264313_Surge_Protection_Devices.pdf
PDF 133 KB Posted
- Attached to
- Volusia County Branch Jail Air Handler-Fire Suppression System Removal, Replacement and Upgrade
- Solicitation number
- 26-B-110IF
- Issued by
- Volusia County, Florida
About this file
This is a technical specification document for surge protection devices (SPDs) issued by Volusia County, Florida for installation at the Branch Jail facility located at 1300 Red John Drive, Daytona Beach. The specification outlines comprehensive requirements for low-voltage electrical power circuit surge protection systems designed to protect the facility's electrical infrastructure against transient voltage surges, including lightning-induced damage. The project requires SPDs for multiple installation locations including service entrance protection, distribution panels, motor control centers, subpanels, and lighting panels, with devices sourced from a single manufacturer. All SPDs must be Type 1 certified to UL 1283 and UL 1449 standards (Fourth Edition), manufactured in the USA by firms with a minimum ten-year history of SPD design and manufacturing, and capable of protecting all voltage modes (L-G, L-N, L-L, N-G) with discrete suppression circuitry. Manufacturers must receive written verification of product acceptance from the specifying engineer at least ten days prior to the bid date of December 5, 2025.
The specification mandates that all surge protection devices include a comprehensive thirty-year manufacturer warranty covering unlimited free replacements if the unit is destroyed by lightning or other electrical transients during the warranty period, with the warranty applying to the entire device rather than individual components. SPDs must meet stringent performance criteria including specific let-through voltage limitations across multiple impulse categories (ANSI/IEEE C62.41 Categories A, B, and C), maximum continuous operating voltage requirements of at least 125 percent for 120V systems and proportionally lower percentages for higher voltage systems, and internal monitoring systems with visual LCD display panels. All devices must include Form C dry contacts for remote monitoring capability, internal audible alarms, NEMA 4 steel enclosures, and comply with applicable provisions of the National Electrical Code, NFPA 70, NFPA 75, NFPA 780, and Canadian Standards. Installation must follow manufacturer guidelines with conductors kept as short and straight as practicable, and all neutral conductors must be bonded to system ground at the service entrance or isolation transformer prior to SPD installation.
View the file
Other files
Show 40 more
Latest 50 of 128 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BID SET VOLUSIA COUNTY
DECEMBER 5, 2025 BRANCH JAIL
SURGE PROTECTION DEVICES FOR 264313.00 - 1
LOW-VOLTAGE ELECTRICAL POWER CIRCUITS
SECTION 264313 SURGE PROTECTION DEVICES FOR LOW-VOLTAGE ELECTRICAL POWER
CIRCUITS
PART 1 - GENERAL
1.1 SUMMARY
A. The specifications in this section describe the electrical and mechanical requirements for a protection system provided by high-energy transient voltage surge suppressors. The specified system shall provide effective, high-energy surge current diversion and but suitable for application in ANSI/IEEE C62.41 Category A, B and C environments (as tested by ANSI/IEEE C62).
1.2 STANDRADS
A. The specified system shall be designed, manufactured, tested, and installed in compliance with the following codes and standards:
1. Institute of Electrical and Electronic Engineers (ANSI/IEEE C62.11, C62,41, C62.45)
2. American National Standards Institute
3. Federal Information Processing Standards Publication 94 (FIPS PUB 94)
4. National Electrical Manufacturer Association (prior to repeal NEMA LS-1 1992 Peak
Current Testing)
5. National Fire Protection Association (NFPA 70, 75 and 780)
6. MIL Standard 220A Method of Insertion Loss Measurement
7. National Electric Code
8. Underwriters Laboratories UL 1283 and UL 1449 (most recent edition)
9. Canadian Standards (cUL or cETL0
1.3 ENVIRONMENTAL REQUIREMENTS
A. The operating temperature range shall be -40° to 70° C (-40° to 160° F)
B. The unit shall be capable of operation up to 13,000 feet above sea level.
C. No appreciable magnetic fields shall be generated.
1.4 SUBMITTALS
A. Product Data: Provide catalog sheets showing voltage, physical size, IEEE let through voltage for each waveform listed, UL1449 latest revision, latest edition, suppressed voltage ratings, dimensions showing construction, lifting and support points, enclosure details, per mode and per phase peak surge current, modes of discrete suppression circuitry, warranty period and replacement terms, conductor size, conductor type and lead length.
B. Submit product data for all components and accessories.
SURGE PROTECTION DEVICES FOR 264313.00 - 2
C. Manufacturer’s Installation Instructions: Indicate application conditions and limitations of use stipulated by product testing agency specified under Regulatory Requirements. Include instructions for storage, handling, protection, examination, preparation, installation, and starting of product.
Indicate maximum size of circuit breaker or fuse to be connected for each unit.
D. List and detail all protection systems such as fuses, disconnecting means and protective features.
E. Provide verification that the SPD device complies with the required UL1449 latest edition, latest revision, and CSA approvals.
F. Provide actual let through voltage test data in the form of oscillograph results for the ANSI/IEEE C62.41 Category C3 & C1 (combination wave) and A1 (ring wave) tested in accordance with
ANSI/IEEE C62.45.
G. Provide spectrum analysis of each unit based on MIL-STD-220A test procedures between 10 kHz and 100 kHz verifying the devices noise attenuation equals or exceeds 40 dB at 100 kHz.
H. Provide test report from a recognized independent testing laboratory verifying the suppressor components can survive published surge current rating on a per mode basis using the IEEE Cc62.41, 8x20 microsecond current wave. Test data must be on a complete SPD with internal fusing in place. Test data on an individual module is not acceptable.
1.5 QUALITY ASSURANCE AND WARRANTY
A. The SPD and supporting components shall be guaranteed by the manufacturer to be free of defects in material and workmanship for a period of thirty (30) years from the date of substantial completion of service and activation of the system to which the suppressor is attached.
Additionally, the warranty shall state that during the applicable warranty period any SPD which fails due to any transient surge activity, including lightning, shall be repaired, or replaced by the manufacturer without charge. Special or optional warranties in excess of the unit’s standard warranty for purposes of this bid are not acceptable.
B. Since “acts of Nature” or similar statements typically include the threat of lightning to which the SPDs shall be exposed, any such clause limiting warranty responsibility in the general conditions of this specification shall not apply to this particular section. That is, the warranty must specifically provide for unlimited free replacements of the SPD in the event of failure caused by the effects of lightning and all other electrical anomalies. The warranty shall cover the entire device, not just various components, such as modules only.
C. Provide electrically operated equipment specified in this Section that is listed and labeled. As defined in the National Electrical Code, Article 100, Listing and Labeling Agency Qualifications:
A “Nationally Recognized Testing Laboratory” as defined in OSHA Regulation 1910.7.
D. Comply with NFPA 70 and Nema LS1.
1.6 MANUFACTURER QUALIFICATIONS
SURGE PROTECTION DEVICES FOR 264313.00 - 3
A. The SPDs shall be manufactured in the USA by a manufacturer that has been regularly engaged in the design, manufacturing, and testing of SPDs of the types and ratings required for a period of not less than ten years. Manufacturers requesting product approval must meet or exceed the written specification contained herein. Manufacturers requesting approval must receive written verification of product acceptance by the specifying engineer 10-days prior to the bid date.
PART 2 – PRODUCTS
2.1 PERFORMANCE
A. GENERAL
1. The SPD shall be listed by ETL, UL, or other nationally recognized test laboratory to UL’s 1283 and UL’s 1449 standards (latest edition, latest revision), and not merely the components or modules. All SPD’s shall be Type 1 for use in Type 1 and Type 2 locations.
2. The SPD shall protect all modes L-G, L-N, L-L, and N-G, have discrete suppression circuitry in L-G, L-N and N-G, and have bidirectional, positive and negative impulse protection. Line-to-neutral-to-ground protection is not acceptable where line-to-ground is specified, and accordingly reduced mode units with suppression circuitry built into only 4 modes are not acceptable. In delta systems, line-to-ground-to-line protection is not acceptable where line-to-line is specified.
3. Obtain all surge suppression devices through one source from a single manufacturer.
4. The maximum continuous operating voltage (MCOV) of all components shall not be less than 125% for a 120V system and 120% for 220 and 240V systems, and 115% for 277 and 480V systems.
5. All SPD’s shall be equipped with a comprehensive monitoring system which shall include a visual LCD panel display providing information on unit status and phase loss/protection loss.
6. All SPD’s shall be Total Protection Solutions.
7. If a disconnect switch is specified, the disconnect switch and the SPD as a system shall be capable of interrupting up to a 200kA symmetrical fault current with 600 VAC applied.
8. Each design configuration shall have the maximum single pulse surge current capacity per mode verified through testing at an independent, nationally recognized test laboratory. To be considered for approval, the manufacturer must submit a test report on a unit which was tested with internal over current fusing in place. The test shall include a
1.2 X 50 µsec 6000V open circuit voltage waveform and an 8 X 20 µsec 500A short circuit current waveform to benchmark the unit’s suppression voltage, followed by a single pulse surge of maximum rated surge current magnitude with an approximated 8 X 20 µsec waveform. To complete the test, another identical surge shall be applied to verify the unit’s survival. Compliance is achieved if the suppression voltages found from the two impulses do not vary by more than +10%. Test data on an individual module is not acceptable.
9. For technical support and ordering information call 407-951-5777 or Toll Free at: 800- 448-4087.
SURGE PROTECTION DEVICES FOR 264313.00 - 4
B. SERVICE ENTRANCE PROTECTION
1. The SPD for this location shall be as indicated on project drawings. SPD shall be separate from panelboard. Integral SPD shall not be acceptable. SPD’s shall be certified to UL1283 and UL 1449 Forth Ed. Type 1 for use in Type 1 or Type 2 locations.
2. The manufacturer shall provide written specifications showing let-through voltage of the unit with six inches of lead length (at the module or at the lug data is not acceptable as it does not represent true "as installed" performance) pursuant to ANSI/IEEE C62.41 and C62.45, 2002, categories C1and C3 bi-wave, 90 degree phase angle, positive polarity, measurements in peak voltage from the zero reference, all dynamic tests except N-G, and UL suppressed voltage ratings, all of which shall be no higher than:
ANSI/IEEE C62.41-1991 Measured Limiting Voltage
B3/C1 Impulse (6kV, 3kA)
Voltage (Voltage Code) L-N L-G L-L N-G
120/208 (3Y208) 725V 726V 1098V 728V
277/480 (3Y480) 1075V 1077V 1718V 1073V
480 delta (480NN) 1616V 1616V
C3 Impulse (20kV, 10kA)
Voltage (Voltage Code) L-N L-G L-L N-G
120/208 (3Y208) 1040V 1420V 1300V 1240V
277/480 (3Y480) 1490V 2290V 1830V 1690V
480 delta (480NN) 2160V 2470V
UL Voltage Protection Ratings
120/208 (3Y208) 800V 800V 1000V 800V
277/480 (3Y480) 1200V 1200V 1800V 1200V
480 delta (480NN) 1800V 1800V
C. DISTRIBUTION PANEL AND MOTOR CONTROL CENTER
PROTECTION
1. SPD(s) for this location shall be as indicated on project drawings. SPD shall be separate from panelboard. Integral SPD shall not be acceptable. SPD’s shall be certified to UL 1283 and UL1449 Forth Ed. Type 1 for use in Type 1 and Type 2 locations.
2. The manufacturer shall provide written specifications showing let-through voltage of the unit with six inches of lead length (at the module or at the lug data is not acceptable as it does not represent true "as installed" performance) pursuant to ANSI/IEEE C62.41 and C62.45, 2002, categories B3/C1 and C3 bi-wave, 90 degree phase angle, positive
SURGE PROTECTION DEVICES FOR 264313.00 - 5
polarity, measurements in peak voltage from the zero reference, all dynamic tests except N-G, and UL suppressed voltage ratings, all of which shall be no higher than:
B3/C1 Impulse (6kV, 3kA)
Voltage (Voltage Code) L-N L-G L-L N-G
120/208 (3Y208) 651V 640V 1041V 646V
277/480 (3Y480) 968V 979V 1792V 967V
480 (480NN) 1689V 1697V
C3 Impulse (20kV, 10kA)
120/208 (3Y208) 970V 1160V 1430V 1100V
277/480 (3Y480) 1540V 1600V 2260V 1550V
480 (480NN) 2760V 2340V
120/208 (3Y208) 700V 700V 1200V 700V
277/480 (3Y480) 1000V 1000V 1800V 1000V
480 (480NN) 1800V 1800V
3. The SPD shall come standard with not less than a Thirty-Year Warranty, and the warranty shall include unlimited free replacements of the unit if destroyed by lightning or other transients during the warranty period. Special or optional warranties in excess of the unit's standard warranty for purposes of this bid are not acceptable.
4. The suppressor shall include Form C dry contacts (N.O. or N.C.) for remote monitoring capability, and shall have at minimum a Nema 4 steel enclosure.
5. The SPD shall have an internal audible alarm with mute on front cover.
D. SUBPANEL AND LIGHTING PANEL PROTECTION
1. SPD(s) for this location shall be as indicated on project drawings. SPD shall be separate from panelboard. Integral SPD shall not be acceptable. SPD’s shall be certified to UL1283 and UL1449 Forth Ed. Type 1 for use in Type 1 and Type 2 locations.
2. The manufacturer shall provide written specifications showing let-through voltage of the unit with six inches of lead length (at the module or at the lug data is not acceptable as it does not represent true "as installed" performance) pursuant to ANSI/IEEE C62.41 and C62.45, 2002, categories A1 & A3 ring wave, 180 degree phase angle, category B3 Ringwave, and UL suppressed voltage ratings, 90 degree phase angle, positive polarity, SURGE PROTECTION DEVICES FOR 264313.00 - 6 measurements in peak voltage from the zero reference, all dynamic tests except N-G, which shall be no higher than:
A1 Ring Wave (2kV, 67A) Tested at 180 degree phase angle
Voltage (Voltage Code) L-N L-G L-L N-G
120/240 (1S240) 29V 46V 39V 40V
120/208 (3Y208) 29V 46V 39V 40V
277/480 (3Y480) 34V 54V 40V 39V
A3 Ring Wave (6kV, 200A) Tested at 180 degree phase angle
120/240 (1S240) 56V 61V 88V 112V
120/208 (3Y208) 56V 61V 88V 112V
277/480 (3Y480) 66V 115V 83V 94V
B3 Ring Wave (6kV, 500A) Tested at 90 degree phase angle
120/240 (1S240) 437V 592V 612V 324V
120/208 (3Y208) 437V 592V 612V 324V
277/480 (3Y480) 670V 785V 1020V 324V
120/240 (1S240) 700V 700V 1000V 700V
120/208 (3Y208) 700V 700V 1000V 700V
277/480 (3Y480) 1200V 1200V 2000V 1200V
PART 3 – EXECUTION
3.1 INSTALLATION
A. Install the SPDs with the conductors as short and straight as practically possible.
B. Follow the SPD manufacturer’s recommended installation practice as outlined in the equipment installation manual. The electrical contractor shall ensure that all neutral conductors are bonded to the system ground at the service entrance or the serving isolation transformer prior to installation of the associated SPD.
SURGE PROTECTION DEVICES FOR 264313.00 - 7
C. Main service entrance units shall be installed on a circuit breaker or disconnect that meets or exceeds the fault current rating of the switchgear.
D. Distribution, branch panel, and motor control center units shall be installed on a dedicated circuit breaker.
E. The installing contractor shall comply with all applicable codes.
END OF SECTION 264313