About this file
This Addendum No. 1 is a narrative of changes document issued by Colliers Engineering & Design for the Lansing School District's Gardner Elementary Food Service Equipment Replacement & Renovations project (SO-1852) located at 333 Dahlia Drive, Lansing, Michigan 48911. The addendum, dated April 3, 2026, revises the contract documents and specifications related to Bid Pack 2 for the kitchen remodel project. Key revisions include clarifications on paint specifications referencing Sheet A141, modifications to door schedules on Sheet A601 designating doors 131, 136A, D-118, and D-126 as 90-minute rated doors with new hardware installed in existing frames, addition of Forte Opening Solutions (Masonite Architectural) as an acceptable manufacturer for wood doors, and electrical lighting specification changes on Sheet E100 establishing Lumenwerx 1500 Lumen per linear foot as the basis of design with Watt Stopper approved for lighting controls and Williams and Columbia as approved lighting manufacturers. The addendum also includes reissued drawings (G001, A141, A601, E100) and three construction manager clarifications addressing painting specifications, division of mechanical work into separate plumbing and HVAC divisions, and scope definitions for various trades including food service equipment, plumbing, and HVAC work phased across summer 2026 and summer 2027.
The addendum was prepared and signed by Courtney Norris on April 3, 2026, and distributed via multiple methods including email, Newforma, FTP, and hand delivery to Beckering Construction (djb@beckering.com) in Grand Rapids, Michigan 49548. The project involves kitchen area renovations in Phase 1 scheduled for summer 2026 and additional work in Phase 2 for summer 2027. Construction manager clarifications specify that plumbing and HVAC contractors must coordinate with the general trades contractor and food service equipment contractor, with the plumbing contractor responsible for disconnecting kitchen equipment on project start and performing all required permits and daily housekeeping. The addendum forms part of the contract documents and requires strict attention to revised drawings and specifications for accurate take-offs, quantities, and identification of deleted or revised items.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LSD Gardner Food Service – Bid Pack 2, Addendum No. 1 – Narrative of Changes Page 1 | 2
LSD Gardner Food Service Bid Pack 2, Addendum No. 1 Narrative of Changes
Project Name: Gardner Elementary Food Service – Equipment Replacement & Renovations SO-1852
Date: April 3, 2026
Project Location:
333 Dahlia Dr, Lansing, MI 48911
Architect’s Project #: 26000752A
Owner/Client: Lansing School District Attention: David Beckering
Issued to: Beckering Construction Email: djb@beckering.com City/State: Grand Rapids, MI Zip: 49548
Delivered via:
This Addendum revises the Contract Documents and shall have the same force and effect;
make the following changes to the Specifications and Drawings for this project. The following is a written summary of the changes made by this Addendum. Strict attention should be given to the Drawings and Specifications for area take-off, quantities and items deleted or revised herein. This addendum forms a part of the Contract Documents.
Issued by CED by: Courtney Norris Date Signed: 04/03/2026 Prepared by: Courtney Norris Date Signed: 04/03/2026 Distribution:
Below is a list of the changes made to our documents in response to the comments, RFIs, or clarifications provided prior to Bid. Please feel free to reach out with any further questions or clarifications in a timely manner.
Sincerely, Courtney Norris
☐ Messenger
☐ Express
☐ Hand-carried
☐ Pick-up
☐ UPS
Address Sent to:
☐ Newforma
☐ FTP
LSD Gardner Food Service – Bid Pack 2, Addendum No. 1 – Narrative of Changes Page 2 | 2
General Notes/ Clarifications
• Paint specifications can be found on sheet A601. Basis of design for the paint is on A141.
Drawings
• G001 – CODE COMPLIANCE & LIFE SAFETY PLANS
o Added notes about existing ‘B’ labeled rated doors
• A141 – FIRST FLOOR FINISH PLAN (Reissued) o Removed paint tag from bubbled door. All hm door frames and HM doors to get painted. Existing wood doors remain unpainted. New wood doors are factory finished. Doors not in the door schedule have been noted on sheet A141 as to what gets painted.
• A601 – DOOR SCHEUDLE AND SPECIFICATIONS (Reissued) o Added Forte Opening Solutions (Masonite Architectural) to acceptable manufacturers for wood doors.
o Doors 131, 136A, D-118 and D-126 are to be 90 minute doors. Existing door and frames are ‘B’ labeled. New door and hardware to maintain existing rating in exiting frame.
• E100 – DETAILS, SYMBOL LEGEND & SPECIFICATIONS (Reissued) o Changed type B to Lumenwerx 1500 Lumen per LF o Watt stopper is approved for lighting controls o Williams, Columbia approved lighting manufactures
ATTACHMENTS
Reissued Drawings:
G001, A141, A601, E100
CM Clarifications 1, 2, 3
END OF ADDENDUM NO. 1
FE
FE
X
X
X
24X42 24X42
24X4824X48
24X60
X
X
24X42 24X42
X
X
X
24X42 24X42
X
X
X
X
24X48 24X48
24X48
24X42 24X42
X
X
24X42
24X42
X
X
24X42
D
W
OCCUPANCY GROUP
# OCCUPANTS
S.F.
PHASING LEGEND
EXIT SIGN
EXIT
COMMON PATH OF EGRESS DISTANCE
EXIT ACCESS TRAVEL DISTANCE
(ALONG STAIRWAY NOSING AT OPEN
STAIRWAYS)
FIRE EXTINGUISHER ON WALL BRACKET
FIRE EXTINGUISHER CABINET
1-HR RATED WALL
1-HR. RATED FLOOR/BEAM/COLUMN
TO SUPPORT RATED ELEVATOR
SHAFT & MACHINE ROOM ENCLOSURE
DF DRINKING FOUNTAIN
SS SERVICE SINK
SIGN DIRECTION
FACE OF SIGN
EATD
CPET
1. APPLICABLE CODES:
A. WORK SHALL CONFORM TO FEDERAL, STATE AND LOCAL CODES
AS INTERPRETED BY THE AUTHORITY HAVING JURISDICTION.
2. COMPLIANCE:
A. PROVIDE FIRE EXTINGUISHERS IN CONFORMANCE WITH THE FIRE
CODE SECTION 906 AND COORDINATE WITH FIRE MARSHAL
PRIOR TO INSTALLATION. DO NOT INSTALL FIRE EXTINGUISHERS
UNTIL LOCATIONS HAVE BEEN REVIEWED AND APPROVED BY THE
AUTHORITY HAVING JURISDICTION.
B. OBTAIN ALL REQUIRED PERMITS AND PAYMENT OF PERMIT AND
APPLICATION FEES FOR THE WORK.
3. CERTIFICATIONS:
A. THE ARCHITECT'S CERTIFICATION IS ONLY FOR THE WORK
SHOWN TO BE DONE. IT DOES NOT CONSTITUTE APPROVAL OF
PRE-EXISTING CONDITIONS OR REVIEW OF THOSE CONDITIONS
FOR CODE COMPLIANCE.
GENERAL NOTES
A-2
7068 SF
/15 = 471
A-2
2800 SF
/200 = 14
A-2
760 SF
/60 = 12
COMBINED CAFETERIA
EAST SERVING AREA
WEST SERVING AREA
KITCHEN
NEW COOLER
130B
STORAGE
WEST PLATFORM
EAST PLATFORM
STORAGE
D-126
STORAGE
D-118
CORRIDOR
D-111
CORRIDOR
D-123
CORRIDOR
D-147
VESTIBULE
D-112
A-2
760 SF
/60 = 12
TRAVEL DISTANCE: 78' - 6"
TRAVEL DISTANCE: 35' - 0"
TRAVEL DISTANCE: 18' - 6"
TRAVEL DISTANCE: 78' - 6"
TRAVEL DISTANCE: 40' - 6"
TRAVEL DISTANCE: 82' - 0"
TRAVEL DISTANCE: 80' - 0"
TRAVEL DISTANCE: 78' - 0"
EX 'B'
LABEL DR
EX 'B'
LABEL DR
EX 'B'
LABEL DR
EX 'B'
LABEL DR
Colliers Engineering & Design, Architecture, Landscape Architecture, Surveying, CT P.C.
Colliers
Engineering & Design
Colliers
Engineering & Design
GRAND RAPIDS
560 5th St. NW
Suite 305
Grand Rapids, MI 49504
Phone: 616.827.4270
A R
C H
D x
PROJECT MANAGER:
DESIGNER: REVIEWER:
DISCIPLINE LEAD:
DRAWING NUMBER:
DATE ISSUED: PROJECT NUMBER:
SHEET NAME:
Copyright © 2024. Colliers Engineering & Design All Rights Reserved. This drawing and all the information contained herein is authorized for use only by the party for whom the services were contracted or to whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied upon for any other purpose without the express written consent of
Colliers Engineering & Design.
www.colliersengineering.com
NOTE: DO NOT SCALE DRAWING FOR CONSTRUCTION.
MI ARCHITECTURE
FIRM LICENSE # NLP000605
E F
D
CB
A
KEY PLAN
BID PACK 2
/3
/2
:5 :2
P
M
GARDNER ELEMENTARY
FOOD SERVICE - EQUIPMENT
REPLACEMENT &
RENOVATION SO-1852
333 DAHLIA DRIVE
LANSING, MI 48911
C NORRIS
E POST
B HUYLER
G001
CODE COMPLIANCE &
LIFE SAFETY PLANS
LANSING SCHOOL
DISTRICT
3/13/26 26000752A
SCALE : 1/16" = 1'-0"
LIFE SAFETY PLAN - AREA OF WORK
N
REHABILITATION OF EXISTING STRUCTURES:
REPAIRS
PER THE 2021 MICHIGAN RAHABILITATION CODE FOR EXISTING BUILDINGS (2021 EIBC)
ALTERATIONS - LEVEL 1
CHANGE OF OCCUPANCY
FORMER OCCUPANCY CLASSIFICATION(S):
NEW OCCUPANCY CLASSIFICATION(S):
PARTIAL CHANGE OF OCCUPANCY: YES NO
ADDITIONS
IF YES: SEPARATED NOT SEPARATED
ALTERATIONS - LEVEL 2
ALTERATIONS - LEVEL 3
SEPARATED ADDITION: YES NO
IF YES, FIRE RESISTENCE RATING:
HISTORIC BUILDING
(CHAPTER 6)
(CHAPTER 7)
(CHAPTER 8)
(CHAPTER 9)
(CHAPTER 10)
(CHAPTER 11)
(CHAPTER 12)
RELOCATED BUILDING (CHAPTER 13)
ACCESSIBILITY UPGRADES: COMPLY WITH
SECTION 410 AND ADDENDA
FIRE WALL
FIRE BARRIER
HR
HR
X
SINGLE
MIXED OCCUPANCY
IF SEPARATED, FIRE RESISTANCE RATING OF FIRE BARRIER:
OCCUPANCY CLASSIFICATION(S):
USES:
HR
(CHAPTERS 3 & 5)
(TABLE 508.4)
SEPARATED COMBINATIONNON-SEPARATED
OCCUPANCY CLASSIFICATION AND MIXED OCCUPANCIES:
ACCESSORY - GROUP ; % OF FLOOR AREA
AREA OF WORK IS KITCHEN/SERVING (B/M) AND CAFETERIA (A-2)
E- EDUCATION
X
AUTOMATIC SPRINKLER SYSTEM PROVIDED THROUGHOUT BUILDING:
YES
13R
NO
13NFPA STANDARD:
PARTIAL/LIMITED-AREA SPRINKLER SYSTEM:
YES NO
ALT. FIRE PROTECTION SYSTEM:
X
CONSTRUCTION TYPE:
REQUIRED PROVIDED
STRUCTURAL FRAME
BEARING WALLS
NON-BEARING WALLS
NON-BEARING WALLS
FLOOR CONSTRUCTION
ROOF CONSTRUCTION
SECTION
(TABLE 601)
(TABLE 601)
(TABLE 602)
(TABLE 601)
(TABLE 601)
(TABLE 601)
(EXTERIOR)
(INTERIOR)
(EXTERIOR)
BEARING WALLS (TABLE 601)(INTERIOR)
FIRE RESISTANCE OF BUILDING ELEMENTS:
(CHAPTER 6)
BUILDING ELEMENTS
SECTION 601II (000)
BUILDING CODE SUMMARY
PROJECT NAME:
PROJECT INFORMATION:
PROJECT NUMBER:
PREPARED BY:
DATE:
CHECKED BY:
DATE:
APPLICABLE CODE:
COMPLIANCE WITH THE: 2021 MICHIGAN BUILDING, REHABILITATION, AND ENERGY CONSERVATION CODES (BASED ON 2021 I-CODES), 2021 MICHIGAN MECHANICAL CODE, 2021 PLUMBING CODE (BASED ON 2021 IPC) INCLUDING MICHIGAN ADDENDA AND ERRATA; 2023 MICHIGAN ELECTRICAL CODE, PART 8 RULES (BY REFERENCE, 2023 NEC); BOILER CODE (2019 ASME BOILER AND PRESSURE VESSEL CODES WITH ADDENDA); ELEVATOR CODE (2016 ASME 17.1, 2011 ASME A18.1 AND ELEVATOR SAFETY BOARD GENERAL RULES, ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES (ICC A117.1-17), AND OTHER LOCAL, STATE, AND FEDERAL CODES AND REGULATIONS APPLICABLE TO THIS PROJECT.
DWIGHT RICH CAFETERIA RENOVATIONS
25015929A/25015928A
E POST
2/19/20
C NORRIS
INTERIOR FINISH:
WALL AND CEILING
LOCATION
(CHAPTER 8)
FINISH CLASS
A EXITS CORRIDORS/ EXIT ACCESS ROOMS/ SPACES
B EXITS CORRIDORS/ EXIT ACCESS ROOMS/ SPACES
C EXITS CORRIDORS/ EXIT ACCESS ROOMS/ SPACES
OCCUPANCIES
ALL GROUPS:
ALL GROUPS:
ALL GROUPS:
FINISH CLASS
I
FLOORING
OCCUPANCY:
II
DOC FF-1
X
X
X X
X
X
X
X
X
X
X E
SCALE : 6" = 1'-0"
LIFE SAFETY PLAN - OVERALL EXISTING ALL TRAVEL DISTANCE AND EGRESS IS EXISTING
REV DATE DESCRIPTION
3 03/13/26 BID PACK 2 - BIDS & PERMITS
4 Date 4 BID PACK 2 - ADDENDUM 1
LAIAFADAAA 7.5AAWURPN
KITCHEN
STORAGE
EAST SERVING AREA
NEW COOLER
130B
WEST SERVING AREA
DRY STORAGE
LOCKER ROOM
D-138
JAN
D-139
TLT.
D-140
OFFICE
D-141
COMBINED CAFETERIA
PASSAGE
D-122
PASSAGE
D-124
EAST PLATFORM
STORAGE
D-126
WEST PLATFORM
STORAGE
D-118
TEACHERS DINING
D-135
DISHWASH AREA
STORAGE
130A
EP-1
EP-1
P-2
P-1 P-2
P-2RT-1
RB-1
RT-1
RB-1
RST-1 RST-1
P-3P-3
EP-1
EP-1
P-2
P-3
EP-2
EP-2
FF
FF
P-3
P-3
P-3
PATCH FLOOR
TO MATCH
EXISTING
QUARRY TILE
P-1 P-2
P-3
P-4 P-4 P-4
FT-1
TB-1
FT-1
TB-1
P-4 P-4 P-4
P-4
P-4P-4
FRAME ONLY
FRAME ONLY
HM DOOR
& FRAME
FRAME ONLY
FRAME ONLY
FRAME ONLY
FRAME ONLY
09 51 13 ACOUSTIC PANEL CEILINGS
09 65 13 RESILIENT BASE AND ACCESSORIES
BASIS OF DESIGN
09 91 23 INTERIOR PAINTING
RB-1
MANUFACTURER: ROPPE
TYPE: STANDARD TOE
SIZE: 4" COVE
COLOR: LUNAR DUST
P-1
MANUFACTURER: SHERWIN WILLIAMS
COLOR:
FINISH: SEMI-GLOSS
LOCATION: FIELD PAINT COLOR
P-2
MANUFACTURER: SHERWIN WILLIAMS
COLOR:
FINISH: SEMI-GLOSS
LOCATION: FIELD PAINT COLOR
P-3
MANUFACTURER: SHERWIN WILLIAMS
COLOR:
FINISH: EG-SHELL
LOCATION: CEILING PAINT COLOR
ACT-1
MANUFACTURER: ARMSTRONG
TYPE: SCHOOL ZONE FINE FISSURED
EDGE: SQUARE LAY-IN
SIZE: 24' X 24'
GRID: 15/16" PRELUDE - WHITE
COLOR: WHITE
ACT-2
MANUFACTURER: ARMSTRONG
TYPE: KITCHEN ZONE
SIZE: 24' X 48'
EDGE: SQUARE LAY-IN
GRID: 15/16" PRELUDE - WHITE
COLOR: WHITE
09 65 13.23 RESILIENT STAIR TREADS & RISERS
RST-1
MANUFACTURER: ROPPE
TYPE: #95 HAMMERED DESIGN WITH RISER
COLOR: MARBLEIZED LUNAR DUST
09 65 19 RESILIENT TILE FLOOR
RT-1
MANUFACTURER: ROPPE
SIZE: 19-11/16" X 19-11/16"
TYPE: #995 HAMMERED DESIGN
COLOR: MARBLEIZED LUNAR DUST
P-4
MANUFACTURER: SHERWIN WILLIAMS
COLOR:
FINISH: SEMI-GLOSS
LOCATION: DOORS AND FRAMES
NOTE: ALL EXISTING FRAMES TO BE PAINTED WHERE P-4 IS
INDICATED. DOORS PAINTED WHERE NOTED.
09 67 23 RESINOUS FLOORING
EP-1
MANUFACTURER: SHERWIN WILLIAMS
STYLE: RESUFLOR DECO FLAKE BC
COLOR: TBD BY CLIENT FROM MANUF STANDARD COLORS
EP-2
MANUFACTURER: SHERWIN WILLIAMS
STYLE: POLY-CRETE SLB
COLOR: TBD BY CLIENT FROM MANUF STANDARD COLORS
09 30 13 CERAMIC TILING
FT-1
MANUFACTURER: AMERICAN OLEAN
STYLE: QUARRY TILE
COLOR: CANYON RED Q01
SIZE: 4x8
PATTERN: HORIZONTAL STACKED - MATCH EXISTING
GROUT: MAPEI - MATCH EXISTING
TB-1 TILE BASE
MANUFACTURER: AMERICAN OLEAN
STYLE: QUARRY TILE
COLOR: CANYON RED Q01
SIZE: ROUND TOP COVE BASE 5x6 - MATCH EXISTNG
GROUT: MAPEI - MATCH EXISTING
FINISH HATCH LEGEND
AREAS OF FLOOR PATCHING -
MATCH EXISTING QUARRY TILE
FLOOR FINISH
WALL BASE FINISH
FLOOR FINISH ONLY
GENERAL WALL FINISH
WALL FINISH ABOVE WAINSCOT
WAINSCOT FINISH
WINDOW TREATMENT
SIGNAGE TAG
FINISH SYMBOL LEGEND
XX#
XX#
XX#
X#
X# X#
X#
ACCENT WALL FINISH - TO EXTENTS
X#
X#
GENERAL FINISH NOTES
A. COMPLY WITH MANUFACTURER'S RECOMMENDATIONS FOR
PREPARING AND INSTALLING FINISHES.
B. PROTECT ADJACENT WORK BY SUITABLY COVERING
DURING WORK.
C. REMOVE ADHESIVE OR PAINT SPOTS FROM FINISHED
FLOORS, WALLS, GLASS OR OTHER SURFACES. FINISHES
TO MEET OR EXCEED CODE REQUIREMENTS.
D. INSTALL MATERIALS USING MANUFACTURER'S APPROVED
ADHESIVES AND METHODS, U.O.N.
E. FILL MINOR DRYWALL IRREGULARITIES WITH SPACKLING
COMPOUND AND SAND TO A SMOOTH LEVEL SURFACE.
EXERCISE CARE TO AVOID RAISING THE NAP OF PAPER
F. DO NOT PERFORM PAINTING AND OTHER FINISHING WORK
UNDER CONDITIONS UNSUITABLE FOR EXECUTION OF
PAINTING WORK. AIR SHALL BE FREE FROM DUST AND DIRT
TO PREVENT LODGING OF FOREIGN MATTER IN FRESH
PAINT. FLOORS MUST BE BROOM CLEAN BEFORE PAINTING
IS STARTED.
G. PAINT DESIGNATIONS INDICATE LOCATION ONLY. OWNER TO
MAKE FINAL DECISIONS ON COLOR AND SHEEN.
H. EDGES OF PAINT ADJOINING OTHER COLORS OR MATERIALS
TO BE SHARP AND CLEAN WITHOUT OVERLAP.
I. EXAMINE SURFACES TO RECEIVE PAINT CAREFULLY FOR
DEFECTS. DO NOT PROCEED WITH WORK UNTIL DEFECTS
ARE CORRECTED.
J. WHENEVER NECESSARY TO OBTAIN REQUIRED RESULTS,
REFINISH AN ENTIRE WALL RATHER THAN SPOT FINISHING
WHERE A PORTION OF THE FINISH HAS BEEN DAMAGED OR
IS UNSATISFACTORY.
K. PREPARE FLOOR SURFACES INCLUDING, BUT NOT LIMITED
TO, THE FOLLOWING:
A. PREPARE/PROPERLY REPAIR AND PATCH SUBFLOORS
TO A SMOOTH AND LEVEL FINISH.
B. FLASH PATCH AS REQUIRED, READY TO RECEIVE NEW
FINISH.
L. PROVIDE THE REQUIRED TRANSITIONS BASED ON TYPES
IDENTIFIED ON DRAWINGS AT EACH FINISH TRANSITION
LOCATION
M. CENTER FLOOR MATERIAL TRANSITIONS ON DOOR ABOVE.
N. FINISHED FLOORS EXTEND INTO TOE SPACES, CLOSETS,
DOOR REVEALS AND SIMILAR OPENINGS.
O. REFER TO REFLECTED CEILING PLANS FOR CEILING
FINISHES.
P. ALL EXPOSED CONDUIT AND MISC STEEL TO BE PAINTED TO
MATCH ADJACENT SURFACE.
Q. CONTRACTOR REQUIRED TO PROVIDE DETAILED SHOP
SUBMITTALS WITH REQUIRED STRIPING DIMENSIONS TO
MEET REGIONAL, STATE, AND NATIONAL COMPETITION
GUIDELINES FOR HIGHSCHOOL BASKETBALL, VOLLEYBALL,
AND PICKLEBALL.
EPOXY SEAMLESS
FLOORING SYSTEM
/8
3/4" (19MM) RADIUS COVE
C O
V E
H E
IG
H
T
1/8"
Colliers Engineering & Design, Architecture, Landscape Architecture, Surveying, CT P.C.
Colliers
Engineering & Design
Colliers
Engineering & Design
GRAND RAPIDS
560 5th St. NW
Suite 305
Grand Rapids, MI 49504
Phone: 616.827.4270
A R
C H
D x
PROJECT MANAGER:
DESIGNER: REVIEWER:
DISCIPLINE LEAD:
DRAWING NUMBER:
DATE ISSUED: PROJECT NUMBER:
SHEET NAME:
Copyright © 2024. Colliers Engineering & Design All Rights Reserved. This drawing and all the information contained herein is authorized for use only by the party for whom the services were contracted or to whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied upon for any other purpose without the express written consent of
Colliers Engineering & Design.
www.colliersengineering.com
NOTE: DO NOT SCALE DRAWING FOR CONSTRUCTION.
MI ARCHITECTURE
FIRM LICENSE # NLP000605
E F
D
CB
A
KEY PLAN
BID PACK 2
/3
/2
:4 :0
P
M
GARDNER ELEMENTARY
FOOD SERVICE - EQUIPMENT
REPLACEMENT &
RENOVATION SO-1852
333 DAHLIA DRIVE
LANSING, MI 48911
C NORRIS
C. NORRIS B. HUYLER
B. HUYLER
A141
FIRST FLOOR FINISH
PLAN
LANSING SCHOOL
DISTRICT
3/13/26 26000752A
SCALE : 3/32" = 1'-0"
FIRST FLOOR FINISH PLAN
ROOM FINISH SCHEDULE
ROOM
FLOOR BASE
WALL FINISH CEILING
FINISH REMARKSNUMBER NAME NORTH EAST SOUTH WEST
FIRST FLOOR
121 WEST PLATFORM RT-1 RB-1 P-2 P-2 -- P-2 ACT-1 RST-1 ON STEPS UP TO PLATFORM
125 EAST PLATFORM RT-1 RB-1 P-2 P-2 -- P-2 ACT-1 RST-1 ON STEPS UP TO PLATFORM
129 WEST SERVING
AREA
FT-1 TB-1 P-3 P-3 P-3 P-3 ACT-2 PROVIDE ALTERNATE 1: TO INFILL FLOOR
WITH CONCRETE LEVEL WITH CAFETERIA AND
PROVIDE EP-1 FLOOR & BASE
130A STORAGE EP-2 EP-2 P-2 P-2 P-2 P-2 ACT-2
130B NEW COOLER FF FF FF FF FF FF FF FF- FACTORY FINISH
131 STORAGE EP-1 EP-1 P-2 P-2 P-2 P-2 ACT-1
132 EAST SERVING
AREA
FT-1 TB-1 P-3 P-3 P-3 P-3 ACT-2 PROVIDE ALTERNATE 1: TO INFILL FLOOR
WITH CONCRETE LEVEL WITH CAFETERIA AND
PROVIDE EP-1 FLOOR & BASE
133 COMBINED
CAFETERIA
EP-1 EP-1 P-1/P-2 P-1/P-2 P-1/P-2 P-1/P-2 ACT-1
134 DISHWASH AREA EXISTING EXISTNG P-3 P-3 P-3 P-3 ACT-2 PATCH AND REPAIR EXISTING QUARRY TILE
AS REQUIRED FOR NEW EQUIPMENT
136 KITCHEN EXISTING EXISTING P-3 P-3 P-3 P-3 ACT-2 PATCH AND REPAIR EXISTING QUARRY TILE
AS REQUIRED FOR NEW EQUIPMENT
137 DRY STORAGE EXISTING EXISTING P-3 P-3 P-3 P-3 ACT-2
REV DATE DESCRIPTION
3 03/13/26 BID PACK 2 - BIDS & PERMITS
4 Date 4 BID PACK 2 - ADDENDUM 1
SCALE : 6" = 1'-0"
EPOXY BASE DETAIL
NG
SCHEDULE
SEE
S E
E S
C H
E D
U L E
6" 9"
F
SCHEDULE
SEE
S E
E S
C H
E D
U L E
Colliers Engineering & Design, Architecture, Landscape Architecture, Surveying, CT P.C.
Colliers
Engineering & Design
Colliers
Engineering & Design
GRAND RAPIDS
560 5th St. NW
Suite 305
Grand Rapids, MI 49504
Phone: 616.827.4270
A R
C H
D x
PROJECT MANAGER:
DESIGNER: REVIEWER:
DISCIPLINE LEAD:
DRAWING NUMBER:
DATE ISSUED: PROJECT NUMBER:
SHEET NAME:
Copyright © 2024. Colliers Engineering & Design All Rights Reserved. This drawing and all the information contained herein is authorized for use only by the party for whom the services were contracted or to whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied upon for any other purpose without the express written consent of
Colliers Engineering & Design.
www.colliersengineering.com
NOTE: DO NOT SCALE DRAWING FOR CONSTRUCTION.
MI ARCHITECTURE
FIRM LICENSE # NLP000605
E F
D
CB
A
KEY PLAN
BID PACK 2
/3
/2
:4 :0
P
M
GARDNER ELEMENTARY
FOOD SERVICE - EQUIPMENT
REPLACEMENT &
RENOVATION SO-1852
333 DAHLIA DRIVE
LANSING, MI 48911
C NORRIS
E POST
B HUYLER
A601
DOOR SCHEDULE AND
SPECIFICATIONS
LANSING SCHOOL
DISTRICT
3/13/26 26000752A
DOOR SCHEDULE
DOOR #
DOOR FRAME GENERAL
DOOR #
WIDTH
LEAF 1
WIDTH
LEAF 2 HEIGHT T
H
K
T Y
P E
M A
T -F
IN
T Y
P E
M A
T -F
IN
H D
W R
R A
T
IN
G
REMARKS
FIRST FLOOR
129A
3' - 0" 7' - 0" 0' - 1 3/4" NG WD - ST EXIST EXIST -
NEW PAINT
TBD
NEW DOOR + HDWR, EXIST
FRAME (PH. 2)
129A
3' - 0" 3' - 0" 7' - 0" 0' - 1 3/4" F WD - ST EXIST EXIST -
NEW PAINT
TBD
MIN
(2) NEW DOORS + HDWR,
EXIST FRAME (PH. 2)
132A
3' - 0" 7' - 0" 0' - 1 3/4" NG WD - ST EXIST EXIST -
NEW PAINT
TBD
NEW DOOR + HDWR, EXIST
FRAME (PH. 2)
132A
133A
3' - 0" 7' - 0" 0' - 1 3/4" NG WD - ST EXIST EXIST -
NEW PAINT
TBD
NEW DOOR + HDWR, EXIST
FRAME (PH. 2)
133A
133B
3' - 0" 7' - 0" 0' - 1 3/4" NG WD - ST EXIST EXIST -
NEW PAINT
TBD
NEW DOOR + HDWR, EXIST
FRAME (PH. 2)
133B
133C
3' - 1" 7' - 0" 0' - 1 3/4" NG WD - ST EXIST EXIST -
NEW PAINT
TBD
NEW DOOR + HDWR, EXIST
FRAME (PH. 2)
133C
133D
3' - 0" 7' - 0" 0' - 1 3/4" NG WD - ST EXIST EXIST -
NEW PAINT
TBD
NEW DOOR + HDWR, EXIST
FRAME (PH. 2)
133D
136A
3' - 8" 7' - 0" 0' - 1 3/4" F WD - ST EXIST EXIST -
NEW PAINT
TBD
MIN
NEW DOOR + HDWR, EXIST
FRAME (PH. 1) VERIFY SIZE OF
OPENING AND ANY RATING
REQUIREMENTS IN FIELD
136A
D-118
3' - 0" 3' - 0" 7' - 0" 0' - 1 3/4" F WD - ST EXIST EXIST -
NEW PAINT
TBD
MIN
(2) NEW DOORS + HDWR,
EXIST FRAME (PH. 2)
D-118
D-126
3' - 0" 3' - 0" 7' - 0" 0' - 1 3/4" F WD - ST EXIST EXIST -
NEW PAINT
TBD
MIN
(2) NEW DOORS + HDWR,
EXIST FRAME (PH. 2)
D-126
D-135A
3' - 0" 7' - 0" 0' - 1 3/4" F WD - ST EXIST EXIST -
NEW PAINT
TBD
NEW DOOR + HDWR, EXIST
FRAME (PH. 1)
D-135A
DOOR - TYPES
REV DATE DESCRIPTION
3 03/13/26 BID PACK 2 - BIDS & PERMITS
4 Date 4 BID PACK 2 - ADDENDUM 1
081416 - FLUSH WOOD DOORS
A. ACCEPTABLE MANUFACTURERS: EGGERS INDUSTRIES, OSHKOSH DOOR COMPANY, VT
INDUSTRIES, AND FORTE OPENING SOLUTIONS (MASONITE ARCHITECTURAL).
B. INTERIOR DOORS: SOLID-CORE FIVE-PLY FLUSH WOOD VENEER-FACED DOORS FOR
TRANSPARENT FINISH.
a. PERFORMANCE GRADE: ANSI/WDMA I.S. 1A EXTRA HEAVY DUTY.
b. FACES: PLAIN SLICED RED OAK, CENTER-BALANCE MATCH.
c. EXPOSED VERTICAL AND TOP EDGES: SAME SPECIES AS FACES, ARCHITECTURAL
WOODWORK STANDARDS EDGE TYPE A.
d. FIRE RATED DOORS: PROVIDE EDGE CONSTRUCTION WITH INTUMESCENT SEALS
CONCEALED BY OUTER STILE.
e. CORE FOR FIRE-RATED DOORS: AS REQUIRED TO ACHIEVE FIRE-PROTECTION RATING
INDICATED ON SCHEDULE.
C. FINISH: FACTORY FINISH, TRANSPARENT, SATIN, STAIN COLOR TO BE SELECTED BY
ARCHITECT FROM MANUFACTURER'S STANDARD
COLORS.
087100 - DOOR HARDWARE:
A. MANUFACTURERS/PRODUCTS
a. HINGES: IVES 5BB SERIES. ALSO ACCEPTABLE: HAGER BB1191/1279 SERIES OR MCKINNEY
TB SERIES.
b. CONTINUOUS HINGES: IVES. ALSO ACCEPTABLE: SELECT OR PEMKO.
c. MORTISE LOCKS: SCHLAGE L9000 SERIES. ALSO ACCEPTABLE: SARGENT 8200 SERIES.
• WARRANTY: 10 YEARS.
d. CYLINDERS: BEST. NO SUBSTITUTION. PROVIDE INTERCHANGEABLE CYLINDERS/CORES
TO MATCH OWNER'S EXISTING KEY SYSTEM, COMPLIANT WITH ANSI/BHMA A156.5; LATEST
REVISION.
e. DOOR CLOSERS: LCN 4040XP SERIES. ALSO ACCEPTABLE: SARGENT 281 SERIES.
• WARRANTY: 30 YEARS.
f. PROTECTION PLATES: IVES. ALSO ACCEPTABLE: TRIMCO OR ROCKWOOD.
g. OVERHEAD STOPS AND OVERHEAD STOP/HOLDERS: GLYNN-JOHNSON. ALSO
ACCEPTABLE: SARGENT OR ABH.
h. DOOR STOPS AND HOLDERS: IVES. ALSO ACCEPTABLE: TRIMCO OR ROCKWOOD.
i. THRESHOLDS, SEALS, DOOR SWEEPS, AUTOMATIC DOOR BOTTOMS, AND GASKETING:
ZERO INTERNATIONAL. ALSO ACCEPTABLE: NATIONAL GUARD, REESE, OR PEMKO.
j. FINISHES: GENERALLY, SATIN CHROMIUM, BHMA 626/652 (US26D). PROVIDE FINISH FOR
EACH ITEM AS INDICATED IN THE SETS.
B. KEYING
a. SCHEDULED SYSTEM:
• EXISTING FACTORY REGISTERED SYSTEM:
1. PROVIDE CYLINDERS/CORES 0-BITTED FOR OWNER'S EXISTING FACTORY
REGISTERED KEYING SYSTEM. COMPLY WITH GUIDELINES IN ANSI/BHMA A156.28.
b. REQUIREMENTS:
• PERMANENT KEYING: PROVIDED BY OWNER.
C. HARDWARE SETS TBD IN FUTURE ADDENDUM.
D. ALL HARDWARE TO MEET ACCESSIBILITY REQUIREMENTS SET BY 2017 ICC 117.1 AND ADA.
088000 - GLAZING:
A. MONOLITHIC GLASS:
a. HEAT STRENGTHENED FULLY TEMPERED FLOAT GLASS.
b. MINIMUM 6 MM THICK.
c. LOCATION: INTERIOR, NON-FIRE RATED LOCATIONS UNLESS OTHERWISE NOTED.
099123 - INTERIOR PAINTING:
A. BASIS OF DESIGN MANUFACTURER: SHERWIN WILLIAMS. ALSO ACCEPTABLE: BENJAMIN MOORE
AND PPG PAINTS.
B. PREPARATION OF SURFACES TO RECEIVE PAINT: CLEAN, DRY, DULL, AND SOUND.
C. PAINT SYSTEMS:
a. CMU (EXISTING PREVIOUSLY PAINTED):
• PRIMER: EXTREME BOND PRIMER, B51 SERIES
1. 3.1 MILS WET, .9 MILS DRY.
• ADHESION TEST: USE PRINCIPLES OF ASTM D3359 AFTER MINIMUM 7 DAY CURE TIME OF
PRIMER TO ENSURE 90% OF COATING CONTINUES TO ADHERE, CONTACT COATINGS
MANUFACTURER FOR ASSISTANCE AS NEEDED.
• INTERMEDIATE COAT: MATCH TOPCOAT.
• TOPCOAT: PRO INDUSTRIAL PRE-CAT EPOXY, K45-2150 SERIES.
1. 4.0 MILS WET, 1.6 MILS DRY PER COAT.
b. CMU (NEW/BARE):
• PRIMER: PRO INDUSTRIAL HEAVY DUTY BLOCK FILLER, B42 SERIES
• INTERMEDIATE COAT: MATCH TOP COAT
• TOPCOAT: PRO INDUSTRIAL PRE-CAT EPOXY, K45-2150 SERIES.
1. 4.0 MILS WET, 1.6 MILS DRY PER COAT.
c. HOLLOW METAL FRAMES AND DOORS:
• PRIMER: PRO INDUSTRIAL PRO CRYL UNIVERSAL PRIMER, B66-310 SERIES.
1. 5.0 TO 10 MILS WET, 2.0 TO 4.0 MILS DRY.
• INTERMEDIATE COAT: MATCH TOPCOAT.
• TOPCOAT: PRO INDUSTRIAL ACRYLIC SEMI-GLOSS COAT, B66-650 SERIES.
1. 2.5 TO 4.0 MILS DRY PER COAT.
d. GYPSUM BOARD AND PLASTER:
• PRIMER: PROMAR 200 ZERO VOC INTERIOR LATEX PRIMER, B28W2600
1. 4.0 MILS WET, 1.0 MILS DRY.
• INTERMEDIATE COAT: MATCH TOPCOAT.
• TOPCOAT: PROMAR 200 ZERO VOC INTERIOR LATEX EG-SHEL, B20-2600 SERIES.
1. 4.0 MILS WET, 1.6 MILS DRY.
D. COLORS: REFER TO BASIS OF DESIGN.
SPECIFICATIONS
SYMBOL NOTES:
1. "AC" DENOTES ABOVE COUNTER. COORDINATE HEIGHT WITH ARCHITECT.
2. "H" DENOTES HORIZONTAL MOUNTING OF DEVICE.
3. "B" DENOTES MOUNTED IN BASE.
4. "F" DENOTES MOUNTED IN FACE OF CABINETS.
D
S
SECURITY INTERCOM
SECURITY DOOR CONTACT
CEILING SPEAKER
AUDIO ONLY ALARM
VISUAL ONLY ALARM
FIRE ALARM CONTROL RELAY
REMOTE ALARM KEY TEST SWITCH
WATER FLOW SWITCH
O,S,&Y TAMPER SWITCH
HEAT DETECTOR
DUCT SMOKE DETECTOR
AREA SMOKE DETECTOR-PHOTOELECTRIC
FIRE ALARM PULL STATION
CEILING SPEAKER
SPEAKER/STROBE LIGHT
LMTG. HT. TO CDESCRIPTIONSYMBOL
SYSTEMS SYMBOL LEGEND
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
F
CO
CR
FS
D
TS
RT
F.A.A.
F.A.C.P.
F.A. NOTES:
1. MATCH EXISTING FIRE ALARM SYSTEM.
SECURITY DOOR REQUEST TO EXIT
CO
R CARD READER
MAGNETIC DOOR HOLD OPENDH
CARBON MONOXIDE SENSOR. E.C TO ROUGH-IN SINGLE
GANG BOX AND 1/2"C. TO ACCESSIBLE CEILING SPACE.
46"
80"
80"
46"
46"
AT DOOR HEAD
46"
AT DOOR HEAD
TYPICALLY CLG
MOUNTED
SMOKE/HORN BASE
CO-DENOTES COMBO CARBON MONOXIDE/SMOKE
I
C
X
H
FIRE/SMOKE DAMPER
BEAM DETECTOR
F/SD
BD ---
SECURITY CAMERA - "W" DENOTES WALL MOUNTED
CHEVRON INDICATES AIM LINE
WP FIRE ALARM HORN/STROBE LIGHT
(WP-DENOTES WEATHER PROOF)
T THERMOSTAT. E.C TO ROUGH-IN SINGLE GANG BOX AND
1/2"C. TO ACCESSIBLE CEILING SPACE.
TRANSFORMER
SURFACE OR FLUSH MTD. BRANCH CIRCUIT PANELBOARD
THREE PHASE ELECTRIC MOTOR
SINGLE PHASE ELECTRIC MOTOR
MAGNETIC MOTOR STARTER-MS
DIMMER SWITCH
46"
KEY OPERATED SWITCH-SPEC. GRADE
FOUR WAY SWITCH-SPEC. GRADE
T
F
P
F
J
ELECTRICAL SYMBOL LEGEND
S
S
S
WR
D
K
S
SYMBOL DESCRIPTION
MTG. HT. TO CL
SPECIAL OUTLET-CHARACTERISTICS AS NOTED ON PLANS
FLOOR BOX 1 RECEPT, 1 DATA - THOMAS & BETTS-# 664-SC
1-1/4"C TO FLOORBOX FOR DATA
FLOOR BOX 2 RECEPT, 2 DATA THOMAS & BETTS-# 665-SC
1-1/4"C TO FLOORBOX FOR DATA
OS
IRDS IR SWITCH DIMMABLE
OCCUPANCY SENSOR
PUSH BUTTONPB
TV
IRS IR SWITCH
CS CONTROL STATION
C
SPECIAL SINGLE RECEPTACLE
VARIABLE FREQUENCY DRIVEVFD
PC PHOTO CELL
46"
46"
46"
46"
46"
46"
18"
18"
18"
18"
18"
AS NOTED
18"
46"
46"
46"
AT EQUIP.
AS NOTED
AS NOTED
46"
46"
46"
46"
72" TO TOP
18"
SINGLE POLE OR 3-WAY SWITCH-
SPECIFICATION GRADE
SPLIT WIRED RECEPTACLE
C - DENOTES CONTROLLED VIA RELAY OR OCC SENSOR
WATER RESISTANT GROUND FAULT CIRCUIT INTERRUPTER
WR-DENOTES WEATHERPROOF WHILE IN USE COVER
DUPLEX OUTLET-SPEC. GRADE
CIRCLE AROUND SYMBOL= CEILING MOUNTED
DATA OUTLET-4" SQ. BOX W/ 1 GANG RAISED COVER.
1-1/4"C. UP WALL TO CLG. SPACE
CIRCLE AROUND SYMBOL= CEILING MOUNTED
TV OUTLET-4" SQ. BOX W/ 1 GANG RAISED COVER.
1-1/4"C. UP WALL TO CLG. SPACE
CIRCLE AROUND SYMBOL= CEILING MOUNTED
JUNCTION BOX - HUBBELL NSAV62M WITH RECEPTACLE KIT
HUBBELL NSOKP. PROVIDE CONNECTOR PLATE FOR A/V
JUNCTION BOX -4" SQ. BOX W/ 2 GANG RAISED COVER.
1"C. UP WALL TO CLG. SPACE UNLESS OTHERWISE NOTED
FUSED DISCONNECT SWITCH-
FDS-HEAVY DUTY
NON-FUSED DISCONNECT SWITCH-
NFDS-HEAVY DUTY
SW. AND PLUGFUSE HOLDER- BUSSMANN
"SSU" & FUSESTAT FUSE
COMBINATION MAG. STARTER/ FUSED DISC. SWITCH - CS/FDS
COMBINATION MAG. STARTER/NON-FUSED DISC.
SWITCH - CS/NFDS
(2) DUPLEX OUTLET-SPEC. GRADE
CIRCLE AROUND SYMBOL= CEILING MOUNTED
S
PARTIALLY SHADED LUMINAIRE OR WITH "E" SUFFIX ARE
EMERGENCY
BATTERY EMERGENCY LUMINAIRE
REMOTE EMERGENCY HEAD
RECESSED LUMINAIRE 2'x4' OR 2'x2'
RECESSED WALLWASH LUMINAIRE
RECESSED DOWNLIGHT LUMINAIRE
LED ACCENT/UNDER CABINET LUMINAIRE
TRACK LIGHTING LUMINAIRE
SURFACE LUMINAIRE
WALL MOUNTED LUMINAIRE
PENDANT LUMINAIRE
SITE LIGHTING LUMINAIRE
NIGHT LIGHT
STRIP LUMINAIRE
SURFACE LUMINAIRE 2'x4' OR 2'x2'
EXIT SIGN - WALL MOUNTED OR CEILING MOUNTED
ARROWS INDICATE PATH OF EGRESS
NL
EE
H HUMIDISTAT. E.C TO ROUGH-IN SINGLE GANG BOX AND
1/2"C. TO ACCESSIBLE CEILING SPACE. 46"
WN ---
PS SWITCH WITH PILOT LIGHT 46"
18"TELEPHONE OUTLET-4" SQ. BOX W/ 1 GANG RAISED
COVER. 1-1/4"C. UP WALL TO CLG. SPACE
18"TELEPHONE/DATA OUTLET-4" SQ. BOX W/ 1 GANG
RAISED COVER. 1-1/4"C. UP WALL TO CLG. SPACE
M ---ELECTRIC UTILITY METER
P ---POWER POLE - SEE DRAWING FOR POWER -
POWER/DATA SPECIFICATIONS
DS DAYLIGHT SENSOR ---
MS MANUAL MOTOR STARTER SWITCH 46"
ELECTRICAL IDENTIFICATION
N.T.S.
FRONT
REAR SIDE
OF PLATE
FRONT
REAR SIDE OF
PLATE
BPA-15LP2-5
LABEL CKT. NO. OF EACH DEVICE ON REAR
SIDE OF COVER PLATE. USE PERMANENT
MARKER PEN, BRADY MARKING SYSTEM OR
OTHER METHOD APPROVED BY THE ENGINEER
JUNCTION BOXES (EXPOSED
OR CONCEALED ABOVE
ACCESSIBLE CEILING)
LABEL COVERS WITH CKT.'S CONTAINED
WITHIN. USE PERMANENT MARKER PEN
OR OTHER APPROVED METHOD.
FOR J.B.'S CONTAINING OTHER
THAN POWER OR LIGHTING CKT.'S
LABEL COVERS INDICATING
SYSTEM TYPE AND ZONES.
CKT.S
LP4-13,15,17
DUPLEX RECEPTACLE
PLATE
STANDARD TOGGLE
SWITCH PLATE
LABEL EXAMPLES:
"FIRE ALARM-ZONES 2&3"
"P.A. ZONES 4,5,&6" "DATA
CIRCUITS A&B" "EXIT
SIGNS-EMI&2" "EMERG.
CKTS. BPEM-3,4"
E100 A-1
PP POWER PACK ---
EV ---EV CHARGER
F= FUTURE
WIRELESS ROUTER
CIRCLE AROUND SYMBOL= CEILING MOUNTED
SURFACE MOUNT KITCHEN FLOOR BOX DETAIL
N.T.S.
SIMILAR TO HUBBELL SA6685G-2G U.O.N.
DEVICE BOX W/20A-120V DUPLEX RECEPTACLE.
NOTE: FOR 50A,240V PROVIDE HUBBELL
SA6685-4G WITH NEMA 14-50R. COORDINATE
WITH EQUIPMENT.
FLOOR
3/4" RIGID CONDUIT
E1.00 A-2
E100
DETAILS, SYMBOL
LEGENDS &
SPECIFICATIONS
03/16/2026
100 Cesar E Chavez Ave SW Grand Rapids, Michigan 49503
(616) 742-2810 www.classicengineering.com Project # 2026022
Classic Engineering, LLC
26000063A
LANSING SCHOOL
DISTRICT
Colliers Engineering & Design, Architecture, Landscape Architecture, Surveying, CT P.C.
Colliers
Engineering & Design
Colliers
Engineering & Design
GRAND RAPIDS
560 5th St. NW
Suite 305 Grand Rapids, MI 49504
Phone: 616.827.4270
A R
C H
D
4x
PROJECT MANAGER:
DESIGNER: REVIEWER:
DISCIPLINE LEAD:
DRAWING NUMBER:
DATE ISSUED: PROJECT NUMBER:
SHEET NAME:
NOTE: DO NOT SCALE DRAWING FOR CONSTRUCTION.
MI ARCHITECTURE
FIRM LICENSE # NLP000605
E F
D
CB
A
KEY PLAN
BID PACK 2
www.colliersengineering.com Copyright © 2024. Colliers Engineering & Design All Rights Reserved. This drawing and all the information contained herein is authorized for use only by the party for whom the services were contracted or to whom it is certified. This drawing may not be copied, reused, disclosed, distributed or relied upon for any other purpose without the express written consent of Colliers Engineering & Design.
GARDNER ELEMENTARY
FOOD SERVICE - EQUIPMENT
REPLACEMENT &
RENOVATION SO-1852
REV DATE DESCRIPTION
3 04/03/26 BID PACK 2 - ADDENDUM 1
L. WOOD
C. LADEWIG
C. LADEWIG
P :\2
6\
LS
D
G ar dn er
C af et er ia \W or ki ng D ra w in gs
\2
E 2.
dw g, /3
/2
9:
:2
A
M , m de lo ra
LANSING SCHOOL DISTRICT
2026 SUMMER PROJECTS
KITCHEN REMODEL PROJECTS
BID PACKAGE #2
CM CLARIFICATION #1
CM CLARIFICIATION #1
1. Attwood Elementary:
A. The Tectum Panels will be an accent color and they should be painted before they are installed.
B. The exposed ceiling will be painted with SW Flat Ceiling Paint.
C. The Paint Specification is on Sheet A141.
2. Ebersole Center:
A. Painting notes are on Sheet A101.
B. Wood trim will be painted with SW Semi-Gloss, Color to match existing trim.
C. Walls and ceilings will be painted with SW Eggshell, Color to match existing.
D. The painter will not be required to provide plywood floor protection for Tectum Ceiling touch up paint.
3. Dwight Rich:
A. Paint Specification is on Sheet A101.
4. Gardner Elementary:
A. Paint Specification is on Sheet A141.
B. Any areas where masonry infill is noted will need to be primed and painted, P-1.
C. Masonry infill is located at Passage D122, Passage D124, New Cooler 130B, Dishwash Area A134 and any other location that note new masonry walls.
D. Several HM door frames require paint as noted on Sheet A141. All new doors will be factory finished.
KITCHEN REMODEL PROJECTS
BID PACKAGE #2
CM CLARIFICATION #2
CM CLARIFICIATION #2
1. General note for Attwood Elementary:
Resinous Flooring is removed from the Painting Division ‘D’ and moved to Bid Division ‘C’ Flooring.
The flooring bidders must include an allowance of $5,000.00 for nonstandard prep work.
There will be substantial prep work involved with the Attwood floor project and the flooring contractor will be expected to track the floor prep hours and collect signed T&M slips from the CM Superintendent. When the project is finished the flooring contractor must submit the slips to be billed against the allowance and a change order will be issued to cover the transaction.
2. If painters want to bid on the resinous floor work they should include voluntary alternates on the bid form for the resinous flooring at Attwood and Gardner.
KITCHEN REMODEL PROJECTS
BID PACKAGE #2
CM CLARIFICATION #3
CM CLARIFICIATION #3
1. The current Bid Division E – Mechanical has been divided into two separate divisions. Bid Division E will be “Plumbing” and Bid Division “G” will be HVAC.
2. Bid Division E – Plumbing will include:
Section 024119 Selective Demo 078400 Firestopping 220000 Plumbing
Gardner Phase 1 includes Kitchen Area only to be completed Summer of 2026.
Gardner Phase 2 will proceed in Summer 2027.
All Plumbing demolition detailed on the drawings is included in this contract.
The day these projects start the plumbing contractor must be on site to disconnect kitchen equipment so the food service contractor can remove it.
This division includes labor, material, and equipment to furnish and install all plumbing including all domestic water systems, pipes, pumps, heads, sanitary soil waste and vent systems, storm drain systems, Grease trap and vent system, plumbing fixtures and equipment, traps and supports, insulation for plumbing systems and fixture installation, pipe and valve identification for a complete and operating system as shown and/or specified.
This division includes supply and installation of all gas piping and regulators, supply and installation of stainless-steel sinks in prefabricated casework, water heaters, condensate drains and fireproof sealants where plumbing work penetrates fire rated walls and ceilings.
The plumbing plans detail several new sanitary lines that must be connected to existing UG sanitary piping.
In areas that require cutting, removal and replacement of concrete floors, the General Trades Contractor will remove and replace the concrete. The Plumbing Contractor must perform all required excavation, backfill, compaction and removal of excess dirt.
The drawings detail several new water pipes to connect to new equipment and fixtures and this piping is included in the Plumbing division.
This division includes the following prep work for the Food Service Equipment Contractor.
All required rough-ins and piping with stop valves, elbows, nipples, couplers, traps, waste vents, gas regulators for water, steam, gas, etc. and will also make final connections to the equipment. The plumber will also install all equipment accessories furnished by the FSEC. The plumber will provide the required water heater and piping unless noted otherwise and plumbing, mechanical and electrical subs shall disconnect and reconnect relocated equipment if applicable.
This division includes all required permits and fees as required by state code. Housekeeping and cleanup on a daily basis is included in this division.
KITCHEN REMODEL PROJECTS
BID PACKAGE #2
CM CLARIFICATION #3
This division includes as built drawings, operation and maintenance manuals, owner training and specified attic stock material.
Gardner Phase 1 includes all work in Kitchen Area including Rooms 130A, 134, 136 and 137.
Gardner Phase 2 includes the balance of the Plumbing work including Rooms 131, 132, 129, 133, 121 and
125.
3. Bid Division G – HVAC will include:
Section 024119 Selective Demo 078400 Firestopping
230000 HVAC
Gardner Elementary is the only school that includes HVAC work.
Gardner Phase 1 includes Kitchen Area only to be completed Summer of 2026.
Gardner Phase 2 will proceed in Summer 2027.
Any roof patching must be scheduled with the roofing company that holds the warranties for these projects.
If roof curbs are required, they must be provided with the roof top equipment. Placement of roof top equipment must be approved by the CM. If additional steel is required, the CM will arrange for supply and erection of the steel.
This division includes labor, material and equipment to make the specified revisions to the HVAC system as detailed in the contract documents. The majority of the HVAC work involves revisions to the existing ductwork, grilles, diffusers and dampers, but if the documents specify new equipment such as pumps, stacks, flues, unit heaters, air handling units, unit vents, exhaust fans or furnaces, this contractor must provide and install all of the specified equipment.
Any required connections or adjustments to the ATC / BMS system are included in this contract. All engineering, installation, calibration, software programming and start-up of the ATC / BMS system are included in this contract.
Any specified testing and balance for the HVAC systems is included in this division.
This division includes all required permits and fees as required by state code. Housekeeping and cleanup on a daily basis is included in this division.
This division includes as built drawings, operation and maintenance manuals, owner training and specified attic stock material.
Gardner Phase 1 includes all work in Kitchen Area including Rooms 130A, 134, 136 and 137.
Gardner Phase 2 includes the balance of the HVAC work including Rooms 131, 132, 129, 133, 121 and
125.