Site Visit Q and A Part 1 - 15A00023R00000085.docx
DOCX document 18 KB Posted
- Attached to
- Laboratory Dual In-Line Uninterrupted Power Supply Installation Federal contract opportunity
- Solicitation number
- 15A00023R00000085
About this file
This document contains questions and answers regarding a site visit for solicitation number 15A00023R00000085 for a Laboratory Dual In-Line Uninterrupted Power Supply Installation for the Department of Justice Bureau of Alcohol Tobacco Firearms and Explosives. Key details include that the winning bidder will be responsible for providing all equipment and personnel to transport the uninterrupted power supply and batteries from the first floor to the fourth floor, as the laboratory has no means to do so. Dimensions for the elevator, doorway, and raised floor space are provided. The number of available electrical circuits and panel capacity will be detailed in an updated Statement of Work. A room measuring 9 feet by 12 feet is the usable space for the uninterrupted power supply. A load survey is currently being conducted to determine the appropriate battery type and verify that the 60kVA uninterrupted power supply unit meets requirements. The solicitation period will be extended to accommodate the completion of the load survey.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| ATF Load Study.pdf | ||
| Site Visit Q and A Part 2 - 15A00023R00000085.docx | DOCX document | |
| Attachment 1 - Statement of Work Update 2.docx | DOCX document | |
| Attachment 1 - Statement of Work Update 1.docx | DOCX document | |
| FSL-A Chemistry Instrument Power Breakout.xlsx | XLSX spreadsheet | |
| Questions and Answers 1 - 15A00023R00000085.docx | DOCX document | |
| Site Visit Instructions - 15A00023R00000085.docx | DOCX document | |
| Attachment 4 - Past Performance Survey.docx | DOCX document | |
| 15A00023R00000085 - CO Signed.pdf | ||
| Attachment 1 - Statement of Work.docx | DOCX document | |
| Attachment 2 - Quotation Instructions.docx | DOCX document | |
| Attachment 3 - Evaluation Criteria.docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
15A00023R00000085 Site Visit Questions and Answers Part 1
· Regarding equipment handling equipment onsite:
· What is onsite (pallet jack, roll-o-lift, or other, and weight capacity?
· Whether said equipment can be operated by either the winning bidder or building/lab staff to move the UPS and Batts to the 4th floor?
· The lab has no equipment to get the items from the 1st floor to the 4th floor. The awardee will be responsible for providing the equipment and personnel.
· Elevator:
· Dimensions and weight limit?
· Doorway 44 ½ inch wide
· Inside 48 x 77 inch
· Weight limit TBD
· There is a door to go through from docking bay to elevator and through lab that is 34 inches wide after removal of the doors (to be done by ATF)
· Raised floor:
· Weight bearing capacity?
· TBD
· Existing electrical circuits to be repurposed:
· Details on number of available circuits, panel feeds and capacity?
· See updated Section 4.7 in the Statement of Work.
· Room size for UPS?
· 9 feet x 12 feet usable space
· Battery Type needed?
· To be determined after load survey.
· Is there a load survey to verify the 60kVA is correct unit?
· No. Load survey currently being performed. Solicitation will be extended to provide time for this to be completed.
File details come from the government source that posted it. Updated .