This document provides specifications for integrated door assemblies to be installed at a Veterans Affairs medical facility. The specifications cover metal doors, frames, hardware including exit devices, continuous hinges, seals, and finishes. The document requires door assemblies to meet ANSI standards for grade, fire resistance, and smoke resistance. It outlines submittal requirements, qualifications, delivery and storage, field conditions, warranties, and provides a schedule of door hardware sets specifying exit devices, hinges, closers, seals, and other components. Relevant agencies include the Department of Veterans Affairs and Veterans Health Administration.

View the file

Other files

File Type Posted
36C24123B0002 0011.docx DOCX document
Bedford Womens Health Construction RFIs 07262023.docx DOCX document
36C24123B0002 0010.docx DOCX document
518-21-103 Site Visit Sign-In Sheet.pdf PDF
List of Attachments.pdf PDF
36C24123B0002 0009.pdf PDF
Plumbing-21053.pdf PDF
branches_productsheet.pdf PDF
FP-20153.pdf PDF
Interiors-21053.pdf PDF
087100.pdf PDF
375-Ultra-Durable-Guide-Specifications-2109861.pdf PDF
090600 SCHEDULE FOR FINISHES.pdf PDF
Architectural-21053.pdf PDF
085113.pdf PDF
Structural-21053.pdf PDF
Civil-20153.pdf PDF
Mechanical-21053.pdf PDF
Electrical-21053.pdf PDF
General-21053.pdf PDF
074624.pdf PDF
375Info sheet.pdf PDF
518-21-103 012 HA102.pdf PDF
518-21-103 Bedford Womens Clinic RFIs (COMPILED).docx DOCX document
36C24123B0002 0008.docx DOCX document
518-21-103 012 HA101.pdf PDF
028211_Bedford VAMC Bldg 12.pdf PDF
02833313_Bedford VAMC Bldg 12.pdf PDF
518-21-103 Contracting and VA RFIs.docx DOCX document
36C24123B0002 0007.docx DOCX document
36C24123B0002 0006.docx DOCX document
36C24123B0002 0005.docx DOCX document
36C24123B0002 0004.docx DOCX document
100 - Interior.pdf PDF
36C24123B0002 0003.docx DOCX document
36C24123B0002 0002.docx DOCX document
36C24123B0002_2.docx DOCX document
36C24123B0002 0001.docx DOCX document
Full Set Drawings.pdf PDF
36C24123B0002_1.docx DOCX document
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.pdf PDF
S02 PRE-AWARD CONTRACTOR EVALUATION FORM.pdf PDF
General Decision MA20230001 03032023.pdf PDF
SOW 518-21-103 Womens Health Construction.pdf PDF
Asbestos Documents.pdf PDF
100 Percent Specifications.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

06-09-23

08 17 10 - 1

SECTION 08 17 10

INTEGRATED DOOR ASSEMBLIES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Integrated door assemblies including metal door frame, door, and hardware, unless specified in another Section, installed at cross-corridor locations.

B. Smoke and draft control seals, unless specified in another Section.

1.2 RELATED WORK

A. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS: Non-Flooring

Adhesives and Sealants and Paints and Coatings VOC Limits.

B. Section 08 71 00, DOOR HARDWARE: Lock Cylinders.

C. Section 08 71 13, AUTOMATIC DOOR OPERATORS: Automatic Door Operators.

D. Section 09 06 00, SCHEDULE FOR FINISHES: Door and Frame Color.

E. DIVISION 26, ELECTRICAL: Electrical Power.

1.3 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this section.

B. Builders Hardware Manufacturers Association (BHMA):

A156.3-14...............Exit Devices.

A156.26-06..............Continuous Hinges.

A156.32-14..............Integrated Door Opening Assemblies.

C. ASTM International (ASTM):

A1011/A1011M-18a........Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved

Formability, and Ultra-High Strength.

E2180-18................Determining the Activity of Incorporated

Antimicrobial Agents in Polymeric or

Hydrophobic Materials.

D. Door and Hardware Institute (DHI):

1. Recommended Locations for Architectural Hardware for Standard Doors

& Frames (2004).

2. Recommended Locations for Builders' Hardware Custom Steel Doors &

Frames (1996).

E. National Fire Protection Association (NFPA):

08 17 10 - 2

105-16..................Smoke Door Assemblies and Other Opening

Protectives.

252-12..................Fire Tests of Door Assemblies.

F. Steel Door Institute (SDI):

A250.3-11...............Test Procedure and Acceptance Criteria for

Factory Applied Finish Coatings for Steel Doors and Frames.

A250.8-14...............Specifications for Standard Steel Doors and

Frames.

A250.10-11..............Test Procedure and Acceptance Criteria for

Prime Painted Steel Surfaces for Steel Doors and Frames.

G. UL LLC (UL):

10C-09..................Positive Pressure Fire Tests of Door

Assemblies.

1784-15.................Air Leakage Tests of Door Assemblies and Other

Opening Protectives.

1.4 PREINSTALLATION MEETINGS

A. Conduct preinstallation meeting at project site minimum 30 days before beginning Work of this section.

1. Required Participants:

a. Contracting Officer's Representative.

b. Architect/Engineer.

c. Contractor.

d. Installer.

e. Other installers responsible for adjacent and intersecting work, including electrical.

2. Meeting Agenda: Distribute agenda to participants minimum 3 days before meeting.

a. Installation schedule.

b. Installation sequence.

c. Preparatory work.

d. Protection before, during, and after installation.

e. Installation.

f. Transitions and connections to other work.

g. Other items affecting successful completion.

08 17 10 - 3

3. Document and distribute meeting minutes to participants to record decisions affecting installation.

1.5 SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Submittal Drawings:

1. Show size, configuration, and fabrication and installation details.

2. For each opening, list finish hardware items included in assembly, finish, degree of opening, and electrical rough-in requirements according to Door Schedule.

3. Submit templates to door and frame manufacturers to ensure proper size and location of hardware.

C. Manufacturer's Literature and Data:

1. Description of each product.

2. Installation instructions.

D. Sustainable Construction Submittals:

1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.

2. Low Pollutant-Emitting Materials:

a. Show volatile organic compound types and quantities.

E. Certificates: Indicate integrated door assemblies comply with specifications.

1. Show fire rated integrated door assembly is UL Listed for specified application.

F. Qualifications: Substantiate qualifications comply with specifications.

1. Installer.

G. Operation and Maintenance Data:

1. Care instructions for each exposed finish product.

2. Maintenance and adjustment instructions for integrated door assemblies.

1.6 QUALITY ASSURANCE

A. Installer Qualifications:

1. Regularly installs specified products.

2. Installed specified products with satisfactory service on five similar installations for minimum five years.

a. Provide contact names and addresses for completed projects when requested by Contracting Officer's Representative.

08 17 10 - 4

1.7 DELIVERY

A. Deliver products in manufacturer's original sealed packaging.

B. Mark packaging, legibly. Indicate manufacturer's name.

C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.

1.8 STORAGE AND HANDLING

A. Store products indoors in dry, weathertight facility.

B. Protect products from damage during handling and construction operations.

1.9 FIELD CONDITIONS

A. Field Measurements: Verify field conditions affecting integrated door assembly fabrication and installation. Show field measurements on

Submittal Drawings.

1. Coordinate field measurement and fabrication schedule to avoid delay.

2. Coordinate electrical work for electrified hardware installation.

1.10 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of

Construction."

B. Manufacturer's Warranty: Warrant door closers and hinges against material and manufacturing defects.

1. Warranty Periods:

a. Door Closers: 10 years.

b. Steel Pinned Continuous Hinges: 10 years.

PART 2 - PRODUCTS

2.1 SYSTEM PERFORMANCE

A. Design integrated door assemblies complying with specified performance:

1. BHMA A156.32: Grade 1: 1,000,000 cycles.

B. Fire Rated Doors:

1. Fire Resistance Rating: As shown in Door Schedule.

2. Label: Comply with NFPA 252, UL 10C, and labeled by qualified testing and inspection agency showing fire resistance rating.

C. Smoke Rated Doors:

1. Smoke Resistance Rating: As shown in Door Schedule.

2. Label: Comply with NFPA 105, UL 1784, and labeled by qualified testing and inspection agency showing smoke resistance rating.

08 17 10 - 5

2.2 PRODUCTS - GENERAL

A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.

B. Provide each integrated door assembly from one manufacturer.

C. Sustainable Construction Requirements:

1. Steel Recycled Content: 30 percent total recycled content, minimum.

2. Low Pollutant-Emitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:

a. Non-flooring adhesives and sealants.

b. Paints and coatings.

2.3 INTEGRATED DOOR ASSEMBLY

A. Metal Doors: SDI A250.8; Level 2 and Physical Performance Level B, heavy duty; Model 2 seamless.

1. Face: ASTM A1011/A1011M; cold rolled steel, 1.0 mm (0.04 inches) thick, minimum.

a. Cladding: Plastic laminate .

2. Core: Kraft paper honeycomb or polystyrene.

3. Thickness: 44 mm (1-3/4 inch).

4. Reinforce door for hardware installation.

B. Metal Frames: SDI A250.8 Level 2.

1. Metal: ASTM A1011/A1011M; cold rolled steel, 1.3 mm (0.05 inches) thick, minimum.

2. Construction: Continuously welded.

3. Reinforce frame for hardware.

a. Continuous Hinges: 2.3 mm (0.09 inches) thick.

b. Other Hardware: Comply with SDI A250.8.

4. Frame Anchors: Provide adjustable type anchors coordinated with wall construction, minimum 4 per jamb.

C. Integrated Hardware:

1. Exit Device: BHMA A156.3; Grade 1, passage function, inset in door face, clean and unobtrusive in design.

a. Push Bar End Caps: Metal, plated satin nickel (BHMA 619) finish.

b. Exit Device Trim: Lever matching door hardware specified in

Section 08 71 00, DOOR HARDWARE.

2. Continuous Hinges: BHMA A156.26.

08 17 10 - 6

a. Plastic Laminate Clad Doors: Wrap-around style hinge guards and provide stainless steel wrap-around edge guards at strike edge of door.

3. Other Hardware: As scheduled in this section.

2.4 FINISHES

A. Hardware Finish Symbols:

TABLE I – Hardware Finish Symbols

US BHMA 156.18 Description

USP 600 Primed for field painting

US15 619 Dull Nickel Plated

US26D 626/652 Satin Chrome Plated

US28 628 Satin Aluminum

US32 629 Bright Stainless

US32D 630 Satin Stainless

N/A 689 Aluminum Painted

B. Finish Requirements:

1. Door Faces: Plastic Laminate .

2. Frames: Factory Pre-Finished, SDI A250.3 .

3. Door Hardware:

a. Continuous Hinges: BHMA 630.

b. Push Bar: BHMA 630 clad with BHMA 619 end caps.

c. Exit Device Trim: BHMA 630.

d. Push/Pull Trim: BHMA 626.

e. Door Closers: BHMA 689.

f. Miscellaneous: To match other finishes.

4. Anti-Microbial Coating: ASTM E2180; ionic silver coating.

5. Apply coating to hand-operated hardware including levers, pulls, push bars, push plates, and paddles.

PART 3 - EXECUTION

3.1 PREPARATION

A. Examine and verify substrate suitability for product installation.

B. Protect existing construction and completed work from damage.

3.2 INSTALLATION - INTEGRATED DOOR ASSEMBLIES

A. Install products according to manufacturer's instructions and approved submittal drawings .

B. Install door hardware at locations indicated in DHI Recommended

Locations for Architectural Hardware for Standard Steel Doors & Frames

08 17 10 - 7 and DHI Recommended Locations for Builders' Hardware Custom Steel Doors

& Frames, unless otherwise indicated, or to comply with requirements of governing regulations, or if otherwise directed by Contracting

Officer's Representative.

C. Install door hardware in compliance with manufacturers' instructions, and templates. Comply with specified degree of opening for doors with automatic operators and overhead door closers. Securely fasten hardware. Confirm operating parts move freely and smoothly without binding, sticking, and excessive clearance.

D. Coordinate installation and interface wiring with fire alarm and smoke detection systems. Provide auxiliary contacts, relays, and interface for fire alarm and security systems.

E. Remove or protect door hardware, before painting and finishing performed after integrated door assembly installation.

F. Adjust and check door assembly and each operating hardware item to ensure correct operation and function. Replace products which cannot be adjusted to operate as intended.

G. Final Adjustment: Perform final hardware check and adjustment maximum one month before building acceptance or partial building occupancy.

3.3 CLEANING

A. Clean exposed surfaces, including hardware. Do not use cleaners that will harm finishes.

3.4 PROTECTION

A. Protect integrated door assemblies from construction operations.

3.5 SCHEDULES

A. The following is a general listing of the Integrated Door Assembly requirements and is not intended for use as a final door submittal.

Provide hardware items required by established standards and practices, and to meet IBC and NFPA 101 whether specified or not in the following listed groups.

HW-6D

Each [ADO] Integrated Door to Have: RATED

1 Steel Frame -

1 Integrated Door w/Exit Device Q2131 x TYPE 8 ELECTRIC DEVICE (E04) x F08 LEVER

1 Continuous Transfer Hinge A51031B x 8-THRUWIRE

TRANSFER x IN-HINGE ACCESS PANEL

08 17 10 - 8

Each [ADO] Integrated Door to Have: RATED

1 Power Supply BY EXIT DEVICE MFR. FOR E04 FUNCTION

1 Armor Plate J101 x 1.275 mm (0.050 inch)

THICKNESS

1 Floor Stop L02121 x 3 FASTENERS

1 Set Self-Adhesive Seals R0E154

1. Each [ADO] Integrated Door to Have:

a. Power transfer shared by electric panic and re-activation sensor wiring (re-activation sensors provided by Section 08 71 13).

b. Lock cylinder by section 08 71 00, door hardware.

c. Auto door operator and controls by Section 08 71 13, AUTOMATIC

DOOR OPERATORS.

HW-8

Each [MHO] Pair Integrated Doors to Have: RATED

1 Steel Frame -

1 Integrated Pair Doors w/Auto

Flush Bolts & Push/Pull Trim

Q2241 x TYPE 25 LESS BOTTOM

BOLT AUTO FLUSH BOLT (INACTIVE

LEAF) x ACTIVE CONCEALED

VERTICAL LATCH (ACTIVE LEAF)

2 Continuous Hinges A51031B x WIDE THROW AS

REQUIRED TO ACHIEVE FULL DOOR

SWING

1 Coordinator TYPE 21A

1 Self-Adhesive Astragal R0Y_14

2 Closers C02011 (PT4D, PT4H) x 180°

SWING

2 Magnetic Holders C00011 TRI-VOLTAGE

1 Set Self-Adhesive Seals R0E154

2. Power, wiring, conduit, and fire alarm connection by Division 26.

HW-12A

Each [ADO] Integrated Door to Have: RATED

1 Steel Frame -

1 Integrated Pair Doors w/Exit

Devices and Pull Trim

Q2231 x TYPE 8 EXIT DEVICES

(F01/ACTIVE FLUSH PULL PASSAGE

TRIM)

2 Continuous Hinges A51031B

1 Self-Adhesive Astragal R0Y_14

08 17 10 - 9

Each [ADO] Integrated Door to Have: RATED

2 Closers C02011/C02021 (PT4D, PT4H)

2 Magnetic Holders C00011 TRI-VOLTAGE

1 Set Self-Adhesive Seals R0E154

3. Power, wiring, conduit, and fire alarm connection by Division 26.

HW-12B

Each [ADO] Pair Integrated Doors to Have: RATED

1 Steel Frame -

1 Integrated Pair Doors w/Elec

Exit Devices

Q2231 x TYPE 8 (E04) ELECTRIC

EXIT DEVICES (F01/F08)

2 Continuous Transfer Hinges A51031B x 8-THRUWIRE

TRANSFER x IN-HINGE ACCESS

PANEL

1 Power Supply BY EXIT DEVICE MFR. FOR E04

FUNCTION

1 Self-Adhesive Astragal R0Y_14

2 Armor Plates J101 x 1.275 mm (0.050 inch)

THICKNESS

2 Floor Stops L02121 x 3 FASTENERS

1 Set Self-Adhesive Seals R0E154

4. Power, wiring, conduit, and fire alarm connection by Division 26.

a. Power transfer shared by electric panic and re-activation sensor wiring (re-activation sensors provided by section 08 71 13).

b. Lock cylinder by Section 08 71 00, door hardware.

c. Auto door operator and controls by Section 08 71 13, AUTOMATIC

DOOR OPERATORS.

HW-12C

Each [ADO] Pair Integrated Double Egress Doors to Have: RATED

1 Steel Frame -

1 Integrated Pair Doors w/Exit Devices Q2331 x TYPE 8 EXIT DEVICES (F01)

2 Continuous Hinges A51031B

1 Overlapping Astragal with Self-Adhesive Seal

R5Y634 x R0E154 x THRU-BOLTS

2 Closers C02011/C02021 (PT4D, PT4H)

08 17 10 - 10

Each [ADO] Pair Integrated Double Egress Doors to Have:

RATED

2 Magnetic Holders C00011 TRI-VOLTAGE

1 Set Self-Adhesive Seals R0E154

5. Power, wiring, conduit, and fire alarm connection by Division 26.

HW-12D

Each [ADO] Pair Integrated Double Egress Doors to Have:

RATED

1 Steel Frame -

1 Integrated Pair Doors w/Elec Exit

Exit Devices Q2331 x TYPE 8 (E04) ELECTRIC

EXIT DEVICES (F01)

2 Continuous Transfer Hinges A51031B x 8-THRUWIRE

TRANSFER x IN-HINGE ACCESS

PANEL

1 Power Supply BY EXIT DEVICE MFR. FOR E04

FUNCTION

1 Overlapping Astragal with Self-Adhesive Seal

R5Y634 x R0E154 x THRU-BOLTS

2 Armor Plates J101 x 1.275 mm (0.050 inch)

THICKNESS

2 Floor Stops L02121 x 3 FASTENERS

1 Set Self-Adhesive Seals R0E154

6. Power, wiring, conduit, and fire alarm connection by Division 26.

a. Power transfer shared by electric panic and re-activation sensor wiring (re-activation sensors provided by Section 08 71 13).

b. Auto door operator and controls by Section 08 71 13, AUTOMATIC

DOOR OPERATORS.

HW-SH-4

Each [AC, EL, REX, DPS]Integrated Door to Have:

RATED

1 Steel Frame -

1 Integrated Door w/Elec. Exit Device Q2131 x TYPE 8 ELECTRIC DEVICE (E01, E05/E06-VERIFY)x F13 LEVER

1 Continuous Transfer Hinge A51031B x 4-THRUWIRE TRANSFER x

IN-HINGE ACCESS PANEL

1 Power Supply REGULATED, FILTERED, 24VDC, AMPERAGE AS REQUIRED

1 Closer C02021 (PT4D, PT4F, PT4H)

08 17 10 - 11

Each [AC, EL, REX, DPS]Integrated Door to Have:

RATED

1 Armor Plate J101 x 1.275 mm (0.050 inch)

THICKNESS

1 Floor Stop L02121 x 3 FASTENERS

1 Set Self-Adhesive Seals R0E154

1 Alarm Contact -

B. 120VAC power, conduit, and wiring by Division 26.

1. Card reader by Division 28.

2. Lock cylinder by Section 08 71 00, DOOR HARDWARE.

HW-SH-4A

Each [ADO, AC, ELR, REX, DPS] Integrated Door to Have: RATED

1 Steel Frame -

1 Integrated Door w/Elec Exit

Device Q2131 x TYPE 8 ELECTRIC DEVICE (E01, E04)x F13 LEVER

1 Continuous Transfer Hinge A51031B x 12-THRUWIRE TRANSFER x

IN-HINGE ACCESS PANEL

1 Power Supply BY EXIT DEVICE MFR. FOR E04

FUNCTION

1 Armor Plate J101 x 1.275 mm (0.050 inch)

THICKNESS

1 Floor Stop L02121 x 3 FASTENERS

1 Set Self-Adhesive Seals R0E154

1 Alarm Contact -

C. 120VAC power, conduit, and wiring by Division 26.

1. Auto door operator and controls by Section 08 71 13, AUTOMATIC DOOR

OPERATORS.

2. Card reader by Division 28.

3. Power transfer shared by electric panic and re-activation sensor wiring (re-activation sensors provided by Section 08 71 13).

4. Lock cylinder by Section 08 71 00, DOOR HARDWARE.

HW-SH-10

Each [AC, EL, REX, DPS] Pair Integrated Doors to Have:

RATED

1 Steel Frame -

1 Integrated Pair Doors w/Elec Exit Devices

Q2231 x TYPE 8 EXIT DEVICES

08 17 10 - 12

Each [AC, EL, REX, DPS] Pair Integrated Doors to Have:

RATED

(F01-E01/F13-E01, E05/E06-VERIFY)

2 Continuous Transfer Hinges A51031B x 4-THRUWIRE TRANSFER x

IN-HINGE ACCESS PANEL

1 Power Supply Regulated, Filtered, 24VDC, Amperage

1 Self-Adhesive Astragal R0Y_14

2 Closers C02021 (PT4D, PT4F, PT4H)

2 Armor Plates J101 x 1.275 mm (0.050 inch)

THICKNESS

2 Floor Stops L02121 x 3 FASTENERS

1 Set Self-Adhesive Seals R0E154

5. Power, wiring, and conduit by Division 26.

6. Lock cylinder by Section 08 71 00, DOOR HARDWARE.

HW-SH-10A

Each [AC, ADO, EL, REX, DPS] Pair Integrated Doors to Have:

RATED

1 Steel Frame -

1 Integrated Pair Doors w/Elec. Exit Devices

Q2231 x TYPE 8 (E01, E04)

ELECTRIC EXIT DEVICES

(F01/F08)

2 Continuous Transfer Hinges A51031B x 12-THRUWIRE TRANSFER x IN-HINGE ACCESS PANEL

1 Power Supply

BY EXIT DEVICE MFR. FOR E04

FUNCTION

1 Self-Adhesive Astragal R0Y_14

2 Armor Plates J101 x 1.275 mm (0.050 inch)

THICKNESS

2 Floor Stops L02121 x 3 FASTENERS

1 Set Self-Adhesive Seals R0E154

D. Power, wiring, conduit, and fire alarm connection by Division 26.

1. Power transfer shared by electric panic and re-activation sensor wiring (re-activation sensors provided by Section 08 71 13).

2. Lock cylinder by Section 08 71 00, DOOR HARDWARE.

3. Auto door operator and controls by Section 08 71 13, AUTOMATIC DOOR

OPERATORS.

HW-SH-12

08 17 10 - 13

Each [AC, ADO, EL, REX, DPS] Integrated Door to Have:

NON-RATED

1 Steel Frame -

1 Integrated Door w/Elec. Exit Device Q2131 x TYPE 8 ELECTRIC DEVICE (E01, E04) x F03 OUTSIDE CYLINDER

ONLY

1 Continuous Transfer Hinge A51031B x 12-THRUWIRE TRANSFER x

IN-HINGE ACCESS PANEL

1 Power Supply BY EXIT DEVICE MFR. FOR E04

FUNCTION

1 Offset Pull J402 x 1” (25mm) DIAMETER x 12” (305mm)CTC

1 Closer C02021 (PT4D, PT4F, PT4H)

1 Kick Plate J102

1 Floor Stop L02121 x 3 FASTENERS

1 Threshold J35130 x SILICONE GASKET

1 Door Sweep 90100CNB (PEMKO), OR EQUAL

1 Set Frame Seals 2891AS X CSK SCREWS (PEMKO), OR

EQUAL

1 Drip R0Y976

1 Alarm Contact -

E.

F. 120VAC power, conduit, and wiring by DIVISION 26.

1. Card reader by DIVISION 28.

2. Lock cylinder by Section 08 71 00, DOOR HARDWARE.

G. All hardware to be coordinated with and submitted by ahc certified consultant to provide a complete and workable system, including necessary components not specifically listed.

- - E N D - -