16-P Speaker/Strobe 1st by Rm 117A 51496173 0 07/21-P 02/16-P Speaker/Strobe 1st In Rm 117A 51496174 0 07/21-P 02/16-P Speaker/Strobe 1st By Rm 110A 51496181 0 07/21-P 02/16-P Speaker/Strobe 1st By Rm 110E 51496184 0 07/21-P 02/16-P Speaker/Strobe 1st By Rm 127 51496125 0 07/21-P 02/16-P Speaker/Strobe 1st North in Rm 128 51496157 0 07/21-P 02/16-P Speaker/Strobe 1st By Rm 135 51496127 0 07/21-P 02/16-P Speaker/Strobe 1st In Rm 133 51496130 0 07/21-P 02/16-P Speaker/Strobe 1st by Rm 134K 51496131 0 07/21-P 02/16-P Speaker/Strobe 1st By Rm 134H 51496132 0 07/21-P 02/16-P Speaker/Strobe 1st By Rm 135B 51496133 0 07/21-P 02/16-P Speaker/Strobe 1st By Rm 131E 51496129 0 07/21-P 02/16-P Speaker/Strobe 1st Elev Lobby 51496186 0 07/21-P 02/16-P Speaker/Strobe 1st By Stair 2 51496123 0 07/21-P 02/16-P Speaker/Strobe 1st By Rm 131A 51496128 0 07/21-P 02/16-P Speaker/Strobe 1st In Rm 121 71417611 7 07/21-P 02/16-P Speaker/Strobe 2nd By Rm 203 51496134 0 07/21-P 02/16-P Speaker/Strobe 2nd By Rm 202 51496155 0 07/21-P 02/16-P

Page of 17 31

Fire Equipment, Inc. Download Date: 12/30/2024

Device Type Location ScanID Address Q3/23 Q1/24 Speaker/Strobe 2nd By Rm 227 51496145 0 07/21-P 02/16-P Speaker/Strobe 2nd By 223A 51496139 0 07/21-P 02/16-P Speaker/Strobe 2nd Office 223 51496141 0 07/21-P 02/16-P Speaker/Strobe 2nd By Rm 204 51496202 0 07/21-P 02/16-P Speaker/Strobe 2nd By Rm 208 51496203 0 07/21-P 02/16-P Speaker/Strobe 2nd By Rm 214 51496212 0 07/21-P 02/16-P Speaker/Strobe 2nd By Rm 219 51496208 0 07/21-P 02/16-P Speaker/Strobe 2nd Near Rm 217D 51496209 0 07/21-P 02/16-P Speaker/Strobe 2nd In Rm 217A 51496210 0 07/21-P 02/16-P Speaker/Strobe 2nd By Rm 210G 51496213 0 07/21-P 02/16-P Speaker/Strobe 2nd By Rm 233B 51496148 0 07/21-P 02/16-P Speaker/Strobe 2nd By Rm 234B 51496151 0 07/21-P 02/16-P Speaker/Strobe 2nd By Rm 234F 51496152 0 07/21-P 02/16-P Speaker/Strobe 2nd South Stair 5 51496154 0 07/21-P 02/16-P Speaker/Strobe 2nd By Rm 231C 51496149 0 07/21-P 02/16-P Speaker/Strobe 2nd Alcove in office 51496142 0 07/21-P 02/16-P Speaker/Strobe Attic Outside elev Eqip Rm 51496193 0 07/21-P 02/16-P Speaker/Strobe Attic Inside Elev Equip Rm 51496194 0 07/21-P 02/16-P Speaker/Strobe Attic Outside elev Equip Rm SW 51496196 0 07/21-P 02/16-P Speaker/Strobe Attic East of Door 51496191 0 07/21-P 02/16-P Speaker/Strobe Attic Attic by Door 51496192 0 02/16-P The above device replaced ScanID 51496190:

Speaker/Strobe Attic Attic by Door 51496190 0 07/21-P 02/16-R Speaker/Strobe Attic Southeast End 59133958 0 07/21-P 02/16-F Speaker/Strobe Attic Northwest 51496198 0 07/21-P 02/16-F

Device Total: 60 Return to Executive Summary

Page of 18 31

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Strobe 10 9 1 10 10

Device Type Location ScanID Address Q3/23 Q1/24 Strobe 1st In Rm 113 51496116 0 07/21-P 02/16-P Strobe 1st wash rm 112 71417609 7 07/21-P 02/16-P Strobe 1st In Rm 129 51496126 0 07/21-P 02/16-P Strobe 1st In Rm 121 71417610 0 07/21-P 02/16-P Strobe 2nd In Rm 226 51496144 0 07/21-P 02/16-P Strobe 2nd In Rm 221 51496206 0 07/21-P 02/16-P Strobe 2nd In Rm 213 51496207 0 07/21-P 02/16-P Strobe 2nd In Rm 229 51496146 0 07/21-P 02/16-P Strobe 2nd In Rm 236 51496150 0 07/21-P 02/16-P Strobe Attic Northwest 51496199 0 07/21-P 02/16-F

Device Total: 10 Return to Executive Summary

Page of 19 31

Fire Equipment, Inc. Download Date: 12/30/2024

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment.

NFPA 90A (2024) 6.4.1

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Duct Detector 4 4 0 4 4

Device Type Location ScanID Address Q3/23 Q1/24 Duct Detector Basement Inside Rm B02A 51496080 0-7-5-002 07/21-P 02/16-P Duct Detector Attic Inside Elev Equip Rm 51496195 0-12-004 07/21-P 02/16-P Duct Detector Attic Attic North 51496197 0-12-002 07/21-P 02/16-P Duct Detector Attic South Stair 1 51496200 0-12-003 07/21-P 02/16-P

Page of 20 31

Fire Equipment, Inc. Download Date: 12/30/2024

LS 02.01.34 EP 02 Protected master fire alarm control panel

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Control Panel 1 0 1 1 1

Device Type Location ScanID Address Q3/23 Q1/24 Control Panel Basement Bldg 7 51496044 0 07/21-P 02/16-F

Device Total: 1 Return to Executive Summary

Page of 21 31

Fire Equipment, Inc. Download Date: 12/30/2024

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Battery 4 2 2 4 4

Device Type Location ScanID Address Q3/23 Q1/24 Battery Basement Bldg 7 51496043 0-12V55A 07/21-P 02/16-P Battery Basement Bldg 7 51496045 0 07/21-P 02/16-P Battery Basement Bldg 7 51496042 0-12V8A 07/21-P 02/16-F Battery Basement Bldg 7 51496041 0-12V8A 07/21-P 02/16-F

Page of 22 31

Fire Equipment, Inc. Download Date: 12/30/2024

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q1/24 Pass Q1/24 Fail Q1/24 Tested YTD (2024) Total Quantity Power Supply 1 1 0 1 1

Device Type Location ScanID Address Q3/23 Q1/24 Power Supply Basement Bldg 7 51496040 0 07/21-P 02/16-P

Device Total: 1 Return to Executive Summary

Page of 23 31 Service Summary

Fire Equipment, Inc. Download Date: 12/30/2024

Service Summary Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 7 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Failed/Other Battery Tested 2 Control Panel Tested 1 Pull Station Tested 1 Speaker/Strobe Tested 3 Strobe Tested 1

Total 8

Passed Battery Tested 2 Duct Detector Tested 3 Duct Detector Visually Checked 1 Heat Detector Tested 5 Horn/Strobe Tested 4 Power Supply Tested 1 Pull Station Tested 23 Releasing Device Tested 14 Smoke Detector Tested 2 Smoke Detector Tested/Cleaned 55 Smoke Detector Visually Checked 1 Speaker/Strobe Tested 57 Strobe Tested 9

Total 177 Grand Total 185

Page of 24 31 Auxiliary Functions Testing

Fire Equipment, Inc. Download Date: 12/30/2024

Auxiliary Functions Testing Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 7 Control Panel: 0 - EST EST 3 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Releasing Device

Door Holder Basement Door to Bldg 8 Passed 18142234 Door Holder Basement Door to Bldg 8 Passed 18142235 Door Holder Basement Doors by B06 Passed 18142243 Door Holder Basement Doors by B06 Passed 18142242 Door Holder Basement To Bldg 61 Passed 18142239 Door Holder Basement To Bldg 61 Passed 18142238 Door Holder 1st Door to 102A Passed 18142262 Door Holder 1st Door to 102A Passed 18142265 Door Holder 1st Doors to Dining Rm 123 Passed 18142261 Door Holder 1st Doors to Dining Rm 123 Passed 18142260 2nd By Rm 204 Passed 18142253 2nd By Rm 204 Passed 18142252 Door Holder 2nd Door to Rm 223 Passed 51496138 Door Holder 2nd Elev Lobby Door Passed 18142254

Duct Detector AHU Shutdown Basement Inside Rm B02A Passed 51496080

Heat Detector Shunt Trip Basement Elev Eq Room Passed 58984201

Building: Bedford VAMC Bldg 7 Control Panel: 7 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Duct Detector

AHU Shutdown Attic Attic North Passed 51496197 AHU Shutdown Attic South Stair 1 Passed 51496200

Heat Detector Shunt Trip Basement Elev Eq Room Passed 51496910

Smoke Detector Elevator Recall Basement Elev Lobby Passed 51496055 javascript:editViewDevice('18142234');

javascript:editViewDevice('18142235');

javascript:editViewDevice('18142243');

javascript:editViewDevice('18142242');

javascript:editViewDevice('18142239');

javascript:editViewDevice('18142238');

javascript:editViewDevice('18142262');

javascript:editViewDevice('18142265');

javascript:editViewDevice('18142261');

javascript:editViewDevice('18142260');

javascript:editViewDevice('18142253');

javascript:editViewDevice('18142252');

javascript:editViewDevice('51496138');

javascript:editViewDevice('18142254');

javascript:editViewDevice('51496080');

javascript:editViewDevice('58984201');

javascript:editViewDevice('51496197');

javascript:editViewDevice('51496200');

javascript:editViewDevice('51496910');

javascript:editViewDevice('51496055');

Page of 25 31 Auxiliary Functions Testing

Fire Equipment, Inc. Download Date: 12/30/2024

Building: Bedford VAMC Bldg 7 Control Panel: 7 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Smoke Detector

Elevator Recall 1st Elev Lobby Passed 51496187 Elevator Recall 2nd Elev Lobby Passed 51496136 Elevator Recall Attic At Elevator Machine room Passed 51496909 javascript:editViewDevice('51496187');

javascript:editViewDevice('51496136');

javascript:editViewDevice('51496909');

Page of 26 31 Battery & Power Supply Testing

Fire Equipment, Inc. Download Date: 12/30/2024

Battery & Power Supply Testing Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 7 Control Panel: 0 - EST EST 3 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Battery

Passed Sealed Lead Acid Basement Bldg 7 55 12 Sealed Lead Acid Basement Bldg 7 55 12

Failed/Other Sealed Lead Acid Basement Bldg 7 55 12 Sealed Lead Acid Basement Bldg 7 7 12

Page of 27 31 Inventory & Warranty Report

Fire Equipment, Inc. Download Date: 12/30/2024

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 7 Control Panel: 0 - EST EST 3 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Battery Control 2.16% 4

Control Panel Control 0.54% 1

Duct Detector Initiating 2.16% 4

Heat Detector Initiating 2.70% 5

Horn/Strobe Indicating 2.16% 4

Power Supply Control 0.54% 1

Pull Station Initiating 12.97% 24

Releasing Device Auxiliary 7.57% 14

Smoke Detector Initiating 31.35% 58

Speaker/Strobe Indicating 32.43% 60

Strobe Indicating 5.41% 10

Type Qty Model # Description Install Date

In Service - 3 Years to 5 Years

EST

Control Panel 1 EST 3 Addressable 04/23/2020 Duct Detector 1 SIGA-SD 04/23/2020 Heat Detector 4 SIGA-HRS 04/23/2020 Power Supply 1 bps-10a 04/23/2020 Pull Station 6 SIGA-278 04/23/2020 Pull Station 1 SIGA-278 Single Action 04/23/2020 Smoke Detector 22 SIGA-PD 04/23/2020 Smoke Detector 3 SIGA-PD Photoelectric 04/23/2020 Speaker/Strobe 3 G4HFRF-S2VMC 04/23/2020

Est Speaker/Strobe 43 G4HFRF-S2VMC 04/23/2020 Strobe 2 04/23/2020 Strobe 2 G1RF-VM 04/23/2020

Interstate batteries Battery 2 sla-1165 Sealed Lead Acid 04/23/2020

System Sensor Horn/Strobe 3 G1RF-VM 04/23/2020 Releasing Device 2 04/23/2020 Releasing Device 12 Door Holder 04/23/2020 Speaker/Strobe 12 G4HFRF-S2VMC 04/23/2020

Page of 28 31 Inventory & Warranty Report

Fire Equipment, Inc. Download Date: 12/30/2024

Strobe 1 04/23/2020 Strobe 4 G1RF-VM 04/23/2020

In Service - 5 Years to 10 Years Interstate

Battery 1 sla 1075 Sealed Lead Acid 10/01/2018

Interstate batteries Battery 1 sla-1075 Sealed Lead Acid 10/01/2018

Building: Bedford VAMC Bldg 7 Control Panel: 1 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Type Qty Model # Description Install Date

In Service - 3 Years to 5 Years

EST

Duct Detector 1 SIGA-SD 04/23/2020 Pull Station 1 SIGA-SD 04/23/2020

System Sensor Smoke Detector 1 Photoelectric 04/23/2020

Building: Bedford VAMC Bldg 7 Control Panel: 7 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Type Qty Model # Description Install Date

In Service - 3 Years to 5 Years

EST

Duct Detector 2 SIGA-SD 04/23/2020 Pull Station 3 SIGA-278 04/23/2020 Pull Station 13 SIGA-278 Single Action 04/23/2020 Smoke Detector 1 SIGA-278 04/23/2020 Smoke Detector 1 SIGA-278 Photoelectric 04/23/2020 Smoke Detector 19 SIGA-PD 04/23/2020 Smoke Detector 11 SIGA-PD Photoelectric 04/23/2020 Speaker/Strobe 1 g 04/23/2020 Strobe 1 g 04/23/2020

Est Speaker/Strobe 1 g 04/23/2020

System Sensor Heat Detector 1 G4HFRF-S2VMC Fixed Temperature 04/23/2020

System sensor Horn/Strobe 1 04/23/2020

Page of 29 31 Zone Address Report

Fire Equipment, Inc. Download Date: 12/30/2024

Zone Address Report Generated by: BuildingReports.com

Building: Bedford VAMC Bldg 7 Control Panel: 0 - EST EST 3 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID 7-5-002 Duct Detector Basement Inside Rm B02A 51496080 7-5-006 Smoke Detector Basement Tunnel to Bldg 61 Photoelectric 51496046 7-5-017 Smoke Detector 1st Corr by Rm 126 51496103 7-5-028 Smoke Detector 1st Northeast Rm 117 CTR 2 Photoelectric 51496092 7-5-032 Smoke Detector 1st Rm 131H 51496160 7-5-033 Smoke Detector 1st Rm 131E 51496161 7-5-034 Smoke Detector 1st Rm 131C 51496162 7-5-035 Smoke Detector 1st Rm 131J 51496159 7-5-038 Smoke Detector 1st Rm 131K Photoelectric 51496158 7-5-039 Smoke Detector 1st Rm 131A 51496163 7-5-041 Smoke Detector 1st East in Cube 15-16 51496164 7-5-042 Smoke Detector 1st East in Rm 134B 51496171 7-5-043 Smoke Detector 1st East in Rm 134C 51496170 7-5-044 Smoke Detector 1st East in Rm 134J 51496165 7-5-045 Smoke Detector 1st East in Rm 134F 51496167 7-5-046 Smoke Detector 1st East in Rm 134H 51496166 7-5-047 Smoke Detector 1st East in Cubicle 7-8 51496168 7-5-048 Smoke Detector 1st East in Cubicle 9-10 51496169 7-5-049 Smoke Detector 1st In Rm 110J 51496179 7-5-050 Smoke Detector 1st In Rm 110B 51496175 7-5-051 Smoke Detector 1st In Rm 110K 51496180 7-5-053 Smoke Detector 1st In Rm 110H 51496178 7-5-054 Smoke Detector 1st In Rm 110A 51496177 7-5-158 Pull Station 1st In Rm 117A @ Stair 4 Single Action 51496093 7-12-001 Smoke Detector 2nd North Corr Outside Rm 208 51496205 7-12-007 Smoke Detector 2nd North Corr by Rm 204 51496201 7-12-126 Pull Station Attic Attic by Door 51496189 7-12-130 Pull Station 2nd North Stair 4 51496211 7-12-141 Pull Station 2nd South 51496140 7-12-149 Pull Station Basement North Hall trailer 51496060 7-12-150 Pull Station Basement Rear Hall 51496062 7-12-151 Pull Station Basement Left Entrance trailer 51496066 12V8A Battery Basement Bldg 7 Sealed Lead Acid 51496041 12V8A Battery Basement Bldg 7 Sealed Lead Acid 51496042

12V55A Battery Basement Bldg 7 Sealed Lead Acid 51496043

Building: Bedford VAMC Bldg 7 Control Panel: 1 javascript:editViewDevice('51496080');

javascript:editViewDevice('51496046');

javascript:editViewDevice('51496103');

javascript:editViewDevice('51496092');

javascript:editViewDevice('51496160');

javascript:editViewDevice('51496161');

javascript:editViewDevice('51496162');

javascript:editViewDevice('51496159');

javascript:editViewDevice('51496158');

javascript:editViewDevice('51496163');

javascript:editViewDevice('51496164');

javascript:editViewDevice('51496171');

javascript:editViewDevice('51496170');

javascript:editViewDevice('51496165');

javascript:editViewDevice('51496167');

javascript:editViewDevice('51496166');

javascript:editViewDevice('51496168');

javascript:editViewDevice('51496169');

javascript:editViewDevice('51496179');

javascript:editViewDevice('51496175');

javascript:editViewDevice('51496180');

javascript:editViewDevice('51496178');

javascript:editViewDevice('51496177');

javascript:editViewDevice('51496093');

javascript:editViewDevice('51496205');

javascript:editViewDevice('51496201');

javascript:editViewDevice('51496189');

javascript:editViewDevice('51496211');

javascript:editViewDevice('51496140');

javascript:editViewDevice('51496060');

javascript:editViewDevice('51496062');

javascript:editViewDevice('51496066');

javascript:editViewDevice('51496041');

javascript:editViewDevice('51496042');

javascript:editViewDevice('51496043');

Page of 30 31

Fire Equipment, Inc. Download Date: 12/30/2024

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID 7-12-148 Pull Station Basement South Hall trailer 51496064 12-004 Duct Detector Attic Inside Elev Equip Rm 51496195

Building: Bedford VAMC Bldg 7 Control Panel: 7 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID 5-001 Smoke Detector Basement Elev Lobby Photoelectric 51496055 5-004 Smoke Detector Basement Tunnel to Bldg 8 Photoelectric 51496050 5-005 Smoke Detector Basement Corr Outside Rm B06 Photoelectric 51496053 5-009 Smoke Detector 1st Outside Rm 129 51496105 5-010 Smoke Detector 1st IRM Closet 51496188 5-011 Smoke Detector 1st Elev Lobby Photoelectric 51496187 5-012 Smoke Detector 1st South Hall Outside Rm 125 51496104 5-013 Smoke Detector 1st Corr 132A Closet 51496107 5-014 Smoke Detector 1st 132 Closet 51496111 5-015 Smoke Detector 1st South Corr by Rm 134A 51496112 5-016 Smoke Detector 1st South Corr by Rm 135B Photoelectric 51496113 5-018 Smoke Detector 1st South Corr Rm 123 51496102 5-019 Smoke Detector 1st West Dining 123 51496101 5-020 Smoke Detector 1st West Dining 123 51496097 5-021 Smoke Detector 1st Corr Fire Doors by Rm 105 Photoelectric 51496095 5-022 Smoke Detector 1st North Hall Outside Rm 111 51496088 5-023 Smoke Detector 1st Corr by 112 51496089 5-024 Smoke Detector 1st North Corr by Rm 110E 51496183 5-025 Smoke Detector 1st North Corr by Rm 110B 51496182 5-026 Smoke Detector 1st Corr 115 51496090 5-027 Smoke Detector 1st Northeast Rm 117 CTR 1 Photoelectric 51496091 5-029 Smoke Detector 1st South Corr by Kitchen 51496096 5-030 Smoke Detector 1st North Corr by rm 104 51496094 5-036 Smoke Detector 1st South Corr by Rm 131F Photoelectric 51496110 5-037 Smoke Detector 1st South Corr by Rm 131B 51496109 5-040 Smoke Detector 1st South By Rm 133 51496108 5-052 Smoke Detector 1st In Rm 110c 59133956 5-055 Smoke Detector 1st South in Rm 125 51496172 5-126 Pull Station Basement Tunnel to Bldg 61 Single Action 51496074 5-127 Pull Station Basement At Stair 3 Single Action 51496051 5-128 Pull Station Basement Tunnel to Bldg 8 Single Action 51496048 5-134 Pull Station Basement Tunnel to Bldg 6 Single Action 51496086 5-138 Pull Station Basement At Stair 1 Single Action 51496057 5-143 Pull Station Basement South In Rm B02 Single Action 51496081 5-156 Pull Station 1st At Stair 1 51496106 5-157 Pull Station 1st South in rm 134A Single Action 51496114 javascript:editViewDevice('51496064');

javascript:editViewDevice('51496195');

javascript:editViewDevice('51496055');

javascript:editViewDevice('51496050');

javascript:editViewDevice('51496053');

javascript:editViewDevice('51496105');

javascript:editViewDevice('51496188');

javascript:editViewDevice('51496187');

javascript:editViewDevice('51496104');

javascript:editViewDevice('51496107');

javascript:editViewDevice('51496111');

javascript:editViewDevice('51496112');

javascript:editViewDevice('51496113');

javascript:editViewDevice('51496102');

javascript:editViewDevice('51496101');

javascript:editViewDevice('51496097');

javascript:editViewDevice('51496095');

javascript:editViewDevice('51496088');

javascript:editViewDevice('51496089');

javascript:editViewDevice('51496183');

javascript:editViewDevice('51496182');

javascript:editViewDevice('51496090');

javascript:editViewDevice('51496091');

javascript:editViewDevice('51496096');

javascript:editViewDevice('51496094');

javascript:editViewDevice('51496110');

javascript:editViewDevice('51496109');

javascript:editViewDevice('51496108');

javascript:editViewDevice('59133956');

javascript:editViewDevice('51496172');

javascript:editViewDevice('51496074');

javascript:editViewDevice('51496051');

javascript:editViewDevice('51496048');

javascript:editViewDevice('51496086');

javascript:editViewDevice('51496057');

javascript:editViewDevice('51496081');

javascript:editViewDevice('51496106');

javascript:editViewDevice('51496114');

Page of 31 31

Fire Equipment, Inc. Download Date: 12/30/2024

Address Device Type Location Type ScanID 5-159 Pull Station 1st At Stair 3 Single Action 51496087 5-160 Pull Station 1st South Dining 123 51496099 5-161 Pull Station 1st South in Rm 123 Single Action 51496185 5-162 Pull Station 1st North in Rm 128 Single Action 51496156 5-163 Pull Station Basement North In Rm B08E Single Action 51496076

7-5-035 Horn/Strobe 1st Inside Bathroom 136 71417608 12-002 Duct Detector Attic Attic North 51496197 12-003 Duct Detector Attic South Stair 1 51496200

12-5 Smoke Detector 2nd Elev Lobby Photoelectric 51496136 12-006 Smoke Detector 2nd Corr inside Rm 223 Photoelectric 51496143

12-8 Smoke Detector Attic At Elevator Machine room Photoelectric 51496909 12-9 Smoke Detector 2nd IRM Closet Photoelectric 51496137

12-128 Pull Station 2nd South Stair 1 Single Action 51496147 12-129 Pull Station 2nd South Stair 5 51496153 12-131 Pull Station 2nd North Single Action 51496204 12-132 Heat Detector Basement Elev Eq Room Fixed Temperature 51496910 javascript:editViewDevice('51496087');

javascript:editViewDevice('51496099');

javascript:editViewDevice('51496185');

javascript:editViewDevice('51496156');

javascript:editViewDevice('51496076');

javascript:editViewDevice('71417608');

javascript:editViewDevice('51496197');

javascript:editViewDevice('51496200');

javascript:editViewDevice('51496136');

javascript:editViewDevice('51496143');

javascript:editViewDevice('51496909');

javascript:editViewDevice('51496137');

javascript:editViewDevice('51496147');

javascript:editViewDevice('51496153');

javascript:editViewDevice('51496204');

javascript:editViewDevice('51496910');

Fire Alarm and Life Safety System Inspection Certificate
Discrepancy Report
Proposed Solutions Report
Notes & Recommendations
Inspection & Testing
Service Summary
Auxiliary Functions Testing
Battery & Power Supply Testing
Inventory & Warranty Report
Zone Address Report