262726_Wiring_Devices.pdf
PDF 121 KB Posted
- Attached to
- Volusia County Branch Jail Air Handler-Fire Suppression System Removal, Replacement and Upgrade
- Solicitation number
- 26-B-110IF
- Issued by
- Volusia County, Florida
About this file
This is a Scope of Work specification document for Volusia County, Florida, detailing wiring devices required for the Branch Jail renovation project scheduled for bid on December 5, 2025. The specification outlines requirements for switches, receptacles, contactors, and time clocks to be installed throughout the facility located at 1300 Red John Drive, Daytona Beach, Florida. Switches must be specification-grade, silent-operation toggle types rated for 20 amps at 120-277 volts AC, available as single-pole single-throw or 3-way configurations from manufacturers including Eaton-Arrow-Hart, Hubbell, or Bryant. Receptacles shall be specification-grade, tamper-resistant duplex types rated for 20 amps at 125 volts, NEMA 5-20 configuration, with isolated grounding and ground fault circuit interrupter options available. Weatherproof receptacles must feature gasket-sealed, key-lockable flip covers, and surge suppression outlets are required in specified locations. The contractor is responsible for providing all final wiring pigtails for air handling units, air conditioning units, water heaters, and other equipment connections. Device plates must match manufacturer specifications with grey devices and stainless steel plates for unfinished and back-of-house spaces, while galvanized plates with rounded edges are required for surface-mounted devices in unfinished areas.
Installation requirements mandate adherence to manufacturer specifications, NECA installation standards, and the National Electrical Code, with coordination among all trades to ensure proper device placement. Standard mounting heights include receptacles at 18 inches above finished floor, telephone outlets at 18 inches, general switches at 42 inches, and countertop receptacles at a maximum of 46 inches, with all heights subject to field verification and ADA accessibility compliance. Devices must be located within 4 inches of door trim for switches and grouped within 4 inches of each other when shown on drawings. The contractor shall coordinate with architectural and interior design drawings to verify proper device locations relative to furniture, cabinetry, and millwork layouts. Back-to-back device boxes are prohibited; all boxes must be located in different stud frame areas with UL-approved fire sealing or putty packs to maintain ratings between walls and floors. Electrically or mechanically held contactors for lighting circuit control must be Square D Type L Class 8903 or equivalent, rated for 100-amp continuous load at 208 volts, with NEMA 1 surface-mounted enclosures. Electronic time clocks with 7-day load control, manual override, and battery backup are specified as Intermatic models ET173C or ET70215CR.
View the file
Other files
Show 40 more
Latest 50 of 128 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BID SET VOLUSIA COUNTY
DECEMBER 5, 2025 BRANCH JAIL
WIRING DEVICES 262726.00 - 1
SECTION 262726 WIRING DEVICES
PART 1 - GENERAL
1.1 SCOPE:
A. This section outlines the quality and requirements of the basic devices, switches, receptacles, etc., to be used and the installation instructions for the devices.
PART 2 - PRODUCTS
2.1 WIRING DEVICES:
A. Switches and receptacles shall be A.C. type of the kind indicated.
B. Switches shall be specification grade silent operation toggle rated for use at 20 amps, 120-277 volts
AC. SCHEDULE:
Acceptable Manufacturers
Switch Type Eaton-Arrow-Hart Hubbell # Bryant #
20A SPST 1221 1221 4901
20A 3-way 1223 1223 4903
C. Receptacles shall be specification grade tamper resistant type and shall be provided in duplex arrangement unless otherwise noted.
Acceptable Manufacturers
Receptacle Type Eaton-Arrow-Hart Hubbell Bryant #
20A Duplex 2P, 3W
125V, NEMA 5-20
TRBR20 5362T 5362T
20A Duplex xP 3W
125V NEMA 5-20
Isolated Grounding Type
IG5362 IG5362 BRY5362IG
Ground Fault Circuit Interrupters
VGF20 GF20 GF20
D. Weatherproof receptacles shall be GFCI types with gasketed key lockable flip cover type cover plates.
Cover plates shall be Eaton-Arrow-Hart #WIUMV-1X. Surge suppression type outlets shall be Arrow-Hart 5362BLS (blue) or equal.
E. Receptacles provided for attachment of cord and plug equipment shall be heavy duty, specification grade, non-interchangeable, flush mounted types of the proper NEMA configuration to serve the equipment. Device NEMA configurations shall be verified prior to installation of circuit conductors.
All power type outlets shall be twist lock type.
WIRING DEVICES 262726.00 - 2
F. Contractor shall provide all final wiring pigtails for all AHU, ACU, water heaters, and any other equipment or motor connection that is required.
2.2 PLATES AND ACCESSORIES:
A. All devices shall have proper plates, carpet flanges, trim, etc., as manufactured by same manufacturer as devices. Any telephone or other outlet which is not equipped with a plate furnished by others shall have one provided by this Contractor. Device plates shall be color and type as shown below.
B. Unfinished and Back of House Spaces:
1. Grey Devices
2. Stainless Steel Plates
C. Surface mounted devices in unfinished areas shall have galvanized plate with rounded edges.
2.3 ELECTRICALLY OR MECHANICALLY HELD CONTACTOR AND TIME CLOCKS:
A. Contactor for control of lighting circuits shall be Square D, Type L, Class 8903, or equivalent, in Allen-Bradley or Cutler Hammer. Contactor shall be mechanically (as indicated) operated, electrically or mechanically (as indicated) held type designed for two-wire control circuit, fully rated for tungsten, resistance, and ballast loads, and with 100-amp continuous load current rating and 208-volt voltage rating. Provide number of poles as required for circuits indicated. Contactors shall be furnished with NEMA 1 surface mounted enclosure unless otherwise called for on the drawings. All lighting contactors shall be identified as to circuits and loads controlled.
B. Time Clocks: Electronic type with 7-day load control. Provide integral manual override feature, and spring wound or battery carryover. Unit shall be Intermatic #ET173C #ET70215CR.
PART 3- EXECUTION
3.1 INSTALLATION:
A. All devices shall be installed so that only one wire is connected to each terminal.
B. Install all components in accordance with the manufacturer's written instructions, NECA's
"Standard of Installation", the applicable requirements of the National Electrical Code, and recognized industry practice.
C. Coordinate location of boxes prior to rough in with mill work cabinets, built-ins, marker and tack board and all other trades.
WIRING DEVICES 262726.00 - 3
3.2 MOUNTING HEIGHTS:
A. Mounting heights are approximate. The exact locations and mounting heights shall be determined on the job, and it shall be the Contractor's responsibility to coordinate with all trades to insure correct installation, i.e., over counters in or above back-splashes, in blocks walls, tile, and other specific construction features. Location of outlets mounted in built-ins, millwork, and cabinetry shall be verified. Outlets mounted in kick or toe spaces shall be mounted horizontally. Outlet boxes shall be mounted to prevent device plate from overlapping backsplash, trim, tile, etc. Locate so device plate will lay flat against surface completely around the perimeter of plate.
B. Outlets, other than those coordinated with counter tops, shelves, and cabinets, shall be located with the center line of outlet boxes the following distance above the finished floor, unless otherwise indicated:
1. Receptacles, General 1’-6”
2. Telephone Outlets: 1'-6"
3. Switches, General: 3’-6”
4. Receptacles, countertop maximum height: 3’-10” (Field Verify)
C. All device mounting heights shall be in accordance with requirements for making buildings accessible to the handicapped. (ADA)
3.3 GENERAL MOUNTING:
A. Verify all door swings with the Architectural drawings. Locate boxes for light switches within 4" of door trim. Where switches are shown on the drawing grouped together and shall be installed under a single plate. Where required, barriers shall be provided in the outlet boxes.
B. Where receptacles, telephone outlets, computer outlets, TV outlets and auxiliary system outlets are shown on the drawings grouped together they shall be installed with a maximum of 4" between outlets. Coordinate the actual dimensions in the field.
C. Devices and associated plates shall not be used as supports. Outlet boxes shall be rigidly supported from structural members.
D. Contractor shall review all drawings of the Architect and Interior design team in order to locate all devices and lighting fixtures properly and finally with the furniture, cabinet, and millwork layouts.
E. Back-to-Back to back devices and or device boxes and Panels shall not be utilized. Locate all boxes within a different stud frame area and provide UL approved fire sealing and or Putty packs as required to maintain the UL listing between walls and floors.
END OF SECTION 262726
| 1. |
| 1.1 SCOPE: |
| 2. |
| 2.1 WIRING DEVICES: |
| 2.2 PLATES AND ACCESSORIES: |
| 2.3 ELECTRICALLY OR MECHANICALLY HELD CONTACTOR AND TIME CLOCKS: |
| 3. |
| 3.1 INSTALLATION: |
| 3.2 MOUNTING HEIGHTS: |
| 3.3 GENERAL MOUNTING: |
| END OF SECTION 262726 |