FSL-A Chemistry Instrument Power Breakout.xlsx

XLSX spreadsheet 15 KB Posted

Attached to
Laboratory Dual In-Line Uninterrupted Power Supply Installation
Solicitation number
15A00023R00000085
Issued by

About this file

This spreadsheet details power requirements for various laboratories and instruments within the Fire Debris Lab, XRD Lab, Explosives Lab, Explosives Lab 2, Trace Lab, and related uninterrupted power supply needs. Locations, instruments, voltage and amperage needs, circuit breakers, existing uninterruptible power supplies, and required upgrades are specified. A related federal contract opportunity from the Department of Justice Bureau of Alcohol Tobacco Firearms and Explosives seeks offers for laboratory dual in-line uninterruptible power supply installation to address the needs documented in the spreadsheet, with response due by the listed solicitation number and closing date. Relevant details include federal agency, required products and services, and incumbent equipment to be disposed of or upgraded.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

LocationRoomNameVoltsAmpsVAHzCircuitBreakersUPS?/comments
Fire Debris Lab460FD1GC120225047.5-63LD49/11Toshiba 6KVA-to be disposed
need two quad boxesMS120110060
run one new circuit to LD panel ~40 feet
2 ovens verify the power pole is on LD panel
Fire Debris Lab460FD4GC220295047.5-63LD510/12none
need two quad boxesMS120110060LD145none
run one new circuit to LD ~40 feethas a 220 already
Fire Debris Lab460FD5GC120225047.5-63LD42/4Toshiba 6KVA-to be disposed
need to desginate a 220 outlet (has power)MS220110050-60
has a 220 already
Fire Debris Lab460FD6GC120225047.5-63LD278none
need two quad boxes (has power)MS120110060??none
Fire Debris Lab460FD7GC120235050-60LD269Eaton 2KVA
need two quad boxes (has power)MS120110060LD147Eaton 1.5KVA
Fire Debris Lab460ISQGC120200050-60LD45/7Toshiba 6KVA-to be disposed
need one quad box (has power)MS1201550-60
XRD Lab456PanyliticalXRD2303860LD244none
has all outletsHaskirsChiller2081560LD243none
Explosives Lab454FTIR12010LD271Eaton 3KVA
need one quad box (has power)
Explosives Lab454HPLCDAD12025550-60LD270Eaton 3KVA
need one quad box (has power)Sampler12055050-60
Pump12025550-60
Column12033050-60
Explosives Lab2450ICSampler120450-60LD41/3Toshiba 8KVA-to be disposed
need one quad box (has power)DC1201050-60
EG1202
Pump120250-60
PeakGenerator1201260
ISQECMS1201550-60?Eaton 2KVA
Explosives Lab2450HPLCDAD12015050-60LD276/77Powervar (new)
need three 220 outlets (has power)Sampler12055050-60
need one quad box (has power)Pump12055050-60
Column12033050-60
TSQMS2301050-60
PeakGenerator230750-60
SogevacPump2301250-60
441BrukerXRD230???LD539/41Integrity (new)
has all outlets
Trace Lab418EDAXXRF12013L159Eaton 2KVA
need one quad box (has power)
run one new circuit to LD panel ~30 feet
Trace Lab418FTIRBench1201050-60LD54Eaton 3KVA
need one quad box (has power)Scope120350-60
Trace Lab418PyroGCGC120235050-60L155none
Need one quad box (has power)MS120110060LD530
Pyrolysis12010LD530
four extraToshiba 6KVA-to be disposed