26 05 00 - COMMON WORK RESULTS FOR ELECTRICAL Specs.pdf

PDF 400 KB Posted

Attached to
DPW Minor Construction Program MATOC Federal contract opportunity
Solicitation number
W91247-22-R-0064
Issued by
Department of the Army Materiel Command Mission and Installation Contracting Command

View the file

Other files for this federal contract opportunity

Other files attached to DPW Minor Construction Program MATOC, newest first.
File Type Posted
W91247-22-R-0064 Amendment 0002 4 Aug.pdf PDF
Attachment 1 FA-00040-22 Seed Project Final SOW 20 July.pdf PDF
QAs W9124722R0064 Solicitation 19 July 22.pdf PDF
W91247-16-R-0064 Final RV5 18 July.pdf.pdf PDF
W91247-22-R-0064 Amendment 00001.pdf PDF
W91247-16-R-0064 Final RV3 7 July.pdf PDF
22 00 00 PLUMBING GENERAL PURPOSE Specs.pdf PDF
01 Size_Standards_Table (Effective Aug 19 2019) 236220 pg.5.pdf PDF
07 60 00 - FLASHING AND SHEET METAL Specs.pdf PDF
Attachment 2 - 09 06 00 - SCHEDULES FOR FINISHES Specs.pdf PDF
09 30 10 CERAMIC PORCELAIN QUARRY AND MOSAIC TILING Specs.pdf PDF
09 90 00 - PAINTINGS AND COATINGS Specs.pdf PDF
26 05 26.doc_safe Specs.pdf PDF
01 00 00 - STANDARD ABBREVIATIONS Specs.pdf PDF
09 22 00.pdf_safe Specs.pdf PDF
Attachment 3 - Seed Project Price Schedule final.xlsx XLSX spreadsheet
attachment 1 - FA-00040-22 Seed Project SOW final.pdf PDF
23 00 00 AIR SUPPLY DISTRIBUTION VENTILATION AND EXHAUST SYSTEMS Specs.pdf PDF
09 26 00 - GYPSUM AND CEMENTITIOUS BOARD ASSEMBLIES Specs.pdf PDF
08 14 00 - WOOD DOORS Specs.pdf PDF
09 65 00 - RESILIENT FLOORING specs.pdf PDF
32 31 13.pdf_safe Specs.pdf PDF
32 31 13.53.pdf_safe Specs.pdf PDF
02 85 00 - MOLD REMEDIATION Specs.pdf PDF
W91247-22-R-0064 Matoc Sol final RV2 7july.pdf PDF
08 71 00 - DOOR HARDWARE Specs.pdf PDF
26 20 00.pdf_safe Specs.pdf PDF
09 51 00 - ACOUSTICAL CEILINGS Specs.pdf PDF
23 23 00.pdf_safe Specs.pdf PDF
26 05 19.pdf_safe Specs.pdf PDF
Attachment 4 - MAIDIQ Cap Rates.xlsx XLSX spreadsheet
Show all 31

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IDG Updated: 13 Jul 2021

SECTION 26 05 00. PAGE 1 OF 6

DIVISION 26 – ELECTRICAL

SECTION 26 05 00

COMMON WORK RESULTS FOR ELECTRICAL

PART 1 GENERAL

1.1 REFERENCES: The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

a. ASTM INTERNATIONAL (ASTM)

i. ASTM D709, (2017) Standard Specification for Laminated Thermosetting

Materials

b. ELECTRONIC INDUSTRIES ALLIANCE (EIA)

i. EIA 480, (1981) Toggle Switches

c. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

i. IEEE Stds Dictionary, (2009) IEEE Standards Dictionary: Glossary of

Terms & Definitions

d. INTERNATIONAL CODE COUNCIL (ICC)

i. ICC/ANSI A117.1, (2009) Accessible and Usable Buildings and Facilities

e. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

i. ANSI Z535.1, (2017) American National Standard for Safety--Color Code

ii. ANSI/NEMA OS 1, (2013) Sheet-Steel Outlet Boxes, Device Boxes, Covers, and Box Supports

iii. NEMA 250, (2018) Enclosures for Electrical Equipment (1000 Volts

Maximum

iv. NEMA FB 1, (2014) Standard for Fittings, Cast Metal Boxes, and Conduit

Bodies for Conduit, Electrical Metallic Tubing, and Cable

v. NEMA KS 1, (2013) Enclosed and Miscellaneous Distribution Equipment

Switches (600 V Maximum)

vi. NEMA PB 1, (2011) Panelboards

SECTION 26 05 00. PAGE 2 OF 6

vii. NEMA RN 1, (2005; R 2013) Polyvinyl-Chloride (PVC) Externally

Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit

viii. NEMA TC 2, (2013) Standard for Electrical Polyvinyl Chloride (PVC)

Conduit

ix. NEMA TC 3, (2015) Standard for Polyvinyl Chloride (PVC) Fittings for

Use With Rigid PVC Conduit and Tubing

x. NEMA VE 1, (2009) Standard for Metal Cable Tray Systems

xi. NEMA WD 1, (1999; R 2015) Standard for General Color Requirements for Wiring Devices

xii. NEMA WD 6, (2016) Wiring Devices Dimensions Specifications

f. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

i. NFPA 70, (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2; TIA 17-3; TIA

17-4; TIA 17-5; TIA 17-6; TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;

TIA 17-11; TIA 17-12; TIA 17-13; TIA 17-14) National Electrical Code

g. UNDERWRITERS LABORATORIES (UL)

i. UL 1, (2005; Reprint Jul 2012) Standard for Flexible Metal Conduit

ii. UL 1242, (2006; Reprint Mar 2014) Standard for Electrical Intermediate

Metal Conduit – Steel

iii. UL 489, (2016) UL Standard for Safety Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures

iv. UL 6, (2007; Reprint Nov 2014) Electrical Rigid Metal Conduit-Steel

v. UL 797, (2007; Reprint Dec 2012) Electrical Metallic Tubing – Steel

vi. UL 870, (2016) UL Standard for Safety Wireways, Auxiliary Gutters, and

Associated Fittings

1.2 DEFINITIONS

a. Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, are as defined in IEEE Stds Dictionary.

SECTION 26 05 00. PAGE 3 OF 6

b. The technical sections referred to herein are those specification sections that describe products, installation procedures, and equipment operations and that refer to this section for detailed description of submittal types.

1.3 SUBMITTALS: Submit the following in accordance with Section 01 33 00 Submittals

a. SD-01 Preconstruction Submittals: Material, Equipment, and Fixture Lists

b. SD-03 Product Data: Conduits and Raceways, Wire and Cable, Splices and

Connectors, Switches, Receptacles, Outlet Boxes, Pull Boxes and Junction Boxes, Circuit Breakers, Panelboards, Lamps and Lighting Fixtures

c. SD-06 Test Reports: Continuity Test, Phase-Rotation Tests, Insulation Resistance

Test

d. SD-08 Manufacturer's Instructions: Manufacturer's Instructions

PART 2 PRODUCTS

2.1 EQUIPMENT: Provide the standard cataloged materials and equipment of manufacturers regularly engaged in the manufacture of the products. For material, equipment, and fixture lists submittals, show manufacturer's style or catalog numbers, specification and drawing reference numbers, warranty information, and fabrication site.

2.2 CONDUITS AND RACEWAYS

a. Rigid Steel Conduit: Provide hot dipped galvanized rigid steel conduit complying with UL 6. Except where installed underground, or in corrosive areas, provide polyvinylchloride (PVC), or painted with bitumastic coated rigid steel conduit in accordance with NEMA RN 1.

i. Use threaded fittings for rigid steel conduit.

ii. Use solid gaskets. Ensure conduit fittings with blank covers have gaskets, except in clean, dry areas or at the lowest point of a conduit run where drainage is required.

iii. Provide covers with captive screws and are accessible after the work has been completed

b. Electrical Metallic Tubing (EMT): Ensure EMT is in accordance with UL 797 and is zinc coated steel. Provide zinc-coated couplings and connectors that are rain

SECTION 26 05 00. PAGE 4 OF 6

tight, gland compression type with insulation throat. Crimp, spring, or setscrew type fittings are not acceptable.

c. Flexible Metallic Conduit: Ensure flexible metallic conduit is galvanized steel and complies with UL 1.

i. Ensure fittings for flexible metallic conduit are specifically designed for such conduit.

ii. Provide liquid tight flexible metallic conduit with a protective jacket of

PVC extruded over a flexible interlocked galvanized steel core to protect wiring against moisture, oil, chemicals, and corrosive fumes.

iii. Ensure fittings for liquid tight flexible metallic conduit are specifically designed for such conduit.

d. Intermediate Metal Conduit: Ensure intermediate metal conduit is galvanized steel and complies with UL 1242.

e. Rigid Nonmetallic Conduit: Ensure rigid nonmetallic conduit complies with

NEMA TC 2 and NEMA TC 3 with a wall thickness not less than Schedule 40

f. Wireways and Auxiliary Gutters: Ensure wireways and auxiliary gutters are a minimum 4 by 4-inch trade size conforming to UL 870

g. Surface Raceways and Assemblies: Ensure surface metal raceways and multi-outlet assemblies conform to NFPA 70, and have receptacles conforming to

NEMA WD 1, Type 5-20R.

h. Cable Trays: Provide ladder type cable trays conforming to NEMA VE

2.3 WIRE AND CABLE: Use copper 600-volt type THHN for conductors installed in conduit. Ensure all conductors AWG No. 8 and larger, are stranded. All conductors smaller than AWG No. 8 are solid

a. Ensure flexible cable is Type SO and contains a grounding conductor with green insulation.

b. Ensure conductors installed in plenums are marked plenum rated.

2.4 SWITCHES

SECTION 26 05 00. PAGE 5 OF 6

a. Safety Switches: Ensure safety switches comply with NEMA KS 1, and are the heavy-duty type with enclosure, voltage, current rating, number of poles, and fusing as indicated on the drawings. Ensure switch construction is such that, when the switch handle in the "ON" position, the cover or door cannot be opened.

Cover release device is coin proof and so constructed that an external tool is used to open the cover. Make provisions to lock the handle in the "OFF" position.

Ensure the switch is not capable of being locked in the "ON" position.

i. Provide switches of the quick-make, quick-break type and terminal lugs for use with copper conductors.

ii. Ensure safety color coding for identification of safety switches conforms to ANSI Z535.1.

b. Toggle Switches: Ensure toggle switches comply with EIA 480, control LED lighting fixtures and are the heavy duty, general purpose, non-interchangeable flush-type.

i. Provide commercial grade toggle switches, single -pole, two-position devices rated 20 amperes at 277 volts, 60 hertz alternating current (ac) only.

ii. Ensure all toggle switches are products of the same manufacturer.

2.5 RECEPTACLES: Provide commercial grade, NEMA 5-20R receptacles, 20A, 125 VAC, 2-pole, 3-wire duplex conforming to NEMA WD 6.

2.6 OUTLET BOXES, PULL BOXES AND JUNCTION BOXES: Ensure outlet boxes for use with conduit systems are in accordance with NEMA FB 1 and ANSI/NEMA OS 1 and are not less than 1-1/2 inches deep. Furnish all pull and junction boxes with screw-fastened covers.

2.7 PANELBOARDS: Provide circuit breaker type lighting and appliance branch circuit panelboards in accordance with NEMA PB 1. Bolt circuit breakers to the bus. Plug-in circuit breakers are not acceptable. Provide copper buses of the rating indicated on the drawings, with main lugs or main circuit breaker. Provide all panelboards for use on grounded ac systems with a full-capacity isolated neutral bus and a separate grounding bus bonded to the panelboard enclosure. Ensure panelboard enclosures are NEMA 250, Type 1, in accordance with NEMA PB 1. Provide enclosure fronts with latchable hinged doors.

2.8 CIRCUIT BREAKERS: Ensure circuit breaker interrupting rating is not less than those indicated and in no event less than 10,000 amperes root-mean-square (rms) symmetrical

SECTION 26 05 00. PAGE 6 OF 6

at 208 volts, respectively. Provide multipole circuit breakers of the common-trip type with a single handle. Molded case circuit breakers are bolt-on type conforming to UL

489.

2.9 LAMPS AND LIGHTING FIXTURES: Manufacturers and catalog numbers shown on the drawings are indicative of the general type desired and are not intended to restrict the selection to fixtures of any particular manufacturer. Fixtures with the same salient features and equivalent light distribution and brightness characteristics, of equal finish and quality, are acceptable. Provide lamps of the proper type and wattage for each fixture.

2.10 MANUFACTURER'S NAMEPLATE: Ensure each item of equipment has a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent is not acceptable.

PART 3 EXECUTION

3.1 PREPARATION: Submit manufacturer's instructions including special provisions required to install equipment components and system packages. Special provisions include impedances, hazards and safety precautions.

Clean and paint conduit, supports, fittings, cabinets, pull boxes, and racks as specified in

Section 09 90 00 - PAINTS AND COATINGS.

Colors shall be as Follows:

Protect metallic materials against corrosion. Provide equipment enclosures with the standard finish by the manufacturer when used for most indoor installations. For harsh indoor environments (any area subjected to chemical and abrasive action), and all outdoor installations. Do not use aluminum when in contact with earth or concrete and, where connected to dissimilar metal, protect by using approved fittings and treatment.

Except where other equivalent protective treatment is specifically approved in writing, provide hot-dip galvanized ferrous metals for items such as, anchors, bolts, braces, boxes, bodies, clamps, fittings, guards, nuts, pins, rods, shims, thimbles, washers, and miscellaneous items not made of corrosion-resistant steel.