Summary
This is a specification document for meters and gages for HVAC piping systems required by Volusia County, Florida for the Branch Jail facility located at 1300 Red John Drive, Daytona Beach. The specification details the requirements for installing and supplying thermometers (metal-case liquid-in-glass, plastic-case liquid-in-glass, and duct-type variants), pressure gages (direct-mounting and remote-mounting dial types), test plugs, thermal-energy meters, and associated fittings and accessories for the facility's air handling unit and fire suppression system replacement and upgrade project. The document establishes approved manufacturers for each product category, including Palmer-Wahl Instruments Inc., Trerice H.O. Co., Weiss Instruments Inc., AMETEK Inc., and others, with specific technical requirements such as accuracy ratings (ranging from plus or minus 1 to 2 percent), pressure ratings of 500 psig at 200 degrees Fahrenheit for test plugs, and temperature ranges from minus 40 to plus 220 degrees Fahrenheit depending on application.
The specification requires thermometers to be installed at inlet and outlet points of hydronic coils, thermal storage tanks, and air ducts, while pressure gages must be installed at chiller water connections, pump discharge points, and pressure-reducing valve discharge locations. All components must comply with industry standards including ASME B40.100 for pressure gages and ASME B40.5 for snubber fittings. Contractors must submit product data, shop drawings with manufacturer specifications and locations, product certificates signed by manufacturers, and operation and maintenance documentation. Installation requirements include calibration of all meters following manufacturer instructions and positioning components for optimal visibility and accessibility for maintenance purposes. The specification document does not reference specific pricing, quantities, response dates, or contract award information, as these details are contained in separate procurement documents related to the Branch Jail HVAC system replacement and upgrade project.
View the file
Other files
Show 40 more
Latest 50 of 128 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BID SET VOLUSIA COUNTY
DECEMBER 5, 2025 BRANCH JAIL
METERS AND GAGES FOR HVAC PIPING 230519.00 - 1
SECTION 230519 - METERS AND GAGES FOR HVAC PIPING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following meters and gages for mechanical systems:
1. Thermometers.
2. Gages.
3. Test plugs.
4. Thermal-energy meters.
B. Related Sections include the following:
1. Division 2 Section "Water Distribution" for domestic and fire-protection water service meters outside the building.
2. Division 13 Section "Electric-Drive, Centrifugal Fire Pumps for fire-pump flowmeter systems.
1.3 DEFINITIONS
A. CR: Chlorosulfonated polyethylene synthetic rubber.
B. EPDM: Ethylene-propylene-diene terpolymer rubber.
1.4 SUBMITTALS
A. Product Data: For each type of product indicated; include performance curves.
B. Shop Drawings: Schedule indicating manufacturer's number, scale range, and location for each.
C. Product Certificates: For each type of thermometer, gage and flowmeter, signed by product manufacturer.
D. Operation and Maintenance Data: For flowmeters to include in emergency, operation, and maintenance manuals.
METERS AND GAGES FOR HVAC PIPING 230519.00 - 2
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection:
1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified.
2. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified.
2.2 METAL-CASE, LIQUID-IN-GLASS THERMOMETERS
A. Manufacturers:
1. Palmer - Wahl Instruments Inc.
2. Trerice, H. O. Co.
3. Weiss Instruments, Inc.
4. Weksler Instruments Operating Unit; Dresser Industries; Instrument Div.
B. Case: Die-cast aluminum or brass, 9 inches long.
C. Tube: Red or blue reading, organic-liquid filled, with magnifying lens.
D. Tube Background: Satin-faced, nonreflective aluminum with permanently etched scale markings.
E. Window: Glass.
F. Connector: Adjustable type, 180 degrees in vertical plane, 360 degrees in horizontal plane, with locking device.
G. Stem: Copper-plated steel, aluminum, or brass for thermowell installation and of length to suit installation.
H. Accuracy: Plus or minus 1 percent of range or plus or minus 1 scale division to maximum of
1.5 percent of range.
2.3 PLASTIC-CASE, LIQUID-IN-GLASS THERMOMETERS
A. Manufacturers:
1. Ernst Gage Co.
2. Eugene Ernst Products Co.
3. Marsh Bellofram.
4. Miljoco Corp.
METERS AND GAGES FOR HVAC PIPING 230519.00 - 3
5. Trerice, H. O. Co.
6. Weksler Instruments Operating Unit; Dresser Industries; Instrument Div.
7. Winters Instruments.
B. Case: Plastic, 9 inches long.
C. Tube: Red or blue reading, mercury or organic-liquid filled, with magnifying lens.
D. Tube Background: Satin-faced, nonreflective aluminum with permanently etched scale markings.
E. Window: Glass or plastic.
F. Connector: Adjustable type, 180 degrees in vertical plane, 360 degrees in horizontal plane, with locking device.
G. Stem: Metal, for thermowell installation and of length to suit installation.
H. Accuracy: Plus or minus 1 percent of range or plus or minus 1 scale division to maximum of
1.5 percent of range.
2.4 DUCT-TYPE, LIQUID-IN-GLASS THERMOMETERS
A. Manufacturers:
1. Miljoco Corp.
2. Palmer - Wahl Instruments Inc.
3. Trerice, H. O. Co.
4. Weiss Instruments, Inc.
B. Case: Metal or plastic, 7 inches long.
C. Tube: Red or blue reading, mercury or organic filled, with magnifying lens.
D. Tube Background: Satin-faced, nonreflective aluminum with permanently etched scale markings.
E. Window: Glass or plastic.
F. Connector: Adjustable type, 180 degrees in vertical plane, 360 degrees in horizontal plane, with locking device.
G. Stem: Metal, for installation in mounting bracket and of length to suit installation.
H. Mounting Bracket: Flanged fitting for attachment to duct and made to hold thermometer stem.
I. Accuracy: Plus or minus 1 percent of range or plus or minus 1 scale division to maximum of
1.5 percent of range.
METERS AND GAGES FOR HVAC PIPING 230519.00 - 4
2.5 THERMOWELLS
A. Manufacturers:
1. AMETEK, Inc.; U.S. Gauge Div.
2. Ashcroft Commercial Instrument Operations; Dresser Industries; Instrument Div.
3. Palmer - Wahl Instruments Inc.
4. Tel-Tru Manufacturing Company.
5. Trerice, H. O. Co.
6. Weiss Instruments, Inc.
7. Weksler Instruments Operating Unit; Dresser Industries; Instrument Div.
B. Manufacturers: Same as manufacturer of thermometer being used.
C. Description: Pressure-tight, socket-type metal fitting made for insertion into piping and of type, diameter, and length required to hold thermometer.
2.6 PRESSURE GAGES
A. Manufacturers:
1. AMETEK, Inc.; U.S. Gauge Div.
2. Ashcroft Commercial Instrument Operations; Dresser Industries; Instrument Div.
3. Palmer - Wahl Instruments Inc.
4. Trerice, H. O. Co.
5. Weiss Instruments, Inc.
6. Weksler Instruments Operating Unit; Dresser Industries; Instrument Div.
B. Direct-Mounting, Dial-Type Pressure Gages: Indicating-dial type complying with
ASME B40.100.
1. Case: Liquid-filled type, drawn steel or cast aluminum 6-inch diameter.
2. Pressure-Element Assembly: Bourdon tube, unless otherwise indicated.
3. Pressure Connection: Brass, NPS 1/4, bottom-outlet type unless back-outlet type is indicated.
4. Movement: Mechanical, with link to pressure element and connection to pointer.
5. Dial: Satin-faced, nonreflective aluminum with permanently etched scale markings.
6. Pointer: Red metal.
7. Window: Glass.
8. Ring: Metal
9. Accuracy: Grade B, plus or minus 2 percent of middle half scale.
10. Vacuum-Pressure Range: 30-in. Hg of vacuum to 15 psig of pressure.
11. Range for Fluids under Pressure: Two times operating pressure.
C. Remote-Mounting, Dial-Type Pressure Gages: ASME B40.100, indicating-dial type.
1. Case: Dry type, drawn steel or cast aluminum, 6-inch diameter with holes for panel mounting.
2. Pressure-Element Assembly: Bourdon tube, unless otherwise indicated.
METERS AND GAGES FOR HVAC PIPING 230519.00 - 5
3. Pressure Connection: Brass, NPS 1/4, bottom-outlet type unless back-outlet type is indicated.
4. Movement: Mechanical, with link to pressure element and connection to pointer.
5. Dial: Satin-faced, nonreflective aluminum with permanently etched scale markings.
6. Pointer: Red metal.
7. Window: Glass.
8. Ring: Metal.
9. Accuracy: Grade B, plus or minus 2 percent of middle half scale.
10. Vacuum-Pressure Range: 30-in. Hg of vacuum to 15 psig of pressure
11. Range for Fluids under Pressure: Two times operating pressure.
D. Pressure-Gage Fittings:
1. Valves: NPS 1/4 brass or stainless-steel needle type.
2. Syphons: NPS 1/4 coil of brass tubing with threaded ends.
3. Snubbers: ASME B40.5, NPS 1/4 brass bushing with corrosion-resistant, porous-metal disc of material suitable for system fluid and working pressure.
2.7 TEST PLUGS
A. Manufacturers:
1. Flow Design, Inc.
2. MG Piping Products Co.
3. National Meter, Inc.
4. Peterson Equipment Co., Inc.
5. Sisco Manufacturing Co.
6. Trerice, H. O. Co.
7. Watts Industries, Inc.; Water Products Div.
B. Description: Corrosion-resistant brass or stainless-steel body with core inserts and gasketed and threaded cap, with extended stem for units to be installed in insulated piping.
C. Minimum Pressure and Temperature Rating: 500 psig at 200 deg F.
D. Core Inserts: One or two self-sealing rubber valves.
1. Insert material for air, water, oil, or gas service at 20 to 200 deg F shall be CR.
2. Insert material for air or water service at minus 30 to plus 275 deg F shall be EPDM.
E. Test Kit: Furnish one test kit(s) containing one pressure gage and adaptor, two thermometer(s), and carrying case. Pressure gage, adapter probes, and thermometer sensing elements shall be of diameter to fit test plugs and of length to project into piping.
1. Pressure Gage: Small bourdon-tube insertion type with 2- to 3-inch-diameter dial and probe. Dial range shall be 0 to 200 psig.
2. Low-Range Thermometer: Small bimetallic insertion type with 1- to 2-inch- diameter dial and tapered-end sensing element. Dial ranges shall be 25 to 125 deg F.
3. High-Range Thermometer: Small bimetallic insertion type with 1- to 2-inch- diameter dial and tapered-end sensing element. Dial ranges shall be 0 to 220 deg F.
METERS AND GAGES FOR HVAC PIPING 230519.00 - 6
4. Carrying case shall have formed instrument padding.
PART 3 - EXECUTION
3.1 THERMOMETER APPLICATIONS
A. Install liquid-in-glass thermometers in the following locations:
1. Inlet and outlet of each hydronic coil in air-handling units and built-up central systems.
2. Inlet and outlet of each thermal storage tank.
3. Outside-air, return-air, and mixed-air ducts.
B. Install direct-mounting, vapor-actuated dial thermometers in the following locations:
1. Inlet and outlet of each hydronic coil in air-handling units and built-up central systems.
2. Inlet and outlet of each thermal storage tank.
C. Install remote-mounting, vapor-actuated dial thermometers in the following locations:
1. Inlet and outlet of each hydronic zone.
2. Inlet and outlet of each hydronic coil in air-handling units and built-up central systems.
3. Inlet and outlet of each thermal storage tank.
D. Install bimetallic-actuated dial thermometers in the following locations:
1. Inlet and outlet of each hydronic zone.
2. Inlet and outlet of each hydronic coil in air-handling units and built-up central systems.
3. Inlet and outlet of each thermal storage tank.
E. Install liquid-filled-case-type, vapor-actuated dial thermometers at suction and discharge of each pump.
F. Provide the following temperature ranges for thermometers:
1. Air Ducts: Minus 40 to plus 110 deg F, with 2-degree scale divisions.
3.2 GAGE APPLICATIONS
A. Install dry-case-type pressure gages for discharge of each pressure-reducing valve.
B. Install liquid-filled-case-type pressure gages at chilled-water inlets and outlets of chillers.
C. Install liquid-filled-case-type pressure gages at suction and discharge of each pump.
3.3 INSTALLATIONS
A. Install direct-mounting thermometers and adjust vertical and tilted positions.
METERS AND GAGES FOR HVAC PIPING 230519.00 - 7
B. Install remote-mounting dial thermometers on panel, with tubing connecting panel and thermometer bulb supported to prevent kinks. Use minimum tubing length.
C. Install thermowells with socket extending one-third of diameter of pipe and in vertical position in piping tees where thermometers are indicated.
D. Duct Thermometer Support Flanges: Install in wall of duct where duct thermometers are indicated. Attach to duct with screws.
E. Install direct-mounting pressure gages in piping tees with pressure gage located on pipe at most readable position.
F. Install remote-mounting pressure gages on panel.
G. Install needle-valve and snubber fitting in piping for each pressure gage for fluids.
H. Install needle-valve and syphon fitting in piping for each pressure gage for steam.
I. Install test plugs in tees in piping.
J. Install flow indicators, in accessible positions for easy viewing, in piping systems.
K. Assemble and install connections, tubing, and accessories between flow-measuring elements and flowmeters as prescribed by manufacturer's written instructions.
L. Install flowmeter elements in accessible positions in piping systems.
M. Install differential-pressure-type flowmeter elements with at least minimum straight lengths of pipe upstream and downstream from element as prescribed by manufacturer's written instructions.
N. Install wafer-orifice flowmeter elements between pipe flanges.
O. Install permanent indicators on walls or brackets in accessible and readable positions.
P. Install connection fittings for attachment to portable indicators in accessible locations.
Q. Install flowmeters at discharge of hydronic system pumps and at inlet of hydronic air coils.
R. Assemble components and install thermal-energy meters.
S. Mount meters on wall if accessible; if not, provide brackets to support meters.
3.4 CONNECTIONS
A. Install meters and gages adjacent to machines and equipment to allow service and maintenance for meters, gages, machines, and equipment.
B. Connect flowmeter-system elements to meters.
METERS AND GAGES FOR HVAC PIPING 230519.00 - 8
C. Connect flowmeter transmitters to meters.
D. Connect thermal-energy-meter transmitters to meters.
E. Ground equipment according to Division 26 Section "Grounding and Bonding."
F. Connect wiring according to Division 26 Section "Conductors and Cables."
3.5 ADJUSTING
A. Calibrate meters according to manufacturer's written instructions, after installation.
B. Adjust faces of meters and gages to proper angle for best visibility.
END OF SECTION 230519
| PART 1 - GENERAL |
| 1.1 RELATED DOCUMENTS |
| A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. |
| 1.2 SUMMARY |
| A. This Section includes the following meters and gages for mechanical systems: |
| 1. Thermometers. |
| 2. Gages. |
| 3. Test plugs. |
| 4. Thermal-energy meters. |
| B. Related Sections include the following: |
| 1. Division 2 Section "Water Distribution" for domestic and fire-protection water service meters outside the building. |
| 2. Division 13 Section "Electric-Drive, Centrifugal Fire Pumps for fire-pump flowmeter systems. |
| 1.3 DEFINITIONS |
| A. CR: Chlorosulfonated polyethylene synthetic rubber. |
| B. EPDM: Ethylene-propylene-diene terpolymer rubber. |
| 1.4 SUBMITTALS |
| A. Product Data: For each type of product indicated; include performance curves. |
| B. Shop Drawings: Schedule indicating manufacturer's number, scale range, and location for each. |
| C. Product Certificates: For each type of thermometer, gage and flowmeter, signed by product manufacturer. |
| D. Operation and Maintenance Data: For flowmeters to include in emergency, operation, and maintenance manuals. |
| PART 2 - PRODUCTS |
| 2.1 MANUFACTURERS |
| A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection: |
| 1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified. |
| 2. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified. |
| 2.2 METAL-CASE, LIQUID-IN-GLASS THERMOMETERS |
| A. Manufacturers: |
| 1. Palmer - Wahl Instruments Inc. |
| 2. Trerice, H. O. Co. |
| 3. Weiss Instruments, Inc. |
| 4. Weksler Instruments Operating Unit; Dresser Industries; Instrument Div. |
| B. Case: Die-cast aluminum or brass, 9 inches long. |
| C. Tube: Red or blue reading, organic-liquid filled, with magnifying lens. |
| D. Tube Background: Satin-faced, nonreflective aluminum with permanently etched scale markings. |
| E. Window: Glass. |
| F. Connector: Adjustable type, 180 degrees in vertical plane, 360 degrees in horizontal plane, with locking device. |
| G. Stem: Copper-plated steel, aluminum, or brass for thermowell installation and of length to suit installation. |
| H. Accuracy: Plus or minus 1 percent of range or plus or minus 1 scale division to maximum of 1.5 percent of range. |
| 2.3 PLASTIC-CASE, LIQUID-IN-GLASS THERMOMETERS |
| A. Manufacturers: |
| 1. Ernst Gage Co. |
| 2. Eugene Ernst Products Co. |
| 3. Marsh Bellofram. |
| 4. Miljoco Corp. |
| 5. Trerice, H. O. Co. |
| 6. Weksler Instruments Operating Unit; Dresser Industries; Instrument Div. |
| 7. Winters Instruments. |
| B. Case: Plastic, 9 inches long. |
| C. Tube: Red or blue reading, mercury or organic-liquid filled, with magnifying lens. |
| D. Tube Background: Satin-faced, nonreflective aluminum with permanently etched scale markings. |
| E. Window: Glass or plastic. |
| F. Connector: Adjustable type, 180 degrees in vertical plane, 360 degrees in horizontal plane, with locking device. |
| G. Stem: Metal, for thermowell installation and of length to suit installation. |
| H. Accuracy: Plus or minus 1 percent of range or plus or minus 1 scale division to maximum of 1.5 percent of range. |
| 2.4 DUCT-TYPE, LIQUID-IN-GLASS THERMOMETERS |
| A. Manufacturers: |
| 1. Miljoco Corp. |
| 2. Palmer - Wahl Instruments Inc. |
| 3. Trerice, H. O. Co. |
| 4. Weiss Instruments, Inc. |
| B. Case: Metal or plastic, 7 inches long. |
| C. Tube: Red or blue reading, mercury or organic filled, with magnifying lens. |
| D. Tube Background: Satin-faced, nonreflective aluminum with permanently etched scale markings. |
| E. Window: Glass or plastic. |
| F. Connector: Adjustable type, 180 degrees in vertical plane, 360 degrees in horizontal plane, with locking device. |
| G. Stem: Metal, for installation in mounting bracket and of length to suit installation. |
| H. Mounting Bracket: Flanged fitting for attachment to duct and made to hold thermometer stem. |
| I. Accuracy: Plus or minus 1 percent of range or plus or minus 1 scale division to maximum of 1.5 percent of range. |
| 2.5 THERMOWELLS |
| A. Manufacturers: |
| 1. AMETEK, Inc.; U.S. Gauge Div. |
| 2. Ashcroft Commercial Instrument Operations; Dresser Industries; Instrument Div. |
| 3. Palmer - Wahl Instruments Inc. |
| 4. Tel-Tru Manufacturing Company. |
| 5. Trerice, H. O. Co. |
| 6. Weiss Instruments, Inc. |
| 7. Weksler Instruments Operating Unit; Dresser Industries; Instrument Div. |
| B. Manufacturers: Same as manufacturer of thermometer being used. |
| C. Description: Pressure-tight, socket-type metal fitting made for insertion into piping and of type, diameter, and length required to hold thermometer. |
| 2.6 PRESSURE GAGES |
| A. Manufacturers: |
| 1. AMETEK, Inc.; U.S. Gauge Div. |
| 2. Ashcroft Commercial Instrument Operations; Dresser Industries; Instrument Div. |
| 3. Palmer - Wahl Instruments Inc. |
| 4. Trerice, H. O. Co. |
| 5. Weiss Instruments, Inc. |
| 6. Weksler Instruments Operating Unit; Dresser Industries; Instrument Div. |
| B. Direct-Mounting, Dial-Type Pressure Gages: Indicating-dial type complying with ASME B40.100. |
| 1. Case: Liquid-filled type, drawn steel or cast aluminum 6-inch diameter. |
| 2. Pressure-Element Assembly: Bourdon tube, unless otherwise indicated. |
| 3. Pressure Connection: Brass, NPS 1/4, bottom-outlet type unless back-outlet type is indicated. |
| 4. Movement: Mechanical, with link to pressure element and connection to pointer. |
| 5. Dial: Satin-faced, nonreflective aluminum with permanently etched scale markings. |
| 6. Pointer: Red metal. |
| 7. Window: Glass. |
| 8. Ring: Metal |
| 9. Accuracy: Grade B, plus or minus 2 percent of middle half scale. |
| 10. Vacuum-Pressure Range: 30-in. Hg of vacuum to 15 psig of pressure. |
| 11. Range for Fluids under Pressure: Two times operating pressure. |
| C. Remote-Mounting, Dial-Type Pressure Gages: ASME B40.100, indicating-dial type. |
| 1. Case: Dry type, drawn steel or cast aluminum, 6-inch diameter with holes for panel mounting. |
| 2. Pressure-Element Assembly: Bourdon tube, unless otherwise indicated. |
| 3. Pressure Connection: Brass, NPS 1/4, bottom-outlet type unless back-outlet type is indicated. |
| 4. Movement: Mechanical, with link to pressure element and connection to pointer. |
| 5. Dial: Satin-faced, nonreflective aluminum with permanently etched scale markings. |
| 6. Pointer: Red metal. |
| 7. Window: Glass. |
| 8. Ring: Metal. |
| 9. Accuracy: Grade B, plus or minus 2 percent of middle half scale. |
| 10. Vacuum-Pressure Range: 30-in. Hg of vacuum to 15 psig of pressure |
| 11. Range for Fluids under Pressure: Two times operating pressure. |
| D. Pressure-Gage Fittings: |
| 1. Valves: NPS 1/4 brass or stainless-steel needle type. |
| 2. Syphons: NPS 1/4 coil of brass tubing with threaded ends. |
| 3. Snubbers: ASME B40.5, NPS 1/4 brass bushing with corrosion-resistant, porous-metal disc of material suitable for system fluid and working pressure. |
| 2.7 TEST PLUGS |
| A. Manufacturers: |
| 1. Flow Design, Inc. |
| 2. MG Piping Products Co. |
| 3. National Meter, Inc. |
| 4. Peterson Equipment Co., Inc. |
| 5. Sisco Manufacturing Co. |
| 6. Trerice, H. O. Co. |
| 7. Watts Industries, Inc.; Water Products Div. |
| B. Description: Corrosion-resistant brass or stainless-steel body with core inserts and gasketed and threaded cap, with extended stem for units to be installed in insulated piping. |
| C. Minimum Pressure and Temperature Rating: 500 psig at 200 deg F. |
| D. Core Inserts: One or two self-sealing rubber valves. |
| 1. Insert material for air, water, oil, or gas service at 20 to 200 deg F shall be CR. |
| 2. Insert material for air or water service at minus 30 to plus 275 deg F shall be EPDM. |
| E. Test Kit: Furnish one test kit(s) containing one pressure gage and adaptor, two thermometer(s), and carrying case. Pressure gage, adapter probes, and thermometer sensing elements shall be of diameter to fit test plugs and of length to project int... |
| 1. Pressure Gage: Small bourdon-tube insertion type with 2- to 3-inch-diameter dial and probe. Dial range shall be 0 to 200 psig. |
| 2. Low-Range Thermometer: Small bimetallic insertion type with 1- to 2-inch- diameter dial and tapered-end sensing element. Dial ranges shall be 25 to 125 deg F. |
| 3. High-Range Thermometer: Small bimetallic insertion type with 1- to 2-inch- diameter dial and tapered-end sensing element. Dial ranges shall be 0 to 220 deg F. |
| 4. Carrying case shall have formed instrument padding. |
| PART 3 - EXECUTION |
| 3.1 THERMOMETER APPLICATIONS |
| A. Install liquid-in-glass thermometers in the following locations: |
| 1. Inlet and outlet of each hydronic coil in air-handling units and built-up central systems. |
| 2. Inlet and outlet of each thermal storage tank. |
| 3. Outside-air, return-air, and mixed-air ducts. |
| B. Install direct-mounting, vapor-actuated dial thermometers in the following locations: |
| 1. Inlet and outlet of each hydronic coil in air-handling units and built-up central systems. |
| 2. Inlet and outlet of each thermal storage tank. |
| C. Install remote-mounting, vapor-actuated dial thermometers in the following locations: |
| 1. Inlet and outlet of each hydronic zone. |
| 2. Inlet and outlet of each hydronic coil in air-handling units and built-up central systems. |
| 3. Inlet and outlet of each thermal storage tank. |
| D. Install bimetallic-actuated dial thermometers in the following locations: |
| 1. Inlet and outlet of each hydronic zone. |
| 2. Inlet and outlet of each hydronic coil in air-handling units and built-up central systems. |
| 3. Inlet and outlet of each thermal storage tank. |
| E. Install liquid-filled-case-type, vapor-actuated dial thermometers at suction and discharge of each pump. |
| F. Provide the following temperature ranges for thermometers: |
| 1. Air Ducts: Minus 40 to plus 110 deg F, with 2-degree scale divisions. |
| 3.2 GAGE APPLICATIONS |
| A. Install dry-case-type pressure gages for discharge of each pressure-reducing valve. |
| B. Install liquid-filled-case-type pressure gages at chilled-water inlets and outlets of chillers. |
| C. Install liquid-filled-case-type pressure gages at suction and discharge of each pump. |
| 3.3 INSTALLATIONS |
| A. Install direct-mounting thermometers and adjust vertical and tilted positions. |
| B. Install remote-mounting dial thermometers on panel, with tubing connecting panel and thermometer bulb supported to prevent kinks. Use minimum tubing length. |
| C. Install thermowells with socket extending one-third of diameter of pipe and in vertical position in piping tees where thermometers are indicated. |
| D. Duct Thermometer Support Flanges: Install in wall of duct where duct thermometers are indicated. Attach to duct with screws. |
| E. Install direct-mounting pressure gages in piping tees with pressure gage located on pipe at most readable position. |
| F. Install remote-mounting pressure gages on panel. |
| G. Install needle-valve and snubber fitting in piping for each pressure gage for fluids. |
| H. Install needle-valve and syphon fitting in piping for each pressure gage for steam. |
| I. Install test plugs in tees in piping. |
| J. Install flow indicators, in accessible positions for easy viewing, in piping systems. |
| K. Assemble and install connections, tubing, and accessories between flow-measuring elements and flowmeters as prescribed by manufacturer's written instructions. |
| L. Install flowmeter elements in accessible positions in piping systems. |
| M. Install differential-pressure-type flowmeter elements with at least minimum straight lengths of pipe upstream and downstream from element as prescribed by manufacturer's written instructions. |
| N. Install wafer-orifice flowmeter elements between pipe flanges. |
| O. Install permanent indicators on walls or brackets in accessible and readable positions. |
| P. Install connection fittings for attachment to portable indicators in accessible locations. |
| Q. Install flowmeters at discharge of hydronic system pumps and at inlet of hydronic air coils. |
| R. Assemble components and install thermal-energy meters. |
| S. Mount meters on wall if accessible; if not, provide brackets to support meters. |
| 3.4 CONNECTIONS |
| A. Install meters and gages adjacent to machines and equipment to allow service and maintenance for meters, gages, machines, and equipment. |
| B. Connect flowmeter-system elements to meters. |
| C. Connect flowmeter transmitters to meters. |
| D. Connect thermal-energy-meter transmitters to meters. |
| E. Ground equipment according to Division 26 Section "Grounding and Bonding." |
| F. Connect wiring according to Division 26 Section "Conductors and Cables." |
| 3.5 ADJUSTING |
| A. Calibrate meters according to manufacturer's written instructions, after installation. |
| B. Adjust faces of meters and gages to proper angle for best visibility. |