262813_Fuses.pdf
PDF 116 KB Posted
- Attached to
- Volusia County Branch Jail Air Handler-Fire Suppression System Removal, Replacement and Upgrade
- Solicitation number
- 26-B-110IF
- Issued by
- Volusia County, Florida
About this file
This is a specification document for electrical fuses issued by Volusia County for the Branch Jail facility located at 1300 Red John Drive, Daytona Beach, Florida. The specification section 262813 details the requirements for cartridge fuses rated 600 V ac and less for use in control circuits, motor-control centers, panelboards, switchboards, enclosed controllers, and enclosed switches, along with spare-fuse cabinets. The fuses specified are NEMA FU 1, current-limiting, nonrenewable cartridge fuses of Type T rated at 250-V with zero- to 1200-A rating and 200 kAIC time delay. Bidders must provide product data including construction details, dimensions, electrical characteristics, current-limitation curves, and time-current coordination curves. Installation requires compliance with NFPA 70 standards, with fuses arranged for readable rating information and installed in fusible devices as indicated in project drawings. Maintenance material submittals require furnishing spare fuses equal to 10 percent of the quantity installed for each size and type, with a minimum of three of each size and type, packaged with protective covering and properly labeled.
The specification requires that all fuses be obtained from a single manufacturer source and that electrical components be listed and labeled by a qualified testing agency. Contractors must examine fuses before installation and reject any that are moisture or physically damaged. Spare-fuse cabinets must be wall-mounted steel units with gray baked enamel finish, featuring full-length recessed piano-hinged doors with key-coded cam locks, and exterior identification marking. All fuses must include labels indicating replacement information adjacent to fuse blocks, sockets, and holders in compliance with Section 260553 for electrical systems identification. Ambient temperature adjustment factors must be applied when fuses are directly exposed to temperatures below 40°F or above 100°F, with supporting manufacturer technical data required as part of operation and maintenance documentation submitted in PDF format.
View the file
Other files
Show 40 more
Latest 50 of 128 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BID SET VOLUSIA COUNTY
DECEMBER 5, 2025 BRANCH JAIL
FUSES 262813.00 - 1
SECTION 262813 - FUSES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Cartridge fuses rated 600 V ac and less for use in the following:
a. Control circuits.
b. Motor-control centers.
c. Panelboards.
d. Switchboards.
e. Enclosed controllers.
f. Enclosed switches.
2. Spare-fuse cabinets.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for spare-fuse cabinets. Include the following for each fuse type indicated:
1. Ambient Temperature Adjustment Information: If ratings of fuses have been adjusted to accommodate ambient temperatures, provide list of fuses with adjusted ratings.
a. For each fuse having adjusted ratings, include location of fuse, original fuse rating, local ambient temperature, and adjusted fuse rating.
b. Provide manufacturer's technical data on which ambient temperature adjustment calculations are based.
2. Dimensions and manufacturer's technical data on features, performance, electrical characteristics, and ratings.
3. Current-limitation curves for fuses with current-limiting characteristics.
4. Time-current coordination curves (average melt) and current-limitation curves
(instantaneous peak let-through current) for each type and rating of fuse. Submit Coordination charts and tables and related data.
5. Fuse sizes for elevator feeders and elevator disconnect switches.
FUSES 262813.00 - 2
1.4 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For fuses to include in emergency, operation, and maintenance manuals. In addition to items specified in Section 017700 "Closeout Procedures, Section 017823 "Operation and Maintenance Data," include the following:
1. Ambient temperature adjustment information.
2. Current-limitation curves for fuses with current-limiting characteristics.
3. Time-current coordination curves (average melt) and current-limitation curves
(instantaneous peak let-through current) for each type and rating of fuse used on the Project. Submit in PDF format.
4. Coordination charts and tables and related data.
1.5 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Fuses: Equal to 10 percent of quantity installed for each size and type, but no fewer than three of each size and type.
1.6 FIELD CONDITIONS
A. Where ambient temperature to which fuses are directly exposed is less than 40 deg F (5 deg C) or more than [100 deg F (38 deg C)] apply manufacturer's ambient temperature adjustment factors to fuse ratings.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Source Limitations: Obtain fuses, for use within a specific product or circuit, from single source from single manufacturer.
2.2 CARTRIDGE FUSES
A. Characteristics: NEMA FU 1, current-limiting, nonrenewable cartridge fuses with voltage ratings consistent with circuit voltages.
1. Type T: 250-V, zero- to 1200-A rating, 200 kAIC time delay.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
C. Comply with NEMA FU 1 for cartridge fuses.
D. Comply with NFPA 70.
FUSES 262813.00 - 3
E. Coordinate fuse ratings with utilization equipment nameplate limitations of maximum fuse size and with system short-circuit current levels.
2.3 SPARE-FUSE CABINET
A. Characteristics: Wall-mounted steel unit with full-length, recessed piano-hinged door and key-coded cam lock and pull.
1. Finish: Gray, baked enamel.
2. Identification: "SPARE FUSES" in 1-1/2-inch- (38-mm-) high letters on exterior of door.
3. Fuse Pullers: For each size of fuse, where applicable and available, from fuse manufacturer.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine fuses before installation. Reject fuses that are moisture damaged or physically damaged.
B. Examine holders to receive fuses for compliance with installation tolerances and other conditions affecting performance, such as rejection features.
C. Examine utilization equipment nameplates and installation instructions. Install fuses of sizes and with characteristics appropriate for each piece of equipment.
D. Evaluate ambient temperatures to determine if fuse rating adjustment factors must be applied to fuse ratings.
E. Proceed with installation only after unsatisfactory conditions have been corrected.
1. r fuse covers with open fuse indication.
3.2 INSTALLATION
A. Install fuses in fusible devices. Arrange fuses so rating information is readable without removing fuse.
B. Install spare-fuse cabinet(s) in location shown on the Drawings or as indicated in the field by Construction Manager.
3.3 IDENTIFICATION
A. Install labels complying with requirements for identification specified in Section 260553 "Identification for Electrical Systems" and indicating fuse replacement information inside of door of each fused switch and adjacent to each fuse block, socket, and holder.
END OF SECTION 262813
| PART 1 - GENERAL |
| 1.1 RELATED DOCUMENTS |
| A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. |
| 1.2 SUMMARY |
| A. Section Includes: |
| 1. Cartridge fuses rated 600 V ac and less for use in the following: |
| a. Control circuits. |
| b. Motor-control centers. |
| c. Panelboards. |
| d. Switchboards. |
| e. Enclosed controllers. |
| f. Enclosed switches. |
2. Spare-fuse cabinets.
| 1.3 ACTION SUBMITTALS |
| A. Product Data: For each type of product. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for spare-fuse cabinets. Include the following for each fuse type indicated: |
| 1. Ambient Temperature Adjustment Information: If ratings of fuses have been adjusted to accommodate ambient temperatures, provide list of fuses with adjusted ratings. |
| a. For each fuse having adjusted ratings, include location of fuse, original fuse rating, local ambient temperature, and adjusted fuse rating. |
| b. Provide manufacturer's technical data on which ambient temperature adjustment calculations are based. |
| 2. Dimensions and manufacturer's technical data on features, performance, electrical characteristics, and ratings. |
| 3. Current-limitation curves for fuses with current-limiting characteristics. |
| 4. Time-current coordination curves (average melt) and current-limitation curves (instantaneous peak let-through current) for each type and rating of fuse. Submit Coordination charts and tables and related data. |
| 5. Fuse sizes for elevator feeders and elevator disconnect switches. |
| 1.4 CLOSEOUT SUBMITTALS |
| A. Operation and Maintenance Data: For fuses to include in emergency, operation, and maintenance manuals. In addition to items specified in Section 017700 "Closeout Procedures, Section 017823 "Operation and Maintenance Data," include the following: |
| 1. Ambient temperature adjustment information. |
| 2. Current-limitation curves for fuses with current-limiting characteristics. |
| 3. Time-current coordination curves (average melt) and current-limitation curves (instantaneous peak let-through current) for each type and rating of fuse used on the Project. Submit in PDF format. |
| 4. Coordination charts and tables and related data. |
| 1.5 MAINTENANCE MATERIAL SUBMITTALS |
| A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. |
| 1. Fuses: Equal to 10 percent of quantity installed for each size and type, but no fewer than three of each size and type. |
| 1.6 FIELD CONDITIONS |
| A. Where ambient temperature to which fuses are directly exposed is less than 40 deg F (5 deg C) or more than [100 deg F (38 deg C)] apply manufacturer's ambient temperature adjustment factors to fuse ratings. |
| PART 2 - PRODUCTS |
| 2.1 MANUFACTURERS |
| A. Source Limitations: Obtain fuses, for use within a specific product or circuit, from single source from single manufacturer. |
| 2.2 CARTRIDGE FUSES |
| A. Characteristics: NEMA FU 1, current-limiting, nonrenewable cartridge fuses with voltage ratings consistent with circuit voltages. |
| 1. Type T: 250-V, zero- to 1200-A rating, 200 kAIC time delay. |
| B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. |
| C. Comply with NEMA FU 1 for cartridge fuses. |
| D. Comply with NFPA 70. |
| E. Coordinate fuse ratings with utilization equipment nameplate limitations of maximum fuse size and with system short-circuit current levels. |
| 2.3 SPARE-FUSE CABINET |
| A. Characteristics: Wall-mounted steel unit with full-length, recessed piano-hinged door and key-coded cam lock and pull. |
| 1. Finish: Gray, baked enamel. |
| 2. Identification: "SPARE FUSES" in 1-1/2-inch- (38-mm-) high letters on exterior of door. |
| 3. Fuse Pullers: For each size of fuse, where applicable and available, from fuse manufacturer. |
| PART 3 - EXECUTION |
| 3.1 EXAMINATION |
| A. Examine fuses before installation. Reject fuses that are moisture damaged or physically damaged. |
| B. Examine holders to receive fuses for compliance with installation tolerances and other conditions affecting performance, such as rejection features. |
| C. Examine utilization equipment nameplates and installation instructions. Install fuses of sizes and with characteristics appropriate for each piece of equipment. |
| D. Evaluate ambient temperatures to determine if fuse rating adjustment factors must be applied to fuse ratings. |
| E. Proceed with installation only after unsatisfactory conditions have been corrected. |
| 1. r fuse covers with open fuse indication. |
| 3.2 INSTALLATION |
| A. Install fuses in fusible devices. Arrange fuses so rating information is readable without removing fuse. |
| B. Install spare-fuse cabinet(s) in location shown on the Drawings or as indicated in the field by Construction Manager. |
| 3.3 IDENTIFICATION |
| A. Install labels complying with requirements for identification specified in Section 260553 "Identification for Electrical Systems" and indicating fuse replacement information inside of door of each fused switch and adjacent to each fuse block, socke... |
| END OF SECTION 262813 |