Site Visit Q and A Part 2 - 15A00023R00000085.docx

DOCX document 22 KB Posted

Attached to
Laboratory Dual In-Line Uninterrupted Power Supply Installation Federal contract opportunity
Solicitation number
15A00023R00000085
Issued by
Department of Justice Bureau of Alcohol Tobacco Firearms and Explosives

About this file

This document provides answers to questions from a site visit regarding Solicitation Number 15A00023R00000085 for the Laboratory Dual In-Line Uninterrupted Power Supply Installation. The lab has no equipment to transport the uninterrupted power supply (UPS) and batteries from the first floor to the fourth floor, so the awardee will be responsible for providing all necessary equipment and personnel. The elevator dimensions are 44 inches wide by 48 x 77 inches inside, with a weight limit of 2,500 pounds. There is a 34-inch wide door from the docking bay to the elevator and through the lab. The floor weight capacity cannot be determined but a previous unit weighing 1,978 pounds was delivered with no issues. Details on available electrical circuits, panel feeds and capacities are provided in the updated Statement of Work. The room for the UPS measures 9 feet by 12 feet. Lithium ion batteries are required. A load survey to verify the 60kVA UPS specification is currently being performed and the solicitation will be extended to allow time for its completion.

View the file

Other files for this federal contract opportunity

Other files attached to Laboratory Dual In-Line Uninterrupted Power Supply Installation, newest first.
File Type Posted
ATF Load Study.pdf PDF
Attachment 1 - Statement of Work Update 2.docx DOCX document
Site Visit Q and A Part 1 - 15A00023R00000085.docx DOCX document
Attachment 1 - Statement of Work Update 1.docx DOCX document
FSL-A Chemistry Instrument Power Breakout.xlsx XLSX spreadsheet
Questions and Answers 1 - 15A00023R00000085.docx DOCX document
Site Visit Instructions - 15A00023R00000085.docx DOCX document
15A00023R00000085 - CO Signed.pdf PDF
Attachment 1 - Statement of Work.docx DOCX document
Attachment 2 - Quotation Instructions.docx DOCX document
Attachment 3 - Evaluation Criteria.docx DOCX document
Attachment 4 - Past Performance Survey.docx DOCX document
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

15A00023R00000085 Site Visit Questions and Answers Part 2

· Regarding equipment handling equipment onsite:

· What is onsite (pallet jack, roll-o-lift, or other, and weight capacity?

· Whether said equipment can be operated by either the winning bidder or building/lab staff to move the UPS and Batts to the 4th floor?

· The lab has no equipment to get the items from the 1st floor to the 4th floor. The awardee will be responsible for providing the equipment and personnel.

· Elevator:

· Dimensions and weight limit?

· Doorway 44 ½ inch wide

· Inside 48 x 77 inch

· Weight limit: 2,500 lbs.

· There is a door to go through from docking bay to elevator and through lab that is 34 inches wide after removal of the doors (to be done by ATF)

· Raised floor:

· Weight bearing capacity?

· Floor weight cannot be determined, however, in the past the laboratory had an instrument delivered that weighed approximately 1,978 lbs with a floor capacity of approximately 225.3lbs/ft2. There were no floor issues bringing the unit through the halls, or elevator.

· Existing electrical circuits to be repurposed:

· Details on number of available circuits, panel feeds and capacity?

· See updated Section 4.7 in the Statement of Work.

· Room size for UPS?

· 9 feet x 12 feet usable space

· Battery Type needed?

· Lithium Ion.

· Is there a load survey to verify the 60kVA is correct unit?

· No. Load survey currently being performed. Solicitation will be extended to provide time for this to be completed.