Attachment F- Workstation Power and Data Requirements and Application.pdf
PDF 365 KB Posted
- Attached to
- DOS-OVERSEAS SYSTEMS FURNITURE
- Solicitation number
- 19AQMM24Q0123
About this file
This document is a Request for Quotation (RFQ) for a Blanket Purchase Agreement (BPA) to provide systems furniture for the U.S. Department of State's diplomatic facilities worldwide. The Department of State is seeking high-quality, low-maintenance systems furniture that can adapt to evolving facility requirements. The RFQ covers both panel-based and freestanding furniture systems, with requirements for integrated power, telecommunications, storage, and ergonomic features. The BPA has a one-year base period with four one-year option periods, with a maximum ceiling of $100 million. Responses are due by August 19, 2024, and the Department will award the BPA against an existing GSA schedule. Offerors must provide details on products, drawings, wiring diagrams, industry certifications, and past performance with overseas 220V/50Hz furniture installations. The RFQ also has requirements for designated local furniture dealers with security clearances and past project experience.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment A-Past Performance Survey.docx | DOCX document | |
| 19AQMM24Q0123 P00001.pdf | ||
| Attachment D - Systems Furniture Evaluation Technical Factors.docx | DOCX document | |
| Q and A Questions and Answers RFQ-08-05-2024.pdf | ||
| 8-05-Systems Furniture SOW Final.docx | DOCX document | |
| 2024 OBO_FIRE_CODE.pdf | ||
| 19AQMM24Q0123 (2).pdf | ||
| Attachment A-Past Performance Survey.docx | DOCX document | |
| Attachment D - Systems Furniture Evaluation Technical Factors.docx | DOCX document | |
| Systems Furniture SOW Final.pdf | ||
| Attachment B- OBO FY24 Typicals Systems Furniture.pdf | ||
| Attachment C - Offeror Cost Estimate System Furniture.docx | DOCX document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Davis Brody Bond / Spacesmith LLP © 201812
POWER REQUIREMENTS
• The receptacle configuration shall utilize host country voltages (all receptacles UL listed).
– For 220V/50Hz - NEMA 6-20R receptacles.
– For 120V/60Hz - NEMA 5-20R receptacles.
• The electrified configuration typically uses a
10 wire (4+4+2) OR 8-wire (2+2) four circuit configuration.
• Two circuits used for computers, and two used for lighting and general purpose receptacles.
• Power is factory assembled GFE wiring harness (in-feed or “whip”) to connect the power conductors junction box for each cluster.
• At the junction box, the four furniture circuits shall be wired to at least two separate branch circuits, one each for the computers and accessories.
Knoll September 6, 2007
Morrison, Currents and Reff Raceways
Technical Specifications 2 + 2 Four 20-amp circuits, nondirectional 8-wire configuration: four hots, two neutrals (10 gauge, 35A rated), two grounds.
Power rails and outlet modules: steel with molded polypropylene distribution blocks.
Connectors/jumpers: flexible steel conduit with strain relief.
Outlets: molded polycarbonate, preconfigured duplex on any one of four circuits, indicated as A, B (black), X, Y (black, orange, or black with orange triangle).
Infeed: molded plastic shroud, watertight conduit with 6’ whip, snap-in fit at any outlet position in rail or into outlet module distribution block; or hardwire box in center of panel base raceway.
Typical circuiting, cluster of eight workstations: 8 convenience duplexes on each circuit A, B; four computer duplexes on each circuit X, Y.
3 + 3 Six 20-amp circuits, nondirectional 10-wire configuration: six hots, two neutrals (10 gauge, 35A rated), two grounds.
Power rails and outlet modules: steel with molded polypropylene distribution blocks.
Connectors/jumpers: flexible steel conduit with strain relief.
Outlets: molded polycarbonate, preconfigured duplex on any one of six circuits, indicated as A, B, C (black), X, Y, Z (black, orange, or black with orange triangle).
Infeed: molded plastic shroud, watertight conduit with 6’ whip, snap-in fit at any outlet position in rail or into outlet module distribution block; or hardwire box in center of panel base raceway.
Typical circuiting, cluster of 12 workstations: eight convenience duplexes on each circuit A, B, C; four computer duplexes on each circuit X, Y, Z.
4 . 4 . 2 Four 20-amp circuits, nondirectional 10 wire configuration: four hots, four neutrals (12 gauge), two grounds.
Power rails and outlet modules: steel with molded polypropylene distribution blocks.
Connectors/jumpers: flexible steel conduit with strain relief.
Outlets: molded polycarbonate, preconfigured duplex on any one of four circuits, indicated as 1, 2, 3, 4 (black or black with orange triangle).
Infeed: molded plastic shroud, watertight conduit with 6’ whip, snap-in fit at any outlet position in rail or into outlet module distribution block (Currents); or hardwire box in center of panel base raceway.
Typical circuiting, cluster of eight workstations: 8 convenience duplexes on each circuit 1, 2; four computer duplexes on each circuit 3, 4.
Note: Outlets on circuits with dedicated ground must be specified orange face with black triangle or black face with orange triangle.
Approvals: Morrison, Currents and Reff systems raceways are UL listed, CSA approved and comply with UL 1286 and CSA 203.1 electrical and mechanical safety standards.
Morrison / Currents UL file no. E76704 CSA FIle no. LR62867 Reff UL file no. E76558 CSA FIle no. LR62867
2+2, 3+3 and 4.4.2 components are also listed under UL file no. E30326 and CSA no. LR55923.
Y
X
N2
G2
Black
Red
White/ Black
Green
Tan
Pink
White/ Red
Green/ Yellow
2+2 Wiring Diagram
A
B
N1
G1
A B X Y
Black
Red
Blue
White/ Black
Green
C
G1
G2
Z
Orange
Tan
Pink
White/ Red
Green/ Yellow
3+3 Wiring Diagram
A B C X Y Z
N2
N4
N3
G2
Black
Red
White/ Black
White/ Red
Green
Pink
Blue
White/ Purple
White/ Blue
Green/ Yellow
4.4.2 Wiring Diagram
1 2 3 4
© Knoll, Inc. 2007 knoll.com
Knoll September 6, 2007
Morrison, Currents and Reff Raceways
Technical Specifications 2 + 2 Four 20-amp circuits, nondirectional 8-wire configuration: four hots, two neutrals (10 gauge, 35A rated), two grounds.
Power rails and outlet modules: steel with molded polypropylene distribution blocks.
Connectors/jumpers: flexible steel conduit with strain relief.
Outlets: molded polycarbonate, preconfigured duplex on any one of four circuits, indicated as A, B (black), X, Y (black, orange, or black with orange triangle).
Infeed: molded plastic shroud, watertight conduit with 6’ whip, snap-in fit at any outlet position in rail or into outlet module distribution block; or hardwire box in center of panel base raceway.
Typical circuiting, cluster of eight workstations: 8 convenience duplexes on each circuit A, B; four computer duplexes on each circuit X, Y.
3 + 3 Six 20-amp circuits, nondirectional 10-wire configuration: six hots, two neutrals (10 gauge, 35A rated), two grounds.
Power rails and outlet modules: steel with molded polypropylene distribution blocks.
Connectors/jumpers: flexible steel conduit with strain relief.
Outlets: molded polycarbonate, preconfigured duplex on any one of six circuits, indicated as A, B, C (black), X, Y, Z (black, orange, or black with orange triangle).
Infeed: molded plastic shroud, watertight conduit with 6’ whip, snap-in fit at any outlet position in rail or into outlet module distribution block; or hardwire box in center of panel base raceway.
Typical circuiting, cluster of 12 workstations: eight convenience duplexes on each circuit A, B, C; four computer duplexes on each circuit X, Y, Z.
4 . 4 . 2 Four 20-amp circuits, nondirectional 10 wire configuration: four hots, four neutrals (12 gauge), two grounds.
Power rails and outlet modules: steel with molded polypropylene distribution blocks.
Connectors/jumpers: flexible steel conduit with strain relief.
Outlets: molded polycarbonate, preconfigured duplex on any one of four circuits, indicated as 1, 2, 3, 4 (black or black with orange triangle).
Infeed: molded plastic shroud, watertight conduit with 6’ whip, snap-in fit at any outlet position in rail or into outlet module distribution block (Currents); or hardwire box in center of panel base raceway.
Typical circuiting, cluster of eight workstations: 8 convenience duplexes on each circuit 1, 2; four computer duplexes on each circuit 3, 4.
Note: Outlets on circuits with dedicated ground must be specified orange face with black triangle or black face with orange triangle.
Approvals: Morrison, Currents and Reff systems raceways are UL listed, CSA approved and comply with UL 1286 and CSA 203.1 electrical and mechanical safety standards.
Morrison / Currents UL file no. E76704 CSA FIle no. LR62867 Reff UL file no. E76558 CSA FIle no. LR62867
2+2, 3+3 and 4.4.2 components are also listed under UL file no. E30326 and CSA no. LR55923.
G2
Black
Red
White/ Black
Green
Tan
Pink
White/ Red
Green/ Yellow
2+2 Wiring Diagram
G1
A B X Y
Black
Red
Blue
White/ Black
Green
C
G2
Z
Orange
Tan
Pink
White/ Red
Green/ Yellow
3+3 Wiring Diagram
A B C X Y Z
N2
N4
N3
G2
Black
Red
White/ Black
White/ Red
Green
Pink
Blue
White/ Purple
White/ Blue
Green/ Yellow
4.4.2 Wiring Diagram
1 2 3 4
© Knoll, Inc. 2007 knoll.com
4-4-2 Wiring: Four 20-AMP Circuits
• Non-directional 10 wire configuration:
– Four hots
– Four neutrals (12 gauge)
– Two grounds
• Typical circuiting, cluster of 8 workstations:
– Eight convenience duplexes on each circuit 1, 2
– Four computer duplexes on each circuit 3, 4
2+2 Wiring: Four 20-AMP Circuits
• Non-directional 8 wire configuration:
– Four hots
– Two neutrals (10 gauge, 35A rated)
– Two grounds
• Typical circuiting, cluster of 8 workstations:
– Eight convenience duplexes on each circuit A, B
– Four computer duplexes on each circuit X, Y
WIRING DIAGRAMS FROM HERMAN MILLER
Workstation Power and Data Requirements and Application
IT REQUIREMENTS
• Four CAT X UTP cables at each Non-CAA work area.
• Work area (desk) outlets shall be distributed to provide:
– DoS OpenNet+
– One computer per desk
– One printer at chief of section
– One printer per 5 desks located near files
• One telephone per desk.
• 60% fill ratio, with a maximum of 19 cables per raceway.
• Grommets at openings within panel to protect cables.
OBO Furniture Standards Study / Final Report 3.5.2018 13
G
N 110V
G
N 250V
POWERDATA
WINDOW SIDE CORRIDOR SIDE
CORRIDOR
SIDE
WINDOW
SIDE
ELEVATION A
POWERDATA
WINDOW SIDECORRIDOR SIDE
WINDOW
SIDE
CORRIDOR
SIDE
ELEVATION B
WINDOW
SIDE
CORRIDOR
SIDE
A
B
TYPICAL DAY 2 PLAN
POWERDATA
DATA CABLES,
16 PER
RACEWAY
DESKTOP
BELTLINE
POWER
BASE POWER
Project F 17271
DRAWING
PROJECT
CHK'D BY:
DRAWN BY:
DATE:
SCALE:
DWG. NO.
PROJECT NO:
One New York Plaza, Suite 4200 New York, NY 10004
P:212 620 5583 www.spacesmith.com
ARCHITECTURE PLANNING INTERIOR DESIGN
As indicated
11/15/2017 3:26:36 PM
Unnamed
Author
Checker
11/10/2017
A-06
FLOOR ENTRY
POWERDATA
DATA CABLES,
16 PER
RACEWAY
DESKTOP
BELTLINE
POWER
BASE POWER
Project F 17271
DRAWING
PROJECT
CHK'D BY:
DRAWN BY:
DATE:
SCALE:
DWG. NO.
PROJECT NO:
One New York Plaza, Suite 4200 New York, NY 10004
P:212 620 5583 www.spacesmith.com
ARCHITECTURE PLANNING INTERIOR DESIGN
As indicated
11/15/2017 3:26:36 PM
Unnamed
Author
Checker
11/10/2017
A-06
CEILING ENTRY
POWERDATA
DATA CABLES,
16 PER
RACEWAY
DESKTOP
BELTLINE
POWER
BASE POWER
Project F 17271
DRAWING
PROJECT
CHK'D BY:
DRAWN BY:
DATE:
SCALE:
DWG. NO.
PROJECT NO:
One New York Plaza, Suite 4200 New York, NY 10004
P:212 620 5583 www.spacesmith.com
ARCHITECTURE PLANNING INTERIOR DESIGN
As indicated
11/15/2017 3:26:36 PM
Unnamed
Author
Checker
11/10/2017
A-06
WALL ENTRY
POWER/DATA ENTRY OPTIONS