Architectural-21053.pdf

PDF 22 MB Posted

Attached to
Z1DA--518-21-103 Women's Health 3 floors Construction Presolicitation Notice
Solicitation number
36C24123B0002
Issued by

About this file

This notice provides details for a solicitation by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1. The solicitation, numbered 36C24123B0002, is for construction services to build three floors of women's health facilities. Interested parties should refer to the attached architectural plans PDF file for additional specifications. The opportunity is designated as a solicitation and is seeking responses for the construction of new women's health floors at a VA medical center within VISN 1. The agency point of contact and response deadline are not provided in this presolicitation notice.

View the file

Other files

File Type Posted
36C24123B0002 0011.docx DOCX document
Bedford Womens Health Construction RFIs 07262023.docx DOCX document
36C24123B0002 0010.docx DOCX document
518-21-103 Site Visit Sign-In Sheet.pdf PDF
List of Attachments.pdf PDF
36C24123B0002 0009.pdf PDF
Plumbing-21053.pdf PDF
branches_productsheet.pdf PDF
FP-20153.pdf PDF
Interiors-21053.pdf PDF
087100.pdf PDF
375-Ultra-Durable-Guide-Specifications-2109861.pdf PDF
090600 SCHEDULE FOR FINISHES.pdf PDF
081710.pdf PDF
085113.pdf PDF
Structural-21053.pdf PDF
Civil-20153.pdf PDF
Mechanical-21053.pdf PDF
Electrical-21053.pdf PDF
General-21053.pdf PDF
074624.pdf PDF
375Info sheet.pdf PDF
518-21-103 012 HA102.pdf PDF
518-21-103 Bedford Womens Clinic RFIs (COMPILED).docx DOCX document
36C24123B0002 0008.docx DOCX document
518-21-103 012 HA101.pdf PDF
028211_Bedford VAMC Bldg 12.pdf PDF
02833313_Bedford VAMC Bldg 12.pdf PDF
518-21-103 Contracting and VA RFIs.docx DOCX document
36C24123B0002 0007.docx DOCX document
36C24123B0002 0006.docx DOCX document
36C24123B0002 0005.docx DOCX document
36C24123B0002 0004.docx DOCX document
100 - Interior.pdf PDF
36C24123B0002 0003.docx DOCX document
36C24123B0002 0002.docx DOCX document
36C24123B0002_2.docx DOCX document
36C24123B0002 0001.docx DOCX document
Full Set Drawings.pdf PDF
36C24123B0002_1.docx DOCX document
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.pdf PDF
S02 PRE-AWARD CONTRACTOR EVALUATION FORM.pdf PDF
General Decision MA20230001 03032023.pdf PDF
SOW 518-21-103 Womens Health Construction.pdf PDF
Asbestos Documents.pdf PDF
100 Percent Specifications.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UP

DEMOLITION NOTES:

1. COORDINATE EXTENT OF DEMOLITION WITH

LOCATIONS OF PARTITIONS DESCRIBED ON PLANS

AND WITH LOCATIONS OF FINISHES NOTED AS

EXISTING TO REMAIN.

2. ANY WALL, PARTITION OR SURFACE DISTURBED

BECAUSE OF NEW WORK OR DEMOLITION SHALL BE

PATCHED AND FINISHED CONTINUOUSLY TO THE

NEAREST CORNER UNLESS NOTED OTHERWISE,

MATCH EXISTING ADJACENT CONSTRUCTION

FINISHES, CONTINUITY AND FIRE RATINGS UNLESS

NOTED OTHERWISE.

3. PROTECT ALL FINISHES, MATERIALS AND EQUIPMENT

NOTED AS EXISTING TO REMAIN. CONTRACTOR SHALL

BE RESPONSIBLE TO REPLACE ALL FINISHES,

MATERIALS AND EQUIPMENT DAMAGED DURING

CONSTRUCTION.

4. DIMENSIONS INDICATED WITH A ± ARE EXISTING

CONDITION AND NEED TO BE VERIFIED IN FIELD.

5. CONTRACTOR TO HOLD A PRE-DEMOLITION MEETING

WITH OWNER, CONSTRUCTION MANAGER, SUB

CONTRACTORS, ETC. PRIOR TO BEGINNING

DEMOLITION WORK TO REVIEW HOSPITALS POLICIES,

NOISE CONTROL MEASURES, ETC.

6. CLEARLY INDENTIFY AND TAG MECHANICAL,

PLUMBING AND ELECTRICAL FIXTURES OR EQUIPMENT

THAT ARE STILL IN USE PRIOR TO DEMOLITION TO

AVOID ACCIDENTAL REMOVAL.

7. SEE MECHANICAL, ELECTRICAL AND PLUMBING

DRAWINGS FOR THE SCOPE OF DEMOLITION IN THOSE

DISCIPLINES.

HAZARDOUS MATERIALS

GENERAL NOTE:

HAZARDOUS MATERIALS MAY BE PRESENT THROUGHOUT

THE BUILDING AND SITE. REFERENCE HAZARDOUS

MATERIALS SURVEY AND ASSOIATED SPECIFICATIONS AND

DRAWINGS FOR ADDITIONAL INFORMATION.

A

B

C

D

E

1 2 3 4 5 6 7 8 9 10

3 4 111111

3 43 43 43 43 43 43 43 43 43 43 43 43 4

1 1

1 1 1 3 43 4

3 43 4

3 4

2222222222222

222222 2 2

INFILL OPENINGS IN

FLOOR SLAB TO

PROVIDE CODE

COMPLIANT

SEPARATION BETWEEN

FLOORS.

1 8 7 7

22 2 2

14 14 14 14 14 14

14 14

14 14 14 14 14 14

141414141414141414141414

3 4

3 43 43 4 1 1 1 1 1 1

11111

1313 13

13131313

13131313

1313 13 13 13 13 13 13 13

REMOVE STAIR, RAILS, SLAB

AND RETAINING WALL

REMOVE STAIR, RAILS, SLAB

AND RETAINING WALL

REMOVE STAIR, RAILS, SLAB

AND RETAINING WALL

1_

TRENCHED AREA

TRENCH LEGEND:

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:0

AM

AD100

GROUND FLOOR DEMOLITION PLAN WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 MC MC/MP/BL

200 SPRINGS ROAD, BEDFORD, MA 01730

SCALE: 1/8" = 1'-0"F2 GROUND FLOOR DEMOLITION PLAN

DEMOLITION KEYNOTES LEGEND

KEYNOTE DESCRIPTION

1 REMOVE EXISTING WALL FROM FLOOR TO

STRUCTURE ABOVE.

2 REMOVE EXISTING DOOR AND FRAME ASSEMBLY

COMPLETE.

3 REMOVE EXISTING CEILING AND ALL ASSOCIATED

MECHANICAL, ELECTRICAL, AND PLUMBING

FIXTURES. COORDINATE WITH MEP DISCIPLINES

FOR EXTENT OF WORK.

4 REMOVE EXISTING FLOORING AND ASSOCIATED

ACCESSORIES TO STRUCTURE/SUBFLOOR BELOW.

5 REMOVE EXISTING STAIR AND ASSEMBLY

COMPLETE.

6 REMOVE EXISTING CHIMNEY COMPLETE. INFILL

SLAB PENETRATIONS AS NEEDED TO MAINTAIN

FLOOR RATING.

7 REMOVE EXISTING WINDOW COMPLETE

INCLUDING FRAME, SILL, AND CAST STONE.

8 REMOVE DASHED PORTION OF WALL FOR NEW

DOOR.

9 REMOVE EXISTING DECORATIVE COLUMNS.

10 REMOVE RAILINGS COMPLETE.

11 REMOVE EXISTING CONCRETE SLAB FOR NEW

STAIRS TO THE GROUND LEVEL.

12 REMOVE EXISTING PORCH STRUCTURE FROM 1ST

FLOOR SLAB TO ROOF.

13 REMOVE EXTERIOR WALL FINISHES BACK TO

STRUCTURE AND PREP FOR NEW SPRAY FOAM

INSULATION

14 REMOVE WINDOW, FRAME, AND SILL. MAINTAIN

EXTERIOR CAST STONE SILL

15 SAWCUT SLAB FOR NEW PLUMBING WORK.

CONTRACTOR TO USE GROUND PENETRATING

RADAR PRIOR TO TRENCHING FOR VERIFICATION

OF EXISTING MAIN. COORDINATE EXTEND OF

CUTTING WITH PLUMBING.

16 REMOVE AREA OF EXISTING ASPHALT PAVING AS

NEEDED TO ALLOW FOR PROPOSE

CONSTRUCTION

Revisions: Date:

ADDENDUM 1 JUNE 9, 2023

UP

UP

UP

UP

DEMOLITION NOTES:

1. COORDINATE EXTENT OF DEMOLITION WITH

LOCATIONS OF PARTITIONS DESCRIBED ON PLANS

AND WITH LOCATIONS OF FINISHES NOTED AS

EXISTING TO REMAIN.

2. ANY WALL, PARTITION OR SURFACE DISTURBED

BECAUSE OF NEW WORK OR DEMOLITION SHALL BE

PATCHED AND FINISHED CONTINUOUSLY TO THE

NEAREST CORNER UNLESS NOTED OTHERWISE,

MATCH EXISTING ADJACENT CONSTRUCTION

FINISHES, CONTINUITY AND FIRE RATINGS UNLESS

NOTED OTHERWISE.

3. PROTECT ALL FINISHES, MATERIALS AND EQUIPMENT

NOTED AS EXISTING TO REMAIN. CONTRACTOR SHALL

BE RESPONSIBLE TO REPLACE ALL FINISHES,

MATERIALS AND EQUIPMENT DAMAGED DURING

CONSTRUCTION.

4. DIMENSIONS INDICATED WITH A ± ARE EXISTING

CONDITION AND NEED TO BE VERIFIED IN FIELD.

5. CONTRACTOR TO HOLD A PRE-DEMOLITION MEETING

WITH OWNER, CONSTRUCTION MANAGER, SUB

CONTRACTORS, ETC. PRIOR TO BEGINNING

DEMOLITION WORK TO REVIEW HOSPITALS POLICIES,

NOISE CONTROL MEASURES, ETC.

6. CLEARLY INDENTIFY AND TAG MECHANICAL,

PLUMBING AND ELECTRICAL FIXTURES OR EQUIPMENT

THAT ARE STILL IN USE PRIOR TO DEMOLITION TO

AVOID ACCIDENTAL REMOVAL.

7. SEE MECHANICAL, ELECTRICAL AND PLUMBING

DRAWINGS FOR THE SCOPE OF DEMOLITION IN THOSE

DISCIPLINES.

HAZARDOUS MATERIALS

GENERAL NOTE:

HAZARDOUS MATERIALS MAY BE PRESENT THROUGHOUT

THE BUILDING AND SITE. REFERENCE HAZARDOUS

MATERIALS SURVEY AND ASSOIATED SPECIFICATIONS AND

DRAWINGS FOR ADDITIONAL INFORMATION.

A

B

C

D

E

1 2 3 4 5 6 7 8 9 10

11 12

1/

2"

9"

3 4

3 4

3 4

3 4

3 4

2 2 2

2 2

2 2 2

2 2

2 2 22

2 22

3 4

3 4 3 4

3 4

3 4

3 4

3 4

3 4

3 4

3 4

3 4

3 4

3 4

3 4

3 4

3 4 3 4

3 4

9 10

9 10 9

7 78

14 14 14 14 14 14 14 14 14 14 14 14 14

141414141414

141414141414

1313 13

3 43 43 4 1 1

1 1 1 1 1 1

11111

13 13 13 13 13 13 13 13 13

13131313131313131313

TRENCHED AREA

TRENCH LEGEND:

LEVEL 1

175' - 0"

LEVEL 2

186' - 0"

5 6

REMOVE & MODIFY EXISTING WD

COLUMNS & PILASTERS TO ALLOW FOR

REINSTALLATION. CUT COLUMN TO SIZE

AND REPLACE BASE AS NEEDED TO

MATCH EXISTING. TYPICAL FOR ALL

COLUMNS AND PEIRS IN THIS AREA.

REPLACE MASONRY AND CONCRETE

ENTRY STEPS, AND ADD AN ACCESSIBLE

RAMP. REFER TO THE SITE PLAN FOR

RAMP EXTENTS. REPLACE STAIR RAILINGS

AND GUARDRAILS WITH RAILINGS AND

GUARDRAILS THAT MEET ACCESSIBILITY

REQUIREMENTS.

REMOVE DOOR & REPLACE IN KIND W/

BLAST RESISTANT. BORROWED LITES,

TRIM AND CLERESTORY WINDOW TO

REMAIN, CONTRACTOR TO PROVIDE

SECURITY FILM ON EXISTING GLAZING.

A

B

C

D

E

1 2 3 4 5 6 7 8 9 10

10' - 2"

3 4

3 4

3 4

3 4

3 4

2 2 2

2 2

2 2 2

2 2

2 2 22

2 22

3 4

3 4 3 4

3 4

3 4

3 4

3 4

3 4

3 4

3 4

3 4

3 4

3 4

7 78

129 9

129 9

12 99

12 99

14 14 14 14 14 14

14 14 14

14 14 14 14 14 14

14141414141414141414141414

1313 13

13131313

13 13131313

3 43 43 4 1 1

1 1

1 1 1

11111

13 13 13 13 13 13 13 13 13

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:1

AM

AD101

FIRST AND SECOND FLOOR

DEMOLITION PLANS

WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 MC MC/MP/BL

200 SPRINGS ROAD, BEDFORD, MA 01730

SCALE: 1/8" = 1'-0"F1 FIRST FLOOR DEMOLITION PLAN

DEMOLITION KEYNOTES LEGEND

KEYNOTE DESCRIPTION

1 REMOVE EXISTING WALL FROM FLOOR TO

STRUCTURE ABOVE.

2 REMOVE EXISTING DOOR AND FRAME ASSEMBLY

COMPLETE.

3 REMOVE EXISTING CEILING AND ALL ASSOCIATED

MECHANICAL, ELECTRICAL, AND PLUMBING

FIXTURES. COORDINATE WITH MEP DISCIPLINES

FOR EXTENT OF WORK.

4 REMOVE EXISTING FLOORING AND ASSOCIATED

ACCESSORIES TO STRUCTURE/SUBFLOOR BELOW.

5 REMOVE EXISTING STAIR AND ASSEMBLY

COMPLETE.

6 REMOVE EXISTING CHIMNEY COMPLETE. INFILL

SLAB PENETRATIONS AS NEEDED TO MAINTAIN

FLOOR RATING.

7 REMOVE EXISTING WINDOW COMPLETE

INCLUDING FRAME, SILL, AND CAST STONE.

8 REMOVE DASHED PORTION OF WALL FOR NEW

DOOR.

9 REMOVE EXISTING DECORATIVE COLUMNS.

10 REMOVE RAILINGS COMPLETE.

11 REMOVE EXISTING CONCRETE SLAB FOR NEW

STAIRS TO THE GROUND LEVEL.

12 REMOVE EXISTING PORCH STRUCTURE FROM 1ST

FLOOR SLAB TO ROOF.

13 REMOVE EXTERIOR WALL FINISHES BACK TO

STRUCTURE AND PREP FOR NEW SPRAY FOAM

INSULATION

14 REMOVE WINDOW, FRAME, AND SILL. MAINTAIN

EXTERIOR CAST STONE SILL

15 SAWCUT SLAB FOR NEW PLUMBING WORK.

CONTRACTOR TO USE GROUND PENETRATING

RADAR PRIOR TO TRENCHING FOR VERIFICATION

OF EXISTING MAIN. COORDINATE EXTEND OF

CUTTING WITH PLUMBING.

16 REMOVE AREA OF EXISTING ASPHALT PAVING AS

NEEDED TO ALLOW FOR PROPOSE

CONSTRUCTION

SCALE: 1/8" = 1'-0"F9 SOUTH ELEVATION - DEMOLITION

SCALE: 1/8" = 1'-0"C1 SECOND FLOOR DEMOLITION PLAN

OC OC OC OC

OC OC

OC

NL/EM NL/EM NL/EM NL/EM

OCOC

OC

OC OC

OC

NL/EM NL/EM NL/EM

NL/EM

NL/EM

A

B

C

D

E

1 2 3 4 5 6 7 8 9 10

11 12

AE201

F5

PROGRAM

ASSISTANT &

ADMIN

WORKSTATION

B19

PROGRAM

MANAGER

B18

PATIENT

ADVOCATE

B17

VOLUNTEERS

B03

ELEVATOR

MACHINE

ROOM

B02

BUILDING

SUPPORT

B08

TOILET

B09

HOUSEKEEPING

B10

BENEFITS

ADVISOR

B04

RESEARCH

ASSISTANT

B12

TOILET

B15

CORRIDOR

B00

RESIDENCY

PROGRAM

DIRECTOR

B12A

LOUNGE

B13

TOILET

B14A

LOCKER

B14 VACANT

SPACE

B11

AE201

B2

ELEVATOR

LOBBY

B21A

BUILDING

SUPPORT

B07

ELECTRIC

B06

IT/DATA

B05

STORAGE

CLOSET

B01

CORRIDOR

B21

AE100 D1

STAIR 1

B16

UP

UP

UP

UP

AD101

F9

ELEV.

E01

AE

0A

AE

0B

MULTI-PURPOSE/

CONFERENCE/YOGA

B20

ADDITION EXISTING EXISTING ADDITION

PROVIDE SPRAY ON

WATERPROOFING MEMBRANE @

EXISTING BELOW GRADE BRICK

FOUNDATION WALL & FOOTING

DRAIN. COORDINATE W/ SITE CIVIL

DRAWINGS

PROVIDE SPRAY ON

WATERPROOFING MEMBRANE @

EXISTING BELOW GRADE BRICK

FOUNDATION WALL & FOOTING

DRAIN. COORDINATE W/ SITE CIVIL

DRAWINGS

AE100

F1

A

B

C

D

E

1 2 3 4 5 6 7 8 9 10

11 12

EXPOSED TO

STRUCTURE

ABOVE

133 SF

PROGRAM

ASSISTANT &

ADMIN

WORKSTATION

B19123 SF

PROGRAM

MANAGER

B18

144 SF

PATIENT

ADVOCATE

B17

84 SF

VOLUNTEERS

B03

52 SF

ELEVATOR

MACHINE

ROOM

B02

979 SF

BUILDING

SUPPORT

B08

102 SF

TOILET

B09

42 SF

HOUSEKEEPING

B10

58 SF

RESEARCH

ASSISTANT

B12

58 SF

TOILET

B15

386 SF

CORRIDOR

B00

97 SF

RESIDENCY

PROGRAM

DIRECTOR

B12A

129 SF

LOUNGE

B13

55 SF

TOILET

B14A

108 SF

LOCKER

B14

693 SF

VACANT

SPACE

B11

96 SF

ELEVATOR

LOBBY

B21A 455 SF

BUILDING

SUPPORT

B07

102 SF

BENEFITS

ADVISOR

B04

119 SF

IT/DATA

B05

209 SF

ELECTRIC

B06

27 SF

STORAGE

CLOSET

B01

CONSTRUCT AND SEAL WALL

TIGHT TO PERIMETER OF DUCT

RISER ABOVE, TYP.

446 SF

STAIR 1

B16

433 SF

MULTI-PURPOSE/

CONFERENCE/YOGA

B20

79 SF

ELEV.

E01

382 SF

CORRIDOR

B21

382 SF

CORRIDOR

B21

8' - 0"

7' - 9"

FLOOR PLAN NOTES:

1. SEE GI002 FOR GENERAL PROJECT NOTES, LEGENDS

AND ABBREVIATIONS.

2. SEE GI003 FOR GENERAL MOUNTING HEIGHTS, TOP OF

WALL DETAILS AND PARTITION TYPES.

3. CONTRACTOR IS RESPONSIBLE FOR REVIEWING CODE

COMPLIANCE PLANS AND NOTIFYING THE ARCHITECT OF

CONFLICTS BETWEEN WHAT IS IN THE FIELD AND ON

THE CODE DOCUMENTS.

4. DIMENSIONS ARE FACE OF CONCRETE, FACE OF

MASONRY AND CENTERLINE OF STUD, UNLESS NOTED

OTHERWISE.

5. DOOR JAMBS (HINGE SIDE) SHALL BE 6" FROM CORNER

IN STUD PARTITIONS AND 8" FROM CORNER IN MASONRY

PARTITIONS UNLESS NOTED OTHERWISE.

6. REFER TO DETAILS FOR ADDITIONAL DIMENSIONING

INFORMATION.

7. REFER TO ENLARGED PLANS FOR PARTITION TYPES AND

DIMENSIONS IN AREAS WHICH ARE DETAILED AT A

LARGER SCALE.

8. FURNITURE AND OWNER PROVIDED EQUIPMENT ARE

INDICATED BY DASHED LINE TYPE.

9. CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION

OF OWNER PROVIDED EQUIPMENT INCLUDING BUT NOT

LIMITED TO DIMENSIONAL INFORMATION, AND

MECHANICAL, ELECTRICAL AND PLUMBING

REQUIREMENTS.

10. CENTER FLOOR DRAINS IN SPACE UNLESS INDICATED

OTHERWISE.

INFILLED AREA

PLAN LEGEND:

EXISTING WALL/PARTITION/COLUMN

NEW WALL/PARTITION

VACANT SPACE

CEILING NOTES:

1. SEE GI001 FOR GENERAL PROJECT NOTES.

2. SEE FINISH SCHEDULE FOR CEILING AND CEILING GRID

TYPES.

3. EXCEPT WHERE INDICATED, CENTER CEILING GRIDS IN

ROOMS. USE HALF TILES OF GREATER @ PERIMETERS

WHEN POSSIBLE.

4. ALIGN CEILING ITEMS AS SHOWN, WITH COMMON

CENTERLINES TYPICALLY. CENTER ITEMS IN CEILING, OR

IN AREAS UNLESS INDICATED OTHERWISE.

5. WHERE TEGULAR OR BEVELED TILE IS USED, PAINT ALL

CUT EDGES TO MATCH.

6. CAULK JOINT BETWEEN CEILING GRID (WALL ANGLE)

AND WALL WHERE GAPS ARE LARGER THAN 1/8" OR

GREATER.

7. PROVIDE ACCESS PANELS AS REQUIRED IN GWB

CEILINGS FOR ACCESS AS REQUIRED BY ALL TRADES.

8. FIRE SPRINKLERS SHALL BE CENTERED IN CEILING TILE

OR HALF TILE AS SHOWN. FIRE SPRINKLERS SHALL BE

LOCATED IN ALIGNMENT WITH OTHER CEILING ITEMS

AND SHALL BE PLACED IN COORDINATION WITH LIGHT

FIXTURE POSITIONS INDICATED, TYPICAL.

9. FIRE SPRINKLERS ARE SHOWN FOR COORDINATION

PURPOSES ONLY. ADDITIONAL SPRINKLER HEADS MAY

BE REQUIRED FOR CODE COMPLIANCE, AS DETERMINED

BY THE FIRE PROTECTION DESIGNER. SPRINKLERS ARE

NOT SHOWN IN ALL AREAS WHERE REQUIRED. FIRE

PROTECTION CONTRACTOR SHALL BE RESPONSIBLE

FOR PROVIDING A COMPLETE AND FULLY CODE

COMPLIANT SYSTEM, INCLUDING HEADS NOT INDICATED

IN THIS DRAWING. SIDEWALL MOUNT SPRINKLER HEADS

UNDER BALCONIES ARE NOT SHOWN IN THE CEILING

PLANS.

10. SEE MECHANICAL, ELECTRICAL AND PLUMBING

DRAWINGS FOR ADDITIONAL INFORMATION.

11. WHERE ARCHITECTURAL DRAWINGS DEPICT

MECHANICAL OR ELECTRICAL ITEMS OR EQUIPMENT

(LIGHTS, DIFFUSERS, ETC.) INSTALLATION OF SUCH

ITEMS SHALL BE COORDINATED WITH EACH RESPECTIVE

TRADE SUB-CONTRACTOR.

12. WHERE DRAWINGS DO NOT ACCESS INSTALLATION

METHODOLOGY, THE CONTRACTOR SHALL BE BOUND

TO PERFORM IN STRICT COMPLIANCE WITH THE

MANUFACTURER'S SPECIFICATIONS, AND STANDARD

INDUSTRY STANDARDS.

13. CONTRACTOR TO COORDINATE ANY BLOCKING OR

STRUCTURAL SUPPORT ABOVE THE CEILING FOR

OWNER PROVIDED EQUIPMENT.

SUPPLY DIFFUSER

RETURN DIFFUSER

EXHAUST DIFFUSER

LINEAR DIFFUSER

GWB CEILING

DOWN LIGHT

2x2 LIGHT FIXTURE

2x2 CEILING TILE AND GRID (ACT-1)

CEILING LEGEND:

2x2 LIGHT FIXTURE (EMERG.)

UTILITY LIGHT FIXTURE

UTILITY LIGHT FIXTURE (EMERG.)

EMERGENCY EXIT SIGN

OCCUPANCY SENSOROC

R

WALL SCONCE

LINEAR WALL LIGHT

EXTERIOR WALL SCONCE

ACCESS CONTROL, RE: ELEC.

KEYED NOTES:

REFRIGERATOR

MICROWAVE OVEN

COFFEE MAKER

SOAP DISPENSER

PAPER TOWEL DISPENSER

2'

- 6

2'

- 0

3'

- 0

4' - 0" 4' - 0"

4' - 0" 2' - 0" 2' - 0"

B

F1a

CGCG

CGCG

F1a

F1a

F1a

S3a

S3a

NOTE: ADJACENT/CONNECTING PARTITION LAYOUT/TYPE WILL VARY

BY LOCATION. REFER TO OVERALL AND ENLARGED FLOOR PLANS.

EXISTING COLUMN TO REMAIN

PROVIDE CORNER GUARDS

AT ALL EXTERIOR CORNERS

OF COLUMN FURRING

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:1

AM

AE100

OVERALL GROUND FLOOR PLANS WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 MC MC/MP/BL

200 SPRINGS ROAD, BEDFORD, MA 01730

SCALE: 1/8" = 1'-0"F3 OVERALL GROUND FLOOR PLAN

SCALE: 1/8" = 1'-0"C3 GROUND FLOOR REFLECTED CEILING PLAN

Revisions: Date:

ADDENDUM 1 JUNE 9, 2023

SEE STRUCTURAL DRAWINGS FOR STAIR/SLOPED

WALKWAY FOOTINGS AND FOUNDATIONS

GROUND FLOOR (BASEMENT) CEILING SCHEDULE

# Name Ceiling Finish Ceiling Height Comments

B00 CORRIDOR ACT-1/GWB 8'-0" SEE PLAN FOR GWB SOFFIT/BULKHEAD LOCATIONS

B01 STORAGE CLOSET ACT-1 8'-0"

B02 ELEVATOR MACHINE ROOM EXPOSED VARIES

B03 VOLUNTEERS ACT-1 7'-8"

B04 BENEFITS ADVISOR ACT-1 7'-8"

B05 IT/DATA EXPOSED VARIES

B06 ELECTRIC EXPOSED VARIES

B07 BUILDING SUPPORT EXPOSED 9'-6"

B08 BUILDING SUPPORT EXPOSED VARIES

B09 TOILET ACT-1 7'-8"

B10 HOUSEKEEPING ACT-1 7'-8"

B11 VACANT SPACE ACT-1 8'-0"

B12 RESEARCH ASSISTANT ACT-1 7'-8"

B12A RESIDENCY PROGRAM

DIRECTOR

ACT-1 7'-8"

B13 LOUNGE ACT-1 7'-8"

B14 LOCKER ACT-1 7'-8"

B14A TOILET ACT-1 7'-8"

B15 TOILET ACT-1 7'-8"

B16 STAIR 1 ACT-1/GWB 8'-0" SEE PLAN FOR GWB SOFFIT/BULKHEAD LOCATIONS

B17 PATIENT ADVOCATE ACT-1 7'-8"

B18 PROGRAM MANAGER ACT-1 7'-8"

B19 PROGRAM ASSISTANT &

ADMIN WORKSTATION

ACT-1 7'-8"

B20 MULTI-PURPOSE/

CONFERENCE/YOGA

ACT-1 7'-8"

B21 CORRIDOR ACT-1/GWB 7'-10" SEE PLAN FOR GWB SOFFIT/BULKHEAD LOCATIONS

B21A ELEVATOR LOBBY ACT-1 7'-10"

E01 ELEV. ACT-1 8'-0" COORDINATE WITH ELEVATOR MANUFACTURER

LIGHTING FIXTURES SHOWN FOR

REFERENCE ONLY. REFER TO ELECTRICAL

DRAWINGS FOR ADDITIONAL INFORMATION.

SCALE: 1/4" = 1'-0"D1 INTERIOR ELEVATION - LOUNGE B13

SCALE: 1 1/2" = 1'-0"F1 TYPICAL COLUMN FURR-OUT DETAIL

FLOOR PLAN NOTES:

1. SEE GI002 FOR GENERAL PROJECT NOTES, LEGENDS

AND ABBREVIATIONS.

2. SEE GI003 FOR GENERAL MOUNTING HEIGHTS, TOP OF

WALL DETAILS AND PARTITION TYPES.

3. CONTRACTOR IS RESPONSIBLE FOR REVIEWING CODE

COMPLIANCE PLANS AND NOTIFYING THE ARCHITECT OF

CONFLICTS BETWEEN WHAT IS IN THE FIELD AND ON

THE CODE DOCUMENTS.

4. DIMENSIONS ARE FACE OF CONCRETE, FACE OF

MASONRY AND CENTERLINE OF STUD, UNLESS NOTED

OTHERWISE.

5. DOOR JAMBS (HINGE SIDE) SHALL BE 6" FROM CORNER

IN STUD PARTITIONS AND 8" FROM CORNER IN MASONRY

PARTITIONS UNLESS NOTED OTHERWISE.

6. REFER TO DETAILS FOR ADDITIONAL DIMENSIONING

INFORMATION.

7. REFER TO ENLARGED PLANS FOR PARTITION TYPES AND

DIMENSIONS IN AREAS WHICH ARE DETAILED AT A

LARGER SCALE.

8. FURNITURE AND OWNER PROVIDED EQUIPMENT ARE

INDICATED BY DASHED LINE TYPE.

9. CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION

OF OWNER PROVIDED EQUIPMENT INCLUDING BUT NOT

LIMITED TO DIMENSIONAL INFORMATION, AND

MECHANICAL, ELECTRICAL AND PLUMBING

REQUIREMENTS.

10. CENTER FLOOR DRAINS IN SPACE UNLESS INDICATED

OTHERWISE.

INFILLED AREA

PLAN LEGEND:

EXISTING WALL/PARTITION/COLUMN

NEW WALL/PARTITION

VACANT SPACE

ACCESS CONTROL, RE: ELEC.

KEYED NOTES:

A

B

C

D

E

1 2 3 4 5 6

F2

AE301

F2

AE301

F9

AE310

C3

AE312

C3

AE312

AE100 D1

F1

AE504

F3

AE312

F6

AE310

AD101

F9

PROGRAM

ASSISTANT &

ADMIN

WORKSTATION

B19

PROGRAM

MANAGER

B18

PATIENT

ADVOCATE

B17

RESEARCH

ASSISTANT

B12

TOILET

B15

CORRIDOR

B00

RESIDENCY

PROGRAM

DIRECTOR

B12A

LOUNGE

B13

TOILET

B14A

LOCKER

B14

VACANT

SPACE

B11

AE201

B2

B1

B1

B14A

B1

B1

B1

B1

B02

B00

B2

B1

B2 0B

B20A

STAIR 1

B16

CONCRETE PAD. RE:

STRUCT & CIVIL

PROVIDE CONCRETE PAD

SLOPED AWAY FROM BUILDING

RE: STRUCT & CIVIL

UP

UP

F4

AE310

D1

AE502

F5

AE502

/2

6'

- 8

/2

5'

- 0

2'

- 9

/2

/2

9'

- 2

1/ 2"

2'

- 8

10' - 7 1/2" 9' - 2" 10' - 0" 31' - 2 1/2" 1' - 8 1/2"

9' - 1"

7'

- 2

/2

7'

- 5

6'

- 5

/2

7'

- 0

7'

- 1 0"

9'

- 1

1/

2" 4'

- 7

/2 " 8'

- 0

/2

6'

- 6

/2

8' - 11 1/2" 8' - 2" 9' - 6" 1' - 4" 13' - 3 1/2"

CORRIDOR

B21

5'

- 0

4'

- 1 1"

16' - 10" 4" 12' - 1 1/2" 13' - 11 1/2" 2' - 0 1/2" 16' - 0" 7' - 10"

10 1/2"

9' - 11 1/2" 10' - 8" 2"

12' - 1 1/2" 16' - 0" 16' - 0" 18' - 8" 10' - 8"

3 3 3 3 3 3 3

15' - 0 1/2" CLEAR

/2 " C

LE

AR

A1

B A1

B

B16

433 SF

MULTI-PURPOSE/

CONFERENCE/YOGA

B20

B1

106A106A106A106A106A 106A

106A

B16A

AE100

F1 SIM

W3

W3

W3

W3

Q3.0

Q3.0

S3a

S3a

S3a

S3a

Q3.0

S3a

Q3.0

S3a

S3a

S3a

S3a

S3a

F3a

S3.2a

S3.2a

S3.2a

S3a

S3a

S3a

S3a

S3a

S3a

S3a

F3a

S3a

S3a

Q3.0

F10

Q3.0

Q3.0

F2a

F2a

F2a

F2a

PROVIDED PAINTED STEEL CANE RAIL UNDER STAIR STRUCTURE;

CANE RAIL TO LIMIT ACCESS TO AREA WITH HEAD HEIGHTS LESS

THAN 6'-8" CLEAR FROM FINISHED FLOOR

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:2

AM

AE100A

ENLARGED GROUND FLOOR PLAN -

WEST

WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 MC MC/MP/BL

200 SPRINGS ROAD, BEDFORD, MA 01730

SCALE: 1/4" = 1'-0"F1 ENLARGED GROUND FLOOR PLAN - WEST

SEE STRUCTURAL DRAWINGS FOR STAIR/SLOPED

WALKWAY FOOTINGS AND FOUNDATIONS

Revisions: Date:

ADDENDUM 1 JUNE 9, 2023

FURNITURE, FIXTURES AND EQUIPMENT SHOWN FOR

REFERENCE ONLY. REFER TO EQUIPMENT PLANS

FOR ADDITIONAL INFORMATION.

A

B

C

D

E

6 7 8 9 10

AE201

F5

C7

AE301

C7

AE301

F2

AE301

F2

AE301

C7

AE312

C7

AE312

F4

AE310

F6

AE311

F8

AE311

VOLUNTEERS

B03

ELEVATOR

MACHINE

ROOM

B02

BUILDING

SUPPORT

B08

TOILET

B09

HOUSEKEEPING

B10

BENEFITS

ADVISOR

B04

AE201

B2

ELEVATOR

LOBBY

B21A

B0

B0

B1

B02

B08

B1

B0

107L2L2107107107

106A

L33333

BUILDING

SUPPORT

B07

ELECTRIC

B06

B0

IT/DATA

B05

B0

STORAGE

CLOSET

B01

CORRIDOR

B21

B01

DN

UP

UP

F9

AE310

F1

AE310

F6

AE310

9"

3'

- 4

/2

" C L

INFILL EXISTING OPENING

TO MATCH EXISTING

ADJACENT MATERIALS AND

CONSTRUCTION

SUMP PIT

RE: STRUCT. / PLUMB.

D1

AE502

EXISTING FLOOR DRAIN LOCATION

PROVIDE NEW DRAIN AND CONNECT TO

EXISTING STORM SYSTEM, SLOPE LANDING

1/8":1'-0" TO DRAIN

A1

A A1

A

B07A

B0

AE100

F1 SIM

W2

W2

W2

M8.2

Q3.0 S3a Q3.0

W3

W3

W3

W3

11' - 1 1/2" 4' - 3" 44' - 6" 16' - 10"

2'

- 9

/2

/2

9'

- 2

1/ 2"

2'

- 8

4' - 10" 7" 7' - 1" 8' - 11" 15' - 2" 12' - 1"

11" 4' - 2" 3' - 5"

1/

2" 9'

- 4

9" 6' - 9 1/2" 11' - 4"

5' - 0 1/2" 6' - 8" 7' - 9 1/2" 7' - 3"

/2

15' - 5 1/2"

/2

6'

- 5

/2

4'

- 1

1" 7'

- 5

/2

7'

- 2

/2

6'

- 4

/2

8'

- 2

6'

- 5

/2

S3.2a

S3.2a

S3a

Q3.0 Q3.0

Q3.0Q3.0

F2a

F2a

F2a

F2aF2a

Q3.0

Q3.0

S3.1a S3.1a

S6.1

Q3.0

Q3.0 Q3.0

S6.0

S3a

S3a

S3a S3a

S3.1a

S3.1a

S3a

S3.2a

S3a

S3.1a

18' - 8" 16' - 0" 16' - 0" 12' - 1 1/2"

/2

6'

- 8

/2

5'

- 0

/2

FLOOR PLAN NOTES:

1. SEE GI002 FOR GENERAL PROJECT NOTES, LEGENDS

AND ABBREVIATIONS.

2. SEE GI003 FOR GENERAL MOUNTING HEIGHTS, TOP OF

WALL DETAILS AND PARTITION TYPES.

3. CONTRACTOR IS RESPONSIBLE FOR REVIEWING CODE

COMPLIANCE PLANS AND NOTIFYING THE ARCHITECT OF

CONFLICTS BETWEEN WHAT IS IN THE FIELD AND ON

THE CODE DOCUMENTS.

4. DIMENSIONS ARE FACE OF CONCRETE, FACE OF

MASONRY AND CENTERLINE OF STUD, UNLESS NOTED

OTHERWISE.

5. DOOR JAMBS (HINGE SIDE) SHALL BE 6" FROM CORNER

IN STUD PARTITIONS AND 8" FROM CORNER IN MASONRY

PARTITIONS UNLESS NOTED OTHERWISE.

6. REFER TO DETAILS FOR ADDITIONAL DIMENSIONING

INFORMATION.

7. REFER TO ENLARGED PLANS FOR PARTITION TYPES AND

DIMENSIONS IN AREAS WHICH ARE DETAILED AT A

LARGER SCALE.

8. FURNITURE AND OWNER PROVIDED EQUIPMENT ARE

INDICATED BY DASHED LINE TYPE.

9. CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION

OF OWNER PROVIDED EQUIPMENT INCLUDING BUT NOT

LIMITED TO DIMENSIONAL INFORMATION, AND

MECHANICAL, ELECTRICAL AND PLUMBING

REQUIREMENTS.

10. CENTER FLOOR DRAINS IN SPACE UNLESS INDICATED

OTHERWISE.

INFILLED AREA

PLAN LEGEND:

EXISTING WALL/PARTITION/COLUMN

NEW WALL/PARTITION

VACANT SPACE

ACCESS CONTROL, RE: ELEC.

KEYED NOTES:

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:2

AM

AE100B

ENLARGED GROUND FLOOR PLAN -

EAST

WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 MC MC/MP/BL

200 SPRINGS ROAD, BEDFORD, MA 01730

SCALE: 1/4" = 1'-0"F1 ENLARGED GROUND FLOOR PLAN - EAST

Revisions: Date:

ADDENDUM 1 JUNE 9, 2023

FURNITURE, FIXTURES AND EQUIPMENT SHOWN FOR

NEMA

3R

NEMA

3R

NL/EM NL/EM

NL/EM

NL/EM

NL/EM

NL/EM

NL/EM

NL/EM NL/EM NL/EM NL/EM

NL/EM

NL/EM

NL/EM

NL/EM

A

B

C

D

E

1 2 3 4 5 6 7 8 9 10

11 12

224 SF

TREATMENT

ROOM

48 SF

CLEAN

UTILITY

55 SF

PATIENT

TOILET

120A

146 SF

EXAM ROOM

51 SF

PATIENT

TOILETS

118A

151 SF

EXAM ROOM

76 SF

TOILET

83 SF

TOILET

191 SF

CORRIDOR

440 SF

WAITING

125 SF

INTERVIEW

126 SF

RECEPTION

175 SF

LAB

(PHLEBOTOMY)

119 SF

IT/DATA

48 SF

HOUSEKEEPING

223 SF

BARIATRIC

TREATMENT

ROOM

61 SF

SOILED

UTILITY

70 SF

BARIATRIC

TOILET

122A

145 SF

EXAM ROOM

75 SF

BARIATRIC

TOILET

125A

PATIENT

TOILET

124A

186 SF

BARIATRIC

EXAM ROOM

125 386 SF

WAITING

114 SF

LACTATION A

137 SF

SHARED

DOCUMENTATION

WORK AREA

80 SF

MED ROOM

55 SF

EQUIPMENT

STORAGE

51 SF

PATIENT

TOILETS

117A

48 SF

STAFF TOILET

ELECTRICAL

CLOSET

107468 SF

STAIR 1

S11

49 SF

TOILET

111A

347 SF

CORRIDOR

323 SF

CORRIDOR

357 SF

STAIR 2

S12

AE101D1

UP

DN

DN

DN

UP

DN

DN DN

ELEV.

E11

DN DN

AE

1A

AE

1B

ADDITION EXISTING EXISTING ADDITION

109 SF

MECH.

E12

AE100

F1 SIM

A

B

C

D

E

1 2 3 4 5 6 7 8 9 10

11 12

224 SF

TREATMENT

ROOM

48 SF

CLEAN

UTILITY

55 SF

PATIENT

TOILET

120A

146 SF

EXAM ROOM

51 SF

PATIENT

TOILETS

118A

151 SF

EXAM ROOM

76 SF

TOILET

83 SF

TOILET

191 SF

CORRIDOR

440 SF

WAITING

125 SF

INTERVIEW

126 SF

RECEPTION

175 SF

LAB

(PHLEBOTOMY)

119 SF

IT/DATA

48 SF

HOUSEKEEPING

223 SF

BARIATRIC

TREATMENT

ROOM

61 SF

SOILED

UTILITY

70 SF

BARIATRIC

TOILET

122A

145 SF

EXAM ROOM

75 SF

BARIATRIC

TOILET

125A

56 SF

PATIENT

TOILET

124A

186 SF

BARIATRIC

EXAM ROOM

386 SF

WAITING

114 SF

LACTATION A

137 SF

SHARED

DOCUMENTATION

WORK AREA

80 SF

MED ROOM

55 SF

EQUIPMENT

STORAGE

51 SF

PATIENT

TOILETS

117A

48 SF

STAFF TOILET

9 SF

ELECTRICAL

CLOSET

468 SF

STAIR 1

S11

BARIATRIC PATIENT LIFT AND

TRACK. TYP OF 6 (EXAM ROOMS

AND PROCEDURE ROOMS)

RE: STRUCT FOR MOUNTING

49 SF

TOILET

111A

357 SF

STAIR 2

S12

CEILING HEIGHT

ADJUSTED AT WINDOW

WALL TO COORDINATE

WITH EXISTING WINDOW

HEADS(TYP.)

8' - 6"

7' - 0" 7' - 0"

8' - 8"

FLOOR PLAN NOTES:

1. SEE GI002 FOR GENERAL PROJECT NOTES, LEGENDS

AND ABBREVIATIONS.

2. SEE GI003 FOR GENERAL MOUNTING HEIGHTS, TOP OF

WALL DETAILS AND PARTITION TYPES.

3. CONTRACTOR IS RESPONSIBLE FOR REVIEWING CODE

COMPLIANCE PLANS AND NOTIFYING THE ARCHITECT OF

CONFLICTS BETWEEN WHAT IS IN THE FIELD AND ON

THE CODE DOCUMENTS.

4. DIMENSIONS ARE FACE OF CONCRETE, FACE OF

MASONRY AND CENTERLINE OF STUD, UNLESS NOTED

OTHERWISE.

5. DOOR JAMBS (HINGE SIDE) SHALL BE 6" FROM CORNER

IN STUD PARTITIONS AND 8" FROM CORNER IN MASONRY

PARTITIONS UNLESS NOTED OTHERWISE.

6. REFER TO DETAILS FOR ADDITIONAL DIMENSIONING

INFORMATION.

7. REFER TO ENLARGED PLANS FOR PARTITION TYPES AND

DIMENSIONS IN AREAS WHICH ARE DETAILED AT A

LARGER SCALE.

8. FURNITURE AND OWNER PROVIDED EQUIPMENT ARE

INDICATED BY DASHED LINE TYPE.

9. CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION

OF OWNER PROVIDED EQUIPMENT INCLUDING BUT NOT

LIMITED TO DIMENSIONAL INFORMATION, AND

MECHANICAL, ELECTRICAL AND PLUMBING

REQUIREMENTS.

10. CENTER FLOOR DRAINS IN SPACE UNLESS INDICATED

OTHERWISE.

INFILLED AREA

PLAN LEGEND:

EXISTING WALL/PARTITION/COLUMN

NEW WALL/PARTITION

VACANT SPACE

CEILING NOTES:

1. SEE GI001 FOR GENERAL PROJECT NOTES.

2. SEE FINISH SCHEDULE FOR CEILING AND CEILING GRID

TYPES.

3. EXCEPT WHERE INDICATED, CENTER CEILING GRIDS IN

ROOMS. USE HALF TILES OF GREATER @ PERIMETERS

WHEN POSSIBLE.

4. ALIGN CEILING ITEMS AS SHOWN, WITH COMMON

CENTERLINES TYPICALLY. CENTER ITEMS IN CEILING, OR

IN AREAS UNLESS INDICATED OTHERWISE.

5. WHERE TEGULAR OR BEVELED TILE IS USED, PAINT ALL

CUT EDGES TO MATCH.

6. CAULK JOINT BETWEEN CEILING GRID (WALL ANGLE)

AND WALL WHERE GAPS ARE LARGER THAN 1/8" OR

GREATER.

7. PROVIDE ACCESS PANELS AS REQUIRED IN GWB

CEILINGS FOR ACCESS AS REQUIRED BY ALL TRADES.

8. FIRE SPRINKLERS SHALL BE CENTERED IN CEILING TILE

OR HALF TILE AS SHOWN. FIRE SPRINKLERS SHALL BE

LOCATED IN ALIGNMENT WITH OTHER CEILING ITEMS

AND SHALL BE PLACED IN COORDINATION WITH LIGHT

FIXTURE POSITIONS INDICATED, TYPICAL.

9. FIRE SPRINKLERS ARE SHOWN FOR COORDINATION

PURPOSES ONLY. ADDITIONAL SPRINKLER HEADS MAY

BE REQUIRED FOR CODE COMPLIANCE, AS DETERMINED

BY THE FIRE PROTECTION DESIGNER. SPRINKLERS ARE

NOT SHOWN IN ALL AREAS WHERE REQUIRED. FIRE

PROTECTION CONTRACTOR SHALL BE RESPONSIBLE

FOR PROVIDING A COMPLETE AND FULLY CODE

COMPLIANT SYSTEM, INCLUDING HEADS NOT INDICATED

IN THIS DRAWING. SIDEWALL MOUNT SPRINKLER HEADS

UNDER BALCONIES ARE NOT SHOWN IN THE CEILING

PLANS.

10. SEE MECHANICAL, ELECTRICAL AND PLUMBING

DRAWINGS FOR ADDITIONAL INFORMATION.

11. WHERE ARCHITECTURAL DRAWINGS DEPICT

MECHANICAL OR ELECTRICAL ITEMS OR EQUIPMENT

(LIGHTS, DIFFUSERS, ETC.) INSTALLATION OF SUCH

ITEMS SHALL BE COORDINATED WITH EACH RESPECTIVE

TRADE SUB-CONTRACTOR.

12. WHERE DRAWINGS DO NOT ACCESS INSTALLATION

METHODOLOGY, THE CONTRACTOR SHALL BE BOUND

TO PERFORM IN STRICT COMPLIANCE WITH THE

MANUFACTURER'S SPECIFICATIONS, AND STANDARD

INDUSTRY STANDARDS.

13. CONTRACTOR TO COORDINATE ANY BLOCKING OR

STRUCTURAL SUPPORT ABOVE THE CEILING FOR

OWNER PROVIDED EQUIPMENT.

SUPPLY DIFFUSER

RETURN DIFFUSER

EXHAUST DIFFUSER

LINEAR DIFFUSER

GWB CEILING

DOWN LIGHT

2x2 LIGHT FIXTURE

2x2 CEILING TILE AND GRID (ACT-1)

CEILING LEGEND:

2x2 LIGHT FIXTURE (EMERG.)

UTILITY LIGHT FIXTURE

UTILITY LIGHT FIXTURE (EMERG.)

EMERGENCY EXIT SIGN

OCCUPANCY SENSOROC

R

WALL SCONCE

LINEAR WALL LIGHT

EXTERIOR WALL SCONCE

ACCESS CONTROL, RE: ELEC.

KEYED NOTES:

COUNTER TOP

WITH BACK

SPLASH

2'

- 1

1"

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:2

AM

AE101

OVERALL FIRST FLOOR PLANS WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 MC MC/MP/BL

200 SPRINGS ROAD, BEDFORD, MA 01730

SCALE: 1/8" = 1'-0"F3 OVERALL FIRST FLOOR PLAN

SCALE: 1/8" = 1'-0"C3 FIRST FLOOR REFLECTED CEILING PLAN

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:2

AM

AE101

OVERALL FIRST FLOOR PLANS WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 MC MC/MP/BL

200 SPRINGS ROAD, BEDFORD, MA 01730

Revisions: Date:

ADDENDUM 1 JUNE 9, 2023

Revisions: Date:

ADDENDUM 1 JUNE 9, 2023

FIRST FLOOR CEILING SCHEDULE

# Name Ceiling Finish Ceiling Height Comments

100 CORRIDOR ACT-1/GWB 8'-0" SEE PLAN FOR GWB SOFFIT/BULKHEAD LOCATIONS

101 WAITING ACT-1/GWB 8'-0" SEE PLAN FOR GWB SOFFIT/BULKHEAD LOCATIONS

102 INTERVIEW ACT-1 8'-0"

103 IT/DATA ACT-1 8'-0"

104 SHARED DOCUMENTATION WORK AREA ACT-1 8'-0"

105 EQUIPMENT STORAGE ACT-1 8'-0"

106 MED ROOM ACT-1 8'-0"

107 ELECTRICAL CLOSET ACT-1 8'-0"

109 LAB (PHLEBOTOMY) ACT-1 8'-0"

110 HOUSEKEEPING ACT-1 8'-0"

111 LACTATION A ACT-1 8'-0"

111A TOILET ACT-1 8'-0"

112 STAFF TOILET ACT-1 8'-0"

113 RECEPTION ACT-1 8'-0"

114 WAITING ACT-1 8'-0"

115 TOILET ACT-1 8'-0"

116 TOILET ACT-1 8'-0"

117 EXAM ROOM ACT-1 8'-0"

117A PATIENT TOILETS ACT-1 8'-0"

118 EXAM ROOM ACT-1 8'-0"

118A PATIENT TOILETS ACT-1 8'-0"

119 CLEAN UTILITY ACT-1 8'-0"

120 TREATMENT ROOM ACT-1 8'-6"

120A PATIENT TOILET ACT-1 8'-6"

122 BARIATRIC TREATMENT ROOM ACT-1 8'-6" COORDINATE WITH PATIENT LIFT TRACK

122A BARIATRIC TOILET ACT-1 8'-6" COORDINATE WITH PATIENT LIFT TRACK

123 SOILED UTILITY ACT-1 8'-0"

124 EXAM ROOM ACT-1 8'-0"

124A PATIENT TOILET ACT-1 8'-0"

125 BARIATRIC EXAM ROOM ACT-1 8'-6" COORDINATE WITH PATIENT LIFT TRACK

125A BARIATRIC TOILET ACT-1 8'-6" COORDINATE WITH PATIENT LIFT TRACK

130 CORRIDOR ACT-1 8'-0"

140 CORRIDOR ACT-1 8'-0"

E11 ELEV. ACT-1 8'-0" COORDINATE WITH ELEVATOR MANUFACTURER

E12 MECH. EXPOSED 10'-6"

S11 STAIR 1 ACT-1/GWB 8'-6" SEE PLAN FOR GWB SOFFIT/BULKHEAD LOCATIONS

S12 STAIR 2 ACT-1/GWB 9'-0" SEE PLAN FOR GWB SOFFIT/BULKHEAD LOCATIONS

LIGHTING FIXTURES SHOWN FOR

REFERENCE ONLY. REFER TO ELECTRICAL

DRAWINGS FOR ADDITIONAL INFORMATION.

SCALE: 1/4" = 1'-0"D1 INTERIOR ELEVATION -SOILED UTILITY (TYP.)

C

D

E

1 2 3 4 5 6

F2

AE301

F2

AE301

F9

AE310

C3

AE312

C3

AE312

F1

AE504

F3

AE312

AE101D1

F6

AE310

AD101

F9

224 SF

TREATMENT

ROOM

CLEAN

UTILITY

55 SF

PATIENT

TOILET

120A

146 SF

EXAM ROOM

51 SF

PATIENT

TOILETS

118A

151 SF

EXAM ROOM

76 SF

TOILET

83 SF

TOILET

223 SF

BARIATRIC

TREATMENT

ROOM

61 SF

SOILED

UTILITY

70 SF

BARIATRIC

TOILET

122A

145 SF

EXAM ROOM

75 SF

BARIATRIC

TOILET

125A

56 SF

PATIENT

TOILET

124A

51 SF

PATIENT

TOILETS

117A

468 SF

STAIR 1

S11

121B

UP

DN

COORD. TO ALIGN

W/ MILLWORK

DN DN

DN

DN

3T

3T

3T 3T

3L 3L 3L 3L 3L 3L 3L 2B

2B

3L3L3L3L3L3L

3T3T

3T

3T

121A

122A

125A

7118A

117A

120A

1 1

D 6' - 0"

D 6' - 0"

R 5'

- 6

" M

IN

RE: CIVIL

MAX SLOPE 1:48

7' - 0" LANDING

18" CHANGE IN ELEVATION

30' - 0" AT 1:20 SLOPE

14" CHANGE IN ELEVATION

23' - 8" AT 1:20 SLOPE

MAX SLOPE 1:48

7' - 0" LANDING

8.5" CHANGE IN ELEVATION

14' - 0" AT 1:20 SLOPE

SLOPE DOWN MAX 1:20

SLOPE DOWN MAX 1:20

SLOPE DOWN MAX 1:20

SLOPE DOWN MAX 1:20

174.8

169.9

VERIFY OVERALL RISE/RUN

OF SLOPED WALKWAY IN

THE FIELD, SO ALSO CIVIL

70 SF

BARIATRIC

TOILET

122A

INFILL CAVITY WITH SPRAY FOAM

INSULATION TO MAINTAIN CONTINUOUS

INSULATED PERIMETER

186 SF

BARIATRIC

EXAM ROOM

A1

B A1

B

FEC

D 6' - 0"

6' - 5 1/2"3' - 8 1/2"6' - 5 1/2"

5'

- 0

3'

- 8

/2

7'

- 5

/2

7'

- 5

/2

3'

- 8

/2

4'

- 1

1/ 2"

FURNITURE, FIXTURES AND EQUIPMENT SHOWN FOR

REFERENCE ONLY. REFER TO EQUIPMENT PLANS

FOR ADDITIONAL INFORMATION.

PROVIDED PAINTED STEEL CANE RAIL UNDER STAIR STRUCTURE;

CANE RAIL TO LIMIT ACCESS TO AREA WITH HEAD HEIGHTS LESS

THAN 6'-8" CLEAR FROM FINISHED FLOOR

347 SF

CORRIDOR

191 SF

CORRIDOR

100A

AE100

F1 SIM

W2

12' - 1 1/2" 16' - 0" 16' - 0" 18' - 8" 10' - 8"

/2

6'

- 8

/2

5'

- 0

1"

15' - 6 1/2"

15' - 9 1/2" 1' - 2" 4' - 0" 5' - 9" 1' - 0" 10' - 7 1/2" 10" 3' - 10" 2' - 4" 5' - 6" 12' - 3"

3' - 8 1/2" 10' - 6 1/2" 5' - 7 1/2" 2' - 10"

16' - 9 1/2" 2' - 0" 6' - 11" 10' - 11" 8' - 2" 7' - 6" 10" 2' - 8 1/2" 7' - 9" 2' - 1 1/2"

1/

2" 6'

- 5

4'

- 7

2'

- 6

/2

7'

- 6

7'

- 7

/2

7'

- 0

6'

- 7

/2

/2

7'

- 1

7'

- 1

6"

7'

- 0

/2

6'

- 1

1/

2"

/2

6'

- 9

/2

4'

- 1

1/

2"

1'

- 4

"3'

- 9

/2

/2

8'

- 6

/2

6'

- 4

/2

1'

- 0

/2

124A

16' - 7 1/2" W2

W2

Q3.0

Q3.0

S3a S6.1

U4.1

U4.1 S6.1 S3.1a

S3.1a S3a

Q3.0 F3a

F3a

F3a

F3a Q3.0

S3a

S6.0

S3a

F3a

F3a

F6

S3a

F6

S3a

S3a

F3a

F3a

Q3.0

Q3.0

S3a

U4.1

S3.1a

S3.1a

S3.1a

U4.1

F6

S6.0

S3a

S3a

S3a

S3a

S3a

F3a

F3a

S3a

F3a

Q3.0

Q3.0

S3a

S3a

S3a

S3.1a

F1a

U4.1U4.1

F3a

F3a

F3aF3a

F3a

F3a

S3a

S3a

PROVIDE CONC. CURB ALONG ALL

EDGES OF SLOPED WALKWAY

AND LANDINGS, 4" WIDE, 4" HIGH

REGRADE AROUND ALL SIDES OF SLOPED

WALKWAY AND LANDINGS TO PROVIDE A MAX. 30"

DROP-OFF FROM TOP OF CURB TO FINISH GRADE

FLOOR PLAN NOTES:

1. SEE GI002 FOR GENERAL PROJECT NOTES, LEGENDS

AND ABBREVIATIONS.

2. SEE GI003 FOR GENERAL MOUNTING HEIGHTS, TOP OF

WALL DETAILS AND PARTITION TYPES.

3. CONTRACTOR IS RESPONSIBLE FOR REVIEWING CODE

COMPLIANCE PLANS AND NOTIFYING THE ARCHITECT OF

CONFLICTS BETWEEN WHAT IS IN THE FIELD AND ON

THE CODE DOCUMENTS.

4. DIMENSIONS ARE FACE OF CONCRETE, FACE OF

MASONRY AND CENTERLINE OF STUD, UNLESS NOTED

OTHERWISE.

5. DOOR JAMBS (HINGE SIDE) SHALL BE 6" FROM CORNER

IN STUD PARTITIONS AND 8" FROM CORNER IN MASONRY

PARTITIONS UNLESS NOTED OTHERWISE.

6. REFER TO DETAILS FOR ADDITIONAL DIMENSIONING

INFORMATION.

7. REFER TO ENLARGED PLANS FOR PARTITION TYPES AND

DIMENSIONS IN AREAS WHICH ARE DETAILED AT A

LARGER SCALE.

8. FURNITURE AND OWNER PROVIDED EQUIPMENT ARE

INDICATED BY DASHED LINE TYPE.

9. CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION

OF OWNER PROVIDED EQUIPMENT INCLUDING BUT NOT

LIMITED TO DIMENSIONAL INFORMATION, AND

MECHANICAL, ELECTRICAL AND PLUMBING

REQUIREMENTS.

10. CENTER FLOOR DRAINS IN SPACE UNLESS INDICATED

OTHERWISE.

INFILLED AREA

PLAN LEGEND:

EXISTING WALL/PARTITION/COLUMN

NEW WALL/PARTITION

VACANT SPACE

ACCESS CONTROL, RE: ELEC.

KEYED NOTES:

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:3

AM

AE101A

ENLARGED FIRST FLOOR PLAN - WEST WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 MC MC/MP/BL

200 SPRINGS ROAD, BEDFORD, MA 01730

SCALE: 1/4" = 1'-0"F1 ENLARGED FIRST FLOOR PLAN - WEST

C

D

E

6 7 8 9 10

AE201

F5

C7

AE301

C7

AE301

F2

AE301

F2

AE301

C7

AE312

C7

AE312

F4

AE310

F7

AE312

F6

AE311

F6

AE311

F8

AE311

191 SF

CORRIDOR

440 SF

WAITING

114 125 SF

INTERVIEW

175 SF

LAB

(PHLEBOTOMY)

48 SF

HOUSEKEEPING

114 SF

LACTATION A

137 SF

SHARED

DOCUMENTATION

WORK AREA

80 SF

MED ROOM

48 SF

STAFF TOILET

ELECTRICAL

CLOSET

49 SF

TOILET

111A

119 SF

IT/DATA

126 SF

RECEPTION

386 SF

WAITING

55 SF

EQUIPMENT

STORAGE

357 SF

STAIR 2

S12

109 SF

MECH.

E12

UP

DN

DN

3L 3L 3L 3L 3L

3T 3T

3T

3T

3T

L1

3L3L3L3L3L3L

2B

111A

79 SF

ELEV.

E11

AE501

C3 SIM

AE501

2 SIM

AE501

C1 SIM

AE501

C6 SIM

A1

A A1

A

CLEAR

4' - 0"

PROVIDED PAINTED STEEL CANE RAIL UNDER STAIR STRUCTURE;

CANE RAIL TO LIMIT ACCESS TO AREA WITH HEAD HEIGHTS LESS

THAN 6'-8" CLEAR FROM FINISHED FLOOR

6' - 5 1/2" 3' - 8 1/2"

6' - 5 1/2"

5'

- 0

3'

- 8

/2

7'

- 5

/2

7'

- 5

/2

3'

- 8

/2

4'

- 1

1/ 2"

108B 100B

AE100

F1 SIM

18' - 8" 16' - 0" 16' - 0" 12' - 1 1/2"

/2

6'

- 8

/2

5'

- 0

5'

- 1

1/

2"

15' - 6 1/2"

3' - 4" 11' - 1 1/2" 11" 1' - 0" 1' - 0" 8' - 5 1/2" 1' - 4" 7' - 6 1/2" 10' - 1" 5' - 4 1/2" 4' - 9 1/2" 7' - 0"

2' - 2" 1' - 11" 5' - 4 1/2" 7' - 4" 1' - 1 1/2"

3' - 7 1/2" 6' - 1 1/2" 7' - 10 1/2" 9' - 0"

7' - 9" 9' - 5 1/2"

1' - 0 1/2"

7' - 5 1/2" 9' - 8 1/2" 15' - 6 1/2"

1' - 4 1/2"

7'

- 4

/2

2'

- 2

/2

5'

- 1

6'

- 5

/2

7'

- 7

7'

- 0

/2

6'

- 5

1'

- 9

/2 " 7'

- 5

/2

5'

- 4

/2

1'

- 1

4'

- 9

4'

- 4

4'

- 8

/2

1'

- 2

/2

5'

- 8

/2

1'

- 2

0" 4'

- 1 1"

8' - 6"

9'

- 4

16' - 7 1/2"

/2

W2

W2 W2

M8.2 W2

W2

U4.1

F2a

W2

Q3.0 S3a

S3a

S3a

S3a

S3a

U4.1

Q3.0

U4.1

F2a

Q3.0

F3a

S3.1a S3a

U4.1

S3a

F3aS3a

F3a

F3a

S3a

F3a

Q3.0

S3a S3a

F3a

Q3.0

F3a

S3a

F3a

S3a

S3.1a

S3.1a

U4.1

U4.1

S3.1aS3a

F3a

S3a

U4.1

S3a

Q3.0Q3.0

Q3.0

Q3.0

U4.1

U4.1 F3a

F1a

8A

FLOOR PLAN NOTES:

1. SEE GI002 FOR GENERAL PROJECT NOTES, LEGENDS

AND ABBREVIATIONS.

2. SEE GI003 FOR GENERAL MOUNTING HEIGHTS, TOP OF

WALL DETAILS AND PARTITION TYPES.

3. CONTRACTOR IS RESPONSIBLE FOR REVIEWING CODE

COMPLIANCE PLANS AND NOTIFYING THE ARCHITECT OF

CONFLICTS BETWEEN WHAT IS IN THE FIELD AND ON

THE CODE DOCUMENTS.

4. DIMENSIONS ARE FACE OF CONCRETE, FACE OF

MASONRY AND CENTERLINE OF STUD, UNLESS NOTED

OTHERWISE.

5. DOOR JAMBS (HINGE SIDE) SHALL BE 6" FROM CORNER

IN STUD PARTITIONS AND 8" FROM CORNER IN MASONRY

PARTITIONS UNLESS NOTED OTHERWISE.

6. REFER TO DETAILS FOR ADDITIONAL DIMENSIONING

INFORMATION.

7. REFER TO ENLARGED PLANS FOR PARTITION TYPES AND

DIMENSIONS IN AREAS WHICH ARE DETAILED AT A

LARGER SCALE.

8. FURNITURE AND OWNER PROVIDED EQUIPMENT ARE

INDICATED BY DASHED LINE TYPE.

9. CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION

OF OWNER PROVIDED EQUIPMENT INCLUDING BUT NOT

LIMITED TO DIMENSIONAL INFORMATION, AND

MECHANICAL, ELECTRICAL AND PLUMBING

REQUIREMENTS.

10. CENTER FLOOR DRAINS IN SPACE UNLESS INDICATED

OTHERWISE.

INFILLED AREA

PLAN LEGEND:

EXISTING WALL/PARTITION/COLUMN

NEW WALL/PARTITION

VACANT SPACE

ACCESS CONTROL, RE: ELEC.

KEYED NOTES:

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:4

AM

AE101B

ENLARGED FIRST FLOOR PLAN - EAST WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 MC MC/MP/BL

200 SPRINGS ROAD, BEDFORD, MA 01730

SCALE: 1/4" = 1'-0"F1 ENLARGED FIRST FLOOR PLAN - EAST

Revisions: Date:

ADDENDUM 1 JUNE 9, 2023

FURNITURE, FIXTURES AND EQUIPMENT SHOWN FOR

OC

NL/EM NL/EM NL/EM NL/EM NL/EM

NL/EM

A

B

C

D

E

1 2 3 4 5 6 7 8 9 10

11 12

AE201

F5

223 SF

BARIATRIC

TREATMENT

ROOM

69 SF

BARIATRIC

TOILET

218A

61 SF

SOILED

UTILITY

145 SF

EXAM ROOM

56 SF

PATIENT

TOILET

220A

75 SF

BARIATRIC

TOILET

221A

213 SF

BARIATRIC

EXAM ROOM

212 SF

CORRIDOR

200 117 SF

NURSE

MANAGER

203 217 SF

TRAINING

46 SF

HOUSEKEEPING/

ATTIC

ACCESS

119 SF

IT/DATA

62 SF

TOILET

61 SF

TOILET

620 SF

SPECIALITY

PROVIDER &

RN CARE

MANAGER

WORKSTATIONS

212151 SF

EXAM ROOM

51 SF

PATIENT

TOILET

213A

50 SF

PATIENT

TOILET

214A

147 SF

EXAM ROOM

48 SF

CLEAN

UTILITY

55 SF

PATIENT

TOILET

216A

224 SF

TREATMENT

ROOM

216 119 SF

MED ROOM

155 SF

OFFICE/EXAM

222 SF

EQUIPMENT

STORAGE

9 SF

ELECTRICAL

CLOSET

147 SF

OFFICE/EXAM

48 SF

STORAGE

212A

357 SF

STAIR

468 SF

STAIR 1

DNDN

ELEV.

E21

A1

A

A1

B

ADDITION EXISTING EXISTING ADDITION

109 SF

MECH.

E12

AE100

F1 SIM

FLOOR PLAN NOTES:

1. SEE GI002 FOR GENERAL PROJECT NOTES, LEGENDS

AND ABBREVIATIONS.

2. SEE GI003 FOR GENERAL MOUNTING HEIGHTS, TOP OF

WALL DETAILS AND PARTITION TYPES.

3. CONTRACTOR IS RESPONSIBLE FOR REVIEWING CODE

COMPLIANCE PLANS AND NOTIFYING THE ARCHITECT OF

CONFLICTS BETWEEN WHAT IS IN THE FIELD AND ON

THE CODE DOCUMENTS.

4. DIMENSIONS ARE FACE OF CONCRETE, FACE OF

MASONRY AND CENTERLINE OF STUD, UNLESS NOTED

OTHERWISE.

5. DOOR JAMBS (HINGE SIDE) SHALL BE 6" FROM CORNER

IN STUD PARTITIONS AND 8" FROM CORNER IN MASONRY

PARTITIONS UNLESS NOTED OTHERWISE.

6. REFER TO DETAILS FOR ADDITIONAL DIMENSIONING

INFORMATION.

7. REFER TO ENLARGED PLANS FOR PARTITION TYPES AND

DIMENSIONS IN AREAS WHICH ARE DETAILED AT A

LARGER SCALE.

8. FURNITURE AND OWNER PROVIDED EQUIPMENT ARE

INDICATED BY DASHED LINE TYPE.

9. CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION

OF OWNER PROVIDED EQUIPMENT INCLUDING BUT NOT

LIMITED TO DIMENSIONAL INFORMATION, AND

MECHANICAL, ELECTRICAL AND PLUMBING

REQUIREMENTS.

10. CENTER FLOOR DRAINS IN SPACE UNLESS INDICATED

OTHERWISE.

INFILLED AREA

PLAN LEGEND:

EXISTING WALL/PARTITION/COLUMN

NEW WALL/PARTITION

VACANT SPACE

CEILING NOTES:

1. SEE GI001 FOR GENERAL PROJECT NOTES.

2. SEE FINISH SCHEDULE FOR CEILING AND CEILING GRID

TYPES.

3. EXCEPT WHERE INDICATED, CENTER CEILING GRIDS IN

ROOMS. USE HALF TILES OF GREATER @ PERIMETERS

WHEN POSSIBLE.

4. ALIGN CEILING ITEMS AS SHOWN, WITH COMMON

CENTERLINES TYPICALLY. CENTER ITEMS IN CEILING, OR

IN AREAS UNLESS INDICATED OTHERWISE.

5. WHERE TEGULAR OR BEVELED TILE IS USED, PAINT ALL

CUT EDGES TO MATCH.

6. CAULK JOINT BETWEEN CEILING GRID (WALL ANGLE)

AND WALL WHERE GAPS ARE LARGER THAN 1/8" OR

GREATER.

7. PROVIDE ACCESS PANELS AS REQUIRED IN GWB

CEILINGS FOR ACCESS AS REQUIRED BY ALL TRADES.

8. FIRE SPRINKLERS SHALL BE CENTERED IN CEILING TILE

OR HALF TILE AS SHOWN. FIRE SPRINKLERS SHALL BE

LOCATED IN ALIGNMENT WITH OTHER CEILING ITEMS

AND SHALL BE PLACED IN COORDINATION WITH LIGHT

FIXTURE POSITIONS INDICATED, TYPICAL.

9. FIRE SPRINKLERS ARE SHOWN FOR COORDINATION

PURPOSES ONLY. ADDITIONAL SPRINKLER HEADS MAY

BE REQUIRED FOR CODE COMPLIANCE, AS DETERMINED

BY THE FIRE PROTECTION DESIGNER. SPRINKLERS ARE

NOT SHOWN IN ALL AREAS WHERE REQUIRED. FIRE

PROTECTION CONTRACTOR SHALL BE RESPONSIBLE

FOR PROVIDING A COMPLETE AND FULLY CODE

COMPLIANT SYSTEM, INCLUDING HEADS NOT INDICATED

IN THIS DRAWING. SIDEWALL MOUNT SPRINKLER HEADS

UNDER BALCONIES ARE NOT SHOWN IN THE CEILING

PLANS.

10. SEE MECHANICAL, ELECTRICAL AND PLUMBING

DRAWINGS FOR ADDITIONAL INFORMATION.

11. WHERE ARCHITECTURAL DRAWINGS DEPICT

MECHANICAL OR ELECTRICAL ITEMS OR EQUIPMENT

(LIGHTS, DIFFUSERS, ETC.) INSTALLATION OF SUCH

ITEMS SHALL BE COORDINATED WITH EACH RESPECTIVE

TRADE SUB-CONTRACTOR.

12. WHERE DRAWINGS DO NOT ACCESS INSTALLATION

METHODOLOGY, THE CONTRACTOR SHALL BE BOUND

TO PERFORM IN STRICT COMPLIANCE WITH THE

MANUFACTURER'S SPECIFICATIONS, AND STANDARD

INDUSTRY STANDARDS.

13. CONTRACTOR TO COORDINATE ANY BLOCKING OR

STRUCTURAL SUPPORT ABOVE THE CEILING FOR

OWNER PROVIDED EQUIPMENT.

SUPPLY DIFFUSER

RETURN DIFFUSER

EXHAUST DIFFUSER

LINEAR DIFFUSER

GWB CEILING

DOWN LIGHT

2x2 LIGHT FIXTURE

2x2 CEILING TILE AND GRID (ACT-1)

CEILING LEGEND:

2x2 LIGHT FIXTURE (EMERG.)

UTILITY LIGHT FIXTURE

UTILITY LIGHT FIXTURE (EMERG.)

EMERGENCY EXIT SIGN

OCCUPANCY SENSOROC

R

WALL SCONCE

LINEAR WALL LIGHT

EXTERIOR WALL SCONCE

ACCESS CONTROL, RE: ELEC.

KEYED NOTES:

A

B

C

D

E

1 2 3 4 5 6 7 8 9 10

11 12

223 SF

BARIATRIC

TREATMENT

ROOM

69 SF

BARIATRIC

TOILET

218A

61 SF

SOILED

UTILITY

219 145 SF

EXAM ROOM

56 SF

PATIENT

TOILET

220A

75 SF

BARIATRIC

TOILET

221A

213 SF

BARIATRIC

EXAM ROOM

212 SF

CORRIDOR

117 SF

NURSE

MANAGER

217 SF

TRAINING

119 SF

IT/DATA

62 SF

TOILET

61 SF

TOILET

620 SF

SPECIALITY

PROVIDER &

RN CARE

MANAGER

WORKSTATIONS

151 SF

EXAM ROOM

51 SF

PATIENT

TOILET

213A

50 SF

PATIENT

TOILET

214A

147 SF

EXAM ROOM

48 SF

CLEAN

UTILITY

55 SF

PATIENT

TOILET

216A

224 SF

TREATMENT

ROOM

119 SF

MED ROOM

155 SF

OFFICE/EXAM

222 SF

EQUIPMENT

STORAGE

9 SF

ELECTRICAL

CLOSET

BARIATRIC PATIENT LIFT AND

TRACK. TYP OF 6 (EXAM ROOMS

AND PROCEDURE ROOMS)

RE: STRUCT FOR MOUNTING

147 SF

OFFICE/EXAM

357 SF

STAIR

468 SF

STAIR 1

48 SF

STORAGE

212A

AE102

B1

1-HR. RATED GWB CEILING ON

(5/8" TYPE 'X' GWB ON 7/8"

RESILIENT CHANNEL)

UNDERSIDE OF STRUCTURE

ABOVE ACT AT NEW

STAIRWELL, TYP. (AREA SHOWN

HATCHED)

1-HR. RATED GWB CEILING ON

(5/8" TYPE 'X' GWB ON 7/8"

RESILIENT CHANNEL)

UNDERSIDE OF STRUCTURE

ABOVE ACT AT NEW

STAIRWELL, TYP. (AREA SHOWN

HATCHED)

2-HR. RATED HORIZONTAL SHAFTWALL AT

TOP OF ELEVATOR SHAFT. SEE DETAILS

46 SF

HOUSEKEEPING/

ATTIC

ACCESS

298 SF

CORRIDOR

109 SF

MECH.

E12

449 SF

CORRIDOR

8' - 0" 8' - 0"

C

WALLS TO

UNDERSIDE OF

ATTIC FLOOR.

C5

AE504

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678 www.smrtinc.com

SMRT Architects and Engineers 200 Brickstone Square, Suite 303

Andover, Massachusetts 01810

200 Envoy Circle, Suite 201, Louisville, KY 40299 www.paradigmusa.com

FULLY SPRINKLERED

BEDFORD VA MEDICAL CENTER

C :\U se rs

\m cu tle r\D oc um en ts

\2

_V

A Be df or d W om en s C lin ic

_A rc h_ R

_m cu tle rH N

JT

K.

rv t

6/ 9/

1:

:4

AM

AE102

OVERALL SECOND FLOOR PLANS WOMEN'S CLINIC DESIGN

518-21-103

06-09-2023 MC MC/MP/BL

200 SPRINGS ROAD, BEDFORD, MA 01730

SCALE: 1/8" = 1'-0"F3 OVERALL SECOND FLOOR PLAN

SCALE: 1/8" = 1'-0"C3 SECOND FLOOR REFLECTED CEILING PLAN

SCALE: 1/2" = 1'-0"B1 HOUSE KEEPING / ATTIC ACCESS

Revisions: Date:

ADDENDUM 1 JUNE 9, 2023

SECOND FLOOR CEILING SCHEDULE

# Name Ceiling Finish Ceiling Height Comments

200 CORRIDOR ACT-1/GWB 8'-0" SEE PLAN FOR GWB SOFFIT/BULKHEAD LOCATIONS

201 OFFICE/EXAM ACT-1 8'-0"

202 IT/DATA ACT-1 8'-0"

203 NURSE MANAGER ACT-1 8'-0"

204 TRAINING ACT-1 8'-0"

205 ELECTRICAL CLOSET ACT-1 8'-0"

206 STAIR ACT-1 8'-0"

207 MED ROOM ACT-1 8'-0"

208 HOUSEKEEPING/ ATTIC ACCESS ACT-1 8'-0" COORDINATE WITH ATTIC ACCESS

209 EQUIPMENT STORAGE ACT-1 8'-0"

210 TOILET ACT-1 8'-0"

211 TOILET ACT-1 8'-0"

212 SPECIALITY PROVIDER & RN CARE

MANAGER WORKSTATIONS

ACT-1 8'-0"

212A STORAGE ACT-1 8'-0"

213 EXAM ROOM ACT-1 8'-0"

213A PATIENT TOILET ACT-1 8'-0"

214 EXAM ROOM ACT-1 8'-0"

214A PATIENT TOILET ACT-1 8'-0"

215 CLEAN UTILITY ACT-1 8'-0"

216 TREATMENT ROOM ACT-1 8'-6"

216A PATIENT TOILET ACT-1 8'-6"

217 STAIR 1 ACT-1 8'-0"

218 BARIATRIC TREATMENT ROOM ACT-1 8'-6" COORDINATE WITH PATIENT LIFT TRACK

218A BARIATRIC TOILET ACT-1 8'-6" COORDINATE WITH PATIENT LIFT TRACK

219 SOILED UTILITY ACT-1 8'-0"

220 EXAM ROOM ACT-1 8'-0"

220A PATIENT TOILET ACT-1 8'-0"

221 BARIATRIC EXAM ROOM ACT-1 8'-6" COORDINATE WITH PATIENT LIFT TRACK

221A BARIATRIC TOILET ACT-1 8'-6" COORDINATE WITH PATIENT LIFT TRACK

222 OFFICE/EXAM ACT-1 8'-0"

230 CORRIDOR ACT-1 8'-2"

240 CORRIDOR ACT-1/GWB 8'-0" SEE PLAN FOR GWB SOFFIT/BULKHEAD LOCATIONS

E21 ELEV. ACT-1 8'-0" COORDINATE WITH ELEVATOR MANUFACTURER

LIGHTING FIXTURES SHOWN FOR

REFERENCE ONLY. REFER TO ELECTRICAL

DRAWINGS FOR ADDITIONAL INFORMATION.

AND ABBREVIATIONS.

2. SEE GI003 FOR GENERAL MOUNTING HEIGHTS, TOP OF

WALL DETAILS AND PARTITION TYPES.

3. CONTRACTOR IS RESPONSIBLE FOR REVIEWING CODE

COMPLIANCE PLANS AND NOTIFYING THE ARCHITECT OF

CONFLICTS BETWEEN WHAT IS IN THE FIELD AND ON

THE CODE DOCUMENTS.

4. DIMENSIONS ARE FACE OF CONCRETE, FACE OF

MASONRY AND CENTERLINE OF STUD, UNLESS NOTED

OTHERWISE.

5. DOOR JAMBS (HINGE SIDE) SHALL BE 6" FROM CORNER

IN STUD PARTITIONS AND 8" FROM CORNER IN MASONRY

PARTITIONS UNLESS NOTED OTHERWISE.

6. REFER TO DETAILS FOR ADDITIONAL DIMENSIONING

INFORMATION.

7. REFER TO ENLARGED PLANS FOR PARTITION TYPES AND

DIMENSIONS IN AREAS WHICH ARE DETAILED AT A

LARGER SCALE.

8. FURNITURE AND OWNER PROVIDED EQUIPMENT ARE

INDICATED BY DASHED LINE TYPE.

9. CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION

OF OWNER PROVIDED EQUIPMENT INCLUDING BUT NOT

LIMITED TO DIMENSIONAL INFORMATION, AND

MECHANICAL, ELECTRICAL AND PLUMBING

REQUIREMENTS.

10. CENTER FLOOR DRAINS IN SPACE UNLESS INDICATED

OTHERWISE.

INFILLED AREA

PLAN LEGEND:

EXISTING WALL/PARTITION/COLUMN

NEW WALL/PARTITION

VACANT SPACE

ACCESS CONTROL, RE: ELEC.

KEYED NOTES:

A

B

C

D

E

1 2 3 4 5 6

F2

AE301

F2

AE301

F9

AE310

C3

AE312

C3

AE312

F3

AE312

F6

AE310

BARIATRIC

TREATMENT

ROOM

BARIATRIC

TOILET

218A

SOILED

UTILITY

EXAM ROOM

PATIENT

TOILET

220A

BARIATRIC

TOILET

221A

BARIATRIC

EXAM ROOM

EXAM ROOM

PATIENT

TOILET

213A

PATIENT

TOILET

214A

EXAM ROOM

CLEAN

UTILITY

PATIENT

TOILET

216A

TREATMENT

ROOM

3B 3B3B

3B3B3B

3B3B3B3B3B3B3B

2A 2A

2A

0 22

213A216A

214A

221A

220A

218A

OFFICE/EXAM

STAIR 1

200B

AE101D1

2T2T

2T

2T

2T

2T

2T

2T 2T

DN

F4

AE310

6 21

1 1

1 1

A1

B A1

B

5'

- 0

3'

- 8

/2

3'

- 8

/2

4'

- 1

1/ 2"

6' - 5 1/2" 3' - 8 1/2" 6' - 5 1/2"

7'

- 5

/2

7'

- 5

/2

AE100

F1 SIM

/2

6'

- 8

/2

5'

- 0

12' - 1 1/2" 16' - 0" 16' - 0" 18' - 8" 10' - 8"

1"

15' - 7 1/2"

15' - 10 1/2" 1' - 1" 4' - 0" 5' - 9" 1' - 0" 10' - 7 1/2" 10" 3' - 10" 2' - 4" 1' - 7" 3' - 11 1/2" 14' - 1"

16' - 9 1/2" 2' - 0 1/2" 6' - 11" 11' - 0" 8' - 1 1/2" 7' - 6 1/2" 3' - 7 1/2"

7'

- 1

/2

3'

- 0

/2

3'

- 7

6'

- 5

4'

- 7

2'

- 7

7'

- 2

/2

3"

7'

- 0

7'

- 3

/2

7'

- 4

6'

- 5

6'

- 1

1/ 2"

/2

6'

- 9

/2

3'

- 1

1/

2"

1'

- 0

/2

6'

- 5

1'

- 0

/2

16' - 7 1/2"

W2

W2

W2

F1a

Q3.0

S6.0

S3.1a

U4.1

S3.1a

S3.1a

F3a

F3a

S3a

F3a F3a

F3a

S3a

S3a

F3a

S3a

S6.0

Q3.0

S3a

S3a

S6.0

S3.1aU4.1

S3.1a

U4.1

S3aQ3.0

Q3.0

F3a

F3a

S3a

S6.1

U4.1

S6.1

Q3.0

F6

F6

S3a

Q3.0

F3a

F3a

Q3.0

S3a

S3a

F3aQ3.0

F3a

Q3.0

Q3.0

S3a

Q3.0

F6

U4.1

U4.1

S3.1a

S3.1a

F3a

F3a

S3a

S3a

TRUE NORTH

Architecture Engineering Design-Build paradigm

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS FOR

CONSTRUCTION

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

1.877.700.7678…

This is the start of the file's text. The full file is on GovTribe.