This document package includes construction drawings and specifications for a federal construction project. The project involves renovating an existing three-story building to create a women's health clinic, including addressing life safety issues, accessibility deficiencies, installing an elevator and walkway, and replacing all mechanical, electrical, plumbing and lighting systems. The project will provide areas for primary care, acupuncture, mental health and case management services. Key details include the solicitation number 36C24123B0002 for the Women's Health 3 floors Construction project, with responses due on unspecified dates. The work will be performed at the Bedford VA Medical Center in Bedford, Massachusetts for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1. Applicable codes and standards are listed.

View the file

Other files

File Type Posted
36C24123B0002 0011.docx DOCX document
Bedford Womens Health Construction RFIs 07262023.docx DOCX document
36C24123B0002 0010.docx DOCX document
518-21-103 Site Visit Sign-In Sheet.pdf PDF
List of Attachments.pdf PDF
36C24123B0002 0009.pdf PDF
Plumbing-21053.pdf PDF
branches_productsheet.pdf PDF
FP-20153.pdf PDF
Interiors-21053.pdf PDF
087100.pdf PDF
375-Ultra-Durable-Guide-Specifications-2109861.pdf PDF
090600 SCHEDULE FOR FINISHES.pdf PDF
081710.pdf PDF
Architectural-21053.pdf PDF
085113.pdf PDF
Structural-21053.pdf PDF
Civil-20153.pdf PDF
Mechanical-21053.pdf PDF
Electrical-21053.pdf PDF
074624.pdf PDF
375Info sheet.pdf PDF
518-21-103 012 HA102.pdf PDF
518-21-103 Bedford Womens Clinic RFIs (COMPILED).docx DOCX document
36C24123B0002 0008.docx DOCX document
518-21-103 012 HA101.pdf PDF
028211_Bedford VAMC Bldg 12.pdf PDF
02833313_Bedford VAMC Bldg 12.pdf PDF
518-21-103 Contracting and VA RFIs.docx DOCX document
36C24123B0002 0007.docx DOCX document
36C24123B0002 0006.docx DOCX document
36C24123B0002 0005.docx DOCX document
36C24123B0002 0004.docx DOCX document
100 - Interior.pdf PDF
36C24123B0002 0003.docx DOCX document
36C24123B0002 0002.docx DOCX document
36C24123B0002_2.docx DOCX document
36C24123B0002 0001.docx DOCX document
Full Set Drawings.pdf PDF
36C24123B0002_1.docx DOCX document
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.pdf PDF
S02 PRE-AWARD CONTRACTOR EVALUATION FORM.pdf PDF
General Decision MA20230001 03032023.pdf PDF
SOW 518-21-103 Womens Health Construction.pdf PDF
Asbestos Documents.pdf PDF
100 Percent Specifications.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W1

R1

W2 W3

F -E

B.

O

DI

SP

EN

SE

R

B.

O

DI

SP

EN

SE

R

B.

O

M

IR

RO

RM

AX

LIQUID SOAP

DISPENSER

(S. DISP.)

PAPER TOWEL DISP.

(PT. DISP. & PTD.)

MIRROR

STANDARD MOUNTING HEIGHTS FOR MISCELLANEOUS WALL-MOUNTED ACCESSORIES

3'

- 6

3'

- 6

3'

- 4

4'

- 2

2'

- 1 0"

1' - 6"

2'

- 1

0"

00:00

1' - 0" 3' - 6"

3'

- 0

" M

AX

3' - 0" 6"

STD WATER CLOSET W/

TOILET SEAT COVER

DISPENSER

HC WATER

CLOSET

GRAB BARS AT

WATER CLOSET

GRAB BARS AT

WATER CLOSET

TOILET PAPER DISP. W/

SANITARY DISPOSAL. (FEMALE

TOILETS ONLY)

STD.

URINAL

HC

URINAL

STD

LAVATORY

2'

- 0

1' - 3"

2'

- 0

1'

- 5

3'

- 8 " M

AX

MIN

1' - 3"

2'

- 1

0" A

DA

STANDARD PLUMBING FIXTURES AND WALL-MOUNTED ACCESSORY MOUNTING HEIGHTS

4'

- 6

5'

- 0

5'

- 0

5'

- 0

" 6'

- 8

6'

- 8

4'

- 0

STANDARD MOUNTING HEIGHTS FOR WALL-MOUNTED MEDICAL EQUIPMENT

STANDARD HEIGHTS FOR TRANSACTION COUNTER/ SHELVING/ SEATING

1' - 3"

T.

O

. S

YR

IN

G

E

DR

OP

TY

P.

U

NO

T.

O

. S

HE

LF

TO

C

EN

TE

RL

IN

E O

F

BO

X

TO

M

AT

CH

LI

NE

O F

BO

XE

S

TO

C

EN

TE

RL

IN

E O

F

CL

OC

K

TO

C

EN

TE

RL

IN

E O

F

BU

TT

ON

TO

C

EN

TE

RL

IN

E O

F

CL

OC

K

SHARPS/GLOVE DISP. GOWN SHELF VIEW BOX

TYPICAL FOR 2, 4, RECESSED

OR WALL MOUNTED VIEW

BOXES

STACKED VIEW BOXES

TYPICAL FOR 2, 4, RECESSED

OR WALL MOUNTED VIEW

BOXES

CLEAR

3' - 0" MIN

HE

IG

HT

2'

- 1 0"

A

DA

3'

- 6

HE

IG

HT

2'

- 1 0"

A

DA

MAX

2' - 0"

CLEAR

2' - 6"

OVERHANG

6" MIN.

1'

- 5

1'

- 7

1'- 0"

" M

AX

A

DA

9"

CLOCK ELAPSED TIMER

STD HT VARIES

MAX 3'-8" FOR

HC REACHOVER

M

IN

TRANSACTION COUNTERS

FRONT ELEVATION

HC TRANSACTION COUNTERS

SIDE APPROACH SECTION

DRESSING

ROOM SEAT

SECTION

SHELVING

SECTION

TOWEL BAR SANITARY NAPKIN

DISPENSER

CHANGING STATION STD. WALL

PHONE

STD. WALL PHONE

AT WORKSTATIONS

CE

NT

ER

L

IN

E

O F

CO

IN

S

LO

T

3'

- 6

4'

- 0

4'

- 6

4'

- 0

ALIGN WITH

TOP OF

DOOR

FULL HEIGHT

MIRROR

3'

- 4

M

IN

1'

- 6

3' - 4"

2' -9

" M

IN

3'

- 0

M

AX

1' - 6"

3'

- 0

" T

YP

2'

- 1

0"FRONT SIDE

1' - 6"

2' -9

" M

IN

M

IN

M

AX

M

IN

HC LAVATORY/MIRROR TYP. LAVATORY DISPENSERS/TYP.

TOILET RM. DEVICES

MIN

1' - 3"

2'

- 1

0" M

AX

2'

- 5

" M

IN

3'

- 4

" M

AX

MIN

1' - 3"

CL

EA

R 2'

- 5

3'

- 6

STANDARD PLUMBING FIXTURES AND WALL-MOUNTED ACCESSORY MOUNTING HEIGHTS

B.

O

. R

EF

LE

CT

IN

G

SU

RF

AC

E

M

AX

T O

H

IG

HE

ST

O

PE

RA

TI

NG

P

AR

T

M

AX

R

IM

2'

- 1

0"

2'

- 9

3'

- 1

/2

11" 1' - 2"

DRINKING

FOUNTAIN

5" 6"

4'

- 8

2'

- 1 0"

2' - 0"

TYP LAVATORY IN

COUNTER W/ FULL MIRROR

1'

- 7

FLUSH RIM

SERVICE SINK

READ

THIS

HANDRAILS AND

WALL BUMPERS

RAMP AND STAIR

HANDRAILS

COAT HOOK/ROBE

HOOK

COAT RACK

2'

- 1

0" 2'-

8" F

O R

RE

HA

B

SIGNAGE

4'- 0"

R

O

BE

H O

OK

4'

- 6

3'

- 0

" 5'

- 0

4'

- 0

4'

- 0

M

ID

DL

E

O F

UN

IT

TO

C

EN

TE

R O

F

UN

IT

SPHYGMOMANOMETER

(SPHYG)

OTOSCOPE/

OPHTHALMOSCOPE

(OTO/OPTHO)

AIR & VAPOR BARRIER

MEMBRANE ROOFING

TAPERED INSULATION

PROTECTION BOARD

MASONRY TIE

VAPOR BARRIER

SHEATHING

ROOF ASSEMBLIES EXTERIOR WALL ASSEMBLIES

R30 MIN.

COLD-FORMED METAL

FRAMING

GWB

SHEATHING

AIR & VAPOR BARRIER

SHEATHING

2" Z- FURRING (BASIS OF

DESIGN: THERMAFAST)

PAINTED

CEMENTITIOUS

PANEL SIDING

BRICK MASONRY

AIR GAP

2HR RATED CMU BLOCK

3"

2" RIGID INSULATION2" RIGID INSULATION

W2 EXTERIOR WALL (STUD)

SCALE: 3" = 1'-0"

W1 EXTERIOR WALL (MASONRY)

SCALE: 3" = 1'-0"

NOTE: RATED DESIGN: UL P522

AIR & VAPOR BARRIER

MASONRY TIE

BRICK MASONRY

AIR GAP

POURED CONCRETE

3"

2" RIGID INSULATION

W3 EXTERIOR WALL (MASONRY)

SCALE: 3" = 1'-0"

2 1/2" METAL FRAMING

5/8" GWB

CLOSED CELL SPRAY

INSULATION

SHEATHING

2" Z- FURRING (BASIS OF

DESIGN: THERMAFAST)

PAINTED

CEMENTITIOUS

PANEL SIDING

EXISTING FLOOR ASSEMBLY

NOTE: RATED DESIGN: UL J941

1- 1/

2" M

IN

PRECAST CONCRETE UNIT

MIN. BEARING 3"

CONCRETE TOPPING

5-1/4" MIN. SLAB THICKNESS

15' MAX.

4' MIN.

EXISTING BRICK MASONRY

EXISTING CLAY TILE BACK UP

ME8.8

EXISTING MASONRY

SCALE: 1 1/2" = 1'-0"

2" C-T STUD FRAMING

1" GLASROC SHAFT LINER

5/8" TYPE-X GWB

CONTINUOUS FIRE CAULKING

CONTINUOUS FIRE CAULKING

INTERIOR PARTITION NOTES:

1. PARTITION TYPE DRAWINGS ARE GRAPHIC

REPRESENTATION ONLY. THEY ARE NOT TO SCALE

TYPICAL.

2. REFERENCE PLANS FOR PARTITION TAGS.

3. ALL BLANKET AND ACOUSTICAL INSULATION IS TO BE

FULL HEIGHT AND FULL THICKNESS UNLESS NOTED

OTHERWISE.

4. REFERENCE STRUCTURAL FOR COLD FORMED STUD

SPECIFICATIONS TYPICAL.

5. REFERENCE STRUCTURAL DRAWINGS FOR MASONRY

REINFORCING REQUIREMENTS AND ADDITIONAL DETAILS.

6. REFERENCE CODE COMPLIANCE PLANS FOR WHICH

WALLS ARE SMOKE AND FIRE BARRIER ASSEMBLIES.

7. MORTAR USED IN THE RATED ASSEMBLIES SHALL HAVE

SAND TO CEMENT RATIO BETWEEN 2.25 & 3.6, AND THE

HYDRATED LIME TO CEMENT RATIO LESS THAN 0.5.

8. CMU WALL ASSEMBLIES HAVE BEEN DESIGNED FOR FIRE

RESISTANCE PER CALCULATIONS INDICATED IN THE

"ANALYTICAL METHODS OF DETERMINING FIRE

ENDURANCE OF CONCRETE AND MASONRY-MODEL CODE

APPROVED PROCEDURES" AS PUBLISHED BY THE

CONCRETE AND MASONRY INDUSTRY FIRE SAFETY

COMMITTEE. BY CALCULATION, ALL ASSEMBLIES MEET

OR EXCEED THE REQUIREMENT. THE CONTRACTOR

SHALL PROVIDE SOLID GROUT AT ALL FIRE RATED

MASONRY ASSEMBLIES AS REQUIRED TO PROVIDE THE

FOLLOWING EQUIVALENT THICKNESS: 1 HOUR RATED -

2.8 INCHES, 2 HOUR RATED - 4.2 INCHES.

9. APPLY CONTINUOUS FIRESTOPPING SEALANT AT ALL

PENETRATIONS IN FIRE RATED AND SMOKE PARTITIONS.

REFER TO SPECIFICATIONS FOR FIRESTOPPING

INFORMATION.

10. PROVIDE FIRE RESISTIVE JOINT SYSTEMS AT TOP &

BOTTOM OF ALL FIRE RATED PARTITIONS.

11. PROVIDE ACOUSTICAL JOINT SYSTEMS AT TOP OF ALL

STC-RATED PARTITIONS.

12. TYPICAL TOP OF WALL DETAILS AND THROUGH WALL

PENETRATION DETAILS ARE TO BE COORDINATED FOR

EACH INDIVIDUAL WALL CONDITION BY THE

CONTRACTOR PRIOR TO PROCEEDING WITH WORK.

NOTIFY ARCHITECT IN WRITING OF ANY DISCREPANCIES

OR INCONSISTENCIES BETWEEN THE DETAIL AND TRUE

CONDITIONS. FAILURE TO REPORT ANY DISCREPANCIES

WITHIN THESE CONSTRUCTION DOCUMENTS TO THE

ARCHITECT WILL NOT BE GROUNDS FOR ADDITIONAL

COST OR CHANGE ORDERS.

13. REFER TO INTERIOR FINISH PLAN FOR APPLIED FINISHES

SUCH AS TILE. PROVIDE SPECIFIED WALL FINISH

SUBSTRATE IN PLACE OF GYPSUM BOARD WHERE TILE IS

SCHEDULED.

14. REFER TO INTERIOR FINISH PLAN FOR ADDITIONAL

INFORMATION ON EXTENTS OF FINISHES APPLIED TO

WALLS.

15. CMU LAID IN FULL 3/8" MORTAR BED WITH VERTICAL

JOINTS STAGGERED.

16. AT EXTERIOR MASONRY WALL ASSEMBLY CMU IS

EXTENDED TO STRUCTURE ABOVE WITH #4 VERTICAL

REINFORCING @ 8" CENTERS (U.N.O. BY STRUCTURAL).

HORIZONTAL LADDER TYPE REINFORCING @16"

CENTERS, AND SOLID GOUT. PROVIDE WALL TOP

CONNECTION AS REQUIRED BY STRUCTURAL.

17. PROVIDE CONTROL JOINTS FOR MASONRY WALLS.

LOCATE CONTROL JOINTS TO ALIGN WITH DOOR HEAD

OR WINDOW EDGES WHERE POSSIBLE, OR AS INDICATED

BY ARCHITECT.

18. PROVIDE CONTROL JOINTS AND ALLOWANCE FOR

PERIMETER MOVEMENT FOR INTERIOR GYPSUM WALLS.

LOCATE CONTROL JOINTS TO ALIGN WITH DOOR HEAD

OR WINDOW EDGES WHERE POSSIBLE, OR AS

INDICATED BY ARCHITECT.

19. REFERENCE SPECIFICATIONS FOR LABELING OF FIRE

RATED PARTITIONS.

20. AT STC RATED PARTITIONS COORDINATE SUCH THAT

ELECTRICAL BOXES IN ADJOINING ROOMS DO NOT

SHARE STUD CAVITIES. ALL PENETRATIONS MUST BE

SEALED AND IN STAGGERED CAVITIES.

21. FURRING PARTITIONS TO BE HELD OFF EXTERIOR WALL

1/4" TYPICAL UNLESS NOTED OTHERWISE

22. WOOD BLOCKING/PLYWOOD TO BE FIRE TREATED, TYP.

SEE SCHEDULE

BELOW FOR DIMENSION

FINISHED FLOOR

ACOUSTICAL SEALANT

(1) LAYER OF 5/8" GWB

SOUND ATTENUATION

BLANKET

(SEE SCHEDULE BELOW)

FINISHED CEILING (SEE RCP)

UNDERSIDE OF DECK

ABOVE

F1a

F2a

1-5/8"

2-1/2"

3-5/8"

2-1/4"

3-1/8"

4-1/4"

N/A

N/A

N/A

LINE OF NEW OR

EXISTING PARTITION

OR SUBSTRATE

TYPE STUD

SIZE

PART.

THICK. RATING DESIGN

DEFLECTION TRACK

ACOUSTICAL SEALANT

SOUND ATTN

BLANKET

BRACE FRAMING TO

SUBSTRATE NOT TO

EXCEED 8'-0" O.C.

F3a

NONE

FULL

DEPTH

FULL

DEPTH

SEE PLAN FOR DIMENSION

F#.

FURRING - NON RATED PARTITIONS

SCALE: 1 1/2" = 1'-0"

FINISHED FLOOR

ACOUSTICAL SEALANT

(1) LAYER OF 5/8" GWB

FINISHED CEILING (SEE RCP)

UNDERSIDE OF DECK

ABOVE

3-5/8" 4-1/4" N/A

LINE OF EXISTING EXTERIOR

MASONRY WALL

TYPE

DEFLECTION TRACK

ACOUSTICAL SEALANT

BRACE FRAMING TO

SUBSTRATE NOT TO

EXCEED 8'-0" O.C.

Q3a FULL

DEPTH

Q#.

FURRING - NON RATED PARTITIONS

SCALE: 1 1/2" = 1'-0"

MIN.

2"

2" SPRAY FOAM INSULATION FROM

FLOOR TO UNDERSIDE OF DECK ABOVE

3-5/8" METAL STUD

FINISHED CEILING (SEE

RCP)

UNDERSIDE OF DECK

ABOVE

M#.x

EXISTING MASONRY WALL AND INFILL

SCALE: 1 1/2" = 1'-0"

TYPE CMU FIRE

RATING

PART.

THICK. RATING DESIGN

8" 2 HR 7-5/8"M8.2 U905

EXIST. MASONRY - 12" THICK

SEE SCHEDULE

BELOW FOR DIMENSION

FINISHED FLOOR

1HR: (1) LAYER 5/8" TYPE "X" GWB EACH SIDE

2HR: (2) LAYERS 5/8" TYPE "X" GWB EACH SIDE

3HR: (3) LAYERS 5/8" TYPE "X" GWB EACH SIDE

STEEL STUD FRAMING (SEE

SCHEDULE BELOW)

SOUND ATTENUATION

BLANKET

(SEE SCHEDULE BELOW)

FINISHED CEILING (SEE RCP). TERMINATE

CEILING EDGE AT OUTERMOST WALL LAYER

FIRE RESISTIVE JOINT

SYSTEM

DEFLECTION TRACK

UNDERSIDE OF DECK

ABOVE

FIRE

RATING

STUD

SIZE

PART.

THICK. RATING DESIGN

6" 7-1/4"

SOUND ATTN

BLANKET

FULL

DEPTH

SEE SCHEDULE

BELOW FOR DIMENSION

FINISHED FLOOR

CONTINUOUS FIRE CAULKING

1HR: (1) LAYER OF 5/8" TYPE "X" GWB

2HR: (2) LAYERS OF 5/8" TYPE "X" GWB

3HR: (3) LAYERS OF 5/8" TYPE "X" GWB

STEEL STUD FRAMING (SEE

SCHEDULE BELOW)

SOUND ATTENUATION BLANKET

(SEE SCHEDULE BELOW)

FINISHED CEILING (SEE RCP)

FIRE RESISTIVE JOINT

SYSTEM

FLOOR, SIDE, AND

CEILING RUNNERS

UNDERSIDE OF DECK

ABOVE

U4.1 4" CH 4- 5/8"

INTERMEDIATE STUD AS NECESSARY TO

SUPPORT LINER PANELS

1" TYPE X GYPSUM LINER PANEL

5/8" GWB

CANT AT ALL

PROJECTIONS

OVER 2"

ELEVATOR

SHAFT

TYPE STUD

SIZE

PART.

THICK. RATING DESIGNSOUND ATTN

BLANKET

FULL

DEPTH

S#.#

STUD PARTITIONS - TO DECK

SCALE: 1 1/2" = 1'-0"

N/A

UL DESIGN U415 - SYSTEM A

U#.1

SHAFTWALL - 1 HOUR PARTITIONS

SCALE: 1 1/2" = 1'-0"

FIRE

RATING

1 HR

TYPE

S6.0 NONE

3-5/8" 4-7/8" FULL

DEPTH N/AS3a NONE

3-5/8" 4-7/8" FULL

DEPTH UL DESIGN U419S3.1a 1 HR.

6" 7-1/4" FULL

DEPTH UL DESIGN U419S6.1 1 HR.

U4.2 4" CH 4- 5/8"

FULL

DEPTH UL DESIGN U415 - SYSTEM A2 HR

3-5/8" 6-1/4" FULL

DEPTH UL DESIGN U419S3.2 2 HR.

FIRE

RATING

STUD

SIZE

PART.

THICK. RATING DESIGNSOUND ATTN

BLANKET

N/A

INTERIOR PARTITIONS

3/8" MORTOR

EXISTING WALL TO REMAIN

6" 6-5/8" N/AF6 FULL

DEPTH

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:3

AM

GI003

MOUNTING HEIGHTS, INTR.

PARTITIONS, EXT. WALL & ROOF TYPES

WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 MC MC/MP/BL

200 SPRINGS ROAD, BEDFORD, MA 01730

SCALE: 1/4" = 1'-0"F1 TYPICAL MOUNTING HEIGHTS

Revisions: Date:

ADDENDUM 1 JUNE 9, 2023

BUILDING: MASSACHUSETTS BUILDING CODE 2015

(BASED ON INTERNATIONAL BUILDING CODE, 2015 EDITION)

MASSACHUSETTS EXISTING BUILDING CODE 2015

(BASED ON INTERNATIONAL EXISTING BUILDING CODE, 2015 EDITION)

NFPA INCLUDING 101 LIFE SAFETY CODE 2021 EDITION

FIRE: NFPA INCLUDING 101 LIFE SAFETY CODE 2021 EDITION

527 CMR MA FIRE PREVENTION

ACCESSIBILITY: MASSACHUSETTS ACCESSIBILITY CODE

ADA, STANDARDS FOR ACCESSIBLE DESIGN 2010 EDITION.

521 CMR ARCHITECTURAL ACCESS BOARD

PROJECT SUMMARY:

THIS PROJECT INVOLVES RENOVATING BUILDING 12, WHICH INCLUDES ADDRESSING BUILDING IMPROVEMENTS, LIFE SAFETY ISSUES, ACCESSIBILITY DEFICIENCIES, INSTALLING AN ELEVATOR AND SLOPED WALKWAY, REMOVING AND REPLACING ALL MECHANICAL, ELECTRICAL, PLUMBING, ELECTRICAL AND LIGHTING SYSTEMS. THE RENOVATION INTO A WOMENS CLINIC WILL PROVIDE AREAS FOR PRIMARY CARE, ACUPUNCTURE, MENTAL HEALTH, CASE MANAGEMENT/

SERVICES.

FOR FLOOR PLAN REVIEWS, REFER TO GI102 & GI103.

APPLICABLE CODES:

ILLUMINATION OF MEANS OF EGRESS:

EMERGENCY LIGHTING WILL BE PROVIDED BY AN ESSENTIAL ELECTRICAL SYSTEM UTILIZING EMERGENCY POWER

GENERATION AND CONFORMING WITH THE REQUIREMENTS OF NFPA 99.

PROTECTION FROM HAZARDS:

BUILDING TO BE FULLY SPRINKLERED

NFPA 101 SECTION 39.3.2.1 & 8.7 ONE HOUR FIRE RATED SEPARATION BETWEEN BUSINESS AND LOW AND ORDINARY

HAZARD STORAGE WITH SPRINKLER SYSTEM

INTERIOR FINISH:

IBC CHAPTER 8, NFPA 101 CHAPTER 11

WALL AND CEILING FINISHES: (IBC TABLE 803.9 & NFPA TABLE 1.10.2.2)

VERTICAL EXITS & PASSAGEWAYS: CLASS A FOR BUSINESS USE WITHOUT SPRINKLER, CLASS B FOR BUSINESS USE

WITH SPRINKLER

EXIT ACCESS CORRIDORS: CLASS B FOR BUSINESS USE WITHOUT SPRINKLER, CLASS C FOR BUSINESS USE WITH

SPRINKLER

ROOMS & ENCLOSED SPACES: CLASS A, B, OR C

FLOOR FINISHES: EXITS CLASS II IBC 804.4.2

EXTINGUISHMENT:

PORTABLE FIRE EXTINGUISHERS IN ACCORDANCE WITH 2013 EDITION OF STANDARD FOR PORTABLE FIRE

EXTINGUISHERS.

DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS:

FIRE ALARM SYSTEM REQUIRED IN ACCORDANCE WITH IBC CHAPTER 9 AND NFPA 101, SECTION 9.6

EMERGENCY FORCES:

FIRE DEPARTMENT NOTIFICATION REQUIRED IN CONFORMANCE WITH NFPA 101 SECTION 9.6.4.

NOTES:

1. EMERGENCY EGRESS LIGHTING AND EXIT SIGN MODIFICATIONS SHALL COMPLY WITH NFPA 101: LIFE SAFETY

CODE AND NFPA 70: NATIONAL ELECTRIC CODE.

2. FIRE ALARM SYSTEM MODIFICATIONS SHALL COMPLY WITH NFPA 72: NATIONAL FIRE ALARM AND SIGNALING CODE

AND THE AMERICANS WITH DISABILITIES ACT.

BUILDING DATA:

FUNCTION: MEDICAL OFFICE BUILDING AND SUPPORT SPACES.

USE GROUPS: IBC: B - BUSINESS

NFPA: BUSINESS

CONSTRUCTION TYPE: IBC: TYPE III-B

NFPA: TYPE III (200)

CONTRACTOR RESPONSIBILITIES

• CONTRACTOR SHALL COMPLY WITH ALL REQUIREMENTS IN BUILDING CODE RELATED TO SAFEGUARDS DURING

CONSTRUCTION, INCLUDING, BUT NOT LIMITED TO REQUIREMENTS RELATED TO: CONSTRUCTION SAFEGUARDS;

DEMOLITION; SITE WORK; SANITARY; PROTECTION OF PEDESTRIANS AND ADJOINING PROPERTY; TEMPORARY USE OF STREETS, ALLEYS AND PUBLIC PROPERTY; FIRE EXTINGUISHERS; MEANS OF EGRESS; STANDPIPES; AUTOMATIC SPRINKLER SYSTEM; WATER SUPPLY FOR FIRE PROTECTION; FIRE WATCH DURING CONSTRUCTION.

• SEE CHAPTER 33 "SAFEGUARDS DURING CONSTRUCTION" FOR MORE DETAILS.

USE, OCCUPANCY AND CONSTRUCTION TYPE

EXISTING PROPOSED

• OCCUPANCY CLASSIFICATION (302.1): B B

• PROPOSED CONSTRUCTION TYPE: TYPE III-B NO CHANGE

• SPRINKLER REQ'D (903.2): NO NFPA 13 PROVIDED

• BUILDING SQUARE FOOTAGE:

EXISTING: 16,594 SF

PROPOSED ADDITIONS: 3,005 SF

TOTAL: 19,599 SF

• OCCUPANT LOAD (BY FLOOR)

BSMT: 58

1ST FLOOR: 182

2ND FLOOR: 37

TOTAL: 277

• FIRE APPARATUS ACCESS (F503): PROVIDED

STORIES, HEIGHT & AREA ALLOWABLE PROPOSED

• STORIES (504.4): 4 STORIES 2 STORIES (PLUS BASEMENT)

• HEIGHT (504.3): 75' 49'-3"

• AREA (506.2): 57,000 SF 19,599 SF

• FRONTAGE INCREASE (506.3) : YES NOT REQUIRED

BLDG ELEMENT (HRS) (601) REQUIRED PROVIDED

• STRUCTURAL FRAME, INCL. COLUMNS, GIRDERS, TRUSSES. 0 0

• BEARING WALLS (EXTERIOR) 2 N/A

• BEARING WALLS (INTERIOR) 0 0

• NON-BEARING WALLS

1. EXTERIOR 0 0

2. INTERIOR 0 0

• FLOOR CONST, INCL. SUPPORTING BEAMS & JOISTS 0 0

• ROOF CONST, INCL. SUPPORTING BEAMS & JOISTS 0 0

FIRE SEPARATION ASSEMBLIES

• SHAFT ENCLOSURES (713): 1 1

• FIRE BARRIERS (707.3.10):

STAIRS 1 1

• FIRE PARTITIONS - CORRIDORS (708, 1020): 0 0

EGRESS

• CORRIDOR RATING(1020.1): 0 HOUR (W/ SPRINK) 0 HOUR

• EXIT ENCLOSURE RATING (1023.2) : 1 HOUR 1 HOUR

• EXIT ACCESS TRAVEL DISTANCE (1017.2) : 300 FT MAX 300 FT

• DEAD END (1020.4): 50 FT MAX 50 FT

• EGRESS WIDTHS (1005):

STAIRS .3" x 137 = 41.1" 48" CLEAR OTHER EGRESS COMPONENTS (DOORS) .2" x 179 = 27.4" MIN. 36"

• AREA OF REFUGE (1009.6): REQUIRED REQUIRED

• MINIMUM CORRIDOR WIDTHS (1020): 44" MIN. 63" CLEAR

• EXIT CONFIGURATION (1007.1):

MIN EXIT SEPARATION (SPRINKLERED) 1/3 LENGTH OF MAX DIAGONAL BUILDING DISTANCE

SEE LIFE SAFETY PLANS

• SPACES WITH ONE MEANS OF EGRESS (1006.2.1): MAX OCCUPANT LOAD MAX COMMON PATH OF TRAVEL

OCCUPANCY B 49 100

• NUMBER OF EXITS - SUMMARY: REQUIRED PROVIDED ACCESSIBLE

BASEMENT MIN 2 REQUIRED 3 PROVIDED 2 OF 3

FIRST FLOOR MIN 2 REQUIRED 3 PROVIDED 3 OF 3

SECOND FLOOR MIN 2 REQUIRED 3 PROVIDED 3 OF 3

MISCELLANEOUS TECHNICAL CHECKLIST REQUIRED PROVIDED

• ACCESSIBILITY (ANSI 117.1): YES YES

• EXTERIOR WALL OPENING PROTECTION (705.8):

FIRE SEPARATION DISTANCE 30' OR MORE NO LIMIT SEE PLANS

• AUTOMATIC SPRINKLER SYSTEM (903): YES YES

• STANDPIPE SYSTEM (905): NO NO

• SMOKE AND HEAT VENTS (910.2): NO NO

• MEANS OF EGRESS ILLUMINATION (1008): YES YES

• DRAFTSTOPPING (718): NO NO

• ILLUMINATED EXIT SIGNS (1013): YES YES

NOT REQUIRED IN ROOMS/AREAS REQUIRING ONLY ONE EXIT

• INTERIOR WALL AND CEILING FINISHES (803.13): REQUIRED PROVIDED

BUSINESS

EXIT STAIRWAYS CLASS B CLASS A OR B

CORRIDORS CLASS C CLASS A, B OR C

ROOMS AND ENCLOSED SPACES CLASS C CLASS A, B OR C

STAIRWAYS AND ELEVATORS REQUIRED PROVIDED

• WIDTH MIN. 48" 48"

• HEADROOM MIN. 6'-8" CLEAR 6'-8" CLEAR OR MORE

• RISERS MAX. 7" 7" OR LESS

• TREADS MIN. 11" 11" OR MORE

• LANDINGS MIN 48" 48" OR MORE

• RATED CONSTRUCTION 1-HR 1-HR

ENERGY CONSERVATION CODE - PRESCRIPTIVE PATH

• ZONE CLASSIFICATION: ZONE 5

BUILDING ENVELOPE PRESCRIPTIVE RQMTS REQUIRED PROVIDED

• ROOF ASSEMBLIES R-30 CI YES

• MASS WALLS R-12.5 CI YES

• WALLS ABOVE GRADE R-13 + R-7.5 CI YES

• WALLS BELOW GRADE R-7.5 CI YES

• FLOORS OVER UNCONDITIONED SPACE R-12.5 CI N/A

• SLAB-ON-GRADE R-10 FOR 24" YES

• OPAQUE DOORS R-4.75 YES

• FENESTRATION TBL C402.4 YES

• WINDOWS AND GLASS DOORS U = 0.36 - 0.77 YES

• SKYLIGHTS U = 0.5, <3% N/A

• GLAZED AREA C402.4.1 YES

• VERTICAL FENESTRATION <30% YES

IBC CODE COMPLIANCE SUMMARY:

REQUIRED PROVIDED

• FIRE EXTINGUISHERS (906.1): YES YES - SEE PLANS

MAX FLOOR AREA PER EXTINGUISHER 11,250 SF 11,250 SF OR LESS

MAX TRAVEL DISTANCE TO EXTINGUISHER 75' 75' OR LESS

LOCATED:

1. In Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies.

2. Within 30 feet (9144 mm) distance of travel from commercial cooking equipment and from domestic cooking equipment in

Group I-1; I-2, Condition 1; and R-2 college dormitory occupancies.

3. In areas where flammable or combustible liquids are stored, used or dispensed.

4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1 of the

International Fire Code.

5. Where required by the International Fire Code sections indicated in Table 906.1.

6. Special-hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official.

PLUMBING FIXTURE CALCULATIONS (BASED ON MASSACHUSETTS PLUMBING CODE)

• MINIMUM FACILITIES FOR BUILDING OCCUPANCY OTHER THAN RESIDENTIAL

• MEDICAL AND HEALTHCARE BUILDING TOILET FACILITIES

1. IN ALL MEDICAL AND HEALTH CARE BUILDINGS THERE SHALL BE SEPARATE DESIGNATED TOILET FACILITIES

ON EACH FLOOR FOR MALE AND FEMALE PATIENTS AND VISITORS.

2. THE TOILET FACILITIES MAY BE LOCATED IN A COMMON OR CORE AREA ON EACH FLOOR SO LONG AS THE

TOILET FACILITIES ARE WITHIN 300 FEET OF ALL OFFICES.

3. ACCESSIBILITY TO THE TOILET FACILITIES SHALL BE DIRECT; IT SHALL NOT REQUIRE GOING FROM ONE

MEDICAL OFFICE THROUGH ANOTHER FOR ACCESS TO THE TOILET FACILITIES.

4. HANDICAP TOILET FACILITIES ARE REQUIRED ON EACH FLOOR.

5. A MINIMUM OF ONE DRINKING FOUNTAIN SHALL BE INSTALLED FOR EACH SET OF TOILET FACILITIES.

• # OF BLDG OCCUPANTS: 277

B OCC. = 274 (138.5 FEMALE/138.5 MALE)

• WATER CLOSETSMALE

FEMALE 1 PER 45 = 3.08 (4)

MALE 1 PER 55 = 2.52 (3)

• LAVATORIES

FEMALE 1 PER 200 = .693 (1)

MALE 1 PER 200 = .693 (1)

• DRINKING FOUNTAINS 1 PER EACH SET OF RESTROOMS

• SERVICE SINK 1 = 1 (1)

SUMMARY REQUIRED PROVIDED % ACCESSIBLE

• WATER CLOSETS

FEMALE 4 4 4 OF 4 = 100%

MALE 3 3 3 OF 3 = 100%

MIXED USE 0 14 14 OF 14 = 100%

TOTAL 7 21 21 OF 21 = 100%

• LAVATORIES

FEMALE 1 4 4 OF 4 = 100%

MALE 1 3 3 OF 3 = 100%

MIXED USE 0 14 14 OF 14 = 100%

TOTAL 2 21 14 OF 14 = 100%

• DRINKING FOUNTAINS 3 6 (3 HIGH-LOW) 3 OF 6 = 50%

• SERVICE SINK 1 3 N/A

NFPA 101 CODE COMPLIANCE SUMMARY:

REQUIRED PROVIDED

• STAIR WIDTH (TABLE 7.2.2.2.1.2 (B)) <2000 PEOPLE = 44" 48"

• COMMON PATH OF TRAVEL (39.2.5.2.1) 100' X

• MAXIMUM TRAVEL DISTANCE (39.2.6.3) 300' W/ SPRINKLER X

• MAXIMUM DEAD END (39.2.5.3) 50' W/ SPRINKLER X

• CORRIDOR RATING 0 0

• CORRIDOR WIDTH (39.2.3.2) 44" X

• MINIMUM NUMBER OF REQ'D EXITS (39.2.4) 2 PER FLOOR MIN. 2 PER FLOOR

• AREA OF REFUGE (7.2.12) REQUIRED X

• FIRE EXTINGUISHERS (9.7.4.1) CLASS ABC MAX 75' APART X

EXIT

Room name

15,000 SF

100 SF

PATH INTO EXIT

1-HOUR BARRIER

ROOM TAG

LIFE SAFETY LEGEND:

ROOM AREA

ROOM OCCUPANT LOAD FACTOR

NO. OF OCCUPANTS

STAIR, OR DOOR EGRESS TAG

STAIR OR DOOR CLEAR WIDTH

EXIT CAPACITY FACTOR

EXIT CAPACITY

ACTUAL OCCUPANT LOAD

2-HOUR BARRIER

CIRCULATION PATH

TRAVEL DISTANCE LINE

Travel Distance Path ID TRAVEL DISTANCE TAG

MOST REMOTE POINT OF EGRESS ACCESS

FS FIRE SHUTTER

ROOM IDENTIFIER

MRP

EXIT ACCESS TRVEL DISTANCE TO AN EXIT (IN FEET)100

STAIR OR DOOR IDENTIFIER

max.

actualin. in.

44 0.3

FE

F

F

FEC

S

EXIT DISCHARGE

SMOKE CONTAINMENT BARRIER

FIRE DEPT. CONNECTION

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER WALL HUNG

ACCESSIBLE ENTRY/EGRESS

FIRE ALARM VISIBLE ONLY NOTIFICATION

INDICATOR

FIRE ALARM AUDIBLE/VISIBLE NOTIFICATION

INDICATOR

EXIT SIGN

MECHANICAL AREA

DOOR/FIXTURE CLEARANCE

TURNING RADIUS

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:4

AM

GI101

CODE COMPLIANCE SUMMARY WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 MC MC/MP/BL

200 SPRINGS ROAD, BEDFORD, MA 01730

A

B

C

D

E

1 2 3 4 5 6 7 8 9 10

11 12 max.

actualin. in.

DOOR

40 0.2 max.

actualin. in.

DOOR

34 0.3 max.

actual in.in.

DOOR

380.3

PATH 1A: 71' TRAVEL DISTANCE PATH 1B: 78' TRAVEL DISTANCE

PATH 1C: 59' TRAVEL DISTANCE

FEC

DNDN @ MAX 1:20 DN

DN @ MAX 1:20

DN @ MAX 1:20

DN @ MAX 1:20

DN

DN

DN

DN

MRP

MRP

MRP

2691 SF

BUSINESS

150 1995 SF

BUSINESS

EX

IT

EXIT EXIT

USE CLASSIFICATION

Assembly Concentrated (chairs only - not fixed)

Business Areas (IBC 2018)

FEC

1046 SF

ASSEMBLY

EXIT

Room name

15,000 SF

100 SF

PATH INTO EXIT

1-HOUR BARRIER

ROOM TAG

LIFE SAFETY LEGEND:

ROOM AREA

ROOM OCCUPANT LOAD FACTOR

NO. OF OCCUPANTS

STAIR, OR DOOR EGRESS TAG

STAIR OR DOOR CLEAR WIDTH

EXIT CAPACITY FACTOR

EXIT CAPACITY

ACTUAL OCCUPANT LOAD

2-HOUR BARRIER

CIRCULATION PATH

TRAVEL DISTANCE LINE

Travel Distance Path ID TRAVEL DISTANCE TAG

MOST REMOTE POINT OF EGRESS ACCESS

FS FIRE SHUTTER

ROOM IDENTIFIER

MRP

EXIT ACCESS TRVEL DISTANCE TO AN EXIT (IN FEET)100

STAIR OR DOOR IDENTIFIER

max.

actualin. in.

44 0.3

FE

F

F

FEC

S

EXIT DISCHARGE

SMOKE CONTAINMENT BARRIER

FIRE DEPT. CONNECTION

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER WALL HUNG

ACCESSIBLE ENTRY/EGRESS

FIRE ALARM VISIBLE ONLY NOTIFICATION

INDICATOR

FIRE ALARM AUDIBLE/VISIBLE NOTIFICATION

INDICATOR

EXIT SIGN

MECHANICAL AREA

DOOR/FIXTURE CLEARANCE

TURNING RADIUS

A

B

C

D

E

1 2 3 4 5 6 7 8 9 10

11 12

1810 SF

MECH/ELEC

3519 SF

BUSINESS

max.

actualin. in.

40 0.2

48 EX

IT

max.

actualin. in.

36 0.2

MRP

EX

IT

max.

actualin. in.

34 0.3

PATH 0A: 67' TRAVEL DISTANCE PATH 0B: 66' TRAVEL DISTANCE

FEC

EXIT

USE CLASSIFICATION

Accessory Storage Areas, Mechanical Equipment Room

Assembly Unconcentrated (Tables and Chairs)

Business Areas (IBC 2018)

FEC

435 SF

MULTI-PURPOSE

ROOM

PA

TH

C:

6`

AV

EL

D

IS

TA

NC

E

NON-ACCESSIBLE EXIT

PROVIDE SIGNAGE INDICATING

THIS IS A NON-ACCESSIBLE EXIT

FEC

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:5

AM

GI102

GROUND & FIRST FLOOR CODE

COMPLIANCE PLANS

WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 MC MC/MP/BL

200 SPRINGS ROAD, BEDFORD, MA 01730

SCALE: 1/8" = 1'-0"C2 FIRST FLOOR CODE COMPLIANCE PLAN

SCALE: 1/8" = 1'-0"F2 GROUND FLOOR CODE COMPLIANCE PLAN

A

B

C

D

E

1 2 3 4 5 6 7 8 9 10

11 12

EXIT

Room name

15,000 SF

100 SF

PATH INTO EXIT

1-HOUR BARRIER

ROOM TAG

LIFE SAFETY LEGEND:

ROOM AREA

ROOM OCCUPANT LOAD FACTOR

NO. OF OCCUPANTS

STAIR, OR DOOR EGRESS TAG

STAIR OR DOOR CLEAR WIDTH

EXIT CAPACITY FACTOR

EXIT CAPACITY

ACTUAL OCCUPANT LOAD

2-HOUR BARRIER

CIRCULATION PATH

TRAVEL DISTANCE LINE

Travel Distance Path ID TRAVEL DISTANCE TAG

MOST REMOTE POINT OF EGRESS ACCESS

FS FIRE SHUTTER

ROOM IDENTIFIER

MRP

EXIT ACCESS TRVEL DISTANCE TO AN EXIT (IN FEET)100

STAIR OR DOOR IDENTIFIER

max.

actualin. in.

44 0.3

FE

F

F

FEC

S

EXIT DISCHARGE

SMOKE CONTAINMENT BARRIER

FIRE DEPT. CONNECTION

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER WALL HUNG

ACCESSIBLE ENTRY/EGRESS

FIRE ALARM VISIBLE ONLY NOTIFICATION

INDICATOR

FIRE ALARM AUDIBLE/VISIBLE NOTIFICATION

INDICATOR

EXIT SIGN

MECHANICAL AREA

DOOR/FIXTURE CLEARANCE

TURNING RADIUS

A

B

C

D

E

1 2 3 4 5 6 7 8 9 10

11 12 max.

actualin. in.

STAIR

44 0.3

5757 SF

BUSINESS

150 max.

actual in.in.

STAIR

440.3 max.

actualin. in.

DOOR

34 0.3 max.

actual in.in.

DOOR

340.3

MRP

PATH 2A: 134' TRAVEL DISTANCE PATH 2B: 58' TRAVEL DISTANCE

USE CLASSIFICATION

Business Areas (IBC 2018)

FEC FEC

ARA

PROVIDE AREA OF RESCUE

ASSISTANCE WITH TWO-WAY

COMMUNICATION DEVICE

ARA

PROVIDE AREA OF RESCUE

ASSISTANCE WITH TWO-WAY

COMMUNICATION DEVICE

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:1

AM

GI103

SECOND FLOOR & ATTIC CODE

COMPLIANCE PLANS

WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 RJC MLB

200 SPRINGS ROAD, BEDFORD, MA 01730

SCALE: 1/8" = 1'-0"C2 ATTIC CODE COMPLIANCE PLAN

SCALE: 1/8" = 1'-0"F2 SECOND FLOOR CODE COMPLIANCE PLAN