ATF Load Study.pdf
PDF 706 KB Posted
- Attached to
- Laboratory Dual In-Line Uninterrupted Power Supply Installation Federal contract opportunity
- Solicitation number
- 15A00023R00000085
About this file
This report summarizes the results of a load metering study conducted on Panel LD1. The study found that Phase A averaged 56.11 amps, Phase B averaged 45.23 amps, and Phase C averaged 49.90 amps over seven days. The panel averaged 17.48 KW of power usage and peaked at 27.18 KW.
The related federal contract opportunity is a solicitation from the Department of Justice Bureau of Alcohol Tobacco Firearms and Explosives seeking offers for the installation of laboratory dual in-line uninterrupted power supplies. The solicitation number is 15A00023R00000085. The report and solicitation appear to be related to an upcoming project to install backup power equipment in ATF laboratories.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site Visit Q and A Part 2 - 15A00023R00000085.docx | DOCX document | |
| Attachment 1 - Statement of Work Update 2.docx | DOCX document | |
| FSL-A Chemistry Instrument Power Breakout.xlsx | XLSX spreadsheet | |
| Site Visit Q and A Part 1 - 15A00023R00000085.docx | DOCX document | |
| Attachment 1 - Statement of Work Update 1.docx | DOCX document | |
| Questions and Answers 1 - 15A00023R00000085.docx | DOCX document | |
| Site Visit Instructions - 15A00023R00000085.docx | DOCX document | |
| 15A00023R00000085 - CO Signed.pdf | ||
| Attachment 1 - Statement of Work.docx | DOCX document | |
| Attachment 2 - Quotation Instructions.docx | DOCX document | |
| Attachment 3 - Evaluation Criteria.docx | DOCX document | |
| Attachment 4 - Past Performance Survey.docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
This report presents a summary of the results for the load metering done on Panel LD‐1. The meter was set up on the input of Panel LD‐1 to moniter load usage for 7 days. Phase A averaged 56.11 amps, Phase B averaged 45.23 amps, and Phase C averaged 49.90 amps. The Panel averaged 17.48 KW and peaked at a max of 27.18 KW.
Event #1 at 08/25/2023 10:00:29.000 AIrms Current Journal Trigger Normal To High
Timeplot
Min Max Avg A-BVrms 188.8 211.2 207.5 B-CVrms 188.9 212.5 208.5 C-AVrms 162.4 210.9 207.0 AIrms 38.20 172.8 56.11 BIrms 30.91 92.73 45.23 CIrms 32.49 130.8 49.90
V ol ts
A-B Vrms
V ol ts
B-C Vrms
V ol ts
C-A Vrms
A m ps
A Irms
A m ps
B Irms
A m ps
C Irms
10:00 08/25/2023
Friday
10:00 08/26/2023 Saturday
10:00 08/27/2023
Sunday
10:00 08/28/2023
Monday
10:00 08/29/2023
Tuesday
10:00 08/30/2023 Wednesday
10:00 08/31/2023
Thursday
10:00 09/01/2023
Friday
Timeplot
Min Max Avg TOTP(kW) 14.38 27.18 17.48
15.0
17.5
20.0
22.5
25.0
27.5 kW
TOT P(kW)
10:00 08/25/2023
Friday
10:00 08/26/2023 Saturday
10:00 08/27/2023
Sunday
10:00 08/28/2023
Monday
10:00 08/29/2023
Tuesday
10:00 08/30/2023 Wednesday
10:00 08/31/2023
Thursday
10:00
Timeplot
Min Max Avg AVrms 102.8 122.0 119.9 AIrms 38.20 172.8 56.11
10:00 08/25/2023
Friday
10:00 08/26/2023 Saturday
10:00 08/27/2023
Sunday
10:00 08/28/2023
Monday
10:00 08/29/2023
Tuesday
V ol ts
A Vrms
A m ps
A Irms
10:00 08/30/2023 Wednesday
10:00 08/31/2023
Thursday
10:00
Timeplot
Min Max Avg BVrms 111.3 122.2 119.9 BIrms 30.91 92.73 45.23
V ol ts
B Vrms
A m ps
B Irms
10:00 08/25/2023
Friday
10:00 08/26/2023 Saturday
10:00 08/27/2023
Sunday
10:00 08/28/2023
Monday
10:00 08/29/2023
Tuesday
10:00 08/30/2023 Wednesday
10:00 08/31/2023
Thursday
10:00
Timeplot
Min Max Avg CVrms 97.49 122.2 119.9 CIrms 32.49 130.8 49.90
V ol ts
C Vrms
A m ps
C Irms
10:00 08/25/2023
Friday
10:00 08/26/2023 Saturday
10:00 08/27/2023
Sunday
10:00 08/28/2023
Monday
10:00 08/29/2023
Tuesday
10:00 08/30/2023 Wednesday
10:00 08/31/2023
Thursday
10:00
| ATF_Load Study_082523 |
| ATF2_00 |
| 0 Phase to Phase |
| 5 Active Power |
| ATF_Load Study_082523 |
| 1 Phase A |
| 2 Phase B |
| 3 Phase C |
File details come from the government source that posted it. Updated .