This document is a set of construction drawings and related documents for the design and construction of a new boiler plant facility at the West Los Angeles VA Medical Center. The drawings and specifications cover the structural design, including the framing plans, sections, and details for the reinforced concrete foundation and steel-framed superstructure. Key details include the structural loads, materials, reinforcing, connections, and coordination with other building systems. This project is part of a solicitation (Solicitation #36C10F24R0018) issued by the Department of Veterans Affairs Office of Construction and Facilities Management for the construction of the new boiler plant facility in West Los Angeles, California.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT TEAM
CLIENT/ OWNER
DEPARTMENT OF VETERAN'S AFFAIRS
CONSTRUCTION AND FACILITIES MANAGEMENT,
WESTERN REGION
400 MARE ISLAND WAY, SUITE 100
VALLEJO, CA 94590
VA PROJECT NUMBER: 691-20-150
ATTN: TIMOTHY LAFAVE
ARCHITECT / INTERIORS / SIGNAGE
LEO A DALY
550 SOUTH HOPE STREET, 27TH FLR
LOS ANGELES, CA 90071
213.629.0100
ATTTN: PARI TIVAY
STRUCTURAL ENGINEER
JOHN A. MARTIN & ASSOCIATES
950 S. GRAND AVENUE, 4TH FLOOR
LOS ANGELES, CA 90015
213.785.3161
ATTN: SHANE FITZGERALD
MECHANICAL & PLUMBING
OPERATIONAL SECURITY
GUIDEPOST SOLUTIONS
2121 N. CALIFORNIA BLVD, SUITE 800
WALNUT CREEK, CA 94596
ATTN: RAY KOLODZIECZAK
FIRE PROTECTION
LEO A DALY
730 SECOND AVE SOUTH SUITE 1300
MINNEAPOLIS, MN 55402
612.341.9559
ATTN: DANIEL OLIG
LEO A DALY
8600 INDIAN HILLS DRIVE,
OMAHA, NE 68114-4039
402.390.4437
ATTN: MIKE BRADY
ELECTRICAL
LEO A DALY
8600 INDIAN HILLS DRIVE,
OMAHA, NE 68114-4039
402.390.4247
ATTN: JUERGEN NOETZEL
ELEVATOR AND TRANSPORT
ST. ONGE
1400 WILLIAMS ROAD
YORK, PA 17402
717.505.8026
ATTN: SEAN STEINER
LOW VOLTAGE
LEO A DALY
10 TENTH STREET NE SUITE 200
ATLANTA, GA 30309
404.885.7922
ATTN: STEVE DAVIS
CIVIL ENGINEER
PSOMAS
3 HUTTON CENTRE DRIVE SUITE 200
SANTA ANA, CA 92707
714.751.7353
ATTN: ROBERT J. TALAFUS
LANDSCAPE ARCHITECT
PAMELA BURTON & COMPANY
1430 OLYMPIC BOULEVARD
SANTA MONICA, CA 90404
310.828.6373
ATTN: PAUL FIEGENSCHUE
PHYSICAL SECURITY
KPFF CONSULTING ENGINEERS
45 FREEMONT ST, 28TH FLOOR
SAN FRANCISCO, CA 94105
415.989.1004
ATTN: SHARON GALLANT
COST MANAGEMENT
CUMMING CORP
660 S. FIGUEROA ST., SUITE 900
LOS ANGELES, CA 90071
213.405.0694
ATTN: TREVOR SHULTERS
GEOTECHNICAL ENGINEER
NINYO & MOORE
475 GODDARD, SUITE 200
IRVINE, CA 92618
949.753.7070
ATTN: GREG CORSON
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /0
-1
-0
V A
W
L A
-C C
C C
U P
S it e
U ti ls
R e n o o f_ B
/6
-2
-1
.6
.A
R C
H .r v t
/1
/2
:0
:2
P
M
GI000
COVER SHEET
LEO A DALY COMPANY
LOS ANGELES, CA 90071
(213) 629-0100
PARI TIVAY
WEST LA MEDICAL CENTER
NEW BOILER PLANT
WEST LOS ANGELES, CA
691-20-150
10/31/2023
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
550 SOUTH HOPE STREET, 27TH FLOOR
UPGRADE BOILER PLANT by REPLACEMENT (SEISMIC and PHYSICAL SECURITY COMPLIANCE)
VA PROJECT #: 691-20-150
LAD PROJECT #: 046-10092-000
CONSTRUCTION DOCUMENTS - ADDENDUM 2
ISSUE DATE - AUGUST 19, 2024
11301 WILSHIRE BLVD, LOS ANGELES, CA 90073
WEST LOS ANGELES MEDICAL CENTER
VA GREATER LOS ANGELES HEALTH CARE SYSTEM
NEW BOILER PLANT (B603)
Revisions: Date:
GENERAL
1. THE PROJECT SPECIFICATIONS FORM A PART OF THESE GENERAL NOTES.
2. CONTRACTOR SHALL CAREFULLY REVIEW ALL CONTRACT DOCUMENTS TO IDENTIFY THE
EXTENT OF THE SCOPE OF WORK. VISIT THE SITE TO RELATE THE SCOPE OF WORK TO
EXISTING CONDITIONS AND DETERMINE THE EXTENT TO WHICH THOSE CONDITIONS AND
PHYSICAL SURROUNDINGS WILL IMPACT THE WORK.
3. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION. THE DESIGN
TEAM SHALL BE NOTIFIED OF ANY DISCREPANCIES OR INCONSISTENCIES.
4. THE CONTRACTOR SHALL RESOLVE ANY CONFLICTS ON THE CONTRACT DOCUMENTS WITH
THE DESIGN TEAM BEFORE PROCEEDING WITH THE WORK.
5. ALL WORK SHALL CONFORM TO THE STANDARDS OF THE FOLLOWING:
AND ANY OTHER REGULATING AGENCIES WHICH HAVE AUTHORITY OVER ANY PORTION OF
THE WORK, INCLUDING BUT NOT LIMITED TO CAL/OSHA, DIVISION OF OCCUPATIONAL SAFETY
AND HEALTH, AND THOSE CODES AND STANDARDS LISTED IN THE CONTRACT DOCUMENTS.
6. CODES AND STANDARDS NOTED IN THE CONTRACT DOCUMENTS SHALL BE OF THE LATEST
ADOPTED ISSUE, INCLUDING SUPPLEMENTS, UNLESS OTHERWISE NOTED. MATERIAL
SPECIFICATIONS SHALL COMPLY WITH ASTM REFERENCED STANDARDS LATEST ADOPTED
EDITION.
7. INFORMATION SHOWN ON THE DRAWINGS RELATED TO EXISTING CONDITIONS REPRESENTS
THE PRESENT KNOWLEDGE, BUT WITHOUT GUARANTEE OF ACCURACY. REPORT CONDITIONS
THAT CONFLICT WITH THE CONTRACT DOCUMENTS TO THE COR DO NOT DEVIATE FROM THE
CONTRACT DOCUMENTS WITHOUT WRITTEN DIRECTION FROM THE COR
8. DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED DRAWINGS. DRAWINGS SHALL NOT BE
SCALED.
9. DETAILS IN SHEETS TITLED 'TYPICAL DETAILS', TYPICAL DETAILS AND GENERAL NOTES APPLY
TO ALL PARTS OF THE WORK, EXCEPT WHERE SPECIFICALLY DETAILED OR UNLESS NOTED
OTHERWISE. THESE DETAILS ARE NOT SPECIFICALLY REFERENCED WHERE THEY OCCUR.
10. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND
TYPICAL DETAILS. WHERE NOTES AND DETAILS ON DRAWINGS ARE IN CONFLICT WITH
GENERAL NOTES, TYPICAL DETAILS, OR PROJECT SPECIFICATIONS THE MOST STRINGENT
SHALL APPLY. CONDITIONS NOT SPECIFICALLY SHOWN SHALL BE CONSTRUCTED AS SHOWN
FOR SIMILAR WORK.
11. SEE ARCHITECTURAL DRAWINGS FOR THE FOLLOWING:
A. SIZE AND LOCATION OF ALL DOOR AND WINDOW OPENINGS.
B. SIZE AND LOCATION OF ALL NON-BEARING PARTITIONS.
C. SIZE AND LOCATION OF ALL CONCRETE CURBS, FLOOR DRAINS, SLOPES, DEPRESSED
AREAS, CHANGES IN LEVEL, CHAMFERS, GROOVES, INSERTS, ETC.
D. EXTERIOR WALL SYSTEM.
E. SIZE AND LOCATION OF ALL FLOOR AND ROOF OPENINGS.
F. STAIR DIMENSIONS AND DETAILS.
G. DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS.
12. SEE MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR THE FOLLOWING:
A. PIPE RUNS, SLEEVES, HANGERS, TRENCHES, WALL, ROOF AND FLOOR OPENINGS, ETC.,
NOT SHOWN OR NOTED.
B. ELECTRICAL CONDUIT RUNS, BOXES, OUTLETS IN WALLS AND SLABS.
C. ANCHORAGE AND BRACING FOR ELECTRICAL, MECHANICAL OR PLUMBING EQUIPMENT
TO THE STRUCTURE.
D. ANCHOR BOLTS FOR EQUIPMENT MOUNTS.
E. SIZE, WEIGHT, AND LOCATION OF MACHINE AND EQUIPMENT BASES.
13. ANY DEVIATION FROM THE APPROVED SET OF CONTRACT DOCUMENTS SHALL BE SUBMITTED
TO THE COR FOR REVIEW/APPROVAL BEFORE PROCEEDING WITH THE WORK. SUBSTITUTIONS
OF PRODUCTS OR MATERIALS SPECIFIED ON THE CONSTRUCTION DOCUMENTS ARE NOT
ALLOWED WITHOUT COR APPROVAL.
14. MANUFACTURED MATERIALS SHALL BE APPROVED BY THE CHECKING AGENCY PRIOR TO
THEIR USE. ALL REQUIREMENTS OF THOSE APPROVALS SHALL BE FOLLOWED.
15. THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE
THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE MEANS, METHOD,
TECHNIQUES, SEQUENCE AND PROCEDURE OF CONSTRUCTION AS REQUIRED. SITE VISITS
PERFORMED BY THE COR DO NOT INCLUDE INSPECTIONS OF MEANS AND METHODS OF
CONSTRUCTION PERFORMED BY CONTRACTOR.
16. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY SHORES, BRACES AND GUYS REQUIRED
TO SUPPORT ALL LOADS TO WHICH THE BUILDING STRUCTURE AND COMPONENTS, SOILS,
OTHER STRUCTURES AND UTILITIES MAY BE SUBJECTED DURING CONSTRUCTION. SHORING
SYSTEMS SHALL BE DESIGNED AND STAMPED BY A CIVIL OR STRUCTURAL ENGINEER
LICENSED IN THE STATE OF CALIFORNIA. VISITS TO THE SITE BY THE SEOR WILL NOT INCLUDE
OBSERVATION OF THE ABOVE NOTED ITEMS.
17. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED FLOORS OR
ROOFS. LOAD SHALL NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT SPECIFIED
ON THIS SET OF DRAWINGS. PROVIDE ADEQUATE SHORING AND/OR BRACING WHERE
STRUCTURE HAS NOT ATTAINED DESIGN STRENGTH OR WHERE OVERLOAD IS ANTICIPATED.
18. DO NOT SPLICE STRUCTURAL MEMBERS UNLESS SPECIFICALLY DETAILED AND INDICATED
IN THIS SET OF DRAWINGS. DO NOT PLACE OPENINGS, POCKETS, ETC. IN STRUCTURAL
MEMBERS UNLESS SPECIFICALLY DETAILED AND INDICATED IN THIS SET OF STRUCTURAL
DRAWINGS.
19. NOTIFY THE STRUCTURAL ENGINEER OF RECORD IF DRAWINGS BY OTHERS REQUIRE
MODIFICATIONS TO STRUCTURAL MEMBERS AS SHOWN IN THIS SET OF STRUCTURAL
DRAWINGS PRIOR TO PROCEEDING WITH THE WORK.
20. UNLESS NOTED OTHERWISE, COLUMNS, WALLS, BEAMS, FOOTINGS, ETC, ARE CENTERED
AT GRIDLINES. WHERE BEAM TO BEAM SPACING IS NOT SHOWN, BEAM SHALL BE EQUALLY
SPACED BETWEEN GRIDLINES.
21. STRUCTURAL OBSERVATIONS PERFORMED BY THE STRUCTURAL ENGINEER DURING
CONSTRUCTION ARE NOT THE REQUIRED CONTINUOUS AND SPECIAL INSPECTION SERVICES
AND DO NOT WAIVE THE RESPONSIBILITY FOR THE INSPECTIONS REQUIRED OF THE BUILDING
INSPECTOR OR THE DEPUTY INSPECTOR. OBSERVATIONS ALSO DO NOT GUARANTEE
CONTRACTOR'S PERFORMANCE AND SHALL NOT BE CONSIDERED AS SUPERVISION OF
CONSTRUCTION.
22. CONTRACTOR SHALL REVIEW SHOP DRAWINGS FOR COMPLETENESS AND COMPLIANCE WITH
CONTRACT DOCUMENTS AND SHALL STAMP SHOP DRAWINGS PRIOR TO SUBMISSION TO THE
COR
23. ARCHITECT'S / ENGINEER'S REVIEW OF THE SHOP DRAWINGS SHALL NOT BE CONSTRUED AS
AN AUTHORIZATION TO DEVIATE FROM CONTRACT DOCUMENTS.
24. SHOP DRAWINGS WILL NOT BE PROCESSED DUE TO INCOMPLETENESS, LACK OF
COORDINATION WITH RELEVANT PORTION OF CONTRACT DOCUMENTS, LACK OF
CALCULATIONS IF REQUIRED AND WHERE DEVIATIONS, MODIFICATIONS AND SUBSTITUTIONS
ARE INDICATED WITHOUT PRIOR WRITTEN APPROVAL FROM THE COR
PG18-15
VA SEISMIC HAND BOOK HI8-8
IBC 2021
ASCE 7-16
GENERAL CONTINUED
25. ALLOW SEVEN WORKING DAYS FOR PROCESSING SHOP DRAWINGS OTHER THAN
STRUCTURAL STEEL & DELEGATED DESIGN ITEMS AFTER RECEIPT BY THE STRUCTURAL
ENGINEER. ALLOW FOURTEEN WORKING DAYS FOR PROCESSING STRUCTURAL STEEL &
DELEGATED DESIGN ITEMS SHOP DRAWINGS. SHOP DRAWINGS AND SUBMITTALS WILL BE
REVIEWED A MAXIMUM OF TWO TIMES.
26. ALLOW FIVE WORKING DAYS TO RESPOND TO REQUESTS FOR INFORMATION (RFI'S)
27. DESIGN LOADS:
A. DEAD LOADS: CONSIST OF BUILDING SELF-WEIGHT PLUS SUPERIMPOSED DEAD LOADS.
REFER TO COMPLETE SET OF DRAWINGS FOR DETERMINING DEAD LOADS.
B. LIVE LOADS:
AREA DESIGN LIVE LOAD REMARK
C. SEISMIC DESING LOADS:
SEISMIC IMPORTANCE FACTOR Ie =
RISK CATEGORY =
SS =
S1 =
SITE CLASS =
SDS =
SD1 =
SEISMIC DESIGN CATEGORY =
R =
ΩO =
CD =
CS =
SEISMIC DESIGN BASE SHEAR =
ANALYSIS PROCEDURE USED =
PROGRESSIVE COLLAPSE = 2015 VA PHYSICAL SECURITY
DESIGN MANUAL (VA PSDM)
D. WIND DESIGN LOADS:
BASIC WIND SPEED (3 SEC. GUST) =
RISK CATEGORY =
WIND EXPOSURE =
INTERNAL PRESSURE COEFFICIENT =
COMPONENTS &
CLADDING WIND PRESSURE =
1.5
IV
2.019g 0.723g
1.367g 0.964g
5 (SPECIAL REINFORCED
SHEAR WALLS)
2.5 3.5 0.410 0.410
SCALED DOMAL RESPONSE
SPECTRUM ANALYSIS
105 MPH
VI
PER ASCE 7-16 CHAPTER 30
0.18 FOR ENCLOSED STRUCTURE
B
CATWALK 40 PSF REDUCIBLE
STAIRS, LOBBIES 100 PSF UNREDUCED
ROOF 20 PSF UNREDUCIBLE
FUEL TANK LID 250 PSF AASHTO HL93 LOADING
ADMINSTRATIVE SUPPORT 80 PSF + 20 PSF REDUCIBLE
(PARTITIONS)
D
D
1. THE DESIGN OF THE FOUNDATION SYSTEM IS BASED UPON THE CRITERIA AND
RECOMMENDATIONS CONTAINED IN THE GEOTECHNICAL INVESTIGATION REPORT
ENTITLED NINYO & MOORE REPORT PROJECT NO. 209826018, DATED OCTOBER 16, 2020
AND ALL SUBSEQUENT ADDENDA. COPIES SHALL BE MADE AVAILABLE AT THE PROJECT
SITE AT ALL TIMES.
2. FOOTING DESIGN IS BASED ON THE FOLLOWING:
3. ALL EARTHWORK SHALL BE DONE IN ACCORDANCE WITH SOILS REPORT
RECOMMENDATIONS.THE GEOTECHNICAL INVESTIGATION REPORT AND ITS
RECOMMENDATIONS SHALL BE FOLLOWED AND SHALL BE CONSIDERED MINIMUM
REQUIREMENTS UNLESS MORE STRINGENT REQUIREMENTS ARE PRESENTED IN
THE CONSTRUCTION DOCUMENTS.
4. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR EXCAVATION PROCEDURES
INCLUDING LAGGING, SHORING, UNDERPINNING AND PROTECTION OF EXISTING
CONSTRUCTION.
5. CONTRACTOR SHALL PROVIDE DE-WATERING OF EXCAVATIONS FROM SURFACE
WATER, GROUND WATER OR SEEPAGE AS REQUIRED. REMOVE LOOSE SOIL AND
STANDING WATER FROM FOUNDATION EXCAVATIONS PRIOR TO PLACING CONCRETE.
6. EXCAVATION AND COMPACTING IF REQUIRED SHALL BE APPROVED BY THE GOVERNING
AGENCY AND THE GEOTECHNICAL ENGINEER PRIOR TO PLACING THE CONCRETE AND
REINFORCING. THE GEOTECHNICAL ENGINEER SHALL SUBMIT LETTER OF COMPLIANCE
TO THE COR
7. ALL EXCAVATIONS SHALL BE PROPERLY BACKFILLED. DO NOT PLACE BACKFILL BEHIND
RETAINING WALLS BEFORE WALLS HAVE ATTAINED FULL DESIGN STRENGTH.
CONTRACTOR SHALL BRACE OR PROTECT ALL BUILDING AND PIT WALLS BELOW GRADE
FROM LATERAL LOADS UNTIL ATTACHING FLOORS ARE COMPLETELY IN PLACE AND
HAVE ATTAINED FULL STRENGTH. CONTRACTOR SHALL PROVIDE FOR DESIGN, PERMITS
AND INSTALLATION OF SUCH BRACING.
8. FOOTINGS SHALL BE PLACED AND ESTIMATED ACCORDING TO DEPTHS SHOWN ON
DRAWINGS. SHOULD SOIL ENCOUNTERED AT THESE DEPTHS NOT BE APPROVED BY
THE FOUNDATION ENGINEER, FOOTING ELEVATIONS SHALL BE ALTERED AS REQUIRED.
9. FOOTING BACKFILL AND UTILITY TRENCH BACKFILL WITHIN BUILDING AREA SHALL BE
MECHANICALLY COMPACTED IN LAYERS IN ACCORDANCE WITH SOIL REPORT.
FLOODING IS NOT BE PERMITTED.
10. LOCATE AND PROTECT EXISTING UTILITIES TO REMAIN DURING AND/OR AFTER
CONSTRUCTION.
11. ALL ABANDONED FOOTINGS, UTILITIES, ETC., THAT INTERFERE WITH NEW
CONSTRUCTION SHALL BE REMOVED.
FOUNDATIONS AND SITE WORK
THICKNESS
3 FEET
EMBEDMENT (LOWEST ADJACENT
GRADE TO BOTTOM OF FOOTING
WIDTH
CONTINUOUS FTG
DESCRIPTION MINIMUM DIMENSION
ISOLATED FTG
5 FEET (3 FEET FOR STAIR & OTHER MINOR
ELEMENTS)
24 INCHES
LATERAL (PASSIVE) BEARING PRESSURE
4000 PSF
COEFFICIENT OF FRICTION
VERTICAL BEARING
PRESSURES
CONTINUOUS FTG
DESCRIPTION ALLOWABLE CAPACITY
ISOLATED FTG
0.35
COMMENTS
SEE NOTE A
SEE NOTE A
N/A
N/A
4000 PSF
350 PCF
A. CAPACITY MAY BE INCREASED BY 1/3 FOR SHORT-TERM WIND OR SEISMIC LOADS
12 INCHES
CONCRETE
1. ALL CONCRETE IS REINFORCED AND CAST-IN-PLACE UNLESS OTHERWISE NOTED.
2. ALL PHASES OF WORK PERTAINING TO THE CONCRETE CONSTRUCTION SHALL CONFORM TO
THE LATEST ADOPTED EDITION OF 'BUILDING CODE REQUIREMENTS FOR REINFORCED
CONCRETE' AND ACI 318 WITH MODIFICATIONS AS NOTED IN THE CONTRACT DOCUMENTS.
3. CONCRETE MIXING OPERATION, ETC., SHALL CONFORM TO ASTM C94.
4. PLACEMENT OF CONCRETE SHALL CONFORM TO ACI 304 AND CONTRACT
DOCUMENTS.
5. STRUCTURAL CONCRETE SHALL HAVE THE FOLLOWING PROPERTIES:
6. CONTRACTOR IS RESPONSIBLE FOR CAREFULLY COORDINATING AND ACCURATELY PLACING
CONCRETE WHEN MULTIPLE GRADES OF CONCRETE ARE ON THE JOBSITE AT ANY ONE TIME.
7. CONCRETE MIXES SHALL BE DESIGNED BY AN APPROVED LABORATORY. THE DESIGN
SHALL BE STAMPED BY A CIVIL OR STRUCTURAL ENGINEER LICENSED IN THE STATE
OF CALIFORNIA AND SUBMITTED TO THE COR FOR REVIEW AND APPROVAL. ADMIXTURES
CONTAINING CALCIUM CHLORIDE ARE NOT ALLOWED.
8. NORMAL WEIGHT CONCRETE AGGREGATES SHALL CONFORM TO ASTM C33. LIGHT WEIGHT
CONCRETE AGGREGATES SHALL CONFORM TO ASTM C330. DRY DENSITY OF NORMAL WEIGHT
CONCRETE SHALLL NOT EXCEED 145 PCF. DRY DENSITY OF LIGHTWEIGHT CONCRETE
SHALL NOT EXCEED 110 PCF.
9. NON-SHRINK CEMENT GROUT SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE
STRENGTH OF 6000 PSI. USE "SIKA GROUT 212" OR "MASTERFLOW 928").
10. FORMS FOR CONCRETE SHALL BE LAID OUT AND CONSTRUCTED TO PROVIDE THE
SPECIFIED CAMBERS SHOWN ON THE DRAWINGS.
11. PROVIDE POUR POCKETS IN FORMS AND UNDER EXISTING STRUCTURAL MEMBERS AS
REQUIRED TO PREVENT AIR POCKETS AND OR "HONEYCOMB" UNDER OR AROUND
THE EXISTING MEMBERS. CONCRETE CAST WITH AIR POCKETS AND OR
"HONEYCOMB" UNDER OR AROUND THE MEMBERS IS NOT ACCEPTABLE.
12. THE CONTRACTOR SHALL MAINTAIN A LOG OF STRUCTURAL SLAB ELEVATIONS BASED
ON THE ARCHITECTURAL DRAWINGS PLUS THE ADDITION OF ANY CAMBERS INDICATED
ON THE CONSTRUCTION DOCUMENTS. THIS LOG SHALL INDICATE SCREED ELEVATIONS
PRIOR TO THE CONCRETE POUR, AND TOP OF CONCRETE SLAB PRIOR TO REMOVAL OF
FORMS.
13. REFER TO PROJECT SPECIFICATIONS FOR CONCRETE FINISHING REQUIREMENTS.
THE MINIMUM CONCRETE SLAB THICKNESS SHALL BE AS SHOWN ON PLANS.
OVERPOUR MAY BE REQUIRED DUE TO FORMING AND STRUCTURE DEFLECTION.
15. THOROUGHLY CLEAN AND ROUGHEN ALL EXISTING CONCRETE, CONCRETE PREVIOUSLY
POURED AND HARDENED AND MASONRY SURFACES TO RECEIVE NEW CONCRETE.
INTERFACE SHALL BE ROUGHENED TO A FULL AMPLITUDE OF 1/4" UNLESS NOTED
OTHERWISE.
16. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR
REINFORCEMENT PLACED IN CAST-IN-PLACE OR CONCRETE:
A. CONCRETE CAST AGAINST AND PERMANENTLY
EXPOSED TO EARTH 3"
B. FORMED CONCRETE EXPOSED TO EARTH OR
WEATHER:
#5 BAR, W31 OR D31 WIRE, AND SMALLER 1 1/2"
#6 THROUGH # 18 BARS 2"
C. CONCRETE NOT EXPOSED TO WEATHER OR IN
CONTACT WITH GROUND:
SLABS AND JOISTS:
#14 AND #18 BARS 1 1/2"
#11 BAR AND SMALLER 1"
BEAMS, COLUMNS AND WALLS:
PRIMARY REINFORCEMENT, TIES, STIRRUPS,
AND SPIRALS:
#3 THROUGH #11 1 1/2"
#14 AND #18 BARS 2 1/2"
17. ALL REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS SHALL BE
WELL SECURED IN POSITION PRIOR TO PLACING CONCRETE.
18. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL OPENINGS IN CONCRETE BEFORE
PLACING. DO NOT CUT ANY REINFORCING WHICH MAY CONFLICT. CORING IN
CONCRETE IS NOT PERMITTED EXCEPT AS SHOWN. NOTIFY THE STRUCTURAL
ENGINEER IN ADVANCE OF CONDITIONS NOT SHOWN ON THE DRAWINGS.
19. CONDUIT OR PIPE SIZE (O.D.) SHALL NOT EXCEED ONE THIRD OF SLAB THICKNESS
AND SHALL BE PLACED BETWEEN THE TOP AND BOTTOM REINFORCING, UNLESS
SPECIFICALLY DETAILED OTHERWISE. CONCENTRATIONS OF CONDUITS OR PIPES
SHALL BE AVOIDED EXCEPT WHERE DETAILED OPENINGS ARE PROVIDED.
20. PROJECTING CORNERS OF BEAMS, WALLS, COLUMNS, ETC., SHALL BE FORMED WITH
A 3/4 IN. CHAMFER, UNLESS OTHERWISE NOTED ON ARCHITECTURAL DRAWINGS.
21. CURING COMPOUNDS USED ON CONCRETE TO RECEIVE A FINISH SHALL BE
APPROVED BY THE FINISH APPLICATOR BEFORE USE.
22. THE MAXIMUM SIZE OF A SINGLE POUR FOR ANY DAY FOR ELEVATED SLABS SHALL
NOT EXCEED 20,000 SQUARE FEET, AND THE RATIO OF LENGTH TO WIDTH OF THE
POUR SHALL NOT EXCEED 2 TO 1 WITHOUT THE APPROVAL OF THE COR
14. HORIZONTAL CONSTRUCTION JOINTS ARE NOT PERMITTED IN BEAMS AND SLABS
UNLESS SPECIFICALLY SHOWN ON THE CONSTRUCTION DRAWINGS
LOCATION
FILL ON METAL DECK
SLAB ON GRADE
COLUMNS
WALLS
ALL OTHER CONCRETE
STRENGTH (f'c)
AT 28 DAYS UNOA
4000 PSI
4000 PSI
5000 PSI
4000 PSI
F0 S1 W0 C1
EXPOSURE
CLASS B,C
F0 S1 W0 C1
F0 S1 W0 C1
F0 S1 W0 C1
0.5
MAX W/C
RATIO
0.45
N/A
N/A
NMSAD
3/4"
1/2"
3/4"
A. ALL CONCRETE IS NORMAL WEIGHT UNO. REFER TO NOTE 8 FOR DEFINITION OF NORMAL
WEIGHT AND LIGHT WEIGHT CONCRETE.
B. EXPOSURE CLASS IS AS DEFINED BY ACI 318 TABLE 19.3.1.1.
C. PROVIDE CEMENTITIOUS MATERIAL TYPES AS LIMITED BY EXPOSURE CLASS PER ACI 318.
TABLE 19.3.2.1.
D. NMSA = NOMINAL MAXIMUM AGGREGATE SIZE
5000 PSI
F0 S1 W0 C1 N/A 3/4"
3/4"
3/4"
PRECAST PLANKS 5000 PSI LWC F0 S1 W0 C1 N/A 3/4"
FUEL TANK MAT FOUNDATION 5000 PSI 0.45 3/4"F0 S1 W0 C1
REINFORCING STEEL
1. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE
WITH THE 'BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE' (ACI 318)
AND THE 'MANUAL OF STANDARD PRACTICE FOR REINFORCED CONCRETE
CONSTRUCTION' BY THE C.R.S.I. AND THE W.C.R.S.I., OR AS MODIFIED BY THE
CONSTRUCTION DOCUMENTS.
2. REINFORCING BARS SHALL CONFORM TO THE FOLLOWING, UNLESS NOTED
OTHERWISE.
CLASSIFICATION TYPE
REINFORCING STEEL TO BE WELDED ASTM A706, 60 KSI
ALL OTHER REINFORCING STEEL ASTM A615, 60 KSI*
* ASTM A706 GR 60 MAY BE CONSIDERED EQUIVALENT
TO ASTM A615, BUT ASTM A615 IS NOT EQUIVALENT
TO ASTM A706.
3. MECHANICAL COUPLERS: LENTON THREADED COUPLERS BY ERICO, IAPMO UES ER
0129, HRC 500/510 XTENDER BY HEADED REINFORCEMENT CORPORATION, ICC ESR
#2764, OR BAR-LOCK BY DAYTON SUPERIOR CORP, IAPMO UES ER 0319). COUPLERS
FOR BEAM AND SLAB BARS AT FORMED CONSTRUCTION JOINTS MAY BE LENTON
FORM SAVERS BY ERICO, IAPMO UES ER 0129. MECHANICAL COUPLERS MAY BE
USED IN LIEU OF LAP SPLICING REINFORCING BARS ONLY WHERE SPECIFICALLY
APPROVED BY THE SEOR
4. WELDING OF REINFORCEMENT SHALL BE WITH LOW HYDROGEN E90XX
ELECTRODES FOR WELDING ASTM A615 BARS AND E80XX ELECTRODES FOR
WELDING ASTM A706 BARS TO OTHER A706 BARS. WELDING OF A706 BARS
TO A36 OR A572 STEEL SHALL BE WITH E70XX ELECTRODES ALL WELDING SHALL
BE IN CONFORMANCE WITH AMERICAN WELDING SOCIETY, AWS-D1.4. ONLY
WELDERS SPECIFICALLY CERTIFIED FOR REINFORCING STEEL AND IN ACCORDANCE
WITH AWS D1.4 SHALL PERFORM WELDING OF REINFORCING STEEL.
5. DRAWINGS SHOW TYPICAL REINFORCING CONDITIONS. CONTRACTOR SHALL
PREPARE DETAILED PLACEMENT DRAWINGS OF ALL CONDITIONS SHOWING
QUANTITY, SPACING, SIZE, CLEARANCES, LAPS, INTERSECTIONS AND COVERAGE
REQUIRED BY STRUCTURAL DETAILS, APPLICABLE CODE AND TRADE STANDARDS.
CONTRACTOR SHALL NOTIFY REINFORCING DEPUTY INSPECTOR OF ANY
ADJUSTMENTS FROM TYPICAL CONDITIONS THAT ARE PROPOSED IN PLACEMENT
DRAWINGS TO FACILITATE FIELD PLACEMENT OF REINFORCING STEEL AND
CONCRETE.
6. ALL REINFORCING BAR BENDS SHALL BE MADE COLD. RE-BENDING OF REINFORCING
IS NOT PERMITTED.
7. WELDED WIRE REINFORCEMENT (WWR) SHALL CONFORM TO ASTM A1064. MINIMUM
LAP OF WELDED WIRE FABRIC SHALL BE 12 INCHES, OR ONE FULL MESH PLUS TWO
INCHES, WHICHEVER IS GREATER.
8. REINFORCING SPLICES SHALL ONLY BE MADE AS INDICATED ON THE DRAWINGS.
9. DOWELS BETWEEN FOOTINGS AND WALLS OR COLUMNS SHALL BE THE SAME
GRADE, SIZE AND SPACING AS THE VERTICAL REINFORCING, RESPECTIVELY,
UNLESS NOTED OTHERWISE.
10. DOWELS BETWEEN SLABS AND WALLS OR COLUMNS SHALL BE THE SAME GRADE,
SIZE AND SPACING AS THE VERTICAL REINFORCING, RESPECTIVELY, UNLESS
NOTED OTHERWISE.
11. ALL BARS SHALL BE MARKED SO THEIR IDENTIFICATION CAN BE MADE WHEN THE
FINAL IN-PLACE INSPECTION IS MADE.
12. CONTRACTOR SHALL PROVIDE FOR AN ALLOWABLE OF 5 TONS OF REINFORCING
TO BE FABRICATED AND PLACED DURING PROGRESS OF WORK AS MAY BE
DIRECTED BY THE STRUCTURAL ENGINEER. THE UNUSED PORTION SHALL BE
CREDITED TO THE GOVERNMENT AT THE COMPLETION OF THE CONCRETE WORK.
13. PROVIDE 3/8" STITCH BOLTS AND STITCH PLATE TO MATCH GUSSET PLATE x 4" SQ
AT 2'-0" AND 2'-0" MINIMUM FROM ENDS AT ALL DOUBLE ANGLE MEMBERS.
ALTERNATIVELY IN LIEU OF STITCH BOLTS, PROVIDE 3/16" FILLET WELD TO EACH
ANGLE (4 SIDES).
METAL DECK
1. THE STEEL DECKING SHALL BE OF TYPE AND GAUGE AS CALLED FOR ON THE
DRAWINGS MANUFACTURED BY ASC STEEL DECK (IAPMO UES ER 0329 AND IAPMO
UES ER 0161) OR VERCO DECKING, INC (IAPMO UES ER 2018) OR APPROVED
EQUAL. DECKING AND ALL ACCESSORIES SHALL BE FORMED FROM STEEL
SHEETS HAVING A MINIMUM YIELD STRENGTH OF AS DEFINED IN THE PRODUCT
APPROVAL REPORTS. GALVANIZED DECK SHALL CONFORM TO ASTM A653 OR A1063
AND SHALL BE ZINC-COATED CONFORMING TO ASTM A525, MINIMUM CLASS G60.
PAINTED DECKS SHALL CONFORM TO ASTM A1008 OR A1039.
2. DECK LAYOUT SHALL PROVIDE ALL DECK SHEETS OF SUFFICIENT LENGTH TO
EXTEND CONTINUOUSLY OVER AT LEAST 3 SPANS WHERE POSSIBLE. DECK
SPANNING OVER FEWER THAN 3 SPANS SHALL HAVE THE MINIMUM VERTICAL
AND DIAPHRAGM CAPACITY OF THE THREE SPAN CONDITION (INCREASING
THE DECK GAUGE OR SHORING THE DECK MAY BE NECESSARY).
3. MINIMUM BEARING OF DECKING ON SUPPORTS SHALL BE 2 INCHES. SHEETS SHALL
BE ATTACHED TO ALL SUPPORTING STEEL MEMBERS BY WELDING AS INDICATED ON
DRAWINGS AND IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
UPON COMPLETION OF ERECTION, ALL WELDS IN EXPOSED DECK AREAS SHALL HAVE
TOUCH-UP, DE-SLAG, CLEAN AND PRIME WITH A ZINC RICH PRIMER. DECK
WELDING SHALL BE AS NOTED ON PLANS. WHERE NO WELDING IS NOTED, THE
SIDE LAP OF EACH PANEL SHALL BE FASTENED BY 1 INCH LONG FILLET WELDS AT
3 FEET ON CENTER MAXIMUM, OR BUTTON PUNCHED AT 18 INCHES ON CENTER.
4. SEE DRAWINGS FOR DETAIL OF REINFORCING OF DECK OPENINGS. SEE
ARCHITECTURAL, MECHANICAL, ELECTRICAL DRAWINGS, ETC., FOR SIZE AND
LOCATION OF REQUIRED OPENINGS.
5. ALL WELDING OF STEEL DECK SHALL BE IN COMPLIANCE WITH AWS D1.3 AND SHALL
BE PERFORMED BY LIGHT GAUGE WELDERS CERTIFIED BY THE GOVERNING
JURISDICTION.
6. HANGERS SUPPORTED BY METAL DECKING ONLY OR METAL DECKING WITH
INSULATING FILL SHALL BE ATTACHED TO STEEL BARS, 3/8" ROUND X 12" OR 1/8"
x 1 1/2" x 12" FLAT, PLACED PERPENDICULAR TO FLUTES. ONLY LIGHT
DUCTWORK (12" X 16" MAX.), PIPING (1 1/2" ROUND PIPING MAX), OR CEILINGS
MAY BE HUNG FROM SUCH INSTALLATIONS. HANGERS MUST BE TWO FLUTES APART
WHERE THEY OCCUR ON THE SAME SPAN.
7. HANGERS SUPPORTED BY METAL DECK WITH STRUCTURAL CONCRETE FILL SHALL BE
INSTALLED USING ICC APPROVED ANCHORAGE SYSTEMS. SUCH HANGERS SHALL BE
USED TO SUPPORT DUCTWORK (54" X 16" MAX.), PIPING (4" ROUND MAX.), OR
CEILINGS, HANGERS MUST BE AT LEAST TWO FLUTES APART ON SAME DECK SPAN.
LARGER DUCTWORK AND PIPING SHALL BE SUPPORTED BY STRUCTURAL BEAMS OR
COLUMNS.
8. ALL METAL DECK WITH CONCRETE FILL SHALL BE VENTED.
MASONRY (CONCRETE BLOCK)
1. MASONRY CONSTRUCTION SHALL COMPLY WITH THE REQUIREMENTS OF
TMS 402-16.
2. CONCRETE BLOCK SHALL BE HOLLOW LOAD-BEARING CONCRETE MASONRY
UNITS CONFORMING TO C90 MEDIUM WEIGHT. USE DOUBLE OPEN END
UNITS EXCEPT AT EXPOSED END USE SINGLE OPEN END BLOCK USE BOND BEAM
UNITS AT HORIZONTAL REINFORCING. MINIMUM COMPRESSIVE STRENGTH OF
BLOCKS AS REQUIRED TO MEET SPECIFIED COMPRESSIVE STRENGTH OF
MASONRY (f'm) SPECIFIED IN THE CONSTRUCTION DOCUMENTS.
3. SPECIFIED COMPRESSIVE STRENGTH OF MASONRY, f'm, SHALL BE 2500 PSI
AT 28 DAYS, TYPICAL UNLESS NOTED OTHERWISE.
4. DEPUTY INSPECTOR SHALL VERIFY SPECIFIED COMPRESSIVE STRENGTH OF
MASONRY IN ACCORDANCE WITH ONE OF THE FOLLOWING METHODS AS
ALLOWED BY AND DEFINED IN SECTION 2105 OF THE CALIFORNIA BUILDING
CODE:
PRISM TEST METHOD FOR f'm 2000 PSI
5. CEMENT SHALL CONFORM TO ASTM C150, TYPE I OR TYPE II, LOW ALKALI.
6. MORTAR MIX SHALL CONFORM TO THE ASTM C270 REQUIREMENTS FOR
TYPE S. MORTAR SHALL ATTAIN A MINIMUM COMPRESSIVE STRENGTH AS
REQUIRED TO MEET THE SPECIFIED COMPRESSIVE STRENGTH OF
MASONRY (f'm). IN NO CASE SHALL THE COMPRESSIVE STRENGTH OF THE
MORTAR BE LESS THAN OF 2500 PSI AT 28 DAYS.
7. PROVIDE GROUT COMPLYING WITH ASTM C476 ATTAINING A MINIMUM
COMPRESSIVE STRENGTH AS REQUIRED TO MEET THE SPECIFIED
COMPRESSIVE STRENGTH OF MASONRY (f'm). IN NO CASE, THE
COMPRESSIVE STRENGTH OF THE GROUT SHALL BE LESS THAN 2500 PSI
AT 28 DAYS.
8. ADMIXTURES OR "SIKA GROUT AID" SHALL BE ADDED TO GROUT PER
MANUFACTURER'S RECOMMENDATIONS.
9. PROVIDE A MINIMUM OF ONE BAR DIAMETER (1/2 INCH MINIMUM) GROUT
BETWEEN MAIN REINFORCING AND MASONRY UNITS.
10. PROVIDE A MINIMUM OF ONE BAR DIAMETER (1 INCH MINIMUM) GROUT
BETWEEN PARALLEL BARS.
11. MAXIMUM GROUT POUR HEIGHT SHALL COMPLY WITH SECTION 3.2.1 AND
TABLE 3.2.1 OF TMS 402/602-16 BUILDING CODE REQUIREMENTS FOR
MASONRY STRUCTURES.
12. ALL CELLS IN CONCRETE BLOCKS SHALL BE FILLED SOLID WITH GROUT,
UNLESS NOTED OTHERWISE.
13. CELLS SHALL BE IN VERTICAL ALIGNMENT. DOWELS IN FOOTINGS AND
FLOORS SHALL BE SET TO ALIGN WITH CELLS CONTAINING REINFORCING
STEEL AND SHALL MATCH THE SIZE OF THE WALL REINFORCING.
14. REFER TO ARCHITECTURAL DRAWINGS FOR SURFACE AND HEIGHT OF
UNITS, LAYING PATTERN, AND JOINT TYPE.
15. IF WORK IS STOPPED FOR AN HOUR OR LONGER, PROVIDE HORIZONTAL
CONSTRUCTION JOINT PER TYPICAL DETAILS AND BY STOPPING GROUT
1 1/2" BELOW TOP OF MASONRY UNIT.
16. USE STACK BOND
DATE SIGNED:
S H
A N E
S . F I T Z G E R A L
D
No. 4757RE
GI
ST
ERED PROFESSIONAL ENGINE ER
S T A T E O F C A L I F O R N I A
S
T R U C T U R A
L
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10/31/2023
A u to d e s k D o c s /0
-1
-0
V
A W
L A
-C C
C
C U
P S it e
U ti ls
R e n o o f_
B
/6
-2 -1
.6
.S
T R
U .r v t
/1
/2
:4
:3
P
M
S001
GENERAL NOTES
LEO A DALY COMPANY
LOS ANGELES, CA 90071
(213) 629-0100
PARI TIVAY
JOHN A MARTIN & ASSOCIATES
950 S GRAND AVENUE, SUITE 400
LOS ANGELES, CA 90015
(213) 483-6490
SHANE FITZGERALD, SE
WEST LA MEDICAL CENTER
NEW BOILER PLANT
WEST LOS ANGELES, CA
691-20-150
10/31/2023
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
550 SOUTH HOPE STREET, 27TH FLOOR
STRUCTURAL:
Revisions: Date:
Revision 2 Date 2
ADDENDUM 2 08/19/2024
W x2
3/
4>
W x2
W8x10
W8x10
W12x16
W8x10
W x4
W x4
W x3
1/ 4>
W x2
W x4
W x2
W24x55
2 3
D
C
C.1
B
5.3 5.7 7.34
6 7 8
8.1
FUTURE CUP
R-1
W16x26
W8x31
W 8x
W 8x
W 8x
W 8x
W16x26
W8x31
W 8x
W8x67
D-1
303' - 4"
TOC ELEV =W
x3
1/
4>
R -1
W x1
A
TOD ELEV=
TOD ELEV=
S
LO
P E
D
N
C.8
C.5
C.3
8.2
HSS COL
BEL PER
(4 TOTAL)
B9
S501
R-1
W12x16
S701
D1STAIR
PLAN
D N
301' - 7 1/2"
301' - 10 3/4"
301' - 10 1/4"
TOD ELEV=
301' - 7 1/2"
TOD ELEV=
SLOPE DN
301' - 11 1/4"
TOD ELEV=
E9
S501W14x22
W14x22
C3
S503
TYP
TYP
E1
S503 F9
S503
F1
S503
3.9
W 8x
C.7
1"
8' - 6 1/2" 2' - 4"
3/
4>
W 8x
W 8x
W 8x
W 8x
HSS4x2x1/4 ABV
TYP (12 TOTAL)
SEE B9
S504
W8x10
S701 F4
STAIR
PLAN
D N
F3B
S010
F9
S008
OH
F3A
S010
F3A
S010
OH
E7
S008
TYP
C3
S505
TYP
10 3/8"
F3B
S010
C5
S505
OH
W 8x
W 8x
W8x31
MAX
15' - 10 1/2"
M C
6x
.1
4' - 3 1/2" 5' - 3" 9' - 4" 4' - 9"
E9
S504
4' - 7"
2' - 0"
B1
S504
W8x31
E7
S008
TYP
B7
S504
F9
S008
F3B
S010
OH
LO
E O
D
/2
B9
S503
TYP B7
S503
TYP SPLICE TYP
PER E7
S007
F9
S008
TYP AT
BEAM
E1A
S010
EDGE OF
DECK
B5
S504
TYP AT
BEAM
1'
/2
E O
D 7"
B5
S503
TYP AT
WALL
S505 E7
S505 E3
S505
E3 OH
S505 E3
TYP
1' - 4"
<3/4>
C7
S505
E9
S402
B1
S009
C1
S009
TYP
TYP
W12x14
W12x14
TYP UNO
C3
S009
C7
S505C1
S009
C7
S505
SIM
SIM
E1B
S010
E9
S402
SLOPE 1/4:12 MAX
SEE ARCH
W x1
D-2
10' - 7 1/2"
FOM
F O
M
FOM
FOM
F O
M
F O
M
C
C
C1
C1
3' - 6"
1' - 0"
12' - 8"
1' - 0"
B3
S603
TYP
304' - 0"
TOG ELEV
2' - 0"
W 8x
EQ EQ
302' - 1 1/2"
TOS ELEV=
HSS6x3x3/8 FLAT
(HI)
D-1
INDICATES TOP OF STRUCTURAL CONCRETE
SLAB ELEVATION
INDICATES BOTTOM FLANGE BRACE. SEE
DETAIL F5D/S006. LEADING ARROW INDICATES
LOW END OF BRACING. PLACE BRACES
EQUALLY BETWEEN PERP BEAMS UNO
INDICATES CANTILEVERED CONNECTION. SEE
DETAILS C1/S006 AND C3/S006
INDICATES DRAG BEAM CONNECTION. SEE
SPECIFIC SECTION DETAILS.
INDICATES BENT BEAM. SEE DETAIL B1/S007
HATCHED AREA INDICATES SLAB DEPRESSION,
SEE E1 & E3/S009 AND ARCH DRAWINGS
FOR EXACT LOCATION.
INDICATES CONCRETE CURB. SEE
ARCHITECTURAL DRAWINGS FOR EXACT
LOCATION AND EXTENT.
INDICATES BEAM BOTTOM FLANGE BRACING
PER F5/S006
HATCHED AREA INDICATES CONCRETE PADS
SEE ARCHITECTURAL AND MECHANICAL
DRAWINGS FOR LOCATION AND SEE C1/S010.
EL. 0'-0"
1. REFER TO AND CHECK WITH ARCHITECTURAL DRAWING,
DIMENSION FOR ROOF SLOPE. GUTTERS, VENTS, DRAINS,
SADDLES, ETC,. AND DIMENSIONS NOT SHOWN.REFER TO
AND CHECK WITH MECHANICAL DRAWING, FOR DUCTS
OPENING, EQUIPMENT SIZE AND LOCATION ETC. LOCATE
SUPPORT MEMBERS ACCORDINGLY.
2. FOR GENERAL NOTES AND TYPICAL DETAILS, SEE SHEET
S001 THRU S015
3. VERIFY ALL FINISH FLOOR ELEVATIONS WITH
ARCHITECTURAL DRAWINGS.
4. FOR NON-FRAME COLUMN SCHEDULE SEE S301
5. TOP OF STRUCTURAL STEEL SHALL BE 5 1/2" BELOW TOP OF
STRUCTURAL SLAB. TYPICAL UNLESS NOTED OTHERWISE
THUSLY (-5 1/2").
6. WHEN POURING CONCRETE FILL, SHOOT SLAB LEVEL WITH
A TRANSET. SEE DETAIL B5/S007
7. BEAMS SHALL BE EQUALLY SPACED ACROSS Wx GIRDER, UNLESS SHOWN OR NOTED OTHERWISE ON PLANS.
8. BEAMS FRAMING AROUND INTERIOR SLAB OPENINGS THAT
ARE NOT LOCATED ON GRID OR DIMENSIONED ON PLAN
SHALL BE CLEAR 10" FROM EDGE OF SLAB.
9. FRAMING FOR OPENINGS IN FLOOR OR ROOF NOT SHOWN
ON FRAMING PLAN USE TYPICAL DETAILS ON S011 AS
APPROPRIATE.
PLAN NOTES
PLAN LEGEND
<7/8>
[20]
R-1
SYMBOL INDICATES W2 FORMLOK 18 GA. METAL
DECK WITH 3 1/2" THICK NORMAL WEIGHT CONC
FILL OVER TOP OF FLUTES (5 1/2" TOTAL) WITH
#4@16" EACH WAY, TYPICAL U.N.O. (1" CLEAR
FROM TOP OF SLAB). 10'-6" MAX. CLEAR SPAN
FOR 2 SPANS MIN., 9'-0" MAX CLEAR SPAN FOR
SINGLE SPAN. SHORE AS REQUIRED.
DECK WELDING:
4-1/2"Ø EFFECTIVE PUDDLE WELDS PER SHEET
PER SUPPORT. 3/4"Ø PUDDLE WELDS @ 12" @
MARGINS, BUTTON PUNCH @ 12".
SYMBOL INDICATES W2 FORMLOK 18 GA. METAL
DECK WITH 3 1/2" MIN - 5 1/2" MAX THICK
NORMAL WEIGHT CONC FILL OVER TOP OF
FLUTES 8'-0" MAX. CLEAR SPAN FOR 2 SPAN
MIN. REINF, WELDING ETC PER DECK TYPE D-1
SYMBOL INDICATES PLN3 18 GA. METAL
DECK. 11'-2" MAX. SPAN.
DECK WELDING:
4-1/2"Ø EFFECTIVE PUDDLE WELDS PER SHEET
PER SUPPORT. 3/4"Ø PUDDLE WELDS @ 12" @
MARGINS, BUTTON PUNCH @ 12".
INDICATES NUMBER OF 3/4"Ø WELDED STUDS
BOLTS OVER WIDE FLANGE BEAM. REFERENCE
DETAIL F5B/S010 FOR TYP SPACING OF STUDS
UNO ON PLAN
INDICATES CAMBER IN Wx BEAM (INCHES
UPWARD) MEASURED AT MID-SPAN FOR BEAMS
WITH SUPPORTS AT BOTH ENDS, MEASURED AT
FREE END OF CANTILEVERS.
D-2
DATE SIGNED:
S H
A N E
S . F I T Z G E R A L
D
No. 4757RE
GI
ST
ERED PROFESSIONAL ENGINE ER
S T A T E O F C A L I F O R N I A
S
T R U C T U R A
L
N TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10/31/2023
A u to d e s k D o c s /0
-1
-0
V
A W
L A
-C C
C
C U
P S it e
U ti ls
R e n o o f_
B
/6
-2 -1
.6
.S
T R
U .r v t
/1
/2
:4
:3
P
M
S113
FRAMING PLAN LEVEL 2 AND LOW
ROOF OVERALLLEO A DALY COMPANY
LOS ANGELES, CA 90071
(213) 629-0100
PARI TIVAY
JOHN A MARTIN & ASSOCIATES
950 S GRAND AVENUE, SUITE 400
LOS ANGELES, CA 90015
(213) 483-6490
SHANE FITZGERALD, SE
WEST LA MEDICAL CENTER
NEW BOILER PLANT
WEST LOS ANGELES, CA
691-20-150
10/31/2023
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
550 SOUTH HOPE STREET, 27TH FLOOR
STRUCTURAL:
SCALE: 1/8" = 1'-0"
E1
FRAMING PLAN LEVEL 2 OVERALL
4'
SCALE : 1/8" = 1'-0"
0 8' 16'
Revisions: Date:
Revision 2 Date 2
ADDENDUM 2 08/19/2024
D-1 W x8
1/ 4>
W x8
1/ 4>
W x8
1>
W12x14 W12x14
W12x14 W12x14
W x8
1/ 2>
W x8
1/ 4>
W x8
1>
W x8
1/ 4>
W24x76 W24x55 W24x146 W24x68
D
C
C.1
5.3 5.7 7.3
C.6
W12x14
W12x14
316' - 6 5/8"
TOC ELEV =
TOC ELEV =
S
LO
P E
D N
W x8
1/ 2>
W x8
1/ 2>
W x8
1/ 2>
W x8
1/ 2>
W x8
1>
W x8
/4
W x8
1/ 4>
W x8
/4
W14x43
W8x10
W8x10
HSS8x8x5/16
COLS ABV
TYP UNO
W12x14
W 8x
W14x43
W x4
1/ 2>
315' - 4 1/2"
W x1
W12x14
W12x14 C.4
W x2
W12x14
W12x14
W12x14
E9
S501
W24x55
C9
S302
C7
S302
C5
S302
C3
S302 W12x14 W12x14W12x14
W12x14 W12x14
3.9
W12x14
W12x14W12x14
W12x14
C9.5
8.47.9
2'
/2
C.7
W16x61
W14x22
S701
F2STAIR
PLAN
F5
S302
F3
S302
F9
S302
F7
S302
ADD 3-#6
IN SLAB
76' - 0"
W12x14
W12x14 W12x14
W12x14W12x14
W16x61
W12x14
8' - 10"
8' - 10 1/2" 9' - 10"
18' - 8 1/2"11' - 3 1/2"1' - 7 1/2"
6' - 7 1/2"6' - 3 1/2"7' - 5 3/4"7' - 5 3/4"8' - 7"8' - 5"8' - 9"4' - 8"9' - 8" 7' - 0"10' - 3"8' - 11"9' - 10"7' - 8"
EOD
6"
W12x14
9' - 0"
E O
D
1/ 2"
3'
E O
D 6"
E O
D 6"
7' - 0"
W12x14
W12x14
W12x14
W x1
W x1
W x1
W12x14
W12x14
W12x14
W x1
W12x14W12x14
W12x14
W12x14
W12x14
W x1
W x1
W12x14
W x1
W12x14
W12x14
W x1
W12x14
W12x14
W12x14
W12x14
W12x14
W12x14
W12x14 W12x14 W12x14 W12x14
W x1
W x1
W12x14
W x1
W x1
W12x14
W12x14W x1
W12x14
W12x14
W12x14
W x1
W12x14
W x1
W12x14
W12x14
ADD #5@12"
E1A
S010
OH W/#5
DOWELS
@8"
F9
S008
TYP @ BM
E9
S402
E9
S402
E5
S503
S505 B7
E1B
S010
B3
S505
B5
S505
TYP 3
SIDES
E1A
S010
TYP
F9
S008
OH
TYP
@ BM
S504 C3
TYP
4'
" E9
S503
TYP 3
SIDES
10' - 0"
E O
D 5"
B1
S503
E7
S007
TYP
W12x14 W12x14
W12x14
HSS5x4x1/2 FLAT (LO)HSS5x4x1/2 FLAT (LO)
T Y
P 1'
/2
3'
"8'
7'
9'
4'
TYP
W12x14
W12x14
TYP
W12x14 W12x14
2"
2"
2"
2"
2"
W x1
ACC1 MAX
OP WT =
1,750 LBS
PLAN LEGEND
INDICATES TORSION CONNECTION, SEE DETAIL F5/S006
SYMBOL INDICATES W2 FORMLOK 18 GA.
METAL DECK WITH 3 1/2" THICK NORMAL
WEIGHT CONC FILL OVER TOP OF FLUTES
(5 1/2" TOTAL) WITH #4@16" EACH WAY,
TYPICAL U.N.O. (1" CLEAR FROM TOP OF
SLAB). 10'-6" MAX CLR SPAN FOR 2 SPANS MIN,
9'-0" MAX CLR SPAN FOR SINGLE SPAN.
SHORE AS REQUIRED.
DECK WELDING:
4-1/2"Ø EFFECTIVE PUDDLE WELDS PER
SHEET PER SUPPORT. 3/4"Ø PUDDLE WELDS
@ 12" @ MARGINS, BUTTON PUNCH @ 12".
INDICATES OPENINGS IN CONC SLAB ON
DECK TYP UNO SEE SHEET S011
INDICATES FALL PROTECTION SYSTEM PER
DETAIL E1/S504.
HATCHED AREA INDICATES CONCRETE PADS
SEE ARCHITECTURAL AND MECHANICAL
DRAWINGS FOR LOCATION AND SEE C1/S010.
D-1
1. REFER TO AND CHECK WITH ARCHITECTURAL DRAWING,
DIMENSION FOR ROOF SLOPE. GUTTERS, VENTS, DRAINS,
SADDLES, ETC,. AND DIMENSIONS NOT SHOWN. REFER TO
AND CHECK WITH MECHANICAL DRAWING, FOR DUCTS
OPENING, EQUIPMENT SIZE AND LOCATION ETC. LOCATE
SUPPORT MEMBERS ACCORDINGLY.
2. FOR GENERAL NOTES AND TYPICAL DETAILS, SEE SHEET
S001 THRU S016
3. VERIFY ALL FINISH ROOF ELEVATIONS WITH
ARCHITECTURAL DRAWINGS.
4. Wx BEAM WEBS TO BE PERPENDICULAR TO DECK (UNO)
5. TOP OF STRUCTURAL STEEL SHALL BE 5 1/2" BELOW TOP OF
STRUCTURAL SLAB. TYPICAL UNLESS NOTED OTHERWISE
THUSLY (-5 1/2").
PLAN NOTES
D
C.6
D-1
W x2
W x2
W x1
W12x19
319' - 0"
TOC ELEV
C1
S501
E9
S503
TYP 3
SIDES
B3A
S505
ELEVATOR MACHINE
BEAMS BY ELEVATOR
SUPPLIER
C9.5
8.47.9
C1
S505
E O
D 7"
EOD
7"
EOD
7"
E O
D
/2
"CMU WALL
BEL
W x3
W x3
C1
S505
DATE SIGNED:
S H
A N E
S . F I T Z G E R A L
D
No. 4757RE
GI
ST
ERED PROFESSIONAL ENGINE ER
S T A T E O F C A L I F O R N I A
S
T R U C T U R A
L
N TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10/31/2023
A u to d e s k D o c s /0
-1
-0
V
A W
L A
-C C
C
C U
P S it e
U ti ls
R e n o o f_
B
/6
-2 -1
.6
.S
T R
U .r v t
/1
/2
:4
:3
P
M
S114
FRAMING PLAN ROOF OVERALL
LEO A DALY COMPANY
LOS ANGELES, CA 90071
(213) 629-0100
PARI TIVAY
JOHN A MARTIN & ASSOCIATES
950 S GRAND AVENUE, SUITE 400
LOS ANGELES, CA 90015
(213) 483-6490
SHANE FITZGERALD, SE
WEST LA MEDICAL CENTER
NEW BOILER PLANT
WEST LOS ANGELES, CA
691-20-150
10/31/2023
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
550 SOUTH HOPE STREET, 27TH FLOOR
STRUCTURAL:
SCALE: 1/8" = 1'-0"
E1
FRAMING PLAN ROOF OVERALL 4'
SCALE : 1/8" = 1'-0"
0 8' 16'
SCALE: 1/8" = 1'-0"
B6
MACH ROOM FLOOR FRAMING PLAN
Revisions: Date:
Revision 2 Date 2
PLAN LEGEND
INDICATES ORDINARY MOMENT CONNECTION
SYMBOL INDICATES PLN3 VERCO DECK (3"
TOTAL) 11'-0" MAX.
DECK WELDING:
4-1/2"Ø EFFECTIVE PUDDLE WELDS PER
SHEET PER SUPPORT. 3/4"Ø PUDDLE WELDS
@ 12" @ MARGINS, BUTTON PUNCH @ 12".
R-1
1. REFER TO AND CHECK WITH ARCHITECTURAL DRAWING,
DIMENSION FOR ROOF SLOPE. GUTTERS, VENTS, DRAINS,
SADDLES, ETC,. AND DIMENSIONS NOT SHOWN. REFER TO
AND CHECK WITH MECHANICAL DRAWING, FOR DUCTS
OPENING, EQUIPMENT SIZE AND LOCATION ETC. LOCATE
SUPPORTS MEMBER ACCORDINGLY.
2. FOR GENERAL NOTES AND TYPICAL DETAILS, SEE SHEET
S001 THRU S016
3. VERIFY ALL FINISH ROOF ELEVATIONS WITH
ARCHITECTURAL DRAWINGS.
4. TOP OF STRUCTURAL STEEL SHALL BE 1 1/2" BELOW TOP OF
STRUCTURAL METAL DECK. TYPICAL UNLESS NOTED
OTHERWISE THUSLY (-1 1/2").
5. FOR BALANCE OF NOTES, SEE SHEET S112
PLAN NOTES
D
C
C.6 C.6
INDICATES EDGE
OF BLDG BELOW
16' - 8" 18' - 9" 19' - 11" 20' - 5" 17' - 0"
HSS6x4x1/4 FLAT
HSS4x4x1/4
M F
M F
M F
M F
MFMF
R -1 S
LO
P E
D N
TOS EL
TOS EL
329' - 5 1/2"
MFMF
329' - 1"
W x3
CMU PARAPET BELOW SEE
ARCH AND ELEVATIONS
E5
S503
TYP
(5 TOTAL)
HSS8x 8x
5/
TYP (1
TOTAL)
HSS6x4x1/4 FLAT HSS6x4x1/4 FLAT HSS6x4x1/4 FLAT
(GALV) TYP
F5
S503
HOIST BM
(LO)W8x35
C9.5
8.47.9
R -1
HSS6x4x1/4 FLAT HSS6x4x1/4 FLAT HSS6x4x1/4 FLAT HSS6x4x1/4 FLAT
MFMF
MFMF
M F
M F
M F
M F
FOM
F O
M
FOM
4'
1'
E O
D 7"
2' - 0" 7' - 0"
E O
D 7"
EOD
11 1/2"
B1
S505
OH TYP
4 SIDESSLOPE
12' - 11"
2'
18' - 8 1/2"
/2
W8x35
HOIST BM
(LO)
E O
D 1'
E
O D
7"
EOD
7"
EOD
7"
B1
S505
TYP
4 SIDES
F O
M
EOD
7" W12x14
W12x14
W12x14
W12x14 (-2")
(-2")
(2")
(G
ALV
(GALV) HI & LO (GALV) HI & LO
(GALV) HI & LO (GALV) HI & LO
(GALV) HI & LO
(GALV) HI & LO
(GALV) HI & LO
(GALV) HI & LO
E3
S504
DATE SIGNED:
S H
A N E
S . F I T Z G E R A L
D
No. 4757RE
GI
ST
ERED PROFESSIONAL ENGINE ER
S T A T E O F C A L I F O R N I A
S
T R U C T U R A
L
N TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10/31/2023
A u to d e s k D o c s /0
-1
-0
V
A W
L A
-C C
C
C U
P S it e
U ti ls
R e n o o f_
B
/6
-2 -1
.6
.S
T R
U .r v t
/1
/2
:4
:3
P
M
S115
FRAMING PLAN HIGH ROOF
OVERALLLEO A DALY COMPANY
LOS ANGELES, CA 90071
(213) 629-0100
PARI TIVAY
JOHN A MARTIN & ASSOCIATES
950 S GRAND AVENUE, SUITE 400
LOS ANGELES, CA 90015
(213) 483-6490
SHANE FITZGERALD, SE
WEST LA MEDICAL CENTER
NEW BOILER PLANT
WEST LOS ANGELES, CA
691-20-150
10/31/2023
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
550 SOUTH HOPE STREET, 27TH FLOOR
STRUCTURAL:
SCALE: 1/8" = 1'-0"
E1
FRAMING PLAN HIGH ROOF OVERALL 4'
SCALE : 1/8" = 1'-0"
0 8' 16'
Revisions: Date:
Revision 2 Date 2
CONC OVER METAL
DECK PER PLAN, TYP
600T150-54 TRACK
W/ #10 SMS EA FLG
EA STUD
600S162-54 @ 16"
ELEV MACHINE ROOM
FINISH PER ARCH
ROOF
(VARIES)
HIGH ROOF
+330' - 0"
M A
X
WF BEAM PER PLAN
TYP
ROOFING AND INSULATION
PER ARCH
B5
S505
CURB AND STUD
BASE CONN PER
DECK DIRECTION
VARIES - SEE PLAN
3/16
AT
REBAR
1/2"⌀x24" NELSON
DEFORMED BAR ANCHOR
OR #4x24" REBAR @18"
SEE PLAN
EOD
DECK DIRECTION
VARIES - SEE PLAN
S505 B1
CONC OVER METAL
DECK PER PLAN
WF BEAM PER PLAN
3/
4" M
IN
3"
L6x4x5/16 EA SIDE OF HSS
W/ 3/4"⌀ A307 THRU BOLT
CENTERED IN 2 1/2" LONG
SLOTTED HOLE
HSS POST
PER PLAN
1/4
TYP
1/
4"
CLOSURE PL
PER
TYP
E5
S010
TYP
1 1/2"
TYP
1/2" MAX
1/4
TYP
1/4
TYP
L4x4x3/8 x 0'-6" (GALV)
TYP
1/4
TYP
OMIT FRAMING ON
ONE SIDE AT END COL
CAP PL3/8" (GALV)
TYP
PL3/8" x 0'-6"
(GALV) TYP
CONN PER
TYP CONC OVER METAL
DECK PER PLAN
HSS COL PER PLAN
TYP
CAP PL3/8"
HSS COL PER PLAN
HSS BM PER PLAN
Wx BM PER PLAN
S E
E A
R C
H
6" M
IN
HSS BM
PER PLAN
ROOFING PER ARCH
SCREEN PER
ARCH
SCREEN
PER ARCH
E5
S504
PERP BM WHERE
OCCURS (NOT SHOWN
FOR CLARITY) TYP
6"
BOT OF SCREEN
C1
S503
TOP OF SCREEN
C1
S503
TYP
TYP
ALIGN TOP OF COL
W/TOP OF SCREEN
(TYP)
6"
TYP
3"
TYP
1 1/2"3/4"⌀ A307 BOLTS
(GALV) TYP
(2) 5/8"Ø HEADED BOLTS
x 10" EFF EMBED (4" GA)
Wx BM PER PLAN
CMU WALL TYP REINF NOT
SHOWN FOR CLARITY
2" MAX NON-
SHRINK GROUT
3-#3 HAIRPINS @ 3"
EMBED PL1"x WIDTH OF WALL W/ 6-#8 A706 WELDED BARS x 72" MIN
POCKET AS REQ'D NON-SHRINK
GROUT AFTER BEAM IS IN PLACE AND
GROUT SET UNDER BEARING PL
5/16
BEARING PL1/2"
2'
LAP SPLICE WITH TYPICAL WALL
REINFORCEMENT
1/4
T Y
P
4"
MIN
4"
CJP & FILLET
TYP
PL1/2"
5/16
TYP
M
IN
1/
2" T
Y P
1/
2" 3"
TYP
1/2"
TYP
2"
TYP
3"
TYP
3"
Wx BM PER PLAN
5/16
TYP
TYP
1/2" GAP
3" TYP
3" TYP
2" TYP
M
IN
1/
2" M
IN
1/ 2"
T Y
P 3"
1'
M
IN
DRAG BEAM
PER PLAN, TYP
PL1/2" W/ (10) 7/8"⌀
A325 SC BOLTS, TYP
2"
CONN PL3/8" W/ (3) 7/8"Ø
SC BOLTS
(2) 5/8"Ø
HEADED BOLTS
Wx BM
PER PLAN
LAP SPLICE
4' - 6" MIN
CMU WALL TYP REINF NOT
SHOWN FOR CLARITY
2" MAX GROUT
(3) #3 HAIRPINS
@ 3"
EMBED PL1" x WIDTH OF WALL x 8" W/ (2) #7 A706
WELDED BARS
TYP
1 1/2"
5/16
Wx BM PER PLAN Wx BM PER PLAN Wx BM PER PLANFULL DEPTH CONN
PER
TYP
C3
S006
METAL DECK
PER PLAN
CONN PER
SIM
Wx HOIST BM
PER PLAN
Wx HOIST BM
PER PLAN
SIM
C3
S006
MAX
1/2"
CL OF HORIZ
LEG & SPLICE
ELEVATION B1B SECTION B1A
600T150-54
SHOT PIN
@ 16" TYP
C.1
PLAN
SEE
B1B
1/2"x24" NELSON
DEFORMED ANCHOR
OR #4x24" REBAR @ 18"
@ REBAR
3/16
PLAN
SEE
SIM W/
(6) BOLTS
1/4 3
B1A
EOD
L4x4x1/4 2 EACH
BEAM FS
STUD CONN TO
HSS BELOW
TOS
SEE ARCH
HSS PER PLAN
SEE 'B1B' FOR
SPLICE
GLAZING OR
LOUVER PER
ARCH
B1
S505
C3
S006
C.1
362S162-54 @ 16" W/
(2) #10 SCREWS EACH
END
362S162-54 @ 16"
L2x2x43MIL W/ #10 SCREWS
EACH LEG EACH STUD / JOIST
TYP
362T150-54 W/ #10 SCREWS
EACH FLANGE EACH JOIST
& 1/4" TAPCON ANCHORS
@ 16" TO CMU WALL
600T150-97 W/ #10
SCREW EACH FLANGE
EACH STUD @16" TO HSS
600S162-54 @ 16"
1 1/2" FLANGE BRAKE
TRACK W/ #10 EACH
FLANGE EACH STUD
#10 @ 16" E7
S008
1 1/2" FLANGE BRAKE TRACK
W/ #10 EA FLANGE EA STUD &
#10 SCREWS @16"
HSS BM PER PLAN 1"
PLAN
SEE
EOD
400T150-62 W/
#10 SCREWS EA
FLANGE EA STUD
400S162-54 @ 16"
L2x2x43MIL W/ #10
SCREWS EA LEG EA
STUD/ JOIST, TYP
162S125-33 @ 16"
250S162-54 @ 16"
W/ (2) #10 SCREWS
EA END
CONT 68MIL
PL W/ #10
SCREWS @
16" EA END
L3x3x97MIL W/
#10 @ 16" TYP
250S162-54
@16" TYP
(2) #10
CONT BENT PL 2"x11" (LLH) x 118 MIL
L1 1/2"x1 1/2"x68MIL @ 16" W/
(2) #10 SCREWS EA LEG.
LOCATE ANGLE AT CENTER
OF DECK LOW FLUTE
PAF @ 16"
FLANGE 1 1/2"x54 MIL BRAKE TRACK
W/ #10 SCREWS EA FLANGE EA JOIST
ROLL UP DOOR
PER ARCH
250T150-54 W/
(2) #10 @ 8"
A
TYP
1/2"
MAX
1"
BLOCKING PER
'E5B/S012'
(4) #10 EA STUD
(2) #10 EA FLUTE
(4) TOTAL 1"
E5
S012
TYP
1/2" MAX
BEAM PER PLAN
1" NON-SHRINK
GROUT
3/4"Ø AB @ 16"
NOTE:
FOR ITEMS NOT
NOTED SEE B7
S503
A
DATE SIGNED:
S H
A N E
S . F I T Z G E R A L
D
No. 4757RE
GI
ST
ERED PROFESSIONAL ENGINE ER
S T A T E O F C A L I F O R N I A
S
T R U C T U R A
L
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10/31/2023
A u to d e s k D o c s /0
-1
-0
V
A W
L A
-C C
C
C U
P S it e
U ti ls
R e n o o f_
B
/6
-2 -1
.6
.S
T R
U .r v t
/1
/2
:4
:3
P
M
S503
SECTIONS AND DETAILS
LEO A DALY COMPANY
LOS ANGELES, CA 90071
(213) 629-0100
PARI TIVAY
JOHN A MARTIN & ASSOCIATES
950 S GRAND AVENUE, SUITE 400
LOS ANGELES, CA 90015
(213) 483-6490
SHANE FITZGERALD, SE
WEST LA MEDICAL CENTER
NEW BOILER PLANT
WEST LOS ANGELES, CA
691-20-150
10/31/2023
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
550 SOUTH HOPE STREET, 27TH FLOOR
STRUCTURAL:
SCALE: 1" = 1'-0"E9 SECTION
SCALE: 1" = 1'-0"C3 SECTION
SCALE: 1" = 1'-0"C1 GIRT TO HSS COL
SCALE: 3/4" = 1'-0"E5 SECTION
SCALE: 1" = 1'-0"E1 SECTION
SCALE: 1" = 1'-0"F9 CONNECTION DETAIL
SCALE: 1" = 1'-0"F1 DRAG BEAM CONN TO CMU WALL
SCALE: 1" = 1'-0"F5 ELEVATOR HOIST BEAM ELEVATION
SCALE: NONEB1 SECTION
SCALE: NONEB5 SECTION
SCALE: NONEB7 SECTION
SCALE: NONEB9 SECTION
Revisions: Date:
Revision 2 Date 2
3.7 KLF MAX
BLAST LOAD
3.7 KLF MAX
BLAST LOAD
1/4
TYP
HSS PER ELEV
LOUVER BY OTHERS
INTERIOR FACE OF
CMU WALL
PL1/2" W/ (4) 3/4"Ø
ANCHORS E
M B
E D
8"
T Y
P 2"
T Y
P 3"T Y
P
1/ 2"
CMU WALL
PER ELEV
MAX LOAD = 15 KIP (LRFD)
1/
2"
3"
1/
2"
PL3/8" EA SIDE W/ (2)
1/2"⌀ A307 THRU BOLTS
5/16
TYP
1/4
5/16
PJP
45°
CAP PL3/8"
2"
1'
M A
X
3/4"Ø U-BAR (50 KSI)
EYE ATTACHMENT
CONC OVER METAL
DECK PER PLAN
Wx BM
PER PLAN
Wx BM
PER PLAN
PIPE 4 STD, MITER AS
REQ'D TO COMPENSATE
FOR ROOF SLOPE
2"
FULL HEIGHT
STIFF PL
PER
T Y
P 2"
T Y
P 3"T Y
P
1/ 2"
CMU WALL
PER ELEV
1/4
TYP
LOUVER BY OTHERS
E M
B E
D 8"
1" C
LR
PL 3/8"x6" EACH SIDE
W/ (2) 3/4"Ø A307 BOLTS AND
STD WASHERS, CENTERED
IN 13/16"x2 1/2" VERTICAL
SLOTTED HOLE, HAND
TIGHTEN & SPOIL THREADS
PLAN
SECTION
4"
INTERIOR FACE OF
CMU WALL
PL1/2" W/ (4) 3/4"
ANCHORS
9"
A
LEVEL 2
C
E1
S010
HILTI KH-EZ 3/8"x3 1/4"
EMBED @ 16"
1 1/2" FLANGEx54 MIL BRAKE
TRACK W/ #10 EACH FLANGE
EACH JOIST
400S162-54 @ 16"
TOD = 301 ' 10 1/2"
B7
S503
NOTE:
FOR ITEMS NOT
NOTED SEE
C.1
PAF @ 16"
B5
S503
C.1
E7
S008
B5
S503 BM PER PLAN
POST PER
PLAN
6"
B9A
S504
C3
S012
400S162-54 @ 16"
C.1
C
6"
AB CL
CMU WALL (REINF
NOT SHOWWN)MAX
1'-0"
1/2"
1/4 4
BASE PL
3/4"x10 SQ 3/4" AB
AB CL
B9
S505
C5
S504
C.1C
SIM W/ (6) BOLTS
@ BEAM BEYOND
FULL DEPTH STIFF
PL @ BEAM BEYOND
BEAM BEYOND
1" NON-SHRINK
GROUT
PILASTER
C1
S006
C3
S006
TWO SETS OF TYP
TIES WITHIN TOP 4"
OF PILASTER
1/4
3 SIDES
TYP
T Y
P
1/ 2"
T Y
P 3"T Y
P
HSS BM
PER ELEV
HSS BM
PER ELEV
(2) 1/2"Ø A307
THRU BOLTS,
TYP
L6x4x3/8 (LLV) x WIDTH OF
VERT HSS TYP EA SIDE
1'
TYP
1 1/2"
Wx BM
PER PLAN
HSS COL
PER PLAN
PL1 1/4"x BM FLG WIDTH
W/ (4) 3/4"Ø A325 BOLTS
SECTION
1/4
HSS OR PIPE
COLUMN SEE
PLAN
Wx BM
PER PLAN
PIPE COLUMN
E5A
S504
STIFF PL
PER C1
S006
CL OF POST & SPLICE
SPLICE WHERE
OCCURS AT
CONTRACTOR'S
OPTION. LOCATE
SPLICE @ CL OF
POST BELOW
1/2" MAX
1/4
SECTION B9A
1/4
TYP EA
FACE
HSS PER
PLAN (TYP)
(E)
DATE SIGNED:
S H
A N E
S . F I T Z G E R A L
D
No. 4757RE
GI
ST
ERED PROFESSIONAL ENGINE ER
S T A T E O F C A L I F O R N I A
S
T R U C T U R A
L
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10/31/2023
A u to d e s k D o c s /0
-1
-0
V
A W
L A
-C C
C
C U
P S it e
U ti ls
R e n o o f_
B
/6
-2 -1
.6
.S
T R
U .r v t
/1
/2
:4
:4
P
M
S504
SECTIONS AND DETAILS
LEO A DALY COMPANY
LOS ANGELES, CA 90071
(213) 629-0100
PARI TIVAY
JOHN A MARTIN & ASSOCIATES
950 S GRAND AVENUE, SUITE 400
LOS ANGELES, CA 90015
(213) 483-6490
SHANE FITZGERALD, SE
WEST LA MEDICAL CENTER
NEW BOILER PLANT
WEST LOS ANGELES, CA
691-20-150
10/31/2023
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
550 SOUTH HOPE STREET, 27TH FLOOR
STRUCTURAL:
SCALE: 3/4" = 1'-0"C7 SECTION
SCALE: 3/4" = 1'-0"C1 TYPICAL STEEL CONNECTION
SCALE: NONEC9 SECTION
SCALE: NONEB1 SECTION
SCALE: NONEB5 SECTION
SCALE: NONEB7 SECTION
SCALE: NONEB9 SECTION
SCALE: NONEE9 SECTION
SCALE: NONEC3 SECTION
SCALE: NONEC5 SECTION
SCALE: 1 1/2" = 1'-0"E7 SECTION
Revisions: Date:
Revision 2 Date 2
SCALE: 3/4" = 1'-0"E5 CARRIED COLUMN DETAIL
SCALE: 1 1/2" = 1'-0"E3 HSS TO HSS CONN DETAIL
2 2
2" BEARING
SEE PLAN
600T150-54 W/ #10
EACH FLANGE EACH
STUD
600S162-54 @ 16"
CONT BENT PL 1/4"
3/16 1 1/2-12
EOD
METAL DECK
PER PLAN
WF BEAM
PER PLAN
GRID
C7
S013
B1
S505
CMU WALL
PER PLAN
SEE ARCH
SEE PLAN FOR
DECK DIRECTION
DK CONT WHERE
OCCURS
SEE ARCH
COLUMN BEYOND
C1
S010
C7
S013
C7
S008
B1
S505
1" NON-SHRINK
GROUT
1 3/4" 3 1/2"
CL OF BEAMCL OF BOLT
5/8"Ø AB @ 8"
LEVELING NUT
ELEVATOR MACHINE
BM AND CONNECTION
TO RF BM BY ELEVATOR
SUPPLIER
FOW
C.1
F9
S008
MAX
1' - 0"
B9
S505
PLAN
SEE
FOR ITEMS NOT
NOTED SEE
PLAN
SEE
STIFF PL 3/8"
C.1
MACHINE RM SLAB @
DETAIL "3A" ONLY
SEE12" CMU LINTEL
W/ #5 @ 16" EA
FACE EA WY
(2) 3/4"Ø AB @ 4"
GA (6 TOTAL)
5/16
PL 5/8"x7"
5"
7"
C7
S008
C3
S006 C3
S505
SLOPE PER
ARCH
GUARDRAIL
POST PER ARCH
L6x6x3/8 W/ 3/4"⌀
AB @24"
#4 DOWELS @ 16"
SEE PLAN
FOR DECK
DIRECTION
1" C
LR
4"
1'
GRID
INV SOLID GRT
AFTER BM IS
INPLACE
CMU WALL.
REINF NOT
SHOWN
E7
S007
3.9
C.1
CMU WALL
REINF NOT
SHOWN, TYP
BM PER
PLAN, TYP
E9
S505CMU WALL, REINF
NOT SHOWN, TYP
GRID
C.1
CL OF
BM & COL
BASE PL 3/4"x11"
SQ W/ (4) 1/2" AB
CL OF
BEARING
PL & WALL
FACE PL 1/2"x5" W/
(2) #6x4'-6" WELDED
REBARS
BEARING PL 3/4"x11"
W/ (2) 3/4" WELDED
HEADED BOLTS
BM PER
PLAN
C9
S505
1/4
GRID
C.1
(2) #6 (4 TOTAL)
#4 TIES @ 8"
WALL WHERE
CONTINUES
OMIT HK @ EXTEND
BARS WHERE WALL
CONTINUES
JAMB BAR
Ls
GRID
(2) #4 TIES
WITHIN TOP 4"
WELDED REBARS
CMU WALL REINFNOT
SHOWN
PILASTER
INVPERP BM NOT
SHOWN FOR
CLARITY
1" NON-SHRINK GRT
5/16
C3
S006
E3
S007
DATE SIGNED:
S H
A N E
S . F I T Z G E R A L
D
No. 4757RE
GI
ST
ERED PROFESSIONAL ENGINE ER
S T A T E O F C A L I F O R N I A
S
T R U C T U R A
L
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
10/31/2023
A u to d e s k D o c s /0
-1
-0
V
A W
L A
-C C
C
C U
P S it e
U ti ls
R e n o o f_
B
/6
-2 -1
.6
.S
T R
U .r v t
/1
/2
:4
:4
P
M
S505
SECTION AND DETAILS
LEO A DALY COMPANY
LOS ANGELES, CA 90071
(213) 629-0100
PARI TIVAY
JOHN A MARTIN & ASSOCIATES
950 S GRAND AVENUE, SUITE 400
LOS ANGELES, CA 90015
(213) 483-6490
SHANE FITZGERALD, SE
WEST LA MEDICAL CENTER
NEW BOILER PLANT
WEST LOS ANGELES, CA
691-20-150
10/31/2023
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
550 SOUTH HOPE STREET, 27TH FLOOR
STRUCTURAL:
SCALE: NONEB1 SECTION
SCALE: NONEB3 SECTION
SCALE: 3/4" = 1'-0"B5 SECTION
SCALE: 3/4" = 1'-0"C1 PLAN
SCALE: NONEB7 SECTION
SCALE: NONEB9 SECTION
B3A
SCALE: 3/4" = 1'-0"C3 PLAN
SCALE: 3/4" = 1'-0"C5 SECTION
SCALE: 3/4" = 1'-0"C7 SECTION
SCALE: 3/4" = 1'-0"E9 SECTION
SCALE: 3/4" = 1'-0"E7 SECTION
SCALE: 3/4" = 1'-0"E3 SECTION
SCALE: 3/4" = 1'-0"E5 SECTION
SCALE: 3/4" = 1'-0"C9 SECTION
Revisions: Date:
Revision 2 Date 2
| GENERAL |
| GI000 - COVER SHEET |
| STRUCTURAL |
| S001 - GENERAL NOTES |
| S113 - FRAMING PLAN LEVEL 2 AND LOW ROOF OVERALL |
| S114 - FRAMING PLAN ROOF OVERALL |
| S115 - FRAMING PLAN HIGH ROOF OVERALL |
| S503 - SECTIONS AND DETAILS |
| S504 - SECTIONS AND DETAILS |
| S505 - SECTION AND DETAILS |