This is a specifications document for electrical boxes and systems issued by Volusia County for the Branch Jail project, dated December 5, 2025. The document provides detailed technical requirements for outlet boxes, junction boxes, pull boxes, gutters (wireways), and cabinets that will be installed as part of a comprehensive replacement and upgrade of the facility's air handling unit infrastructure, fire/smoke damper systems, and related fire suppression controls at 1300 Red John Drive, Daytona Beach, Florida. The specification outlines material standards, construction requirements, and installation procedures but does not specify item quantities, response dates, due dates, site visits, bidders' conferences, award dates, or contract terms.

The specification mandates that all boxes and fittings be labeled by Underwriters' Laboratories, Inc., and establishes specific material requirements including hot-dipped galvanized steel for interior outlet boxes, corrosion-resistant cast-type boxes for weatherproof applications, and NEMA 12 class sheet steel cabinets. Installation must comply with NFPA 70 (National Electrical Code), NECA standards, and manufacturer instructions. The document prohibits PVC junction boxes and back-to-back boxes, requires proper box sizing and support independent of other building systems, and mandates accessible placement with specific height and distance requirements. Square D #24366 surface-mounted cabinets with integral lockable covers and internal plywood backboards are specified. The document contains no information regarding pricing, set-asides, incumbent contractors, funding sources, or contract renewal options.

View the file

Other files

File Type Posted
Volusia_County_Branch_Jail_Air_Handler-Fire_Suppression_System_Removal,_Replacement_and_Upgrade_(Addendum_#6_Revision).pdf PDF
Exhibit_R_-_VCBJ_Existing_Drawings_(As-Builts)_1983.pdf PDF
Exhibit_Q_-_NFPA_72_Inspection_Documents.pdf PDF
Exhibit_P_-_E4.03_-_FLOOR_PLAN_C_-_SKETCH_(REPLACES_ALL_PREVIOUS_VERSIONS)_(1).pdf PDF
Exhibit_O_-_E4.01_-_FLOOR_PLAN_A_-_SKETCH_(REPLACES_ALL_PREVIOUS_VERSIONS).pdf PDF
Exhibit_N_-_238216.11_Hydronic_Air_Coils_(REPLACES_ALL_PREVIOUS_VERSIONS).pdf PDF
Volusia_County_Branch_Jail_Air_Handler-Fire_Suppression_System_Removal,_Replacement_and_Upgrade_(Addendum_#3_Revision).pdf PDF
Exhibit_M_-_Diagram_RTU_Curb_and_Tie_Down.pdf PDF
Volusia_County_Branch_Jail_Air_Handler-Fire_Suppression_System_Removal,_Replacement_and_Upgrade_(Addendum_#1_Revision).pdf PDF
Volusia_County_Branch_Jail_Air_Handler-Fire_Suppression_System_Removal,_Replacement_and_Upgrade.pdf PDF
Exhibit_L_-_Contractor_-_Vendor_Background_Packet_Rev_05-22-2025.pdf PDF
Exhibit_K_-_Pre-Bid_Parking_Map.pdf PDF
Exhibit_J_-_VCBJ_Bidder_Disclaimer_and_Notice_to_Bidders.pdf PDF
Exhibit_I_-_VC_Branch_Jail_AHU_Fire_Suppression_Scope.pdf PDF
Exhibit_H_-_Special_Conditions_26-B-110IF.pdf PDF
Exhibit_G_-_Bid_Price_Sheet_26-B-110IF.xlsx XLSX spreadsheet
Exhibit_F_-_Sales_Tax_Exemption_Procedures.pdf PDF
Exhibit_E_-_Technical_Specifications.pdf PDF
Exhibit_D_-_Construction_Plans.pdf PDF
Exhibit_C_-_Draft_Contract_26-B-110IF.pdf PDF
Exhibit_B_-_PRIME-SUB_FORM_for_Contractors_26-B-110IF.xlsx XLSX spreadsheet
Exhibit_A_-_Insurance_Requirements_26-B-110IF.pdf PDF
Construction_Bid_Request_Air_Handler.docx DOCX document
Pre-Bid_Meeting_Invitee_Listing_(1).docx DOCX document
283000_Digital,_Addressable_Fire_Alarm_System.pdf PDF
Table_of_Contents.pdf PDF
270500_Special_Systems.pdf PDF
264313_Surge_Protection_Devices.pdf PDF
260501_Electrical_Scope.pdf PDF
260533_Raceways_-_Metal.pdf PDF
262726_Wiring_Devices.pdf PDF
233300_Air_Duct_Accessories.pdf PDF
260534_Raceways_-_Non-metallic.pdf PDF
262813_Fuses.pdf PDF
260519_Low-Voltage_Electrical_Power_Conductors_and_Cables.pdf PDF
262816_Safety_Switches.pdf PDF
VCBJ_Bidder_Disclaimer.docx DOCX document
264113_Lightning_Protection_System.pdf PDF
Special_Conditions.docx DOCX document
232923_Variable_Frequency_Motor_Controllers.pdf PDF
237313_Modular_Indoor_Central_Station_Air_Handler_Units.pdf PDF
237413_Packaged,_Outdoor,_Central_Station_Rooftop_Units.pdf PDF
230529_Hangers_and_Supports_for_HVAC_Piping.pdf PDF
230519_Meters_and_Gages_for_HVAC_Piping.pdf PDF
260526_Grounding_and_Bonding_for_Electrical_Systems.pdf PDF
262416_Panelboards.pdf PDF
230548_Vibration_Controls_for_HVAC.pdf PDF
MD3.1_-_ENLARGED_MECHANICAL_ROOM_DEMO_PLAN.pdf PDF
260502_Basic_Materials_&_Methods.pdf PDF
VCDCH_Fire_Damper_100%CD_Submission_G-001_Cover_Sheet.pdf PDF
Show 40 more

Latest 50 of 128 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BID SET VOLUSIA COUNTY

DECEMBER 5, 2025 BRANCH JAIL

BOXES FOR ELECTRICAL SYSTEMS 260535.00 - 1

SECTION 260535 BOXES FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.1 SCOPE:

A. This section outlines the quality, type and installation of outlet boxes, junction boxes and gutters (wireways) for general and special use.

PART 2 - PRODUCTS

2.1 GENERAL:

A. All boxes and fittings shall be labeled by Underwriters' Laboratories, Inc.

B. Interior outlet boxes shall be galvanized steel constructed with stamped knockouts in back and sides, and threaded holes with screws for securing box coverplates or wiring devices.

C. Weatherproof outlet boxes and boxes to be cast within the concrete walls, floors and ceilings shall be corrosion-resistant, watertight, cast type suited to each application and having threaded conduit ends, cast face plate with spring-hinged waterproof cap suitably configured, gasket, and corrosion-proof fasteners. All fastener, springs, hinges shall be totally corrosion proof and corrosion resistant .

D. Provide outlet box accessories as required for each installation, including mounting brackets, wallboard hangers, extension rings, device rings, outlet boxes, and corrosion-resistant knockout closures compatible with outlet boxes being used and meeting requirements of individual wiring situations.

E. Pull boxes and junction boxes shall be constructed of code gauge galvanized sheet steel. Provide pull boxes with screw-on covers of the type and size to suit each respective location and installation. Boxes shall have continuously welded seams and shall be equipped with steel nuts, bolts, screws, and washers. Provide cast metal, gasketed type pull boxes for outdoor locations.

F. All boxes shall be sized as required by NFPA 70.

G. NOTE: PVC junction boxes are strictly prohibited.

2.2 OUTLET BOXES:

A. Shall be standard type, with knockouts, made of hot dipped galvanized steel as manufactured by Steel City, Raco or Appleton.

B. Ceiling outlet boxes shall be 4" octagon or square with plaster ring 1-1/2" deep or larger when required due to number of wires.

C. Boxes shall be provided with approved 3/8" fixture studs where required.

BOXES FOR ELECTRICAL SYSTEMS 260535.00 - 2

D. Except when located in exposed concrete block, switch and receptacle boxes shall be 4" square with plaster or masonry rings for single gang installation. Appropriate gang boxes shall be used for mounting ganged switches.

E. When installed in exposed concrete block, switch and receptacle boxes shall be masonry type stamped steel boxes.

2.3 JUNCTION BOXES AND PULL BOXES (INTERIOR):

A. Sheet Metal: Shall be standard NEMA 1 type with hinged lockable cover, with knockouts, made of hot dipped galvanized steel as manufactured by Steel City, Raco or Appleton.

B. Cast: Shall be type FS, FD, JB, GS, or SEH as required for application.

C. Mounting Panel: Provide removable plywood internal mounting panel for component installation.

2.4 JUNCTION AND PULL BOXES (EXTERIOR):

A. Shall be precast concrete for all below grade exterior use and where shown. All boxes installed above grade shall be NEMA 3R weatherproof and watertight, or as indicated on the drawings.

B. Precast concrete below grade boxes located in exterior locations shall have 28-day concrete compressive strength = 4500 psi and be designed for H-20-44 loading. Install pull eyes and inserts for cable rack in two sides of box. Contractor shall install box at depth where top of box is 3 inches above final surrounding grade elevation. Provide beaded weld lettering on cover, indicating service enclosed IE “systems”, “power”, etc.

2.5 CABINETS:

A. Comply with UL 50, "Electrical Cabinets and Boxes" and NEMA ICS 6.

B. Construction: Sheet steel, NEMA 12 class except as otherwise indicated. Cabinet shall consist of a box and a front consisting of a one-piece frame and a hinged door. Arrange door to close against a rabbet placed all around the inside edge of the frame, with a uniformly close fit between door and frame. Provide concealed fasteners, not over 24" apart, to hold fronts to cabinet boxes and provide for adjustment.

C. Provide flush or concealed door hinges not over 24" apart and not over 6" from top and bottom of door. For flush cabinets, make the front approximately 3/4" larger than the box all around. For surface mounted cabinets, make front same height and width as box.

D. Doors: Double doors for cabinets wider than 24".

E. Locks: Combination spring catch and key lock, with all locks for cabinets of the same system keyed alike. Locks shall be of a type to permit doors to latch closed without locking. All cabinets to be provided with locks.

F. Mounting Panel: Provide removable plywood internal mounting panel for equipment and component installation.

G. Provide color-coded identification nameplates for all junction boxes over 6" x 6” square per specification SECTION 26 05 01 - ELECTRICAL SCOPE.

BOXES FOR ELECTRICAL SYSTEMS 260535.00 - 3

H. Cabinets shall be Square D #24366, surface mounted with integral lockable cover and internal plywood backboard.

PART 3 - EXECUTION

3.1 INSTALLATION:

A. Comply with applicable portions of the National Electrical Contractor's Association's (NECA) "Standard of Installation".

B. Install all boxes and fittings in compliance with NFPA 70, the manufacturer's written instruction, and with recognized industry practices.

C. For locations exposed to weather or moisture (interior or exterior), provide weatherproof boxes and accessories.

D. Install pull boxes in all raceways runs having more than 270 degrees total bending (all directions combined and each complete offset counting as 90 degrees) or in runs more than 200' long.

E. Provide knockout closures to cap unused knockout holes where blanks have been removed and plugs for unused threaded hubs.

F. Boxes and conduit bodies shall be located so that all electrical wiring is accessible.

G. All boxes shall be sized per NEC .

H. Install pull boxes and wire troughs with hinged front covers accessible per code requirements.

I. All flush floor outlets shall be leveled and flush with floor; shall be parallel and perpendicular to building construction lines and shall be compatible with floor material used. Verify exact location of floor boxes with Owner's Authorized Representative prior to any concrete pour. Maintain all fire ratings through the floor system.

J. All recessed boxes shall be installed in a flush rigid manner with box lines at perpendicular and parallel angles to finished surfaces. Boxes shall be supported by appropriate hardware selected for the type of surface from which the box shall be supported. For example, provide metal screws for metal, wood screws for wood, and expansion devices for masonry or concrete.

K. The Contractor shall coordinate work with that of all trades so that each electrical box is the type suitable for the wall or ceiling construction provided.

L. Provide supporting channel and hardware as necessary to support boxes, enclosures, and cabinets.

3.2 INSTALLATION OF OUTLET BOXES:

A. Outlet boxes shall be securely fastened to structural members and shall not be supported by dry wall, gypsum board, plaster, etc. The device or plate installed in conjunction with the outlet box shall not be used for support.

BOXES FOR ELECTRICAL SYSTEMS 260535.00 - 4

B. Surface fixture outlet boxes shall be set so edge of cover comes flush with finished surface.

C. There shall be no more knockouts opened in any outlet box than are actually required.

D. Boxes shall be sealed during construction.

E. Back-to-back boxes shall not be utilized, and all boxes shall be staggered between boxes at least

36” or as required by UL listing for rated walls and shall be installed using UL rated Putty packs or equal.

F. Under no circumstances shall thru-the-wall or back-to-back boxes be used.

G. Outlet boxes two gangs and wider shall not be supported by attachment clips or any means which supports the box from less than two opposite sides. Such outlet boxes in stud walls shall be supported securely by support members spanning between studs.

3.3 INSTALLATION OF JUNCTION BOXES:

A. Provide junction or pull boxes where shown on the drawings and as required to facilitate installing conductors. Such boxes shall be "Code" sized unless required to be larger by the plans or other sections of this specification. All junction boxes shall be accessible.

B. Junction boxes shall be securely fastened to the building structure independent of ductwork, plumbing, etc. Junction boxes shall not be supported by conduit fittings.

C. Boxes to be embedded in concrete shall be properly leveled and anchored in place before the concrete is poured.

D. There shall be no more knockouts opened in any box than are actually required.

E. Boxes shall be properly protected during construction and shall be cleaned of all foreign matter before conductors are installed.

F. All junction boxes shall be located a minimum of 12” and maximum of 36” from ceiling grid.

Overhead junction boxes may not be installed where accessibility is dependent on removal of a lighting fixture or access cover. No junction shall be located above drywall ceiling. All junction boxes’ locations shall be coordinated with all other trades such that all are accessible.

G. Wall mounted junction boxes and terminal cabinets shall be mounted at a maximum height of 60”

AFF.

3.4 INSTALLATION OF GUTTERS:

A. Conductors serving a wiring gutter shall be extended without reduction in size for the entire length of the gutter.

END OF SECTION 260535

SECTION 260535 BOXES FOR ELECTRICAL SYSTEMS
1.1 SCOPE:
2.
2.1 GENERAL:
2.2 OUTLET BOXES:
2.3 JUNCTION BOXES AND PULL BOXES (INTERIOR):
2.4 JUNCTION AND PULL BOXES (EXTERIOR):
2.5 CABINETS:
3.
3.1 INSTALLATION:
3.2 INSTALLATION OF OUTLET BOXES:
3.3 INSTALLATION OF JUNCTION BOXES:
3.4 INSTALLATION OF GUTTERS: