260519_Low-Voltage_Electrical_Power_Conductors_and_Cables.pdf

PDF 118 KB Posted

Attached to
Volusia County Branch Jail Air Handler-Fire Suppression System Removal, Replacement and Upgrade
Solicitation number
26-B-110IF
Issued by
Volusia County, Florida

About this file

This is a technical specification document for low-voltage electrical power conductors and cables prepared by Volusia County for the Branch Jail facility located at 1300 Red John Drive, Daytona Beach, Florida. The specification outlines requirements for wire and cable installation as part of a comprehensive replacement and upgrade project addressing the facility's air handling unit infrastructure, fire/smoke damper systems, and building automation controls. The document details conductor specifications, including minimum wire gauges (#12 AWG average minimum for 20-amp circuits), insulation types (THWN/THHN), and manufacturer requirements (Southwire Corporation or approved equal). Installation requirements include conductor placement in conduit, prohibition of splices in certain systems (control, security, fire alarm, television, and communications), and mandatory color coding standards for branch circuits and feeders based on voltage systems (120/208 volts and 277/480 volts phases).

The specification establishes comprehensive execution standards for wire and cable installation within the correctional facility, requiring all conductors to be continuous and unspliced where installed in conduit, with splices permitted only within wiring troughs, wireways, junction boxes, outlet boxes, or equipment enclosures. Wire connections for conductors larger than #10 must use solderless connectors covered with electrical tape, while connections in exterior, handholes, and underground locations must be completely watertight and waterproof. Additional requirements include the provision of identifying tags or pressure-sensitive labels on all cables and feeders corresponding to drawing markings, strict adherence to specified color coding (phase tape is not permitted), and coordination with the utility company for main electrical service installation and secondary connections to transformer equipment. The document specifies that fixture wire shall be type THHN with maximum length of 6 feet from fixture to first junction box, and control wire shall be minimum #12 AWG copper with full color range as indicated for individual systems.

View the file

Other files

File Type Posted
Volusia_County_Branch_Jail_Air_Handler-Fire_Suppression_System_Removal,_Replacement_and_Upgrade_(Addendum_#6_Revision).pdf PDF
Exhibit_R_-_VCBJ_Existing_Drawings_(As-Builts)_1983.pdf PDF
Exhibit_Q_-_NFPA_72_Inspection_Documents.pdf PDF
Exhibit_P_-_E4.03_-_FLOOR_PLAN_C_-_SKETCH_(REPLACES_ALL_PREVIOUS_VERSIONS)_(1).pdf PDF
Exhibit_O_-_E4.01_-_FLOOR_PLAN_A_-_SKETCH_(REPLACES_ALL_PREVIOUS_VERSIONS).pdf PDF
Exhibit_N_-_238216.11_Hydronic_Air_Coils_(REPLACES_ALL_PREVIOUS_VERSIONS).pdf PDF
Volusia_County_Branch_Jail_Air_Handler-Fire_Suppression_System_Removal,_Replacement_and_Upgrade_(Addendum_#3_Revision).pdf PDF
Exhibit_M_-_Diagram_RTU_Curb_and_Tie_Down.pdf PDF
Volusia_County_Branch_Jail_Air_Handler-Fire_Suppression_System_Removal,_Replacement_and_Upgrade_(Addendum_#1_Revision).pdf PDF
Volusia_County_Branch_Jail_Air_Handler-Fire_Suppression_System_Removal,_Replacement_and_Upgrade.pdf PDF
Exhibit_L_-_Contractor_-_Vendor_Background_Packet_Rev_05-22-2025.pdf PDF
Exhibit_K_-_Pre-Bid_Parking_Map.pdf PDF
Exhibit_J_-_VCBJ_Bidder_Disclaimer_and_Notice_to_Bidders.pdf PDF
Exhibit_I_-_VC_Branch_Jail_AHU_Fire_Suppression_Scope.pdf PDF
Exhibit_H_-_Special_Conditions_26-B-110IF.pdf PDF
Exhibit_G_-_Bid_Price_Sheet_26-B-110IF.xlsx XLSX spreadsheet
Exhibit_F_-_Sales_Tax_Exemption_Procedures.pdf PDF
Exhibit_E_-_Technical_Specifications.pdf PDF
Exhibit_D_-_Construction_Plans.pdf PDF
Exhibit_C_-_Draft_Contract_26-B-110IF.pdf PDF
Exhibit_B_-_PRIME-SUB_FORM_for_Contractors_26-B-110IF.xlsx XLSX spreadsheet
Exhibit_A_-_Insurance_Requirements_26-B-110IF.pdf PDF
Construction_Bid_Request_Air_Handler.docx DOCX document
Pre-Bid_Meeting_Invitee_Listing_(1).docx DOCX document
283000_Digital,_Addressable_Fire_Alarm_System.pdf PDF
Table_of_Contents.pdf PDF
270500_Special_Systems.pdf PDF
264313_Surge_Protection_Devices.pdf PDF
260501_Electrical_Scope.pdf PDF
260533_Raceways_-_Metal.pdf PDF
262726_Wiring_Devices.pdf PDF
233300_Air_Duct_Accessories.pdf PDF
260534_Raceways_-_Non-metallic.pdf PDF
262813_Fuses.pdf PDF
262816_Safety_Switches.pdf PDF
VCBJ_Bidder_Disclaimer.docx DOCX document
264113_Lightning_Protection_System.pdf PDF
260535_Boxes_for_Electrical_Systems.pdf PDF
Special_Conditions.docx DOCX document
232923_Variable_Frequency_Motor_Controllers.pdf PDF
237313_Modular_Indoor_Central_Station_Air_Handler_Units.pdf PDF
237413_Packaged,_Outdoor,_Central_Station_Rooftop_Units.pdf PDF
230529_Hangers_and_Supports_for_HVAC_Piping.pdf PDF
230519_Meters_and_Gages_for_HVAC_Piping.pdf PDF
260526_Grounding_and_Bonding_for_Electrical_Systems.pdf PDF
262416_Panelboards.pdf PDF
230548_Vibration_Controls_for_HVAC.pdf PDF
MD3.1_-_ENLARGED_MECHANICAL_ROOM_DEMO_PLAN.pdf PDF
260502_Basic_Materials_&_Methods.pdf PDF
VCDCH_Fire_Damper_100%CD_Submission_G-001_Cover_Sheet.pdf PDF
Show 40 more

Latest 50 of 128 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BID SET VOLUSIA COUNTY

DECEMBER 5, 2025 BRANCH JAIL

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519.00 - 1

SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS/CABLES

PART 1 - GENERAL

1.1 SCOPE:

A. This section outlines the quality and type of conductors to be used in the various systems, locations, and conditions.

PART 2 - PRODUCTS

2.1 WIRE AND CABLE 600 VOLT:

A. GENERAL:

1. Conductors shall have current carrying capacities as per NEC and with 600-volt insulation, #12 AWG average minimum for 20-amp circuits except for controls, and fixture wire.

Conductors shall be copper./GENERAL USE:

1. #12 and #10 shall be solid, type THWN/THHN insulation.

C. FEEDERS AND GENERAL USE:

1. #8 awg and larger, and any size to motors shall be stranded type THWN.

D. FIXTURE WIRE:

1. Fixture wire shall be type THHN may be used in the channel of and flex to all fixtures. Wire size shall be #12 AWG for all fixtures. Fixture wire shall extend only from the fixture to the first junction box and not over 6' in length.

E. CONTROL WIRE:

1. Control wire shall be minimum #12 AWG copper, type THHN-THWN. Full color range as indicated for individual systems. See other sections of the specifications for requirements.

F. MANUFACTURER:

1. Wire and cable shall be as manufactured by Southwire Corporation or approved equal.

G. WIRE CONNECTIONS:

1. On wire larger than #10 shall be made with approved solderless connectors and covered with Scotch #33 electrical tape so that insulation is Owner approved equal to conductor insulation.

2. All connections and splices in exterior, handholes, pull/junction boxes, and underground locations shall be made completely watertight and waterproof.

H. #10 AND SMALLER COPPER CONNECTIONS:

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519.00 - 2

1. Shall be made with T & B Sta-Kon wire joints, PT series, complete with insulating caps and installed with WT161 Tool or WT2000 Tool, Ideal Super-Nuts (not wire nuts), Ideal Wing Nuts, or Buchanan Elec. Products B Cap or Series 2000 Pres-Sure connectors complete with nylon snap-on insulators and installed with C24 pressure tool.

PART 3 - EXECUTION

3.1 INSTALLATION OF WIRE AND CABLE:

A. No conductor shall be smaller than #12 except where so designated on the drawings or hereinafter specified.

B. All conductors, wire, and cable shall be installed in conduit unless otherwise noted.

C. Multi-wire lighting branches shall be used as indicated.

D. All joints and splices in wire shall be made with approved solderless connectors and covered so that insulation is Owner approved equal to conductor insulation. Splices shall not be permitted in control, security, fire alarm, television, or communications systems, or where otherwise noted.

Splicing of wire or cables will not be allowed below grade, including within boxes below grade.

E. No splices shall be pulled or installed into conduit.

F. Both conductors and conduits shall be continuous from outlet to outlet.

G. No conductor shall be pulled until conduit is cleaned of all foreign matter.

H. In installing the main electrical service, additional slack conductors shall be provided and terminated as required by electric utility for connection to utility equipment. Field coordinate with the power utility company prior to installing conductors. Contractor shall provide all secondary connections to utility company transformer per utility company requirements. Provide all lugs, spade conductors, etc., per drawing and utility company requirements.

I. In installing parallel conductors, it is mandatory that all conductors making up the feeder be exactly the same length, the same size, and the same type of conductor with the same insulation. Further, each group of conductors making up a phase or neutral must be bonded at both ends in an approved manner.

J. Conductor sizes indicated on circuit homeruns or in panelboard schedules shall be installed over the entire length of the circuit unless noted otherwise on the drawings.

K. Conductors shall be continuous and unspliced where installed in conduit. Splices shall occur only within wiring troughs, wireways, junction boxes, outlet boxes, or equipment enclosures where sufficient additional room is provided for all splices.

L. Provide isolated ground conductors per drawing requirements.

3.2 CIRCUITS AND BRANCH CIRCUITS:

A. Outlets shall be connected to branch circuits as indicated on drawings. No more outlets than are

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519.00 - 3

indicated shall be connected to a circuit.

3.3 WIRE AND CABLE DESIGNATION AND COLOR CODING:

A. Non-ferrous identifying tags or pressure sensitive labels shall be securely fastened to all cables, feeders, and power circuits in panels, starters, terminations of cables, etc. Tags or labels shall be stamped or printed to correspond with markings on drawings so that feeder or cable number and phase can be readily identified.

B. Each branch circuit and feeder conductor shall be color coded. For all conductor sizes the entire insulation shall be of the color as indicated below. Color code shall be strictly adhered to. Phase tape is not permitted.

120/208 Volts Phase Color

A Black B Red C Blue

Neutral White Ground Green

277/480 Volts

Phase Color

A Brown B Orange C Black

Neutral Gray Ground Green

END OF SECTION 260519