262816_Safety_Switches.pdf

PDF 104 KB Posted

Attached to
Volusia County Branch Jail Air Handler-Fire Suppression System Removal, Replacement and Upgrade
Solicitation number
26-B-110IF
Issued by
Volusia County, Florida

About this file

This is a specification document for safety switches required for the Volusia County Branch Jail facility located at 1300 Red John Drive, Daytona Beach, Florida, as part of a comprehensive air handler and fire suppression system replacement and upgrade project. The specification outlines requirements for quick-make, quick-break, NEMA heavy-duty type safety switches to be installed for branch circuits and general use throughout the facility. Switches must be fused or non-fused as indicated on drawings, with fully visible switch blades in the off position and mechanical lugs sized for copper or aluminum conductors. Acceptable manufacturers are Square D, Eaton, ITE, and Siemens, and all switches must be coordinated with other distribution equipment from the same manufacturer.

Installation requirements mandate that safety switches be located with proper clearance and access in accordance with the National Electrical Code (NEC), with motor disconnect switches rated by horsepower and non-motor load switches sized according to equipment full-load current. Switches must be mounted in NEMA 1 enclosures under standard conditions or NEMA 3R steel enclosures for moisture-prone areas and outdoor installations. All switches require mounting at 60 inches above finished floor to the top of the enclosure unless otherwise specified, with Class R fuses and rejection clips required for elevator motor connections. Permanent identification labels must be provided for all safety switches, and roof-mounted disconnects and safety switches require permanent printed ampacity rating labels on the inside cover per Brevard County requirements. Adequate support must be provided for mounting, and switches shall not be mounted directly to the equipment they serve.

View the file

Other files

File Type Posted
Volusia_County_Branch_Jail_Air_Handler-Fire_Suppression_System_Removal,_Replacement_and_Upgrade_(Addendum_#6_Revision).pdf PDF
Exhibit_R_-_VCBJ_Existing_Drawings_(As-Builts)_1983.pdf PDF
Exhibit_Q_-_NFPA_72_Inspection_Documents.pdf PDF
Exhibit_P_-_E4.03_-_FLOOR_PLAN_C_-_SKETCH_(REPLACES_ALL_PREVIOUS_VERSIONS)_(1).pdf PDF
Exhibit_O_-_E4.01_-_FLOOR_PLAN_A_-_SKETCH_(REPLACES_ALL_PREVIOUS_VERSIONS).pdf PDF
Exhibit_N_-_238216.11_Hydronic_Air_Coils_(REPLACES_ALL_PREVIOUS_VERSIONS).pdf PDF
Volusia_County_Branch_Jail_Air_Handler-Fire_Suppression_System_Removal,_Replacement_and_Upgrade_(Addendum_#3_Revision).pdf PDF
Exhibit_M_-_Diagram_RTU_Curb_and_Tie_Down.pdf PDF
Volusia_County_Branch_Jail_Air_Handler-Fire_Suppression_System_Removal,_Replacement_and_Upgrade_(Addendum_#1_Revision).pdf PDF
Volusia_County_Branch_Jail_Air_Handler-Fire_Suppression_System_Removal,_Replacement_and_Upgrade.pdf PDF
Exhibit_L_-_Contractor_-_Vendor_Background_Packet_Rev_05-22-2025.pdf PDF
Exhibit_K_-_Pre-Bid_Parking_Map.pdf PDF
Exhibit_J_-_VCBJ_Bidder_Disclaimer_and_Notice_to_Bidders.pdf PDF
Exhibit_I_-_VC_Branch_Jail_AHU_Fire_Suppression_Scope.pdf PDF
Exhibit_H_-_Special_Conditions_26-B-110IF.pdf PDF
Exhibit_G_-_Bid_Price_Sheet_26-B-110IF.xlsx XLSX spreadsheet
Exhibit_F_-_Sales_Tax_Exemption_Procedures.pdf PDF
Exhibit_E_-_Technical_Specifications.pdf PDF
Exhibit_D_-_Construction_Plans.pdf PDF
Exhibit_C_-_Draft_Contract_26-B-110IF.pdf PDF
Exhibit_B_-_PRIME-SUB_FORM_for_Contractors_26-B-110IF.xlsx XLSX spreadsheet
Exhibit_A_-_Insurance_Requirements_26-B-110IF.pdf PDF
Construction_Bid_Request_Air_Handler.docx DOCX document
Pre-Bid_Meeting_Invitee_Listing_(1).docx DOCX document
283000_Digital,_Addressable_Fire_Alarm_System.pdf PDF
Table_of_Contents.pdf PDF
270500_Special_Systems.pdf PDF
264313_Surge_Protection_Devices.pdf PDF
260501_Electrical_Scope.pdf PDF
260533_Raceways_-_Metal.pdf PDF
262726_Wiring_Devices.pdf PDF
233300_Air_Duct_Accessories.pdf PDF
260534_Raceways_-_Non-metallic.pdf PDF
262813_Fuses.pdf PDF
260519_Low-Voltage_Electrical_Power_Conductors_and_Cables.pdf PDF
VCBJ_Bidder_Disclaimer.docx DOCX document
264113_Lightning_Protection_System.pdf PDF
260535_Boxes_for_Electrical_Systems.pdf PDF
Special_Conditions.docx DOCX document
232923_Variable_Frequency_Motor_Controllers.pdf PDF
237313_Modular_Indoor_Central_Station_Air_Handler_Units.pdf PDF
237413_Packaged,_Outdoor,_Central_Station_Rooftop_Units.pdf PDF
230529_Hangers_and_Supports_for_HVAC_Piping.pdf PDF
230519_Meters_and_Gages_for_HVAC_Piping.pdf PDF
260526_Grounding_and_Bonding_for_Electrical_Systems.pdf PDF
262416_Panelboards.pdf PDF
230548_Vibration_Controls_for_HVAC.pdf PDF
MD3.1_-_ENLARGED_MECHANICAL_ROOM_DEMO_PLAN.pdf PDF
260502_Basic_Materials_&_Methods.pdf PDF
VCDCH_Fire_Damper_100%CD_Submission_G-001_Cover_Sheet.pdf PDF
Show 40 more

Latest 50 of 128 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BID SET VOLUSIA COUNTY

DECEMBER 5, 2025 BRANCH JAIL

SAFETY SWITCHES 262816.00 - 1

SECTION 262816 - SAFETY SWITCHES

PART 1 - GENERAL

1.1 SCOPE:

A. This section deals with safety switches for branch circuits and general use.

PART 2 - PRODUCTS

2.1 SAFETY SWITCHES:

A. Switches shall be quick-make, quick-break, NEMA heavy duty type HD sized as shown on drawings and as specified, fused or non-fused as shown or as required to maintain NEMA and UL listing of equipment served. Switch blades shall be fully visible in the off position. Switches shall not utilize circuit breaker components or butt type blow-off contacts.

B. Lugs shall be mechanical for copper or aluminum conductors and sized for conductors as shown.

C. Safety switches shall be of the same manufacturer as all other distribution equipment

D. Switches shall be by Square D, Eaton, ITE Siemens

PART 3 - EXECUTION:

3.1 SAFETY SWITCHES:

A. Safety switches shall be installed as shown on the plans and in accordance with NEC. Locate for proper clearance and access.

B. Disconnect switches for motors shall be rated in horsepower and shall be sized for motor served.

C. Disconnect switches for non-motor loads shall be sized in accordance with equipment full load current. Safety switches shall be installed in NEMA 1 enclosures except where installed in locations subject to moisture within kitchens and/or installed outdoors in which case safety switches shall have a NEMA 3R steel enclosure and except where other types of enclosures are shown or indicated on the drawings.

D. Adequate support shall be provided for mounting safety switches. Switches shall not be mounted directly to the equipment they serve. Switches shall be located so that the equipment served may be removed without dismantling the branch circuit.

E. Mount safety switches 60" AFF to top of enclosure U.O.N.

F. Provide Class R fuses and rejection clips for all fused disconnect switches serving Elevator motor connections.

G. Provide permanent identification label for all safety switches.

BID SET VOLUSIA COUNTY

DECEMBER 5, 2025 BRANCH JAIL

SAFETY SWITCHES 262816.00 - 2

H. All roof mounted Disconnect and Safety switches shall have a permanent printed label on the inside cover of the switch indicating the switch ampacity rating per Brevard County requirements.

END OF SECTION 262816

1.
1.1 SCOPE:
2.
2.1 SAFETY SWITCHES:
3.
3.1 SAFETY SWITCHES: