This is a Design Criteria and Facility Standards Manual section document from the University of Maryland, College Park, detailing electrical controls standards and specifications. The document, effective July 10, 2009, outlines design requirements and installation standards for automatic transfer switch systems, switchgear gateways, generator monitoring systems, and lighting control systems applicable to UMCP facilities. The standards reference applicable NEMA and ANSI specifications including NEMA ICS 2, ANSI/NEMA ICS 4, and NEMA ICS 6. Required submittals include shop drawings with control device enclosure wiring diagrams and panel layouts, product data for each specified control device, and operating and maintenance instructions for adjustment, repair, cleaning, and lubrication procedures.
The document specifies detailed product requirements for lighting control components including heavy-duty oil-tight control switches and stations rated to Class A150, photocell switches with gasketed feralloy enclosures, magnetic control relays rated Class A300, time-delay relays rated Class A600, and clock timers with 24-hour, 7-day astronomical dials. All enclosures must comply with NEMA Type 1 standards for interior applications and NEMA Type 4 for exterior use, with coil voltages at 120 volts, 60 Hz, single phase. For generator and automatic transfer switch integration, connection to building automation system gateways is required to monitor and transmit data points including battery voltage, oil pressure and temperature, fuel level, engine status, and power metrics. Electrical switchgear gateway integration must provide monitoring data for each breaker including apparent and active energy, breaker status, and protective device settings.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 3 Page.pdf | ||
| 26 40 00.pdf | ||
| Attachment 4.pdf | ||
| 26 32 00.pdf | ||
| 33 71 00.pdf | ||
| Additional Drawings.zip | ZIP file | |
| 26 56 00.pdf | ||
| AMENDMENT 002- RFP 00042061.pdf | ||
| Attachment 7.pdf | ||
| Questions RFP No. 00042061.pdf | ||
| AMENDMENT 001 - RFP 00042061.pdf | ||
| 26 05 01.pdf | ||
| AMENDMENT 004- RFP 00042061.pdf | ||
| AMENDMENT 003- RFP 00042061.pdf | ||
| Attachment 5.pdf | ||
| Attachment 6.pdf | ||
| 26 05 00.pdf | ||
| 26 29 23.pdf | ||
| RFP No. 00042061 Rooftop solar PV v2.pdf | ||
| Attachment 7- Proposer Submission Checklist (3).xlsx | XLSX spreadsheet | |
| 33_00_00.pdf | ||
| Attachment2.pdf | ||
| 26 01 00.pdf | ||
| 26 51 00.pdf | ||
| Attachment 1.pdf | ||
| 26 56 00.pdf | ||
| 33 71 00.pdf | ||
| 33_00_00.pdf | ||
| 26 05 00.pdf | ||
| 26 01 00.pdf | ||
| 26 51 00.pdf | ||
| 26 05 01.pdf | ||
| 26 29 23.pdf | ||
| 26 40 00.pdf | ||
| 26 32 00.pdf | ||
| 26 09 00.pdf |
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Electrical Controls 26.09.00
Design Criteria/Facility Standards Manual Page 1 University of Maryland, College Park
Description:
The purpose of the section is to highlight the current applicable UMCP Design Standards for the design, selection and installation of Automatic Transfer Switch systems, switchgear gateways, generator monitoring systems and lighting control systems.
Related Sections:
● TBD
Effective Date:
● July 10, 2009
Applicable Standards:
● NEMA ICS 2
● ANSI/NEMA ICS 4
● NEMA ICS 6
General Requirements:
1. Required Submittals:
● Shop Drawings: Indicate control device enclosure wiring diagrams and panel layout drawings
● Product Data: Provide data on each control device specified
● Operating and Maintenance Instructions: Include instructions on adjusting, repairing, cleaning, and lubricating each control device specified
2. Lighting Control Product Requirements:
● Control Switches and Stations
● Description: Heavy duty, oil-tight control switches and stations manufactured to NEMA ICS 2
● Contact Ratings: Class A150
● Photocells Switch
● Description: Photocell switch manufactured to NEMA ICS 2
● Ratings: Contact Ratings: Class A150
● Enclosure: Gasketed, cast feralloy box with conduit hub
● Relays
● Description: Relays manufactured to NEMA ICS 2
● Magnetic Control Relay: Class A300
● Time-Delay Relay: Class A600
● Ratings:
● Contact Ratings: Minimum Class A150
● Coil Voltage: 120 volts, 60 Hz., Single Phase
● Enclosure: NEMA Type 1 for interior and NEMA type 4 for exterior use
● Time Switch
● Description: Clock timer manufactured to NEMA ICS 2, with astronomical dial
● Ratings:
● Contact Ratings: Class A150; SPST
● Coil Voltage: 120 volts, 60 Hz., Single Phase
● Dial Time: 24 hours, 7 days
● Enclosure: NEMA Type 1 for indoor applications, and NEMA Type 4 for outdoor applications
Electrical Controls 26.09.00
Design Criteria/Facility Standards Manual Page 2 University of Maryland, College Park
● Control Device Enclosures
● Description: Shop, fabricate and wire control device enclosures to NEMA ICS 1, for groupings of more than one device
● Use hinged cover enclosures under provisions of 26.05.00
● Terminal Blocks: ANSI/NEMA ICS 4
● Fabrication: Shop assemble to NEMA ICS 6 - Use plastic wiring through to route internal wiring
● Installation Requirements
● Install control devices in accordance with manufacturer’s instructions
● Install individual components in enclosures
● Connect control devices to systems controlled, to achieve proper system operation
● Adjustments
● Adjust time delay relays and clock timers to achieve specified system operation.
3. Generator and Automatic Transfer Switch Building Automation Integration:
● Connection shall be made to the generators monitoring system gateway to establish communication to the building automation system; If available by manufacturer, the following points shall be brought out to the building automation system:
● Battery Voltage
● Oil Pressure
● Oil Temperature
● Coolant Temperature
● Fuel Level/Rate
● Engine Start
● Engine Stop
● Total kWH
● Frequency
● Connection shall be made the Automatic Transfer Switch monitoring system gateway to establish communication to the building automation system. The Following points shall be brough out:
● Utility Source Availability
● Generator Source Availability
● Utility Average Voltage (Phase to Phase)
● Utility Average Current
● Utility Frequency
● Generator Average Voltage (Phase to Phase)
● Generator Average Current
● Generator Frequency
● Electrical Switchgear Gateway Integration for Trip Units Connection shall be made to the buildings main switchgear monitoring system gateway to establish communication to the building automation system. The following points shall be brought out for each breaker:
● Apparent Energy
● Active Energy
● Active Energy Total
● Breaker Status (Open/Closed)
● Long Time Pick Up (Ir)
● Short Time Pick Up (Isd)
● Instantaneous (Ii)
● Ground Fault (lg)