repost-70-08 Structural DWGs BP E rev.pdf
PDF 6 MB Posted
- Solicitation number
- 36C10F20R0091
About this file
This document package includes structural drawings and notes for a federal construction project along with a related federal contract opportunity notice.
The structural drawings and notes provide specifications for constructing cooling towers, including requirements for drilled pier foundations, concrete mix designs and placement, formwork, reinforcing steel, structural steel, welding, and inspection. The federal contract opportunity is a special notice for construction of a Central Utility Plant project located at the Dallas VA Medical Center campus. The notice indicates that Solicitation Number 36C10F20R0091 will be released for an unrestricted procurement and advises contractors to monitor the beta.sam.gov website for posting of the solicitation and any additional special notices related to the pre-proposal site visit date.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL
1. THIS PROJECT DESIGN MEETS THE REQUIREMENTS OF:
2009 INTERNATIONAL BUILDING CODE
UFC 4-023-03 w/ CHANGE 1 27JAN2010
DEPARTMENT OF VETERANS AFFAIRS INSTRUCTIONS TO ARCHITECTS AND ENGINEERS
DEPARTMENT OF VETERANS AFFAIRS SEISMIC DESIGN REQUIREMENTS H-18-8 JULY 2010
2. DETAILS SHALL BE ASSUMED TO APPLY TO ALL LOCATIONS TO WHICH THEY CAN BE APPLIED REGARDLESS OF
THE LACK OF A TYPICAL NOTATION.
3. THE GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS SHOWN ON THE STRUCTURAL DRAWINGS WITH THE ARCHITECTURAL DRAWINGS. THE CONTRACTOR SHALL VERIFY DIMENSIONS, BEFORE CONSTRUCTION AND NOTIFY THE RESIDENT ENGINEER OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE WORK.
THE FOLLOWING DATA WAS USED IN THE DESIGN OF THE SUBJECT STRUCTURE:
ROOF LIVE LOAD = 20 PSF (UNREDUCED)
GROUND SNOW LOAD = 5 PSF
IN AREAS WHERE THE REQUIRED LOADING EXCEEDS THE TYPICAL LOADING LISTED ABOVE THE FOLLOWING
LOADS ARE USED:
UPS AND OTHER FIXED EQUIPMENT=DESIGNED FOR EQUIPMENT WEIGHT
WIND LOAD:
BASIC WIND SPEED = 90 MPH (3 SECOND GUST)
WIND IMPORTANCE FACTOR=1.15
WIND EXPOSURE C
GCpi = ±0.18
DESIGN LOADS FOR COMPONENTS AND CLADDING SHALL BE BASED ON ASCE 7-05
EARTHQUAKE DESIGN DATA:
SEISMIC OCCUPANCY CATEGORY IV, I =1.50
S = 0.113 S = 0.049
SITE CLASS C (TO BE VERIFIED BY GEOTECH)
S = 0.090 < 0.167 S = 0.055 > 0.067
SEISMIC DESIGN CATEGORY A
BASIC SEISMIC FORCE RESISTING SYSTEMS ARE:
STEEL SYSTEM SPECIFICALLY NOT DETAILED FOR SEISMIC RESISTANCE
SEISMIC BASE SHEAR = 0.01W
ANALYSIS PROCEDURE IS INDEX FORCE ANALYSIS PER ASCE 7 SECTION 11.7.2.
4. CONSTRUCTION LOADS SHALL NOT EXCEED THE DESIGN LIVE LOAD OF THE STRUCTURE. PROVIDE
ADEQUATE SHORING AND/OR BRACING AS REQUIRED DURING CONSTRUCTION.
5. THE STRUCTURAL CONSTRUCTION DOCUMENTS, SPECIFICATIONS AND GENERAL NOTES REPRESENT THE IN PLACE FINISHED STRUCTURE. THEY DO NOT INDICATE THE MEANS OR METHODS OF CONSTRUCTION.
THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE AND LIFE SAFETY DURING CONSTRUCTION. SITE VISITS, SUBMITTAL REVIEWS, AND RESPONSES TO CONTRACTOR QUESTIONS BY THE ENGINEER OF RECORD DO NOT INCLUDE INSPECTION OR OBSERVATION OF THE ABOVE.
DS
S
D1
FOUNDATION
1. REFER TO SITE DRAWINGS AND SPECIFICATIONS FOR GENERAL SITE PREPARATION. THESE FOUNDATION SOIL PREPARATION NOTES APPLY TO THE PREPARATION OF SOILS BENEATH BUILDING FOUNDATIONS AND
SLABS, AND GRADE BEAM BACKFILL.
2. FOUNDATION AND SOIL PREPARATION NOTES ARE BASED ON THE GEOTECHNICAL INVESTIGATION REPORT
PREPARED BY TERRACON CONSULTANTS, INC DATED JUNE 18, 2010.
FOUNDATIONS SHALL BE CONSTRUCTED PER THE RECOMMENDATIONS OUTLINED IN THE REPORT.
3. ALL PIERS HAVE BEEN DESIGNED AS CAST IN PLACE STRAIGHT SHAFT REINFORCED CONCRETE DRILLED PIERS
WITHIN THE STRATUM WITH ALLOWABLE CAPACITIES AS FOLLOWS:
NET ALLOWABLE END BEARING PRESSURE = 40,000 psf ALLOWABLE SKIN FRICTION = 8,000 psf
*SKIN FRICTION IS CONSIDERED TO ACT ONLY ON PORTION OF PIER EMBEDDED IN THE BEARING STRATA. COMPLETE
INSTALLATION OF INDIVIDUAL SHAFTS SHOULD BE ACCOMPLISHED WITHIN 8 HOURS OF
INITIATING PENETRATION. PIER HOLES LEFT OPEN LONGER SHALL BE REPENETRATED (WITH GEOTECH APPROVAL) PRIOR TO FILLING WITH CONCRETE. REFER TO 1/S-021 FOR TYPICAL PIER DETAIL. REFER TO THE
GEOTECHNICAL REPORT FOR ADDITIONAL INSTALLATION REQUIREMENTS.
4. DO NOT EXCAVATE A PIER OPENING WITHIN TWO AND A HALF PIER DIAMETERS OF AN ADJACENT PIER UNTIL 24 HOURS
AFTER CONCRETING.
5. GROUNDWATER SEEPAGE WILL LIKELY BE ENCOUNTERED DURING INSTALLATION OF THE PIER SHAFTS. TEMPORARY CASINGS MAY BE REQUIRED. THE CASING SHOULD BE SEATED IN THE BEARING STRATUM WITH ALL WATER AND MOST LOOSE MATERIAL REMOVED PRIOR TO BEGINNING DESIGN PENETRATION. SUFFICIENT HEAD OF PLASTIC CONCRETE SHALL BE MAINTAINED IN THE CASING DURING EXTRACTION. PENETRATION SHALL BE COUNTED ONLY BELOW THE BOTTOM OF THE CASING. THE INSIDE DIAMETER OF THE CASING SHALL BE THE DESIGN PIER DIMENSION.
6. CONCRETE MUST BE PLACED IN THE PIER HOLE WITH A TREMIE TO INSURE A VERTICAL DROP WITHOUT SEGREGATION.
7. THE CROSS SECTION OF THE PIER AT GROUND LEVEL SHOULD NOT BE ENLARGED TO FORM A MUSHROOM UNDER ANY
CIRCUMSTANCES.
8. PIER REINFORCING STEEL SHALL BE PROPERLY POSITIONED WITHIN THE DRILLED SHAFT BY A POSITIVE MEANS EQUAL TO CENTRALIGNER PIER SLEDS MANUFACTURED BY PIERESEARCH, ARLINGTON, TEXAS. SLEDS SHALL BE PLACED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS, BUT NOT FARTHER APART THAN 15 FEET. PROVIDE
MINIMUM 2 LEVELS OF SLEDS PER PIER.
9. PIER EXCAVATIONS SHALL BE INSPECTED BY THE OWNERS TESTING LAB TO CONFIRM THAT FOUNDATIONS ARE PROPERLY
CONSTRUCTED.
CONCRETE
1. BEFORE PLACING CONCRETE REFER TO ALL DRAWINGS APPLICABLE TO THE AREA CONCERNED FOR COORDINATION OF
DETAILS SHOWN, NOTED, OR REQUIRED FOR THE PROPER EXECUTION OF THE WORK.
2. VERIFY SIZE AND LOCATION OF ALL OPENINGS WITH APPLICABLE DRAWINGS AND SCHEDULES. NO STRUCTURAL MEMBER
SHALL BE INTERRUPTED UNLESS SO SHOWN ON THE DRAWINGS.
3. CONCRETE FOR THE VARIOUS PORTIONS OF THE WORK SHALL BE AS FOLLOWS:
PIERS 3000 PSI
BASIN WALLS, 4000 PSI
SLAB, BEAMS, JOIST, AND GIRDERS 4000 PSI
COLUMNS 4000 PSI
4. NO CALCIUM CHLORIDE SHALL BE PERMITTED IN CONCRETE MIXES.
5. ALL CONCRETE EXPOSED TO WEATHER SHALL BE AIR ENTRAINED, REFER TO SPECIFICATION.
6. CONSTRUCTION JOINTS MAY BE USED ONLY WHERE SHOWN ON THE CONTRACTOR'S REVIEWED PLACING DRAWINGS.
ALL CONSTRUCTION JOINTS NOT SHOWN ON THE CONSTRUCTION DOCUMENTS SHALL BE KEYED AND LOCATED AT
MIDSPAN. REINFORCING SHALL BE CONTINUOUS THROUGH THE JOINT.
7. ALL FORMWORK, CONCRETE REINFORCING PLACEMENT, AND CONCRETE PLACEMENT SHALL BE UNDER THE
OBSERVATION OF THE OWNER'S TESTING LABORATORY.
8. THE MAXIMUM SLUMP AND WATER/CEMENT RATIO SHALL NOT BE EXCEEDED.
9. ALL CONCRETE SHALL BE DESIGNED, MIXED, TRANSPORTED, AND PLACED IN ACCORDANCE WITH THE LATEST EDITION OF
THE AMERICAN CONCRETE INSTITUTE'S ACI 301.
10. SLEEVES OR OTHER PENETRATIONS SHALL BE ALLOWED THROUGH STRUCTURAL MEMBERS ONLY WITH PRIOR WRITTEN APPROVAL OF THE STRUCTURAL RESIDENT ENGINEER REGARDLESS OF NOTATION ON OTHER DISCIPLINE'S DOCUMENTS.
THE CONTRACTOR IS TO SUBMIT THROUGH THE RESIDENT ENGINEER TO BEGIN APPROVAL PROCESS.
11. REFER TO THE SPECIFICATIONS FOR SLAB SEALERS AND JOINT FILLERS AND SEALANTS. ALL JOINTS ARE TO BE FILLED.
12. ALL FACES OF ALL GRADE BEAMS AND PLINTHS ARE TO BE FORMED IF THEY ARE TO RECEIVE WATERPROOFING OR
ARCHITECTURAL FINISH.
13. STRUCTURAL RESIDENT ENGINEER APPROVAL IS REQUIRED IN ADVANCE WHEN ADDING WATER TO BATCH WITHHELD AT PLANT. IN SUCH CASE THE MIX DESIGN AND TRUCK TICKET MUST CLEARLY STATE THE AMOUNT OF WATER WITHHELD AND THE MAXIMUM AMOUNT OF WATER PERMISSIBLE TO BE ADDED NOT TO EXCEED THE DESIGN MIX RATIO OF WATER
TO CEMENT CONTENT. REFER TO ACI 304R SECTION 4.5.3.1 AND 4.5.3.2.
14. ANY ITEM TO BE CAST INTO THE CONCRETE SHALL BE REVIEWED AND APPROVED BY THE STRUCTURAL RESIDENT ENGINEER PRIOR TO PLACEMENT IN THE FORMS. THIS REQUIREMENT APPLIES TO ITEMS INDICATED ON PAGE DRAWINGS AS WELL AS ITEMS REQUIRED BY THE CONTRACTOR AND THEIR SUBCONTRACTORS. THIS REQUIREMENT IS INCLUSIVE OF BUT NOT LIMITED TO THE FOLLOWING; BLOCKOUTS OR INSERTS FOR THE CONTRACTOR DESIGNED CONSTRUCTION PHASE FALL PROTECTION SYSTEM, ELECTRICAL CONDUITS, FLOOR DRAINS, JUNCTION BOXES, ETC.. THE CONTRACTOR
IS TO SUBMIT THROUGH THE RESIDENT ENGINEER TO BEGIN APPROVAL PROCESS.
FORMWORK
1. FORMWORK AND THEIR SUBMITTALS SHALL COMPLY WITH ACI 347R, RECOMMENDED PRACTICE FOR
CONCRETE FORMWORK.
2. ANCHOR BOLTS AND EMBEDDED PLATES SHALL BE SET WITH SECURELY FASTENED TEMPLATES.
3. PROVIDE CHAMFER STRIPS IN FORMS AT ALL CORNERS, EXPANSION JOINTS, AND END OF WALLS AND BEAMS.
REF. ARCH.
REINFORCING STEEL
1. ALL DOWEL BARS TO BE BENT IN THE FIELD SHALL CONFORM TO ASTM A615, GRADE 40. ALL OTHER REINFORCING STEEL FOR STRUCTURES SHALL CONFORM TO ASTM A615, GRADE 60. WELDED WIRE FABRIC
SHALL CONFORM TO ASTM SPECIFICATION A185 AND BE PROVIDED IN FLAT SHEETS.
2. ALL REINFORCEMENT SHALL BE DESIGNED AND DETAILED IN ACCORDANCE WITH THE LATEST EDITION OF THE ACI "MANUAL OF STANDARD PRACTICE FOR DETAILING CONCRETE STRUCTURES" (ACI 315)
3. NO MEMBER IS UNREINFORCED. WHERE REINFORCING IS NOT SHOWN, IT SHALL BE DETAILED THE SAME AS A
SIMILAR MEMBER AND FLAGGED ON THE SHOP DRAWINGS FOR VERIFICATION.
4. ALL REINFORCING SHALL BE SECURELY AND ACCURATELY HELD PRIOR TO PLACEMENT OF THE CONCRETE.
5. ALL REINFORCING BAR BENDS SHALL BE MADE COLD. GRADE 60 BARS MAY NOT BE RE-BENT IN THE FIELD.
6. REINFORCEMENT SHALL BE SUPPORTED ON CHAIRS PROVIDING THE MINIMUM CONCRETE COVER SHOWN IN
TABLE 1 SHOWN ON THIS SHEET.
7. SLAB REINFORCING STEEL SHALL BE SUPPORTED BY CHAIRS ONLY. BRICK OR BLOCK SUPPORTS ARE NOT ALLOWED. PROPER ACCESSORIES/SUPPORTS ARE TO BE USED AS NOTED AND APPROVED ON THE SHOP DRAWINGS. PROVIDE GALVANIZED OR PLASTIC COATED CHAIRS AND BAR SUPPORTS AT THE SOFFITS OF ALL
EXPOSED MEMBERS.
8. ALL BAR LENGTHS DETAILED OR SCHEDULED ARE OUT-TO-OUT AND DO NOT INCLUDE HOOKS AND/OR BENDS.
9. WHERE SPLICES ARE NECESSARY, THEY MUST BE MADE AT LOCATIONS SHOWN IN DETAILS OR SCHEDULES.
10. STIRRUPS AND TIES OF THE SIZE AND SPACING DETAILED OR SCHEDULED SHALL BE SET WITH THE
REQUIRED CONCRETE COVER LISTED IN TABLE 1 SHOWN ON THIS SHEET.
11. WHERE SPLICES ARE REQUIRED IN REINFORCING, BARS SHALL BE LAPPED. LAP W.W.F. AT LEAST NINE (9) INCHES.
12. BEAM SPLICES MAY BE MADE WITH MECHANICAL SPLICING COUPLERS IN LIEU OF LAPPING. MECHANICAL COUPLERS SHALL BE "BAR LOCK MBT" OR AN APPROVED EQUAL. LOCATIONS OF COUPLERS MUST BE SUBMITTED TO THE PROJECT STRUCTURAL ENGINEER FOR REVIEW. THE CONTRACTOR IS TO SUBMIT THROUGH THE
RESIDENT ENGINEER TO BEGIN APPROVAL PROCESS
13. ONE HALF OF THE EQUIVALENT OF THE REINFORCEMENT CUT AT SLAB OPENINGS SHALL BE ADDED ON EACH SIDE OF THE OPENINGS SHOWN ON THE PLAN. ANY ADDITIONAL OPENINGS SHALL BE APPROVED BY THE PROJECT STRUCTURAL ENGINEER. PROVIDE 2-#4x4'-0" PLACED DIAGONALLY AT EACH CORNER OF ANY OPENINGS IN THE SLAB, WITH TWO (2) INCHES TO THE FIRST BAR FROM THE CORNER AND AN ADDITIONAL SIX
(6) INCHES TO THE SECOND BAR.
14. DO NOT FIELD BEND ANY REINFORCEMENT FOR ANY REASON EXCEPT AS SPECIFICALLY NOTED ON THE STRUCTURAL
DRAWINGS. TORCH CUTTING AND HEATING OF BARS IS PROHIBITED.
15. PLACE DOWELS MAXIMUM 2" FROM OUTSIDE OF FACE OF SLAB/WALL/BEAM ELEMENT. DOWEL LENGTHS SHALL BE
SUFFICIENT TO DEVELOP BAR CAPACITY WITHIN EACH CONNECTED ELEMENT.
STRUCTURAL STEEL
1. STRUCTURAL STEEL FOR COLUMNS AND BEAMS SHALL BE NEW DOMESTIC STEEL CONFORMING TO ASTM A992 FOR WIDE FLANGE SHAPES, A572 FOR PLATES AND BARS, A500 GR. B FOR HSS, AND A36 FOR CHANNELS, ANGLES, AND ANY OTHER MISCELLANEOUS SECTIONS. MEMBERS AND CONNECTIONS SHALL BE DESIGNED, FABRICATED, AND ERECTED IN ACCORDANCE WITH THE LATEST EDITION OF THE
AISC SPECIFICATIONS.
2. UNLESS OTHERWISE NOTED, ALL BOLTS SHALL BE 3/4" DIAMETER A325-N BOLTS. ALL CONNECTIONS NOT DETAILED SHALL BE "FRAMED BEAM CONNECTIONS" USING 3/4" DIA. A325-N BOLTS AS SHOWN IN THE AISC MANUAL, THIRTEENTH EDITION. BOLTS AT MOMENT CONNECTIONS SHALL BE 3/4" DIAMETER
A325-SC. BOLTS SHALL BE PROOF LOADED IN ACCORDANCE WITH ONE OF THE APPROPRIATE
METHODS APPROVED BY AISC. REFER TO THE SPECIFICATIONS.
3. ALL SHOP CONNECTIONS SHALL BE WELDED, UNLESS NOTED OTHERWISE.
4. ALL WELDING SHALL CONFORM TO THE REQUIREMENTS OF THE AMERICAN WELDING SOCIETY AND THE AISC, AND SHALL BE DONE ONLY BY CERTIFIED WELDERS. WELDER CERTIFICATIONS SHALL BE
AVAILABLE AT THE PROJECT SITE AT ALL TIMES DURING FIELD WELDING WORK.
5. ALL WELDS EXPOSED TO WEATHERING AFTER FINAL CONSTRUCTION SHALL BE GROUND SMOOTH
AFTER WELDING. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PAINTING.
6. ANCHOR BOLTS SHALL BE SET WITH A TEMPLATE AND DOUBLE NUTS TO ENSURE PROPER LOCATION
AND ALIGNMENT. CONTRACTOR SHALL VERIFY ANCHOR BOLT PLACEMENT WITH FINAL ERECTION
DRAWINGS PRIOR TO STEEL FABRICATION.
7. TOLERANCES: ANCHOR BOLTS SHALL BE SET WITHIN 1/8"OF THAT SHOWN ON THE DRAWINGS.
8. FIELD BEAM TO COLUMN CONNECTIONS SHALL BE WELDED AS DETAILED TO DEVELOP THE FULL
MOMENT CAPACITY OF THE BEAM THROUGH THE COLUMN AT CONNECTIONS SO NOTED ON THE
DRAWINGS.
9. PROVIDE BOLTS AND PUNCH HOLES IN STRUCTURAL AND MISCELLANEOUS METAL FOR
ATTACHMENTS/WOOD NAILERS AS REQUIRED ON THE ARCHITECTURAL, MECHANICAL OR STRUCTURAL
DRAWINGS.
10. HOT DIP GALVANIZE ALL STRUCTURAL STEEL EXPOSED TO THE WEATHER.
11. ALL FULL PENETRATION WELDS SHALL BE TESTED.
1. ANY SHOP DRAWING NOT CHECKED AND INITIALED BY THE SUPPLIER/DETAILER PRIOR TO
SUBMITTING FOR ARCHITECTURAL AND ENGINEERING REVIEW, WILL BE RETURNED
WITHOUT REVIEW.
2. THE CONSTRUCTION DOCUMENTS MAY NOT BE REPRODUCED FOR USE AS SHOP DRAWINGS.
SHOP DRAWINGS
3. ELECTRONIC FILES OF CONSTRUCTION DOCUMENTS WILL NOT BE MADE AVAILABLE FOR
USE AS SHOP DRAWINGS.
SPECIAL INSPECTION
1. CONTRACTOR SHALL ENGAGE AN INDEPENDENT QUALIFIED TESTING LAB TO PROVIDE THE CODE REQUIRED
SPECIAL INSPECTIONS.
2. REFER TO THE IBC CHAPTER 17 SECTION 1704 FOR THE SPECIAL INSPECTION REQUIREMENTS FOR
THE TABLES/SECTIONS LISTED BELOW:
SECTION 1704.2: "INSPECTION OF FABRICATORS"
TABLE 1704.3: "REQUIRED VERIFICATION AND INSPECTIONS OF STEEL CONSTRUCTION"
TABLE 1704.4: "REQUIRED VERIFICATION AND INSPECTIONS OF CONCRETE CONSTRUCTION"
TABLE 1704.5.1: "LEVEL 1 SPECIAL INSPECTION"
TABLE 1704.5.2: "LEVEL 2 SPECIAL INSPECTION"
TABLE 1704.7: "REQUIRED VERIFICATION AND INSPECTION OF SOILS"
TABLE 1704.9: "REQUIRED VERIFICATION AND INSPECTION OF PIER FOUNDATIONS"
SECTION 1704.10: "SPRAYED FIRE-RESISTANT MATERIALS"
SECTION 1704.11: "MASTIC AND INTUMESCENT FIRE-RESISTANT COATINGS"
A. CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH................................3 in.
B. FORMED (OR CAST AGAINST VAPOR BARRIER), EXPOSED TO EARTH OR
WEATHER.......................................................................................................................2 in.
C. FORMED, NOT EXPOSED TO WEATHER OR IN CONTACT WITH
GROUND...................................................................................................................1 1/2 in.
D. BEAMS, GIRDERS, COLUMNS...........................................................................1 1/2 in.
E. TOP REINFORCEMENT IN SLABS...........................................................................1 in.
REFER TO DETAILS FOR SPECIAL COVER CONDITIONS.
TABLE 1 - CONCRETE CLEAR COVERS
PLAN LEGEND AND ABBREVIATIONS
SYMBOL DESCRIPTION REMARKS
OPENING IN FLOOR OR ROOF SEE PLANS
MOMENT CONNECTION
AMERICAN SOCIETY FOR TESTING MATERIALS
AMERICAN WELDING SOCIETY
BOTTOM OF DECK
BOTTOM OF FOOTING
BOTTOM OF STEEL
CLEAR
DEGREES
EXPANSION JOINT
FINISHED FLOOR ELEVATION
MASONRY CONTROL JOINT
MAXIMUM
MINIMUM
ON CENTER
SIMILAR
TRENCH INVERT
TOP OF BEAM
TOP OF CONCRETE
TOP OF DRILLED PIER
TOP OF FOOTING
TOP OF JOIST
TOP OF PARAPET
TOP OF STEEL
TOP OF WALL
TYPICAL
UNLESS NOTED OTHERWISE
NOT IN CONTRACT
ON CENTER, EACH WAY
CENTER LINE
NIC
UNO
TYP
TOW
TOS
TOP
TOJ
TOF
TODP
TOC
TOB
TI
SIM
OPPOSITE HANDOH
OCEW
OC
MIN
MAX
EXISTING CONSTRUCTION
MCJ
FFE
EJ
(E)
DEG
DIAMETERDIA/Ø
CLR
BOS
BOF
BOD
AWS
ASTM
SEE FRAMING DETAILS
HEADED STUD ANCHORHSA
AFF ABOVE FINISHED FIRST FLOOR ELEVATION
SPACESPA
EQUALEQ
ELEVATIONEL/ELEV
REINFORCINGREINF
REFERREF
EACHEA
CL/
BOTT BOTTOM
EDGE OF SLABEOS
EDGE OF DECKEOD
SOFT METRIC BAR SIZE
#9
#18
#11
#10
#14
#5
#7
#6
#8
#3
#4
#29
#57
#36
#43
#32
#22
#25
#16
#19
#10
#13
REINFORCING BAR SIZE CONVERSION CHART
INCH-POUND BAR SIZE
NOTE: INCH-POUND BAR SIZE DESIGNATIONS USED THROUGHOUT THE DOCUMENTS.
#8
#9
#5
#7
#6
#4
#3
5'-10" 7'-10"
1'-5"
4'-7"
3'-6"
2'-1"
1'-1"
1'-0"
1'-11"
6'-0"
4'-7"
2'-8"
1'-5"
1'-1"
TABLE 2 - BAR LAP LENGTHS FOR SPLICES
BAR SIZE
SLAB BARS, CORNER BARS
VERTICAL WALL BARS BEAM
BOTTOM BARS
HORIZONTAL BARS WITH
MORE THAN 12" CAST BELOW
(TOP BARS)
NOTE:
1. TABLE IS BASED ON 3" BARS SPACING WITH MINIMUM 1 1/2" COVER AND MINIMUM CONCRETE COMPRESSIVE STRENGTH f'c=5000PSI. FOR f'c=4000PSI, MULTIPLY VALUES BY FACTOR OF 1.12.
FOR f'c=3000PSI, MULTIPLY VALUES BY FACTOR OF 1.3.
2. INCREASE BAR LENGTHS BY 30% FOR LIGHTWEIGHT CONCRETE APPLICATION.
3. FOR VALUES GREATER THAN THOSE INDICATED IN NOTE 1 THE CONTRACTOR CAN USE THE
TABULATED LENGTHS OR OPTIONALLY CAN USE LENGTHS CALCULATED BASED ON ACI318
D A
T E
ST
A
M P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and
Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
C
U se rs \r w e ll s\
D o cu m e n ts
\3 b S-
C o o li n g_
T o w e r-c e n tr a l rw e ll s@ p a ge th in k .c o m
.r v t
/2
/2
:3 :5
P
M
C:\Users\rwells\Documents\309070b2S-Cooling_Tower-central 2018_rwells@pagethink.com.rvt
70-S-010
CONSTRUCTION
STRUCTURAL - TYPICAL ABBREVIATIONS, SYMBOLS, PLAN
NOTES AND GENERAL NOTES
ENERGY CENTER COOLING TOWERS VA
NORTH TEXAS HEALTH CARE SYSTEM
4500 LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR, CENTRAL REGION
02 JUNE 2020
70VA-LTSCIF-D
549-820E
BID PACKAGE E
CL PIER IS CL BEAM OR
WALL UNLESS NOTED
OTHERWISE ON PLAN
TRIPLE AT TOP OF
PIER 2" OC
PIER REINFORCEMENT:
24"Ø: (6)-#7
SHAFT DIAMETER PER
PLAN
BEARING STRATA: GREY,
MODERATELY HARD
SHALE
TOP OF PIER ELEV = BOTT
OF FOUNDATION FRAMING
#3 ROUND TIES AT
12" O.C. W/ 3"
CLEAR COVER
TEMPORARY CASING MAY BE
REQUIRED TO PRECLUDE
GROUNDWATER SEEPAGE.
REFER TO THE GEOTECH
REPORT
P E
N E
T R
A T
IO
N
S
IN
D
IC
A T
E D
BOTTOM OF PIER
T O
B E
D E
T E
R M
IN
E
D B
Y G
E O
T E
C H
N
IC
A L E
N G
IN
E
E
R CLEAN ALL LOOSE
SOILS AT BOTOM OF
DRILLED SHAFT
BEFORE PLACEMENT
OF CONCRETE
CL BEAM
STL BM REF PLAN
STD A.I.S.C. DBL ANGLE CONNX,
TYP UNO (MIN 2 FOR ERECTION)
3/16
3 SIDES
NOTES: ALL FILLET WELDS
SHALL BE 1/8" LESS THAN
THINNEST BASE MATERIAL.
U.N.O
FIELD BOLTS (TYPICAL)
STD. A.I.S.C. DOUBLE ANGLE
CONNX. (TYP. U.N.O)
SHOP BOLTS. (TYPICAL)
ALTERNATE
TO
SHOP
BOLTING
3/4" Ø BOLTS
NOMINAL BEAM
DEPTH "D" IN
INCHES
NUMBER OF ROWS
OF BOLTS
UP TO 7
8-11
12-14
15-17
18-20
21-26
27-29
30-32
33-35
FABRICATOR SHALL TAKE
NECESSARY PRECAUTIONS AGAINST
BOLT SHANK OUT.
FABRICATOR OPTION:
1. PROVIDE THICKER SHEAR PLATE.
2. PROVIDE MULTIPLE WASHERS AT
EITHER END (2MAX PER END)
1' - 6 3/4"
1' - 0 3/8"GRIP LENGTH 1" MIN
SLOPE 1:3
TOOLED EDGE FOR
EXPOSED SLAB
"T
NOTE: PREFORMED 24 GA MIN
COLD KEY MAY BE USED
NOTE: CONSTRUCTION JOINT SHALL BE LOCATED IN THE
MIDDLE THIRD OF THE SPAN BETWEEN SUPPORTS
DOWELS: #4 x 2'-0" @ 18"
OC IN ADDITION TO TYP
SLAB REINF
0.375 "T"
0' - 10 1/4" 0' - 9 1/8"EQUAL EQUAL
1 1/2" SHEAR KEY &
WATER STOP
PROVIDE 48 BAR DIA LAP
*IN LIEU OF LAP SPLICE, LENTON
FORMSAVERS MAY BE USED.
CONTINUOUS
REINFORCING
REF SECTION FOR
CLEAR COVER
3' - 4 1/2"
PREVIOUS POUR NEW POUR
6"
R E
F M
E C
H
NOTE: COORDINATE WITH ARCHITECTURAL AND
MECHANICAL FOR PAD SIZE AND LOCATION.
NOTE: ALL HOUSEKEEPING PADS ON ELEVATED
STRUCTURAL FLOORS SHALL BE LIMITED TO 4" MAX
THICK AND SHALL BE LIGHTWEIGHT CONCRETE.
FACE OF EQUIPMENT
#3 @ 12" OC HOUSEKEEPING
PAD. THICKNESS <=4"
#3 @ 18" OC EW DRILL 4" INTO
SLAB ON GRADE AND PLACE
WITH HIGH STRENGTH, NON-
SHRINK GROUT. OMIT @
ELEVATED SLABS AND PADS
<3" THICK.
#4 @ 12" OC HOUSEKEEPING
PAD. THICKNESS >4"
ROUGHEN SURFACE AND
APPLY BONDING AGENT
1' - 3 1/2" 1' - 3 1/2" 1' - 3 1/2"
D
IA
30 DIA 30 DIA 30 DIA
D
IA
NOTE: FURNISH CORNER BARS AT ALL
BEAMS TO MATCH OUTSIDE FACE
HORIZONTAL REINFORCEMENT
HORIZ REINF
IN BEAMS
0' - 1 7/8"2" 0" 0' - 1 5/8"2" 0"
D A
M P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and
Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
C
U se rs \r w e ll s\
D o cu m e n ts
\3 b S-
C o o li n g_
T o w e r-c e n tr a l rw e ll s@ p a ge th in k .c o m
.r v t
/2
/2
:3 :5
P
M
C:\Users\rwells\Documents\309070b2S-Cooling_Tower-central 2018_rwells@pagethink.com.rvt
70-S-021
CONSTRUCTION
549-820ETYPICAL DETAILS
ENERGY CENTER COOLING TOWERS VA
NORTH TEXAS HEALTH CARE SYSTEM
4500 LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR, CENTRAL REGION
02 JUNE 2020
3/4" = 1'-0" C1
STRAIGHT SHAFT PIER
1" = 1'-0" B3
BEAM CONNX DETAIL (BM ONE SIDE)
3/4" = 1'-0"
B5
BEAM TO BEAM SHEAR CONNECTION
3/4" = 1'-0" B7
BOLT SCHEDULE FOR TYPICAL STEEL CONNECTIONS
3/4" = 1'-0" F1
TYP SLAB CONST AND CONTROL JOINT
3/4" = 1'-0"
F2
WALL CONSTRUCTION JOINT DETAIL
3/4" = 1'-0" F5
HOUSE KEEPING SLAB
3/4" = 1'-0"
F7
TYPICAL CORNER BAR DETAIL
VA-LTSCIF-D
BID PACKAGE E
LOCATOR MAP
D
GE
OF
O
VER
HA
NG
NOT TO SCALE
E. A
NN
ARB
OR
AVE
S L A N C A S T E R
R D
V E T E R A N S
D R
WORK AREA
EXISTING SLAB &
WALL TO REMAIN
F9
70-S-201
TYP
F6
70-S-201
TYP
F3
70-S-201
TYP
F1
70-S-201
TYP
8" THICK SLAB ON GRADE
W/ #4 @ 12" O.C. EA. WAY 2"
FROM TOP OF SLAB
OVER 2'-4" SELECT FILL
OVER SUBGRADE AS PREPARED
FOR PAVING (SEE CIVIL)
PROVIDE 1/2"
COMPR. FILLER
BETWEEN NEW & EXIST.
APPROX. LOCATION
OF EXIST. STORAGE TANK
NEW
BASINS
EXISTING
BASINS
TB
TB
TC
TC
TD
TD
TE
TE
TF
TF
TG
TG
TH
TH
TI
TI
TJ
TJ
TK
TK
T1 T1
T4 T4
T5 T5
T6 T6
TI.9
TI.9
TH.9
TH.9
TL
TL
TG.9
TG.9
TF.9
TF.9
TE.9
TE.9
TD.9
TD.9
TA
TA
T3 T3
T2 T2
14X20 CONCRETE
PLINTHS. PLACE
ON BOTH NEW AND
EXISTING SLABS.
REF DET D5/70-S-201
16' - 0" 16' - 0" 16' - 0" 16' - 0" 16' - 0" 17' - 9" 16' - 5" 16' - 0" 16' - 1"
D8
70-S-201
TYP
6' - 0" 4' - 10" 5' - 7" 5' - 7" 4' - 10" 5' - 7" 5' - 7" 4' - 10" 5' - 8"
DIMENSIONS ARE
TYPICAL FOR ALL NEW
SUMPS.
24"Ø - 4'
24"Ø - 4' 24"Ø - 4'
24"Ø - 4'24"Ø - 4'
24"Ø - 4'
24"Ø - 4'
24"Ø - 4'
24"Ø - 4'
24"Ø - 4'
24"Ø - 4'
24"Ø - 4'
24"Ø - 4'
24"Ø - 4'
24"Ø - 4'
24"Ø - 4'
24"Ø - 4'
24"Ø - 4'
D1
70-S-201
TYP
FIELD VERIFY WALL
LOCATION. MODIFY PLINTH
WIDTHS IF REQUIRED TO
COORDINATE W/ COOLING
TOWER ANCHOR LOCATIONS.
C8
70-S-201
TYP
DEMO EXISTING
WALLS (HATCHED
PER LEGEND)
BETWEEN NEW
COOLING TOWERS
15' - 6"
COOLING TOWER FOOTPRINT
LEGEND
SAFEDECK SLIP-RESISTANT
FIBERGLASS PANELS OR EQ
C
X
.5
C6X10.5
C
X
.5
C
X
.5
C6X10.5
C
X
.5
C
X
.5
C6X10.5
C
X
.5
C6X10.5
C6X10.5
C6X10.5C6X10.5
C6X10.5C6X10.5
C
X
.5
C6X10.5C6X10.5C6X10.5
C6X10.5
C
X
.5
C
X
.5
C6X10.5
C
X
.5
C
X
.5
C6X10.5
C
X
.5
C
X
.5
C6X10.5
C
X
.5
C6X10.5C6X10.5C6X10.5
C
X
.5
D8
70-S-201
TYP
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5 C
X
.5
C6X10.5
C6X10.5
TYP
DEMO EXISTING WALLS
D A
M P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and
Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
FULLY SPRINKLERED
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
C
U se rs \r w e ll s\
D o cu m e n ts
\3 b S-
C o o li n g_
T o w e r-c e n tr a l rw e ll s@ p a ge th in k .c o m
.r v t
/2
/2
:3 :5
P
M
C:\Users\rwells\Documents\309070b2S-Cooling_Tower-central 2018_rwells@pagethink.com.rvt
70-S-101
CONSTRUCTION
549-820ECOOLING TOWER SCREEN & BASIN FRAMING PLAN
ENERGY CENTER COOLING TOWERS VA
NORTH TEXAS HEALTH CARE SYSTEM
4500 LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR, CENTRAL REGION
02 JUNE 2020
BID PACKAGE EBID PACKAGE E BID PACKAGE EBID PACKAGE E
1/8" = 1'-0" E1
COOLING TOWER SCREEN & BASIN FRAMING PLAN
PLAN NOTES:
1. THE LOCATION OF ALL FLOOR PENETRATIONS, DRAINS, SUMPS, ETC. SHALL
BE VERIFIED AND COORDINATED WITH OTHER TRADES. NO OPENING
SHALL INTERFERE WITH STRUCTURAL ELEMENTS UNLESS COORDINATED
WITH RESIDENT ENGINEER IN WRITING.
2. VERIFY OPENING DIMENSIONS PRIOR TO CONSTRUCTION.
3. GENERAL CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO
CONSTRUCTION. NOTIFY RESIDENT ENGINEER IF FIELD CONDITIONS VARY.
4. NO MODIFICATIONS TO THE EXISTING STRUCTURE SHALL BE MADE
WITHOUT WRITTEN APPROVAL FROM THE RESIDENT ENGINEER UNLESS
INDICATED ON THE CONSTRUCTION DOCUMENTS.
5. COORDINATE DIMENSIONS WITH COOLING TOWER MANUFACTURER.
6. VERIFY PLINTH LOCATIONS WITH EXISTING CONDITIONS & MANUFACTURER.
7. REF SPECIFICATIONS FOR BASING COATING REQUIREMENTS.
8. NEW WALLS CENTERED ON GRIDS U.N.O.
9. HOT DIP GALVANIZE ALL EXPOSED STEEL.
10. PROVIDE STAINLESS STEEL FASTENERS/ANCHORS TYP.
NORTH
PLAN
LOCATOR MAP
D
GE
OF
O
VER
HA
NG
NOT TO SCALE
E. A
NN
ARB
OR
AVE
S L A N C A S T E R
R D
V E T E R A N S
D R
WORK AREA
TB
TB
TC
TC
TD
TD
TE
TE
TF
TF
TG
TG
TH
TH
TI
TI
TJ
TJ
TK
TK
T1 T1
T4 T4
T5 T5
T6 T6
TI.9
TI.9
TH.9
TH.9
TL
TL
TG.9
TG.9
TF.9
TF.9
TE.9
TE.9
TD.9
TD.9
TA
TA
W
X
W
X
W12X22
W12X22
W12X22
W12X22
W
X
W12X22
W12X22
W12X22
W12X22
W
X
W12X22
W12X22
W12X22
W12X22
W
X
W12X22
W12X22
W12X22
W12X22
W
X
W12X22
W12X22
W12X22
W12X22
W
X
W12X22
W12X22
W12X22
W12X22
W
X
W12X22
W12X22
W12X22
W12X22
W
X
W16X40
W16X40
W16X40
W16X40
T3 T3
T2 T2
2' - 0" 16' - 0" 16' - 0" 16' - 0" 16' - 0" 16' - 0" 17' - 9" 16' - 5" 16' - 0" 16' - 1" 2' - 0"
1' - 0" 1' - 0" 1' - 0" 1' - 0" 1' - 0" 1' - 0"
19' - 1"34' - 0" 15' - 0" 16' - 0" 16' - 0" 17' - 9" 16' - 5" 16' - 0"
W12X22W12X22W12X22W12X22W12X22W12X22W12X22W16X40
D1
70-S-201
TYP
DECK
SPAN
HATCH INDICATES
APPROXIMATE LOCATIONS OF
PUMPS BELOW. FOR FUTURE
EQ REPLACEMENT REMOVE
ROOF PANELS AS REQUIRED
AND RE-INSTALL AFTER EQ
INSTALLATION.
FUTURE PANEL REMOVAL
FOR EQ REPLACEMENT
LEGEND
D A
M P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and
Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
FULLY SPRINKLERED
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
C
U se rs \r w e ll s\
D o cu m e n ts
\3 b S-
C o o li n g_
T o w e r-c e n tr a l rw e ll s@ p a ge th in k .c o m
.r v t
/2
/2
:3 :5
P
M
C:\Users\rwells\Documents\309070b2S-Cooling_Tower-central 2018_rwells@pagethink.com.rvt
70-S-102
CONSTRUCTION
549-820ECANOPY FRAMING PLAN
ENERGY CENTER COOLING TOWERS VA
NORTH TEXAS HEALTH CARE SYSTEM
4500 LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR, CENTRAL REGION
02 JUNE 2020
BID PACKAGE EBID PACKAGE E BID PACKAGE EBID PACKAGE E
PLAN NOTES:
1. CANOPY DECK IS 24GA 18" TEE-LOCK PANEL OR EQUAL. 2 TEE-LOCK
CONTINUOUS RIB CLIPS ARE PLACED BACK TO BACK ALONG EACH PANEL SEAM
AND SECURED WITH 2 FASTENERS PER RIB FOR A TOTAL OF 4 FASTENERS PER
ATTACHMENT POINT. FASTEN W/ 1/4"-20 5 POINT SELF DRILLING SCREWS.
PROVIDE TEE-LOCK SEAM CAPS W/ VINYL WEATHER SEAL.
2. HATCHED REGION INDICATES ROOF PANELS WHICH CAN BE REMOVED FOR
MAINTENANCE.
3. THE LOCATION OF ALL FLOOR PENETRATIONS, DRAINS, SUMPS, ETC. SHALL BE
VERIFIED AND COORDINATED WITH OTHER TRADES. NO OPENING SHALL
INTERFERE WITH STRUCTURAL ELEMENTS UNLESS COORDINATED WITH
RESIDENT ENGINEER IN WRITING.
4. VERIFY OPENING DIMENSIONS PRIOR TO CONSTRUCTION.
5. GENERAL CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO
CONSTRUCTION. NOTIFY RESIDENT ENGINEER IF FIELD CONDITIONS VARY.
6. NO MODIFICATIONS TO THE EXISTING STRUCTURE SHALL BE MADE WITHOUT
WRITTEN APPROVAL FROM THE RESIDENT ENGINEER UNLESS INDICATED ON THE
CONSTRUCTION DOCUMENTS.
1/8" = 1'-0" E1
PIPE SUPPORT ROOF
NORTH
PLAN
0' - 8" 0' - 10"
T.O.S.G. EL.
SEE PLAN
3-#6 CONT.
TOP & BOT.
2-#6 CONT.
TOP
1-#4 CONT.
OUTSIDE FACE
#4 @ 12" OC
#4 DOWELS
2'-0"X2'-0"
@ 12" OC
CONT CHANNEL W/
1/2"Ø SS @ 2'-0" OC
(EMBED 3 1/4) (KWIK
BOLT TZ OR EQ)
0' - 8" 1' - 0" SEE PLAN 0' - 8" 2' - 0"
/2
/2
0' - 2"0' - 2"
2-#6 CONT.
TOP & BOT;
#3 TIES @ 8" O.C.
SEE PLAN
STEEL GRATING
0' - 1 1/2"
REF SPECIFICATIONS FOR COATING
#4 @ 12" OC EW EF
#4 @ 12" OC EW
#4 @ 12" OC EW
#4 2'-0" X 2'-0" DOWELS @ 12" OC
#4 2'-0" X 2'-0" DOWELS @ 12" OC
CONT SHEAR KEY W/ WATERSTOP, TYP
CONT L1 1/2X1 1/2X 1/4
W/ 1/2"Ø X 6" HEADED
ANCHORS @ 2'-0" OC
#4 @ 12" OC EW
0' - 8" 0' - 8"
SEE PLAN
0' - 2" 0' - 2"
#6 @ 12" O.C.
#4 @ 12" O.C.
#4 @ 12" O.C. EW
#6 2'-6" X 2'-6" DOWELS @ 12" OC
CONT L2 1/2X2 1/2X 1/4
W/ 1/2"Ø X 6" HEADED
ANCHORS @ 2'-0" OC
CONT SHEAR KEY W/ WATERSTOP, TYP
6"
2' - 0"
T.O.S.G. EL.
TO MATCH EXISITING
#5 CONT TOP
#4 CONT HORIZ
(3)- #6 CONT BOTT
#4 2'-3" X 1'-0"
@ 12" OC
CONT SHEAR KEY
W/ WATERSTOP
#4 3'-0" DOWELS
@ 12" OC
T5 T6
1 1/2" NON-SHRINK
GROUT
FINISHED GRADE
12X12X1" BP W/
(4)- 3/4"Ø ANCHORS
1 1/2" 1 1/2"
12X7 1/2X1"
CAP PL W/
(4)- 3/4"Ø
ANCHORS
M
IN
24"Ø PIPE TO BE
SUPPORTED BY
GIRDERS @
EVERY COLUMN
LINE.
REF MECH FOR
PIPE LOCATIONS
1/4
1/4
10' - 0"
H S
S X
X
/4
T Y
P
H S
S X
X
/4
T Y
P
1/4" PL ALONG
SOUTHERN PERIMETER
BEAMS TYP
3/16 3-12
3/16 3-12
3/16
NS&FS TYP
6" PROJ0'
/8
T.O.S.G. EL.
SEE PLAN
3-#6 CONT.
THICKENED SLAB
DRILL & EPOXY #4
DOWELS X 2'-0" @ 12" OC.
EMBED 6"
1' - 6"
EXISTING
CUT CONT SHEAR KEY W/
WATERSTOP INTO EXISTING
CONT CHANNEL W/ 1/2"Ø SS
@ 2'-0" OC (EMBED 3 1/4)
(KWIK BOLT TZ OR EQ)
T.O.C. TO MATCH EXISTING
WALLS TYP
(6)- #5 VERT IN EACH 14"X20"
PLINTH. DRILL & EPOXY IN HILTI
HY-150 (EMBED 6"). #3 STIRRUPS
@ 8" OC TYP
REPAIR/PATCH ANY EXISTING
COATING TO ENSURE BASIN REMAINS
WATER TIGHT.
ANCHOR BOLT AS
REQUIRED BY TOWER
MANUFACTURER
CONT C6X10.5 W/ (3)- 1/2"Ø SS EA PLINTH
(EMBED 3 1/4) (KWIK BOLT TZ OR EQ)
8"
2' - 0"
3-#6 CONT.
T.O.S.G. EL.
TO MATCH EXISTING
1'-6" 1'-6"
#4 @ 12" O.C.
D A
M P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and
Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
C
U se rs \r w e ll s\
D o cu m e n ts
\3 b S-
C o o li n g_
T o w e r-c e n tr a l rw e ll s@ p a ge th in k .c o m
.r v t
/2
/2
:3 :5
P
M
C:\Users\rwells\Documents\309070b2S-Cooling_Tower-central 2018_rwells@pagethink.com.rvt
70-S-201
CONSTRUCTION
549-820ESECTIONS AND DETAILS
ENERGY CENTER COOLING TOWERS VA
NORTH TEXAS HEALTH CARE SYSTEM
4500 LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR, CENTRAL REGION
02 JUNE 2020
BID PACKAGE EBID PACKAGE E BID PACKAGE EBID PACKAGE E
3/4" = 1'-0" F9
SECTION
3/4" = 1'-0"
F6
SECTION
3/4" = 1'-0" F3
SECTION
3/4" = 1'-0"
F1
SECTION
3/4" = 1'-0" D1
CANOPY SECTION
3/4" = 1'-0" C8
SECTION @ EXISTING
VA-LTSCIF-D
3/4" = 1'-0" D5
TYP BASIN PLINTH
3/4" = 1'-0"
D8
THICKENED BASIN SLAB DETAIL
| Sheets |
| 70-S-010 - STRUCTURAL - TYPICAL ABBREVIATIONS, SYMBOLS, PLAN NOTES AND GENERAL NOTES |
| 70-S-021 - TYPICAL DETAILS |
| 70-S-101 - COOLING TOWER SCREEN & BASIN FRAMING PLAN |
| 70-S-102 - CANOPY FRAMING PLAN |
| 70-S-201 - SECTIONS AND DETAILS |
File details come from the government source that posted it. Updated .